© 2002 eaton corporation. all rights reserved. cabling a rackmounted 9910-p33 ups i5 or p5 with one...
TRANSCRIPT
![Page 1: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/1.jpg)
© 2002 Eaton Corporation. All rights reserved.
Cabling a Rackmounted9910-P33 UPS
i5 or p5 with one PDU or two (redundant) PDUs
How to Connect the Power and Interface (Communication) Cables
World Trade (WT)
![Page 2: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/2.jpg)
2
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Receiving the Rack
UPS will be installed in rack If selected “Rack Install” features in the configurator
Connections that need to be completed Power
• UPS to utility (mains)
• UPS to PDU / Devices
Interface (communications)• UPS to server(s)
![Page 3: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/3.jpg)
3
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Getting Acquainted with the P33
Location of UPS• Installed at bottom of rack
• Connections make @ rear of rack
What a P33 UPS looks like from the rear
![Page 4: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/4.jpg)
4
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Line cords & connectors
C13 connector- 10A rated (female)Rack, HD & E PDU outletsMating connector to server used onP33 and PDU Outlets
C14 connector- 10A rated (male)The inlet on most servers & optionsRack jumper cords
C19 connector- 16A rated (female)P33 Outlet
C20 connector- 16A rated (male)P33 inlet and Part of BladeCenter line
cord
Lower number is female. Power flows from female to male.
![Page 5: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/5.jpg)
5
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
PDU line cord #6656
UPS outputline cord PN
53P1968(1/2 of #9855)
Customersupplied
receptaclevaries
PDU #7188 or#9188
Power Cabling with one PDU & #9855 to 16A Plug
520 or 550 withRedundant Powersupplies #5158 or #7889 being fed
by non-redundantpower source
Server power cablesto one PDU - non- redundant
UPS inputline cord PN
varies
This example showsa server with redundantpower supplies beingpowered by one PDU.Therefore, this installationis classified as non- redundant
POWER CORD TABLEFC Description9866 CEE7 VII Type 189867 SABS 164 Type 229868 CEI 23-16 Type 259871 IEC309 P+N+G 16A Type 469872 SII 32-1971 Type 329874 SAA-AS 3112 Type 549875 IEC 60083-A5 Type 64
![Page 6: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/6.jpg)
6
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
PDU line cord #6656
UPS outputline cord PN
53P1968(1/2 of #9855)
PDU line cord #1449
PN 21H7693
Customersupplied
receptacleIEC309
P+N+G 32A
PDU #7188 or#9188
Power Cabling with one PDU & #9855 to 32A Plug
520 or 550 withRedundant Powersupplies #5158 or #7889 being fed
by non-redundantpower source
Server power cablesto one PDU - non- redundant
UPS inputline cord PN
53P1969(1/2 of #9855)
This example showsa server with redundantpower supplies beingpowered by one PDU.Therefore, this installationis classified as non- redundant
![Page 7: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/7.jpg)
7
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
PDU line cord #6656
UPS outputline cord
PN 53P1968(1/2 of #9855)
PDU line cord #1449
PN 21H7693
Customersupplied
receptacleIEC309
P+N+G 32A
PDU #7188 or#9188
Power Cabling with two PDUs
520 or 550 withRedundant Power
supplies #5158 or #7889 being fed by redundant
power sourceUPS inputline cord
PN 53P1969RedundantPDU line
cord #6656
Customersupplied
receptacleIEC309
P+N+G 32A
2nd or redundant PDU
Server power cablesto two redundant PDUs
UPS input line cordshown using 30/32Aplugs as an exampleonly.
![Page 8: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/8.jpg)
8
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Interface Cabling i5 to P33
520 or 550UPS port
P1-T1
Install i5 UPS Interface
Cable #1827(included with i5)
Install X-Slot Relay Card
#2936
Install UPS to #1827Interface CablePN 05142494
(included with #2936)Follow Relay Card Quick Start Guide directions to set UPS
monitoring functions in i5 OS
![Page 9: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/9.jpg)
9
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Interface Cabling iSeries to P33
8xx Series UPS port
“J14” or ”UPS”
Install X-Slot Relay Card
#2936
Install UPS Interface CablePN 05142494
(included with #2936)
Follow Relay Card Quick Start Guide directions to set UPS
monitoring functions in OS/400 OS
![Page 10: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/10.jpg)
10
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Interface Cabling i5 & serial to P33
520, 550 or 570UPS port
P1-T1
Install i5 UPS Interface
Cable #1827(included with
i5)
Install X-Slot Relay / SerialCard #2939
Install UPS to #1827
Interface CablePN 124902074-030
(included with #2939) Follow Relay / Serial Card Quick
Start Guide directions to set UPS monitoring functions in i5 OS and
serial (TTY) server.
Serial (TTY)server
Install UPS to serial Interface
Cable PN 124102022-
003(with #2939)
Install LanSafe Software (contained on CD)
onto server
![Page 11: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/11.jpg)
11
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Interface - p5 Options
Serial (Non-LPAR) One to three serial
connections possible
LPAR (Logical PARtitions of the p5 Operating System)
Requires a p5 Ethernet connection
Must use #2934 Web/SNMP card
![Page 12: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/12.jpg)
12
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Interface (Serial) p5
p5 520 or 550 NOTE: Must have 2-port Asynchronous
EIA - 232 PCI Adapter #5723
Install UPS serial Interface CablePN 124102022-002
(contained in P33 AccessoryKit PN 21P7229)
Follow Multi-ServerUser’s Guide to set
UPS monitoring functions
NOTE: Obtain 5200-05 Maintenancepackage (APAR IY66260) for AIX 5.2L V5.2
and the 5300-01 maint. Pkg. For AIX 5.3L V5.3(APAR IY62267) from IBM
Multi-Serial Card shown.Your P33 may have asingle serial port card.
Install LanSafe Software (contained on CD)
onto p5
![Page 13: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/13.jpg)
13
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Interface for LPARs (Ethernet) p5
p5 520 or 550 NOTE: Must have Ethernet Port
Follow ConnectUPSWeb/SMMP User’s Guide
to set UPS monitoring functions
Install ConnectUPS Web/SNMP Card
#2934
Install EthernetCable - customer
supplied
Install NetWatch Software (contained on CD)onto each LPAR
![Page 14: © 2002 Eaton Corporation. All rights reserved. Cabling a Rackmounted 9910-P33 UPS i5 or p5 with one PDU or two (redundant) PDUs How to Connect the Power](https://reader035.vdocument.in/reader035/viewer/2022062718/56649e9e5503460f94ba0689/html5/thumbnails/14.jpg)
14
i5 & p5 Training WT
Cabling a Rackmounted P33 UPS - WT - rev 4 - Barry Gruetzmacher – April 2005
Completing Start-Up
You have finished the power and connectivity installation process
Continue with Start-up instructions in User’s Manuals
Questions? Contact: The local IBM office supporting your account Eaton Power Quality Global Services