e0internet.savannah.chatham.k12.ga.us/district/finance... · 2017-05-30 · facp fscu vs wf faa dh...

4
FACP FSCU VS WF FAA DH 2 E4.2 F FIRE ALARM PULL STATION. WALL MOUNTED 46" ABOVE FLOOR. FIRE ALARM SIGNAL, SPEAKER AND FLASHING LIGHT, 6'-8" AFF. FIRE ALARM STROBE LIGHT, 6'-8" IN. MOUNTING HEIGHT. FIRE ALARM CONNECTION, HOOD EXTINGUISHING SYSTEM, SEE MECHANICAL DRAWINGS FOR LOCATION. INTERLOCK WITH SHUNT TRIP BREAKERS FOR EQUIPMENT UNDER HOOD. FIRE ALARM REMOTE LCD ANNUNCIATOR PANEL. FLUSH RECESSED WALL MOUNTED. FIRE ALARM DOOR HOLDER, WALL MOUNTED, CONSULT ARCHITECTURAL DRAWINGS TO DETERMINE TYPE REQUIRED. PROVIDE POWER FROM NEAREST RECEPTACLE CIRCUIT AND CONNECT TO FIRE ALARM SYSTEM. TAMPER SWITCH, FURNISHED AND INSTALLED WITH SPRINKLER SYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL. FLOW SWITCH, FURNISHED AND INSTALLED WITH SPRINKLER SYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL. FIRE ALARM SMOKE DETECTOR, CEILING MOUNTED. FIRE ALARM DUCT SMOKE DETECTOR LOCATED IN HVAC DUCT. FIRE ALARM CONTROL PANEL, SURFACE WALL MOUNTED. FIRE ALARM SIGNAL, HORN. 6 FT.-8 IN. MOUNTING HEIGHT. FIRE ALARM HEAT DETECTOR, 135 DEG, OPERATION. P WEATHER PROOF. FIRE ALARM STROBE LIGHT, CEILING MOUNTED. S M FIRE ALARM: H S WP IC AD AC S 2. COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROL REQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER. INTRUSION DETECTION SYSTEM: CONDUIT SLEEVE: NUMBER & SIZE, (2)-2" FOR ALL CLASSROOMS, (1)-2" FOR ALL OFFICES, UNO CABLE TRAY: SIZE AS INDICATED, 18"W x 4"H TYP. INTERCOM SPEAKER: WEATHERPROOF WALL MOUNTED AT 96"AFF. MICROPHONE JACK: WALL MOUNTED AT 18" AFF, UNO. EMERGENCY CALL PUSH BUTTON: WALL MOUNTED 46" AFF ADMINISTRATIVE DISPLAY PHONE: WALL MOUNT AT 46" AFF INTRUSION SYSTEM: KEY-PAD, MOUNT 48"AFF SECURITY ACCESS: MOUNT ABOVE CEILING AT ENTRY WAY INTRUSION DETECTION DEVICE: WALL MTD. ACCESS CONTROL SYSTEMS SEE DETAIL 2/T2.1 FOR POWER, POWER DISCONNECT, LOW VOLTAGE CABLING, BOXES AND CONDUIT REQUIREMENTS. REFER TO ARCHITECTURAL PLANS AND DOOR SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS. INTERCOM SPEAKER: 2' X 2' SQUARE CEILING MOUNTED COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROL REQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER. SPEAKER SYSTEM: CABLING COMPONENTS: THE CONTRACTOR SHALL PROVIDE ROUGH-IN FOR ALL DEVICES AND WIRING. ROUGH-IN REQUIREMENTS ARE SPECIFIED IN SECTION 261010. VERIFY ADJACENCY TO CORRESPONDING POWER RECEPTACLES. OTHER DEVICES WHOSE LOCATIONS ARE NOT DEPENDENT ON RECEPTACLE PLACEMENT SHALL BE COORDINATED WITH SYSTEM INSTALLER. WALL MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING MTD. TELECOMMUNICATION JUNCTION BOX WALL MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CEILING MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING ROUGH-IN FOR LOW VOLTAGE SYSTEMS: SA K P J J O S O S OS W HD C PC XX-1 T M ABBREVIATIONS: LEGEND: LIGHTING FIXTURES: UPPERCASE LETTER ADJACENT TO FIXTURE DENOTES DESIGNATION PER THE LIGHTING FIXTURE SCHEDULE. LOWERCASE LETTER DENOTES SWITCHLEG. THE RESPECTIVE SWITCH WILL HAVE THE SAME DESTINATIONS. NUMERAL DENOTES BRANCH CIRCUIT CONNECTION. FIXTURE TYPE ENDING WITH 'D' SUFFIX INDICATES FIXTURE THAT REQUIRES DIMMING BALLAST. (EXAMPLE: FIXTURE TYP 'A3D') REFER TO THE FIXTURE SCHEDULE FOR THE SPECIFIC FIXTURE INFORMATION. EMERGENCY FIXTURES SHALL HAVE FACTORY INSTALLED INTERNAL BATTERIES, PER SPECIFICATIONS. NL SUFFIX ADJACENT TO FIXTURE TYPE DENOTES NIGHT LIGHT. DO NOT SWITCH THESE FIXTURES. NON- EMERGENCY EMERGENCY/ BATTERY BACKUP LIGHTING FIXTURE: LINEAR FLUORESCENT ELECTRICAL EQUIPMENT: REFER TO ONE-LINE DIAGRAM AND EQUIPMENT CONNECTION SCHEDULE FOR LOAD DATA USED AS THE BASIS OF DESIGN AND REQUIRED CONNECTIONS. VERIFY LOAD AND LOCATION WITH EQUIPMENT CUT-SHEETS AND INSTALLER. GENERAL NOTES: DEVICE IDENTIFIER TAGS: NUMERAL ADJACENT TO DEVICE DENOTES BRANCH CIRCUIT CONNECTION. IDENTIFIER TAGS ADJACENT TO DEVICES INDICATE: WIRING DEVICES: RECEPTACLES: NOMINAL MOUNTING HEIGHT OF RECEPTACLES SHALL BE 18" TO CENTER, UNO. IF APPLICABLE, ADJUST SO DEVICE COVER IS IN THE CENTER OF MASONRY COURSE NEAREST THAT HEIGHT. THE HEIGHT ESTABLISHED SHALL GOVERN FOR ALL BOX INSTALLATIONS, WHERE INSTALLED IN MASONRY OR FRAMED WALLS. SWITCHES: MOUNTING HEIGHT OF SWITCHES SHALL BE 46" NOMINAL, ADJUSTED IN THE SAME MANNER AS SPECIFIED ABOVE, FOR RECEPTACLES. LOWERCASE LETTER INDICATES SWITCHLEG CONNECTION. THE RESPECTIVE FIXTURE(S) WILL HAVE THE SAME DESIGNATION. BRANCH CIRCUITS: CONDUCTOR COUNTS ARE SHOWN ON THE HOMERUNS ONLY. CONTRACTOR SHALL DETERMINE COUNTS FOR INTERMEDIATE RUNS BASED ON THE MANNER IN WHICH THE CIRCUIT ELEMENTS ARE CONNECTED. REFER TO THE SPECIFICATION SECTIONS 262010, 262080, & 26030 FOR SPECIAL REQUIREMENTS. LA-1,3,5 MISCELLANEOUS COMPONENTS: 3 4 V K O LIGHTING FIXTURE: LINEAR FLUORESCENT LIGHTING FIXTURE: LINEAR FLUORESCENT LIGHTING FIXTURE: FLUORESCENT STRIP LIGHTING FIXTURE: FLUORESCENT, WALL MTD. DOWNLIGHT/SCONCE FIXTURE EXIT AREA OF REFUGE LIGHT: UNIVERSAL MTD. DIRECTIONAL FIXTURES: EMERGENCY TYPE LIGHT TRACK: LENGTH AS SHOWN MOUNT ABOVE COUNTERTOP OR BACKSPLASH, 9" ABOVE WORK SURFACE TO CENTER MOUNT DEVICE AT HEIGHT INDICATED PROVIDE WEATHER-PROOF COVER RECEPTACLE: SIMPLEX RECEPTACLE: DUPLEX, TAMPER RESISTANT TYPE. RECEPTACLE: GROUND-FAULT-INTERRUPTING TYPE, TAMPER RESISTANT TYPE. IN-SLAB FLOOR BOX: SEE SPECIFICATIONS RECEPTACLE: DRYER, 30 AMP, 120/250 VOLT RECEPTACLE: SPECIAL PURPOSE , COORDINATE NEMA RATING WITH SPECIFIED EQUIPMENT ELECTRIC WATER COOLER POWER CONNECTION, GFCI OUTLET. HAND DRYER POWER CONNECTION: COORDINATE MOUNTING HEIGHT W/ ARCHITECTURAL ELEVATIONS SEE DETAIL 3/E7.0. RECEPTACLE FOR CLOCK (RECESSED) AND CLOCK; COORDINATE MOUNTING HEIGHT & LOCATION WITH ARCHITECTURAL FLOOR PLAN AND ELEVATIONS QUAD RECEPTACLE: CEILING MOUNTED SWITCH: SINGLE-POLE SWITCH: THREE-WAY TYPE SWITCH: FOUR-WAY TYPE SWITCH: LOW VOLTAGE OVERRIDE SWITCH FOR VACANCY SENSOR. WHERE MULTIPLE SUBSCRIPTS ARE INDICATED ("ab" FOR EXAMPLE) PROVIDE A PUSHBUTTON FOR EACH CORRESPONDING GROUP OF FIXTURES TO BE CONTROLLED (2 BUTTON SWITCH FOR "ab" FOR EXAMPLE). THE PUSHBUTTONS SHALL BE MOUNTED UNDER A SINGLE GANG FACEPLATE. SWITCH: 0-10V DIMMER TYPE. DIMMER SHALL BE COMPATIBLE WITH DIMMING ROOM CONTROLLER SWITCH: KEY-OPERATED SWITCH: OVERRIDE OCCUPANCY SENSOR, CEILING MOUNTED OCCUPANCY SENSOR, CORNER MOUNTED OCCUPANCY SENSOR, WALL MOUNTED SWITCH: MOTOR RATED, WITHOUT OVERLOAD PROTECTION DISCONNECT SWITCH DRY-TYPE TRANSFORMER PANELBOARD: SURFACE MOUNTED EQUIPMENT AS NOTED, SEE ABBREVIATIONS, THIS SHEET PHOTOCELL: LOCATE UNDER EAVES, FACING NORTH, AVOID ANY OTHER OUTSIDE LIGHT SOURCE BRANCH CIRCUIT: CONCEALED BRANCH CIRCUIT: CONCEALED IN FLOOR SLAB BRANCH CIRCUIT: EXPOSED 'HOMERUN' TO PANEL: NUMBER OF HASH MARKS INDICATES QUANTITY OF No. 12 AWG UNGROUNDED CONDUCTORS IN 3/4" RACEWAY. GROUNDED CONDUCTORS (NEUTRALS) ARE NOT SHOWN - ONE DEDICATED NEUTRAL IS REQUIRED FOR EACH UNGROUNDED CONDUCTOR INSTALLED, SEE SPECIFICATIONS. EACH CONDUCTOR SHALL BE MIN. No. 12 AWG UNLESS NOTED OTHERWISE. JUNCTION BOX: MTD. ABOVE CEILING JUNCTION BOX: WALL MTD. 7. WHERE COMPLETE BRANCH CIRCUIT WIRING IS NOT SHOWN, PROVIDE ACCORDING TO HOMERUNS SHOWN AND CORRESPONDING CIRCUIT NUMBERS ADJACENT TO THE DEVICE OR FIXTURE. REFER TO THE SPECIFICATIONS FOR THE WIRING METHODS. BRANCH CIRCUIT RATINGS SHALL BE BASED ON OVERCURRENT DEVICE RATINGS SHOWN IN THE PANEL SCHEDULES. 8. REFER TO THE ELECTRICAL PANELBOARD SCHEDULES AND EQUIPMENT RATINGS & CONNECTIONS SCHEDULE FOR VOLTAGE, BRANCH CIRCUITS REQUIREMENTS, BREAKERS SIZES AND OTHER RELATED ELECTRICAL EQUIPMENT TO BE PROVIDED AND/OR INSTALLED BY THE ELECTRICAL CONTRACTOR. C XX" WP A AMPERES ACC ALARM COMMAND CENTER AFF ABOVE FINISHED FLOOR AFG ABOVE FINISHED GRADE AH AIR HANDLER AIC AMPERAGE INTERRUPT CAPABILITY ATU AIR TERMINAL UNIT A/V AUDIO/VISUAL AWG AMERICAN WIRE GAUGE BFG BELOW FINISHED GRADE B.E. BOTTOM EDGE C. CONDUIT CU CONDENSING UNIT DACS DIGITAL ALARM COMMUNICATOR SYSTEM DAH DUCTLESS AIR HANDLER DHP DUCTLESS HEAT PUMP V S V S VS VACANCY SENSOR, CEILING MOUNTED VACANCY SENSOR, CORNER MOUNTED VACANCY SENSOR, WALL MOUNTED THE ELECTRICAL DRAWINGS ARE ONLY PART OF THE CONTRACT DOCUMENTS. THE CONTRACTOR SHALL REVIEW ALL OF THE DRAWINGS AND SPECIFICATIONS FOR THEIR INTERRELATIONSHIP AND REQUIRED COORDINATION BETWEEN DISCIPLINES. SYMBOL WHERE SHOWN AT OR NEAR A ROOM INDICATES THAT ROOM IS SHOWN AS A TYPICAL LARGE SCALE. (2) INDICATES THE DETAIL NUMBER AND (E4.2) INDICATES THE SHEET NUMBER. ALL CONDUCTORS SHALL BE COPPER UNLESS NOTED WITH THE WORD "ALUMINUM" IN THE DESCRIPTION. EACH DOOR SHALL HAVE ONE 3/4"C. FROM DOOR FRAME TO DOOR CONTROLLER ENCLOSURE (ASSUME WITHIN 50' OF DOOR), ONE DEDICATED 20A, 120 VOLT CIRCUIT TO SAME CONTROLLER ENCLOSURE. PRIOR TO RUNNING ANY CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTED DEVICES WITH WALL MOUNTED ACOUSTICAL PANELS. SEE ARCHITECTURAL DRAWINGS FOR SPACES IN WHICH WALL PANELS ARE INSTALLED. PRIOR TO RUNNING CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTED DEVICES WITH WALL MOUNTED SAFETY PADS IN GYMNASIUM. 1. 3. 4. 5. 6. DIA. DIAMETER E.C.B. ENCLOSED CIRCUIT BREAKER EF EXHAUST FAN EH ELECTRIC HEATER EMCS ENERGY MANAGEMENT CONTROL UNIT FAAP FIRE ALARM ANNUNCIATOR PANEL FACP FIRE ALARM CONTROL PANEL G GROUND GFI GROUND-FAULT INTERRUPTING HP HORSE POWER HRVU HEAT RECOVERY VENTILATING UNIT HWCP HOT WATER CIRCULATING PUMP KCMIL KILO CIRCULAR MIL MAH MAKEUP AIR HEATER MB MAIN BREAKER MCA MINIMUM CIRCUIT AMPS MCC MOTOR CONTROL CENTER MIN MINIMUM MOCP MAXIMUM OVERCURRENT PROTECTION MTD MOUNTED No. NUMBER NEC NATIONAL ELECTRIC CODE NTS NOT TO SCALE PIV POST INDICATOR VALVE RGS RIGID GALVANIZED STEEL RTU ROOFTOP UNIT SF SUPPLY FAN SPD SURGE PROTECTION DEVICE SWBD SWITCHBOARD TTW THROUGH-THE-WALL HEAT PUMP TYP TYPICAL UH UNIT HEATER UNO UNLESS NOTED OTHERWISE V VOLTAGE W WATTAGE W/ WITH WH WATER HEATER WHP WALL-MOUNTED HEAT PUMP WP WEATHER PROOF XFMR TRANSFORMER SMOKE DAMPER, 120V, PROVIDE POWER CONNECTION AND ALL NEEDED SMOKE DETECTION AND CONTROL MODULES AS REQUIRED BY NFPA 72 FOR PROPER OPERATION. SD FIRE ALARM REMOTE VOICE EVACUATION MICROPHONE, RECESSED WALL MOUNTED. MIC "C" DESIGNATION INDICATES CEILING MOUNTED. S SPEAKER - SEE DRAWINGS AND SPECIFICATIONS FOR TYPE. LA-1,3,5 'HOMERUN' TO PANEL FOR EQUIPMENT: SEE EQUIPMENT CONNECTION SCHEDULES FOR SIZE OF FEEDER AND NUMBER OF CONDUCTORS. a SWITCH: SUBSCRIPT THAT INDICATES CORRESPONDING FIXTURES THAT SWITCH CONTROLS D RECEPTACLE: QUADRUPLEX, TAMPER RESISTANT TYPE. O S OCCUPANCY SENSOR, CEILING MOUNTED HIGHBAY TYPE HBS SCENE CONTROLLER D1 0-10V DIMMING SYSTEM USED IN SPACES WITH ONE DIMMED LIGHTING LOAD. SEE 0-10V DIMMING WIRING SCHEMATIC, DETAIL 9/E0.1. D2 0-10V DIMMING SYSTEM USED IN SPACES WITH TWO DIMMED LIGHTING LOAD. SEE 0-10V DIMMING WIRING SCHEMATIC, DETAIL 9/E0.1. D3 0-10V DIMMING SYSTEM. SEE CAFETERIA LIGHTING SCHEMATIC 0-10V DIMMING, DETAIL 8/E0.1. PS ACCESS CONTROL POWER SUPPLY WALL MTD. TELECOMMUNICATION JUNCTION BOX AND CONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING CB AREA OF REFUGE CALL BOX: WALL MOUNT AT 46" AFF V VOLUME CONTROL: WALL MOUNT AT 46" AFF T PROFESSIONAL N E E R I G N E S I G E R E R E D No. 26308 I G R O E G A A W R. L N E R R A W DRAWING NUMBER DRAWINGS MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION ALL RIGHTS RESERVED COPYRIGHT 2014 DATE: DATE: JOB NO. SCALE: DESIGNED DRAWN CHECKED REVISIONS: 5/9/2016 4:01:35 PM NOT TO SCALE J U L I E T T E L O W E L E M E N T A R Y S C H O O L 15 Blue Ridge Ave Savannah, GA 31401 SAVANNAH CHATHAM COUNTY PUBLIC SCHOOL SYSTEM ELECTRICAL LEGEND & LIGHT FIXTURE SCHEDULE E0.0 215 2001 07 GJC WAL GJC 02/18/2016 CONFORMANCE SET LIGHT FIXTURE SCHEDULE TYPE DESCRIPTION LAMPS MANUFACTURER / SERIES FINISH MOUNTING NOTES A5 KITCHEN 2'X4' LENSED TROFFER WITH 0.125" MIN. #A12 LENS AND FLUSH STEEL DOOR WITH MITERED CORNERS. PROVIDE GASKETING BETWEEN LENS AND DOOR FRAME. LED: 4000 LUMEN, 3500K METALUX "GRLED" SERIES, LITHONIA, LUMAX, CREE WHITE RECESSED B1 2'X4' VOLUMETRIC TROFFER WITH ACRYLIC FROSTED LENS. LED: 4000 LUMEN, 3500K METALUX "CRUZE" SERIES, LITHONIA, LSI, CREE WHITE RECESSED NOTE 1, NOTE 6 B1F 2'X4' VOLUMETRIC TROFFER WITH ACRYLIC FROSTED LENS. LED: 4000 LUMEN, 3500K METALUX "CRUZE" SERIES, LITHONIA, LSI, CREE WHITE FLANGE NOTE 1, NOTE 6 B2 2'X4' VOLUMETRIC TROFFER WITH ACRYLIC FROSTED LENS. LED: 5000 LUMEN, 3500K METALUX "CRUZE" SERIES, LITHONIA, LSI, CREE WHITE RECESSED NOTE 1, NOTE 6 B4 2'X2' VOLUMETRIC TROFFER WITH ACRYLIC FROSTED LENS. LED: 4350 LUMEN, 3500K METALUX "CRUZE" SERIES, LITHONIA, LSI, CREE WHITE RECESSED NOTE 1 D1 8" DIAMETER CYLINDER, 33" LENGTH, OPAL ACRYLIC SANDBLASTED DIFFUSER, VARIOUS PENDANT LENGTHS TO BE DETERMINED BY ARCHITECT (MAXIMUM STEM LENGTH 8'-0") LED 29 WATT, 3500K DELRAY "BIG LIGHT 6341" SERIES, WINONA, BETA CALCO "CYLINDRA", VISA "SEQUENCE" SELECTED BY ARCHITECT PENDANT 0-10 VOLT DIMMING E1 STANDARD STRIP WITH 14 GUAGE WIRE GUARD. 2-32 WATT, T8, 3500K LITHONIA "C" SERIES, METALUX "SS" SERIES, COLUMBIA "CS" SERIES, HE WILLIAMS "76" SERIES WHITE SURFACE NOTE 2 F1 ELEVATOR PIT LIGHT, CLEAR GLASS GLOBE WITH DIE CAST ALUMINUM GUARD. 1-42 WATT TTT, 3500K RIG-A-LITE "CVPW" SERIES, STONECO "VWXL" SERIES, EXCELINE "RLW" SERIES, DAYBRITE "VFSW" SERIES, BASELITE "W2" SERIES EXPOSED PARTS CORROSION RESISTANT WALL G1 DOWNLIGHT, RECESSED SELF FLANGED, 6" APERTURE CLEAR MATT DIFFUSE REFLECTOR. SHOWER LIGHT SUITABLE FOR WET LOCATION. LED: 2000 LUMEN, 3500K HALO COMMERCIAL "PD6" SERIES, LITHONIA, DAYBRITE, LIGHTOLIER,PRESCOLITE WHITE TRIM RING RECESSED G2 DOWNLIGHT, RECESSED SELF FLANGED, 6" APERTURE CLEAR MATT DIFFUSE REFLECTOR. LED: 2000 LUMEN, 3500K HALO COMMERCIAL "PD6" SERIES, LITHONIA, DAYBRITE, LIGHTOLIER,PRESCOLITE WHITE TRIM RING RECESSED G3 DOWNLIGHT, RECESSED SELF FLANGED, 6" APERTURE CLEAR MATT DIFFUSE REFLECTOR. LED: 1000 LUMEN, 3500K HALO COMMERCIAL "PD6" SERIES, LITHONIA, DAYBRITE, LIGHTOLIER,PRESCOLITE WHITE TRIM RING RECESSED H1 1'X4' SURFACE FIXTURE WITH ACRYLIC DIFFUSER. LED: 4600 LUMEN, 3500K LITHONIA "LBLED" SERIES, METALUX, DAYBRITE, H.E. WILLIAMS WHITE SURFACE HB HIGHBAY LED WITH WIDE DISTRIBUTION. PROVIDE WITH DOORFRAME ACRYLIC LENS AND WIRE GUARD. CHAIN MOUNT FIXTURE TO STRUCTURE, SUSPEND TO BOTTOM OF TRUSS. LED: 18000 LUMENS, 3500K METALUX "HBLED" SERIES, DAYBRITE, LITHONIA, H.E. WILLIAMS WHITE CHAIN NOTE 6, 0-10 VOLT DIMMING M1 WALL MOUNTED UP-LIGHT WITH INTEGRAL DRIVER, EXTERNAL YOKE ON CANOPY MOUNTING, CUT OFF VISOR. LED: 1100 LUMENS, 3500K ELLIPTIPAR "STYLE S122" SERIES, WINONA, SPI, FORUM WHITE WALL AT 20'-0" 0-10 VOLT DIMMING OA WALL MOUNTED, WEDGE SHAPE EXTERIOR GRADE FIXTURE. LED: 4000 LUMEN, 3500K LUMARK "CROSSTOUR MAXX" SERIES, LITHONIA, HUBBELL, McGRAW EDISON, PHILLIPS BY ARCHITECT WALL - SURFACE 90 MINUTE BATTERY. OB ROUND, CANOPY CEILING MOUNTED LED LIGHT, MAX 14" DIAMETER, 4" DEEP, OPAL LENS. LED: 2250 LUMEN, 3500K LUMINAIRE LED "ARV13" SERIES, LITHONIA, HUBBELL, McGRAW EDISON, PHILLIPS BY ARCHITECT SURFACE OC BUILDING MOUNTED FLOOD LIGHT WITH MOUNTING BRACKET AND ASSOCIATED HARDWARE. WIDE SYMETRIC FLOOD. LED: 7150 LUMEN, 3500K COOPER "NIGHT FALCON" SERIES, LITHONIA "D" SERIES, BETA, PHILLIPS BRONZE WALL/VERTICAL SURFACE NOTE 3 S1 CYLINDRICAL 48" DIAMETER FIXTURE, 6" DEPTH, ACRYLIC LENS LED: 7500 LUMENS, 3500K EVERGREEN "SATURN CEILING SPECIAL", H.E. WILLIAMS, IMPACT BY ARCHITECT SURFACE T1 TRACK LIGHT. SEE DETAIL 5/E0.1 W1 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLE RESISTANT. FIXTURE SHALL BE EQUIPPED WITH MOTION SENSOR. LED: 4000 LUMEN, 3500K LUMINAIRE "TSL" SERIES, LITHONIA, METALUX, H.E. WILLIAMS WHITE WALL - SURFACE XA SINGLE FACE EXIT LIGHT, DIE CAST ALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED. LED LITHONIA "LE" SERIES, BEGHELLI "LC1E" SERIES, DUAL LITE "CVD" SERIES, SURE-LITE "CX" SERIES BRUSHED STAINLESS WALL 90 MINUTE BATTERY. XB DOUBLE FACE EXIT LIGHT, DIE CAST ALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED LED LITHONIA "LE" SERIES, BEGHELLI "LC1E" SERIES, DUAL LITE "CVD" SERIES, SURE-LITE "CX" SERIES BRUSHED STAINLESS CEILING 90 MINUTE BATTERY. XC SINGLE FACE AREA OF REFUGE SIGN, DIE CAST ALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED. LED LITHONIA "LE" SERIES, BEGHELLI "LC1E" SERIES, DUAL LITE "CVD" SERIES, SURE-LITE "CX" SERIES BRUSHED STAINLESS WALL 90 MINUTE BATTERY. XD DOUBLE FACE AREA OF REFUGE SIGN, DIE CAST ALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OF ARROWS AS INDICATED LED LITHONIA "LE" SERIES, BEGHELLI "LC1E" SERIES, DUAL LITE "CVD" SERIES, SURE-LITE "CX" SERIES BRUSHED STAINLESS CEILING 90 MINUTE BATTERY. XEM 2 HEAD, WALL MOUNT EMERGENCY BATTERY WITH FIXTURE LITHONIA "ELM" SERIES, CHLORIDE, SURELITE, DUALITE WHITE WALL 90 MINUTE BATTERY. LIGHT FIXTURE SCHEDULE NOTES: 1 GENERAL: REFER TO LIGHTING PLANS FOR BALLAST VOLTAGES AND CONFIGURATION OF FIXTURES. FIXTURES INDICATED TO BE DIMMED SHALL BE SUPPLIED WITH DIMMING BALLAST. 2 FIXTURES SHALL BE MOUNTED SUSPENDED OR SURFACE, GIVING RIGHT OF WAY TO HVAC DUCT WORK AND/OR EQUIPMENT. 3 PROVIDE BACKBOX ON ALL FIXTURES OF THIS TYPE SO THAT FIXTURES WITH AND WITHOUT EMERGENCY BALLAST ARE AT THE SAME DEPTH. 4 GENERAL: COORINATE ALL MOUNTING OF FIXTURES (GRID/FLANGE) WITH ARCHITECTURAL RCP. 5 FIXTURES SHALL BE SELECTED FROM THE FIXTURE SCHEDULE NOT ONLY BY CATALOG NUMBER BUT WITH CONSIDERATION TO MOUNTING, NUMBER AND TYPE OF LAMPS, AND REFERENCED NOTES. THE FIRST FIXTURE INDICATED FOR EACH TYPE WITH CATALOG NUMBER IS THE BASIS OF DESIGN FIXTURE, OTHER LISTED MANUFACTURERS PRODUCING AN EQUAL FIXTURE TO THE BASIS OF DESIGNFIXTURE MAY BE PROVIDED. 6 THIS LIGHT FIXTURE IS TO BE SUPPLIED BY THE OWNER, INSTALLED BY THE CONTRACTOR. 01 01 PERMIT COMMENTS - 03/03/2016 01

Upload: dangtuong

Post on 06-Jul-2018

213 views

Category:

Documents


0 download

TRANSCRIPT

FACP

FSCU

VS

WF

FAA

DH

2E4.2

F FIRE ALARM PULL STATION. WALL MOUNTED 46"ABOVE FLOOR.

FIRE ALARM SIGNAL, SPEAKER AND FLASHING LIGHT, 6'-8" AFF.

FIRE ALARM STROBE LIGHT, 6'-8" IN. MOUNTING HEIGHT.

FIRE ALARM CONNECTION, HOOD EXTINGUISHING SYSTEM, SEEMECHANICAL DRAWINGS FOR LOCATION. INTERLOCK WITH SHUNTTRIP BREAKERS FOR EQUIPMENT UNDER HOOD.

FIRE ALARM REMOTE LCD ANNUNCIATOR PANEL. FLUSH RECESSEDWALL MOUNTED.

FIRE ALARM DOOR HOLDER, WALL MOUNTED, CONSULT ARCHITECTURALDRAWINGS TO DETERMINE TYPE REQUIRED. PROVIDE POWER FROMNEAREST RECEPTACLE CIRCUIT AND CONNECT TO FIRE ALARM SYSTEM.

TAMPER SWITCH, FURNISHED AND INSTALLED WITH SPRINKLERSYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL.

FLOW SWITCH, FURNISHED AND INSTALLED WITH SPRINKLERSYSTEM. INTERLOCK WITH FIRE ALARM SYSTEM BY ELECTRICAL.

FIRE ALARM SMOKE DETECTOR, CEILING MOUNTED.

FIRE ALARM DUCT SMOKE DETECTOR LOCATED IN HVAC DUCT.

FIRE ALARM CONTROL PANEL, SURFACE WALL MOUNTED.

FIRE ALARM SIGNAL, HORN. 6 FT.-8 IN. MOUNTING HEIGHT.

FIRE ALARM HEAT DETECTOR, 135 DEG, OPERATION.

P

WEATHER PROOF.

FIRE ALARM STROBE LIGHT, CEILING MOUNTED.

S

M

FIRE ALARM:

H

S WP

IC

AD

AC

S

2.

COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROLREQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER.

INTRUSION DETECTION SYSTEM:

CONDUIT SLEEVE: NUMBER & SIZE, (2)-2" FOR ALLCLASSROOMS, (1)-2" FOR ALL OFFICES, UNO

CABLE TRAY: SIZE AS INDICATED, 18"W x 4"H TYP.

INTERCOM SPEAKER: WEATHERPROOF WALL MOUNTED AT96"AFF.

MICROPHONE JACK: WALL MOUNTED AT 18" AFF, UNO.

EMERGENCY CALL PUSH BUTTON: WALL MOUNTED 46" AFF

ADMINISTRATIVE DISPLAY PHONE: WALL MOUNT AT 46" AFF

INTRUSION SYSTEM: KEY-PAD, MOUNT 48"AFF

SECURITY ACCESS: MOUNT ABOVE CEILING AT ENTRY WAY

INTRUSION DETECTION DEVICE: WALL MTD.

ACCESS CONTROL SYSTEMS

SEE DETAIL 2/T2.1 FOR POWER, POWER DISCONNECT, LOW VOLTAGE CABLING,BOXES AND CONDUIT REQUIREMENTS. REFER TO ARCHITECTURAL PLANSAND DOOR SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.

INTERCOM SPEAKER: 2' X 2' SQUARE CEILING MOUNTED

COORDINATE MOUNTING HEIGHTS, DEVICE LOCATIONS & POWER/CONTROLREQUIREMENTS WITH ARCHITECTURAL DRAWINGS AND SYSTEM INSTALLER.

SPEAKER SYSTEM:

CABLING COMPONENTS:

THE CONTRACTOR SHALL PROVIDE ROUGH-IN FOR ALL DEVICES ANDWIRING. ROUGH-IN REQUIREMENTS ARE SPECIFIED IN SECTION 261010. VERIFY ADJACENCY TO CORRESPONDING POWER RECEPTACLES. OTHERDEVICES WHOSE LOCATIONS ARE NOT DEPENDENT ON RECEPTACLEPLACEMENT SHALL BE COORDINATED WITH SYSTEM INSTALLER.

WALL MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

CEILING MTD. TELECOMMUNICATION JUNCTION BOX

WALL MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

CEILING MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

CEILING MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

ROUGH-IN FOR LOW VOLTAGE SYSTEMS:

SA

KP

J

J

OS

OS

OS

W

HD

C

PC

XX-1

T

M

ABBREVIATIONS:

LEGEND:

LIGHTING FIXTURES:UPPERCASE LETTER ADJACENT TO FIXTURE DENOTES DESIGNATION PER THELIGHTING FIXTURE SCHEDULE. LOWERCASE LETTER DENOTES SWITCHLEG. THERESPECTIVE SWITCH WILL HAVE THE SAME DESTINATIONS. NUMERAL DENOTESBRANCH CIRCUIT CONNECTION. FIXTURE TYPE ENDING WITH 'D' SUFFIX INDICATESFIXTURE THAT REQUIRES DIMMING BALLAST. (EXAMPLE: FIXTURE TYP 'A3D')

REFER TO THE FIXTURE SCHEDULE FOR THE SPECIFIC FIXTURE INFORMATION.

EMERGENCY FIXTURES SHALL HAVE FACTORY INSTALLED INTERNAL BATTERIES, PERSPECIFICATIONS.

NL SUFFIX ADJACENT TO FIXTURE TYPE DENOTES NIGHT LIGHT. DO NOT SWITCHTHESE FIXTURES.

NON-EMERGENCY

EMERGENCY/BATTERY BACKUP

LIGHTING FIXTURE: LINEAR FLUORESCENT

ELECTRICAL EQUIPMENT:REFER TO ONE-LINE DIAGRAM AND EQUIPMENT CONNECTION SCHEDULE FORLOAD DATA USED AS THE BASIS OF DESIGN AND REQUIRED CONNECTIONS.VERIFY LOAD AND LOCATION WITH EQUIPMENT CUT-SHEETS AND INSTALLER.

GENERAL NOTES:

DEVICE IDENTIFIER TAGS:

NUMERAL ADJACENT TO DEVICE DENOTES BRANCH CIRCUIT CONNECTION.IDENTIFIER TAGS ADJACENT TO DEVICES INDICATE:

WIRING DEVICES:

RECEPTACLES:

NOMINAL MOUNTING HEIGHT OF RECEPTACLES SHALL BE 18" TO CENTER, UNO. IFAPPLICABLE, ADJUST SO DEVICE COVER IS IN THE CENTER OF MASONRY COURSENEAREST THAT HEIGHT. THE HEIGHT ESTABLISHED SHALL GOVERN FOR ALL BOXINSTALLATIONS, WHERE INSTALLED IN MASONRY OR FRAMED WALLS.

SWITCHES:

MOUNTING HEIGHT OF SWITCHES SHALL BE 46" NOMINAL, ADJUSTED IN THE SAMEMANNER AS SPECIFIED ABOVE, FOR RECEPTACLES. LOWERCASE LETTER INDICATESSWITCHLEG CONNECTION. THE RESPECTIVE FIXTURE(S) WILL HAVE THE SAMEDESIGNATION.

BRANCH CIRCUITS:

CONDUCTOR COUNTS ARE SHOWN ON THE HOMERUNS ONLY. CONTRACTORSHALL DETERMINE COUNTS FOR INTERMEDIATE RUNS BASED ON THE MANNERIN WHICH THE CIRCUIT ELEMENTS ARE CONNECTED. REFER TO THESPECIFICATION SECTIONS 262010, 262080, & 26030 FOR SPECIALREQUIREMENTS.

LA-1,3,5

MISCELLANEOUS COMPONENTS:3

4

V

K

O

LIGHTING FIXTURE: LINEAR FLUORESCENT

LIGHTING FIXTURE: LINEAR FLUORESCENT

LIGHTING FIXTURE: FLUORESCENT STRIP

LIGHTING FIXTURE: FLUORESCENT, WALL MTD.

DOWNLIGHT/SCONCE FIXTURE

EXIT AREA OF REFUGE LIGHT: UNIVERSAL MTD.

DIRECTIONAL FIXTURES: EMERGENCY TYPE

LIGHT TRACK: LENGTH AS SHOWN

MOUNT ABOVE COUNTERTOP OR BACKSPLASH, 9" ABOVEWORK SURFACE TO CENTER

MOUNT DEVICE AT HEIGHT INDICATED

PROVIDE WEATHER-PROOF COVER

RECEPTACLE: SIMPLEX

RECEPTACLE: DUPLEX, TAMPER RESISTANT TYPE.

RECEPTACLE: GROUND-FAULT-INTERRUPTING TYPE,TAMPER RESISTANT TYPE.

IN-SLAB FLOOR BOX: SEE SPECIFICATIONS

RECEPTACLE: DRYER, 30 AMP, 120/250 VOLT

RECEPTACLE: SPECIAL PURPOSE , COORDINATE NEMARATING WITH SPECIFIED EQUIPMENT

ELECTRIC WATER COOLER POWER CONNECTION, GFCI OUTLET.

HAND DRYER POWER CONNECTION: COORDINATEMOUNTING HEIGHT W/ ARCHITECTURAL ELEVATIONSSEE DETAIL 3/E7.0.

RECEPTACLE FOR CLOCK (RECESSED) AND CLOCK;COORDINATE MOUNTING HEIGHT & LOCATION WITHARCHITECTURAL FLOOR PLAN AND ELEVATIONS

QUAD RECEPTACLE: CEILING MOUNTED

SWITCH: SINGLE-POLE

SWITCH: THREE-WAY TYPE

SWITCH: FOUR-WAY TYPE

SWITCH: LOW VOLTAGE OVERRIDE SWITCH FOR VACANCYSENSOR. WHERE MULTIPLE SUBSCRIPTS ARE INDICATED("ab" FOR EXAMPLE) PROVIDE A PUSHBUTTON FOR EACHCORRESPONDING GROUP OF FIXTURES TO BE CONTROLLED(2 BUTTON SWITCH FOR "ab" FOR EXAMPLE). THEPUSHBUTTONS SHALL BE MOUNTED UNDER A SINGLE GANGFACEPLATE.

SWITCH: 0-10V DIMMER TYPE. DIMMER SHALL BE COMPATIBLEWITH DIMMING ROOM CONTROLLER

SWITCH: KEY-OPERATED

SWITCH: OVERRIDE

OCCUPANCY SENSOR, CEILING MOUNTED

OCCUPANCY SENSOR, CORNER MOUNTED

OCCUPANCY SENSOR, WALL MOUNTED

SWITCH: MOTOR RATED, WITHOUT OVERLOAD PROTECTION

DISCONNECT SWITCH

DRY-TYPE TRANSFORMER

PANELBOARD: SURFACE MOUNTED

EQUIPMENT AS NOTED, SEE ABBREVIATIONS, THIS SHEET

PHOTOCELL: LOCATE UNDER EAVES, FACING NORTH, AVOIDANY OTHER OUTSIDE LIGHT SOURCE

BRANCH CIRCUIT: CONCEALED

BRANCH CIRCUIT: CONCEALED IN FLOOR SLAB

BRANCH CIRCUIT: EXPOSED

'HOMERUN' TO PANEL: NUMBER OF HASH MARKSINDICATES QUANTITY OF No. 12 AWG UNGROUNDEDCONDUCTORS IN 3/4" RACEWAY. GROUNDEDCONDUCTORS (NEUTRALS) ARE NOT SHOWN - ONEDEDICATED NEUTRAL IS REQUIRED FOR EACHUNGROUNDED CONDUCTOR INSTALLED, SEESPECIFICATIONS. EACH CONDUCTOR SHALL BE MIN. No.12 AWG UNLESS NOTED OTHERWISE.

JUNCTION BOX: MTD. ABOVE CEILING

JUNCTION BOX: WALL MTD.

7. WHERE COMPLETE BRANCH CIRCUIT WIRING IS NOT SHOWN, PROVIDE ACCORDINGTO HOMERUNS SHOWN AND CORRESPONDING CIRCUIT NUMBERS ADJACENT TO THEDEVICE OR FIXTURE. REFER TO THE SPECIFICATIONS FOR THE WIRING METHODS.BRANCH CIRCUIT RATINGS SHALL BE BASED ON OVERCURRENT DEVICE RATINGSSHOWN IN THE PANEL SCHEDULES.

8. REFER TO THE ELECTRICAL PANELBOARD SCHEDULES AND EQUIPMENT RATINGS &CONNECTIONS SCHEDULE FOR VOLTAGE, BRANCH CIRCUITS REQUIREMENTS,BREAKERS SIZES AND OTHER RELATED ELECTRICAL EQUIPMENT TO BE PROVIDEDAND/OR INSTALLED BY THE ELECTRICAL CONTRACTOR.

C

XX"

WP

A AMPERES

ACC ALARM COMMAND CENTER

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AH AIR HANDLER

AIC AMPERAGE INTERRUPT CAPABILITY

ATU AIR TERMINAL UNIT

A/V AUDIO/VISUAL

AWG AMERICAN WIRE GAUGE

BFG BELOW FINISHED GRADE

B.E. BOTTOM EDGE

C. CONDUIT

CU CONDENSING UNIT

DACS DIGITAL ALARM COMMUNICATOR SYSTEM

DAH DUCTLESS AIR HANDLER

DHP DUCTLESS HEAT PUMP

VS

VS

VS

VACANCY SENSOR, CEILING MOUNTED

VACANCY SENSOR, CORNER MOUNTED

VACANCY SENSOR, WALL MOUNTED

THE ELECTRICAL DRAWINGS ARE ONLY PART OF THE CONTRACT DOCUMENTS.THE CONTRACTOR SHALL REVIEW ALL OF THE DRAWINGS AND SPECIFICATIONSFOR THEIR INTERRELATIONSHIP AND REQUIRED COORDINATION BETWEENDISCIPLINES.

SYMBOL WHERE SHOWN AT OR NEAR A ROOM INDICATES THATROOM IS SHOWN AS A TYPICAL LARGE SCALE. (2) INDICATESTHE DETAIL NUMBER AND (E4.2) INDICATES THE SHEET NUMBER.

ALL CONDUCTORS SHALL BE COPPER UNLESS NOTED WITH THE WORD "ALUMINUM"IN THE DESCRIPTION.

EACH DOOR SHALL HAVE ONE 3/4"C. FROM DOOR FRAME TO DOOR CONTROLLERENCLOSURE (ASSUME WITHIN 50' OF DOOR), ONE DEDICATED 20A, 120 VOLT CIRCUITTO SAME CONTROLLER ENCLOSURE.

PRIOR TO RUNNING ANY CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTEDDEVICES WITH WALL MOUNTED ACOUSTICAL PANELS. SEE ARCHITECTURAL DRAWINGSFOR SPACES IN WHICH WALL PANELS ARE INSTALLED.

PRIOR TO RUNNING CONDUIT, COORDINATE LOCATIONS OF ALL WALL MOUNTED DEVICESWITH WALL MOUNTED SAFETY PADS IN GYMNASIUM.

1.

3.

4.

5.

6.

DIA. DIAMETER

E.C.B. ENCLOSED CIRCUIT BREAKER

EF EXHAUST FAN

EH ELECTRIC HEATER

EMCS ENERGY MANAGEMENT CONTROL UNIT

FAAP FIRE ALARM ANNUNCIATOR PANEL

FACP FIRE ALARM CONTROL PANEL

G GROUND

GFI GROUND-FAULT INTERRUPTING

HP HORSE POWER

HRVU HEAT RECOVERY VENTILATING UNIT

HWCP HOT WATER CIRCULATING PUMP

KCMIL KILO CIRCULAR MIL

MAH MAKEUP AIR HEATER

MB MAIN BREAKER

MCA MINIMUM CIRCUIT AMPS

MCC MOTOR CONTROL CENTER

MIN MINIMUM

MOCP MAXIMUM OVERCURRENT PROTECTION

MTD MOUNTED

No. NUMBER

NEC NATIONAL ELECTRIC CODE

NTS NOT TO SCALE

PIV POST INDICATOR VALVE

RGS RIGID GALVANIZED STEEL

RTU ROOFTOP UNIT

SF SUPPLY FAN

SPD SURGE PROTECTION DEVICE

SWBD SWITCHBOARD

TTW THROUGH-THE-WALL HEAT PUMP

TYP TYPICAL

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

V VOLTAGE

W WATTAGE

W/ WITH

WH WATER HEATER

WHP WALL-MOUNTED HEAT PUMP

WP WEATHER PROOF

XFMR TRANSFORMER

SMOKE DAMPER, 120V, PROVIDE POWER CONNECTION AND ALLNEEDED SMOKE DETECTION AND CONTROL MODULES AS REQUIREDBY NFPA 72 FOR PROPER OPERATION.

SD

FIRE ALARM REMOTE VOICE EVACUATION MICROPHONE, RECESSEDWALL MOUNTED.

MIC

"C" DESIGNATION INDICATES CEILING MOUNTED.

S SPEAKER - SEE DRAWINGS AND SPECIFICATIONS FOR TYPE.

LA-1,3,5'HOMERUN' TO PANEL FOR EQUIPMENT: SEE EQUIPMENTCONNECTION SCHEDULES FOR SIZE OF FEEDER ANDNUMBER OF CONDUCTORS.

aSWITCH: SUBSCRIPT THAT INDICATES CORRESPONDINGFIXTURES THAT SWITCH CONTROLS

D

RECEPTACLE: QUADRUPLEX, TAMPER RESISTANT TYPE.

OS OCCUPANCY SENSOR, CEILING MOUNTED HIGHBAY TYPEHBS

SCENE CONTROLLER

D1 0-10V DIMMING SYSTEM USED IN SPACES WITH ONE DIMMEDLIGHTING LOAD. SEE 0-10V DIMMING WIRING SCHEMATIC,DETAIL 9/E0.1.

D2 0-10V DIMMING SYSTEM USED IN SPACES WITH TWO DIMMEDLIGHTING LOAD. SEE 0-10V DIMMING WIRING SCHEMATIC,DETAIL 9/E0.1.

D3 0-10V DIMMING SYSTEM. SEE CAFETERIA LIGHTINGSCHEMATIC 0-10V DIMMING, DETAIL 8/E0.1.

PS ACCESS CONTROL POWER SUPPLY

WALL MTD. TELECOMMUNICATION JUNCTION BOX ANDCONDUIT ROUGH-IN TO NEAREST ACCESSIBLE CEILING

CB AREA OF REFUGE CALL BOX: WALL MOUNT AT 46" AFF

V VOLUME CONTROL: WALL MOUNT AT 46" AFF

T

PROFESSIONAL

NEERIG

NE

SIGERERED

No. 26308

IGROEG A

AW

R.LNE

RRA

W

DRAWING NUMBER

DRAWINGS MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION

ALL RIGHTS RESERVED

COPYRIGHT 2014

DATE:

DATE:

JOB NO.

SCALE:

DESIGNED DRAWN CHECKED

RE

VIS

ION

S:

5/9/2016 4:01:35 PM

NOT TO SCALE

JULI

ETTE

LO

W E

LEM

ENTA

RY

SCH

OO

L

15 B

lue

Rid

ge A

ve S

avan

nah,

GA

314

01

SAVA

NN

AH

CH

ATH

AM

CO

UN

TY P

UB

LIC

SC

HO

OL

SYST

EM

EL

EC

TR

ICA

L L

EG

EN

D &

LIG

HT

FIX

TU

RE

SC

HE

DU

LE

E0.0

215 2001 07

GJC WALGJC

02/18/2016

CONFORMANCE SET

LIGHT FIXTURE SCHEDULE

TYPE DESCRIPTION LAMPS MANUFACTURER / SERIES FINISH MOUNTING NOTES

A5 KITCHEN 2'X4' LENSED TROFFER WITH 0.125" MIN. #A12LENS AND FLUSH STEEL DOOR WITH MITERED CORNERS.PROVIDE GASKETING BETWEEN LENS AND DOOR FRAME.

LED: 4000LUMEN,3500K

METALUX "GRLED" SERIES,LITHONIA, LUMAX, CREE

WHITE RECESSED

B1 2'X4' VOLUMETRIC TROFFER WITH ACRYLIC FROSTEDLENS.

LED: 4000LUMEN,3500K

METALUX "CRUZE" SERIES,LITHONIA, LSI, CREE

WHITE RECESSED NOTE 1, NOTE 6

B1F 2'X4' VOLUMETRIC TROFFER WITH ACRYLIC FROSTEDLENS.

LED: 4000LUMEN,3500K

METALUX "CRUZE" SERIES,LITHONIA, LSI, CREE

WHITE FLANGE NOTE 1, NOTE 6

B2 2'X4' VOLUMETRIC TROFFER WITH ACRYLIC FROSTEDLENS.

LED: 5000LUMEN,3500K

METALUX "CRUZE" SERIES,LITHONIA, LSI, CREE

WHITE RECESSED NOTE 1, NOTE 6

B4 2'X2' VOLUMETRIC TROFFER WITH ACRYLIC FROSTEDLENS.

LED: 4350LUMEN,3500K

METALUX "CRUZE" SERIES,LITHONIA, LSI, CREE

WHITE RECESSED NOTE 1

D1 8" DIAMETER CYLINDER, 33" LENGTH, OPAL ACRYLICSANDBLASTED DIFFUSER, VARIOUS PENDANT LENGTHSTO BE DETERMINED BY ARCHITECT (MAXIMUM STEMLENGTH 8'-0")

LED 29 WATT,3500K

DELRAY "BIG LIGHT 6341"SERIES, WINONA, BETACALCO "CYLINDRA", VISA"SEQUENCE"

SELECTED BYARCHITECT

PENDANT 0-10 VOLT DIMMING

E1 STANDARD STRIP WITH 14 GUAGE WIRE GUARD. 2-32 WATT,T8, 3500K

LITHONIA "C" SERIES,METALUX "SS" SERIES,COLUMBIA "CS" SERIES, HEWILLIAMS "76" SERIES

WHITE SURFACE NOTE 2

F1 ELEVATOR PIT LIGHT, CLEAR GLASS GLOBE WITH DIECAST ALUMINUM GUARD.

1-42 WATTTTT, 3500K

RIG-A-LITE "CVPW" SERIES,STONECO "VWXL" SERIES,EXCELINE "RLW" SERIES,DAYBRITE "VFSW" SERIES,BASELITE "W2" SERIES

EXPOSEDPARTS

CORROSIONRESISTANT

WALL

G1 DOWNLIGHT, RECESSED SELF FLANGED, 6" APERTURECLEAR MATT DIFFUSE REFLECTOR. SHOWER LIGHTSUITABLE FOR WET LOCATION.

LED: 2000LUMEN,3500K

HALO COMMERCIAL "PD6"SERIES, LITHONIA, DAYBRITE,LIGHTOLIER,PRESCOLITE

WHITE TRIMRING

RECESSED

G2 DOWNLIGHT, RECESSED SELF FLANGED, 6" APERTURECLEAR MATT DIFFUSE REFLECTOR.

LED: 2000LUMEN,3500K

HALO COMMERCIAL "PD6"SERIES, LITHONIA, DAYBRITE,LIGHTOLIER,PRESCOLITE

WHITE TRIMRING

RECESSED

G3 DOWNLIGHT, RECESSED SELF FLANGED, 6" APERTURECLEAR MATT DIFFUSE REFLECTOR.

LED: 1000LUMEN,3500K

HALO COMMERCIAL "PD6"SERIES, LITHONIA, DAYBRITE,LIGHTOLIER,PRESCOLITE

WHITE TRIMRING

RECESSED

H1 1'X4' SURFACE FIXTURE WITH ACRYLIC DIFFUSER. LED: 4600LUMEN,3500K

LITHONIA "LBLED" SERIES,METALUX, DAYBRITE, H.E.WILLIAMS

WHITE SURFACE

HB HIGHBAY LED WITH WIDE DISTRIBUTION. PROVIDE WITHDOORFRAME ACRYLIC LENS AND WIRE GUARD. CHAINMOUNT FIXTURE TO STRUCTURE, SUSPEND TO BOTTOMOF TRUSS.

LED: 18000LUMENS,

3500K

METALUX "HBLED" SERIES,DAYBRITE, LITHONIA, H.E.WILLIAMS

WHITE CHAIN NOTE 6, 0-10 VOLTDIMMING

M1 WALL MOUNTED UP-LIGHT WITH INTEGRAL DRIVER,EXTERNAL YOKE ON CANOPY MOUNTING, CUT OFF VISOR.

LED: 1100LUMENS,

3500K

ELLIPTIPAR "STYLE S122"SERIES, WINONA, SPI, FORUM

WHITE WALL AT 20'-0" 0-10 VOLT DIMMING

OA WALL MOUNTED, WEDGE SHAPE EXTERIOR GRADEFIXTURE.

LED: 4000LUMEN,3500K

LUMARK "CROSSTOUR MAXX"SERIES, LITHONIA, HUBBELL,McGRAW EDISON, PHILLIPS

BY ARCHITECT WALL - SURFACE 90 MINUTE BATTERY.

OB ROUND, CANOPY CEILING MOUNTED LED LIGHT, MAX 14"DIAMETER, 4" DEEP, OPAL LENS.

LED: 2250LUMEN,3500K

LUMINAIRE LED "ARV13"SERIES, LITHONIA, HUBBELL,McGRAW EDISON, PHILLIPS

BY ARCHITECT SURFACE

OC BUILDING MOUNTED FLOOD LIGHT WITH MOUNTINGBRACKET AND ASSOCIATED HARDWARE. WIDESYMETRIC FLOOD.

LED: 7150LUMEN,3500K

COOPER "NIGHT FALCON"SERIES, LITHONIA "D"SERIES, BETA, PHILLIPS

BRONZE WALL/VERTICALSURFACE

NOTE 3

S1 CYLINDRICAL 48" DIAMETER FIXTURE, 6" DEPTH, ACRYLICLENS

LED: 7500LUMENS,

3500K

EVERGREEN "SATURNCEILING SPECIAL", H.E.WILLIAMS, IMPACT

BY ARCHITECT SURFACE

T1 TRACK LIGHT. SEE DETAIL 5/E0.1

W1 1'X4' FIXTURE, SURFACE MOUNT, LOW PROFILE, VANDLERESISTANT. FIXTURE SHALL BE EQUIPPED WITH MOTIONSENSOR.

LED: 4000LUMEN,3500K

LUMINAIRE "TSL" SERIES,LITHONIA, METALUX, H.E.WILLIAMS

WHITE WALL - SURFACE

XA SINGLE FACE EXIT LIGHT, DIE CAST ALUMINUM,UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OFARROWS AS INDICATED.

LED LITHONIA "LE" SERIES,BEGHELLI "LC1E" SERIES,DUAL LITE "CVD" SERIES,SURE-LITE "CX" SERIES

BRUSHEDSTAINLESS

WALL 90 MINUTE BATTERY.

XB DOUBLE FACE EXIT LIGHT, DIE CAST ALUMINUM,UNIVERSAL MOUNTING, GREEN LETTERS - DIRECTION OFARROWS AS INDICATED

LED LITHONIA "LE" SERIES,BEGHELLI "LC1E" SERIES,DUAL LITE "CVD" SERIES,SURE-LITE "CX" SERIES

BRUSHEDSTAINLESS

CEILING 90 MINUTE BATTERY.

XC SINGLE FACE AREA OF REFUGE SIGN, DIE CASTALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS -DIRECTION OF ARROWS AS INDICATED.

LED LITHONIA "LE" SERIES,BEGHELLI "LC1E" SERIES,DUAL LITE "CVD" SERIES,SURE-LITE "CX" SERIES

BRUSHEDSTAINLESS

WALL 90 MINUTE BATTERY.

XD DOUBLE FACE AREA OF REFUGE SIGN, DIE CASTALUMINUM, UNIVERSAL MOUNTING, GREEN LETTERS -DIRECTION OF ARROWS AS INDICATED

LED LITHONIA "LE" SERIES,BEGHELLI "LC1E" SERIES,DUAL LITE "CVD" SERIES,SURE-LITE "CX" SERIES

BRUSHEDSTAINLESS

CEILING 90 MINUTE BATTERY.

XEM 2 HEAD, WALL MOUNT EMERGENCY BATTERY WITHFIXTURE

LITHONIA "ELM" SERIES,CHLORIDE, SURELITE,DUALITE

WHITE WALL 90 MINUTE BATTERY.

LIGHT FIXTURE SCHEDULE NOTES:1 GENERAL: REFER TO LIGHTING PLANS FOR BALLAST VOLTAGES AND CONFIGURATION

OF FIXTURES. FIXTURES INDICATED TO BE DIMMED SHALL BE SUPPLIED WITHDIMMING BALLAST.

2 FIXTURES SHALL BE MOUNTED SUSPENDED OR SURFACE, GIVING RIGHT OF WAY TOHVAC DUCT WORK AND/OR EQUIPMENT.

3 PROVIDE BACKBOX ON ALL FIXTURES OF THIS TYPE SO THAT FIXTURES WITH ANDWITHOUT EMERGENCY BALLAST ARE AT THE SAME DEPTH.

4 GENERAL: COORINATE ALL MOUNTING OF FIXTURES (GRID/FLANGE) WITHARCHITECTURAL RCP.

5 FIXTURES SHALL BE SELECTED FROM THE FIXTURE SCHEDULE NOT ONLY BYCATALOG NUMBER BUT WITH CONSIDERATION TO MOUNTING, NUMBER AND TYPE OFLAMPS, AND REFERENCED NOTES. THE FIRST FIXTURE INDICATED FOR EACH TYPEWITH CATALOG NUMBER IS THE BASIS OF DESIGN FIXTURE, OTHER LISTEDMANUFACTURERS PRODUCING AN EQUAL FIXTURE TO THE BASIS OF DESIGNFIXTUREMAY BE PROVIDED.

6 THIS LIGHT FIXTURE IS TO BE SUPPLIED BY THE OWNER, INSTALLED BY THECONTRACTOR.

01

01

PE

RM

IT C

OM

ME

NT

S -

03/0

3/2

016

01

KP

AC

AC

AC

0'-0"

1'-6"

0'-0"

1'-6"

7'-0" A.F.F.

LANDING

UP

UP

UP

AC AC

AC

KP

AC AC

AC

AC

AC AC

AC

ACAC

0'-0"

1'-6"

0'-0"

1'-6"

7'-0" A.F.F.

LANDING

UP

UP

UP

ACAC

AC

AC

AC

AC

AC

AC

AC

AC AC

AC

KP

KP

AC

KP

20' A.F.F.

20' A.F.F.

INTRUSION ALARMCONTROL PANEL

MOUNT BOX FOR CAMERA UNDER CANOPY,ROUTE CONDUIT AND MOUNT BOXES SIMILARTO DETAIL 2/E2.0. (TYPICAL)

DISH WASH

1406

CAFETORIUM

1400

STOR.

1207

CHAIR STOR.

1401

BOYS TLT.

1424

IDF

1115

TLT.

1111.1

PRINC. CONF.

1113 JAN.

1203

TECH. PROCESS

1305

MEDIA SPEC

1304

MDF

1501

STOR.

1403.1

CONF. RM.

1102

CL

1104.1

CORR.

1104

GREEN ROOM

1403.2

PLATFORM

1403 RAMP

1402

CORR.

1420

LATE OFFICE

1106

STUDENT RECORDS

1105

OFFICE

1202

TLT

1300.1

TLT

1300.2

TLT.

1112

WORK ROOM

1110

TLT.

1114

CORR.

1200

PRINCIPAL

1111

BOY'S TLT.

1204

GIRL'S TLT.

1205

ENTRY HALL

1100

GYMNASIUM

1206

EQUIP. STOR.

1306

CORR.

1500

TEACHER PLANNING

1502

DINING LOUNGE

1502.1

GIRLS TLT.

1425

LEARNING LAB

1303

COMPUTER LAB

1307

PROD. / BROADCAST

1308

CORR.

1117

SERVERY

1404

DISH DROP

1405

EXTERIOR STORAGE

1423

MEDIA CTR.

1300

CORRIDOR

1500.1

RECEPTION

1103

OFFICE

1107

OFFICE

1108

OFFICE

1109

BATHROOM

1202.1

UTIL.

1201

WAITING

1101

JAN.

1414

OFFICE

1412

COOLER

1409

FREEZER

1410

TLT.

1417.1

LOCKER RM

1417

JAN.

1503

MENS

1502.2

SERVICE

1416

IDF

1415

TLT.

1421.1

KITCHEN RECIEVING

1411

CORR.

1413

WOMENS

1502.3

DRY STOR.

1408

KITCHEN

1407

RECEIVING

1418

STORAGE

1208

MECH.

1427

ELECT.

1426

STORAGE

1419

JAN. LOCKER RM.

1421

CUSTODIAL STAFF

1422

PROF. RESOURCEROOM

1301

CORRIDOR

1209

SEVERE & PROFOUND

1707

SEVERE & PROFOUND

1705

TOILET

1706.1

CHANGING/SHOWER

1706

TOILET

1706.2

TOILET

1704.1 MED. STORAGE

1703.3

SOLITARY

1703.2

TEACHER LOUNGE

1704

INFIRMARY

1703

TOILET

1703.4

NURSE

1703.1

THERAPY

1701

MECHANICAL

1702

I.T. CLOSET

1700.2

JAN.

1700.3

CORRIDOR

1700.1

SEVERE & PROFOUND

1710

TOILET

1709.1

CHANGING/SHOWER

1709

TOILET

1709.2

CORRIDOR

1700

SEVERE & PROFOUND

1708

PROVIDE ROUGH IN FOR CARD ACCESS DOOR, DOORPOSITION SWITCH AND REQUEST TO EXIT DEVICE.

PROVIDE ROUGH IN FOR ELECTRIFIED LATCH RETRACTION,DOOR POSITION SWITCH AND REQUEST TO EXIT DEVICE.

PROVIDE ROUGH IN FOR DOOR POSITION SWITCH, AND EXITDEVICE.

PROVIDE ROUGH IN FOR DOOR POSITION SWITCH, EXTERIORMECHANICAL KEY ENTRY.

1

2

3

4

(THIS SHEET ONLY)NOTES:

(THIS SHEET ONLY)GENERAL NOTES:VERIFY ALL REQUIREMENTS FOR ACCESS CONTROL ROUGH INPRIOR TO INSTALLATION. PROVIDE COMPLETE ROUGH IN AS REQUIRED.

1

3

3 3

1

33

1

3

1

11

4

1

22

1

1

1

1 3

3 3 3

T4.0

1TYP.

TLT.

1626.1

CORR.

1630.2

TLT.

1630.1 TLT.

1632.1

STORAGE

1604.4

TLT.

1605.1TLT.

1607.1

CORR.

1617.2

TLT.

1617.1

TLT.

1619.1

CORR.

1627.2

TLT.

1627.1TLT.

1629.1

CORR.

1633.2

TLT.

1633.1TLT.

1635.1

CORRIDOR

1605.2

CORRIDOR

1610.2

IDF

1600.12

CORR.

1620.2

TLT.

1620.1

TLT.

1622.1

TLT.

1654.1

COUNSELOR

1650.1STORAGE

1652

WAITING

1650

CONFERENCE

1650.2

STORAGE

1650.3

CLINIC

1654

MACHINE RM.

1602

TLT.

1623.2

TLT.

1623.1

MECH.

1634

MECH.

1631

MECH.

1628

ELECT.

1626

MECH.

1624

MECH.

1621MECH.

1618

1ST GRADECLASSROOM

1617

MECH.

1606

ELEV.

1600.4STAIR 1

1600.4

RESOURCE

1604.3

MECH.

1608

CORR.

1600.1

2ND GRADECLASSROOM

1609

1ST GRADECLASSROOM

1607

1ST GRADECLASSROOM

1605

CORR.

1600.5

PRE-K CLASSROOM

1635

KINDERGARTENCLASSROOM

1633

KINDERGARTENCLASSROOM

1632

KINDERGARTENCLASSROOM

1630

KINDERGARTENCLASSROOM

1629

KINDERGARTENCLASSROOM

1627

TEACH. WKRM.

1625

CORRIDOR

1600.2

CLASSROOM

1623

CLASSROOM

1622

CLASSROOM

1620

1ST GRADECLASSROOM

1619

2ND GRADECLASSROOM

1610

MECH

1611

TLT

1612.1

1ST GRADECLASSROOM

1612

TLT

1610.1

SPEECH

1604.2

EIP

1604.1HALLWAY

1604

MECH

1603

JAN

1651

MECH

1649

MECH

1645

STAIR 3

1600.8

PRE-K CLASSROOM

1636

TLT

1636.1 TLT

1638.1

CORRIDOR

1636.2

MECH

1637

PRE-K CLASSROOM

1638

1ST GRADECLASSROOM

1614

1ST GRADECLASSROOM

1616

TLT

1616.1

TLT

1614.1

CORRIDOR

1614.2

MECH

1615

TLT

1609.2

TLT

1609.1

CORR.

1640.2

TLT

1642.1 TLT.

1640.1

MECH.

1641

EXCEPTIONALSTUDENT CLASSROOM

1642

EXCEPTIONALSTUDENT CLASSROOM

1643

TLT

1643.2

ELEC

1600.11

MECH

1644

ART STOR.

1648.1

KILN

1648.2

ART CLASSROOM

1648

MUSIC STOR.

1646.1

MUSIC CLASSROOM

1646

SCIENCE CLASSROOM

1647

SHOWER

1642.2

EXCEPTIONALSTUDENT CLASSROOM

1640

STAIR 2

1600.7

BOOK STORAGE

1601

IDF

1600.10

ELEC

1600.09

SHOWER

1643.1

STORAGE

1653

J

COORDINATE EXACT CONDUITROUTING WITH ARCHITECT ANDCANOPY INSTALLER. PROVIDEUNDERGROUND CONDUIT TOCOLUMN AS REQUIRED.

1

4

12

MAIN ENTRANCE ACC.

KITCHEN ACC

GYM ACC

CAFETERIA ACC

PRIMARY STAFFENTRANCE ACC

DACS

T

PROFESSIONAL

NEERIG

NE

SIGERERED

No. 26308

IGROEG A

AW

R.LNE

RRA

W

1A 1B1C

KEYPLAN

DRAWING NUMBER

DRAWINGS MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION

ALL RIGHTS RESERVED

COPYRIGHT 2014

DATE:

DATE:

JOB NO.

SCALE:

DESIGNED DRAWN CHECKED

RE

VIS

ION

S:

5/9/2016 4:03:56 PM

1/16" = 1'-0"

JULI

ETTE

LO

W E

LEM

ENTA

RY

SCH

OO

L

15 B

lue

Rid

ge A

ve S

avan

nah,

GA

314

01

SAVA

NN

AH

CH

ATH

AM

CO

UN

TY P

UB

LIC

SC

HO

OL

SYST

EM

FIR

ST

FL

OO

R P

LA

N -

SE

CU

RIT

Y S

YS

TE

MS

T2.0

215 2001 07

GJC WALGJC

02/18/2016

CONFORMANCE SET

NORTH

SCALE: 1/16" = 1'-0"1

FIRST FLOOR PLAN - SECURITY SYSTEMS

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE

AR

EA

OF

RE

FU

GE DN

DN

DN

DN

DN DN

3RD GRADECLASSROOM

2608

3RD GRADECLASSROOM

2619

3RD GRADECLASSROOM

2620

3RD GRADECLASSROOM

2622

COUNSELOR

2624.5

4TH GRADECLASSROOM

2627

4TH GRADECLASSROOM

2629

4TH GRADECLASSROOM

2630

5TH GRADECLASSROOM

2632

5TH GRADECLASSROOM

2633

5TH GRADECLASSROOM

2635

CORR.

2617.2

TLT.

2617.1

TLT.

2619.1

CORR.

2627.2

TLT.

2627.1 TLT.

2629.1

CORR.

2630.2

TLT.

2630.1 TLT.

2632.1

CORR.

2633.2

TLT.

2633.1 TLT.

2635.1

CORR.

2620.2

TLT.

2620.1

TLT.

2622.1

MECH.

2634

MECH.

2631

MECH.

2628

STAIR 2

2600.7

MECH.

2621

MECH.

2618

TEACHER'SWORKROOM

2626

STOR.

2602

CORR.

2606.2

TLT.

2606.1

CORR.

2603.2

TLT.

2603.1

TLT.

2605.1

CORR.

2645.2

TLT.

2645.1

TLT.

2647.1

CORR.

2648.2

TLT.

2648.1

TLT.

2650.1

CORR.

2651.2

TLT.

2651.1

TLT.

2653.2

STAIR 3

2600.8

STAIR 1

2600.4

IDF

2600.13

MECH.

2652

MECH.

2649

MECH.

2646

MECH.

2607

MECH.

2604

STOR.

2641

2ND GRADECLASSROOM

2617

CORR.

2600.6

5TH GRADECLASSROOM

2645

5TH GRADECLASSROOM

2647

4TH GRADECLASSROOM

2648

4TH GRADECLASSROOM

2650

4TH GRADECLASSROOM

2651

3RD GRADECLASSROOM

2603

3RD GRADECLASSROOM

2605

3RD GRADECLASSROOM

2606

ELECT

2602.1

4TH GRADECLASSROOM

2653

TLT.

2626.1

SPEECH

2624.2

EIP

2623.1

MECH.

2623

ELEV.

1610.4

2ND GRADECLASSROOM

2614

TLT

2614.1

TLT

2616.1

CORRIDOR

2614.2

MECH

2615

2ND GRADECLASSROOM

2616

STOR.

2623.3

CONFERENCE

2624.4

CORR.

2624

TLT

2608.1

2ND GRADECLASSROOM

2611

2ND GRADECLASSROOM

2609

TLT

2611.1

TLT

2609.1

CORRIDOR

2609.2

MECH

2610

GIFTED CLASSROOM

2636

TLT

2636.1 TLT

2638.1

CORRIDOR

2636.2

MECH.

2637

GIFTED CLASSROOM

2638

5TH GRADECLASSROOM

2644

5TH GRADECLASSROOM

2642

TLT

2644.1TLT

2642.1

CORRIDOR

2642.2

MECH

2643

MECH

2602.2

ELECTRICAL

2600.12

IDF

2600.11

ELECTRICAL

2600.10

STAIR 2

2600.5

JAN.

2600.9

4

TO NEAREST 120 VOLT, 20 AMPUNSWITCHED RECEPTACLECIRCUIT

MOTOR RATEDSWITCH

3#12, 1 / 2 IN. C

INTERIOR VIEW

1 1

22

3

1/2" C. 1/2" C.

5 5

THIS DRAWING IS INTENDED TO INDICATE CONDUIT INFRASTRUCTUREREQUIREMENT ONLY. COORDINATE EXACT REQUIRED COMPONENTSWITH ARCHITECTURAL DOOR SPECIFICATIONS. PROVIDE ALL CONDUITAND BOXES FOR COMPLETE ACCESS CONTROL INSTALLATION.

3#12, 1/2"C.(FLEXIBLECONDUIT)

NOTES:1

2

4

(ACCESS CONTROL CONNECTIONS)

DOOR POSITION SWITCH.

CURRENT TRANSFER HINGE

POWER SUPPLY.

CARD READER.

DELAYED EGRESS SYSTEM - NORMALLY CLOSED FIRE ALARMRELAY REQUIRED, PLUGNPLAY. NORMALLY CLOSED FIRE ALARMRELAY REQUIRED FOR THE DELAYED EGRESS APPLICATION.

3

5

TO MDF/IDF

PROVIDE 12 CONDUCTOR20 GAUGE WIRE WITH THEFOLLOWING COLORS: BLACK,RED, WHITE, GREEN, ORANGE,BLUE, BROWN, YELLOW, PINK,GRAY, TAN AND VIOLET.

T

PROFESSIONAL

NEERIG

NE

SIGERERED

No. 26308

IGROEG A

AW

R.LNE

RRA

W

2A 2B2C

KEYPLAN

DRAWING NUMBER

DRAWINGS MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION

ALL RIGHTS RESERVED

COPYRIGHT 2014

DATE:

DATE:

JOB NO.

SCALE:

DESIGNED DRAWN CHECKED

RE

VIS

ION

S:

5/9/2016 4:03:58 PM

As indicated

JULI

ETTE

LO

W E

LEM

ENTA

RY

SCH

OO

L

15 B

lue

Rid

ge A

ve S

avan

nah,

GA

314

01

SAVA

NN

AH

CH

ATH

AM

CO

UN

TY P

UB

LIC

SC

HO

OL

SYST

EM

SE

CO

ND

FL

OO

R P

LA

N -

SE

CU

RIT

Y S

YS

TE

MS

T2.1

215 2001 07

GJC WALGJC

02/18/2016

CONFORMANCE SET

NORTH

SCALE: 1/16" = 1'-0"1

SECOND FLOOR PLAN - SECURITY SYSTEMS

NOT TO SCALE2

ACCESS CONTROL DOOR DETAIL

LOADING DOCK

OVERHEAD COILING

INTERIOR, WALL

MOUNTED COIL

1101B

14

120VAC INPUT POWER

1" CONDUIT

14

120VAC INPUT POWER

1" CONDUIT

14

120VAC INPUT POWER

1" CONDUIT

14

14

14

120VAC INPUT POWER

1" CONDUIT

14

120VAC INPUT POWER

1414

120VAC INPUT POWER

1/2" CONDUIT 14

14

120VAC INPUT POWER

1" CONDUIT

14

120VAC INPUT POWER

1" CONDUIT

660-PBPUSH BUTTON

LOCATED AS DIRECTED

IN RECEPTION 1101.1

1/2" CONDUIT

2

14

1" CONDUIT

120VAC INPUT POWER

4

DOOR BELL, COORDINATE LOCATION WITH

THE ARCHITECT. LOCATE BELL AS

DIRECTED.

RUN TO DOOR BELL LOCATION

OR DOOR BELL CONTROLLER 4

OVERHEARD DOOR CONTACT

FLOOR MOUNTED ELECTRICAL JUNCTION BOX

2 2

GENERAL NOTES:

1. COORDINATE CABLING WITH SECTION 087100. EXTEND ALL PREWIRED CABLES IN HOLLOW

METAL FRAMES, INCLUDING CONDUIT, TO THE JUNCTION BOX LOCATIONS SHOWN. DO

NOT CUT ANY EXCESS CABLING. SIMPLY COIL IT AND TIE WRAP TO JUNCTION BOX FOR

TERMINATION BY OTHERS.

2.

3.

4.

5.

14

PS PS PS

PSPS

PS PS

PS

PS

J J J

JJ

J J

J

J

J

J

POWER SUPPLY TYPICAL REFER TO 087100

6"x6" JUNCTION BOX TYPICAL

2

1/2" CONDUIT

J

ELECTRICAL CONTRACTOR RESPONSIBLE FOR ALL 120VAC CONNECTIONS TO THE

POWER SUPPLIES.

ELECTRICAL CONTRACTOR SHALL PROVIDE DOOR BELL, PATHWAYS, AND CABLING WHERE

INDICATED. COORDINATE THE LOCATION AND REQUIREMENTS WITH THE ARCHITECT.

ELECTRICAL CONTRACTOR SHALL PROVIDE FOR THE PATHWAYS AND CABLING AT THE

OVERHEARD DOOR. THE OVERHEAD DOOR SWITCH SHALL BE PROVIDED UNDER

SECTION 087100 BUT INSTALLED BY CONTRACTOR.

ELECTRICAL CONTRACTOR SHALL PROVIDE THE PATHWAYS, CABLING, AND MOUNTING

FOR THE 660-PB PUSH BUTTON LOCATED IN RECEPTION 1101.1. COORDINATE THE

LOCATION OF THE PUSH BUTTON WITH THE ARCHITECT AND RELATED TRADES.

1" CONDUIT

1/2" CONDUIT

1" CONDUIT

1/2" CONDUIT

1/2" CONDUIT

1/2" CONDUIT

1/2" CONDUIT

1/2" CONDUIT

1/2" CONDUIT1/2" CONDUIT1/2" CONDUIT

SEE ARCHITECTURAL FLOOR PLAN SHEETS FOR ALL DOOR NUMBERS.6.

T

PROFESSIONAL

NEERIG

NE

SIGERERED

No. 26308

IGROEG A

AW

R.LNE

RRA

W

DRAWING NUMBER

DRAWINGS MAY NOT BE REPRODUCED IN ANY FORM WITHOUT WRITTEN PERMISSION

ALL RIGHTS RESERVED

COPYRIGHT 2014

DATE:

DATE:

JOB NO.

SCALE:

DESIGNED DRAWN CHECKED

RE

VIS

ION

S:

5/9/2016 4:04:09 PM

1/2" = 1'-0"

JULI

ETTE

LO

W E

LEM

ENTA

RY

SCH

OO

L

15 B

lue

Rid

ge A

ve S

avan

nah,

GA

314

01

SAVA

NN

AH

CH

ATH

AM

CO

UN

TY P

UB

LIC

SC

HO

OL

SYST

EM

AC

CE

SS

CO

NT

RO

L D

ET

AIL

S

T4.0

215 2001 07

GJC WALGJC

02/18/2016

CONFORMANCE SET

NOT TO SCALE1

ACCESS CONTROL DETAILS