目录 8 in 1 sensor ◆ 8 in 1 sensor unique features ● built in pir motion sensor and light...
DESCRIPTION
1.Input key target Qty 3.Select IR code from database 2.Select key no. 4.Downlaod 5.Confirm IR Code downloadTRANSCRIPT
目录8 in 1 Sensor
◆8 in 1 SensorUnique Features
●Built in PIR motion sensor and light intensity sensor●Built in 2 Dry Input Ports●Built in 32 Logics●Infrared receiver●Infrared transmitter●Built in security alarm logic (work with Security Module)
Subnet ID and Device ID
Remark
MAC Address
Basic information
1.Input key target Qty
3.Select IR code from database
2.Select key no.
4.Downlaod
5.Confirm
IR Code download
6.Select key no.
7. Select key stroke type
IR Code testing 8. Press Transmit and test
IR Code receiving
1.Configuration same as switch panel, first select key no. of remoter
2.Setup the mode for the key
3.Select key control mode
4.Save
IR Code receiving
5.Select control target
IR Code receiving
6.Input target Subnet ID, Device ID and Parameter
7. Save
IR Code receiving
IR Code receiving
8. Align the Remoter with 8 in 1 sensor, press the key and test
1. Select a Logic Block (Max 32 blocks)
2.Input Remark and charge the status to Valid, default is invalid
3. Save
4.Click Edit to setup menu
Automation logics configuration
Automation logics configuration
Current statusSelect logic condition Select logics
relation
Command
Application
In case of a meeting room has below requirements:
1.When people open the door and come in the meeting room, the lights open automatically2. After people come in the room for more than 1 minute, open the AC and change the temperature to 25℃3. After people leave the room for 1 minute, off the lights and the temperature increase 2℃4.After people leave the room for 3 minute,turn off the AC automaticallyWe need 4 logic blocks to accomplish the requirements above
1.When people open the door and come in the meeting room, the lights open automatically
Requirements
2. Input remark and change current status to Valid
3.Save
4.Edit Logic setting
1.Select a Logic block
Requirement: When people open the door and come in the meeting room, the lights open automatically
5.If the door installed a magnetic contact and connect to 8 in 1 sensor, change condition to disconnect
6. Select Motion sensor and Condition movement
7. Change delay time to 0 sec.
8.Select relation And
9.Save logic setting
10.Click Command to select control target
11. Input light channel to open
12.Save
Requirement: When people open the door and come in the meeting room, the lights open automatically
2. After people come in the room for more than 1 minute, open the AC and change the temperature to 25℃
Requirements
Requirement: After people come in the room for more than 1 minute, open the AC and change the temperature to 25℃
2. Input remark and change current status to Valid
3.Save
4.Edit Logic setting
1.Select a Logic block
5.If the door installed a magnetic contact and connect to 8 in 1 sensor, change condition to disconnect
6. Select Motion sensor and Condition movement
7. Change delay time to 1 minutes
8.Select relation And
9.Save logic setting
10.Click Command to select control target
Requirement: After people come in the room for more than 1 minute, open the AC and change the temperature to 25℃
12.Input target with the subnet ID and device ID of the sensor. Type “Infrared remote sensor", parameter 1 “3”, parameter 2 “on”
13.SaveRequirement: After people come in the room for more than 1 minute, open the AC and change the temperature to 25℃
11.Before set the control target, please go to IR transmitter page and record the key no.(3) of 25℃
3. After people leave the room for 1 minute, off the lights and the temperature increase 2℃
Requirements
2. Input remark and change current status to Valid
3.Save
4.Edit Logic setting
1.Select a Logic block
Requirement: After people leave the room for 1 minute, off the lights and the temperature increase 2℃
Requirement: After people leave the room for 1 minute, off the lights and the temperature increase 2℃
5.Select Motion sensor and Condition No movement
6.Change delay time to 1 minutes
7.Select either AND or OR because there’s only one logic condition
8.Save logic setting
9.Click Command to select control target
10.Input target with the subnet ID and device ID of the sensor. Type “Infrared remote sensor", parameter 1 “5”, parameter 2 “on”
11.Save Requirement: After people leave the room for 1 minute, off the lights and the temperature increase 2℃
4.After people leave the room for 3 minute, turn off the AC automatically
Requirements
2. Input remark and change current status to Valid
3.Save
4.Edit Logic setting
1.Select a Logic block
Requirement: After people leave the room for 3 minute, turn off the AC automatically
5.Select Motion sensor and Condition No movement
6.Change delay time to 3 minutes
7.Select either AND or OR because there’s only one logic condition
8.Save logic setting
9.Click Command to select control target
Requirement: After people leave the room for 3 minute, turn off the AC automatically
10.Input control target
11. SaveRequirement: After people leave the room for 3 minute, turn off the AC automatically
Complete