    HARIPUR COMBINED CYCLE POWER PLANTEPC ENGINEERING DOCUMENT REVIEW FORM

    WORK REQUEST NO: 1172

    REVIEW FORM FOR EPC DOCUMENT: STATUS:

    Transmittal No.: HN/EG D 2783 Approved:

    Drawing Title: LOCAL PANEL INTERNAL ARRANGEMENT DIAGRAM FOR AIR COMPRESSOR PACKAGE Approved with Comment:Drawing No:: MC-CA-I-16-K002 Rev B Disapproved:

    Information

    X

    EPC Contractor is requested to respond to Comments/Recommendations identified below by:

    No. Consultants Comments / RecommendationEPC Contractor Response

    ResolutionStatus

    1 Item 82, Square Light should be simply Annunciator Lamps It has applied as per consultants comment. Accepted,24-1-13

    2 Proposed system uses analogue 0 to 10 V signals, which is in defiance

    of ITB section 14.11.4, Transmitters, which demands all analoguesignals be 4 to 20 mA. Voltage signals are notoriously unreliable andprone to drift due to resistance changes in installed wiring andtermination.

    Second round comment 24-1-13,It is the EPCs responsibility to inform suppliers of the relevant parts ofthe construction specification for this project that must be reflected inthe equipment supplied by the supplier. 4 to 20 mA analogue loopsignals, as opposed to voltage signals, are specified for soundengineering reasons based on common sense and years of fieldexperience to give proven stable performance that are vastly superior

    to analogue voltage signals. If the compressor controls manufacturerhad been advised of this requirement at the time of letting the contractwith him and also when this error was identified by the consultant, thencurrent based analogue signals would have been incorporated for nosignificant difference in price. There is now a non-standard, nonconforming control system on the site that could have been correctedby the contractor six months ago, but due to the EPCs arrogance anddereliction of duty by deliberately not responding to the consultantscomments pointing out this non-conformance for over six months, hasallowed this system to arrive on site where it will now become a non-conformance issue to be rectified before commissioning.Whether the suppliers specification has been applied in other jobs is

    Manufacture standard specification use 0 to 10V signals

    by control processor package. 4~20mA signal type cantbe applied separately.This manufacturers own specification has been applied& accepted for their reference projects (Oman, Saudi

    Arabia, Brazil, Malaysia, etc)

    Page 1

  • 7/29/2019 0-10v Air Compressor

    2/2

    HARIPUR COMBINED CYCLE POWER PLANTEPC ENGINEERING DOCUMENT REVIEW FORM

    entirely irrelevant to this project. The specification is written for thepurpose of ensuring the correct, conforming, equipment is delivered tothe owner and operator of the plant.

    3

    4

    Commented by: Brooke MackleyDate: 15-08-12, second round rejection 14-1-13

    Responded by : K.C.Seo/ J.N.ParkDate: 16/01/13

    Comment reviewed by:Date:

    For PGCB:Date:

    For REB:Date

    For EGCB:Date:

    NOTES:1. EPC Contractor shall provide his response within fourteen (14) days from the date he receives this form.2. The comments provided in this transmittal shall not relieve the Contractor of any of its obligations to meet all the requirements of

    the Contract or relieve the Contractor of the responsibility for the correctness of his drawings/documents. The Contractor shallmake any changes that are necessary to make the work confirm to the provisions and intent of the Contract.

    3. Contractor to ensure that procurement of all equipment / components meets the requirements of the contract.

    Page 2