0004-2287_v05_tps msc
DESCRIPTION
Vestas TurbineTRANSCRIPT
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
QM
S 0
0010 V
ER
01
CLASS 1
TECHNICAL PURCHASE SPECIFICATION
DOCUMENT:
0004-2287 V05 DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank Solutions
Technical Purchase Specification for Generic MSC Bank Solutions
VESTAS PROPRIETARY NOTICE: This document contains valuable confidential information of Vestas Wind Systems A/S. It is protected by copyright law as an unpublished work. Vestas reserves all patent, copyright, trade secret, and other proprietary rights to it. The information in this document may not be used, reproduced, or disclosed except if and to the extent rights are expressly granted by Vestas in writing and subject to applicable conditions. Vestas disclaims all warranties except as expressly granted by written agreement and is not responsible for unauthorized uses, for which it may pursue legal remedies against responsible parties.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
2/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
Version History VERSION:
DATE CHANGE:
03 18.05.11 Updated communication requirements with the
PPC (section 4.1.1.11).
04 26.05.11 Updated template and contents.
05 15.03.12 New corporate address, change to Class 1.
Table of Contents
CHAPTER: DESCRIPTION: PAGE:
1. Introduction 3 1.1 Purpose 3 1.2 Copyright Notice 3 1.3 Disclaimer 3 1.4 Product Described by the Purchase Specification 4 1.5 Function of the Product 5 2. Scope of Supply 6 3. Technical Requirements 8 3.1 Product Requirements 8 3.1.1 General Requirements 8 3.1.2 Interface Requirements 14 3.1.3 Calculation of Structural and Electrical Integrity 14 3.1.4 Material Requirements 15 3.1.5 Health and Safety Requirements 15 3.1.6 Operation Environment 15 3.2 Reference Requirements 16 3.2.1 Reference to Standards 16 3.2.2 Reference to Other Vestas Documents 17 3.3 Traceability Requirements 17 4. Quality Assurance Requirements 18 4.1 Tests to be Carried Out by Supplier 18 4.1.1 Terminology 18 4.1.2 General Requirements 19 4.1.3 Notification of Tests 20 4.1.4 Factory Acceptance Test (FAT) 20 4.1.5 Site Acceptance Test (SAT) 21 4.1.6 Performance Verification Test (PVT) 22 5. Delivery Requirements 25 5.1 Transport and Delivery Requirements 25 5.2 Packing and Storage Requirements 25 5.3 Lifting and Transport Tool Requirements 26 6. Documentation Requirements 27 6.1 Documentation to be Filed by the Supplier 27 6.2 Documentation to be Forwarded to Vestas 27 6.2.1 Design Documents 27 6.2.2 Scope of Documentation 28 6.2.3 Declaration of Conformity 29 7. Definitions 30
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
3/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
1. Introduction
1.1 Purpose
The document is to be used by Vestas (Vestas Wind Systems A/S and its
subsidiaries) as a basis for purchase of Mechanically Switched Capacitors (MSC) for
wind power plants based on Vestas wind turbines. Furthermore, Vestas may decide
to make the document available to third parties intending to purchase MSC for wind
power plants based on Vestas wind turbines.
The document will describe various overall design concept possibilities and
interfaces. The final concept must be decided at a case-by-case approach and will
depend on the specific project.
1.2 Copyright Notice
The document is created by Vestas Wind Systems A/S and contains copyrighted
material, trademarks, and other proprietary information. All rights reserved. You may
not alter or remove any trademark, copyright or other notice from the document.
Unless Vestas’ prior written consent is obtained the documents may only be used as
follows:
a) The document is for your internal use only and may be copied and used by
you only to the extent necessary to fulfil the Purpose. Copies of the
documents may only be distributed or disclosed to and used by your
designated advisors in accordance with the purpose stated below.
b) Vestas’ copyright notice or, where indicated, the notice of confidentiality
must appear in all electronic or hard copies of any documents as well as in
all extracts from the documents and due accreditation must be given to
Vestas in all extracts.
c) Except as expressly permitted by Vestas, you may not in any way modify or
alter the document.
Any rights not expressly granted in these terms or otherwise are reserved by Vestas.
1.3 Disclaimer
In drafting the document, Vestas has used its best practice experience and
knowledge in the field. Notwithstanding the foregoing, Vestas does not assume any
responsibilities for the content of the document nor for the results of using the
document. Specifically it shall be noted that the document should not be relied on as
a final technical specification of MSC fitting all wind power plants based on Vestas
wind turbines and that detailed MSC specifications for each individual wind power
plant application always must be carried out in connection with the final electrical
design of the wind power plant. This disclaimer applies to the document in its
entirety.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
4/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
1.4 Product Described by the Purchase Specification
This technical purchase specification (TPS) describes the MSC installation on the
medium voltage (MV – collecting system voltage level) of a wind power plant (WPP),
as shown in Figure 1.
G
G
G
G
G
G
Connecting Grid:
Typically 110 kV
Cable or overhead line
or a combination
Wind Power Plant:
Typically 50 MW
Mechanically Switched
Shunt Capacitor
Installation
Shunt Capacitor Banks:
In total about 18 Mvar
Wind Power Turbine:
Typically 2 MW
Substation:
Indoor or outdoor
WPP Radials
Collection Grid:
Typically 33 kV
Figure 1 - Single line diagrams of the WPP substation layouts.
The MSC installation is split into a number of similar MSC banks. These banks can
be equally or differently sized. In the shown diagram, a total capacity of 18 MVAr has
been decided. Each capacitor bank comprises disconnector, switching device, short
circuit current interruption device, current limiting reactor, shunt capacitor (a number
of units in an assembly), surge arrester, protection, and control.
The MV grid where the capacitor is connected is a uni-grounded system using either
impedance or earthing reactor.
Main design issues related to the operation of the MSC bank are size, layout, filter,
switching sequences and control strategies, and discharge time. Important
constraints with respect to protection and abnormal conditions are the earthing
system, surge arrestor dimensioning, network interaction and resonance
phenomena, traditional equipment protection, as well as internal and external fuse
protection.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
5/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
1.5 Function of the Product
The MSC installation on the WPP MV level is to be used to support the system with
reactive power. The MSC installation comprises a number of similarly designed
capacitor banks, which are to be controlled individually to supply an appropriate
amount of reactive power according to a predefined control criterion. This control
criterion is based on the voltage, reactive power, or power factor at a predefined
point in the power system. Capacitors are expected to be switched in and out up to
15 times per day. The installation must withstand all reasonable electrical and
mechanical conditions to which it may be exposed in its vicinity.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
6/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
2. Scope of Supply
The Supplier must deliver a complete, properly designed, and sized MSC
installation, including adequate control and protection systems, suitable for its
purpose for the specific WPP installation (according to the functioning of the MSC
installation as described in section 1.5).
Figure 2 shows a schematic drawing of the components included in the scope of
supply. Note that each WPP installation is unique, with respect to the connecting grid
conditions, concerning pure technical conditions such as short circuit capacity and
harmonic levels, and concerning administrative grid code requirements such as
reactive power supply capability, voltage controllability, and communication.
Disconnector
-Optional
Circuit
breaker
Contactor
-Optional
Current
limiting
Reactor
Surge
arrestor
-Optional
Current
transformer
Capacitor
Unit
Assembly
Mounting assembly, earth switch, etc.
Protection
MV Bus
Voltage
transformer
Control
Communication
Communication
Figure 2 – Components included in scope of supply.
A single line diagram for the two possible connections of the capacitor banks is
shown in Figure 3 and Figure 4. A contactor-based MSC installation is shown in
Figure 3.
VT
Shunt Capacitor
Installation
3-6 Shunt Capacitor Banks:
6+6+6 Mvar
3+3+3+3+3+3 Mvar
6+6+3+3 Mvar
Shunt Capacitor Bank:
CT
Vacuum Contactor
Disconnector
Current limiting device
Surge arrestor
Capacitor
Vacuum Contactor
Circuit Breaker
Disconnector
Figure 3 – A contactor-based MSC installation.
The contactor is used for the normal switching of each bank. The circuit breaker is
used for fault clearance. The circuit breaker is common for the entire installation.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
7/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
A single line diagram for a circuit breaker-based installation is shown in Figure 4.
VT
Shunt Capacitor
Installation
3-6 Shunt Capacitor Banks:
6+6+6 Mvar
3+3+3+3+3+3 Mvar
6+6+3+3 Mvar
Shunt Capacitor Bank:
CT
Circuit Breaker
Disconnector
Current limiting device
Surge arrestor
Capacitor
Circuit Breaker
Figure 4 – A circuit breaker-based MSC installation.
For this kind of installation, a circuit breaker for each MSC bank is used for normal
switching and fault clearance.
The MSC bank is connected to the busbar via a disconnector and a circuit breaker.
The disconnector function can be integrated in the circuit breaker function. The
circuit breaker must have the capability to interrupt all possible short circuit currents
without restriking. The circuit breaker must use synchronised point-on-switching in
and out. The capacitor bank bays in the substation will be of the same manufacture
as in the rest of the substation, but with additional control units for the capacitor
bank.
The current limiting device is most likely a reactor chosen in such a way that the risk
for resonances with the connecting grid is small. The surge arrestor between the
capacitor and the current limiting device should be dimensioned to protect the
capacitor by handling all possible switching overvoltages. Lightning overvoltages
should be handled by surge arrestors on the high voltage side of the substation step-
up transformer.
The bus-connected voltage transformer (VT) and current transformer (CT) in the
capacitor bay should provide the control and protection system with relevant
measurements.
The discharging resistors are to be integrated in the capacitor elements. The
discharging resistors should be chosen in such a way that the capacitor voltage
reaches harmless levels after about 5 minutes.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
8/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
3. Technical Requirements
3.1 Product Requirements
3.1.1 General Requirements
3.1.1.1 Shunt Capacitor Design
The MSC design must be in compliance with IEC 60871, Shunt capacitors for a.c. power systems having a rated voltage above 1000 V.
Capacitors must not give less than rated reactive power at rated sinusoidal voltage
and frequency, and not more than 110% of this value, measured at 25˚C uniform
case temperatures.
Figure 5 shows the three-phase layout of the capacitor in a single capacitor bank.
The shunt capacitor comprises a number of parallel- and series-connected capacitor
elements. For each phase (L1, L2, and L3, respectively), the capacitor elements are
connected in two balanced groups to two separate neutrals (N1 and N2). The two
neutrals are normally connected to each other. The connection could comprise a CT
to detect unbalances between the two balanced groups of each phase. It is also
possible to measure the voltage between the neutrals and earth to indicate
unbalance or to measure the current in the connection to earth, if the neutrals are
low-impedance earthed. The different methods to identify unbalances are also
shown in Figure 5.
L1 L2 L3
N1
N2
N1
N2
N1
N2
N1
N2
Figure 5 – Shunt capacitor design and methods for unbalance detection.
It is the Suppliers’ responsibility to choose the design.
The capacitor banks must be able to operate at 3% negative sequence voltage.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
9/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
3.1.1.2 Shunt Capacitor Earthing System
Shunt capacitor earthing must be ungrounded wye-connected banks.
3.1.1.3 Inrush Current Limiting Reactor
Each capacitor bank must be equipped with an inrush current limiting reactor.
3.1.1.4 Shunt Capacitor Discharging
The discharge resistor must be designed so the discharge time must be a maximum
of 5 minutes with a residual voltage of 50 V.
As an option, the discharge resistor must be designed so the discharge time must be
a maximum of 10 seconds with a residual voltage of 50 V. This requirement can be
requested in connection with using the capacitor banks in connection with voltage
control.
3.1.1.5 Shunt Capacitor Dielectric
The Supplier must state the use of capacitor dielectric materials – solid and/or fluent.
Flame point and precautions in case of leakage and decommissioning of materials
must be stated in the offer.
3.1.1.6 Insulators
The insulator lengths must be in accordance with IEC 60815.
3.1.1.7 Shunt Earthing
It must be possible to ground the capacitor bank via a solid earthing switch located
directly between the disconnector and the capacitor bank. The earthing switch must
be according to IEC 62271.
3.1.1.8 Connection
The capacitor bank is connected via a switching device directly to the MV busbar.
There can be a number of capacitor banks in parallel connected to the same busbar.
3.1.1.9 Switching Devices
Switching devices for the MSC can be:
Power circuit breaker, designed to interrupt fault currents
Load switch, designed to interrupt load currents
Other switchgear in the substation gives the type for the circuit breaker and loads switch. Requirements for switching devices are given in section 3.1.1.19 and 3.1.1.20.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
10/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
3.1.1.10 Instrumentation and Communication
The instrumentation comprises indications and measurements for protection, control,
and condition monitoring. Indications should be available, locally as well as at the
WPP control place, for each MSC bank disconnector position and circuit-breaker
position.
Measurements must be available for the MV busbar voltage, and the current from
each MSC bank. These measurements should normally be presented as:
The busbar phase-phase voltage in kV
The reactive power output from the MSC bank in MVAr
Indications from protection relays must be available at a remote WPP control center
via SCADA, as well as the possibility to download disturbance recordings from the
capacitor bank protection, either via Ethernet or manually in the substation.
3.1.1.11 Control System
The control principles for the WPP with MSC are mainly voltage control, reactive
power control, or power factor.
During the WWP operation, the control system for the capacitor banks (located in the Power Plant Controller [PPC]) will send the command for connecting / disconnecting the capacitor steps with a sufficient built-in hysteresis to avoid repetitive switching.
If the PPC controls the switching of the capacitors to obtain optimal control performance, the execution of the issued commands must take place without unnecessary delays. This means that when a command for connecting / disconnecting is issued from the PPC to the capacitor breaker or switch, it must be implemented in less than 250 ms, including intermediate control communication devices (e.g., the R.T.U. or other PLC) and relay delays. Note that the discharging time is not included in the 250 ms.
Additionally, in order for the PPC to use fed-forward control strategies, the feedback status of the MSC (ON/OFF) must reach the PPC with a maximum delay of 90 ms from the moment that the status of the MSC is changed to a new status.
The number of control signals needed in the PPC is shown in Figure 6.
Number of Send / Received data / PPC<-
>Capacitors
Com /protocol
Depending of number of Steps (N): 9 signals x N
Modbus TCP/IP fibre
Figure 6 - Number of control signals needed in the PCC.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
11/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
The PPC uses Modbus signals to communicate with the capacitor steps. The signals are defined as follows in Figure 7.
Figure 7 – Signal definitions.
The capacitors use synchronised point-on-wave switching.
The MSC bank relay system must have the following properties:
The ability to switch in manually (thus blocked by the discharging time) and out each capacitor bank (in manual or automatic mode)
Selectable operational mode: local or remote
Overvoltage protection
Overcurrent protection
Phase-phase unbalance protection
The switchgear will either be three single poles or a three-pole switch with a built-in mechanical delay.
The time for point-on-wave switching must be adjustable.
Note: Selection of switchgear will be dependent on the other equipment installed in the substation. Requirements will be according to this section, and sections 3.1.1.19 and 3.1.1.20.
Signal Description Signal to ‘0’ Signal to ‘1’ Signal to ‘2’ Read/Write
1 Switch position Open Close Indeterminate Read
2 Disconnector in
grounding position Close Open Indeterminate Read
3 Breaker position Open Close Indeterminate Read
4 Temporary
operation block Blocked Free - Read
5 Permanent
operation block Blocked Free - Read
6
Failure for
opening and
closing command
Failure for
opening No failure
Failure for
closing Read
7 Discharging time in
process Activated Finalised - Read
8 Automatic Manual position Automatic position - Read
9 Command to the
step switch Open Close - Write
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
12/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
3.1.1.12 Shunt Capacitor Bank Protection
The mechanically switched capacitor bank must be satisfactorily protected from
abnormal conditions in the network such as overvoltages, harmonics, resonance,
etc. It must also be protected from internal faults, such as earth-faults and short-
circuits to ensure that the MSC is disconnected and any damage is limited. Normally
sufficient protection is achieved by the N-1 criterion, which states that the protection
scheme must be able to fulfill the fault clearance even if one component in the fault-
clearance chain is out of service.
Table 1 shows the events that are of interest from a protection point of view:
Event Protection
External arcing
Protected by surge arrestors on the grid side
of the WPP main transformer
Bank overcurrent
Overcurrent protection, measured on each
MSC bank current
Internal bank current imbalance
Imbalance current measured between each
of the bank neutrals
Loss of bus voltage
Loss of voltage indication, measured on the
busbar
System overvoltage
Overvoltage protection, measured on the
busbar
Loss of VT fuse
A high degree of zero sequence (or negative
sequence) voltage but no zero sequence (or
negative sequence) current. This function is
most important when impedance or
undervoltage protection is used.
Breaker failure protection
Breaker failure protection has to be applied
to all fault current interrupting devices that
lacks other kinds of backup protection for
breaker failure.
Surge arrestor protection
The surge arrestor connected between the
capacitor and the current limiting device has
to protect the shunt capacitor against
overvoltages due to network switchings.
Table 1 – Fault events and protection
Note: Selection of relays will be dependent on the other equipment installed in the substation and requirements will be according to this.
3.1.1.13 Surge Arrestor Protection
Surge arrestors will be placed on the capacitor side of the switch.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
13/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
3.1.1.14 Enclosure and Installation
The capacitor bank must be an outdoor installation.
Note: Selection of switchgear will be dependent on the other equipment installed in the substation. Requirements will be according to this section and sections 3.1.1.19 and 3.1.1.20.
3.1.1.15 Marking of Components
Each capacitor bank and unit must be marked with a visible and unique name plate
showing the information specified in IEC 60871-1.
3.1.1.16 Rated Voltage
The rated voltage area for the capacitor to operate in steady-state is within 0.9 –
1.1 pu. of rated voltage.
3.1.1.17 Shunt Capacitor Bank Maintenance
Maintenance and field measurements must be possible to schedule while the bank is
still on site. It must be possible to remove the capacitor to fulfill maintenance, change
components, and make measurements on site.
Maintenance recommendations must be supplied by Supplier.
3.1.1.18 Current and Voltage Transformer
Type and individual requirements for CT and VT will normally be decided by the
switchgear in the substation.
Class for measurement transformers:
CT must be class 1.0 (IEC 60044-1)
VT must be class 1.0 (IEC 60044-2)
3.1.1.19 Circuit Breaker
Pre- and restrike-free circuit breakers are to be used. Switching can be made as single-pole switching or three-pole switching with a mechanical delay.
If a mechanical delay is used, two poles must switch simultaneously and the last pole with a predefined delay. The circuit breaker is to be prepared for this.
If a setup with load switches after the circuit breaker is used, see Figure 3; synchronised switching of the circuit breaker is not necessary.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
14/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
3.1.1.20 Load Switch
Restrike-free load switches with a controlled energising (so called point-on-wave switching) is to be used; the switching pattern is as for circuit breakers.
Disconnection in case of faults will be made by a circuit breaker in front of the load switch. See Figure 3.
3.1.2 Interface Requirements
Electrical main data for the system in which the capacitor bank is to be placed will be
a combination of the data shown below:
Nominal frequency 50 or 60 Hz
Nominal voltage level 10, 20, or 30 kV
Highest operating voltage 12, 24, or 36 kV
Nominal voltage level 1 min. 50-60 Hz voltage 1.2/50µs impulse voltage
10 kV 28 kV 86 kV
20 kV 50 kV 125 kV
30 kV 70 kV 170 kV
Table 2 - Electrical main data for the connecting system
Short circuit level and X/R-ratio: ISCmax at MV busbar: 30 kA (Um=36 kV)
X/R-ratio: 1.7-10.0
3.1.3 Calculation of Structural and Electrical Integrity
When a candidate shunt capacitor installation design is made according to the
requirements in this TPS, its properties with respect to switching transients have to
be verified. An electromagnetic transient programme like PSCAD/EMTDC is
recommended for the verification. The transient overvoltages at the most critical
points of the WPP have to be observed for the most critical switchings, with respect
to energisation and back-to-back switching, for the most unfavorable operational
conditions. If the candidate design does not pass the verification test, it must be
redesigned and tested again until it passes. See Figure 8.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
15/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
Start
Continue
Switching overvoltage
study to find potential
overvoltages at the WPP
Maximum
overvoltages
= Vmax
Vmax<VdMaximum acceptable overvoltages =
Vd
YES
Return to the current
limiting reactor design
and continue the process
NO
Stop
The design is OK
Current limiting
reactor design for
each bank
Figure 8 - Switching overvoltage study to verify that the switching overvoltages are within acceptable
limits.
The verification study must be reported and forwarded to Vestas for approval of the
final design.
3.1.4 Material Requirements
Materials used in the manufacturing of the complete capacitor bank unit must be of
high quality, suitable for their purpose, and capable of meeting the performance
(including temperature range) and reliability requirements of this document.
3.1.5 Health and Safety Requirements
The delivery of the complete capacitor bank unit must fulfill all necessary
international and national requirements related to health and safety requirements for
design, installation, maintenance, and operation. All components and services to
fulfill this are included in the scope of work.
3.1.6 Operation Environment
3.1.6.1 Operating Ambient Temperature
The ambient temperature for continuous operation of the capacitor units must be
allowed to range between -40 and +50C°, without de-rating of the exchanged
reactive power. The -40 and +50C° must be seen as the minimum performance
required; higher positive or lower negative temperatures are regarded as premium.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
16/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
3.1.6.2 Humidity
The capacitor unit must be able to operate under an atmospheric humidity ranging
between 0% and 100% condensing, including rain and snow.
3.1.6.3 Altitude
The capacitor unit must be able to operate up to 1500 metres above sea level
without de-rating of the continuous reactive power.
The altitude at which the capacitor unit will start reducing its reactive power capability must be clearly specified by the Supplier, together with the de-rating profile as a function of altitude.
3.2 Reference Requirements
3.2.1 Reference to Standards
Because the capacitor unit will be installed worldwide, the Supplier is responsible for
compliance with the standard and guidelines for the region in question. In the
following table, the different standards and guidelines for the different regions are
listed. For regions not mentioned in the list, the capacitor unit must comply with IEC
standards.
Standard Description
IEC 60871 Shunt capacitors for a.c. power systems having a rated voltage
above 1000 V.
IEC 61642 Industrial a.c. networks affected by harmonics – application of filters
and shunt capacitors.
IEC 62271 High-voltage switchgear and controlgear – Part 110: Inductive load
switching.
IEC 60815 Guide for the selection of insulators in respect of polluted conditions.
IEC 60044-1 Instrument transformer – CT.
IEC 60044-2 Instrument transformer – induction VT.
IEEE Std
1036-1992.
IEEE Guide for Application of Shunt Power Capacitor.
IEEE Std
18-2002
IEEE Standard for Shunt Power Capacitors.
Table 3 – Standards and guidelines.
The following description is referring to the relevant IEC standard. According to
Table 3, these standards must be substituted with the applicable standards
depending on site location; e.g., ANSI/IEEE for North America or AS for Australia.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
17/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
3.2.2 Reference to Other Vestas Documents
Table 4 defines other Vestas documents that are mandatory to comply with in
connection with delivery according to this TPS.
ID Subject Requirement References and
comments
4.3.4.1 Vestas Chemical and
Material Blacklist
Available from
www.vestas.com
Table 4 – Other Vestas documents.
3.3 Traceability Requirements
The Supplier must maintain a list for all components included in the complete
capacitor bank unit showing manufacturing data and date.
When asked, this list must be sent to Vestas. The list must cover a period for a
minimum of 10 years. The manufacturing date must be traceable with the serial
number.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
18/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
4. Quality Assurance Requirements
All design and process changes that influence the function, performance, safety,
reliability, robustness, or lifetime of a component or parts hereof must be approved
by Vestas Wind Systems A/S prior to starting redesign.
Design changes must be verified using appropriate calculation and testing methods,
and based on all relevant technical experiences.
All design changes that affect type approvals must be approved by the relevant Type
Approval Bodies prior to starting redesign.
The product must comply with all relevant EU- and international directives. Vestas
wants to cooperate only with Suppliers who continuously prove their ability to meet
Vestas’ requirements. The condition for meeting requirements:
A documented and approved quality system according to ISO 9000/QS 9000/TS 16949 or similar standard together with a successful Supplier approval
A quality activity plan accepted by Vestas for the unit in question
An inspection agreement with Vestas
Continuous deliveries, meeting Vestas’ requirements
A successful part approval (Vestas’ sample test or PPAP)
Quality assurance and inspection must be done by the Supplier, with the result that
non-acceptable units are discarded before delivery to Vestas.
Such collaboration implies an inspection agreement between managers of quality
assurance at Supplier and Vestas.
4.1 Tests to be Carried Out by Supplier
4.1.1 Terminology
FAT: Factory Acceptance Test, which contains type tests and
routine tests to improve quality and performance.
SAT: Site Acceptance Test, which includes commissioning. The
SAT is a routine test to be performed at every
commissioning to improve quality and performance.
PVT: Performance Verification Test, which demonstrates that the
required range of operation can be met, and demonstrates
compliance with grid codes. It can be included in the FAT
and/or SAT.
Type test: This test is not project-specific. It includes design
verification. Normally, the type test is a large part of the FAT.
Routine test: This test is specific to the project and needs to be performed
at each deliverable. It is a part of the FAT.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
19/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
4.1.2 General Requirements
1. Testing must be performed in accordance with the applicable standards in Section 3.2.1 and any additional requirements in this TPS. If the requirements of this specification conflict with any of the above standards or practices, this specification must apply. Where standards are not suitable or applicable, other common industry procedures and mutually acceptable methods must be used.
2. The Supplier may refer to type tests performed in the past. The Supplier must enclose with the bid a list of tests clearly stating the type and routine tests that will be performed for this project. The Supplier must also state the tests where a report from a previously performed test must be considered in lieu of performing new tests.
3. The results obtained from tests must demonstrate that the equipment
conforms to the requirements of this specification.
4. The results obtained from tests must be compiled and organised in writing. All test results must contain the appropriate signature of the Supplier.
5. Vestas reserves the right for itself and/or its representatives to be present and witness all tests. Vestas may require that tests be repeated in the presence of its representatives if the Supplier neglects to provide notification as presented below. If Vestas or its representatives do not attend a test to which proper notification has been given, Vestas has waived the right to witness the test.
6. The Supplier must furnish all labour, materials, instrumentation, recording, and testing facilities for all tests in this specification.
7. If any piece of equipment provided as a part of the capacitor unit system does not pass a test or is damaged, the Supplier must replace or repair the failed or damaged equipment and, if necessary, modify the equipment design. The Supplier must repeat the tests previously done on any equipment that is replaced, repaired, or modified. All expenses for the material, re-installation, and re-testing will be the responsibility of the Supplier.
8. At all times, the Supplier must obtain permission from Vestas to perform field verification tests when the capacitor unit is connected to the power system. These tests may have to be performed during night or low load periods. If transmission system conditions prevent the Supplier from performing field tests, this fact must not delay other contractual activities and obligations, neither of Vestas nor of the Supplier.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
20/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
4.1.3 Notification of Tests
The Supplier must give Vestas notice of type and routine tests three weeks before
the actual testing date.
Inspection and test plans must be submitted to Vestas 30 days prior to
commencement of the test.
The Supplier must furnish a detailed Inspection and Test Plan for the commissioning
and field verification 2 months before the beginning of the testing.
4.1.4 Factory Acceptance Test (FAT)
The Supplier must perform a full-scale FAT. Prior to delivery, the capacitor unit
should be tested at the factory with possible participation of Vestas and the end
user.
Notification of the FAT must be sent to Vestas a minimum of 3 weeks prior to the
start of the test.
The FAT must include, but is not limited to, the following:
Check mechanical state and earthing connection of all cubicles
Check satisfactory equipment labelling
Check that all wiring within cubicles matches drawings, and all cores are clearly identified
Perform insulation resistance tests on all secondary wiring
Perform magnetisation tests on all CTs, and check polarity
Perform primary injection tests on CT to relay terminals, to check ratios, and correct connections
Perform secondary injection tests
Perform functional tests
Perform a test with random change of setpoints in all control modes
Perform a test with random change in feedback process values in all control modes
Check calibrations of all measurement transducers and meters
Demonstrate communication between capacitor unit and SCADA
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
21/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
4.1.5 Site Acceptance Test (SAT)
4.1.5.1 Cold Tests
The cold tests are performed on site with a fully assembled capacitor unit, without
connecting the capacitor unit to the power system. The SAT must include, but is not
limited to, the following:
Check insulation of auxiliary cables Verify operation of capacitor unit auxiliary power distribution Test relay protections and protective control functions (by secondary injection) Test control and monitoring system Check operation and indications of circuit breakers, disconnect, and earthing switches
Check capacitance and tan δ of capacitor banks
Check CTs and VTs
Check overall trip operations from protections to breaker
Check circuits through interface.
4.1.5.2 Heat Tests
Upon satisfactory completion of the cold tests, energising of the capacitor unit
system and a function test must be performed. These tests are performed on site
with the fully assembled capacitor system with the equipment connected to the
power system and in operation. The tests must include, but are not limited to, the
following items:
Measure and verify the capacitor system operation at nominal power system properties
Verify start, stop, and trip sequences
Verify current and voltage waveforms during in-rush and during high voltage / medium voltage (HV/MV) breaker trips
Verify change of reference point and slope setting
Verify manual control mode function
Verify the dynamic response of the voltage / reactive power (V/Q) regulator, and the gain supervision/optimisation functions
Measure harmonic voltage on the Point of Common Coupling (PCC) of the WPP
Measure audible noise
Measure temperature rise at maximum available load
Check supplementary control functions
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
22/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
4.1.6 Performance Verification Test (PVT)
The PVT must demonstrate that the specified functional properties can be met in the
entire operating range, under all conditions. It is the responsibility of the Supplier to
perform and document the PVT. To the extent possible, the PVT must be conducted
in the factory, on the complete and assembled capacitor unit, subject to conditions
as close to the project-specific conditions as possible. All performance verification
tests should be conducted at worst-case combinations of minimum and maximum:
ambient temperatures
continuous frequencies
line voltages
short-circuit ratios
X/R ratios
These tests include, but are not limited to, the following (described in subsections
4.1.6.1 through 4.1.6.3):
Steady-State Properties – Limits of Operation
Robustness
Dynamic Properties of the Capacitor Controller
4.1.6.1 Steady-State Properties – Limits of Operation
In reactive power control, in power factor control, and in voltage control, the following
must be demonstrated:
Operation at maximum capacitive current. Results of interest are harmonic levels and temperature rise.
Operation as 1, with one module out of service (N-1 operation).
Operation as 1, with 3% negative sequence line voltage.
4.1.6.2 Robustness
To test robustness of the capacitor unit, the following must be demonstrated:
Loss of sensor signal. Record response to removal of a CT or VT.
Loss of auxiliary supply: Record response to removal of power supply.
Response to failure in 1 of N units.
Trip of capacitor unit MV breaker in all three control modes.
Trip of WPP HV breaker in all three control modes.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
23/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
4.1.6.3 Dynamic Properties of the Capacitor Controller
The next requirements shall be considered only if the WPP control is implemented
outside the PPC supplied by Vestas.
Reactive power control
Large-signal properties. Response to change in reactive power setpoint from maximum inductive to maximum capacitive current, and reverse.
Small-signal properties. Response to 5% change in reactive power setpoint.
Disturbance rejection. Response to change in turbine reactive power load (possibly to be conducted on site).
Disturbance rejection. Response to change in turbine active power load (possibly to be conducted on site).
Disturbance rejection. Response to step in main transformer on-load tap-changer position (possibly to be conducted on site).
Transition between linear and limited operation. Response to steps in reactive power setpoint.
Power factor control
Large-signal properties. Response to change in power factor setpoint from maximum underexcited to maximum overexcited, and reverse.
Small-signal properties. Response to 0.01 pu change in power factor setpoint.
Disturbance rejection. Response to change in turbine reactive power load (possibly to be conducted on site).
Disturbance rejection. Response to change in turbine active power load (possibly to be conducted on site).
Disturbance rejection. Response to step in main transformer on-load tap-changer position (possibly to be conducted on site).
Transition between linear and limited operation. Response to steps in power factor setpoint.
Voltage control
Large-signal properties. Response to change in voltage setpoint from minimum to maximum, and reverse.
Small-signal properties. Response to 0.01 pu change in voltage setpoint.
Disturbance rejection. Response to symmetrical 3-phase fault causing a drop in line voltage positive-sequence level of 5%, and subsequent fault clearance.
Disturbance rejection. Response to 2-phase fault causing a drop in line voltage positive-sequence level of 5%, and subsequent fault clearance.
Disturbance rejection. Response to 1-phase fault causing a drop in line voltage positive-sequence level of 5%, and subsequent fault clearance.
Disturbance rejection. Response to step in main transformer on-load tap-changer position (possibly to be conducted on site).
Transition between linear and limited operation. Response to steps in reactive power setpoint.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
24/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
Fault ride-through
Response to 3-phase, 2-phase, and 1-phase faults causing a drop in line voltage positive-sequence level to between 0% and 90% remaining voltage, and subsequent fault clearance.
Response to 3-phase overvoltage beyond 110%.
The durations of the faults and the requirements to capacitor unit reactive output during faults will be specified in the project-specific data sheet.
Response to repetitive fault sequences. To be specified in the project-specific data sheet.
In addition to the above, special tests demonstrating grid code compliance may be
required and/or imposed by the grid owner. This will be stated in the project-specific
data sheet.
4.1.6.4 Comments
The Supplier must perform tests at factory and participate on site test. Routine tests
and type test must be performed at factory before the FAT.
For the first capacitor unit, both routine tests and type tests must be performed and
for the remaining capacitor units, only routine tests must be performed.
The test programme and procedures must be developed by the Supplier to ensure
that the commissioning of the equipment and the interconnection to the power
system:
do not adversely affect the security of the transmission/distribution network or the quality of supply.
minimise any possible threat of damage to other plant, equipment, and Vestas installations connected to the transmission/distribution network.
Test programme and procedures must be sent to Vestas a minimum of 3 months
prior to the start of test for approval. All tests must be listed in the bid.
Documentation of the tests must be submitted to Vestas for approval no later then 2
weeks after testing.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
25/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
5. Delivery Requirements
5.1 Transport and Delivery Requirements
The complete capacitor bank unit must be capable of full performance after being
exposed to ground handling and transportation by truck, train, ship, or airplane.
If the delivery of the product does not meet the specified demands, and the product
is damaged during transport, Vestas will bring out a deviation report to be fulfilled
according to the instructions.
If components are missing, the Supplier is obligated to deliver the components to
Vestas as soon as possible.
For transport where Vestas buys Ex Works (EXW), Free on Board (FOB), or Free
Carrier (FCA), the entire responsibility is located at Vestas.
A delivery is considered received when the last unit for the whole delivery, including
required documentation, is received at Vestas.
A delivery is accepted when Vestas has received documentation that the Supplier’s
outgoing inspection has approved the delivery.
However, Vestas has the full right to reject units and demand replacement if
defective units later are found (which can be traced back to lack of fulfilment of the
requirements defined in this document).
The transportation and storage temperature must fit the operating ambient
temperature specified in Section 3.1.6, for a total period of time of no longer than
3 months.
Equipment must be mounted with a G-meter during transport to register unwanted
vertical and horizontal movements during transport.
5.2 Packing and Storage Requirements
The Supplier has the responsibility of properly securing the product during transport
to the means of transportation.
The complete capacitor bank unit must be packed and supported in a way so that
the possibility of damaging any component is absolutely minimal. This includes, in
particular, damage to surface treatments.
Item no. and P no. must be indicated on the package, including on the packing list.
Furthermore, the complete capacitor bank unit must be packed so that the
permanently and temporary markings are visible when the box is opened.
Loose components must be packed in a way to prevent the possibility of scratching
or damaging other components in the delivery.
The complete capacitor bank unit must also be packed in a way so that the risk of oil
spill is absolutely minimal.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
26/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
The packing of the complete capacitor bank unit must ensure protection of untreated
surfaces from corrosion.
The complete capacitor bank unit must be capable of meeting the requirements of
this specification after long-term storage, which is defined as a minimum of 8 months
of normal shelf storage (air humidity [RF] < 50%) under the original packaging
conditions.
5.3 Lifting and Transport Tool Requirements
All necessary lifting and transport provisions are included in the scope of delivery.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
27/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
6. Documentation Requirements
6.1 Documentation to be Filed by the Supplier
The Supplier is requested to file all necessary documentation to comply with
declaration of conformity according to Section 6.2.3.
6.2 Documentation to be Forwarded to Vestas
6.2.1 Design Documents
All documentation must be in the English language.
Design must be based on the International System of Units (SI) and engineering
codes and standards as listed in Section 3.2.1.
All equipment, components, and permanent structures must be designed and
manufactured according to applicable local and international codes.
Designs, drawings, specifications, and supporting documents must be of a quality
and completeness consistent with electrical industry standards.
Coding and marking of equipment and documentation is subject to agreement with
Vestas.
Item number and name must identify each piece of equipment indicated on
diagrams.
The requested documentation is a part of the complete delivery.
Any deviations or changes from data in this TPS – or from data previously presented
and accepted – must be specifically mentioned by the Supplier. Information and data
not specifically mentioned and accepted/signed by Vestas must not be considered.
Vestas must be allowed 10 working days for review and commenting on documents
submitted for approval and acceptance.
Prior to Taking Over Certificate (TOC), the Supplier must submit five printed copies
and one CD with electronic copies of all specifications and drawings to Vestas as
listed below, revised to be ‘As Built’.
Maintenance and troubleshooting must include step-by-step instructions on specific
activities, unique to the equipment, as a part of the maintenance plan and/or
troubleshooting manual.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
28/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
6.2.2 Scope of Documentation
All data and documentation must be collected in electronic form on a CD. The CD
must contain, but is not limited to, the following documentation as .pdfs and drawings
as .dxfs. The documentation listed below must be arranged in the following four
groups on the CD:
Manuals
Drawings
Specifications
Test reports and certificate
Manuals
Operation manual
Installation manual
Service and Installation manual
Drawings
Panel outline drawings
Single line diagrams
Power circuit diagrams
Control circuit diagrams
Terminal connection diagrams
Cable list
Specifications
Component description (Main specifications)
Characteristic data (Detail specifications)
Component data sheets
Parts list
Spare part list
Supplier’s brochures
Test Reports and Certificates
Test specifications
Type test reports and certificates according to section 4.1
Type test certificate for conformity with IEC 60439-1
Test certificates for alarm and protection equipment
Routine test reports and certificates
SAT reports and certificates
PVT reports and certificates
Declaration of conformity
Documentation on manufacturing quality levels
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
29/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
6.2.3 Declaration of Conformity
The supplier shall provide Vestas with an EC Declaration of Conformity for the
product with reference to valid directive(s) and include all supporting test reports to
demonstrate compliance to the applicable directives.
CLASS 1
DOCUMENT:
0004-2287 V05
DESCRIPTION:
Technical Purchase Specification for Generic Mechanically Switched Capacitor (MSC) Bank
Solutions
PAGE
30/30
Copyright © - Vestas Wind Systems A/S, Hedeager 44, 8200 Aarhus N, Denmark, www.vestas.com
7. Definitions
Back-to-back switching Switching a capacitor bank with and in close electric proximity to one or more other capacitor banks.
BIL Basic Impulse Level, which is the level of lightning strike the equipment can withstand.
Capacitor The word ‘capacitor’ is used when it is not necessary to specify the meaning between installation, bank, unit, or element.
Capacitor bank An assembly at one location of capacitors and all necessary accessories, such as switching equipment, protective equipment, controls, etc., required for a complete operating installation. It may be a collection of components assembled at the operating site or may include one or more piece(s) of factory-assembled equipment.
Capacitor element A device consisting essentially of two electrodes separated by a dielectric.
Capacitor installation One or more capacitor banks and their accessories.
Capacitor unit An assembly of dielectric and electrodes in a container (case), with terminals brought out, that is intended to introduce capacitance into an electric power circuit.
CT Current Transformer
EMC Electromagnetic compatibility
MSC Mechanically Switched Capacitor
MV Medium Voltage
PCC Point of Common Coupling
PF Power factor
PPC Power Plant Controller
TPS Technical Purchase Specification
VT Voltage Transformer
WPP Wind Power Plant
WTG Wind Turbine