    Automated Overhead

    Schneider ElectricReclosers & Sectionalisers

    Loop Automation

    Classic & Intelligent

    2014

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    2/31

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    3/31

    3

    REVIEW

    Reclosing & Sectionalising

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    4/31

    4

    Definition

    Reclosing used to quickly

    restore power and limit outages

    for transient(self-clearing) faults

    Sectionalising

    used toisolate sections of the network

    for permanentfaults

    Up to 70% of faults

    are transient

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    5/31

    5

    Comparison

    Recloser Sectionaliser

    Protection Detection

    Multiple trips Single Trip

    Fault Breaker NOT Fault BreakerTransient Fault Permanent Fault

    ADVC Controller / RTU

    Measure Current & VoltageProgrammable Relay

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    6/31

    6

    N-Series ACR U-Series ACR

    W-Series ACR RL-Series LBS

    Switchgear Range

    Range 15kV to 38kV

    SF6insulation

    Integrated CT/CVT

    Vacuum Interrupters

    316 Stainless Steel

    Range 15kV to 27kV

    Solid Dielectric

    Integrated CT/CVT

    Vacuum Interrupters

    316 Stainless Steel

    24kV Single Phase

    Solid DielectricIntegrated CT/CVT

    Vacuum Interrupter

    316 Stainless Steel

    Range 15kV to 38kV

    SF6insulationIntegrated CT/CVT

    Puffer Interrupters

    316 Stainless Steel

    Common control cabinet for all switchgearADVC

    10,000 mechanical operations

    3-phase

    3-phase

    3-phase

    single-phase

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    7/317

    Controller Cubicles

    304 stainless steel

    Compact option

    1 Accessory Tray2-point locking

    316 stainless steel

    2 Accessory Trays

    Optional 12Ah batteries

    3-point locking

    Cubicle height 960mm

    Cubicle width 450mmCubicle depth 302mm

    Cubicle height 730mm

    Cubicle width 420mm

    Cubicle depth 302mm

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    8/318

    Operator Interfaces

    4-line display

    Menu-driven4 Quick Action keys

    Auto On / Off

    20 status lamps

    12 Quick Action keys

    Fully configurable

    Auto On / Off

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    9/319

    Protection & Detection

    Element

    Protection

    RECLOSER

    Detection

    SECTIONALISER

    Phase Overcurrent YES YES

    Earth Fault YES YES

    Sensitive Earth Fault YES YES

    Negative Phase Sequence YES YESInrush Restraint YES YES

    Cold Load Pickup YES YES

    High Current Lockout YES X

    Under/Over Voltage YES X

    Loss of Phase YES X

    Under/Over Frequency YES X

    Index

    http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=j9Gfrps9481pjM&tbnid=5A9A-uC5yGCNLM:&ved=0CAUQjRw&url=http://www.bbc.co.uk/bitesize/standard/physics/using_electricity/resistance/revision/1/&ei=2cM7U4z1COaAiQfFhIFg&bvm=bv.63934634,d.aWc&psig=AFQjCNGMED_tLiAa5A5ipfhj6M0cr_pRQA&ust=1396512031851734http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=j9Gfrps9481pjM&tbnid=5A9A-uC5yGCNLM:&ved=0CAUQjRw&url=http://www.bbc.co.uk/bitesize/standard/physics/using_electricity/resistance/revision/1/&ei=2cM7U4z1COaAiQfFhIFg&bvm=bv.63934634,d.aWc&psig=AFQjCNGMED_tLiAa5A5ipfhj6M0cr_pRQA&ust=1396512031851734http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=j9Gfrps9481pjM&tbnid=5A9A-uC5yGCNLM:&ved=0CAUQjRw&url=http://www.bbc.co.uk/bitesize/standard/physics/using_electricity/resistance/revision/1/&ei=2cM7U4z1COaAiQfFhIFg&bvm=bv.63934634,d.aWc&psig=AFQjCNGMED_tLiAa5A5ipfhj6M0cr_pRQA&ust=1396512031851734http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=j9Gfrps9481pjM&tbnid=5A9A-uC5yGCNLM:&ved=0CAUQjRw&url=http://www.bbc.co.uk/bitesize/standard/physics/using_electricity/resistance/revision/1/&ei=2cM7U4z1COaAiQfFhIFg&bvm=bv.63934634,d.aWc&psig=AFQjCNGMED_tLiAa5A5ipfhj6M0cr_pRQA&ust=1396512031851734http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=j9Gfrps9481pjM&tbnid=5A9A-uC5yGCNLM:&ved=0CAUQjRw&url=http://www.bbc.co.uk/bitesize/standard/physics/using_electricity/resistance/revision/1/&ei=2cM7U4z1COaAiQfFhIFg&bvm=bv.63934634,d.aWc&psig=AFQjCNGMED_tLiAa5A5ipfhj6M0cr_pRQA&ust=1396512031851734http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=j9Gfrps9481pjM&tbnid=5A9A-uC5yGCNLM:&ved=0CAUQjRw&url=http://www.bbc.co.uk/bitesize/standard/physics/using_electricity/resistance/revision/1/&ei=2cM7U4z1COaAiQfFhIFg&bvm=bv.63934634,d.aWc&psig=AFQjCNGMED_tLiAa5A5ipfhj6M0cr_pRQA&ust=1396512031851734http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=j9Gfrps9481pjM&tbnid=5A9A-uC5yGCNLM:&ved=0CAUQjRw&url=http://www.bbc.co.uk/bitesize/standard/physics/using_electricity/resistance/revision/1/&ei=2cM7U4z1COaAiQfFhIFg&bvm=bv.63934634,d.aWc&psig=AFQjCNGMED_tLiAa5A5ipfhj6M0cr_pRQA&ust=1396512031851734http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=sshh5qBkc7oB8M&tbnid=NkebrcK-uJbWwM:&ved=0CAUQjRw&url=http://www.clipartbest.com/generator-symbols&ei=AMI7U6DAIIeViQfS1IC4Cg&bvm=bv.63934634,d.aWc&psig=AFQjCNG15dSI0UoG0VbO7996_WUHAk9wfg&ust=1396511603760704http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=sshh5qBkc7oB8M&tbnid=NkebrcK-uJbWwM:&ved=0CAUQjRw&url=http://www.clipartbest.com/generator-symbols&ei=AMI7U6DAIIeViQfS1IC4Cg&bvm=bv.63934634,d.aWc&psig=AFQjCNG15dSI0UoG0VbO7996_WUHAk9wfg&ust=1396511603760704http://www.google.com.au/url?sa=i&rct=j&q=&esrc=s&frm=1&source=images&cd=&cad=rja&uact=8&docid=sshh5qBkc7oB8M&tbnid=NkebrcK-uJbWwM:&ved=0CAUQjRw&url=http://www.clipartbest.com/generator-symbols&ei=AMI7U6DAIIeViQfS1IC4Cg&bvm=bv.63934634,d.aWc&psig=AFQjCNG15dSI0UoG0VbO7996_WUHAk9wfg&ust=1396511603760704
  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    10/3110

    DNP3balanced (both master and slave can initiate communications)

    IEC 60870-5-101/4

    can operate as balanced or unbalancedMODBUSunbalanced (only master can initiate communications)

    MITS unbalanced

    Communications & SCADA

    PortLabel PortType Comment

    RS232 Port A/B RS-232 No handshaking support

    RS232 Port C/D RS-232 Handshaking supported

    10Base-T Ethernet Simultaneous SCADA & WSOS5

    V23 V23 FSK UHF radio communications

    RS485 RS485 Long distance or multi-drop

    USB USB Local WSOS5 only

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    11/3111

    Wave 1- Classic Loop Automation -

    Quick Win Solution

    Reliable (No Comms)

    Easy to test and Install

    Embedded in the reclosers

    offer at no extra cost

    Customers on the healthy

    circuit can see somedisruption

    Relies on grading multiple

    reclosers which may not

    always be achievable

    >Simple logic scheme basedsolely on loss of voltage

    Wave 2 (2013)- Intelligent Loop Automation -

    Quick Win Solution

    Reliable (single comms)

    Easy to test and InstallEmbedded in the reclosers

    offer at no extra cost

    >Same Logic + Singledownstream message between

    devices to open the down

    stream device to prevent

    closing on to fault (using

    Modbus TCP/IP)

    + Sectionaliser

    + P2P communication

    Quick Win Solution

    Further intelligence

    Easy to test and InstallEmbedded in the reclosers

    offer at no extra cost

    >Enhanced logic calculatingreceiving circuit load to

    prevent overloading of

    alternate source

    Wave 3 (Q2 2014)- Intelligent Loop Automation -

    + Overload Control

    >Enhanced logic supportingconnection to multiple ties

    Wave 4 (Q4 2014)- Intelligent Loop Automation -

    + Multiple Tie

    More complex loops (3

    sources2 ties)

    Reliable (low communications

    requirements)

    Easy to test and install

    Embedded in the reclosers

    offer at no extra cost

    Q2 2014

    Loop Automation4 types

    2013

    INTELLIGENT+OVERLOAD 3 INTELLIGENT+MULTI-TIE 4INTELLIGENT 2CLASSIC 1

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    12/31

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    13/31

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    14/31

    14

    1 Yellow

    2 Blue

    HV / MVSubstation

    5 Pink

    3 Green

    6 Aqua

    NormalOpen Point4 Red

    RR

    R

    RRCB

    FAULT

    1 Y

    2 B

    3 G

    4 R

    5 P

    6 A

    TTL

    1 Y

    1

    2 B

    2

    3 G

    2

    4 R

    3

    5 P

    3

    6 A

    4

    Outages for each line segment

    Customers on the main line are

    protected from branch faults

    Total Segment Outages

    15

    Typical Feeder: reclosers on branches

    Index

    Outage total based on 1 permanent

    fault for each feeder segment

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    15/31

    15

    HV / MV

    Substation

    Normal

    Open Point3 Green1 Yellow

    2 Blue

    5 Pink

    6 Aqua

    4 RedRemote ControlledOr Automated

    CB RR

    R

    RR

    FAULT

    1 Y

    2 B

    3 G

    4 R

    5 P

    6 A

    TTL

    1 Y

    1

    2 B

    2

    3 G

    1

    4 R

    2

    5 P

    1

    6 A

    2

    Outages for each line segment

    Automation / SCADA allows

    supply from alternate source

    Total Segment Outages

    9

    Typical Feeder: automated reclosers

    Index

    Outage total based on 1 permanent

    fault for each feeder segment

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    16/31

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    17/31

    17

    CLASSIC LOOP AUTOMATIONNo communications requiredAvailable for Reclosers & Sectionalisers

    Loop Automation CLASSIC 1Wave 1

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    18/31

    18

    Features & Benefits

    Features Details MessagesAutomatic supply

    from alternate

    source

    When active & configured,

    unfaulted sections are quickly

    re-energised

    No communications

    Benefits

    1. No communications required

    2. No operator intervention

    3. Included in the offer at no cost

    4. Fast restoration of unfaulted sections

    5. SAIDI and SAIFI statistics improved

    CLASSIC 1Wave 1

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    19/31

    19

    Elements & Rules

    Element Type Position Status NormallyFeeder ACR Closest to substation Required Closed

    Midpoint ACR Between Feeder & Tie Optional Closed

    Tie ACR/LBS Between Feeder lines Required Open

    Feeder

    Midpoint

    Tie

    Rule Element Action Conditionswhen ...

    A (1) Feeder Opens (Lockout) Supply is lost

    B (2) Midpoint Changes Protection Group* Supply is lost

    (2) Midpoint Changes to Single Shot Supply is lostC (3) Tie Closes Supply is lost on 1 side

    (4) Midpoint Opens (Single Shot -Lockout) Fault Detected

    Feeder

    Midpoint

    Tie

    Midpoint

    Midpoint

    * From A to Bdirection changed

    CLASSIC 1Wave 1

    # Loop Auto turned off when

    LA actions completed

    #

    #

    #

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    20/31

    20

    Substation CBs

    10km15km

    10km

    7.5km

    Midpoint 4

    Midpoint 3

    2D

    Feeder 2

    2B

    10km

    2A

    1A

    Midpoint 27.5km

    1D

    1B

    7.5km

    1C

    5km

    B

    2C

    Classic Loop Automation with Timer-Controlled Tie

    Fault between substation CB and Feeder device

    Picks up, tripsfrom

    protection & goes to lockout.

    The feeder device tripsand goes to

    lockout.

    Midpoint 1

    Loop Automation Activation Delay

    timers start due to a loss of supply.

    Midpoint devices change protection groupin anticipation

    of the change in the direction of the power flow and go toSingle Shot(no auto-reclose) mode.

    The tie device also changes protection group depending

    on which side the power was lost (source or load), goes to

    Single Shot (no auto-reclose) mode and closes .

    B+SS

    Feeder 1

    Tie

    Fault isolated

    Power restored to unfaulted sections in less than 1 minute

    No operator intervention

    ClosedTripped

    Switchgear

    LiveDead

    Line

    B+SS

    B

    Classic CLASSIC 1Wave 1

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    21/31

    21

    INTELLIGENT LOOP AUTOMATIONPeer to peer IP communicationsDownstream messaging TRIP / CLOSE / CLOSE BLOCK

    Loop Automation INTELLIGENT 2Wave 2

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    22/31

    22

    Features & Benefits

    New Feature Details MessagesPeer to peer

    MODBUS over IP

    communications

    Tie can be Timer or

    Message controlled

    Each switch can

    message the adjacent

    downstream device or

    the tie

    FEED to MID = TRIP

    MID to MID = TRIP

    FEED TO TIE = CLOSE or

    CLOSE BLOCK

    MID TO TIE = CLOSE or

    CLOSE BLOCK

    Additional Benefits

    1. Reduced grading requirements2. Closing alternate supply onto fault

    prevented, avoiding possible upstream trip

    if elements are misgraded

    INTELLIGENT 2Wave 2

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    23/31

    23

    Substation CBs

    10km15km

    10km

    7.5km

    Midpoint 4

    Midpoint 3

    2D

    Feeder 2

    2B

    10km

    2A

    1A

    Midpoint 27.5km

    1D

    1B

    7.5km

    Feeder 1

    2C

    1C

    5km

    B

    Intelligent Loop Auto with Comms-Controlled Tie

    Fault between Feeder and Midpoint devices

    Loop Automation Activation Delay

    timers start due to a loss of supply.

    The downstream device changes protection

    group in anticipation of the change in the

    direction of the power flow, goes to SingleShot (no auto-reclose) mode and trips.

    The tie device also changes protection group

    depending on which side the power was lost (source or

    load), goes to Single Shot (no auto-reclose) mode and

    closes upon receiving a close request.

    Picks up, executes trip/reclose sequence & goes

    to lockout. It will then send a trip request to its

    downstream device using Modbus P2P

    communications.

    Fault isolated

    Power restored to unfaulted sections in less than 1 minute

    No operator intervention

    Alternate source prevented from Closing onto fault

    ClosedTripped

    Switchgear

    LiveDead

    Line

    Modbus Trip Request

    Other midpoint devices change protection group and

    go to Single Shot (no auto-reclose) mode.

    Tie

    Modbus Close Request

    Midpoint 1

    B+SS

    BB+SS

    INTELLIGENT 2Wave 2Intelligent

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    24/31

    24

    INTELLIGENT LOOP AUTOMATIONPeer to peer IP communications

    Downstream messaging TRIP / CLOSE / CLOSE BLOCK

    Loop Automation INTELLIGENT+OVERLOAD 3Wave 3

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    25/31

    25

    Features & Benefits

    NewFeature

    Details Messages

    Overload

    Control

    All elements regularly advise

    phase currents to tietie will

    only close after fault if the

    unfaulted alternate source hassufficient overhead

    Loop Auto OLC ON =

    send settings to TIE

    PING message =

    3 phase currents to TIE

    Additional Benefits

    1. Tie will only close onto unfaulted network ifsufficient overhead exists to prevent

    overload

    INTELLIGENT 3Wave 3

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    26/31

    26

    OLC messaging INTELLIGENT 3Wave 3

    Ping messages from all elements to TIE

    Midpoint

    Tie

    Sources

    Closed

    Open

    Switchgear State

    Feeder

    Feeder

    >3 phase currents

    Device settings> > TIE closes only when availableOVERHEAD exceeds faulted LOAD

    During Loop Automation, TIE uses received data to

    calculate LOAD & OVERHEAD

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    27/31

    27

    INTELLIGENT LOOP AUTOMATIONPeer to peer IP communications

    Downstream messaging TRIP / CLOSE / CLOSE BLOCKOverload control available

    Loop Automation INTELLIGENT+MULTI-TIE 4Wave 4

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    28/31

    28

    Features & Benefits

    New Feature Details MessagesMulti-tie support

    Additional logic to support

    interconnected networks:

    up to 3 sources / 2 ties

    TBA

    Additional Benefits

    1. More complex networks can be supported

    Wave 4 INTELLIGENT+MULTI-TIE 4

    Index

  • 8/10/2019 007d Schneider Electric Reclosers Loop Automation Classic Intelligent 1 . 1.pptx

    29/31

    29

    Creation Configuration Monitoring Validation

    WSOS5Loop Automation Tool