April 11, 2023 PMI Revision 00 1
Dear Participants
WELCOME
To a discussion on
FSSS/ Boiler Protection SystemBasic Concepts
and Standards
April 11, 2023 PMI Revision 00 2
CONTENT
• Basic concept • Function of BMS• Furnace purge procedure• STANDARDS / NFPA
April 11, 2023 PMI Revision 00 3
Main Functions
•Furnace purge before boiler light-up
•Oil firing: Permissives, Sequences and Protections
•Coal firing: Permissives, Sequences and Protections
•Master Fuel Trip (MFT) or Boiler Trip
•Post-Trip Purge Fans Trip•Runback: Graded Mill Tripping•Runback: Graded Mill Tripping
April 11, 2023 PMI Revision 00 4
SG (Steam Generator) CONTROLS
BACK
• BURNER MANAGEMENT SYSTEM
• BOILER PROTECTIONS
• MILLING SYSTEM
• FUEL OIL SYSTEM
• UNIT PURGE
• SEC. AIR DAMPER CONTROL
• SOOT BLOWER CONTROL
• AUX. PRDS CONTROL
• HP-BYPASS CONTROL
April 11, 2023 PMI Revision 00 5
Some Definitions•Boiler Control System:
Deals with Regulating Control
•Burner Management System (BMS):
Deals with Furnace Safety and Start/Stop of Fuel Preparation and Burning Equipment
BMS Logic:
Deals with Control System which would give output based on external inputs and internal logic
April 11, 2023 6
Burner management system
Burner management system is designed to ensure the execution of a safe ,orderly operating sequence in the startup and shutdown of fuel firing equipments and to prevent errors of omission safe operating procedure.
April 11, 2023 7
Function of BMS TO PROVIDE SAFETY TO BOILER. TO PROVIDE ORDERLY SEQUENCE IN THE S/U & S/D OF FUEL FIRING EQUIPMENTS. PREVENT S/U OF FUEL FIRING EQUIPMENTS UNLESS CERTAIN PERMISSIVE INTERLOCKS HAVE BEEN SATISFIED. CONTINUOUS FLAME MONITORING. FAULT DETECTION AND ASSOCIATE S/D. INITIATE MFT UNDER CERTAIN CONDITION OF LOAD COMBINATION.
April 11, 2023 PMI Revision 00 8
Basic Concepts of BMS• BMS is an independent and discreet logic system
specially designed for safety and protection during starting , shutdown, low load and emergency conditions.
• BMS system has been designed to provide increased safety, reliability, flexibility and over all performance of the boiler.
• The system is intended to protect against malfunction of fuel firing equipment and associated systems.
• In some phases of operation, the BMS shall provide permissive interlocks only to ensure safe startup of equipment.
April 11, 2023 PMI Revision 00 9
• The Burner Management system monitors the presence or absence of the forced draft fan running and verifies air flow is being produced, ensures the water level in the boiler drum is satisfactory, and verifies that there is at least one flame in the furnace.
• The Burner Management alarm system provides for a “first out” cause of trip allowing operators to readily identify the reason for an unexpected boiler trip condition.
• The Burner Management System controls the air registers, igniters and fuel oil valves for each burner, as well as monitoring of the flame signals for each burner in service.
April 11, 2023 PMI Revision 00 10
• If the flame quality degrades to 60% of maximum signal strength a poor flame alarm is issued to the alarm system. When a flame quality signal is below 40% for 4 seconds the burner will trip.
• The Burner Management System lights off the initial burner and cuts out burners automatically based on an operator selected sequence.
• It determines when burners need to be cutout based on the steam pressure signal from the ACC (Automatic Combustion Control) system.
• It also provides an interface to the ACC system to tell it when there is a state of change that can affect how the ACC will respond or perform.
April 11, 2023 PMI Revision 00 11
Function of BMS
• Controls boiler purge, fuel headers, and burner field devices, allowing sequential control of the start-up and shutdown of any burners.
• Continuous monitoring of supervisory interlocks, fuel valve positions, flame status and field devices.
• The control strategy normally utilize “de energize to trip” method. • Smart alarms provide “fail to open,” “fail to start,” “fail to close,” and
“fail to stop” information.• Flame monitoring equipment provides the logic controller with flame
status of burners and/or igniters. • Prevent firing unless a satisfactory furnace purge has first been
completed.
April 11, 2023 PMI Revision 00 12
• Prohibit start-up of the equipment unless certain permissive interlocks have first been completed.
• Monitor and control the correct component sequencing during start-up and shut-down of the equipment.
• Conditionally allow the continued operation of the equipment only while certain safety interlocks remaining satisfied.
• Provide automatic supervision when the equipment is in service and provide means to make a Master Fuel Trip (MFT) should certain unacceptable firing conditions occur.
April 11, 2023 13
SIMPLIFIED BLOCK DIAGRAM OF
BURNER MANAGEMENT SYSTEM.
LOCAL CONTROL
BOX AIR DAMPER
BMS
FUELV/V
FLAMEDETECTOR
IGNITER
ABC
DAS
MILLCONTROL
C.C.R
BOILER PLANT
IGNITION CONTROL
PANEL
April 11, 2023 14
BURNER GROUP-EACH STEAM GENERATOR HAS FOUR BURNER GROUPS.EACH GROUP COMPRISES FOUR OIL BURNER WITH ASSOCIATE PF BURNER LOCATED ABOVE AND BELOW.
MILL GROUP- THERE ARE EIGHT MILL GROUPS PER STEAM GENERATOR EACH GROUP COMPRISES A MILL ,ITS ASSOCIATED COAL FEEDER AND A SEAL AIR FAN.
AIR DAMPER-AIR DAMPER ARE DIVIDED AS FOLLOWS-
1-FIVE ELEVATION OF FOUR SECONDARY AIR.
2- 4 ELEVATION OF 4 AIR TO OIL/S.A.D
3-8 ELEVATION OF 4 AIR TO P.F. BURNER.
4-TWO ELEVATION OF FOUR OVERFIRE AIR.
April 11, 2023 15
RELATIONSHIP OF MILL GROUP, ELEVATION NUMBERS & GROUP
NUMBERS.BURNER NOZZLE NOZZLE MILL GROUP
GROUP ELEVATION TYPE GROUP
NUMBER NUMBER 4 13---------------------------SECONDARY AIR
12---------------------------COAL--------------------------- -F
11---------------------------OIL AND S/A
3 10 --------------------------COAL-----------------------------E
9 --------------------------SECONDARY AIR
8---------------------------COAL------------------------------D
2 7-------------------------- OIL AND S/A
6---------------------------COAL------------------------------C
5---------------------------SECONDARY AIR
4---------------------------COAL------------------------------B
1 3---------------------------OIL AND S/A
2---------------------------COAL------------------------------A
1-------------------------- SECONDARY AIR
April 11, 2023 PMI Revision 00 16
April 11, 2023 PMI Revision 00 17
STANDARDS AND CODES
• Prescriptive standards such as NFPA have done well at identifying “what” interlocks should be implemented based upon lessons learned from previous incidents and near misses.
• In today’s microprocessor-based world, it is more important to know “how” to properly implement the prescriptive based interlocks.
• The logic solver was comprised of relays with simple and well-defined failure modes, it was very easy to understand what level of risk reduction the BMS provided.
April 11, 2023 PMI Revision 00 18
NFPA
• Burner Management Systems (BMS) associated with fired devices in the power boilers are defined as Safety Instrumented Systems (SIS) if they contain sensors, a logic solver and a final control element according to NFPA.
• By actively embracing the concept that a BMS may in fact be a SIS, companies can ensure that these systems are designed, maintained, inspected and tested per both the applicable prescriptive standards (API, NFPA, etc.).
• A BMS can be designed that meets all requirements of the prescriptive standards such as NFPA.
April 11, 2023 PMI Revision 00 19
Standard Followed
National Fire Protection Authority (NFPA) of USA
Code 85 of 2001
This code is an amalgamation of earlier codes 8501 to 8506 applicable for various types of boilers and combustion
April 11, 2023 PMI Revision 00 20
IBR Requirements
Fuel supply should be shut off when:Flame failure occursFailure to ignite fuel within a pre-determined
timeAbnormal drum levelTrip of Draft fansIncrease in Boiler Pressure
April 11, 2023 PMI Revision 00 21
BMS Logic Hardware
No specific stipulation regarding type of hardware
NFPA stipulations are not retroactiveExisting system if giving trouble free operation
can continue to work even if not PLC/DCS based
April 11, 2023 PMI Revision 00 22
Some Requirements of NFPA
Burner Management System (BMS) Logic shall:be such that single failure does not prevent shutdownevaluate and address failure of componentsdiagnose improper logic functionshave a direct operable device for MFT which would work
irrespective of BMS logicbe protected from unauthorised logic changesbe provided with independent logic, I/O, power supply
and hardware etc for each boiler separately
April 11, 2023 PMI Revision 00 23
Interesting Insights to NFPA
NFPA recognises that:It is not possible to encompass all specific
hardware applicationsThe code should not be considered a “cook
book”No standard can guarantee elimination of
Furnace explosion or implosionBasic cause of Furnace Explosion is ignition of
accumulated combustibles in the furnace
April 11, 2023 PMI Revision 00 24