01547182
TRANSCRIPT
-
8/2/2019 01547182
1/6
Method of Combined Static and Dynamic
Analysis of Voltage Collapse in Voltage
Stability AssessmentM.Hasani andM.Parniani
Abstract--Different analysis methods have been used for
voltage stability assessment. In comparison with static analysis
methods, little work has been done on dynamic analysis of large
interconnected power systems. Voltage instability can be studied
effectively with a combination of static approaches and time
simulations. This paper discusses voltage stability assessment
using mixed static and dynamic techniques. Using static methods,
a voltage stability based ranking is carried out to specify faint
buses, generators and links in power system. The system isanalyzed for most severe conditions. Then, time domain
simulation is performed for the conditions determined by voltage
instability ranking. The mixed approach benefits from
advantages of both static and dynamic analyses. The New
England (IEEE 39 bus) system was used as a test system.
Index Terms-- Voltage stability, Voltage collapse, Static
methods, Dynamic analysis, Contingency ranking
I. INTRODUCTION
N
im
recent years voltage stability is considered as an
portant concern to electric power industry. Voltageinstability and voltage collapse threaten power system
reliability and security. The voltage problems are often
associated with contingencies like unexpected line and
generator outages, insufficient local reactive power supply and
increased loading of transmission lines. Voltage collapse is
usually characterized by an initial slow and progressive
decrease and a final rapid decline in voltage magnitude at
different buses.
During the past years, there has been a continually
increasing attention to voltage stability assessment using
several analysis methods. Liu and Vu [1] presented a dynamic
description of voltage collapse by characterizing the voltage
stability regions in terms of the continuous tap changer model.
Lee et al [2] introduced a criterion for static voltage stability
enhancement and used accurate models for excitation systems,
tap changer and other equipment for analysis of dynamic
voltage stability. Voltage stability analysis using static and
M.Hasani is with the Department of Electrical Engineering, Sharif
University of Technology, Tehran, Iran (e-mail: [email protected])
M.Parniani is an assistant professor in Department of Electrical
Engineering, Sharif University of Technology, Tehran, Iran (e-mail:
dynamic methods in small radial network was performed by
Morison et al [3]. Some advantages of dynamic simulation of
this phenomenon were shown by Deuse et al [4]. Taylor [5]
and Kundur [6] proposed different static methods and
dynamic simulation with appropriate models for voltage
stability assessments.
Although different approaches have been proposed and
employed for voltage collapse analysis till now, few literature
have dealt with dynamics of this phenomenon in largeinterconnected power systems. Most of the methods that are
applied to these networks are of static type. Little work has
been published on dynamic voltage stability analysis of these
systems, and the differences between the results of two
approaches have been rarely analyzed. The reason elaborate
modeling requirements and time-consuming computations of
dynamic simulation. This paper investigates the discrepancies
between static and dynamic techniques and combines these
techniques to exploit the advantages of both approaches.
In this paper, the New England (IEEE 39 bus) power system
shown in Fig.1 is used as the test system. First, a severity
ranking is carried out on the study system to specify faint buses, generators and links in terms of voltage instability.
Based on this ranking, the most severe conditions for
generator and branch outages and load increment are defined.
For each of these contingencies static methods are employed
to examine the network conditions and stability margins with
relevant curves and factors. Then, time domain simulation is
performed to scrutinize the same conditions. Results obtained
from these methods will be compared with each other. Then
capabilities and limitations of various methods are discussed.
II. VOLTAGE STABILITY ANALYSIS METHODS
A. Static Analysis
Many aspects of voltage stability problems can be
effectively analyzed by using static methods. These methods
examine the viability of the equilibrium point represented by a
specified operating condition of the power system. Static
I
2005 IEEE/PES Transmission and DistributionConference & Exhibition: Asia and Pacific
Dalian, China
0-7803-9114-4/05/$20.00 2005 IEEE. 1
-
8/2/2019 01547182
2/6
Fig.1 Schematic of New England (IEEE 39 bus) power system
approaches like sensitivity analysis, modal analysis and P-V
and Q-V methods for voltage stability assessment use a
system condition or snapshot for voltage stability evaluation.
They usually solve power flow equations of the network with
specific load increments until the point of voltage collapse is
reached. These techniques allow examination of a wide rangeof system conditions and can provide much insight into the
nature of this phenomenon by computation of the contributing
factors.
Sensitivity Analysis: This method calculates the relationship
between voltage changes and reactive power changes at
different buses using reduced Jacobian matrix [6]. Positive
sensitivities represent stable operation and as stability
decreases, the magnitude of the sensitivity increases becoming
infinite at the maximum loadability limit.
Modal Analysis: This analysis approach has the added
advantage that it provides information regarding the
mechanism of instability. Voltage stability characteristics ofthe system can be identified by computing the eigenvalues and
eigenvectors of the reduced Jacobian matrix [6]. Positive
eigenvalues represent voltage stability of system and the
smaller the magnitude, the closer the relevant modal voltage is
to being unstable. The magnitude of the eigenvalues can
provide a relative measure of the proximity to instability.
In this paper, bus and branch and generator participation
factors defined in [6] are widely used for identifying
appropriate measures to relieve voltage stability problems and
for contingency selections.
P-V Curve Method: These curves are produced by running a
series of load flow cases and relate bus voltages to load within
a special region. This methodology has the benefit of
providing an indication of proximity to voltage collapse
throughout the range of load levels. With power transfer
increase in a special region, its voltage profile will becomelower until a point of collapse is reached.
Q-V Curve Method: These curves are also produced by
running a series of load flow cases. They show the necessary
amount of reactive power to achieve a specified voltage level.
This method was developed due to difficulties in power flow
program convergence of stressed cases close to the maximum
loadability limit. To draw the Q-V Curves stretching from
unstable to stable region, special techniques are used to
achieve convergence [5]. Examples are using voltage sensitive
loads; artificially increasing reactive power sources limits and
fixing voltages at critical buses.
B. Dynamic Simulation
Time domain simulation with appropriate models for
devices clarifies this phenomenon more precisely. It shows the
time events and their chronology leading the system to final
phases of voltage collapse. The computer program solves the
differential-algebraic equations describing the power system.
It has the features of modeling important dynamics that are
influential in voltage instability such as dynamic load models,
OLTC, excitation system limiters and various other controllers
in the system. Dynamic analysis is useful for detailed study of
2
-
8/2/2019 01547182
3/6
specific voltage collapse situations and coordination of
protection and time dependent action of controls.
In recent years, capabilities of midterm and long-term time
domain simulation programs have been greatly improved. Full
dynamic simulation considering transient stability models for
these purposes seems to be time consuming. New programs
usually employ fast dynamic simulation techniques, which
have a good compromise between speed and accuracy [7]. The
DigSILENT software, which is suitable for long-termdynamic assessment, is used in the simulation presented in this
paper.
III. VOLTAGE STABILITY IN TEST SYSTEM
A. Modeling for Static and Dynamic Simulation
We will present the idea of mixed static and dynamic
analyses through an example. Then, we make general
conclusions and summarize the proposed approach. For static
power flow simulation, we followed the general methodology
used for planning and operation decision making. The loads,
which were located at the secondary of OLTC transformers,
were represented as voltage sensitive (both in active and
reactive power). Reference [5] describes the general
considerations for static analysis.
For dynamic simulation, we added OLTC transformer
models. Transformers were initialized at their neutral tap and
had 1% tap size (Except for T11-12 which was 2.5%). Other
data for tap changing transformers were 10% tap range with
20 steps of 1 or 2.5% and initial time delay was 5 second.
Based on typical measurements and report of similar
networks, we assumed active load to be 20% resistance and
80% dynamic (voltage and time dependent). Load represented
in bus 12 -which is of concern according to the followingstudies- has active and reactive power voltage dependence of
8.1= and 2.1= and time constants for active and reactive
power voltage dependence were 20 and 10 second. The loads
were represented on the low voltage side of the OLTC
transformers.
The overexcitation limiter was modeled as a part of AC2A
standard type of AVR. Armature current limit may be
encountered, requiring either severe reduction in field
current/reactive power or reduction in active power. Armature
current limit was modeled separately in simulations.
B. Contingency Ranking
The base case condition in IEEE 39 bus was used for
contingency selection. It is noteworthy that this contingency
selection is based on voltage instability in power system and is
different from conventional contingency ranking used for
system security and reliability studies. All of static analysis
methods introduced in part II were used to select the most
severe conditions corresponding to line, transformer and
generator outages and load increment in different buses.
The relationship between voltage and reactive power
changes was assessed for all of the buses using sensitivity
analysis. The results identified buses 12 and 2 as the most and
least sensitive buses with sensitivity factors 0.0334 and 0.0074
%/MVAR respectively. Modal analysis shows that the least
eigenvalues of jacobian matrix in the network has the
magnitude of 9.5609, which has sufficient margin to
instability. The sizes of bus, branch and generator
participation factors corresponding to this mode were
calculated. Bus 12 indicated the most effectiveness of
remedial actions in stabilizing that mode. Line8-9 (linebetween buses 8 & 9) consumes the most reactive power in
response to an incremental change in reactive load at bus 12,
and the generator G3 supplies the most reactive power in such
situation. The P-V and Q-V methods confirm these results.
Based on these observations, three scenarios were selected for
the rest of analyses:
1. Line 8-9 outage
2. Generator G3 outage
3. Load increment at bus 12
IV. STATIC ANALYSIS OF VOLTAGE STABILITY
For voltage stability assessment with static methods all three
cases defined in the previous section were analyzed. Fig.2
shows Q-V sensitivity results for different buses in network
after transmission line outage. Bus 12 shows to be the most
sensitive bus in response to reactive power changes. Using
modal analysis, different participation factors were calculated
for the lowest eigenvalue with magnitude of 6.633. Table.1
shows the bus participation factors indicating nearly the same
result as sensitivity analysis. Branches (line and transformers)
participation factors are shown in Table.2 and generator
participation factors are presented in Table.3.
Figures.3 and 4 show the P-V and Q-V curves for the most
and least sensitive buses in voltage stability assessment. In Q-
V curve method, bus 12 has the least stable condition with 585
MVAR reactive power margin to instability and bus 19 has
the greatest one. P-V curve method identified bus 7 as the
weakest bus in terms of voltage stability.
Similar analyses were performed for two other scenarios
defined in contingency selections. Approximately the same
results were obtained for these conditions. For instance, all
cases have sufficient reactive power margin, and hence are
considered as voltage stable. Results of these stable conditions
are directly comparable with the steady state values at the end
of stable dynamic simulation. Detailed results of the second
and third scenarios are not shown here for the sake of brevity.In the load increment scenario, active and reactive powers
were increased with a fixed pattern until the power flow
program did not converge. Then the network was analyzed in
the situation just before divergence. The critical load at bus 12
in this condition was 44 MW and 420 MVAR as compared to
the initial loading of 8.5 MW and 88 MVAR.
3
-
8/2/2019 01547182
4/6
Fig. 2. Q-V sensitivity results for different buses after line 8-9 outage
Fig. 3. P-V curves for the most and least stable buses after line 8-9 outage
Fig. 4. Q-V curves for the most and least stable buses after line 8-9 outage
TABLE.1
BUS PARTICIPATION FACTORS CORRESPONDING TO THE LEAST STABLE MODE
IN FIRST CONTINGENCY
Bus
Par.
Factor
Bus
No
Bus
Par.
Factor
Bus
No
0.0373170.084812
0.0261270.08228
0.0254160.07987
0.0228240.073840.0149210.06925
0.0126260.06773
0.0051230.06286
0.0047280.062514
0.0047220.057311
0.0038190.056813
0.0022290.051918
0.0013200.048810
0.0011250.039615
TABLE.2
BRANCH PARTICIPATION FACTORS IN FIRST CONTINGENCY
Branch
Par.Factor
Branch
Name
Branch
Par.Factor
Branch
Name
Branch
Par.Factor
Branch
Name
0.05245-60.132526-291T3
0.0483T90.138-50.6813T2
0.047313-100.1269T40.262716-19
0.03667-80.121614-40.2284T6
0.0337T13-120.1199T70.227227-26
0.030328-290.108128-260.191521-22
0.026724-160.097211-60.186226-25
0.026T11-120.0873T50.164315-16
0.02525-20.087121-160.16016-7
0.0225T10.08183-40.147324-23
0.018823-220.0810-110.141817-27
0.0145T80.0814-130.141218-3
0.0143T20-190.070616-170.140714-15
0.01191-390.0554-50.133318-17
TABLE.3
GENERATOR PARTICIPATION FACTORS IN FIRST CONTINGENCY
Gen Par.
Factor
Gen No
13
0.86372
0.48126
0.3994
0.2939
0.27367
0.19555
0.14268
0.12191
0.034710
V. DYNAMIC SIMULATION
Figs. 5-7 show the results of time domain simulation for
three cases identified in the previous part. In this figures bus
12 is the load side of the OLTC transformer and bus 11 and 13
are high voltage side of relevant transformers. In all cases, the
simulated voltages have reached their stable steady state
conditions. However, in Fig.7 which has the load increment of
36 MW and 330 MVAR (to receive the critical load defined in
4
-
8/2/2019 01547182
5/6
the previous section) stability can not be achieved because of
considerable decline in load side voltage which is likely to
activate protection devices.
Acceptability of stable conditions acquired by dynamic
simulation can be judged by the post-disturbance voltage
levels, the remaining reactive power reserves at generating
plants and the time available for operator action. We used
ANSI standard C84.1-1989 for reliability criteria [8], which
suggests 92% voltage for consumer service in firstcontingencies. Also, undervoltage load shedding may be
devised using dynamic simulation results in order to enhance
system reliability. (This was not considered here).
In the first and second scenarios which were stable in both
static and dynamic analyses, the result of static methods can
be directly compared with the results at the steady state of
dynamic simulation. Results for voltage profiles in different
buses and generators reactive power margin are presented in
Table 4 and 5. According to the results of Table 5, the static
method seems to be more conservative. Further investigations
not presented in this paper - are carried out with the aid of
dynamic simulation, to examine the effects of generator
armature and field current limiters, OLTC control parameters,
and load characteristics.
Fig. 5. Voltage for different buses after line 8-9 outage
Fig. 6. Voltage for different buses after generator G3 outage
Fig. 7. Voltage for different buses after load increment at bus 12
TABLE.4
COMPARISON OF VOLTAGES AT LOAD BUSES CALCULATED BY STATIC AND
DYNAMIC METHODS
Voltage
(Dynamic)
Voltage
(Static)
Bus
No
0.990.9730.950.954
0.930.947
0.930.938
0.990.9512
0.960.9815
0.981.0016
0.990.9918
0.920.9820
0.991.0121
1.011.0323
0.991.0124
1.041.0425
1.021.0226
1.001.0027
1.031.0328
1.031.0429
1.001.0031
TABLE.5
COMPARISON OF REACTIVE POWER RESERVES CALCULATED BY STATIC AND
DYNAMIC METHODS
MVAR Reactive
Margin (Dynamic)
MVAR Reactive
Margin (Static)
Gen No
12191
30372
52753
39294
84795
37466
55627
35498
20159
8011210
VI. GENERAL CONSIDERATIONS
Although the voltage instability is a dynamic phenomenon,
different static analysis methods have been proposed and
widely used in different networks. Static methods are
generally easier to implement and require less computing
5
-
8/2/2019 01547182
6/6
time. Some of these methods, e.g. P-V and Q-V curves,
provide valuable information about stability margin. Some
others like modal analysis are very useful to identify the
pattern of voltage instability and thus to devise appropriate
remedial actions. In contrast, dynamic simulation yields more
accurate results; and requires more elaborate models and
computing time. In time domain simulation all controllers,
protective relays, dynamic model of loads, tap-changer
controller and etc can be taken into consideration.And the main limitations in this analysis method are:
1. With dynamic simulation, stability margin for busvoltage is not directly computed.
2. In interconnected networks, because of existing severalcontrollers and protection devices with overlapped time
domain actions, distinction of main factor affecting
instability might be a problem.
Due to limitations of time domain simulation in analyzing
voltage stability in interconnected power systems, a new
method of combined static and dynamic analysis of voltage
collapse is introduced in this paper. In this method, first, a
contingency ranking for voltage stability is carried out on the
study system. Based on this ranking, the most severe
conditions including generators/lines outages and load
changes are identified. For each contingency condition, static
methods are employed again to examine the stability
conditions. Time domain simulation -with more detail models
for these parts- is then performed for the selected contingency
cases. With the result of dynamic analysis, appropriate
controllers and protection devices can be selected for the
system to overcome voltage instability. The method
considerably reduces computations of dynamic analysis with
no complex and detail models required for all equipment.
VII. CONCLUSION
In this paper, a new approach using combination of static
and dynamic methods was proposed for voltage stability
assessment. Using static methods, a voltage stability ranking
was performed to define faint buses, generators and links in
terms of voltage stability. Then, these parts are modeled with
more detail and dynamic analysis was used for most severe
conditions. Results from different static approaches were
compared with more accurate time domain simulations.
Although static methods based on power flow analysis is
suitable for screening, final decisions involving several
considerations both in planning and operation should be
confirmed by more accurate time domain simulation in which
different characteristics of multiple controllers, protectionrelays and coordination of them are taken into account.
VIII. REFERENCES
[1] C.C.Liu and K.T.Vu, "Analysis of tap-changer dynamic andconstruction of voltage stability regions," IEEE Trans. on Circuit and
Systems, Vol.36, No.4, pp.575-590, Apr 1989
[2] B.H.Lee and K.Y.Lee, "Dynamic and static voltage stabilityenhancement of power systems," IEEE Trans. on Power Systems, Vol.8,
pp.231-238, Feb. 1993
[3] G.K.Morison, B.Gao and P.Kundur, "Voltage Stability analysisusing static and dynamic approaches," IEEE Trans. on Power Systems,
Vol. PWRS8, No.3, pp.1159-1171, Aug.1993
[4] J.Deuse and M.Stubbe, "Dynamic simulation of voltagecollapses," IEEE Trans. on Power Systems, Vol.8 pp.894-900, Aug.1993
[5] C.W.Taylor, Power System Voltage Stability, New York:McGraw-Hill, 1994
[6] P.Kundur, Power System Stability and Control, New York:McGraw-Hill, 1994.
[7] T.Van Cutsem, and C.Vournas, Voltage Stability of ElectricPower Systems, Kluwer Academic Publishers, 1998
[8] American National Standard Institute, "American NationalStandard for Electric Power Systems and Equipment Voltage Ratings,"
ANSI C84.1-1989.
Masoud Hasani was born in July 30, 1978. He received the B.Sc. and M.Sc.
degrees in Electrical Power Engineering from Sharif University of
Technology (SUT), Tehran, Iran, in 2001 and 2004 respectively.
He is currently a Ph.D. student in Electrical Power Engineering at Sharif
University of Technology.
Mostafa Parniani obtained his B.Sc. and M.Sc. degrees in Electrical Power
Engineering from Tehran Polytechnic and Sharif University of Technology
(SUT), in 1987 and 1990 respectively; and Ph.D. in Electrical Engineering
from the University of Toronto in 1995. Since then, he has been with the
Electrical Engineering Department of SUT as an assistant professor. He has
worked with Ghods Niroo Consulting Engineers Co., Electric Power ResearchCenter, and Niroo Research Institute. He has also been a member of IEEE
Task Force on Slow Transients, as well as national committees in his field. His
areas of interest are power system control and dynamics, reactive power
control, and applications of power electronics in power systems.
6