01547182

Upload: dhanda-pani

Post on 06-Apr-2018

218 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 01547182

    1/6

    Method of Combined Static and Dynamic

    Analysis of Voltage Collapse in Voltage

    Stability AssessmentM.Hasani andM.Parniani

    Abstract--Different analysis methods have been used for

    voltage stability assessment. In comparison with static analysis

    methods, little work has been done on dynamic analysis of large

    interconnected power systems. Voltage instability can be studied

    effectively with a combination of static approaches and time

    simulations. This paper discusses voltage stability assessment

    using mixed static and dynamic techniques. Using static methods,

    a voltage stability based ranking is carried out to specify faint

    buses, generators and links in power system. The system isanalyzed for most severe conditions. Then, time domain

    simulation is performed for the conditions determined by voltage

    instability ranking. The mixed approach benefits from

    advantages of both static and dynamic analyses. The New

    England (IEEE 39 bus) system was used as a test system.

    Index Terms-- Voltage stability, Voltage collapse, Static

    methods, Dynamic analysis, Contingency ranking

    I. INTRODUCTION

    N

    im

    recent years voltage stability is considered as an

    portant concern to electric power industry. Voltageinstability and voltage collapse threaten power system

    reliability and security. The voltage problems are often

    associated with contingencies like unexpected line and

    generator outages, insufficient local reactive power supply and

    increased loading of transmission lines. Voltage collapse is

    usually characterized by an initial slow and progressive

    decrease and a final rapid decline in voltage magnitude at

    different buses.

    During the past years, there has been a continually

    increasing attention to voltage stability assessment using

    several analysis methods. Liu and Vu [1] presented a dynamic

    description of voltage collapse by characterizing the voltage

    stability regions in terms of the continuous tap changer model.

    Lee et al [2] introduced a criterion for static voltage stability

    enhancement and used accurate models for excitation systems,

    tap changer and other equipment for analysis of dynamic

    voltage stability. Voltage stability analysis using static and

    M.Hasani is with the Department of Electrical Engineering, Sharif

    University of Technology, Tehran, Iran (e-mail: [email protected])

    M.Parniani is an assistant professor in Department of Electrical

    Engineering, Sharif University of Technology, Tehran, Iran (e-mail:

    [email protected])

    dynamic methods in small radial network was performed by

    Morison et al [3]. Some advantages of dynamic simulation of

    this phenomenon were shown by Deuse et al [4]. Taylor [5]

    and Kundur [6] proposed different static methods and

    dynamic simulation with appropriate models for voltage

    stability assessments.

    Although different approaches have been proposed and

    employed for voltage collapse analysis till now, few literature

    have dealt with dynamics of this phenomenon in largeinterconnected power systems. Most of the methods that are

    applied to these networks are of static type. Little work has

    been published on dynamic voltage stability analysis of these

    systems, and the differences between the results of two

    approaches have been rarely analyzed. The reason elaborate

    modeling requirements and time-consuming computations of

    dynamic simulation. This paper investigates the discrepancies

    between static and dynamic techniques and combines these

    techniques to exploit the advantages of both approaches.

    In this paper, the New England (IEEE 39 bus) power system

    shown in Fig.1 is used as the test system. First, a severity

    ranking is carried out on the study system to specify faint buses, generators and links in terms of voltage instability.

    Based on this ranking, the most severe conditions for

    generator and branch outages and load increment are defined.

    For each of these contingencies static methods are employed

    to examine the network conditions and stability margins with

    relevant curves and factors. Then, time domain simulation is

    performed to scrutinize the same conditions. Results obtained

    from these methods will be compared with each other. Then

    capabilities and limitations of various methods are discussed.

    II. VOLTAGE STABILITY ANALYSIS METHODS

    A. Static Analysis

    Many aspects of voltage stability problems can be

    effectively analyzed by using static methods. These methods

    examine the viability of the equilibrium point represented by a

    specified operating condition of the power system. Static

    I

    2005 IEEE/PES Transmission and DistributionConference & Exhibition: Asia and Pacific

    Dalian, China

    0-7803-9114-4/05/$20.00 2005 IEEE. 1

  • 8/2/2019 01547182

    2/6

    Fig.1 Schematic of New England (IEEE 39 bus) power system

    approaches like sensitivity analysis, modal analysis and P-V

    and Q-V methods for voltage stability assessment use a

    system condition or snapshot for voltage stability evaluation.

    They usually solve power flow equations of the network with

    specific load increments until the point of voltage collapse is

    reached. These techniques allow examination of a wide rangeof system conditions and can provide much insight into the

    nature of this phenomenon by computation of the contributing

    factors.

    Sensitivity Analysis: This method calculates the relationship

    between voltage changes and reactive power changes at

    different buses using reduced Jacobian matrix [6]. Positive

    sensitivities represent stable operation and as stability

    decreases, the magnitude of the sensitivity increases becoming

    infinite at the maximum loadability limit.

    Modal Analysis: This analysis approach has the added

    advantage that it provides information regarding the

    mechanism of instability. Voltage stability characteristics ofthe system can be identified by computing the eigenvalues and

    eigenvectors of the reduced Jacobian matrix [6]. Positive

    eigenvalues represent voltage stability of system and the

    smaller the magnitude, the closer the relevant modal voltage is

    to being unstable. The magnitude of the eigenvalues can

    provide a relative measure of the proximity to instability.

    In this paper, bus and branch and generator participation

    factors defined in [6] are widely used for identifying

    appropriate measures to relieve voltage stability problems and

    for contingency selections.

    P-V Curve Method: These curves are produced by running a

    series of load flow cases and relate bus voltages to load within

    a special region. This methodology has the benefit of

    providing an indication of proximity to voltage collapse

    throughout the range of load levels. With power transfer

    increase in a special region, its voltage profile will becomelower until a point of collapse is reached.

    Q-V Curve Method: These curves are also produced by

    running a series of load flow cases. They show the necessary

    amount of reactive power to achieve a specified voltage level.

    This method was developed due to difficulties in power flow

    program convergence of stressed cases close to the maximum

    loadability limit. To draw the Q-V Curves stretching from

    unstable to stable region, special techniques are used to

    achieve convergence [5]. Examples are using voltage sensitive

    loads; artificially increasing reactive power sources limits and

    fixing voltages at critical buses.

    B. Dynamic Simulation

    Time domain simulation with appropriate models for

    devices clarifies this phenomenon more precisely. It shows the

    time events and their chronology leading the system to final

    phases of voltage collapse. The computer program solves the

    differential-algebraic equations describing the power system.

    It has the features of modeling important dynamics that are

    influential in voltage instability such as dynamic load models,

    OLTC, excitation system limiters and various other controllers

    in the system. Dynamic analysis is useful for detailed study of

    2

  • 8/2/2019 01547182

    3/6

    specific voltage collapse situations and coordination of

    protection and time dependent action of controls.

    In recent years, capabilities of midterm and long-term time

    domain simulation programs have been greatly improved. Full

    dynamic simulation considering transient stability models for

    these purposes seems to be time consuming. New programs

    usually employ fast dynamic simulation techniques, which

    have a good compromise between speed and accuracy [7]. The

    DigSILENT software, which is suitable for long-termdynamic assessment, is used in the simulation presented in this

    paper.

    III. VOLTAGE STABILITY IN TEST SYSTEM

    A. Modeling for Static and Dynamic Simulation

    We will present the idea of mixed static and dynamic

    analyses through an example. Then, we make general

    conclusions and summarize the proposed approach. For static

    power flow simulation, we followed the general methodology

    used for planning and operation decision making. The loads,

    which were located at the secondary of OLTC transformers,

    were represented as voltage sensitive (both in active and

    reactive power). Reference [5] describes the general

    considerations for static analysis.

    For dynamic simulation, we added OLTC transformer

    models. Transformers were initialized at their neutral tap and

    had 1% tap size (Except for T11-12 which was 2.5%). Other

    data for tap changing transformers were 10% tap range with

    20 steps of 1 or 2.5% and initial time delay was 5 second.

    Based on typical measurements and report of similar

    networks, we assumed active load to be 20% resistance and

    80% dynamic (voltage and time dependent). Load represented

    in bus 12 -which is of concern according to the followingstudies- has active and reactive power voltage dependence of

    8.1= and 2.1= and time constants for active and reactive

    power voltage dependence were 20 and 10 second. The loads

    were represented on the low voltage side of the OLTC

    transformers.

    The overexcitation limiter was modeled as a part of AC2A

    standard type of AVR. Armature current limit may be

    encountered, requiring either severe reduction in field

    current/reactive power or reduction in active power. Armature

    current limit was modeled separately in simulations.

    B. Contingency Ranking

    The base case condition in IEEE 39 bus was used for

    contingency selection. It is noteworthy that this contingency

    selection is based on voltage instability in power system and is

    different from conventional contingency ranking used for

    system security and reliability studies. All of static analysis

    methods introduced in part II were used to select the most

    severe conditions corresponding to line, transformer and

    generator outages and load increment in different buses.

    The relationship between voltage and reactive power

    changes was assessed for all of the buses using sensitivity

    analysis. The results identified buses 12 and 2 as the most and

    least sensitive buses with sensitivity factors 0.0334 and 0.0074

    %/MVAR respectively. Modal analysis shows that the least

    eigenvalues of jacobian matrix in the network has the

    magnitude of 9.5609, which has sufficient margin to

    instability. The sizes of bus, branch and generator

    participation factors corresponding to this mode were

    calculated. Bus 12 indicated the most effectiveness of

    remedial actions in stabilizing that mode. Line8-9 (linebetween buses 8 & 9) consumes the most reactive power in

    response to an incremental change in reactive load at bus 12,

    and the generator G3 supplies the most reactive power in such

    situation. The P-V and Q-V methods confirm these results.

    Based on these observations, three scenarios were selected for

    the rest of analyses:

    1. Line 8-9 outage

    2. Generator G3 outage

    3. Load increment at bus 12

    IV. STATIC ANALYSIS OF VOLTAGE STABILITY

    For voltage stability assessment with static methods all three

    cases defined in the previous section were analyzed. Fig.2

    shows Q-V sensitivity results for different buses in network

    after transmission line outage. Bus 12 shows to be the most

    sensitive bus in response to reactive power changes. Using

    modal analysis, different participation factors were calculated

    for the lowest eigenvalue with magnitude of 6.633. Table.1

    shows the bus participation factors indicating nearly the same

    result as sensitivity analysis. Branches (line and transformers)

    participation factors are shown in Table.2 and generator

    participation factors are presented in Table.3.

    Figures.3 and 4 show the P-V and Q-V curves for the most

    and least sensitive buses in voltage stability assessment. In Q-

    V curve method, bus 12 has the least stable condition with 585

    MVAR reactive power margin to instability and bus 19 has

    the greatest one. P-V curve method identified bus 7 as the

    weakest bus in terms of voltage stability.

    Similar analyses were performed for two other scenarios

    defined in contingency selections. Approximately the same

    results were obtained for these conditions. For instance, all

    cases have sufficient reactive power margin, and hence are

    considered as voltage stable. Results of these stable conditions

    are directly comparable with the steady state values at the end

    of stable dynamic simulation. Detailed results of the second

    and third scenarios are not shown here for the sake of brevity.In the load increment scenario, active and reactive powers

    were increased with a fixed pattern until the power flow

    program did not converge. Then the network was analyzed in

    the situation just before divergence. The critical load at bus 12

    in this condition was 44 MW and 420 MVAR as compared to

    the initial loading of 8.5 MW and 88 MVAR.

    3

  • 8/2/2019 01547182

    4/6

    Fig. 2. Q-V sensitivity results for different buses after line 8-9 outage

    Fig. 3. P-V curves for the most and least stable buses after line 8-9 outage

    Fig. 4. Q-V curves for the most and least stable buses after line 8-9 outage

    TABLE.1

    BUS PARTICIPATION FACTORS CORRESPONDING TO THE LEAST STABLE MODE

    IN FIRST CONTINGENCY

    Bus

    Par.

    Factor

    Bus

    No

    Bus

    Par.

    Factor

    Bus

    No

    0.0373170.084812

    0.0261270.08228

    0.0254160.07987

    0.0228240.073840.0149210.06925

    0.0126260.06773

    0.0051230.06286

    0.0047280.062514

    0.0047220.057311

    0.0038190.056813

    0.0022290.051918

    0.0013200.048810

    0.0011250.039615

    TABLE.2

    BRANCH PARTICIPATION FACTORS IN FIRST CONTINGENCY

    Branch

    Par.Factor

    Branch

    Name

    Branch

    Par.Factor

    Branch

    Name

    Branch

    Par.Factor

    Branch

    Name

    0.05245-60.132526-291T3

    0.0483T90.138-50.6813T2

    0.047313-100.1269T40.262716-19

    0.03667-80.121614-40.2284T6

    0.0337T13-120.1199T70.227227-26

    0.030328-290.108128-260.191521-22

    0.026724-160.097211-60.186226-25

    0.026T11-120.0873T50.164315-16

    0.02525-20.087121-160.16016-7

    0.0225T10.08183-40.147324-23

    0.018823-220.0810-110.141817-27

    0.0145T80.0814-130.141218-3

    0.0143T20-190.070616-170.140714-15

    0.01191-390.0554-50.133318-17

    TABLE.3

    GENERATOR PARTICIPATION FACTORS IN FIRST CONTINGENCY

    Gen Par.

    Factor

    Gen No

    13

    0.86372

    0.48126

    0.3994

    0.2939

    0.27367

    0.19555

    0.14268

    0.12191

    0.034710

    V. DYNAMIC SIMULATION

    Figs. 5-7 show the results of time domain simulation for

    three cases identified in the previous part. In this figures bus

    12 is the load side of the OLTC transformer and bus 11 and 13

    are high voltage side of relevant transformers. In all cases, the

    simulated voltages have reached their stable steady state

    conditions. However, in Fig.7 which has the load increment of

    36 MW and 330 MVAR (to receive the critical load defined in

    4

  • 8/2/2019 01547182

    5/6

    the previous section) stability can not be achieved because of

    considerable decline in load side voltage which is likely to

    activate protection devices.

    Acceptability of stable conditions acquired by dynamic

    simulation can be judged by the post-disturbance voltage

    levels, the remaining reactive power reserves at generating

    plants and the time available for operator action. We used

    ANSI standard C84.1-1989 for reliability criteria [8], which

    suggests 92% voltage for consumer service in firstcontingencies. Also, undervoltage load shedding may be

    devised using dynamic simulation results in order to enhance

    system reliability. (This was not considered here).

    In the first and second scenarios which were stable in both

    static and dynamic analyses, the result of static methods can

    be directly compared with the results at the steady state of

    dynamic simulation. Results for voltage profiles in different

    buses and generators reactive power margin are presented in

    Table 4 and 5. According to the results of Table 5, the static

    method seems to be more conservative. Further investigations

    not presented in this paper - are carried out with the aid of

    dynamic simulation, to examine the effects of generator

    armature and field current limiters, OLTC control parameters,

    and load characteristics.

    Fig. 5. Voltage for different buses after line 8-9 outage

    Fig. 6. Voltage for different buses after generator G3 outage

    Fig. 7. Voltage for different buses after load increment at bus 12

    TABLE.4

    COMPARISON OF VOLTAGES AT LOAD BUSES CALCULATED BY STATIC AND

    DYNAMIC METHODS

    Voltage

    (Dynamic)

    Voltage

    (Static)

    Bus

    No

    0.990.9730.950.954

    0.930.947

    0.930.938

    0.990.9512

    0.960.9815

    0.981.0016

    0.990.9918

    0.920.9820

    0.991.0121

    1.011.0323

    0.991.0124

    1.041.0425

    1.021.0226

    1.001.0027

    1.031.0328

    1.031.0429

    1.001.0031

    TABLE.5

    COMPARISON OF REACTIVE POWER RESERVES CALCULATED BY STATIC AND

    DYNAMIC METHODS

    MVAR Reactive

    Margin (Dynamic)

    MVAR Reactive

    Margin (Static)

    Gen No

    12191

    30372

    52753

    39294

    84795

    37466

    55627

    35498

    20159

    8011210

    VI. GENERAL CONSIDERATIONS

    Although the voltage instability is a dynamic phenomenon,

    different static analysis methods have been proposed and

    widely used in different networks. Static methods are

    generally easier to implement and require less computing

    5

  • 8/2/2019 01547182

    6/6

    time. Some of these methods, e.g. P-V and Q-V curves,

    provide valuable information about stability margin. Some

    others like modal analysis are very useful to identify the

    pattern of voltage instability and thus to devise appropriate

    remedial actions. In contrast, dynamic simulation yields more

    accurate results; and requires more elaborate models and

    computing time. In time domain simulation all controllers,

    protective relays, dynamic model of loads, tap-changer

    controller and etc can be taken into consideration.And the main limitations in this analysis method are:

    1. With dynamic simulation, stability margin for busvoltage is not directly computed.

    2. In interconnected networks, because of existing severalcontrollers and protection devices with overlapped time

    domain actions, distinction of main factor affecting

    instability might be a problem.

    Due to limitations of time domain simulation in analyzing

    voltage stability in interconnected power systems, a new

    method of combined static and dynamic analysis of voltage

    collapse is introduced in this paper. In this method, first, a

    contingency ranking for voltage stability is carried out on the

    study system. Based on this ranking, the most severe

    conditions including generators/lines outages and load

    changes are identified. For each contingency condition, static

    methods are employed again to examine the stability

    conditions. Time domain simulation -with more detail models

    for these parts- is then performed for the selected contingency

    cases. With the result of dynamic analysis, appropriate

    controllers and protection devices can be selected for the

    system to overcome voltage instability. The method

    considerably reduces computations of dynamic analysis with

    no complex and detail models required for all equipment.

    VII. CONCLUSION

    In this paper, a new approach using combination of static

    and dynamic methods was proposed for voltage stability

    assessment. Using static methods, a voltage stability ranking

    was performed to define faint buses, generators and links in

    terms of voltage stability. Then, these parts are modeled with

    more detail and dynamic analysis was used for most severe

    conditions. Results from different static approaches were

    compared with more accurate time domain simulations.

    Although static methods based on power flow analysis is

    suitable for screening, final decisions involving several

    considerations both in planning and operation should be

    confirmed by more accurate time domain simulation in which

    different characteristics of multiple controllers, protectionrelays and coordination of them are taken into account.

    VIII. REFERENCES

    [1] C.C.Liu and K.T.Vu, "Analysis of tap-changer dynamic andconstruction of voltage stability regions," IEEE Trans. on Circuit and

    Systems, Vol.36, No.4, pp.575-590, Apr 1989

    [2] B.H.Lee and K.Y.Lee, "Dynamic and static voltage stabilityenhancement of power systems," IEEE Trans. on Power Systems, Vol.8,

    pp.231-238, Feb. 1993

    [3] G.K.Morison, B.Gao and P.Kundur, "Voltage Stability analysisusing static and dynamic approaches," IEEE Trans. on Power Systems,

    Vol. PWRS8, No.3, pp.1159-1171, Aug.1993

    [4] J.Deuse and M.Stubbe, "Dynamic simulation of voltagecollapses," IEEE Trans. on Power Systems, Vol.8 pp.894-900, Aug.1993

    [5] C.W.Taylor, Power System Voltage Stability, New York:McGraw-Hill, 1994

    [6] P.Kundur, Power System Stability and Control, New York:McGraw-Hill, 1994.

    [7] T.Van Cutsem, and C.Vournas, Voltage Stability of ElectricPower Systems, Kluwer Academic Publishers, 1998

    [8] American National Standard Institute, "American NationalStandard for Electric Power Systems and Equipment Voltage Ratings,"

    ANSI C84.1-1989.

    Masoud Hasani was born in July 30, 1978. He received the B.Sc. and M.Sc.

    degrees in Electrical Power Engineering from Sharif University of

    Technology (SUT), Tehran, Iran, in 2001 and 2004 respectively.

    He is currently a Ph.D. student in Electrical Power Engineering at Sharif

    University of Technology.

    Mostafa Parniani obtained his B.Sc. and M.Sc. degrees in Electrical Power

    Engineering from Tehran Polytechnic and Sharif University of Technology

    (SUT), in 1987 and 1990 respectively; and Ph.D. in Electrical Engineering

    from the University of Toronto in 1995. Since then, he has been with the

    Electrical Engineering Department of SUT as an assistant professor. He has

    worked with Ghods Niroo Consulting Engineers Co., Electric Power ResearchCenter, and Niroo Research Institute. He has also been a member of IEEE

    Task Force on Slow Transients, as well as national committees in his field. His

    areas of interest are power system control and dynamics, reactive power

    control, and applications of power electronics in power systems.

    6