02 130205 v7.13 evrc2a-n6,nt manual control

306
RECLOSER CONTROL EVRC2A-N6,NT USER’S MANUAL ENTEC ELECTRIC & ELECTRONIC CO., LTD ENTEC Copyright © 2002 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation Release Date: Feb. 2013 / Manual Revision: 7.13

Upload: giancarlo-barahona-aguilar

Post on 02-Oct-2015

586 views

Category:

Documents


163 download

DESCRIPTION

texto referido a equipos de protección para redes de media tensión.

TRANSCRIPT

  • RECLOSER CONTROL EVRC2A-N6,NT

    USERS MANUAL

    ENTECELECTRIC & ELECTRONIC CO., LTD

    ENTEC

    Copyright 2002 by ENTEC ELECTRIC & ELECTRONIC CO., LTD all right reserved. Forerunner Distribution & Automation

    Release Date: Feb. 2013 / Manual Revision: 7.13

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    iENHANCED TECHNOLOGY

    Release Note: [Oct. 2006] Ver4.00 1. Add explanations for new additional function below

    - Support ETHERNET Port(Port4) for EVRC2A - Support IEC60870-5-104 Protocol Communication (add the setup menu)

    [Sept. 2007] Ver4.10 1. Add explanations for new additional function below

    - Dialing Modem Support(add the setup menu) [Sept. 2009] Ver4.12 1. Add explanations for new additional function below

    - Support IEC60870-5-101 Protocol Communication (add the setup menu) - Support Overfrequency Protection Element (add the setup menu)

    [Jan. 2010] Ver5.00

    After the Ver5.00, the manual is applied to the EVRC2A-N(Network type). 1. Support ETIMS(ENTEC Integration Management Software) function(add the setup menu).

    This function is used to interface with ETIMS over Ethernet port. 2. Separate Communication setting into Protocol and Port settings. 3. Describe elements consisting of Protection section in order of the menu shown in LCD. 4. Add CLOSE Function at Normal Frequency restored in Frequency element. 5. Add the description related with STATUS menu omitted in the previous version. 6. Add the description related with MAINTENANCE menu omitted in the previous version. 7. Add Fault Trip(option) in EVENT RECORDER menu. [Jul. 2010] Ver5.10 1. Add contents of RVD(Resistance Voltage Divider), one of Voltage Divider Inputs. [Sep. 2010] Ver5.11 1. Add 6.10. Set Group Change.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    ii ENHANCED TECHNOLOGY

    [Mar. 2011] Ver5.20 1. Add Loss of Phase in PROTECTION menu according to an additional function (option),

    Loss of Phase. 2. Add Supply Outage Measurement as an additional function in menu.

    - Add S-Outage and S-O Dura set-up in RELAY SETUP/ EVENT RECORDER menu. - Add S-Outage Count and S-Outage Event set-up in RELAY SETUP/ CLEAR SAVED

    DATA menu.

    - Add S-OUTAGE COUNTER in MAINTENANCE menu. - Add SUPPLY OUTAGE in EVENT RECORDER menu.

    [Jan. 2012] Ver6.00

    After the Ver6.00, the manual is applied to the EVRC2A-N6(Network type). [Jan. 2012] Ver6.00 1. Change the terms related with battery testing. [Feb. 2012] Ver6.01 1. Add Power Quality set-up in SYSTEM SETUP menu. 2. Change Supply Outage to Power Quality in some menus.

    - Change S-Outage Counter to Power Quality in MAINTENANCE menu. - Change Supply Outage to Power Quality in EVENT RECORDER menu. - Change S-Outage Count and S-Outage Event to P-Quality Count and P-Quality in

    RELAY SETUP/ CLEAR SAVED DATA menu. 3. Add HARMONICS in MAIN MENU/6.METERING menu. [Jun. 2012] Ver6.02 Changed the manual based on EVRC2A-N6 firmware V6.12 upgrading. 1. Section to be rectified in the manual as a result of adding measuring function of

    voltage/current unbalance.

    - Change METERING in 1.2. Summary of Features. - Change Table 2-1. Metering Accuracy in 2.3. Metering Accuracy. - Add 10.1.9. Unbalance. - Change Table 10-1. Metering Accuracy in 10.2. Accuracy.

    2. Section to be rectified in the manual as a result of adding detection function of voltage/current unbalance.

    - Change MONITORING in 1.2. Summary of Features.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    iiiENHANCED TECHNOLOGY

    - Change RECORDER in 1.2. Summary of Features. - Add Power Quality in 2.5. Monitoring. - Change SYSTEM EVENT RECORDER, POWER QUALITY EVENT RECORDER,

    COUNTER in 2.6. Recorder.

    - Change Figure 3-12. Menu Structure Tree in 3.2.1. Main Menu Summary. - Add settings for Unbalance in 6.10. Power Quality. - Add Unbalance Counter in 11.4. Power Quality. - Change 12.2. System Event Recorder. - Change 12.6. Power Quality Event Recorder.

    3. Section to be rectified in the manual as a result of adding Daily Max I and Daily Energy settings.

    - Change 5.2.5. EVENT&ETC. 4. Section to be rectified in the manual as a result of changed range of reclose interval 1.

    - Change Reclose interval 1 in 2.4. Protection Elements/ Reclose Control. - Change Range of Reclose 1 in 7.1. Reclose(79).

    [Aug. 2012] Ver7.00 Changed the manual based on EVRC2A_N6 firmware V6.15 upgrading. 1. Change 5.3. Clock. 2. Change 5.8. Time Set & Display Type.

    - Add Set Type, GMT Sign, GMT Hour, GMT Min and Evt Send Type set-up in RELAY SETUP/ TIME SET & DIS TYPE menu.

    3. Change SEF Pickup Current Setup in 7.4. Sensitive Earth Fault (SEF). 4. Change 9.3. Clock. 5. Change 10.1.4. Synchro Voltage. 6. Change Table 14-1. Warning Events in 14.1. Warning Events. [Nov. 2012] Ver7.10 1. Changed the manual based on EVRC2A_NT firmware V7.04 upgrading.

    - Change 5.2.2.1. DNP 3.0 Protocol Option : Add Time Req(m) set-up in COMMUNICATION / PROTOCOL SETUP / DNP1 and DNP2 menu.

    - Change 5.2.3.1. PORT2-RS232 : Add Parity Bit, Data Bit and Stop Bit set-up in COMMUNICATION/ PORT SETUP/ PORT1-RS232 menu.

    - Change 5.2.5. EVENT&ETC : Add Time Syn Ref and Evt Time Type set-up in COMMUNICATION/ EVENT&ETC menu.

    - Change 5.8. Time Set & Display Type Option : Add Time Syn Ref set-up in RELAY

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    iv ENHANCED TECHNOLOGY

    SETUP / TIME SET&DIS TYPE menu. 2. Changed the manual based on EVRC2A_NT firmware V7.06 upgrading.

    - Change 5.2.2.2. IEC60870-5-101 Protocol Option : Add the setting items in COMMUNICATION / PROTOCOL SETUP / IEC60870-5-101 menu.

    - Change 5.2.2.3. IEC60870-5-104 Protocol Option : Add the setting items in COMMUNICATION / PROTOCOL SETUP / IEC60870-5-104 menu.

    - Change 6.3. Line VL Sensing : Add Install Type set-up in SYSTEM SETUP / LINE VL SENSING menu.

    3. Change the description for SKIP at Fault and Fault I Evt setting in 5.2.5. EVENT&ETC.

    4. Add the Note in 6.4. System Power. [Nov. 2012] Ver7.12 1. Changed the manual based on EVRC2A_NT firmware V7.07 upgrading : Delete Tx Delay

    set-up in COMMUNICATION / PROTOCOL SETUP / DNP1 and DNP2 menu.

    - Change the description for Tx Delay setting in 5.2.2.1. DNP3.0 Protocol Option. 2. Change the description for TX Post Delay and TX Pre Delay in 5.2.3.1. PORT2

    RS232. 3. Change the setting examples of Use of VD(CVD or RVD) in 6.2. Line VS Sensing / 6.2.3.

    Setting Examples. [Dec. 2012] Ver7.12 1. Add the Note in 5.8. Time Set & Display Type Option. 2. Add the Note in 5.2.5. EVENT&ETC. 3. Change Figure 7-33. Non Standard Curves (11, 13, 14, 15, 16, 17, 18) in 7.18. Time

    Overcurrent Curves.

    [Feb. 2013] Ver7.13 1. Add the Notes in 2.4. Protection Elements. 2. Add the Note of SEF Pickup Current Setup in 7.4. Sensitive Earth Fault (SEF). 3. Add the Note of SEF setting in 7.12.3. Cold Load Pickup Setup. 4. Add the Note in 9.4. Control Type.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    vENHANCED TECHNOLOGY

    TABLE OF CONTENTS

    1. INTRODUCTION ........................................................................................................... 1

    1.1. Description .......................................................................................................................... 11.2. Summary of Features .......................................................................................................... 2

    2. TECHNICAL SPECIFICATIONS................................................................................. 5

    2.1. Inputs and Outputs .............................................................................................................. 52.2. Type Withstand Tests ........................................................................................................... 82.3. Metering Accuracy .............................................................................................................. 92.4. Protection Elements........................................................................................................... 112.5. Monitoring ......................................................................................................................... 162.6. Recorder ............................................................................................................................ 192.7. Communications................................................................................................................ 22

    3. USER INTERFACE PANEL ........................................................................................ 23

    3.1. Construction ...................................................................................................................... 243.2. LCD Display ..................................................................................................................... 333.3. Using the LCD Menu ........................................................................................................ 37

    4. SELECT SETBANK ..................................................................................................... 40

    5. RELAY SETUP .............................................................................................................. 41

    5.1. Passcode ............................................................................................................................ 415.2. Communication ................................................................................................................. 425.3. Clock ................................................................................................................................. 765.4. Event Recorder .................................................................................................................. 785.5. Clear Saved Data ............................................................................................................... 795.6. Factory Debug ................................................................................................................... 795.7. Gas Sensor Type ................................................................................................................ 805.8. Time Set & Display Type Option ................................................................................... 80

    6. SYSTEM SETUP ........................................................................................................... 82

    6.1. Current Sensing ................................................................................................................. 826.2. Line VS Sensing ................................................................................................................ 846.3. Line VL Sensing ................................................................................................................ 86

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    vi ENHANCED TECHNOLOGY

    6.4. System Power .................................................................................................................... 886.5. Panel Sleep Time ............................................................................................................... 916.6. Opto Input Set - Option ..................................................................................................... 916.7. Output Relay Set - Option ................................................................................................. 936.8. Loop Control - Option ....................................................................................................... 966.9. Set Group Change - Option ............................................................................................. 1156.10. Power Quality - Option ................................................................................................. 116

    7. PROTECTION ............................................................................................................ 120

    7.1. Reclose (79) ..................................................................................................................... 1227.2. Phase (Fast/Delay) Time Overcurrents (51P) .................................................................. 1287.3. Ground (Fast/Delay) Time Overcurrent (51G) ................................................................ 1327.4. Sensitive Earth Fault (SEF) ............................................................................................. 1367.5. Negative Sequence (Fast/Delay) Time Overcurrent (46) .......................................................... 1387.6. Phase High Current Trip (50P-1) ..................................................................................... 1427.7. Ground High Current Trip (50G-1) ................................................................................. 1447.8. Negative Sequence High Current Trip (46(50)-1) ........................................................... 1467.9. Phase High Current Lockout (50P-2) .............................................................................. 1487.10. Ground High Current Lockout (50G-2) ........................................................................ 1507.11. Negative Sequence High Current Lockout (46(50)-2) ............................................................ 1527.12. Cold Load Pickup .......................................................................................................... 1547.13. Directional Controls (67) ............................................................................................... 1627.14. Undervoltage (27) .......................................................................................................... 1707.15. Overvoltage (59) ............................................................................................................ 1727.16. Frequency(81) ............................................................................................................... 1747.17. Other Element................................................................................................................ 1777.18. Time Overcurrent Curves .............................................................................................. 1807.19. Loss of Phase - Option .................................................................................................. 207

    8. MONITORING ........................................................................................................... 208

    8.1. Demand ........................................................................................................................... 2088.2. Synchronism Check (25) ................................................................................................. 2118.3. Trip Counter .................................................................................................................... 2138.4. Recloser Wear .................................................................................................................. 2158.5. Battery Test ...................................................................................................................... 2178.6. Fault Locator ................................................................................................................... 2188.7. Gas Low Lock Option .................................................................................................. 220

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    viiENHANCED TECHNOLOGY

    8.8. EXT Trip & Lock Option ............................................................................................ 2208.9. Live Load Block Option ............................................................................................... 221

    9. STATUS ........................................................................................................................ 222

    9.1. OPTO Inputs ................................................................................................................... 2229.2. Relay Outputs .................................................................................................................. 2229.3. Clock ............................................................................................................................... 2239.4. Control Type .................................................................................................................... 224

    10. METERING ............................................................................................................... 225

    10.1. Metering Elements ........................................................................................................ 22610.2. Accuracy ........................................................................................................................ 235

    11. MAINTENANCE ....................................................................................................... 237

    11.1. Counters......................................................................................................................... 23711.2. Wear Monitor ................................................................................................................. 23711.3. Output Relay Test .......................................................................................................... 23811.4. Power Quality - Option ................................................................................................. 239

    12. EVENT RECORDER ................................................................................................ 241

    12.1. Waveform Capture ........................................................................................................ 24112.2. System Event Recorder ................................................................................................. 24512.3. Load Profile ................................................................................................................... 24712.4. Diagnostic Event Recorder ............................................................................................ 25012.5. Fault Trip Event Recorder - Option ............................................................................... 25212.6. Power Quality Event Recorder - Option ....................................................................... 254

    13. INSTALLATION ....................................................................................................... 257

    13.1. User Interface Door and Power Switch ......................................................................... 25713.2. Vent and Outer Cover .................................................................................................... 25813.3. Dimensions and Mounting Plan .................................................................................... 25913.4. Earth Wiring Diagram ................................................................................................... 26113.5. Inner Structure ............................................................................................................... 26213.6. Mount Accessories Dimensions .................................................................................... 26313.7. User-Available DC Power ............................................................................................. 26413.8. Terminal Block and Fuses ............................................................................................. 26513.9. EVRC2A Wiring Diagram VD Type .......................................................................... 26613.10. EVRC2A Wiring Diagram - VT Type ......................................................................... 26713.11. Side Panel .................................................................................................................... 268

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    viii ENHANCED TECHNOLOGY

    13.12. Current Inputs Wiring Diagram ................................................................................... 26913.13. VD Wiring Diagram .................................................................................................... 27013.14. VT Wiring Diagram ..................................................................................................... 27113.15. Current and Voltage Inputs Phase Rotation ................................................................. 27213.16. Control Cable Receptacle Pin Descriptions ................................................................ 27313.17. Control Cable Assembling / De-assembling ................................................................ 27513.18. AC Power Receptacle Pin Descriptions ...................................................................... 27513.19. AC Power Cable .......................................................................................................... 27613.20. Fuses ............................................................................................................................ 27613.21. Battery and Control run time ....................................................................................... 27713.22. Charge Circuit ............................................................................................................. 27813.23. Battery Change ............................................................................................................ 27813.24. Battery Protection ........................................................................................................ 27813.25. Communications .......................................................................................................... 27913.26. Communication Cables ............................................................................................... 28113.27. Hardware Block Diagram ............................................................................................ 28213.28. Recloser Trip and Close Circuits ................................................................................. 28313.29. Uninterruptible Power Supply for Trip & Close ......................................................... 28413.30. Main Board .................................................................................................................. 28513.31. Analog Board ............................................................................................................... 28613.32. Recloser EVR Wiring Diagram ................................................................................... 28713.33. Recloser EPR Wiring Diagram .................................................................................... 28813.34. Recloser Current Transformer (CT) ............................................................................ 28913.35. Recloser Voltage Divider (VD) ................................................................................... 28913.36. Recloser Pressure Sensor (Only EVR Type) ............................................................... 29013.37. Recloser 52 contact and 69 contact ............................................................................. 29213.38. Recloser Trip and Close Coil ....................................................................................... 29213.39. Recloser Test Kit ......................................................................................................... 293

    14. MAINTANANCE ...................................................................................................... 294

    14.1. Warning Events ............................................................................................................. 29414.2. Malfunction Events ....................................................................................................... 296

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    1ENHANCED TECHNOLOGY

    1. INTRODUCTION

    1.1. Description

    y EVRC2A with the microprocessor-based digital control technology is designed to provide protective coordination and fault clearance of distribution systems for the continuous best quality of electric service.

    y Remote monitoring and control can be provided by RTU(Remote Terminal Unit - Option)

    which fundamentally installed. y In order to perform the protection function, line voltage and current signal filtered with

    analog filter and digital DFT full-cosin filter is used. y EVRC2A provides protection, control, and monitoring functions with both local and remote.

    It also displays the present trip/alarm conditions, and measured system parameters. y Recording of past trip, alarm or control events, maximum demand levels, and energy

    metering is also performed. y Users can operate Close and Trip, and also control EVRC2A with key buttons on the user

    interface panel; Protection Enabled, Ground Enabled, SEF Enabled, Reclose Enabled, Control Locked, Remote enabled, Alternate-settings, Program 1, Program 2, Hot line tag.

    y Users can manage the Recloser interface software using a portable PC for modification of

    settings, acquisition of event data, and management of operation history. y EVRC2A contains many T-C characteristic curves developed by IEEE C37.112, IEC255-3,

    McGraw Edison, and KEPCO to provide fully protective coordination for the continuous best quality of electric distribution. Users can select any time of current curve simply by programming and modifying.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    2 ENHANCED TECHNOLOGY

    1.2. Summary of Features

    PROTECTION y Phase Instantaneous Over-current Element y Phase Time Over-current Elements y Phase Definite Time High Current Lockout Element y Ground Instantaneous Over-current Element y Ground Time Over-current Elements y Ground Definite Time High Current Lockout Element y Sensitive Earth Fault Elements y Negative Instantaneous Over-current Element y Negative Time Over-current Elements y Negative Definite Time High Current Lockout Element y Phase, Ground, Sensitive Earth and Negative Sequence Directional Control y Automatic Reclosing(Up To 4 Shots) y Cold Load Pickup with Voltage Control y Sequence Coordination Control y Two Under-voltage Elements y Two Over-voltage Elements y Under-frequency Element y Over-frequency Element y Loop Control - Option y Loss of Phase - Option

    METERING y Phase, Ground and Sensitive Ground Current and Phasors y Line and Phase Voltage and Phasors(Source Side and Load Side) y Current and Voltage Symmetrical Component Phasors y Frequency Magnitude and Rate y Synchronizing Voltage, Phasor and Frequency y Synchronizing Delta, Delta and Delta Leg y Single and Three Phase Power(MW, Mvar, MVA, PF) y Energy(MWh, Mvarh) y Maximum Demand(Ia, Ib, Ic, MW, Mvar, MVA) y Voltage and current harmonics - Option y Voltage and current unbalance - Option

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    3ENHANCED TECHNOLOGY

    MONITORING y Fault Locator y Demand trip and alarm(Ia, Ib, Ic, Ig, I2) y Trip Counter Limit y Synchronism Check y Recloser main contact Wear(Per Phase) y Recloser Operation Failure y Voltage Transformer Failure y Battery Automatic Load Test y Breaker Failure with Current Supervision y Power Quality - Option y Recloser Gas Over and Low pressure - Option

    NOTE : According to a recloser type, there may be no gas pressure monitoring.

    COMMUNICATIONS y Front Panel PORT1 RS232 Serial Port : EVRC2A interface software y Side panel PORT2 RS232 Serial Port : EVRC2A interface software , DNP 3.0, MODBUS or

    IEC60870-5-101 Protocol - Option y Side panel PORT3 RS485 or R232* Serial Port : DNP 3.0, MODBUS or IEC60870-5-101

    Protocol Option y Side panel PORT4 RJ45 Port : DNP 3.0, MODBUS or IEC60870-5-104 Protocol and

    EVRC2A interface software Option

    NOTE : The Port3 type of EVRC2A-N is a fixed RS485 port. However, the Port3 type of EVRC2A-N6,NT can be selected as RS485 or RS232 by a user. In order to use RS485 port for EVRC2A-N6,NT, the Pin4 and Pin5 of RS485 should be connected.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    4 ENHANCED TECHNOLOGY

    RECORDER y Trip and fault counter y Supply outage counter and time Option y Sag/Swell detection counter Option y Voltage and current unbalance detection counter - Option y System event recorder - last 2048 events y Diagnostic event recorder - last 512 events y Load profile recorder - last 213days y Fault Waveform - 15 cycles 32 events y Fault trip event recorder - last 512 events - Option y Power Quality event recorder - last 512 events - Option USER INTERFACE y Fault indicators y Manual Battery Load Test: Battery Voltage and Charge Voltage y Dual Functional keypads y 204 Character Display(LCD or VFD : Vacuum Fluorescent Display) y 32 LED indicators - Fault indications, sequence status, battery status, etc y RS232 port y Context Help Messages y Access Security(Passcode)

    AUXILIARY OUTPUTS - Option y 7 Programmable Relays y 1 Programmable Alarm Relay

    AUXILIARY INPUTS - Option y 8 Opto-isolated Programmable Inputs

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    5ENHANCED TECHNOLOGY

    2. TECHNICAL SPECIFICATIONS 2.1. Inputs and Outputs

    Systems y 3phase-3wire or 3phase-4wire, 38 maximum, 800 Amp maximum

    Frequency y 50 / 60 system and ABC/ACB phase rotation

    Control Voltage Input y AC Voltage Input 110V/220Vac or other voltage (+10%,-15%) y Nominal Battery Voltage : 24Vdc y Based on user requirement, prepare 110V/220V Selectable Switch - Option

    User available DC power Output - Option y DC Power Voltage : 12, 15, 24Vdc y DC Power Continuous : 40W y DC Power for 60Sec : 60W

    Voltage Divider Inputs (VD) - Standard Capacitor Voltage Divider Inputs (CVD) Only EVR y Maximum Input Voltage : 5V y Burden : 2e-6 VA y System Voltage : 15, 27, 38 y Capacitor value

    - Phase Capacitor value : 20 Resistance Voltage Divider Inputs (RVD) Only EPR y Maximum Input Voltage : 5V y Burden : Bow 0.0015 VA y System Voltage : 15, 27 y Resistance value

    - Phase Resistance value : 100M

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    6 ENHANCED TECHNOLOGY

    Voltage Transformer Inputs (VT) - Option y Voltage Inputs EVRC2A-N : 4 Channel(VA, VB, VC and VL) EVRC2A-N6,NT : 6 Channel

    - Source Voltage 1 VA,VB,VC - Source Voltage 2 VR,VS,VT

    y Input Voltage Range : Phase-Neutral Continuous

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    7ENHANCED TECHNOLOGY

    Control Output Contacts - Option y Control Outputs 8 Channel Normal Open 5 Channel Normal Close 2 Channel ALARM 1 Channel

    y 300Vac / 350Vdc Varistor for differential surge protection y Operate / Release time : < 5ms at +20(+68) y Maximum operating power

    (L/R=7ms) 125Vdc 0.1A 48Vdc 0.8A 24Vdc 3A

    (cos=0.4) 250Vac 3A 125Vac 5A

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    8 ENHANCED TECHNOLOGY

    2.2. Type Withstand Tests

    Dielectric Strength y CT inputs, VT inputs, Control Power inputs, Opto-isolated inputs and Relay outputs 2(60) for 1 minute

    Impulse Voltage y IEEE C62.45 (1992) Withstand Capability of Relay Systems to Radiated Electromagnetic

    Interference Transceivers, 6(1.250), 3(820)

    Surge Withstand Capability y IEEE C37.90.1 - 1989 IEEE SWC Tests for Protective Relays and Relay Systems

    (3 oscillatory 1 to 1.5, 5 fast transient 1.250) y IEEE C37.90.2 - 1987 IEEE Trial-Use Standard, Withstand Capability of Relay Systems to

    Radiated Electromagnetic Interference from Transceivers, 10 V/m

    (150 and 450, 5 W transmitter 10)

    Vibration Test y IEC 255-21-1 - 1988 Electrical relays, Part 21 : Vibration, shock, bump, and seismic tests on

    measuring relays and protection equipment, Section One - Vibration tests (sinusoidal), Class 2.

    Control Operating Temperature y Operating range : -25+70(-13+158) y LCD : -20+70(-4+158) - standard y VFD : -40+85(-40+185) - option(Vacuum Fluorescent Display)

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    9ENHANCED TECHNOLOGY

    2.3. Metering Accuracy

    The harmonic components of current and voltage are removed from the input voltage and current parameters, so all measurements based on these quantities respond to the fundamental components only except the measurement of harmonics.

    Table 2-1. Metering Accuracy(1/2)

    Measurements Parameters Unit Accuracy Range

    CURRENT

    Phase A RMS Current

    Phase B RMS Current

    Phase C RMS Current

    Phase G RMS Current

    Phase SEF RMS Current

    A 1% of 2CT 20CT

    VOLTAGE

    AN (AB) RMS Voltage

    BN (BC) RMS Voltage

    CN (CA) RMS Voltage

    RN (RS) RMS Voltage

    SN (ST) RMS Voltage*

    TN (TR) RMS Voltage*

    1%

    SYMMETRICAL

    COMPONENTS

    I1, I2, 3I0

    V1, V2, 3V0

    A

    1% of 2CT

    1%

    POWER FACTOR Phase A, B, C

    3 Phase Rate 0.02 1.000 to 1.000

    3REAL POWER Phase A, B, C

    3 Phase MW 2% 32.000 to 32.000

    3REACTIVE POWER

    Phase A, B, C

    3 Phase MVar 2% 32.000 to 32.000

    3APPARENT POWER

    Phase A, B, C

    3 Phase MVA 2% 32.000 to 32.000

    WATT-HOURS Phase A, B, C

    3 Phase MWH 2% 32000 to 32000

    VAR-HOURS Phase A, B, C

    3 Phase MVarH 2% 32000 to 32000

    DEMAND

    Phase A/B/C/RG Current

    A/B/C, 3 Real Power A/B/C, 3 Reactive Power

    A

    MW

    MVar

    2% 2% 2%

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    10 ENHANCED TECHNOLOGY

    Table 2-1. Metering Accuracy(2/2)

    Measurements Parameters Unit Accuracy Range

    FREQUENCY A-N (A-B) Source Voltage

    R-N (R-S) Load Voltage 0.02 40.00~70.00

    HARMONICS

    1st~7th Harmonic of Current

    1st~7th Harmonic of Voltage THD of Current

    THD of Voltage

    1% 1% 3% 3%

    0% to 100%

    0% to 100%

    0% to 100%

    0% to 100%

    UNBALANCE

    Voltage unbalance(V2/V1) in source side

    Voltage unbalance(V2/V1) in load side

    Current unbalance(I2/I1)

    %

    2% 2% 2%

    0% to 999%

    0% to 999%

    0% to 999%

    If the VT connection type is set to delta, all single phase voltage quantities are displayed as zero.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    11ENHANCED TECHNOLOGY

    2.4. Protection Elements

    Phase/Ground/Negative Sequence Time Overcurrent Protection Pickup Level .............................................................. OFF, 10 to 1600 in steps of 1A Dropout Level ........................................................... 96 to 98% of Pickup Curve Type ANSI : Moderately, Normally, Very, Extremely, Short Inverse, Definite Time (1s ,10s) IEC : Standard, Very, Extremely, Long, Short Inverse ESB : Normally, Very, Long Very Inverse User programmable curves : U1, U2, U3, U4 McGraw-Edison : Non Standard Curves 37

    Time dial ................................................................... 0.05 to 15.00 in steps of 0.01 Time adder ................................................................. 0.00 to 10.00 in steps of 0.01s Minimum Response time .......................................... 0.00 to 10.00 in steps of 0.01s Reset Type ................................................................. Instantaneous/Linear Low Set Definite Time .............................................. 1 ~ 600 in steps of 1s (supported from Ver 6.03 of EVRC2A-N6,NT) Pickup Level Accuracy.............................................. 5%

    Timing Accuracy ....................................................... 5% of trip time or 20 Phase/Ground/Negative Sequence Instantaneous Overcurrent Protection Pickup Level .............................................................. OFF, 10 to 20000 in steps of 1A Dropout Level ........................................................... 95 to 98% of Pickup Time Delay ................................................................ 0.00 to 10.00 in steps of 0.01s Active Trip ................................................................ 1 to 5 in steps of 1 Pickup Level Accuracy.............................................. 5%

    Timing Accuracy ....................................................... at 0 time delay (50 max) 5% of trip time or 20

    Phase/Ground/Negative Sequence High Current Lockout Protection Pickup Level .............................................................. OFF, 10 to 20000 in steps of 1A Dropout Level ........................................................... 95 to 98% of Pickup Time Delay ................................................................ 0.00 to 10.00 in steps of 0.01s Active Trip ................................................................ 1 to 5 in steps of 1 Pickup Level Accuracy.............................................. 5%

    Timing Accuracy ....................................................... at 0 time delay (50 max) 5% of trip time or 20

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    12 ENHANCED TECHNOLOGY

    Sensitive Earth Definite Time Overcurrent Protection Pickup Level*NOTE ..................................................... OFF, 4 to 160 in steps of 1A(prior to Ver 6.15)

    OFF, 1 to 160 in steps of 1A(from Ver 6.15) Dropout Level ........................................................... 95 to 98% of Pickup Time Delay ................................................................ 0.00 to 600.00 in steps of 0.01s Pickup Level Accuracy .............................................. 5%

    Timing Accuracy ....................................................... at 0 time delay (50 max) 5% of trip time or 20

    NOTE As per the users request, for the products that are dispatched with ZCT installed, the Pickup Level setting range of the protection element is OFF, 0.1 to 16.0 in steps of 0.1A. To check whether the product is dispatched with ZCT installed, check MAIN MENU/ STATUS/ CONTROL TYPE menu.

    Reclose Control Operations to Lockout - phase trip ............................ 1 to 5 in steps of 1 Operations to Lockout - ground trip .......................... 1 to 5 in steps of 1 Operations to Lockout - SEF trip .............................. 1 to 5 in steps of 1 Operations to Lockout - Negative Seq trip ............... 1 to 5 in steps of 1 Operations of Fast curve - phase trip ......................... 0 to 5 in steps of 1 Operations of Fast curve - ground trip ...................... 0 to 5 in steps of 1 Operations of Fast curve - Negative Seq trip ........... 0 to 5 in steps of 1 Reclose interval 1 ...................................................... 0.50 to 600.00 in steps of 0.01(prior to Ver 6.11)

    0.10 to 600.00 in steps of 0.01(from Ver 6.11) Reclose interval 2 ...................................................... 1.00 to 600.00 in steps of 0.01 Reclose interval 3 ...................................................... 1.00 to 600.00 in steps of 0.01 Reclose interval 4 ...................................................... 1.00 to 600.00 in steps of 0.01 Reset time for Auto Reclose Cycle ............................ 1.00 to 600.00 in steps of 0.01 Reset time from lockout ............................................ 1.00 to 600.00 in steps of 0.01 Timing Accuracy ....................................................... 5%

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    13ENHANCED TECHNOLOGY

    Cold Load Pickup Blocking Cold Load Pickup Trigger ......................................... 52A(Close) or Load Current Phase Pickup Level ................................................... 10 to 20000 in steps of 1A Ground Pickup Level ................................................ 10 to 20000 in steps of 1A SEF Pickup Level*NOTE .............................................. 4 to 2000 in steps of 1A Negative Seq Pickup Level ...................................... 10 to 20000 in steps of 1A Reset Level ................................................................ 95 to 98% of Nominal Pickup Outage Time .............................................................. 0.00 to 600.00 in steps of 0.01s Restore Minimum Time ............................................ 0.00 to 600.00 in steps of 0.01s Reset Time ................................................................. 0.00 to 600.00 in steps of 0.01s Cold Load Pickup Multiplier ..................................... OFF, 1.0 to 5.0 in steps of 0.1 Cold Load Pickup Time Duration ............................. 1 to 720 in steps of 1min Pickup Level Accuracy............................................. 5%

    Timing Accuracy ....................................................... at 0 time delay (50 max) 5% of trip time or 20

    NOTE As per the users request, for the products that are dispatched with ZCT installed, the SEF Pickup Level setting range of the protection element is 0.4 to 200.0 in steps of 0.1A. To check whether the product is dispatched with ZCT installed, check MAIN MENU/ STATUS/ CONTROL TYPE menu.

    Phase Directional Control Polarizing Voltage ..................................................... Positive Sequence Voltage V1 Maximum Torque Angle ........................................... 0 to 359 in steps of 1 Minimum Polarizing Voltage .................................... 0.00 to 1.25 in steps of 0.01 x VT Angle Accuracy ......................................................... 2 Internal Operation Delay ........................................... 1.5cycle

    Ground/Sensitive Earth Directional Control Polarizing Voltage ..................................................... Zero Sequence Voltage Vo For voltage element polarizing the source VTs must be connected in Wye Maximum Torque Angle ........................................... 0 to 359 in steps of 1 Minimum Polarizing Voltage .................................... 0.00 to 1.25 in steps of 0.01 x VT Angle Accuracy ......................................................... 2 Internal Operation Delay ........................................... 1.5cycle

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    14 ENHANCED TECHNOLOGY

    Negative Directional Control Polarizing Voltage ..................................................... Negative Sequence Voltage V2 Maximum Torque Angle ............................................ 0 to 359 in steps of 1 Minimum Polarizing Voltage .................................... 0.00 to 1.25 in steps of 0.01 x VT Angle Accuracy ......................................................... 2 Internal Operation Delay ........................................... 1.5cycle

    Undervoltage 1/2 Protection Pickup Level .............................................................. 0.00 to 1.25 in steps of 0.01 x VT Minimum Voltage ...................................................... 0.00 to 1.25 in steps of 0.01 x VT Dropout Level ........................................................... 102 to 105% of Pickup Time Delay ................................................................ 0.00 to 600.00 in steps of 0.01s Active Phases ............................................................ Any One/Any Two/All Three

    Timing Accuracy ....................................................... 20

    Overvoltage 1/2 Protection Pickup Level .............................................................. 0.00 to 1.25 in steps of 0.01 x VT Dropout Level ........................................................... 95 to 98% of Pickup Time Delay ................................................................ 0.00 to 600.00 in steps of 0.01s Active Phases ............................................................ Any One/Any Two/All Three

    Timing Accuracy ....................................................... 20

    Under/Over frequency Minimum Voltage ...................................................... 0.00 to 1.25 in steps of 0.01 x VT in Phase A Minimum Current ...................................................... 10 to 1600 in steps of 1A in Phase A

    Under frequency Pickup Level .................................. 40.00 to 60.00 in steps of 0.01 Over frequency Pickup Level .................................... 50.00 to 70.00 in steps of 0.01 Dropout Level ........................................................... at VT Pickup 0.02 at VD Pickup 0.05 Under/Over frequency Time Delay ........................... 0.00 to 600.00 in steps of 0.01s(definite time) Normal frequency CLOSE function .......................... OFF/ON Normal frequency CLOSE time delay ...................... 0.0 to 6000.0 in steps of 0.1sec

    Level Accuracy .......................................................... at VT 0.02, at VD 0.05 Timing Accuracy ....................................................... 2cycle

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    15ENHANCED TECHNOLOGY

    Loss of Phase - Option Pickup Level .............................................................. 0.00 to 1.25 in steps of 0.01 x VT Dropout Level ........................................................... 102 to 105% of Pickup Time Delay ................................................................ 0.10 to 100.00 in steps of 0.01s

    Time Accuracy .......................................................... 20

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    16 ENHANCED TECHNOLOGY

    2.5. Monitoring

    Demand Measured Values ........................................................ Phase A/B/C/G Current(A)

    Phase A/B/C/G 3 Real Power(MW) Phase A/B/C/G 3 Reactive Power(Mvar) Measurement Type .................................................... Thermal Exponential/Rolling Demand Time Constant ........................................................... 5, 10, 15, 20, 30 or 60 min. Phase Pickup Level ................................................... OFF, 10 to 1600 in steps of 1A Ground Pickup Level................................................. OFF, 10 to 1600 in steps of 1A Negative Seq Pickup Level ...................................... OFF, 10 to 1600 in steps of 1A Level Accuracy .......................................................... 5%

    Synchronism Check Dead Voltage Maximum ............................................ 0.00 to 1.25 in steps of 0.01 x VT Live Voltage Maximum ............................................. 0.00 to 1.25 in steps of 0.01 x VT Maximum Voltage Difference ................................... 0.00 to 1.25 in steps of 0.01 x VT Maximum Angle Difference ...................................... 0 to 100 in steps of 1

    Maximum Frequency Difference .............................. 0.00 to 5.00 in steps of 0.01 Synchro-check Phase ................................................. R(AB), S(CB), T of Load side

    Trip Counters Number of Pickup Limit............................................ 1 to 20000 in steps of 1 Trip Counter Set ........................................................ 0 to 10000 in steps of 1

    Recloser Wear Pickup Wear............................................................... 0 to 100% in steps of 0.1

    Rate System ............................................................... 15, 27, 38 Rate Interrupt() ...................................................... 5.0 to 50.0 in steps of 0.1 Number of Maximum Interruption ............................ 1 to 999 in steps of 1 Set Phase A Wear ....................................................... 0.0 to 100.0 % in steps of 0.1 Set Phase B Wear ....................................................... 0.0 to 100.0 % in steps of 0.1 Set Phase C Wear ....................................................... 0.0 to 100.0 % in steps of 0.1

    Battery Test Period for automatically check a battery ................... OFF, 1 to 7 in steps of 1day

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    17ENHANCED TECHNOLOGY

    Fault Locator Total Length of Feeder .............................................. 0.1 to 99.9 of 0.1km Real impedance of the feeder positive seq. ............... 0.1 to 6000.0 of 0.1ohms Imaginary impedance of the feeder positive seq. ...... 0.1 to 6000.0 of 0.1ohms Real impedance of the feeder zero seq. ..................... 0.1 to 6000.0 of 0.1ohms Imaginary impedance of the feeder zero seq ............. 0.1 to 6000.0 of 0.1ohms

    Power Quality - Option Detect Function of Supply Outage. ........................... DISABLE, ENABLE Supply Outage Duration ............................................ 1 to 3600 in steps of 1s Detect Function of Voltage Sag. ................................ DISABLE, ENABLE Detect Level of Voltage Sag. ..................................... 0.30 to 0.95 in steps of 0.01 x VT Detect Time of Voltage Sag. ...................................... 1 to 60 in steps of 1cycle Detect Function of Voltage Swell. ............................. DISABLE, ENABLE Detect Level of Voltage Swell. .................................. 1.05 to 1.25 in steps of 0.01 x VT Detect Time of Voltage Swell. ................................... 1 to 60 in steps of 1cycle Detect Function of Voltage Unbalance. ..................... DISABLE, ENABLE Detect Level of Voltage Unbalance ........................... 1 to 100 in steps of 1% Detect Time of Voltage Unbalance ............................ 0.1 to 60.0 in steps of 0.1s Detect Function of Current Unbalance. ..................... DISABLE, ENABLE Detect Level of Current Unbalance ........................... 1 to 100 in steps of 1% Detect Time of Current Unbalance ............................ 0.1 to 60.0 in steps of 0.1s Limit Current to Detect Current Unbalance .............. 1 to 630 in steps of 1A Level Accuracy .......................................................... 5%

    NOTE : The setting for voltage/current unbalance is supported from version 6.12 of EVRC2A-N6,NT.

    Gas Low Lock - Option Pickup Low Level ..................................................... 0.1bar

    External Trip & Lock - Option Use Input Port ........................................................... Opto Input 1,2,3,4,5,6,7 or 8 Reset Method ............................................................ LOCAL, LOCAL&REMOTE

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    18 ENHANCED TECHNOLOGY

    Live Load Blocking - Option Blocking Pickup Voltage ........................................... 0.10 to 0.90 in steps of 0.01 x VT in Load side Dropout Level ........................................................... 95 to 98% of Pickup Time Delay ................................................................ 0.00 to 600.00 in steps of 0.01s

    Timing Accuracy ....................................................... 20

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    19ENHANCED TECHNOLOGY

    2.6. Recorder

    WAVEFORM CAPTURE y Trigger Source Protection pickup Elements Trip command active

    y Data Channels 5 currents, 4 voltages, 85 logic input states, 8ch output relays, 8ch Input

    y Sample Rate : 16 per cycle y Trigger Position : 1 to 15cycle y Storage capacity : 32 events with 15cycle

    SYSTEM EVENT RECORDER y Trigger Source Protection Elements 52A Contact Sequence status Front panel control AC supply External control Fail operation External input status System alarm V1(Source), V2(Load) Power Quality detect, etc.

    y Trigger Time : each 1/4 cycle y Trigger type : Pick up and Dropout y Storage Capacity : Last 2048 Events

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    20 ENHANCED TECHNOLOGY

    DIAGNOSTIC EVENT RECORDER y Trigger Source System Power(AC, Battery, 12V, +5V) A/D Conversion(A/D Fail, Reference Voltage1, Reference Voltage 2) Sleep Mode Power Down Mode(Charge Volt High Alarm) Setting Change Gas Status Alarm Status, etc. NOTE : According to a recloser type, there may be no diagnosis of gas pressure status.

    y Trigger Time : each 1/4 cycle y Trigger type : Pick up and Dropout y Storage Capacity : Last 512 Events

    LOAD PROFILE y Trigger Source Demand Current(A, B, C, G) Demand Real Power(A, B, C, 3) Demand Reactive Power(A, B, C, 3) Demand Power Factor(3) Demand Energy( 3) Trigger Time : 5, 10, 15, 20, 30, 60minute

    y Storage Capacity : Total 5120 Events, 213days/60min.

    FAULT TRIP EVENT RECORDER - Option y Trigger Source Trigger elements : A,B,C,G, SEF phase and Negative Sequence Current[A] each phase when fault occurs

    y Trigger Time : each 1/4 cycle y Trigger type : fault occurrence y Storage Capacity : Last 512 Events

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    21ENHANCED TECHNOLOGY

    POWER QUALITY EVENT RECORDER - Option y Trigger Source Trigger elements : Source, Load

    y Trigger Time : each 1/4 cycle y Trigger type : supply outage occurrence, sag occurrence, swell occurrence, voltage unbalance

    occurrence, current unbalance occurrence NOTE : The detection of voltage/current unbalance is supported from version 6.12 of

    EVRC2A-N6,NT.

    y Storage Capacity : Last 512 Events COUNTER y Trip Counter : 0 to 65,534 y Fault Counter : 0 to 65,534 y System Restart Counter : 0 to 65,534 y Supply Outage Counter : 0 to 60,000 - Option y Supply Outage Time : 0 to 9,999 hours - Option y Sag Counter : 0 to 60,000 - Option y Swell Counter : 0 to 60,000 Option y Voltage Unbalance(Source Side) Counter : 0 to 60,000 - Option y Voltage Unbalance(Load Side) Counter : 0 to 60,000 - Option y Current Unbalance Counter : 0 to 60,000 - Option

    RECLOSER WEAR y Phase A Wear : 0.0 to 100.0% y Phase B Wear : 0.0 to 100.0% y Phase C Wear : 0.0 to 100.0%

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    22 ENHANCED TECHNOLOGY

    2.7. Communications

    Table 2-2. Communications

    Front Panel Port1 RS232, 57600bps, No Parity, 8 Data Bits, 1 Stop bit

    EVRC2A Interface software

    Side panel Port2 - Option RS232, 1200-19200bps, No Parity, 8 Data bits, 1 Stop bit

    DNP 3.0, Modbus or IEC60870-5-101 Protocol and EVRC2A Interface software

    Side panel Port3 Option

    RS485 or RS232*, 1200-19200bps, No Parity, 8 Data bits, 1 Stop bit

    DNP 3.0, Modbus or IEC60870-5-101 Protocol and EVRC2A Interface software

    Side panel Port4 Option RJ-45, 10BASE-T/100BASE-T

    DNP 3.0, Modbus or IEC60870-5-104 Protocol, and EVRC2A Interface software

    NOTE : The Port3 type of EVRC2A-N is a fixed RS485 port. However, the Port3 type of EVRC2A-N6,NT can be selected as RS485 or RS232 by a user. In order to use RS485 port for EVRC2A-N6,NT, the Pin4 and Pin5 of RS485 should be connected.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    23ENHANCED TECHNOLOGY

    3. USER INTERFACE PANEL This section describes the User Interface Panel (front-panel) The User interface Panel control is used for; y Directly control the recloser y Verify control status y View system status y View metering value y View information stored in the EVRC2A unit y View and change the EVRC2A settings

    Figure 3-1. User Interface Panel

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    24 ENHANCED TECHNOLOGY

    3.1. Construction

    Panel consists of 8 sections as below; y Operation section y Local control section y Fault indication section y Voltage elements section y Sequence status section y System diagnostic section y Battery test section y Menu control section

    3.1.1. Operation Section

    OPEN Pressing OPEN push-button sends a trip signal to the Recloser.

    CLOSE Pressing CLOSE push-button sends a close signal to the Recloser. Units operating with firmware version 2.18 or later have a feature of Close Time Delay. The Close Time Delay allows a delay of 0.00 to 600.00 seconds after pressing the close push-button before closing the recloser.

    POSITION LED Indicates the position of the Recloser. Position indicator is based on the Recloser 52a contacts.

    Figure 3-2. Operation Section

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    25ENHANCED TECHNOLOGY

    3.1.2. Local Control Section

    All indicators show status of Control function. The indicators are continuously ON when the control function is enabled and the indicators are continuously OFF when control function is

    DISABLE. The push-button toggles Enable/Disable.

    PROTECTION ENABLED All Protection elements are enabled

    GROUND ENABLED Ground Protection elements are enabled

    SEF ENABLED SEF Protection elements are disabled

    RECLOSE ENABLED Reclose function is enabled

    CONTROL LOCKED Front panel function is unlocked

    REMOTE ENABLED Remote control is enabled

    ALTERNATE SETTINGS Alternate setting is disabled Primary Setting is enabled

    PROGRAM 1 Program 1 function is disabled

    PROGRAM 2 Program 2 function is disabled

    HOT LINE TAG Hot Line Tag function is disabled

    Figure 3-3. Local Control Section

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    26 ENHANCED TECHNOLOGY

    Protection Enabled When illuminated, all protection elements are enabled. The protection enabled condition can be disabled by pressing the Protection Enabled push button on the front panel. The front panel LED will illuminate on each source of all protection enabling.

    NOTE : Although all protection elements are enabled, ground protection elements and SEF element are operated individually.

    Ground Enabled When Ground Enable LED is ON, the ground over-current elements are enabled. The enabled Ground can be disabled by pressing the Ground Enabled push-button on the front panel.

    SEF Enabled When SEF Enable LED is on, the Sensitive Earth Fault(SEF) element is enabled. The enabled SEF can be disabled by pressing the SEF Enabled push-button on the front panel.

    Reclose Enabled When Reclose Enable LED is on, the reclose(79) element is enabled. The enabled reclose element can be disabled by pressing the Recloser Enabled push-button on the front panel.

    Control Locked When Control Locked LED is on, all functions in operation section and all functions in Local control section are locked. These can be unlocked by pressing the Control Locked push-button on the front panel.

    NOTE : Even though Control Locked function is locked, OPEN, Lamp Test, Battery Load Test and menu control section can be normally operated.

    Remote Enabled When Remote Enabled LED is on, all remote control functions (e.g. SCADA system) are enabled. This can be disabled by pressing the Remote Enabled push-button on the front panel. SCADA control refers to supported communications protocol such as DNP3.0.

    Alternate Enabled When Alternate Enabled LED is on, the Alternate setting is activated. When Alternate Enabled LED is off, the primary setting is activated.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    27ENHANCED TECHNOLOGY

    Program 1 A function installed in Program1 is operated when Program1 LED is On. Depending on users request, Manufacturer sets a function in Program1.

    Program 2 A function installed in Program2 is operated when Program2 LED is On. Depending on users request, Manufacturer sets a function in Program2.

    Hot Line Tag When Hot Line Tag LED is on, the Hot Line Tag function is enabled.

    3.1.3. Fault Indication Section

    Indicates current on the phase or neutral lines is above the minimum pickup setting as programmed in any of the EVRC2A over-current elements. y Phase Instantaneous over-current Elements y Phase Time over-current Elements y Phase Definite Time High Current Lockout Element y Ground Instantaneous over-current Elements y Ground Time over-current Elements y Ground Definite Time High Current Lockout Element y Sensitive Ground Time Over-current Elements y Negative Instantaneous over-current Elements y Negative Time over-current Elements y Negative Definite Time High Current Lockout Element y Phase, Neutral, Ground, Sensitive Ground, and Negative Sequence Directional Control

    Figure 3-4. Fault Indication Section

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    28 ENHANCED TECHNOLOGY

    TRIP TYPE y INST : Shows high current trip (50-1) y DELAY : Shows delay trip(51) y HIGH CURR : Shows high current lockout(50-2)

    FAULT INDICATION y A, B, C : Indicates an over-current fault has occurred on one of the phase lines y G : Indicates an over-current fault has occurred on the neutral line y SEF : Indicates a sensitive earth fault has occurred on the neutral line y FI RESET : Reset fault indication/Lamp test

    3.1.4. Voltage Elements Section

    Indicates that voltage pickup element is operated. y Two Under voltage Elements y Two Over voltage Elements y Synchronism Element y Under/Over frequency Element

    27 : Under voltage pickup 59 : Over voltage pickup 25 : Synchronism check pickup 81 : Under/Over frequency pickup

    Figure 3-5. Voltage Elements Section

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    29ENHANCED TECHNOLOGY

    3.1.5. Sequence Status Section

    Indicates the current status of programmed sequence procedure.

    RESET : Sequence shows resetting CYCLE : Sequence shows running LOCKOUT : Sequence shows lockout

    Figure 3-6. Sequence Status Section

    3.1.6. System Diagnostic Section

    Indicates Diagnostic status of the EVRC2A. Control run indicates (green) the EVRC2A has successfully passed its internal diagnostic test. Self Check (Red) indicates the EVRC2A has failed in its internal diagnostic test.

    CONTROL RUN Status of EVRC2A systems shows normal

    SELF CHECK Status of EVRC2A systems shows warning

    Figure 3-7. System Diagnostic Section

    NOTE : Control Run LED is blinking when system functional status is normal.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    30 ENHANCED TECHNOLOGY

    3.1.7. Battery Test Section

    Indicates the system power status of the EVRC2A. AC supply indicates the EVRC2A has external power source. Charge indicates the EVRC2A is charging Battery. Discharge indicates the EVRC2A has failed in battery load testing. AC SUPPLY Status of supplying the external AC power. CHARGE Status of charging the battery. DISCHARGE Status of discharged battery.

    Figure 3-8. Battery Test Section

    BATTERY LOAD TEST Push-button for battery load test. LCD displays during Battery Load Testing.

    LOAD(V) : On Test, Battery is disconnected from the

    Figure 3-9. Battery Test Mode

    charge circuit and connect the battery with load resistor and check the battery. Load resistor shall be connected with AC supply.

    CHARGE[V] : Display the voltage of charge circuit. STATUS : Display Battery status and charge circuit status.

    - B-OK : When the battery voltage is between 21V ~ 28V - B-HI : When the battery voltage is over 28V - B-DF : When the battery voltage is between 15V ~ 21V - B-LO : When the battery voltage is below 15V - C-OK : When the charge circuit is between 25V ~29V - C-HI : When the charge circuit is over 29V - C-LO : When the charge circuit is below 25V

    NOTE : All information above is provided by remote mode.

    [BATTERY TEST MODE] LOAD(V) : 25.00 CHARGE(V): 26.50 STATUS : B-OK C-OK

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    31ENHANCED TECHNOLOGY

    3.1.8. Menu Control Section The Liquid Crystal Display (LCD) of the EVRC2A displays four lines of twenty characters each.

    LCD DISPLAY 4x20 Characters display

    CONTROL KEYS [] [] [] [] Arrow keys are used for moving through the menu window and the changing of the setting value

    [] (METER) : Up arrow key is used to move to the meter menu, operable in menu starting mode [] (AWAKE) : Down arrow key is used for panel awake from sleep mode [] (EVENT) : Left arrow key is used to move to the event menu, operable in menu starting mode [] (SET) : Right arrow key is used to move to the setting menu, operable in menu starting mode [FUN] : To move to main menu when present mode is in starting mode [ESC] : To cancel for data input mode or return the display to the previous level [ENT] : To select sub menu or data input

    Figure 3-10. Menu Control Section

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    32 ENHANCED TECHNOLOGY

    [FUN] Key Press [FUN] key to enter Main menu for displaying information or changing settings. [FUN] key is also used to display a help message in setting change mode and to cancel the help message display. [ESC] Key The ESC key can be used to cancel data input mode and return to the previous menu. [ENT] Key ENT key is used to select a menu by using Up and Down arrow key. Enter key is also used to accept a new setting by using Up or down arrow key.

    [] [] Key Use the left and right arrow keys to move cursor in the data input mode and change display message.

    [] [] Key Use Up and Down arrow keys to move through the various menus and to decrease or increase value in the data input mode.

    PORT1 PORT1 is the port to communicate whit an Interface Software. Communication frame between EVRC2A and a master can be monitored and saved by using DNP Frame Monitor menu of the Interface Software.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    33ENHANCED TECHNOLOGY

    3.2. LCD Display

    y 20 x 4 Character Display(LCD or VFD : Vacuum Fluorescent Display) y All menus are arranged in rotation algorithm. y When cursor is in top menu, if you press [] key, you go to the bottom menu due to Rotation

    Menu Algorithm. y Displays Context Help Message.

    3.2.1. Main Menu Summary EVRC2A has 6 Setting Menu BANKs which can be changed individually. BANK in Primary Setting Menu is applied to System, BANK in Alternate Setting/EditBank

    Setting Menu is not applied to System. Press [Alternate Enabled] button and make the lamp on, Alternate setting Menu is applied to the system. EditBank Setting is used for setting value. EVRC2A Main Menu consists of 8 sub-menus.

    Figure 3-11. Main Menu Tree

    3.2.2. Select Setbank Consists of Primary, Alternate, Edit. y Primary : Select BANK to be applied to System. y Alternate : Press [Alternate Enable] button and select a BANK to apply in the system. y Edit : Select a BANK to edit.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    34 ENHANCED TECHNOLOGY

    3.2.3. Primary Setting RELAY SETUP Consists of PASSCODE, COMMUNICATION, CLOCK, EVENT RECORDER, CLEAR SAVED DATA, FACTORY DEBUG, GAS SENSOR TYPE and TIME SET&DIS TYPE.

    SYSTEM SETUP Consists of CURRENT SENSING, LINE (VS, VL) SENSING, SYSTEM POWER, PANEL SLEEP TIME, OPTO INPUT SET, OUTPUT RELAY SET, LOOP CONTROL(option) and SET GROUP CHANGE(option).

    PROTECTION Set items related to protection elements.

    MONITORING Set items related to measurement and maintenance.

    SAVE SETTINGS Save all changed values.

    3.2.4. Alternate Setting The same as PRIMARY SETTING

    3.2.5. Editbank Setting The same as PRIMARY SETTING

    3.2.6. Status OPTO INPUTS : Shows status of External port. RELAY OUTPUTS : Shows status of Output port. CLOCK : Shows the present time. CONTROL TYPE : Shows specs of Hardware.

    3.2.7. Metering It shows metering values. For more details, refer to (see 10. METERING)

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    35ENHANCED TECHNOLOGY

    3.2.8. Maintenance COUNTERS : Shows counters related with SYSTEM. WEAR MONITOR : Shows any damage Interrupter. RELAY OUTPUT TEST : Tests External Output port. POWER QUALITY : Shows counters and time related with supply outage and counters related with swell, sag and unbalance Option. For more details, refer to (see 11. MAINTENANCE)

    3.2.9. Event Recorder It shows about Event recorder items. For more details, refer to (see 12. EVENT RECORDER).

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    36 ENHANCED TECHNOLOGY

    [LINE CURRENT(A)]A: 0 B: 0C: 0 G: 0

    SG: 0 I2: 0

    [ZERO SEQ CURRENT]0 A 0.0 Lag

    [POS SEQ CURRENT]0 A 0.0 Lag

    [NEG SEQ CURRENT]0 A 0.0 Lag

    [SENSTV CURRENT]0 A 0.0 Lag

    [PHASE C CURRENT]0 A 0.0 Lag

    [GROUND CURRENT]0 A 0.0 Lag

    [PHASE A CURRENT]0 A 0.0 Lag

    [PHASE B CURRENT]0 A 0.0 Lag

    RECLOSER CONTROLEVERC2A-N6

    LOOP CONTROLENTEC E&E CO. V6.05

    EVRC2A - CURRENT (A)A: 0 B: 0C: 0 G: 0

    SG: 0 I2: 0

    EVR2A-SYSTEM STATUSCONTROL : NOPANELBREAKER : OPENBAT:24.00 GAS:NOGAS

    [MAIN MENU]>1.SELECT SETBANK2.PRIMARY SETTING3.ALTERNATE SETTING4.EDITBANK SETTING5.STATUS6.METERING7.MAINTENANCE8.EVENT RECORDER

    [SETTING]>1.RELAY SETUP2.SYSTEM SETUP3.PROTECTION4.MONITORRING5.SAVE SETTING

    ALTERNATEPRIMARY

    EDITBANK

    [SYSTEM SETUP]>1.CURRENT SENSING2.LINE VS SENSING3.LINE VL SENSING4.SYSTEM POWER5.PANEL SLEEP TIME6.OPTO INPUT SET7.OUTPUT RELAY SET8.LOOP CONTROL9.SET GROUP CHANGE10.POWER QUALITY

    [PROTECTION]>1.OPERATION2.INTERVALS3.PICKUP CURRENT4.PHASE FAST5.PHASE DELAY6.GROUND FAST7.GROUND DELAY8.SEF ELEMENT9.NEG SEQ FAST10.NEG SEQ DELAY11.H/C TRIP-PHA12.H/C TRIP-GND13.H/C TRIP-NEQ14.H/C LOCKOUT-PHA15.H/C LOCKOUT-GND16.H/C LOCKOUT-NEQ17.CLOD LOAD PICKUP18.DIRECTION19.VOLTAGE20.FREQUENCY21.OTHER ELEMENT22.USER CURVE SET23.LOSS OF PHASE

    [MONITORING]>1.DEMAND2.SYNCHROCHECK3.TRIP COUNTER4.RECLOSER WEAR5.BATTERY TEST6.FAULT LOCATOR7.GAS LOW LOCK8.EXT TRIP&LOCK9.LIVE LOAD BLOCK

    [COMMUNICATION]>1.PROTOCOL SETUP2.PORT SETUP3.DIALUP MODEM-14.DIALUP MODEM-25.EVENT&ETC

    [CLEAR SAVED DATA]>1.Fault Cycle2.System Status3.Load Profile4.Daignostic5.Max Demand6.Energy7.Counter8.Wear Monitor9.Fault Trip10.P-Quality Count11.P-Quality Event12.Comm Event13.ALL Saved data

    [DIRECTION ELEMENT]>1.PHASE DIRECTION2.GROUND DIRECTION3.SEF DIRECTION4.NEQ DIRECTION

    [VOLTAGE]>1.UNDER VOLTAGE 12.UNDER VOLTAGE 23.OVER VOLTAGE 14.OVER VOLTAGE 2

    [USER CURVE SET]>1.USER CURVE 12.USER CURVE 23.USER CURVE 34.USER CURVE 4

    [STATUS]>1.OPTO INPUTS2.RELAY OUTPUTS3.CLOCK4.CONTROL TYPE

    [METERING]>1.CURRENT2.S-VOLTAGE3.FREQUENCY4.SYNCHRO VOLTAGE5.POWER6.ENERGY7.DEMAND8.SYSTEM9.L-VOLTAGE10.UNBALANCE11.HARMONICS

    [MAINTENANCE]>1.COUNTERS2.WEAR MONITOR3.OUTPUT RELAY TEST4.POWER QUALITY

    [EVENT RECORDER]>1.FAULT CYCLE2.SYSTEM STATUS3.LOAD PROFILE4.DIAGNOSTIC5.FAULT TRIP6.POWER QUALITY

    [RELAY SETUP]>1.PASSCODE2.COMMUNICATION3.CLOCK4.EVENT RECORDER5.CLEAR SAVED DATA6.FACTORY DEBUG7.GAS SENSOR TYPE8.TIME SET&DIS TYPE

    Figure 3-12. Menu Structure Tree

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    37ENHANCED TECHNOLOGY

    3.3. Using the LCD Menu

    Starting mode Screen appears after powering on Control and initializing System.

    INITING LOGO

    Starting mode Message Display.

    Control : Control Status displays Breaker : Breaker Status displays Battery : Battery Voltage displays Gas : Gas Status displays

    On Starting mode screen, to see Main Menu, press [FUN] key. Use [] [] key to select sub-menu. When cursor is in top menu, if you press [] key, you go to the bottom menu due to Rotation Menu Algorithm.

    MAIN MENU

    Main Menu consists of 8 sub-menus.

    You can choose any sub-menu by using [] [] key. Press [ENT] key to select the sub-menu.

    As above explanation, you can move and select sub-menu.

    3.3.1. View Example To see External input port status. Move to MAIN MENU / STATUS / OPTO INPUTS. The following screen is displayed.

    STATUS / OPTO INPUTS

    OPEN : Shows External Input is de-asserted, CLOSE : Shows External Input is asserted.

    Only 4 lines are displayed on LCD Screen, use [] [] key to see next lines.

    EVRC2A-SYSTEM STATUS CONTROL : NORMAL BREAKER : CLOSE BAT:27.49 GAS: NOGAS

    [MAIN MENU] >1.SELECT SETBANK >2.PRIMARY SETTING >3.ALTERNATE SETTING >4.EDITBANK SETTING >5.STATUS >6.METERING >7.MAINTENANCE >8.EVENT RECORDER

    [OPTO INPUTS] >Input 1: OPEN >Input 2: CLOSE >Input 3: OPEN >Input 4: OPEN >Input 5: OPEN >Input 6: OPEN >Input 7: OPEN >Input 8: CLOSE >Door st: CLOSE

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    38 ENHANCED TECHNOLOGY

    3.3.2. Setting Example Step to change Phase Pickup current of protection elements in Primary setting.

    1) Move to PRIMARY SETTING / PROTECTION / PICKUP CURRENT / PHASE. A following screen is displayed.

    PRIMARY SETTING / PROTECTION / PICKUP CURRENT / PHASE

    Range OFF, 10 ~ 1600

    Default 500 Step 1A

    Set the pickup current of Phase Fast/Delay Time Overcurrent Elements.

    2) As above screen, to move to Phase, use [] [] key and press [ENT] key to move into value column.

    3) Use [] [] keys and [] [] keys to change a new value. Press [ENT] key and then you can see the changed Phase value.

    NOTE: You must save all changed values at Setting Save menu.

    3.3.3. Help Function Help function displays the detail requirements for the setting. User can check the detail requirements of a setting after selecting the setting item by pressing

    [FUN] key.

    Help Message

    Help Message : Pickup current - phase (OFF,10~1600A)

    Pick up current - ph>Phase: 500 Ground: 250 S.E.F: OFF

    [PICKUP CURRENT A] >Phase: 500 Ground: 250 S.E.F: OFF

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    39ENHANCED TECHNOLOGY

    3.3.4. Setting Save To save all changed values, steps are as follows;

    Move to PRIMARY, ALTERNATE or EDITBANK SETTING / SAVE SETTINGS and follow each step as below.

    PRIMARY, ALTERNATE or EDITBANK SETTING / SAVE SETTINGS

    1) Type Passcode and press [ENT] key

    2) If Passcode is correct, screen (Left) appears; otherwise screen (Left) appears again.

    3) If screen appears, press [ENT] key to save changed value.

    NOTE : The changed setting can be effective after it is saved. If the save procedure is canceled, the setting keeps previous

    value. However, by EVRC2A version 5.30, if a setting related with communication is changed and then saved, the changed setting is applied after rebooting.

    SAVE SETTING

    SETTING VALUE SAVE :SETTING SAVE

    ENTER PASSCODE 0000

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    40 ENHANCED TECHNOLOGY

    4. SELECT SETBANK There were only Primary and Alternative banks before version 4.40 and 4 more banks added since version 4.40. EVRC2A has 6 setting banks and the user can have 6 different sets depending on Distribution circumstance.

    SELECT SETBANK / PRIMARY

    Range BANK1 ~ 6

    Default BANK1 Step ~

    Set Primary for BANK1.

    SELECT SETBANK / ALTERNATE

    Range BANK1 ~ 6

    Default BANK2 Step ~

    Set Alternate for BANK2.

    SELECT SETBANK / EDIT

    Range BANK1 ~ 6

    Default BANK3 Step ~

    Set Edit for BANK3.

    [SELECT SETBANK] >Primary: BANK1>Alternate: BANK2>Edit: BANK3

    [SELECT SETBANK] >Primary: BANK1 >Alternate: BANK2>Edit: BANK3

    [SELECT SETBANK] >Primary: BANK1>Alternate: BANK2>Edit: BANK3

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    41ENHANCED TECHNOLOGY

    5. RELAY SETUP Relay set shall be set independently for each bank. However, from version 4.41, regardless of bank, it will be applied to all other banks if it is set in a bank. Sets following items for Relay y Passcode y Communication y Clock y Event Recorder y Clear Saved Data y Factory Debug y Gas Sensor Type y Time SET&DIS Type

    NOTE : According to a recloser type, there may be no Gas Sensor Type.

    5.1. Passcode

    PRIMARY, ALTERNATE or EDITBANK SETTING / RELAY SETUP / PASSCODE

    y Press PASSCODE to store changed value. y PASSCODE has 4 digits. y Passcode change procedure is as follows;

    Enter the old PASSCODE, and press [ENT] key.

    Enter new PASSCODE, and press [ENT] key.

    To change and store PASSCODE, enter, [ENT] key.

    After changing PASSCODE, new PASSCODE will be displayed.

    [PASSCODE CHANGE] ENTER NEW PASSCODE

    0000 PASSCODE SAVED: 0000

    [PASSCODE CHANGE] ENTER NEW PASSCODE

    0000 PRESS TO SAVE

    [PASSCODE CHANGE] ENTER NEW PASSCODE

    0000

    [PASSCODE CHANGE] ENTER PASSCODE 0000

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    42 ENHANCED TECHNOLOGY

    5.2. Communication

    5.2.1. Overview EVRC2A has four ports for communication. The EVRC2A has the front panel RS232 port, the side panel RS232 port, the side panel RS485 port(or RS232 port) and the side panel Ethernet port.

    Communication port settings are available as follows in Table 5-1. Communication Ports setting of EVRC2A. Table 5-1. Communication Ports setting of EVRC2A

    Port Type Speed Parity bit Data bit Stop bit Location

    PORT1 RS-232 57600 bps No parity 8 1 User Interface Front Panel

    PORT2 RS-232 1200 - 19200 bps No parity 8 1 User Interface Side Panel

    PORT3 RS-485 or RS-232

    1200 - 19200 bps No parity 8 1 User Interface Side Panel

    PORT4 RJ45 10BASE-T/100BASE-T User Interface Side Panel

    PORT1(RS232) A port to interface with Interface Software.

    PORT2(RS232) Option The Port2 is a port for a serial communication for MODBUS, DNP3.0 or IEC60870-5-101 protocol. A user can select the protocol and configure the Port2 for the selected protocol by changing baud rate and/or other settings for the Port2.

    PORT3(RS485 or RS232) Option The Port3 is a port for a serial communication for MODBUS, DNP3.0 or IEC60870-5-101 protocol. A user can select the protocol and configure the Port3 for the selected protocol by changing baud rate and/or other settings for the Port3. The Port3 type of EVRC2A-N is a fixed RS485 port. However, the Port3 type of EVRC2A can be selected as RS485 or RS232 by a user. In order to use RS485 port for EVRC2A, the Pin4 and Pin5 of RS485 should be connected.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    43ENHANCED TECHNOLOGY

    PORT4(RJ-45) Option The Port4 is a Ethernet port for TCP/IP communication (10 BASE-T /100 BASE-T speed) for Modbus, IEC60870-5-104 or DNP3.0 Protocol. A user can select the protocol and configure the Port4 for the selected protocol by changing its settings.

    NOTE: From EVRC2A version 5.30, if a setting related with communication is changed and

    then saved, the changed setting is applied after rebooting. During IEC60870-5-104 or DNP3.0 communication through Port2, Port3 or Port 4, a user can connect with the Interface Software ETIMS(ENTEC Integration Management Software) and use it.

    Please refer to DNP3.0 Protocol Technical Manual, MODBUS Protocol Technical Manual or IEC60870-5-101/-104 Protocol Technical Manual for more information about setting for each protocol.

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    44 ENHANCED TECHNOLOGY

    5.2.2. Protocol Setup 5.2.2.1. DNP 3.0 Protocol - Option

    EVRC2A can be programmed for communication using the DNP 3.0 through communication

    port2, port3 or port4. For details, refer to DNP3.0 Protocol Technical Manual

    Move to PRIMARY, ALTERNATE or EDITBANK SETTING / RELAY SETUP / COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 to select setting for DNP 3.0 Protocol.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Function

    Range DISABLE, ENABLE

    Default DISABLE Step ~

    Select whether to use DNP3.0 Protocol or not.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Use Port

    Range P2-232, P3-232, P3-485, P4-TCP

    Default DNP1 : P2-232

    Step ~ DNP2 : P3-232

    Select DNP3 communication port.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Master Address

    Range 0 ~ 65519

    Default 60000 Step 1

    Enter the master station address.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Slave Address

    Range 0 ~ 65519

    Default DNP1 : 1

    Step 1 DNP2 : 2

    Enter the slave(EVRC2A) address.

    [DNP3.0-1] >Master Addr: 60000>Slave Addr: 1>D/L Confirm: SOME

    [DNP3.0-1] >Master Addr: 60000>Slave Addr: 1>D/L Confirm: SOME

    [DNP3.0-1] >Function: ENABLE>Use Port: P2-232 >Master Addr: 60000

    [DNP3.0-1] >Function: ENABLEUse Port: P2-232

    Master Addr: 60000

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    45ENHANCED TECHNOLOGY

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / D/L Confirm

    Range NO, YES, SOME

    Default SOME Step ~

    Choose whether Data Link Confirm is used or not.

    NO : Data Link Confirm is not used. YES : Data Link Confirm is used. SOME : Data Link Confirm is used in case of Multi-frame. When Data Link Confirm use-setting, it shall be set as Host setting. If the setting is different from Host setting, the communication may be failed due to Data Link Reset.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / D/L Retries

    Range 0 ~ 255

    Default 2 Step 1

    Enter the number of retries that will be issued for a given data link layer.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / D/L Timeout

    Range 1 ~ 255 sec

    Default 55 Step 1 sec

    Set a waiting time between Data Link Frame transfer till to receive Data Link Confirm(ACK) of Master. If there is no Data Link Confirm receiving and Data Link retry is available, EVRC2A will send Data Link Frame again.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / A/L Retries

    Range 0~ 255

    Default 1 Step 1

    Select the number of retries that will be issued for a given application link layer.

    [DNP3.0-1] >D/L Retries: 2 >D/L Timeout: 55 >A/L Retries: 1

    [DNP3.0-1] >D/L Confirm: SOME >D/L Retries: 2 >D/L Timeout: 55

    [DNP3.0-1] >D/L Confirm: SOME >D/L Retries: 2 >D/L Timeout: 55

    [DNP3.0-1] >D/L Confirm: SOME >D/L Retries: 2 >D/L Timeout: 55

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    46 ENHANCED TECHNOLOGY

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / A/L Timeout

    Range 1 ~ 255 sec

    Default 55 Step 1 sec

    Set a waiting time for Slave Application to receive A/L Confirm(ACK) from Master Application, in case that Confirm is requested during Data transfer from Slave Application to Master Application.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / SBO Time

    Range 1 ~ 255 sec

    Default 15 sec Step 1 sec

    Set a time interval between Select Function and Operate Function. If no operation command during set time, Select command is cancelled.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Multi Inter

    Range 0.01 ~ 300.00 sec

    Default 0.10 Step 0.01 sec

    Enter a time delay between frames when Multi-frame replies.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Tx Delay

    Range 0.00(OFF), 0.01 ~ 300.00 sec

    Default 0.05 Step 0.01 sec

    Delay time of sending Real data after RTS Signal is on.

    NOTE : The setting does not apply to communication and is not indicated from Ver 7.07 of EVRC2A_NT.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / PowUp Unsol

    Range DISABLE, ENABLE

    Default ENABLE Step ~

    Select the unsolicited mode.

    Enable : Unsolicited response is transmitted. Disable : Unsolicited response is not transmitted.

    [DNP3.0-1] >Multi Inter: 0.10>Tx Delay : 0.05>PowUpUnsol: ENABLE

    [DNP3.0] >DNP Address: 1>Multi Inter: 0.10>Tx Delay : 0.05

    [DNP3.0-1] >A/L Timeout: 55>SBO Time: 15>Multi Inter: 0.10

    [DNP3.0-1] A/L Retries: 1 A/L Timeout: 55>SBO Time: 15

    [DNP3.0-1] D/L Timeout: 55 A/L Retries: 1>A/L Timeout: 55

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    47ENHANCED TECHNOLOGY

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Unsol Time

    Range 0 ~ 255 sec

    Default 5 Step 1 sec

    Set a delay time of transmission of event data after the last event occurs.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Unsol Type

    Range NOTRIG, PERIOD

    Default NOTRIG Step ~

    Set a type to configure a method to send event data.

    NOTRIG : If there is no more event occurrence during setting Unsol Time after the last event occurs, the event data is transmitted.

    PERIOD : Unsolicited message is sent to a master with whole event data occurring after setting Unsol Time starting and elapsing when the first event occurs.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Class 1

    Range DISABLE, ENABLE

    Default DISABLE Step ~

    Select the unsolicited response mode of Class 1 events.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Class 2

    Range DISABLE, ENABLE

    Default DISABLE Step ~

    Select the unsolicited response mode of Class 2 events.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Class 3

    Range DISABLE, ENABLE

    Default DISABLE Step ~

    Select the unsolicited response mode of Class 3 events.

    [DNP3.0-1] Class 1: DISABLE Class 2: DISABLE >Class 3: DISABLE

    [DNP3.0-1] >Class 1: DISABLE >Class 2: DISABLE >Class 3: DISABLE

    [DNP3.0-1] >Class 1: DISABLE Class 2: DISABLE >Class 3: DISABLE

    [DNP3.0-1] >PowUpUnsol: ENABLE >Unsol Time: 5 >Unsol Type: NOTRIG

    [DNP3.0-1] >Multi Inter: 0.10 >PowUpUnsol: ENABLE >Unsol Time: 5

  • RECLOSER CONTROL EVRC2A-N6,NT http://www.entecene.co.kr

    48 ENHANCED TECHNOLOGY

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Master IP Oct 1~4

    Range 0 ~ 255

    Default ~ Step 1

    Select the IP Address for DNP3 Communication. IP Address : 192.xxx.xxx.xxx

    IP Addr1,2,3,4 is ,,,

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / TCP/UDP Select

    Range TCP, UDP

    Default TCP Step ~

    Select TCP or UDT communication at the use of Port4(Ethernet).

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / TCP Port

    Range 0 ~ 65535

    Default 20000 Step 1

    Set the TCP/IP port number of EVRC2A for TCP communication.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / UDP Port

    Range 0 ~ 65535

    Default 20000 Step 1

    Set the TCP/IP port number of EVRC2A for UDP communication.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Keep Alive Check Time

    Range 0(OFF), 1 ~ 600 sec

    Default 10 Step 1sec

    Set the Time period that checks the communication connecting status during the idle status.

    COMMUNICATION / PROTOCOL SETUP / DNP1 or DNP2 / Fragment Size

    Range 64 ~ 2048

    Default 2048 Step 1

    Set the size of DNP3.0 fragment.

    [DNP3 SLAVE1] >UDP Port: 20000>K-Alv Check Tm: 10>Fragment Size: 2048

    [DNP3 SLAVE1] >UDP Port: 20000>K-Alv Check Tm: 10>