Auxiliary Contacts TypeAmpere Rating 2 Pole DC HP Ratings Catalog List
Frame Size Open Enclosed 115V 230V 500V 575V NO NC Number Price $
2 32 29 3 5 10 10 2 2 3TC44170A 501.004 75 68 712 15 40 40 2 2 3TC48170A 847.008 220 200 25 50 100 100 2 2 3TC52170A 1348.0012 330 300 40 75 150 150 2 2 3TC56170A 4237.00
3TC44 3TC52
2/202
General PurposeType 3TC
DC Power ControlsDC Contactors and Replacement Parts
Siemens Energy & Automation,
Industrial Controls Cat
Discount Code: Replacement Parts
AC Operated
DC Operated
Suffix K2 for 3TC44.
Main contact kits for size 3TC48 and larger include springs.Smaller sizes do not.On DC operated contactors the maximum number of auxiliary
contacts is 2 NO, 2 NC.
For use in dusty atmosphere and electronic circuits with ratedoperational currents Ie AC-14 and DC-13 from 1 mA to 300 mA at3V to 60V. With 1 changeover contact.
Discount Code: DC Contactors
3TY2480-0A
Coils, AC
Frame Catalog ListType Size Number Price $
3TC44 3TY2440-0A 77.00
3TC3TC48 3TY2480-0A 193.00
3TC52 3TY2520-0A 385.00
3TC56 3TY2560-0A 674.00
Main Contacts
FrameAuxiliary Contacts
Normally Closed/ Block Catalog ListType Size NO NC Late Break Location Number Price $
3TC44 to1 1 Left or Right 3T Y6501 -1AA00 32 .0 0
3TC48
3TC 3TC52 to 1 1 Left 3TY6561-1A 64.00
3TC561 1 Right 3TY6561-1B 64.001 1 Right 3TY6561-1E 64.00
3TC44 to1 1 Left or Right 3TY7561-1UA00 62.00
3TC48
3TY6501-1A
Auxiliary Contact Blocks
3TY7483-0AK6
Device FrameCatalog Number List
Type Size 24V AC 120V AC 220/240V AC 277V AC 480V AC 600V AC Price $
3TC4417-0B 3TY7403-0AC2 3TY7403-0AK6 3TY7403-0AP6 3TY7403-0AU1 3TY7403-0AV0 3TY7403-0AS0 56.00
3TC3TC4817-0B 3TY6483-0AC1 3TY6483-0AK6 3TY6483-0AP6 3TY6483-0AP0 3TY6483-0AV0 3TY6483-0AS0 128.00
3TC5217-0B 3TY6523-0AK6 3TY6523-0AP6 3TY6523-0AP0 3TY6523-0AV0 159.00
3TC5617-0B 3TY6566-0AK6 3TY6566-0AP0 3TY6566-0AV0 3TY6566-0AS0 298.00
3TY2482-0A
3TU6483-0BB4
Device Frame Catalog Number List
Type Size 24V DC 48V DC 110V DC 125V DC 230V DC Price $
3TC4417-0A 3TY6443-0BB4 3TY6443-0BF4 3TY6443-0BG4 92.00
3TC 3T C481 7-0A 3TY6483-0BB4 3TY6483-0BW4 3TY6483-0BF4 3TY6483-0BG4 139.00
3TC5217-0A 3TY6523-0BB4 3TY6523-0BF4 3TY6523-0BG4 3TY6523-0BP4 185.00
3TC5217-0A 3TY6563-0BB4 3TY6563-0BF4 3TY6563-0BG4 3TY6563-0BP4 347.00
Coils, DC
Frame Catalog ListType Size Number Price $
3TC44 3TY2442-0A 71.00
3TC3TC48 3TY2482-0A 128.00
3TC56 3TY2562-0A 482.00
Arc Chutes
Coil Suffix Table
AC V 50/60 Hz Code DC V Code
24 C1 24 B4120 K1 48 W4240 P1 60 E4
460 Q0 110 F4600 S0 125 G4230 P4
Replace in the contactor catalog number with acoil code from the table above.
Ordering Information
Select Contactor from table below. To complete catalog number replace the two daggers () with
appropriate coil voltage suffix. See corresponding coil voltage
suffix table. Technical Data see page 2/203. Dimensions see page 2/203.
Auxiliary Contacts TypeAmpere Rating 2 Pole DC HP Ratings Catalog List
Frame Size Open Enclosed 115V 230V 500V 575V NO NC Number Price $
2 32 29 3 5 10 10 2 2 3TC44170B 375.004 75 68 712 15 40 40 2 2 3TC48170B 674.008 220 200 25 50 100 100 2 2 3TC52170B 1136.0012 330 300 40 75 150 150 2 2 3TC56170B 3274.00
Discount Code: DC Contactors
-
7/29/2019 02_202-203 Dc Contactor
2/2
2/203
General PurposeType 3TC
DC Power ControlsDC Contactors
Siemens Energy & Automation, Inc.
Industrial Controls Catalog
Specifications
Type 3TC general purpose contactors
meet or exceed the requirements
of NEMA, UL, CSA, IEC, VDE and other
international standards. Information on
approvals in Section 1.Application
Type 3TC DC contactors are primarily
used in mining, steel mills, and other
heavy duty industrial applications.These contactors are designed for
continuous operation and they are used
to remotely control DC drives, cranes,
hoists, heaters and lamps as well as
such apparatus as battery-chargers,plating equipment and transit systems.
These contactors can be used for
starting of DC motors where the
starting current does not exceed 10
times the current corresponding to
the horsepower rating of the contactor.
The ratings given in the Contactor
Ratings Table apply for the double-pole
switching of loads or when the two
contact paths of the contactor are
connected in series. When only onecontact is used, the values given can
be switched at voltages up to 220V.
Mounting
The contactors must be mounted in theposition indicated in drawing.
Contactors can be tilted up to 22.5 off
the vertical.
Unit ofContactor Type Measure 3TC44 3TC48 3TC52 3TC56
Mechanical Life 10 million make/break operations
Rated Voltage/ V 600 600 600 600
VDE/IEC V 800 800 800 800
Permissible ambienttemperature ranges in operation C 25 to55 (13F to131F)
when stored C 50 to80 (58F to176F)
Coil ratings(cold coil, 1.0 Uc)DC operation in-rush W 10 19 30 86
sealed W 10 19 30 86AC Operation in-rush (Pf %) VA % 73 (78%) 365 (45%) 730 (38%) 2140 (30%)
sealed VA % 9 (27%) 35 (26%) 56 (24%) 140 (29%)
Coil voltage tolerances 0.8 to 1.1 times rated control voltage (Uc)
Operating times (valid for 20% undervoltage, 10% overvoltage, cold or warm coil)Total break time opening delay arcing time
DC operation closing delay ms 35190 90380 120400 110400opening delay ms 1025 1728 2235 40110arcing time ms 20 20 20 20
AC operation closing delay ms 1040 2050 2050 2050opening delay ms 525 530 1030 1030
Resistance to shock (rectangular pulse)g/ms
7.5/ 5 10/ 5 12 / 5 12 / 53.4/10 5/10 5.5/10 5.5/10
Conductor sizesMain conductor: stranded AWG (2) 148 #8#2 #14/0 (2) 250 MCMAuxiliary conductor: stranded AWG (2) 1814 (2) 1814 (2) 1814 (2) 1814
Switching frequency in make/break operations per hour (1/h)DC and AC operation
with resistive load DC1 duty 1/h 1500 1000 1000 1000with inductive load DC2 and DC4 duty 1/h 750 600 600 600
DC3 and DC5 duty 1/h 250 250 250 250
Contactor Rated voltage Switching capacity
3TC44 to 3TC56 max. 600V AC Heavy duty A600, P600
Ratings for Auxiliary Contacts
Technical Data
3TC44
3TC48 to 3TC56
Mounting positions