Mics Kerys – Basic Reminders
2
Titre de la diapositive
SDMO Training departement
Basic Regulations meanings Set up point : nominal adjustement point
Gain : Time delays from reading to action
Stability : Time réaction to stable state
Droop : Dead band action
Proportional : The action will be proportional of the gap in between set point and reading
Integral :The main purpose of the integral gain is to have actual speed equals to requested speed.High integral gain can cause slow engine hunting (unstable).
Derivative : The main purpose of the derivative gain is to stabilize the system. High dérivative gain can cause very fast and erratic engine hunting (unstable).
Isochronous : No dead band ( droop = 0 )
Off set : Value from Référence to set up
Amplitude : Set up band action
E F C : Electro Fuel Control
E C U : Engine Contrôl Unit
3
Titre de la diapositive
SDMO Training departement
OFF ON
1
Stability
Time
Gain
= Best setting = Best setting
Time
Speed
Speed
Droop
4
Titre de la diapositive
SDMO Training departement
Speed adjustement
Reference
EFC or ECU
Off set
EX MTU = ref 10v – 6v Off Set = 4v
Output Amplitude
Time
U DC
5
Titre de la diapositive
SDMO Training departementPage 5Page 5
Speed governor reminder
Read
Action
Régulation MODULE
6
Titre de la diapositive
SDMO Training departement
Page 6Page 6
Proportionnal gain
The main purpose of the propotionnal gain is to speed up/down reactions.
High proportionnal gain can cause fast engine hunting (unstable).
7
Titre de la diapositive
SDMO Training departement
The main purpose of the integral gain is to have actual speed equals to requested speed.
High integral gain can cause slow engine hunting (unstable).
Page 7Page 7
Integral gain
8
Titre de la diapositive
SDMO Training departement
The main purpose of the derivative gain is to stabilize the system.
High dérivative gain can cause very fast and erratic engine hunting (unstable).
Page 8Page 8
Derivative gain
9
Titre de la diapositive
SDMO Training departement
- Magnetic pick-up voltage must be at least 2.5 Volts at crank speed
- Do not use same pick-up for speed governor and overspeed protection
- 0Volt must be taken from the control box and not from batterie minus
-Remote speed contrôle should always be shielded and must be far away from power cables.
-Size of the power supply leads to control box and to actuator should be twisted and are to be selected regarding distance between modules.
Speed governor reminder Must-do & must-know
10
Titre de la diapositive
SDMO Training departement
STATORWINDING
ROTATINGRECTIFIERS
EXCITER FIELD
ROTORWINDING EXCITER
ARMATURE
A V R
A.C.
D.C.
Action
Read
Voltage regulation reminders
Régulation MODULE
11
Titre de la diapositive
SDMO Training departement
Basic Genset Regulations Loops
Air
Fuel U / HZ
Engine AlternatorSpeed
E F C A V R
Regulation ModuleU / HZ
Action Action
Action Action
Read Read
Read
Voltage Loops
Speed Loops
12
Titre de la diapositive
SDMO Training departement
Genset Synchronizing REMINDERS
13
Titre de la diapositive
SDMO Training departement
Principle of synchronization
14
Titre de la diapositive
SDMO Training departement
We need :- equality of FREQUENCY- equality of VOLTAGE- equality of PHASE ANGLE
Important rules to synchronize two generating sets
15
Titre de la diapositive
SDMO Training departement
Equality of frequency
/2 2 /3 2 0 t
U
T2
T1
T
16
Titre de la diapositive
SDMO Training departement
Equality of voltage
/2 2 /3 2 0 t
U
U
17
Titre de la diapositive
SDMO Training departement
Equality of phase angle
/2 2 /3 2 0 t
U
18
Titre de la diapositive
SDMO Training departement
Main manufacturers of synchronizing equipments used in EUROPE
By direct contact
ALSTHOM.BASLER. WOODWARD.SEG.SELCO.DEIF.AEES. ( ex HENNEQUIN ).CEE. ( ex TECHNIREL, ex REGULATEURS GEORGIN ).
By analogical signal
BARBER COLMAN.WOODWARD.GAC.SEG.HEINZMANN.SELCO.DEIF.CEE. ( ex TECHNIREL, ex REGULATEURS GEORGIN ).
19
Titre de la diapositive
SDMO Training departement
Live Bus synchronization Principle
20
Titre de la diapositive
SDMO Training departement
Dead Bus synchronization principle
21
Titre de la diapositive
SDMO Training departement
Advantage of the dead field synchronization
Availability of all generators, so a faster resumption of the activity.
No risk of energy exchange during the synchronization.Avoid magnetizing currents transformers.
22
Titre de la diapositive
SDMO Training departement
Utilization of the neutral
Power station with one generator :The neutral can be linked to earth whatever the pitch of coil.
Power station with many generators :- alternator pitch 2/3 :
Neutrals can be connected to each other or to the earth.- alternators with same pitch :
Neutrals can be connected.Note: active and reactive loads must be distributed.
- alternators with different pitch :Neutrals cannot be connected.If necessary to connect neutrals, place a coil between each alternator to limit current.
Power station synchronised with the mains :If the neutral is connected, an alternator pitch 2/3 is needed.Reduction of power :
P 2/3 = P full x 3 / 2.
23
Titre de la diapositive
SDMO Training departement
2 Differents synchronizing sequence
A B
a b
Live bus synchronising1- Start A2- Close a3- Start B4- Synchronised B with bus-bar5- Close bDead bus synchronising1- Close a and b2- Start A and B3- Control speed A and B > 1450 tr /mn4- Exitation A and B5- Voltage rise up on bus bar
24
Titre de la diapositive
SDMO Training departement
Dead bus synchronization avantages
Availability of all generators, so a faster resumption of the activity.
No risk of energy exchange during the synchronization.
Avoid in-rush currents transformers.
Possibility of energising transformer bigger than generator
25
Titre de la diapositive
SDMO Training departement
Graph - KW function to KVAR
26
Titre de la diapositive
SDMO Training departement
The “MORDEY” Curve ( relation between I induced and I excitation)
27
Titre de la diapositive
SDMO Training departement
KW & KVAR Graph given by Utility supply ( when sync with Mains)
KW ConsumptionKW Consumption
KVAR ProductionKVAR Production
KW & KVA ProductionKW & KVA Production KVAR ConsumptionKVAR Consumption
KW ProductionKW Production
KW & KVAR consumptionKW & KVAR consumption
28
Titre de la diapositive
SDMO Training departement
• Gensets have to accept load impacts corresponding to change in a production process for example. Typically :
. From 10 to 500 kVA, our gensets are able to accept in a single step, a load impact of 75% of their nominal power.
. From 500 to 2000 kVA, our gensets are able to accept in a single step a load impact of 50% of their nominal power.
NOTE : Of course this load impact will affect frequency and voltage.
(except : MTU have a better abilities for load impacts, approximately 60-70 %)
Load impacts
29
Titre de la diapositive
SDMO Training departement
Load Sharing REMINDERS
30
Titre de la diapositive
SDMO Training departement
Voltage and KVAR relations
For a non-synchronized genset :- KVAR is function of load’s power factor.- Action on the order of the AVR enables to adjust load’s supply voltage.
Genset synchronised with another one :- KVAR is :
- function of the load.function of the behaviour of generators toward each
other.- Action on the order of the AVR enables to adjust the repartition of the reactive power and the voltage of the bus bar.
31
Titre de la diapositive
SDMO Training departement
Speed and KW relations
For a non-synchronized genset :- KW is function of load’s power factor.- Action on the speed regulator’s instruction allows to adjust load’s supply frequency.
Genset synchronized with another one :- KW is :
- function of the load.- function of the behaviour of generators toward
each other.- Action on the instruction of the speed control unit allows to adjust the distribution of the KW and the Bus bar frequency.
32
Titre de la diapositive
SDMO Training departement
KW & KVAR Diagram for generating set
33
Titre de la diapositive
SDMO Training departement
Without KW distribution
Distribution of active power
34
Titre de la diapositive
SDMO Training departement
KW Power Reverse and KVAR Power reverse
KVAR Power reverse
KW Power Reverse
35
Titre de la diapositive
SDMO Training departement
Speed DROOP
36
Titre de la diapositive
SDMO Training departement
KW distribution with DOOP Mode
37
Titre de la diapositive
SDMO Training departement
KW distribution with DROOP Mode
38
Titre de la diapositive
SDMO Training departement
KW distribution with DROOP Mode
39
Titre de la diapositive
SDMO Training departement
Voltage DROOP Mode
40
Titre de la diapositive
SDMO Training departement
KVAR distribution with DROOP Mode
41
Titre de la diapositive
SDMO Training departement
KW distribution in isochronous Mode
42
Titre de la diapositive
SDMO Training departement
KVAR distribution in Isovoltage Mode
43
Titre de la diapositive
SDMO Training departement
Load sharing
A B
a b
KwU I I U
KwKvarKvar
Analog Analog
Digital DigitalBus can : Kw KvarBus DC voltage KW ( Kvar on droop mode )
Bus can : Kerys to Kerys Bus DC : Kerys with other ILSRegulation
moduleRegulation
module
44
Titre de la diapositive
SDMO Training departement
Page 16Page 16
Speed governor – Reminder- Parallel lines
45
Titre de la diapositive
SDMO Training departement
Electrical Genset Protections REMINDERS
46
Titre de la diapositive
SDMO Training departement
When gensets are synchronised to the mains, we have those following regulation mode :
- KW is kept in a constant value (remote controlled or not). KVAR is function of KW or constant PF “cos ”.
Measures which allow the detection of a micro power cut are function of the following electrical parameters :
- F- V- I- KW- KVAR
Detection
47
Titre de la diapositive
SDMO Training departement
GENSET MAINS ( Grid) ( ANSI 49 ) Thermical current ( ANSI 78 ) Rocof « DF/DT » ( ANSI 50 ) Over Load ( ANSI 78 ) Vector Jump ( Shift ) ( ANSI 27 ) Mini Voltage ( ANSI 21 ) Minimum of impedance ( ANSI 59 ) Over Voltage ( ANSI 81 ) Mini Fréquency ( ANSI 81 ) Over Frequency ( ANSI 32-2 ) Max KW ( ANSI 32 ) Max KVAR ( ANSI 32-2 ) Mini KW ( ANSI 32P ) Reverse power ( ANSI 40 / 32) Reverse reactive power ( ANSI 46 ) Imbalance current ( ANSI 51/51V) Short-cicuit ( ANSI 64) Homopolar Current ( ANSI 67 ) Directional short-circuit ( ANSI 67N ) Directional homopolar current ( ANSI 59N ) Homopolar voltage ( ANSI 87B ) Restricted ground
Protections Protections
48
Titre de la diapositive
SDMO Training departement
( ANSI 49 ) Thermical current
Protections - description
( ANSI 32 ) Max KVAR
( ANSI 46 ) Imbalance current
( ANSI 51/51V) Short-cicuit
( ANSI 64) Homopolar Current
49
Titre de la diapositive
SDMO Training departement
( ANSI 59N ) Homopolar voltage
Protections - description
( ANSI 87B ) Restricted ground
50
Titre de la diapositive
SDMO Training departement
This protection allows detection of loss of mains.If mains disappear when genset is paralleled with, the seen load quickly changes and the voltage curve shifts. This is the fastest way to detect loss of mains.
The threshold shift angle can be set between 0.5° and 20°.The setting is choosen regarding the ratio of the genset, the load, the mains total load ...
Electrical protection reminder : Vector Jump ANSI 78
51
Titre de la diapositive
SDMO Training departement
46,5
47
47,5
48
48,5
49
49,5
50
50,5
This protection allows detection of loss of mains.If mains disappear when genset is paralleled with, the seen load changes and after a delay due to engine inertia the speed/frequency decreases with a rate in accordance with the load seenThe threshold rate of change can be set from 0.5Hz/s to 5Hz/s.The setting is choosen regarding the ratio of the genset, the load, the mains total load ...
Electrical protection reminder : Rocof or DF/DT ANSI 78
52
Titre de la diapositive
SDMO Training departement
Impedance
Delay
Threshold 1
Threshold 2
Delay 2 Delay 1
Fault area
This protection allows detection of loss of mains for example. It monitors instantaneous impedance of the load Z=Vrms/Irms seen from the gensetThe thresholds impedance can be set from 4 to 120 Ohms.The setting is choosen regarding the ratio of the genset, the load, the mains total load ...
Electrical protection reminder : Low impedance ANSI 21
53
Titre de la diapositive
SDMO Training departement
U
I
seuil
t
Z
Z = U/I
IF U goes to 0
And
I increase
Z goes to 0
Low impedance Diagram
54
Titre de la diapositive
SDMO Training departement
Threshold 1
Delay
Current value
Delay 1
Delay 2
Threshold 2
Fault area
Page 23Page 23
This protection allows detection of short cicuits between phases, phase to neutral, phase to earth. It monitors instantaneous RMS currents on each phases and the sum of the currents going out of the genset.The thresholds currents can be set from In to 5In for phase, from 0.5In to In for earth fault and from 0.3In to In for neutral fault. In is 1A or 5A.The delays can be set from 0 to 5sFor earth fault current, an 8th order low pass filter removes the 3rd harmonic.
Electrical protection reminder : Overcurrent ANSI 50
55
Titre de la diapositive
SDMO Training departement
Delay
Voltage value
Delay 1
Delay 2
Threshold 1 Threshold 2
Fault area
This protection allows detection of potentially dangerous voltages on the genset. It monitors instantaneous RMS voltage between earth and neutral.The thresholds voltage can be set from 30 volts to 100 volts.An 8th order low pass filter removes the 3rd harmonic.
Electrical protection reminder : Voltage earth fault
56
Titre de la diapositive
SDMO Training departement
Reference voltage =45°
1 No fault area
Fault area
I1
U32
This protection allows detection of short cicuits between phases, phase to neutral, phase to earth inside the generator. It monitors instantaneous RMS currents on each phases and the sum of the currents going out of the genset and compares the phase between these currents and its reference voltage.
Electrical protection reminder : Directionnal overcurrent ANSI 67
57
Titre de la diapositive
SDMO Training departement
Directional homopolar current ANSI 67N
58
Titre de la diapositive
SDMO Training departement
HIGHLIGHTSBasic Reminders on Gensets
59
Titre de la diapositive
SDMO Training departement
Current Tansformer Spécifications
CT are design due to the utilisation :- protection 5P5 - measure Cl1- ratio X/5A ou X/1A- power en VA- isolation
I secondary (A)
5 X In
In
5A 25A
ex: 200/5A . 5P5. 30VA . 50/60Hz .750V
ex: 200/5A . Cl1. 30VA . 50/60Hz . 750V
( 5 In ) ( In )
A
B
I primary (A)
60
Titre de la diapositive
SDMO Training departement
Measurement and protection on Neutral point
3 ~
X/5 - 5P5 - 10VA
X/5 - Cl 0,5 - 10VA
GENSET
32
32P
32Q
51
50
67
21
59
67N
81
51N
32RQ
32RP
dF/dt
27
59 °
Régulation Module
Protection Module
61
Titre de la diapositive
SDMO Training departement
Kerys Voltage and Current measurement
ALTERNATOR
Voltage measure
Voltage measure
genset
Current measure
( 100V à 500V )
( X/5A )
genset
62
Titre de la diapositive
SDMO Training departement
Ph1
Ph2 Ph3
N
I1
U
I2
I3
P = U I 3 cos
Q = U I 3 sin
S = U I 3
Ir1
Ia1
Ir2
Ia2 Ia3 Ir3
Ia Ir I = 2 +
2
Q = P tg
Triangle of the powers
63
Titre de la diapositive
SDMO Training departement
Summary about neutral regimes using C15-100 standard
Regime Number of conductors
Detection Note
TT 4 poles Measure of residual current
Trigging at the 1st default
TNC
S
3 poles Without(Measure of
residual current)
Trigging by protection against
overload4 poles
ITSN
AN
3 poles Measure of the resistance of
insulation
Trigging at the 2nd default by
protection against overload4 poles
64
Titre de la diapositive
SDMO Training departement
PRIMARYPRIMARY
SECONDARYSECONDARY
Connection DELTA / STAR
65
Titre de la diapositive
SDMO Training departement
PLC : Programmable Logical ControleM M I : Man Machine InterfaceTOR : Tout Ou Rien. = binaryCPU : Control Process Unit ECU : Engine Control Unit PC : Common Part Tactil : Tactile = touch screen displayGrid : Mains = NormalI P : Internet ProtocoleJ D B : Jeux De Barres ( French ) = Bus Bar
( english )I L S : Isochronus Load SharingBUS CAN : Bus Controler Area Network
Glossary of terms