03 sep674 ret670 differential protection
TRANSCRIPT
1MRG019260
Transformer protection RET670Restricted earth fault protection
Substation Automation Products
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 2
Contents
Application
Operating characteristics
Logical Diagram
In and output signals
Settings
Monitored data
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 3
Faults resulting in large fault currents may cause severe damages to windings and the core
Could also result in high gas pressure damaging the tank
The restricted earth fault protection is fast and sensitive and can detect faults in the winding: in impedance earthed systems
close to the star point in solid earthed systems
The restricted earth fault protection is often used as main protection for all winding faults involving earth
Application restricted earth fault protection
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 4
Low impedance type
Can be used to protect directly or low impedance earthed windings
Zero sequence differential protection An additional directional comparison feature is
included
No need for magnitude or phase angle correction
Internally summation if multi breaker arrangement
Fundamental frequency components
OLTC does not influence the function
Insensitive to inrush and overexcitation
Only danger is eventual CT saturation 2nd harmonic restraint included
Restricted earth fault protectionApplication
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 5
Restricted earth fault protection Application
1. TransformerA. Solidly earthed winding with or without OLTC
B. Earthed though Z-0 earthing transformer
2. Autotransformer with or without OLTC
3. ReactorA. Solidly earthed
1A 1B
2 3A
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 6
Restricted earth fault protection Application
Single circuit breaker or
Multiple circuit breaker applications summation inside the function
Number of instances Customized: 0 - 3
Pre-configured (A10, A30, B30, A40, B40, A25): Included: A10: 1; x30/y40: 2; A25: 0
Optional: y40: 1
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 7
Calculated or measured residual current on terminal side, 3I0 (Ires)
The differential current, Idiff, is the vector sum:
where
3I0_Wx is the summation of CT1 and CT2 for winding x
3I0_W2 is used in autotransformer applications
Stabilizing current, Ibias The highest current among all
current inputs
125
Operating characteristicsRestricted earth fault protection
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 8
Two fixed slopes defines as:
1st: 70% ; 2nd: 100%
End of slope 1: 125% of IBase
Setting: Minimum operation, Idmin In percent of IBase: 4.0 - 100.0
IBase
Rated current of the winding or CT rating
For autotransformers the highest winding rated current i.e. low voltage side
125
Operating characteristicsRestricted earth fault protection
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 9
The bias current stabilizes the protection
Higher currents harder conditions higher probability that Idiff > Idmin due to: CT saturation
Ibias is defined as the maximum current of: curr(a) = MAX [I3PW1CT1] / CTFactorPri1
curr(b) = MAX [I3PW1CT2] / CTFactorPri2
curr(c) = MAX [I3PW2CT1] / CTFactorSec1
curr(d) = MAX [I3PW2CT2] / CTFactorSec2
curr(x) = MAX [I3PW1CT1 + I3PW1CT2]
curr(y) = MAX [I3PW2CT1 + I3PW2CT2]
curr(z) = INwhere the CTFactor = Irated_CT / Irated_W
default setting: 1.0 (1.0-10.0)
Operating characteristicsRestricted earth fault protection, Ibias
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 10
The CTFactor : gives a possibility to adjust the sensitivity
does not influence curr(x-z)
Single breaker application Normally the CT ratio matches the winding and the
CTFactor = 1.0
Multiple breaker application Could be necessary to modify CTFactor
IBase = Irated_W and
Irated_CT > or >> Irated_W
curr(a and/or b) might stabilize to much due to transfer currents (fault or load currents)
Example: CTFactor = 1000/500 = 2.0
CT1 1000 A
500 A
CT2 1000 A
curr(a) = MAX [I3PW1CT1] / CTFactorPri1
curr(x) = MAX [I3PW1CT1 + I3PW1CT2]
curr(b) = MAX [I3PW1CT2] / CTFactorPri2
Example:
Operating characteristicsRestricted earth fault protection, Ibias
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 11
The restricted earth fault protection may be very sensitive No room for any false unbalance currents
External faults may cause CT saturation false residual currents
false tripping
The stabilizing characteristics helps tostabilize to some extent
Objective: Positively distinguish between internal and
external earth faults
Enhancing the security for heavy external faults
IN , 3I0, IDiff
Operating characteristicsDirectional criterion
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 12
Same direction in the neutral for both external and internal faults Current in the neutral serves as directional reference
External fault The currents are 180o out of phase (IED reference direction: towards the object)
Operating characteristicsDirectional criterion
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 13
Internal fault The residual currents are approximately in phase
Not measuring the same primary current, IN and 3I0
Setting: Relay operate angle (ROA) 60 – 90o
Operating characteristics Directional criterion
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 14
The directional check is executed if: within the operate area of the REF-
characteristic
3I0 (terminal side) is at least 3% of IBase
The trip is issued if: both 3I0 an IN are within the operating region
If the check is not executed (small currents) then: the check is not a condition for trip
Operating characteristics Directional criterion
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 15
Prevent unwanted operation on reactor energizing due to terminal side CT saturation cased by
high DC component
The calculation adaptive (input: 3I0, IN, IBias and timing)
No setting: 2nd harmonic ratio: fixed to 60%
IN 3I0
Cur
rent
[pu]
Cycles
Shunt reactor switching150 Mvar 220 kV 50 Hz
Operating characteristics Second harmonic blocking
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 16
Directionalcheck
TRIP
START
&
≥1
IN > 50% of Idmin&
3I0 < 3% of IBase
3I0 > 3% of Ibase
3I0
IN
Simplified logical diagramRestricted earth fault protection
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 17
Residual current - W1 - CT1
Block input
Neutral point current
- W1 - CT2
Binary input signal
Analog input signals (SMAI group signal output)
- W2 - CT1- W2 - CT2
In- and output signals Restricted earth fault protection
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 18
TripStartDirectionality: High Internal faultSecond harmonic blockingResidual current W1+W2 (3I0)
Binary output signals
Analog output signals HMI and Disturbance recorder
Neutral current (IN) Bias currentDifferential currentAngle from zero sequence feature Second harmonic ratio
In- and output signals Restricted earth fault protection
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 19
Base valuesOperation On/Off
Pick up levelFactors influencing bias
Restricted earth fault protection settingsOverview
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 20
Tests/Functions status/Differential Protection/LowImpREF(PDIF,87N) TRIP
START
DIROK – Internal fault
BLK2H – Block due to 2nd harmonic
IRES – Magnitude of residual current (3I0, A)
IN – Magnitude of neutral current (A)
IBIAS – Magnitude of bias current (A)
IDIFF – Magnitude of differential current (A)
ANGLE – Direction angle from zero sequence feature (deg)
I2RATIO – Second harmonic ratio
Monitored dataRestricted earth fault protection
Chapter 04
© ABB GroupSeptember 10, 2015 | Slide 21© SA-T TrainingSeptember 10, 2015 | Slide 21