Commercial Rinnai Forever Hot Water The water heating system preferred by more Consumers, Home Builders, Business Owners & Installers. You don't use hot water 24 hours a day, but, you're paying to heat water all day long. With a standard water heater, you heat and reheat the same water…even when you're sleeping. Forever Hot Water tankless heating technology is a more efficient way to heat water tankless heating technology is a more efficient way to heat water while saving money and recapturing valuable space in your mechanical room. The Benefits Using the latest in gas technology, it heats water on-demand and delivers an endless supply of hot water for as long as you need it, offering personalized control for your convenience, comfort and safety © 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us safety.

Upload: others

Post on 26-May-2020

5 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Commercial Rinnai• Forever Hot Water• The water heating system preferred by more

Consumers, Home Builders, Business Owners & Installers. You don't use hot water 24 hours a day, but, you're paying to heat water all day long. With a standard water heater, you heat and reheat the same water…even when you're sleeping. Forever Hot Water tankless heating technology is a more efficient way to heat watertankless heating technology is a more efficient way to heat water while saving money and recapturing valuable space in your mechanical room.

• The Benefits• Using the latest in gas technology, it heats water on-demand and

delivers an endless supply of hot water for as long as you need it, offering personalized control for your convenience, comfort and safety

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

safety.

Page 2: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Rinnai Corporation

• Rinnai Corporation is the largest gas appliance f t i th ld E t bli h d i 1920manufacturer in the world. Established in 1920 as a

manufacturer of gas and oil appliances, Rinnai has expanded its business line and today offers a wide range p y gof appliances for home including kitchen appliances, water heating systems, heating and air conditioning units as well as products designed for similar commercial useas well as products designed for similar commercial use. The company built its reputation based upon its achievements in technological innovation, manufacturing ffi i lit d f t

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

efficiency, quality and safety.

Page 3: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Established Company

• Rinnai’s US operation, located in Peachtree City, GA, is ibl f th k ti d di t ib ti f Ri iresponsible for the marketing and distribution of Rinnai

Corporation’s innovative products in North America. Since its inception in 1975, Rinnai’s US product line has p pgrown from distributing spa heaters to marketing and distributing today's extensive product line that includes cooking products direct vent ductless furnaces vent-cooking products, direct vent ductless furnaces, ventfree fan convectors, cooking products, commercial water heaters, and the Rinnai tankless water heating systems.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 4: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Distributors/ Installation

• Rinnai has more than 2000 distributors and more than 60 000 tifi d i t ll th h t th U it d St t60,000 certified installers throughout the United States. Rinnai is installed by registered Rinnai installers to assure proper installation and service. As a responsible p p psupplier to consumers, every prospective installer must go through an installation training class before they are approved as a Rinnai certified installer In addition everyapproved as a Rinnai certified installer. In addition, every installer must comply with state requirements for contractors.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 5: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Water Heater Types Available » Rinnai offers both residential and commercial units in both

d/ t lpropane and/or natural gas.

» Residential units are used in potable water applications only. The maximum water temperature setting is 140 °FThe maximum water temperature setting is 140 F.

» Commercial units are used in potable water applications for restaurants schools hotels car washes hair salons coinrestaurants, schools, hotels, car washes, hair salons, coin laundries, assisted care facilities, camp grounds, etc. The maximum water temperature setting is 185 °F.

» Hydronic heating applications are also allowed with the commercial units.

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 5

DO NOT use these units in any applications involving chemically treated water, (i.e. chlorinated pool water, hot tubs, etc.)

Page 6: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

The LS Series: OverviewThe LS Series: Overview

Page 7: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Major Improvements:

• Improved heat exchanger design– LS Series can do both commercial and residential

li tiapplications• Integrated condensate collector for indoor units• Female vent tops• Female vent tops

• Eliminates need for venting adapters

• EZ Connect• Allows connection of 2 water heaters without use of MSA

• Higher BTU inputs for internal units • R85i = 180 000 R94/R75 = 199 000

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

• R85i = 180,000 R94/R75 = 199,000

Page 8: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

LS Series Spec Summary

ModelMarket

PositionLaunch

DateFlange-

less

Comm'l Applica-

tion Color Min. Btu Max. BtuMin.

Temp.

Max.Temp

ResidentialMax. Temp

CommercialMax.GPM

Standard Remote

R75LSe Flagship Oct-07 ○ ○ Silver 15,000 199,000 98° 140° 160° 7.5 MC-91g p ○ ○ , ,R94LSe Flagship Oct-07 ○ ○ Silver 15,000 199,000 98° 140° 185° 9.4 MC-91R75LSi Flagship Oct-07 ○ ○ Silver 15,000 199,000 98° 140° 160° 7.5 MC-91R94LSi Flagship Oct-07 ○ ○ Silver 15,000 199,000 98° 140° 185° 9.4 MC-91

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 9: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

V-LS Cross Reference ListV Units LS Equivalents

2526W R75LSe

2532W, 2532WD, 2532WC/D R94LSe

2520FFU, 2520FFUD, 2520FFUC/D R75LSi

2532FFU, 2532FFUD, 2532FFUC/D R94LSi

Total Models: 13 4

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 10: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

PRODUCT

FEATURES

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 11: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

• Whole house continuous hot water system when properly sized. Features

• Endless hot water - never run out of hot water.

• Thermal efficiency from 80% to 89% (depending upon model). y % % ( p g p )

• Energy Factor rating of 0.78 to 0.84 (depending upon model)*.

• Remote control for water temperature control.

• Space saving, compact size.

*Appliances over 200,000 Btu’s do not have an Energy Factor rating.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us11

Page 12: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Features• Direct electronic ignition (no standing pilot)• Direct electronic ignition (no standing pilot).

• Very low noise level, 49 decibel

• S f l l l• Safe, low voltage remote controls.

• All parts are replaceable.

• Life expectancy of 20+ years.

• Residential warranty: ten years heat exchanger, five years all y y g , yother parts, one year labor.

• Commercial warranty: five years all parts one year labor

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Commercial warranty: five years all parts, one year labor.

Page 13: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Safety Devices

• Flame rod indicates flame failure.

• Over heat sensor (bi metal) activates at 194°F• Over heat sensor, (bi-metal) activates at 194°F.•• Boiling protection switch activates at 203°F.

• Thermal fuses activate at 279°F.

• Built-in freeze protection to -30ºF. p

• Combustion fan rpm check indicates blocked flue or intake vents.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 14: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Remote Controls

• Model MC-91 controller;•

- Adjustable from 98°F to 140°F in residential applications.• Adj t bl f 98°F t 185°F i i l li ti• - Adjustable from 98°F to 185°F in commercial applications.• - Up to four controllers allowed per installation. • - Can be installed in a kitchen, laundry, master bath, and/or • d b h• a secondary bath.• - Records unit’s flow rate.• - Records unit’s output water temperature. • - Stores valuable data related to unit’s performance history. • - Displays diagnostic codes

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 15: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

MC 91 Cont olleIN USE INDICATOR

Indicates that a hot water tap is

MC – 91 Controller

PRIORITY BUTTON & INDICATOR

popen and that control of the temperature is taken at another controller. DIGITAL MONITOR

Indicates the selected & INDICATORPressing takes control of the water temperature by this controller.

Indicates the selected water temperature. Error messages flash in the event of a failure.

THERMOSTATIncreases or decreases the desired water temperature.

ON/OFF BUTTON

Turns water heater on or off

MODEL NOIndicates remote control model number

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

off.model number

Page 16: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Wireless Remote Control ReceiverCommunication

Strength

P i it

Battery Life

Indicates strength of signal.

Priority

Indicates priority hasbeen taken by this

remote control.

Indicates remainingcharge in battery

Digital Monitor

Indicates the selectedwater temperature. Error

messages flash in the eventof a failure

Thermostat

Increases or decreases thedesired water

of a failure.

On/Off Button

Priority Button

Turns unit on or off

Pressing takes controlof the water temperatureby this remote control.

temperature

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 16

Page 17: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

COMPONENTS

& OPERATION

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 18: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Temperature / Flow Rate

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 19: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

1. Water flow begins.- Water Flow Sensor sends pulses to the PCB.

Sequence of Operation

- PCB senses flow greater than 0.6 GPM.- Firing Sequence begins.

2. Firing Sequence. PCB monitors inlet/outlet water temperature- PCB monitors inlet/outlet water temperature,remote control temperature set point and water flow rate.

- Combustion fan energized.Spark igniter begins sparking- Spark igniter begins sparking.

- Gas control valve opens to minimum fire rate.- Flame rod proves ignition.- Spark igniter stops sparking.

3. Normal Operation. - PCB monitors flame rod, fan motor frequency,

outlet water temperature, remote control temperature set point and water flow rate.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us19

temperature set point and water flow rate.- Gas control valve modulates gas input to

required firing rate.

Page 20: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

S f O ti

- Combustion fan speed is adjusted for the

Sequence of Operation

- Combustion fan speed is adjusted for the required firing rate.

- Water flow control valve is adjusted, as needed.

4 Shut-down Sequence4. Shut-down Sequence. - PCB senses flow rate less than 0.5 gpm.- Gas control valve closes.- Water flow control valve resets to standby

positionposition.- Combustion fan runs for a short period of time

at low speed.

5 Standby Mode5. Standby Mode.- PCB monitors water temperature and remote

controls.- Freeze protection is activated as needed.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us20

Page 21: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Outdoor Unit Schematic Diagram

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 22: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Indoor Unit Schematic Diagram

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 23: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

WATER & GAS PIPING INSTALLATION» The following plumbing drawings are not intended to describe acomplete system. It is up to the engineer/contractor to determine thenecessary components needed for the configuration of the particulary p g psystem being installed.

» The following plumbing drawings do not imply compliance with localg p g g p y pbuilding code requirements. It is the engineer/contractor’s responsibilityto ensure the installation is in accordance with all local and state buildingcodes. Confer with your local building officials before installation.

» All water and gas lines MUST be installed by a qualified or licensedplumber or gas technician.

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 23

Page 24: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Piping-Basic SetupHot & Cold water supply lines to be minimum ¾” piping.

Recommended inlet water pressure; 30-80psi.

Gas piping must be sized for maximum input firing rate of water heater Gasinput firing rate of water heater. Gas system MUST be sized to handle total Btu load of building.

Required inlet gas pressures:Required inlet gas pressures:

6”-10” w.c., Natural gas

10”-13.5” w.c. L.P. gas

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us24

Page 25: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Piping-Storage/Recirculation

Refer to pressure drop curve for model number heater being used and Hot Water System Design manual in order to size circulator pump properly. Drawing is using a R85 unit.

Commercial units MUST be used if the application is not a single family dwelling.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us25

Page 26: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Piping-6 Units & Backup/Recirc.

MSA C t l t i dMSA Controls not required

Pump sized for 42 gpm@ 35 foot of head.

Refer to pressure drop curve for model number heater being used and Hot Water SystemDesign manual in order to size circulator pump properly. Above drawing is using R85 units.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us26

g p p p p y g g

Commercial units MUST be used if the application is not a single family dwelling.

Page 27: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Piping-5 Unit Manifold

MSA controls would be required.

Refer to pressure drop curve for model number heater being used and Hot Water Design manual in order to size circulator pump properly. Above drawing is using a R85 unit.

Commercial units MUST be used if the application is not a single family dwelling.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us27

Page 28: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Sizing Guidelines• Each installation is unique and can vary depending on the application, demand, and

input/output characteristics (i.e. incoming water temperature, pipe sizing, etc). F th d t t t i t th i fl t hi d bFurthermore, ground water temperature can impact the maximum flow rate achieved by the product. It is important to contact Rinnai’s Engineering / Applications department for assistance in sizing all residential and commercial jobs. Please call 1-800-621-9419 for support or utilize Rinnai’s sizing calculators available at www.rinnaisolutions.com.

• Commercial dishwashers;

• 1. Typically, in applications involving commercial dishwashers, two or more tankless water heaters are needed. Contact Rinnai Engineering / Applications department at 1-800-621-9419 for proper sizing in all commercial dishwasherdepartment at 1-800-621-9419 for proper sizing in all commercial dishwasher applications. (Have the dishwasher model number available).

•• 2. A circulating system is required in all commercial dishwasher applications to

ensure you have hot water available at the dishwasher when it calls for hot water. CCirculating systems are also required in tank water heater applications.

• 3. DO NOT use a tankless water heater as a booster heater for commercial dishwashers. When using a tankless water heater in conjunction with a hot water sanitizing type dishwasher a booster heater recommended by the dishwasher

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 28

sanitizing type dishwasher a booster heater recommended by the dishwasher manufacturer must be used.

Page 29: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Commercial ApplicationsExisting/Specified Equipment

Rinnai Replacement EquipmentEquipment

199,000 Btu/ 100 gallonWater Heater

⇒ or+ 120 gal

storageWater Heater

250,000 Btu/ 100 gallon ⇒ or

+ 80 galstorage

Water Heater

270,000 Btu/ 100 gallon ⇒

or

+ 120 gal

storage

100 gallonWater Heater

399,000 Btu/ 100 ll ⇒

or

+ 120 gal

storage

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

100 gallonWater Heater

⇒or

gstorage

Page 30: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

MANIFOLDMANIFOLD

INSTALLATIONSINSTALLATIONS

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 31: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Multiple UnitMultiple Unit

MSA Controls InstallationMSA Controls Installation

Use MSA controls when banking multiple units on the same manifold system in residential or commercial applications. The MSA controls will sequence or rotate between units to prevent one unit from being a “work horse”. In addition, p g ,these controls ensure each unit is firing at the same rate during operation, and it electronically balances the flow rate through each unit, eliminating the need for balancing valves.

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 31

Page 32: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

MSA - 2M Master Board and wiring harness (MSA-2S) Connections

Manifold Controls g ( )

When manifolding two R98/C98 Models, an MSA b d i t Aboard is not necessary. An

EZConnect cable can be used connecting to a special harness

on the primary unit (picture below) and the PCB on the secondary unit (picture tosecondary unit (picture to

right). Three or more R98/C98 Models will require the MSA

components.

In an MSA configuration, a special harness connects to the MSA controller board (left arrow), a single red wire (middle arrow),

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us32

and each unit’s PCB (right arrow).

Page 33: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

MSA Manifold Controls for the REU-25 Series

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

MSA-2M Pack MSA-2M Pack

Page 34: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

External Unit Recess BoxThe rough in dimensions for the R85e, C85e, R70e recess box are;

Length 40 ½”Width 14 ¾”Depth 9 ½”

The rough in dimensions for the R42e, C42e, R53e and C53e recess box are;

Length 40 ½”Width 14 ¾”Width 14 ¾”Depth 7 ½”

The rough in dimensions for the R98e and C98e recess box are; ;

Length 40 ½”Width 19 ¼” Depth 9 ½”

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 34

NOTE: Designer Plus Series will not fit in the recess box. Moisture Seal Recess Boxes are available.

Page 35: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Commercial

ApplicationsApplications

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 36: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

McDonald’s Restaurant (1) REU-2424-W Water Heater( )

• One unit handles all hot water needs for this restaurant.

ll d f• Unit was installed on roof in a recess box.

• Customer gain twenty square foot of space for addition storage.

• The space taken up by a tank• The space taken up by a tank water heater is wasted space and is figured to cost a restaurant $30.00 per month f hi d i

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

for thirty years, per design engineers .

Page 37: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Krystal Restaurant (1) REU-2532-W Water Heater

• One unit handles all hot water needs for this restaurant.

• Unit was installed on roof.

• Customer gain twenty square foot of space for addition storage.

Th t k b t k t• The space taken up by a tank water heater is wasted space and is figured to cost a restaurant $30.00 per month for thirty years, per design y y , p gengineers .

• Manager claims to have noticed a 50% saving in his gas utility bill

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

50% saving in his gas utility bill.

Page 38: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Arby’s Restaurant (1) C85i Water Heater

• One unit handles all hot water needs for this restaurant

• Unit installed in storage space outside• Unit installed in storage space outside building

• Customer gained twenty square feet of space for additional storageof space for additional storage

• The space taken up by a tank water heater is wasted space and is figured to cost a restaurant $30 00 perto cost a restaurant $30.00 per month, for thirty years, per design engineers

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 38

• Manager claims to have noticed a 50% saving in his gas utility bill

Page 39: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

C l llCountry Place Village• (7) Rinnai REU2424-W Water Heaters in

brecess boxes.

• This facility has two separate plumbing systems, one for the rooms, and one for h k h h lthe kitchen. This eliminate using expensive

mixing valves.

• Five of the units handle fifty-two rooms.Five of the units handle fifty two rooms. These units are set at 110 ºF to meet Health Department requirements.

• Two additional units handle the commercial• Two additional units handle the commercial kitchen, set to operate at 140 ºF.

• By placing the units outside the customer gained a one hundred square foot of space

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

gained a one hundred square foot of space back in his equipment room.

Page 40: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Capital Hill Assisted Care

• (4) REU2532-FFUC Water Heaters are being used to handle the laundry forbeing used to handle the laundry for this 200 bed nursing facility.

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us

Page 41: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Maytag Laundry

• 2 Rinnai REU-2532-WC Water Heaters• 2 Rinnai REU-2532-WC Water Heaters

• Customer installed units on roof.

• Space saved by removing old system

from inside building allowed owner to

install two additional dryers.

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us

Page 42: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Henderson High School• 6 Rinnai REU2424-W Water Heaters.

• Units were installed on roof.

• The plumbing system was split into three separate systems to eliminate expensive mixing valves.

• System #1 is four units handling 24 showers.

• System #2 is one unit handling a 250 gallon whirlpool tub.

• System #3 is one unit handling two commercial washing machines.

• The above Rinnai system replaced a one

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us

thousand gallon, three phase electrical system. It also freed up four hundred square feet of storage space.

Page 43: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Sonora High School• (11) R85e Water Heaters

• Units handle 49 showers 17 labs and• Units handle 49 showers, 17 labs, and one commercial washing machine

• Ten units handle the showers and labs set at 120 ºFat 120 ºF

• One unit handles the commercial washing machine. By splitting the system it eliminated the use of an expensive mixingeliminated the use of an expensive mixing valve

• This system replaced a one million six h nd ed tho nd Bt boile ith fi ehundred thousand Btu boiler, with five hundred gallons of storage. The Rinnai system was installed for $5,500.00 less than a replacement boiler, and it reduced

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us43

p ,the customer’s gas bill by $700.00 a month, in 2000

Page 44: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Big Bucket Car Wash

(8) C85i units with 320 gallons of storage handle this car wash

• Ten standard bays

• Two large truck bayso a ge t uc bays

• Two automatic car wash bays

The Rinnai units replaced four• The Rinnai units replaced four 560,000 Btu units, with six hundred gallons of storage

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 44

Page 45: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Mercer University Dormitory Rooms

8 REU-2532-FFUC units handle all the domes8 REU-2532-FFUC units handle all thedomes8 REU 2532 FFUC units handle all the domestic hot water and laundry area For the students dorm rooms. tic hot water and laundry area F h d dFor the students dorm rooms.

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 46: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Ramada Inn

(15) R85e units handle this one hundred and ninety room hotel and convention centerconvention center

• Units are mounted on roof

Ci l ti t i h dl d• Circulating system is handled through a large storage tank water heater

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us 46

Page 47: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 48: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

© 2006 Rinnai Corporation 103 International Drive • Peachtree City, GA 30269 www.rinnai.us

Page 49: 04 Rinnai MORAN - tech-4-you.com · • Rinnai’s US operation, located in Peachtree City, GA, is responsibl f th k ti d di t ib ti f Ri iible for the marketing and distribution

Okaloosa County Department of Corrections

• 10 Rinnai REU-2532-W water heaters.

• Three separate plumbing systems• Three separate plumbing systems are being used at this facility.

• System #1 has four units handling showers for 300 inmates.

• System #2 has four units handling showers for an additional 300showers for an additional 300 inmates.

• System #3 has two units handling th kit h f thi 600 i t

Rinnai Corporation 103 International Drive Peachtree City, GA 30269 800.621.9419 770.829.1700 www.rinnai.us

the kitchen for this 600 inmate facility.