    DISPLAYS

    OPERATIONAL (yellow) : It turns oncontinuously for 6 seconds after power-up orreset. It flashes while the unit is operational.

    EARTHQUAKE (red) : It turns on when the unitdetects a strong motion.

    CABLE BROKEN (red) : It turns on when the unitdetects the rupture of the solenoid cable.

    BATTERY LOW (red) : It turns on if the batteryvoltage falls below the Battery Low Warning Limit.

    SELF TEST

    The unit performs self test at power_on or reset.During the self test, the OPERATIONAL led turnson steadily.

    The self test consists on the application of anexternal acceleration signal to the sensors andchecking back the detection.

    If the unit passes self test, the OPERATIONALled starts to flash normally. If the self test fails, allleds flash, the audible alarm is activated and therelay output is energized.

    INSTALLATION

    The unit is designed for vertical mounting. Thusthe sensors will be placed in the horizontal planeas requested by the standards.

    The unit has an indoor type panel. Do not installthe unit outdoor or at highly humid or warm

    environments.

    The solenoid valve used should have a 12 V-DCcoil. Please contact DATAKOM for the list ofcompatible solenoids.

    The solenoid cable should not exceed 12 metreswith 2x1mm2 cable and 20 metres with 2x1.5mmcable.

    Energize the unit only after the installation iscomplete. When the OPERATIONAL led isflashing, press the TEST key in order to checkvalve operation.

    WARNINGS

    After installation, the OPERATIONAL led shouldbe flashing.

    No red light should be visible on the unit. Howeverif the battery is discharged, the BATTERY LOWled may turn on for a few minutes. Please resetthe unit in this case. If the led turns off, this is nota failure.

    If the EARTHQUAKE led turns on at power-on,please reset the unit. It will turn off.

    PERIODIC MAINTENANCE

    Do not wash the unit. Use a soft damp cloth ifnecessary.

    MONTHLY MAINTENANCE: check that theyellow led is flashing and no red led is on.

    YEARLY MAINTENANCE:

    1) Check that the yellow led is flashing and no redled is on.2) Press the TEST button and check the solenoidoperation.3) Press the RESET button. Check that after afew seconds, the yellow led is flashing and no redled turns on.

    AFTER THE EARTHQUAKE

    The unit will operate the solenoid valve during theearthquake.

    Do not reset the unit. It will be reset only after

    checking earthquake damages by an authorizedperson, otherwise severe risks may occur.

    TECHNICAL SPECIFICATIONS

    AC Power Supply Range: 170 to 270 V-ACAC Frequency range: 45 to 65 HzAC Power Consumption: 3 VA maxBattery Voltage range: 11.5 to 16.3 V-DC12V-DC Supply Current:

    15mA typical60 mA max. (relay output open)

    Relay output: 10A / 12V-DCOutput Pulse Duration: 0.25 sec. (repeatedevery 30 sec.)Audible Alarm: through 85 dB/1m buzzerInternal Battery: 2.2 A-h / 12V-DCBattery Life: minimum 24 hours

    typically 200 hoursBattery Low Warning Limit: 11.5 +/- 0.3 V-DCSensor: Dual axis micro-machined polysilicon

    accelerometersAcceleration Threshold: 180 mg at 2.5HzDetection Delay: 0.5sec maximumFrequency response: 0.5 Hz to 10 Hz.

    Non-earthquake signals filteredCable Broken Limit: 680 ohms (typical)Diagnostics: Self-diagnostics at power-on and

    resetOperating temperature range:

    -20 to 70 C (-4 to +158F)Weight: 3200 grams (approx.)Dimensions: 232 x 200 x 65 mm (W x H x D)Conformity: ANSI Z21.70(1981)

    ASCE 25-97TS 12884