OVERHEAD ELECTRICAL
ALUMINUM CONDUCTORS
Taihan Electric Wire opening up the happier world and more enriched future
CC OO NN TT EE NN TT SS
OVERHEAD ELECTRICAL
ALUMINUM CONDUCTORS
Description of A.C.S.R
Typical Construction for A.C.S.R.
KS JIS KEPCO TEC
ASTM ANSI
IEC
BS AS CSA DIN
Packing and Marking
Alphabetical List
3
4
5
21
41
47
58
61
HAL, AAC, ACSR, TACSR, ACSR/AW, AWS, STACIR,
STACIR/AW,HSTACIR/AW, TACSR/AW, HTACSR/AW,
HAL-OC, ACSR-OC, ACSR/AW-OC
HAL, AAC, ACSR, ACSR/AW, AWS, AL-ALLOY, AAAC,
H.S-ACSR, HAL-OC, ACSR-OC
AAC, ACSR, ACSR/GZ, ACSR/AZ
AAC, AAAC, ACSR, AACSR/EST
2 Overhead Electrical Aluminum Conductors TAIHAN
Description of A.C.S.R.Bare aluminum conductors, especially in the form of Aluminum Conductors Steel Reinforced(ACSR), have been widely used for
overhead transmission lines as the most cost-effective and dependable product.
As the name implies, ACSR is a concentrically stranded conductor composed of one or more layers of hard-drawn EC grade
aluminum wires over a high strength coated steel core. The core may be single wire or stranded, depending on the size. Because
of the numerous stranding combinations of aluminum and steel wires that may be used, it is possible to vary the portions of
aluminum and steel so as to obtain the most suitable relation between current carrying capacity and mechanical strength for each
application.
For instance, a conductor having a small proportion of steel may be most economical for a wood pole line to transmit a large block
of power whereas a conductor with a very large proportion of steel would be required for a long span crossing over water. Between
these two extremes are the conductors with normal proportions of aluminum and steel generally used for the more conventional
transmission and distribution lines.
Anti-corrosion A.C.S.R. Anti-corrosion ACSR is used in the corrosive areas like coastal areas or industrial zones. This ACSR is filledwith anti-corrosive grease applied on the gaps between stranded wires and their external surfaces.
Generally, anti-corrosion ACSR is divided into three types according to the method of greases coating :Light Anti-corrosion Type : Only steel wires are coated
Medium Anti-corrosion Type : All the inner layers are coated
Heavy Anti-corrosion Type : All the inner and outer layers are coated
Light Anti-corrosion Type(ACSR-LZ)
Grease
Medium Anti-corrosion Type(ACSR-MZ)
Grease
Heavy Anti-corrosion Type(ACSR-HZ)
Grease
3TAIHAN Overhead Electrical Aluminum Conductors
Smooth Body 3 Al./ 4 St. 4 Al./ 3 St. 6 Al./ 1 St.Smooth Body
6 Al./ 7 St. 8 Al./ 7 St. 12 Al./ 7 St. 7 Al./ 1 St.8 Al./ 1 St.
16 Al./ 19 St. 18 Al./ 19 St. 21 Al./ 37 St. 18 Al./ 1 St.15 Al./ 19 St.
26 Al./ 7 St. 26 Al./ 19 St. 30 Al./ 7 St. 30 Al./ 19 St.24 Al./ 7 St.
42 Al./ 19 St. 54 Al./ 7 St. 54 Al./ 19 St.34 Al./ 19 St.
Typical Construction for A.C.S.R.
4 Overhead Electrical Aluminum Conductors TAIHAN
O V E R H E A D E L E C T R I C A L A L U M I N U M C O N D U C T O R S
Korean Industrial Standards
Japanese Industrial Standards
Korea Electric Power Corp. Standard
Taihan Standard
KS
JIS
KEPCO
TEC
5TAIHAN Overhead Electrical Aluminum Conductors
TAIHAN Aluminum Clad Steel Wire offers excellentperformance and advantages with improved techniques,especially in the higher grade aluminum conductorswhich are also reasonable in price
TAIHAN Aluminum Clad Steel Wire offers excellentperformance and advantages with improved techniques,especially in the higher grade aluminum conductorswhich are also reasonable in price
These sizes are specified in KS.
Hard-drawn Aluminum Wires for Electric Purposes
ApplicationThis standard covers hard-drawn circular aluminum wires for electricpurposes to be used mainly as component wires of hard-drawnaluminum stranded cables and aluminum cables steel reinforced.
ConstructionSingle aluminum conductor
StandardsConforms to KS C 3111, JIS C 3108
HAL
Diameter Toleranceon Dia.
Tensile Strength(kgf/mm2)
Min. (%) (%) (mm2) (kg/km) ( /km, 20 )Mean
(above)
Elongation(in 250mm)
(above)
Conductivity(above) Cross
SectionalArea
Weight
Min.Mean
(above)
Tensile Load (kgf)
ElectricResistance
Reference
(mm) (mm)
1.61.82.02.32.62.82.93.13.23.53.73.84.04.24.54.85.0
0.030.030.030.030.030.030.030.030.040.040.040.040.040.040.040.040.04
19.018.618.617.917.216.916.916.516.516.516.516.516.216.216.216.216.2
20.019.719.719.018.317.917.917.617.617.617.217.216.916.916.916.916.9
1.31.41.41.51.51.61.61.71.71.71.81.81.92.02.02.02.0
6161616161616161616161616161616161
2.0112.5453.1424.1555.309 6.1586.6057.5488.0429.621
10.7511.3412.5713.8515.9018.1019.64
5.4306.8728.483
11.2214.3316.6317.8320.3821.7125.9829.0330.6233.9437.4042.9348.8753.03
38.247.358.474.491.3
104112125133159177187204224258293318
40.250.161.978.997.2
110118133142169185195212234269306332
14.111.1
9.006.805.324.594.283.743.512.942.632.492.252.041.781.561.44
(Table 1)
6 Overhead Electrical Aluminum Conductors TAIHAN
Stranded Hard-drawn Aluminum ConductorAAC
ASTM
ANSI
IEC
BSAS
CSA
DIN
ApplicationThis standard covers stranded hard-drawn aluminum conductors to beused mainly for overhead distribution wire, overhead feeders andbuses.
ConstructionStranded hard-drawn aluminum conductors
StandardsConforms to KS C 3112, JIS C 3109
These sizes are specified in KS.
NominalCross
SectionalArea
No. andDia. ofStrands
TensileLoad
(above)Calculated
CrossSectional Area
OutsideDia.
Weight ElectricResistance
Hard-drawnCopper
Equiv. Area
StandardLength
Reference
(mm) (mm) (kgf) (mm2) (mm) (kg/km) ( /km, 20 ) (mm2) (m)
22303845557595
100125150200200240250300325400460500510590660725770850880980
1,0001,260
7/2.07/2.37/2.67/2.97/3.27/3.77/4.2
19/2.619/2.919/3.219/3.737/2.619/4.037/2.937/3.261/2.637/3.737/4.061/3.237/4.261/3.561/3.791/3.261/4.061/4.291/3.591/3.7
127/3.291/4.2
369469576699838
1,1201,4101,5601,9002,2703,0303,0503,4903,7004,4305,0205,8906,7607,3007,4608,7309,720
10,89011,14012,30013,02014,50015,20018,350
21.9929.0937.1646.2456.2975.2596.95
100.9125.5152.8204.3196.4238.8244.4297.6323.8397.8465.1490.6512.5586.9655.8731.8766.8844.9875.5978.3
1,0211,260
6.06.97.88.79.6
11.112.613.014.516.018.518.220.020.322.423.425.928.028.829.431.533.335.236.037.838.540.741.646.2
60.0979.40
101.5126.3153.8205.6264.9276.4343.9418.7559.8541.3654.5673.6820.1894.2
1,0971,2821,3551,4131,6211,8122,0272,1182,3342,4262,7162,8403,499
1.3010.9840.7690.6190.5070.3800.2950.2840.2290.1880.1400.1470.1200.1180.09690.08920.07260.06210.05890.05630.04930.04410.03960.03770.03420.03310.02970.02850.0230
1418232935 4760637996
128124150154187204250292309322369412460482531551615642792
2,0001,8001,8001,0001,0001,9001,0002,4002,0001,5001,3002,4001,3002,0001,5001,2001,3001,000
8001,3001,3501,300
8001,0001,300
700600800600
(Table 2)
KSJI
SKE
PCO
TEC
7TAIHAN Overhead Electrical Aluminum Conductors
ApplicationThis standard covers aluminum stranded conductors steel reinforcedwhich could withstand high tensile load to be used mainly for overheadtransmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of galvanized steel and the outer layer orlayers of aluminum.
StandardsConforms to KS C 3113, JIS C 3110
These sizes are specified in KS.
NominalCross
SectionalArea
No. and Dia. of Strands
(No./mm)
TensileLoad
(above)
( /km, 20 ) (mm2) (m)(kgf)
Calculated CrossSectional Area
(mm2)
Outside Dia.
(mm)
Weight ElectricResistance
Hard-drawnCopper
Equiv. Area
StandardLength
Reference
(mm2) Al Al AlSt St St (kg/km)
1215192532384048505864657579809597
110120120140160170200210240250280290290320330330360380
6/1.66/1.86/2.06/2.36/2.6
12/2.06/2.96/3.2
12/2.36/3.5
12/2.66/3.76/4.0
12/2.96/4.26/4.5
12/3.226/2.312/3.530/2.326/2.630/2.626/2.930/2.926/3.230/3.226/3.526/3.754/2.630/3.530/3.754/2.826/4.054/2.930/4.0
1/1.61/1.81/2.01/2.31/2.67/2.01/2.91/3.27/2.31/3.57/2.61/3.71/4.07/2.91/4.21/4.57/3.27/1.79
7/3.57/2.37/2.07/2.67/2.25
7/2.97/2.57/3.27/2.77/2.97/2.67/3.57/3.77/2.87/3.17/2.9
19/2.4
448567698907
1,1403,2501,4001,6604,3401,9805,5102,2202,5106,8202,7703,1808,0503,9639,5905,5504,8106,9905,9808,6207,240
10,2108,5909,7808,820
12,17013,63010,29010,93010,92015,920
12.0715.2718.8524.9331.8537.7039.6348.2549.8657.7363.7164.5075.4279.2683.1095.4096.50
108.0115.5124.7138.0159.3171.7198.2209.1241.3250.1279.5286.7288.6322.5332.5326.8356.7377.1
2.0112.5453.1424.1555.309
21.9906.6058.042
29.0809.621
37.1610.7512.5746.24 13.8515.90 56.2917.61 67.35 29.0921.9937.1627.8346.2434.3656.2940.0846.2437.1667.3575.2543.1152.8446.2485.96
4.85.46.06.97.8
10.08.79.6
11.510.513.011.112.014.512.613.516.014.5717.516.116.418.218.3520.320.322.422.123.523.424.525.925.225.326.128.0
1.61.82.02.32.66.02.93.26.93.57.83.74.08.74.24.59.65.37
10.56.96.07.86.758.77.59.68.18.77.8
10.511.1
8.49.38.7
12.0
48.7361.6676.12
100.7128.6390.4160.0194.8365.2233.1466.5260.5304.6580.4335.5385.2706.8437.4845.6573.7554.7732.8693.8911.7848.5
1,1101,0071,1371,0861,3281,4841,2601,3201,3511,721
2.374 1.8781.521.1500.8990.76470.7230.5930.57750.4970.4520.4440.3800.3640.3450.3010.3010.26690.2500.2330.2100.1820.1690.1470.3190.1200.1160.1040.10060.1010.09000.08730.08880.08140.0770
81012162024253031364041475052606070737890
100110125130152160176180180203210206220240
2,2001,7001,0001,0501,0001,4001,5501,2501,0501,000
9501,2501,1001,5001,0001,3001,2501,2501,0001,3001,4501,9001,2501,4002,0001,4001,7501,5001,6501,0001,2501,6001,0001,3001,100
(Table 3)
Galvanized steel
Aluminum conductor
Aluminum Conductors, Steel Reinforced HCSR
8 Overhead Electrical Aluminum Conductors TAIHAN
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
Remarks1. The values of Table are those at 20 .
2. The values of calculated sectional area, outside diameter and weight are those for the standard diameters of individual wires. The electricresistance is calculated for the standard diameter, by assuming the conductivity of the hard-drawn aluminum wires at 61% and neglectingthe galvanized steel wires.
3. The sectional area of hard-drawn copper stranded conductor with equivalent resistance is calculated by assuming the conductivity of thehard-drawn copper wires at 97% and that of the hard-drawn aluminum wires for electric purposes at 61% and neglecting the length increaseby stranding.
4. The ratio of length increase by stranding to be used for calculating the weight and electric resistance shall be as follows :
5. The tensile load is calculated as 90% of the sum of the minimum tensile load of hard-drawn aluminum wire for electric purposes multipliedby the number of aluminum component wires and tensile load of galvanized steel wire multiplied by the number of steel component wires.
5430262
7771
2.72.72.61.4
0.50.50.50
Construction of CableAluminum Wires Steel Wires Aluminum Wires Steel Wires
Ratio of Length lncrease by Stranding(%)
These sizes are specified in KS.
NominalCross
SectionalArea
No. and Dia. of Strands
(No./mm)
TensileLoad
(above)
( /km, 20 ) (mm2) (m)(kgf)
Calculated CrossSectional Area
(mm2)
Outside Dia.
(mm)
Weight ElectricResistance
Hard-drawnCopper
Equiv. Area
StandardLength
Reference
(mm2) Al Al AlSt St St (kg/km)
410410420430430480480
480(Cardinal)510520580590610680690750810860950
1,160
26/4.554/3.130/4.254/3.226/4.630/4.545/3.754/3.3826/5.054/3.572/3.230/5.054/3.854/4.072/3.554/4.284/3.554/4.584/3.884/4.2
7/3.57/3.1
19/2.57/3.27/3.6
19/2.77/2.477/3.387/3.97/3.5
19/3.219/3.0
7/3.819/2.437/2.519/2.5
7/3.519/2.7
7/3.87/4.2
13,89012,27017,38012,98014,61020,16011,80015,30017,21015,60026,44024,30018,15020,31032,06022,22019,90025,71023,10027,830
413.4407.6415.5434.3432.1477483.84484.53510.6519.5579.0589.2612.4678.6692.7748.1808.2858.6952.6
1,163.7
67.3552.8493.2759.2971.26
108.8033.5462.8183.6267.35
152.80134.3
79.3885.95
181.693.2767.35
108.879.3896.98
28.527.929.428.829.231.529.6130.4231.731.535.235.034.236.038.537.838.540.541.846.2
10.59.3
12.59.6
10.813.5
7.4110.1411.710.516.015.011.412.017.512.510.513.511.412.6
1,6731,5441,8851,6451,7562,1781,5991,8362,0711,9692,6052,6892,3202,5573,3522,8072,7693,2363,2643,986
0.07020.07120.06980.06640.06710.06090.059940.059900.05680.05590.04980.04930.04740.04280.04160.03880.03590.03390.03040.0249
260255261270272300304305321327360371385430440470
-540
--
1,0001,3001,4001,1001,350
8501,0001,0001,1001,000
7001,0001,000
800600
1,000-
600--
(Table 3)
9TAIHAN Overhead Electrical Aluminum Conductors
Aluminum Conductors, Steel Reinforced -Galvanized Steel WiresACSR
These sizes are specified in KS.
ApplicationThis standard covers aluminum stranded conductors steel reinforcedwhich could withstand high tensile load to be used mainly for overheadtransmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of galvanized steel and the outer layer orlayers of aluminum.
StandardsConforms to KS C 3113, JIS C 3110
Diameter Toleranceon Dia.
Min.Tensile
Strength
Min.Elongation
(kgf/mm2) (%) (times) (g/m2) (mins) (kg/km) (kgf)(mm2)
No. ofTwisting Min.
CoatingWeight
Unformity Winding WeightCalculatedCross
Sectional Area
Tensile Load
Galvanizing Test Reference
(mm) (mm)
1.82.02.252.32.42.52.62.72.93.03.13.23.53.63.73.83.94.04.24.5
0.040.040.050.050.050.050.050.050.060.060.060.060.070.070.070.070.070.080.080.09
140135135135135135135135135130130130130130130130130125125125
3.04.04.04.04.04.04.04.04.04.54.54.54.54.54.54.54.55.05.05.0
2020202020202020161616161616161616161616
200215230230230230230230245245245245260260260260260275275275
22222333444444444444
Nomarkedcrackshall
developon thecoatinglayer
of testpiece
2.5453.1423.9764.1554.5244.9095.3095.7266.6057.0697.5488.0429.621
10.1810.7511.3411.9512.5713.8515.90
19.8524.5131.0132.4135.2938.2941.4144.6651.5255.1458.8762.7375.0479.4083.8588.4593.2198.05
108.0124.0
356424537561611663719 773892919981
1,0501,2501,3201,4001,4701,5501,5701,7301,988
(Table 4)
Galvanized steel
Aluminum conductor
10 Overhead Electrical Aluminum Conductors TAIHAN
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
TACSR
SB : Smoth body
ApplicationThis standard covers aluminum-alloy stranded conductors steelreinforced which could withstand high tensile load to be used mainlyfor overhead transmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of galvanized steel and the outer layer or layers of aluminum-alloy.
StandardsConforms to TEC, JEC 3406
Thermal-resistant Aluminum - alloy Conductor Steel Reinforced
NominalCross
SectionalArea
No. and Dia. of Strands
(No./mm)
Min.TensileLoad
Calculated CrossSectional Area
(mm2)
Outside Dia.
(mm)
Weight ElectricResistance
StandardLength
Reference
(mm2) (kgf)Al-alloy Al-alloy St Al-alloy St (kg/km) (m)( /km, 20 )St160240330410480610680810
30/2.630/3.226/4.026/4.545/3.754/3.845/4.445/4.8
7/2.67/3.27/3.17/3.57/2.477/3.87/2.97/3.2
6,97010,21010,95013,91011,26018,35015,59018,450
159.3241.3326.8413.4483.8612.4684.5814.5
37.1656.2952.8467.3533.5479.3846.2456.29
18.222.425.328.529.6134.235.138.4
7.89.69.3
10.57.41
11.48.79.6
732.81,1101,3201,6731,5992,3202,2602,700
0.1850.1220.09040.07140.06100.04810.04310.0363
2,0002,0001,6001,3002,0001,6001,4001,200
(Table 5)
Smooth Body ACSR(Taihan Standard)Nominal
CrossSectional
Area
Construction OutsideDia.
Min.Tensile
StrengthWeight
(kg/km)
ElectricResistance
Hard-drawnCopper
Equiv. Area
StandardLength
Reference
(No./shape) (No./mm)(mm2) (mm) (kgf/mm2) (mm2) (m)( /km, 20 )
Al
Al St Total
St
121925325895
120
6/SB6/SB6/SB6/SB6/SB6/SB6/SB
1/1.61/2.01/2.31/2.61/3.51/3.51/4.2
4.45.56.37.29.7
12.013.6
460698907
1,1401,9802,5103,300
33.0452.3368.8988.09
159.7261.7330.5
15.6924.5132.4141.4175.0475.04
108.0
48.7376.84
101.3129.5234.7336.7438.5
2.401.521.150.9010.4970.3030.240
3.2mm
4.0mm
145.0mm
286080
-900900900600300300
(Table 6)
Anti-corrosion ACSR : ACSR-LZ, ACSR-MZ, ACSR-HZ(Taihan Standard)Nominal
CrossSectional
Area
No. and Dia. of Strands
(No./mm)
Max.TensileLoad
Calculated CrossSectional Area
(mm2)
Outside Dia.(mm)
Weight
(kg/km)
ElectricResistance
StandardLength
Reference
Al St Al St Al St Light Medium Heavy ( /km, 20 ) (m)(mm2) (kgf)
120160200240330410520610
30/2.330/2.630/2.930/3.226/4.026/4.554/3.554/3.8
7/2.37/2.67/2.97/3.27/3.17/3.57/3.57/3.8
5,5506,9008,620
10,21010,93013,89015,60018,150
124.7159.3198.2241.3326.8413.4519.5612.4
29.0937.1646.2456.2952.8467.3567.3579.38
16.118.220.322.425.328.531.534.2
6.97.88.79.69.3
10.510.511.4
580.9742.0923.1
1,1241,3331,6901,9862,340
593.6758.2943.4
1,1491,3671,7332,0592,426
616.7787.7980.0
1,1931,4301,8132,1322,513
0.2330.1820.1470.1200.08880.07020.05590.0474
1,2002,0002,0001,8001,3001,0001,4001,200
(Table 7)
Galvanized steel
Aluminum conductor
11TAIHAN Overhead Electrical Aluminum Conductors
Conductor shall be high strength Al-clad steel core wire.
ApplicationThis standard covers aluminum stranded conductors aluminum-cladsteel reinforced which could withstand high tensile load to be usedmainly for overhead transmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of aluminum-clad steel and the outer layeror layers of aluminum.
StandardsConforms to KEPCO specification
NominalCross
SectionalArea
No. and Dia.of Strands
(No/mm)
TensileLoad
(above)Calculated CrossSectional Area
(mm2)
Outside Dia.
(mm)
Al Aw Al Aw Al Aw
Weight ElectricResistance
Hard-drawnCopper
Equiv. Area
StandardLength
Reference
(mm2) (kgf) (kg/km) (mm2) (m)( /km, 20 )
3258659597
120160240330410
480(Cardinal)
480520
6/2.66/3.5
12/2.66/4.5
12/3.212/3.530/2.630/3.226/4.026/4.554/3.3845/3.754/3.5
1/2.61/3.57/2.61/4.57/3.27/3.57/2.67/3.27/3.17/3.57/3.387/2.477/3.5
1,1401,9805,4153,180
10,6009,5906,990
10,21010,93013,89015,30011,80015,600
31.8557.7363.7195.4096.50
115.45159.30241.30326.80413.40484.53483.84519.50
5.319.62
37.1715.9056.2967.3537.1656.2952.8467.3562.8133.5467.35
7.810.513.013.516.017.518.222.425.328.530.4229.6131.5
2.63.57.84.59.6
10.57.89.69.3
10.510.14
7.4110.5
120.6299.7401.0362.0608.0737.0676.4
1,0241,2391,5781,7601,5441,848
0.852000.471000.380000.285000.295000.210000.169000.111000.084200.066500.057400.058600.05360
213848636286
108163216273318310340
1,0001,0001,0001,0001,0001,0001,0001,0001,0001,0001,0001,0001,000
(Table 8)
Conductor shall be high strength Al-clad steel core wire.
Nominal CrossSectional Area ACSR/GW
(kg/km)ACSR/AW(kg/km)
GW/AW(Ratio)
ACSR/GW( /km, 20 )
ACSR/AW( /km, 20 )
GW/AW(Ratio)
Weight Conductor Resistance
(mm2)
3258659597
120160240330410
480(Cardinal)
480520
128.6233.1465.0385.1708.9845.9732.8
1,1001,3201,6731,8361,5991,969
120.6219.7401.0362.0608.0737.0676.4
1,0241,2391,5781,7601,5441,848
1.0661.0611.1601.0641.1161.1481.0831.0841.0651.0601.0431.0361.065
0.899000.497000.456500.301000.301000.250000.182000.120000.08800.070200.059900.059940.05590
0.852000.471000.380000.285000.295000.210000.169000.111000.084200.066500.057400.058600.05360
1.051.051.201.051.021.191.071.081.051.051.041.021.04
(Table 9)
Aluminum-clad steel
Aluminum conductor
Comparison of ACSR with ACSR/AW
Aluminum Conductors, Aluminum-clad Steel ReinforcedACSR/AW
12 Overhead Electrical Aluminum Conductors TAIHAN
Conductor shall be high strength Al-clad steel core wire.
Diameter Toleranceon Dia.
TensileStrength(above)
Elongation(above)
Conductivity(above)
No. ofTwisting
AIThickness
(above)
WindingCalculated
CrossSectional Area
ElectricResistance
Weight
Reference
(mm) (mm) (kgf/mm2) (%) (%) (times) (mm) ( /km, 20 )(mm2) (kg/km)
2.472.63.13.23.23.383.54.5
0.050.050.060.060.060.070.070.09
135135130130160144130125
1.51.51.51.51.51.51.51.5
20.320.320.320.314.020.320.320.3
2020161620161616
0.100.130.150.150.070.150.150.20
No markedcrack shall
developon thecoatinglayer of
test piece
4.791 5.3097.5488.0428.0428.9739.621
15.90
17.7216.011.310.615.3
9.478.835.34
31.5834.9949.7453.0057.4259.1363.40
104.81
(Table 10)
Aluminum
Steel
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
Aluminum-clad Steel Wires(Reference Spec. ASTM B-415)
13TAIHAN Overhead Electrical Aluminum Conductors
Stranded Aluminum-clad Steel ConductorAWSApplicationThis standard covers stranded aluminum-clad steel conductors to beused mainly for overhead ground wire.
ConstructionStranded aluminum-clad conductor
StandardsConforms to KEPCO specification
NominalCross
SectionalArea
No. andDia.
of Strands
Conductivity(above)
TensileLoad
(above)
(mm2) (mm) (kg/km) ( /km, 20 ) (m)
CalculatedCross
Sectional Area
Outside Dia. Weight ElectricResistance
StandardLength
Reference
(mm2) (No./mm) (%) (kgf)
5570
100125200200
7/3.27/3.5
19/2.619/2.919/3.719/3.7
20.320.34020.34030
6,8708,1906,360
15,48012,87016,547
56.2967.35
100.9125.5204.3204.3
9.610.513.014.518.518.5
371.2444.2474.5842961
1,162
1.5301.2700.4330.6820.2140.285
2,0002,0002,0002,0002,0002,000
(Table 11)
Aluminum-clad Steel Wires
Diameter Toleranceon Dia.
TensileStrength(above)
Elongation(above)
Conductivity(above)
No. ofTwisting(above)
AlThickness
(above)
WindingCalculated
CrossSectional Area
(mm2)
Weight
(kg/km)
ElectricResistance
( /km, 20 )
Reference
(mm) (mm) (kgf/mm2) (%) (%) (times) (mm)
2.62.93.23.53.73.7
0.050.0380.060.070.070.07
70137130130
7090
1.51.51.51.51.51.5
4020.320.320.34030
202016161616
0.330.150.150.150.470.30
No markedcrack shalldevelop onthe coating
layer oftest piece
5.3096.6058.0429.621
10.75210.752
372205
1,0501,250
753968
24.6343.5053.0063.4049.8960.32
(Table 12)
Aluminum
Steel
Aluminum
Steel
14 Overhead Electrical Aluminum Conductors TAIHAN
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
STACIR Super Thermal-resistant Aluminum-alloy Conductors, lnvar-reinforced
ApplicationThis standard covers super thermal-resistant aluminum-alloy strandedconductors galvanized invar reinforced to be used mainly for overheadtransmission lines.
ConstructionThe center wires are of galvanized invar and the outer layers of superthermal-resistant aluminum-alloy.
StandardsConforms to KEPCO specification
NominalCross
SectionalArea
No. andDia. ofStrands
(No./mm)
TensileLoad
(above)Calculated
Cross SectionalArea
(mm2)
Outside Dia.
(mm)
Weight ElectricResistance
Up toTransition
PointTemper-
ature
AboveTransition
PointTemper-
ature
Up toTransition
PointTemper-
ature
AboveTransition
PointTemper-
ature
Modulus ofElasticity(kg/mm2)
Coefficient ofLinear Expansion
(X10-6/ )
StandardLength
Reference
(mm2) (kgf) (kg/km) (m)( /km,20 )
ST-AlAlloy
lnvar ST-AlAlloy
lnvar ST-AlAlloy
lnvar
240330410480
ContinuousEmergencyShort Circuit
90120180
150180260
210240280
30/3.226/4.026/4.545/3.70
7/3.27/3.17/3.57/2.47
9,17010,00012,72010,500
241.3326.8413.4483.84
56.2952.8467.3533.54
22.425.328.529.61
9.69.3
10.57.41
1,1221,3301,6871,611
0.12200.09040.07140.0607
8,2307,7207,7306,960
16,50016,50016,50016,500
15.317.017.019.8
3.63.63.63.6
2,0002,0002,0002,000
(Table 13)
Maximum Operating Temperature( ) ACSR TACSR STACIR
Maximum Operating Temperature
ContinuousEmergency
1.001.00
1.55~1.621.33~1.36
1.94~2.061.60~1.67
Current Capacity lncreasing Ratio ACSR TACSR STACIR
Current Capacity Increasing Ratio
Galvanized invar
Super thermal-resistant aluminum-alloy conductor
15TAIHAN Overhead Electrical Aluminum Conductors
Super Thermal-resistant Aluminum-alloy Conductors, Aluminum-clad Invar-reinforcedSTACIR/AW
HSTACIR/AW
ApplicationThis standard covers super thermal-resistant aluminum-alloy strandedconductors aluminum-clad invar reinforced to be used mainly foroverhead transmission lines.
ConstructionThe center wires are of aluminum-clad invar and the outer layers ofsuper thermal-resistant aluminum-alloy.
StandardsConforms to KEPCO specification
Aluminum-clad invar
Super thermal-resistant aluminum-alloy conductor
NominalCross
SectionalArea
No. and Dia. of Strands
(mm)
TensileLoad
(above)Calculated
Cross SectionalArea
(mm2)
Outside Dia.
(mm)
Weight ElectricResistance
Up toTransition
PointTemper-
ature
AboveTransition
PointTemper-
ature
Up toTransition
PointTemper-
ature
AboveTransition
PointTemper-ature to230
Above230
Modulus of Elasticity(kg/mm2)
Coefficient of Linear Expansion(X10-6/ )
StandardLength
Reference
(mm2) (kgf) (kg/km) (m)( /km,20 )
ST-AlAlloy
Al-cladlnvar
ST-AlAlloy
ST-AlAlloy
Al-cladlnvar
Al-cladlnvar
240330410480
30/3.226/4.026/4.545/3.70
7/3.27/3.17/3.57/2.47
9,17010,00012,72010,500
241.3326.8413.4483.84
56.2952.8467.3533.54
22.425.328.529.61
9.69.3
10.57.41
1,0701,2851,6251,580
0.11590.08690.06860.0600
8,0407,5807,5806,900
15,50015,50015,50015,500
16.017.517.520.0
3.73.73.73.7
10.810.810.810.8
2,0002,0002,0002,000
(Table 14)
High-strength Super Thermal-resistant Alluminum-alloy ConductorsAluminum-clad Invar Reinforced
ApplicationThis standard cover High-strength super thermal-resistant aluminum-alloy stranded conductors aluminum-clad invar reinforced to be usedmainly for overhead transmission lines.
ConstructionThe center wires are of aluminum-clad high strength invar and theouter layers of super thermal-resistant aluminum-alloy.
StandardsConforms to KEPCO specification
Aluminum-clad high strength inver
Super thermal-resistant aluminum-alloy conductor
NominalCross
SectionalArea
No. and Dia. of Strands
(mm)
TensileLoad
(above)Calculated CrossSectional Area
(mm2)
Outside Dia.
(mm)
Weight ElectricResistance
Up toTransition
PointTemper-
ature
AboveTransition
PointTemper-
ature
Up toTransition
PointTemper-
ature
AboveTransition
PointTemper-ature to230
Above230
Modulus of Elasticity(kg/mm2)
Coefficient of Linear Expansion(X10-6/ )
StandardLength
Reference
(mm2) (kgf) (kg/km) (m)( /km,20 )
ST-AlAlloy
Al-cladHigh-
Strengthlnvar
ST-AlAlloy
ST-AlAlloy
Al-cladHigh-
Strengthlnvar
Al-cladHigh-
Strengthlnvar
240330410480
30/3.226/4.026/4.545/3.7
7/3.27/3.17/3.57/2.47
9,70010,50013,30011,000
241.3326.8413.5483.8
56.2952.8467.3533.54
22.425.328.529.61
9.69.3
10.57.41
1,0701,2851,6251,580
0.11590.08690.06860.0600
8,0417,5817,5896,896
15,50015,50015,50015,500
15.9617.5117.4820.19
3.73.73.73.7
10.810.810.810.8
2,0002,0002,0002,000
(Table 15)
16 Overhead Electrical Aluminum Conductors TAIHAN
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
HTACSR/AW
TACSR/AW Thermal-resistant Aluminum-alloy Conductors, Aluminum-clad Steel-reinforced
ApplicationThis standard covers thermal-resistant aluminum-alloy strandedconductors aluminum-clad steel reinforced to be used mainly foroverhead transmission lines.
ConstructionThe center wires are of aluminum-clad steel and the outer layers ofthermal-resistant aluminum-alloy.
StandardsConforms to KEPCO specification
Aluminum-clad steel
Thermal-resistant aluminum-alloy conductor
NominalCross
SectionalArea
No. and Dia. of Strands
(No./mm)
TensileLoad
(above)Calculated CrossSectional Area
(mm2)
Outside Dia.
(mm)
Weight ElectricResistance
StandardLength
Reference
(mm2) (kgf)Al-alloy Al-alloy AW Al-alloy AW (kg/km) (m)( /km, 20 )AW480(Rail) 45/3.7 7/2.47 11,260 483.84 33.54 29.61 7.41 1,561 0.0596 2,000
(Table 16)
High-Strength, Thermal-resistant Aluminum-alloy Conductors,Aluminum-clad Steel Reinforced
ApplicationThis standard covers high-strength, thermal-resistant aluminum-alloystranded conductors aluminum-clad steel reinforced which couldwithstand extra high tensile load to be used mainly for overheadtransmission lines.
ConstructionThe center wires are of aluminum-clad steel and the outer layers ofhigh-strength, themal-resistant aluminum-alloy.
StandardsConforms to KEPCO specification
Aluminum-clad steel
High-strength, thermal-resistant aluminum-alloy conductor
NominalCross
SectionalArea
No. and Dia. of Strands
(No./mm)
TensileLoad
(above)Calculated CrossSectional Area
(mm2)
Outside Dia.
(mm)
Weight ElectricResistance
StandardLength
Reference
(mm2) (kgf)HT-Al Alloy HT-Al Alloy AW HT-Al Alloy AW (kg/km) (m)( /km, 20 )AW480
(Cardinal) 54/3.38 7/3.38 18,880 484.53 62.81 30.42 10.14 1,756 0.0633 2,000
(Table 17)
17TAIHAN Overhead Electrical Aluminum Conductors
Hard-drawn Aluminum Conductor Weather-resistantInsulation WiresHAL-OC
ApplicationThis standard covers HAL-OC(for use in 6,600~22,900 volts circuits) tobe used weather-resistant insulation wire for the distribution ofelectrical energy under the normal conditions of overhead line service.
ConstructionSolid or stranded hard-drawn aluminum conductor and cross-linkedpolyethylene insulation
StandardsConforms to KS C 3139, ES 121-250, 121-255
NominalCross
SectionalArea
lnsulationThickness
Conductor OutsideDia.No. and
Dia. of Strands
OutsideDia.
Max.Electric
Resistance
Min.lnsulationResistance
TestVoltage
TensileLoad
Weight StandardLength
(mm2) (mm) (mm) (mm) ( /km, 20 ) ( km, 20 ) (V/1mins) (kgf) (kg/km) (m)(No./mm)
150 19/3.2 16.0 2.5 21.0 0.193 1,000 12,000 2,270 600 300
(Table 18)Within 6.6kV
NominalCross
SectionalArea
lnsulationThickness
Conductor OutsideDia.No. and
Dia. of Strands
OutsideDia.
Max.Electric
Resistance
Min.lnsulationResistance
TestVoltage
TensileLoad
Weight StandardLength
(mm2) (mm) (mm) (mm) ( /km, 20 ) ( km, 20 ) (V/1mins) (kgf) (kg/km) (m)(No./mm)
150 19/3.2 16.0 4.0 24.0 0.193 1,500 25,000 2,270 650 600
(Table 19)Within 22.9kV
Aluminum conductor
XLPE insulation
18 Overhead Electrical Aluminum Conductors TAIHAN
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
ACSR-OC Aluminum, Steel-reinforced(ACSR) ConductorWeather-resistant Insulation Wire
ApplicationThis standard covers ACSR-OC(for use in 6,600~22,900 volts circuits)to be used weather-resistant insulation wire for the distribution ofelectrical energy under the normal conditions of overhead line service.
NominalCross
SectionalArea
lnsulationThickness
OutsideDia.
Max.Electric
Resistance
Min.lnsulationResistance
TestVoltage
TensileLoad
Weight StandardLength
Conductor
No. and Dia. of Strands(No./mm)
OutsideDia.
(mm2) (mm) (mm) (mm) (V/1mins) (kgf) (kg/km) (m)( /km, 20 ) ( km, 20 )Al St325895
6/SB6/SB6/SB
1/2.61/3.51/3.5
7.29.7
12.0
2.02.52.5
11.214.717.0
0.9280.5120.313
1,5001,5001,000
12,00012,00012,000
1,0901,9002,360
185325455
900600300
(Table 20)
ConstructionAluminum, steel-reinforced conductor and cross-linked polyethyleneinsulation
StandardsConforms to KS C 3138, ES 121-200-202, 121-230-275
Within 6.6kV
NominalCross
SectionalArea
lnsulationThickness
OutsideDia.
Max.Electric
Resistance
Min.lnsulationResistance
TestVoltage
TensileLoad
Weight StandardLength
Conductor
No. and Dia. of Strands(No./mm)
OutsideDia.
(mm2) (mm) (mm) (mm) (V/1mins) (kgf) (kg/km) (m)( /km, 20 ) ( km, 20 )Al St325895
160
6/SB6/SB6/SB
18/SB
1/2.61/3.51/3.51/3.2
7.29.7
12.015.4
3.03.03.54.0
13.215.719.023.4
0.9280.5120.3130.186
2,0001,5001,5001,500
25,00025,00025,00025,000
1,0901,9002,3603,080
215340540740
900600600600
(Table 21)Within 22.9kV
Galvanized steel
XLPE insulation
Aluminum conductor
SB : Smooth body
SB : Smooth body
19TAIHAN Overhead Electrical Aluminum Conductors
Aluminum, Al-clad, Steel-reinforced(ACSR/AW) Conductor Weather-resistant Insulation WiresACSR/AW-OC
ApplicationThis standard covers ACSR/AW-OC(for use in 6,600~22,900 voltscircuits) to be used weather-resistant insulation wire for the distributionof electrical energy under the normal conditions of overhead line service.
ConstructionAluminum, Al-clad steel-reinforced conductor and cross-linkedpolyethylene insulation
StandardsConforms to KEPCO specification
XLPE insulation Aluminum
Al-clad
NominalCross
SectionalArea
lnsulationThickness
OutsideDia.
ElectricResistance
Min.lnsulationResistance
TestVoltage
TensileLoad
Weight StandardLength
Conductor
No. and Dia. of Strands(No./mm)
OutsideDia.
(mm2) (mm) (mm) (mm) (V/1mins) (kgf) (kg/km) (m)( /km, 20 ) ( km, 20 )Al AW325895
6/SB6/SB6/SB
1/2.61/3.51/3.5
7.29.7
12.0
2.02.52.5
11.214.717.0
0.8770.4840.302
1,5001,5001,000
12,00012,00012,000
1,0901,9002,360
180315445
900600300
(Table 22)Within 6.6kV
SB : Smooth body
NominalCross
SectionalArea
lnsulationThickness
OutsideDia.
ElectricResistance
Min.lnsulationResistance
TestVoltage
TensileLoad
Weight StandardLength
Conductor
No. and Dia. of Strands(No./mm)
OutsideDia.
(mm2) (mm) (mm) (mm) (V/1mins) (kgf) (kg/km) (m)( /km, 20 ) ( km, 20 )Al AW325895
160240
6/SB6/SB6/SB
18/SB18/SB
1/2.61/3.51/3.51/3.21/4.0
7.29.7
12.015.418.9
3.03.03.54.04.0
13.215.719.023.427.0
0.8770.4840.3020.1830.123
2,0001,5001,5001,5001,500
25,00025,00025,00025,00025,000
1,0901,9002,3603,0804,500
210330530730
1,040
900600600600600
(Table 23)Within 22.9kV
SB : Smooth body
20 Overhead Electrical Aluminum Conductors TAIHAN
American Society for Testing and Materials
American National Standards Institute
ASTM
ANSI
21TAIHAN Overhead Electrical Aluminum Conductors
Hard-drawn Aluminum Wires for Electric PurposesHAL
ApplicationThis standard covers hard-drawn circular aluminum wires for electricpurposes to be used mainly as component wires of hard-drawnaluminum stranded cables and aluminum cables steel reinforced.
ConstructionSingle aluminum conductor
StandardsConforms to ASTM B 230-97
(Table 24)Tensile RequirementsDiameter
ksi Mpa ksi MpaAverage for a Lot
IndividualTests
Average for a Lot
IndividualTests( %, or in)
Toleranceon Dia.
Average for a Lot lndividual Tests
Min. Tensile Strength Min. Elongation in10 in or 250mm
(%)
Min. VolumeConductivity
(% IACS, 20 (68 ))
in mm
0.2600 to 0.21010.2100 to 0.18010.1800 to 0.15010.1500 to 0.14010.1400 to 0.12010.1200 to 0.11010.1101 to 0.10010.1000 to 0.09010.0900 to 0.08010.0800 to 0.07010.0700 to 0.06010.0600 to 0.05010.0500 to 0.0105
6.604 to 5.3375.334 to 4.5754.572 to 3.8133.810 to 3.5593.556 to 3.0513.048 to 2.7972.794 to 2.5432.540 to 2.2892.286 to 2.0352.032 to 1.7811.778 to 1.5271.524 to 1.2731.270 to 0.267
1%1%1%1%1%1%1%
0.0010 in0.0010 in0.0010 in0.0010 in0.0010 in0.0010 in
23.524.024.024.525.025.526.027.027.528.028.529.025.0
162165165169172176179186190193197200172
22.523.023.023.523.524.024.525.526.026.527.027.023.0
155159159162162165169176179183186186159
2.32.12.01.91.81.71.61.61.61.61.51.4-
2.22.01.91.81.71.61.51.51.51.41.31.2-
61.261.261.261.261.261.261.261.261.261.261.261.261.2
61.061.061.061.061.061.061.061.061.061.061.061.061.0
(Table 25)Equivalent Resistivity Values at 20 C(68 F)
MaterialVolume
Conductivity(% IACS)
Resistivity ConstantsWeightVolume
cmil/ft mm2/m in cm -lb/mile2 -g/m2
CopperAluminumAluminum
10061.061.2
10.37117.00216.946
0.0172410.0282650.028172
0.678791.11281.1091
1.72412.82652.8172
875.20436.23434.81
0.153280.0763990.076149
22 Overhead Electrical Aluminum Conductors TAIHAN
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
Zinc-coated(galvanized) Steel Core Wire (ASTM B 498-93)
(Table 26)
(Table 27)
Tensile Requirements and Permissible Variations in Diameter
Mpa ksi Mpa (%) Plus
in mm
Minus Plus Minusksi
Nominal Dia. Min. Stressat 1% Extension
Min. UltimateTensile Strength
Min.Elogationin 10 in
or 250mm
Permissible Variation
Class A Coating
in mm
0.0500 to 0.08990.0900 to 0.11990.1200 to 0.13990.1400 to 0.1900
1.270 to 2.2832.286 to 3.0453.048 to 3.5533.556 to 4.822
190185180170
1,3101,2801,2401,170
210205205200
1,4501,4101,4101,380
3.03.54.04.0
0.00150.0020.0030.004
0.0010.0020.0020.003
0.0380.0510.0760.102
0.0250.0510.0510.076
Class B Coating
0.0500 to 0.08990.0900 to 0.11990.1200 to 0.13990.1400 to 0.1900
1.270 to 2.2832.286 to 3.0453.048 to 3.5533.556 to 4.822
180175170160
1,2401,2101,1701,100
200195195185
1,3801,3401,3401,280
3.03.03.04.0
0.00150.0020.0030.004
0.0010.0020.0020.003
0.0380.0510.0760.102
0.0250.0510.0510.076
Class C Coating
0.0500 to 0.08990.0900 to 0.11990.1200 to 0.13990.1400 to 0.1900
1.270 to 2.2832.286 to 3.0453.048 to 3.5533.556 to 4.822
170165160155
1,1701,1401,1001,070
190185185180
1,3101,2801,2801,240
3.03.03.04.0
0.00150.0020.0030.004
0.0010.0020.0020.003
0.0380.0510.0760.102
0.0250.0510.0510.076
Minimum Weight of Coating and Mandrel Size for Adherence Test
Nominal Dia. of Coated WireMin. Weight of Zinc-coating
oz/ft2 of Uncoated Wire Surface
Coatingin mm
CoatingClass A Class B Class C Class A Class B Class C
Ratio ofMandrelDia. to
Wire Dia.
Min. Weight of Zinc-coatingg/m2 of Uncoated Wire Surface
0.0500 to 0.05990.0600 to 0.07490.0750 to 0.08990.0900 to 0.10390.1040 to 0.11990.1200 to 0.13990.1400 to 0.17990.1800 to 0.1900
1.270 to 1.5211.524 to 1.9021.905 to 2.2832.286 to 2.6392.642 to 3.0453.048 to 3.5533.556 to 4.5694.572 to 4.822
0.600.650.700.750.800.850.901.00
1.201.301.401.501.601.701.802.00
1.801.952.102.252.402.552.703.00
183198214229244259274305
366396437458488518549610
549550610686732778824915
33344455
23TAIHAN Overhead Electrical Aluminum Conductors
Stranded Hard-drawn Aluminum ConductorAAC
Notes : Class AA - For bare conductors usually used in overhead lines.Class A - For conductors to be covered with weather-resistant materials.
ApplicationThis standard covers stranded hard-drawn aluminum conductors to beused mainly for overhead distribution wire, overhead feeders andbuses.
ConstructionStranded hard-drawn aluminum conductor
StandardsConforms to ASTM B 231-95
CodeWord
ConductorDia.
(in)
Weight
(lb/1000ft)
RatedStrength
(lb)
CalculatedResistance
at 20(68 )
( /1000ft)
Ampacity
(amps)
AWGor
CMILS
sq in Class No. andDia. ofStrands
(in)
Conductor Size Stranding
PeachbellRoseLilyIrisPansyPoppyAsterPhloxOxlipSneezewortValerianDaisyLaurelPeonyTulipDaffodilCannaGoldentuftCosmosSyringaZinniaHyacinthDahliaMistletoeMeadowsweetOrchidHeucheraVerbenaFlagViolet
64321
1/02/03/04/0
250,000250,000266,800266,800300,000336,400350,000397,500450,000477,000477,000500,000500,000556,500556,500600,000636,000650,000700,000700,000715,500
0.02060.03280.04130.05210.06570.08290.10450.13180.16620.19640.19640.20950.20950.23560.26420.27490.31220.35340.37460.37460.39270.39270.43710.43710.47170.49950.51050.54980.54980.5620
AAA
A&AAA&AAA&AAA&AAA&AAA&AA
AAA
AAAAAA
A&AAAAAAA
AAAA
A&AAA&AA
AAAAAAA
AA
7 0.06127 0.07727 0.08677 0.09747 0.10937 0.12287 0.13797 0.15487 0.17397 0.1890
19 0.11477 0.1953
19 0.118519 0.125719 0.133119 0.135719 0.144719 0.153919 0.158437 0.113519 0.162237 0.116219 0.171137 0.122637 0.127337 0.131137 0.132637 0.137561 0.107137 0.1391
0.1840.2320.2600.2920.3280.3680.4140.4640.5220.5670.57405860.5930.6290.6660.6790.7240.7700.7920.7950.8110.8130.8560.8580.8910.9180.9280.9630.9640.974
24.639.149.462.278.498.9
124.8157.2198.4234.4234.7250.2250.1281.4315.5327.9372.9421.8446.8446.8468.5468.3521.4521.3562.0596.0609.8655.7655.8671.0
563881
1,0231,3501,6401,9902,5103,0403,8304,5204,5104,8304,9705,4806,1506,3907,1107,8908,3608,6908,7609,1109,7509,940
10,70011,40011,60012,50012,90012,800
0.66090.41550.32960.26130.20720.16420.13030.10330.081960.06940.06940.065000.065000.05780.05150.04960.043630.03860.036360.036360.3470.3470.031160.031160.02890.027270.02670.02480.02480.02424
103138159185214247286330382414416442444458513521570612639640669670703704721765782804805823
(Table 28)
24 Overhead Electrical Aluminum Conductors TAIHAN
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
(Table 28)
Notes : Class AA - For bare conductors usually used in overhead lines.Class A - For conductors to be covered with weather-resistant materials.
CodeWord
ConductorDia.
(in)
Weight
(lb/1000ft)
RatedStrength
(lb)
CalculatedResistance
at 20(68 )
( /1000ft)
Ampacity
(amps)
AWGor
CMILS
sq in Class No. andDia. ofWires(in)
Conductor Size Stranding
NasturtiumPetuniaCattailArbutusLilacAnemoneCrocusCockscombSnapdragonMagnoliaGoldenrodHawkweedCamelliaBluebellLarkspurMarigoldHawthornNarcissusColumbineCarnationGladiolusCoreopsisDogwoodJessamineCowslipSagebrushLupineBitterrootTrilliumBluebonnet
715,500750,000750,000795,000795,000874,500874,500900,000900,000954,000954,000
1,000,0001,000,0001,033,5001,033,5001,113,0001,192,5001,272,0001,351,0001,431,0001,510,5001,590,0001,590,0001,750,0002,000,0002,250,0002,500,0002,750,0003,000,0003,500,000
0.56200.58900.58900.62440.62440.68680.68680.70690.70690.74930.74930.78540.78540.81170.81170.87410.93660.9990
1.0621.1241.1861.2491.2491.3741.5701.7661.9622.1582.3502.749
AAAA
AAA
AAA
AAA
AAA
AAA
AAA
A&AAA&AAA&AAA&AAA&AAA&AA
AAA
AAAAAAAA
61 0.108337 0.142461 0.110937 0.146661 0.114237 0.153861 0.119837 0.156061 0.121537 0.160661 0.125137 0.164461 0.128037 0.167161 0.130261 0.135161 0.139861 0.144461 0.148861 0.153261 0.157461 0.161491 0.132261 0.169491 0.148291 0.157291 0.165791 0.1738
127 0.1537127 0.1660
0.9750.9970.9981.0261.0281.0771.0781.0921.0941.1241.1261.1511.1521.1701.1721.2161.2581.3001.3391.3791.4171.4531.4541.5251.6301.7291.8231.9121.9962.158
671.0703.2703.2745.3745.7821.0821.0844.0844.0894.5894.8937.3936.8968.4969.2
1,0441,1171,1921,2661,3421,4171,4891,4931,6411,8732,1282,3652,6022,8403,345
13,10013,10013,50013,90014,30014,83015,76016,40015,90016,40016,90017,20017,70017,70018,30019,70021,10022,00023,40024,30025,60027,00028,10029,70034,20037,70041,90046,10050,30058,700
0.024240.02310.02310.021810.021810.019830.019830.01930.01930.018180.018180.01740.01730.016780.016780.015580.014540.013630.012830.012120.011480.010910.010910.009910.008680.007790.007010.006370.005840.00505
824842848874878932932938943982982
1,0031,0051,0311,0321,0791,1251,1701,2121,2541,2951,3341,3341,4991,5951,6861,7721,9532,2832,689
25TAIHAN Overhead Electrical Aluminum Conductors
Aluminum Conductors, Steel ReinforcedACSR
ApplicationThis standard covers aluminum stranded conductors steel reinforcedwhich could withstand high tensile load to be used mainly for overheadtransmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of galvanized steel and the outer layer orlayers of aluminum.
StandardsConforms to ASTM B 232-97
CodeWord
Outside Dia.
(in)
Weight
(lb/1000ft)
UltimateStrength
(lb)
Resistanceat 20
( /1000ft)
Ampacity
(Amps)
AWGor
CMILS
Cross SectionalArea (sq in)
Al Total Al St Total Al StComplete
CableSteelCore
Stranding
Conductor Size
TurkeyThrushSwanSwanateSwallowSparrowSparateRobinRavenQuailPigeonPenguinWaxwingPartridgeOstrichMerlinLinnetOrioleChickadeeBrantIbisLarkPelicanFlickerHawkHenOspreyParakeetDoveEaglePeacockSquabWood DuckTealRook
65443221
1/02/03/04/0
266,800266,800300,000336,400336,400336,400397,500397,500397,500397,500477,000477,000477,000477,000556,500556,500556,500556,500605,000605,000605,000605,000636,000
0.02060.02600.03280.03280.04130.05210.05210.06570.08290.10450.13180.16620.20950.20950.23560.26420.26420.26420.31220.31220.31220.31220.37460.37460.37460.37460.43710.43710.43710.43710.47520.47520.47520.47520.4955
0.02400.03030.03830.04110.04820.06080.06530.07670.09670.12190.15380.19390.22110.24360.27400.27890.30720.32590.32950.35250.36300.38500.39540.42320.43560.46200.46140.49380.50830.53910.53680.55260.58610.58350.5643
6 0.06616 0.07436 0.08347 0.07726 0.09376 0.10527 0.09746 0.11816 0.13276 0.14896 0.16726 0.1878
18 0.121726 0.101326 0.107418 0.136726 0.113730 0.105918 0.148624 0.128726 0.123630 0.115118 0.162824 0.141026 0.135430 0.126118 0.175824 0.152326 0.146330 0.136224 0.158826 0.152530 0.142030 0.142024 0.1628
1 0.06611 0.07431 0.08341 0.10291 0.09371 0.10521 0.12991 0.11811 0.13271 0.14891 0.16721 0.18781 0.12177 0.07887 0.08351 0.13677 0.08847 0.10591 0.14867 0.08587 0.09617 0.11511 0.16287 0.09407 0.10537 0.12611 0.17587 0.10157 0.11387 0.13627 0.10597 0.11867 0.1420
19 0.08527 0.1085
0.1980.2230.2500.2570.2810.3160.3250.3540.3980.4470.5020.5630.6090.6420.6800.6840.7200.7410.7430.7720.7830.8060.8140.8460.8580.8830.8790.9140.9270.9530.9530.9660.9940.9940.997
0.06610.07430.08340.10290.09370.10520.12990.11810.13270.14890.16720.18780.12170.23640.25050.13670.26520.31770.14860.25740.28830.34530.16280.28200.31590.37830.17580.30450.34140.40860.31770.35580.42600.25560.3255
36.145.557.467.072.491.3
106.7115.2145.2183.1230.8291.1290367413365463527432512547623518615657747604717766872780833948940819
24.530.939.039.049.262.062.078.298.6
124.3156.8197.7250.5251.7283.0315.8317.3318.1373.2375375.0375.9447.8450.0450.0451.1522.4525.0525.0526.3570.7570.7572572.1600.0
11.614.618.428.023.329.344.737.046.658.874.093.439.2
115.6129.849.5
145.8209
58.5137171.9246.9
70.2164.5206.8296.3
81.9191.8241.1345.7208.8261.9376367.6219.2
1,1901,4901,8602,3602,2502,8503,6403,5504,3805,3006,6208,3506,900
11,30012,700
8,62014,10017,300
9,90014,60016,30020,30011,80017,20019,50023,80013,70019,80022,60027,80021,60024,30028,90030,00022,600
0.6577-
0.41340.4134
-0.26010.26010.20620.16340.12970.10280.81550.065000.065320.058090.051550.051810.051930.043630.043840.043840.043950.036360.036540.036540.036620.031160.031320.031320.031390.028800.028200.02890.02890.02740
104-
139139
-183184210240275316360448457492518528534575578586593644654658665708718725732757762769772782
(Table 29)
Galvanized steel
Aluminum conductor
26 Overhead Electrical Aluminum Conductors TAIHAN
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
CodeWord
Outside Dia.
(in)
Weight
(lb/1000ft)
UltimateStrength
(lb)
Resistanceat 20
( /1000ft)
Ampacity
(Amps)
AWGor
CMILS
Cross SectionalArea (sq in)
Al Total Al St Total Al StComplete
CableSteelCore
Stranding
Conductor Size
GrosbeakSwiftScoterKingbirdEgretFlamingoGannetCrowStarlingRedwingStiltDrakeMallardTernCondorCootCuckooCraneCanaryRuddyRailCardinalCatbirdOrtolanCurlewTanagerBluejayFinchBuntingGrackleBitternPheasantDipperMartinBobolinkPloverNuthatchParrotLapwingFalconChukarBluebirdKiwiThrasher
636,000636,000636,000636,000636,000666,600666,600715,500715,500715,500715,500795,000795,000795,000795,000795,000795,000874,500900,000900,000954,000954,000954,000
1,033,5001,033,5001,033,5001,113,0001,113,0001,192,5001,192,5001,272,0001,272,0001,351,5001,351,5001,431,0001,431,0001,510,5001,510,5001,590,0001,590,0001,780,0002,156,0002,167,0002,312,000
0.49950.49750.49950.49950.49950.52350.52350.56200.56200.56200.56280.62440.62440.62440.62440.62440.62440.68680.70690.70690.74930.74930.74930.81170.81170.81170.87410.87410.93670.93660.99900.99901.0621.06251.1241.1241.1861.1861.2491.2491.3981.6931.7021.816
0.58090.51340.61610.52920.61340.59140.60870.63480.65350.69010.63560.72610.76680.66760.70530.64170.70530.77590.79850.75550.80110.84640.77010.86780.91690.83420.93460.98491.0011.0551.0681.1261.1351.1961.2021.2661.2681.3371.3351.4071.5121.8281.7761.915
26 0.156436 0.132930 0.145618 0.188030 0.145624 0.166726 0.160154 0.115126 0.165930 0.154424 0.172726 0.174930 0.162845 0.132954 0.121336 0.148624 0.182054 0.127354 0.129145 0.141445 0.145654 0.132936 0.162845 0.151554 0.138336 0.169445 0.157354 0.143645 0.162854 0.148645 0.168154 0.153545 0.173354 0.158245 0.178354 0.162845 0.183254 0.167245 0.188054 0.171684 0.145684 0.160272 0.173576 0.1744
7 0.12161 0.13297 0.14561 0.1880
19 0.08747 0.11117 0.12457 0.11517 0.1290
19 0.09267 0.11517 0.1360
19 0.09777 0.08867 0.12131 0.14867 0.12137 0.12737 0.12917 0.09437 0.09717 0.13291 0.16287 0.10107 0.13831 0.16947 0.1049
19 0.08627 0.1085
19 0.08927 0.1121
19 0.09217 0.1151
19 0.09497 0.1189
19 0.09777 0.1221
19 0.10037 0.1253
19 0.103019 0.087419 0.09617 0.1157
19 0.0814
0.9900.9301.0190.9401.0191.0001.0141.0361.0511.0811.0361.1081.1401.0631.0921.0401.0921.1461.1621.1311.1651.1961.1401.2121.2451.1861.2591.2931.3021.3381.3451.3821.3861.4241.4271.4651.4661.5051.5041.5451.6021.7621.7351.802
0.36480.13290.43680.18800.43700.33330.37350.34530.38700.46300.34530.40800.48850.26580.36390.14860.36390.38190.38730.28290.29130.39870.16280.30300.41490.16940.31470.43100.32550.44600.33630.46050.34530.47450.35670.48850.36630.50150.37590.51500.43700.48050.34710.4070
875644993690988859918921985
1,111922
1,0941,235
8961,024
8051,0241,1261,1591,0151,0751,229
9661,1651,3311,0461,2551,4311,3441,5331,4341,6351,5231,7371,6131,8401,7021,9421,7922,0442,0742,5122,3042,527
600.0597601597601.4628.8629675.0675.0676.6675750.0751.8750.0750.0746750825.0849.0849900.0900.0896975.0975.0970
1,0501,0551,1251,1301,2001,205.81,2751,281.21,3501,356.51,4251,4321,5001,5071,6872,0442,0552,191
275.347
39293
386.8229.8289246.4309.8434.2247344.3483.3146.0274.1
59274301.4310.0166175.0328.5
70190.0356.3
76205376219403234429.5248456263483.3277510292537387468249336
25,20013,80030,40015,70031,50023,70026,40026,30028,40034,60025,50031,50038,40022,10028,20016,80027,90031,40031,90024,40025,90033,80019,80027,70036,60021,40029,80039,10032,00041,90034,10043,60036,20046,30038,30049,10040,10051,70042,20054,50051,00060,30049,80056,700
0.027400.02740.02750.02730.027470.026140.02610.024360.024360.024420.024360.021920.021970.021920.021920.02180.02190.019930.019360.01940.018270.018270.01810.016860.016860.01670.015660.015730.014610.014690.013700.013770.012900.012960.012180.012240.011540.011590.010960.011010.009840.00800.00800.00749
787784792778797805809825847858845903913875881905894935926918953960972
1,0051,0101,0071,0511,0601,0991,1081,1451,1481,1881,1981,2271,2371,2681,2781,3101,3131,4341,6201,6341,875
(Table 29)
27TAIHAN Overhead Electrical Aluminum Conductors
Aluminum Conductors, Aluminum-clad Steel ReinforcedACSR/AW
Note : Class AA - For bare conductors usually used in overhead lines.
ApplicationThis standard covers aluminum stranded conductors aluminum-cladsteel reinforced which could withstand high tensile load to be usedmainly for overhead transmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of aluminum-clad steel and the outer layeror layers of aluminum.
StandardsConforms to ASTM B 549-93
Conductor Size (Al Wire)
CMILS AWG mm2 ClassNo. ofWires
No. ofWiresin mm in mm
Nominal Dia. Nominal Dia.Aluminum Aluminum-clad Steel
kips(1000 lbf)
kN lb/10000ft kg/km
Stranding Rated Strength Linear Density
2,312,0002,167,0002,156,0001,780,0001,590,0001,590,0001,510,0001,510,0001,431,0001,431,0001,351,0001,351,0001,272,0001,272,0001,272,0001,192,5001,192,5001,113,0001,113,0001,033,5001,033,5001,033,500
954,000954,000954,000900,000900,000795,000795,000795,000795,000795,000795,000715,000715,000715,000666,600
1,1711,0981,092
901.9805.7805.7765.1765.1725.1725.1684.6684.6644.5644.5644.5604.2604.2564.0564.0523.7523.7523.7483.4483.4483.4456.0456.0402.8402.8402.8402.8402.8402.8362.3362.3362.3337.8
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
76728484544554455445544554453654455445544536544536544530544526243630262426
0.17440.17350.16020.14560.17160.18800.16720.18320.16280.17830.15820.17330.15350.16810.18800.14860.16280.14360.15730.13830.15150.16940.13290.14560.16280.12910.14140.16280.12130.13290.17490.18200.14860.15440.16590.17270.1601
4.4304.4074.0693.6984.3594.7754.2474.6534.1354.5294.0184.4023.8994.2704.7753.7744.1353.6473.9953.5133.8484.3033.3763.6984.1353.2793.5924.1353.0813.3764.4424.6233.7743.9224.2144.3874.067
197
1919197
197
197
197
1971
197
19777177177
1977771
19777
0.08140.11570.09610.08740.10300.12530.10030.12210.09770.11890.09490.11550.09210.11210.18800.08920.10850.08620.10490.13830.10100.16940.13290.09710.16280.12910.09430.09770.12130.08860.13600.12130.14860.09260.12900.11510.1245
2.0682.9392.4412.2202.6163.1832.5483.1012.4823.0202.4102.9342.3392.8474.7752.2662.7562.1892.6643.5132.5654.3033.3762.4664.1353.2792.3952.4823.0812.2503.4543.0813.7742.3523.2772.9243.162
55.349.159.049.453.041.850.339.747.737.645.135.542.433.425.740.231.337.529.335.627.121.132.925.419.531.024.037.127.821.530.527.516.633.427.524.826.0
24621926222023618622417621216720015818914911417913916713015812193.714611386.613810716512495.413612273.8148122110116
2,4722,2622,4372,0131,9601,7461,8601,6581,7641,5701,6651,4831,5681,3961,2721,4701,3091,3731,2221,2741,1341,0331,1771,047
9541,111
9381,160
980872
1,041981795
1,043936883872
3,6783,3673,5282,9952,9172,5982,7682,4672,6252,3372,4782,2072,3332,0771,8932,1871,9482,0431,8191,8961,6871,5371,7511,5581,4191,6531,4701,7261,4591,2981,5491,4591,1821,5521,3931,3141,298
(Table 30)
Aluminum-clad steel
Aluminum conductor
28 Overhead Electrical Aluminum Conductors TAIHAN
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
Notes : Class AA - For bare conductors usually used in overhead lines.Class A - For conductors to be covered with weather-resistant materials.(+) : Indicates conductors with high strength to current capacity ratios.
Conductor Size (Al Wire)
CMILS AWG mm2 ClassNo. ofWires
No. ofWiresin mm in mm
Nominal Dia. Nominal Dia.Aluminum Aluminum-clad Steel
kips(1000 lbf)
kN lb/10000ft kg/km
Stranding Rated Strength Linear Density
666,600636,000636,000636,000636,000636,000636,000605,000605,000605,000605,000556,500556,500556,500556,500477,000477,000477,000477,000397,500397,500397,500397,500336,400336,400336,400300,000266,800266,800211,600211,300203,200190,800176,900167,800159,000
337.8322.3322.3322.3322.3322.3322.3306.6306.6306.6306.6282.0282.0282.0282.0241.7241.7241.7241.7201.4201.4201.4201.4170.5170.5170.5152.0135.2135.2107.2107.1103.0
96.6889.6485.0280.57
AAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAAA
AA, AAA(+)AA(+)AA(+)AA(+)AA, AAA(+)
24303026243618303026243026241830262418302624183026182626186
121612126
12
0.16670.14560.14560.15640.18280.13290.18800.14200.14200.15250.15880.13620.14830.15230.17580.12610.13540.14100.16280.11510.12360.12870.14860.10590.11370.13670.10740.10130.12170.18780.13270.11270.12610.12140.16720.1151
4.2343.6983.6983.9734.1353.3764.7753.6073.6073.8734.0343.4593.7163.8684.4653.2033.4393.5814.1352.9243.1393.2693.7742.6902.8883.4722.7282.5733.0914.7703.3712.8633.2033.0844.2472.924
719
77711
1977777717771777177177117
197717
0.11110.08740.14560.12160.10850.13290.18800.08520.14200.11860.10590.13620.11380.10150.17580.12610.10530.09400.16280.11510.09610.08580.14860.10590.08840.13670.08350.07880.12170.18780.13270.09770.12610.12140.16720.1151
2.8222.2203.6983.0892.7563.3764.7752.1643.6073.0122.6903.4592.8912.5784.4653.2032.6752.3884.1352.9242.4412.1793.7742.6902.2453.4722.1212.0023.0914.7703.3712.4823.2033.0844.2472.924
23.129.929.324.822.013.615.028.528.423.621.026.821.919.313.223.418.916.711.519.615.814.1
9.7816.713.5
8.5412.110.8
6.827.69
19.827.118.316.9
6.3015.3
103133130110
98.060.666.8
126.6126105
93.3119
97.585.758.9
10484.374.351.087.470.262.543.574.560.038.054.048.030.334.288.0
12081.375.428.068.0
823928935832785636676883889791747818728687591701624589507584520491422495440357392349283277477601431399219359
1,2241,3811,3911,2381,168
9461,0051,3131,3231,1781,1111,2171,0841,022
8791,043
928876754869773730628736654532584520421411709894641594326534
00000000000000000000000000
(Table 30)
29TAIHAN Overhead Electrical Aluminum Conductors
Notes : Class AA - For bare conductors usually used in overhead lines.Class A - For conductors to be covered with weather-resistant materials.(+) : Indicates conductors with high strength to current capacity ratios.
Conductor Size (Al Wire)
CMILS AWG mm2 ClassNo. ofWires
No. ofWiresin mm in mm
Nominal Dia. Nominal Dia.Aluminum Aluminum-clad Steel
kips(1000 lbf)
kN lb/10000ft kg/km
Stranding Rated Strength Linear Density
152,500141,300134,600133,100121,000112,100110,800105,600101,80099,83095,91088,84083,69080,00079,13076,08070,48066,36066,36064,92062,77060,34055,89052,62051,50049,78047,85044,32041,74041,74040,84039,47037,95035,15032,39031,30025,690
77.2771.6068.2067.4461.3156.8056.1453.5151.5850.5848.6045.0242.4140.5440.1038.5535.7133.6233.6232.8931.8130.5728.3226.6626.1025.2224.2522.4621.1521.1520.6920.0019.2317.8116.4115.8613.02
AA(+)AA(+)AA(+)AA,AAA(+)AA(+)AA(+)AA,AAA(+)AA(+)AA(+)AA(+)AA,AAA(+)AA(+)AA(+)AA(+)AA,AAA,AAA(+)AA(+)AA(+)AA(+)
AAA(+)AA(+)AA(+)AA(+)AA,AAA,AAA(+)AA(+)AA(+)AA(+)AA(+)AA(+)AA(+)
54
12654
126
123546835476235462354762354232
0.17470.18800.10590.14890.15560.16740.09610.13270.09210.18240.13850.14900.11810.10000.16240.12340.13270.09740.10520.18020.14460.10990.11820.09370.16050.12880.09780.10530.07720.08340.14290.11470.08710.09370.12730.10220.1133
4.4374.7752.6903.7823.9524.2522.4413.3712.3394.6333.5183.7853.0002.5404.1253.1343.3712.4742.6724.5773.6732.7913.0022.3804.0773.2722.4842.6751.9612.1183.6302.9132.2122.3803.2332.5962.878
2371237174231142311542315423115423545
0.17470.18800.10590.14890.15560.16740.09610.13270.09210.18240.13850.14900.11810.16700.16240.12340.13270.12990.10520.18020.14460.10990.11820.09370.16050.12880.09780.10530.10290.08340.14290.11470.08710.09370.12730.10220.1133
4.4374.7752.6903.7823.9524.2522.4413.3712.3394.6333.5183.7853.0004.2424.1253.1343.3713.2992.6724.5773.6732.7913.0022.3804.0773.2722.4842.6752.6142.1183.6302.9132.2122.3803.2332.5962.878
9.6614.213.0
5.138.03
11.910.8
4.259.91
16.46.589.683.454.89
13.85.458.103.512.76
19.511.2
4.376.602.23
16.59.693.505.262.281.78
13.57.722.794.19
11.36.138.96
43.062.957.822.835.752.748.018.944.172.729.343.015.321.761.224.336.015.612.386.950.019.429.4
9.9273.343.115.623.410.1
7.9359.934.312.418.650.327.339.9
281373304174223296250138230395177234109138313140186100
86.843024811114769341197
88.0117
62.754.5
270156
69.892.6
215124170
41855545225933244037220534258826334816320546620927614912964036916521910250829313117493.381.1
402232104138319185253
00000000000000000000001111122222233333444444444
(Table 30)
30 Overhead Electrical Aluminum Conductors TAIHAN
Stranded Aluminum-clad Steel ConductorAWS
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
ApplicationThis standard covers stranded aluminum-clad steel conductors to beused mainly for overhead ground wire.
ConstructionStranded aluminum-clad steel conductor
StandardsConforms to ASTM B 416-93
Coefficient of linear expansion 0.0000072/ 0.0000126/Final modulus of elasticity 23,000,000psi(160GPa)Temperature coefficient of resistance 0.0020/ 0.0036/Conductivity 20.3%
No. andSize ofWires
Min.BreakingStrength
(lb)
NominalDia.
(in)
No. and Dia. ofIndividual Wires Linear Density
Max.Resistance
( /1000ft, 20 )
NominalCross Section
Number(No.)
Nominal Dia.(in)
lb/1000ft lb/mile CMILS sq in
37 No. 5AWG37 No. 6AWG37 No. 7AWG37 No. 8AWG37 No. 9AWG37 No.10AWG19 No. 5AWG19 No. 6AWG19 No. 7AWG19 No. 8AWG19 No. 9AWG19 No.10AWG7 No. 5AWG7 No. 6AWG7 No. 7AWG7 No. 8AWG7 No. 9AWG7 No.10AWG7 No.11AWG7 No.12AWG3 No. 5AWG3 No. 6AWG3 No. 7AWG3 No. 8AWG3 No. 9AWG3 No.10AWG
373737373737191919191919
77777777333333
0.18190.16200.14430.12850.11440.10190.18190.16200.14430.12850.11440.10190.18190.16200.14430.12850.11440.10190.09070.08080.18190.16200.14430.12850.11440.1019
1.271.131.010.8990.8010.7130.9100.8100.7210.6420.5720.5090.5460.4860.4330.3850.3430.3060.2720.2420.3920.3490.3110.2770.2470.220
142,800120,200100,700
84,20066,77052,95073,35061,70051,73043,24034,29027,19027,03022,73019,06015,93012,63010,020
7,9456,301
12,23010,280
8,6217,2065,7154,532
2,8022,2221,7621,3981,108
879.01,4301,134
899.5713.5565.8448.7524.9416.3330.0261.8207.6164.7130.6103.6224.5178.1141.2112.0
88.8170.43
14,80011,730
9,3057,3795,8524,6417,5525,9904,7503,7672,9872,3692,7722,1981,7431,3821,096
869.4689.4546.8
1,186.0940.2745.6591.3468.9371.8
0.042470.053560.067540.085160.10740.13540.082240.10370.13080.16490.20790.26220.22640.28030.35350.44580.56210.70880.89381.1270.51770.65280.82321.0381.3091.651
1,225,000971,300770,300610,900484,400384,200628,900498,800395,500313,700248,800197,300231,700183,800145,700115,600
91,65072,68057,59045,71099,31078,75062,45049,53039,28031,150
0.96190.76290.60500.47980.38050.30170.49400.39170.31070.24640.19540.15490.18200.14430.11450.090770.071980.057080.045230.035900.078000.061850.049050.038900.030850.02446
(Table 31)
Aluminum
Steel
31TAIHAN Overhead Electrical Aluminum Conductors
Hard-drawn Aluminum Wires for Electric PurposesAL-ALLOY
Diameter Min. Tensile Strength
Individual Tests(%)
Toleranceon Dia.
( %, or in)
Min. Elongationin 10 in or250mm
inksi MPa ksi MPa
mmAverage for a Lot Individual Tests
0.1878 to 0.13280.1327 to 0.0612
4.770 to 3.3733.371 to 1.554
1%0.0010 in
4648
317331
4446
303317
3.03.0
(Table 32)Tensile Requirements
MaterialVolume
Conductivity(% IACS) cmil/ft mm2/m in cm
(Table 33)Equivalent Resistivity Values at 20°C(68°F)Resistivity Constants
Volume
CopperAluminumAluminumAluminum
10061.053.552.5
10.37117.00219.38519.755
0.0172410.0282650.0322270.32841
0.678791.11281.26871.2929
1.72412.82653.22273.2841
ApplicationThis standard covers aluminum-alloy(hard:solution, heat-treated, coldworked, and artificially aged) round wires for electrical purposes to beused mainly as component wires of Al-alloy stranded cables and Al-alloy cables steel reinforced.
ConstructionSingle aluminum-alloy conductor
StandardsConforms to ASTM B 398-97
32 Overhead Electrical Aluminum Conductors TAIHAN
Stranded Aluminum-alloy 6201-T81 ConductorsAAAC
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
ApplicationThis standard covers stranded aluminum-alloy 6201-T81 conductorswhich could high tensile load to be used mainly for overheaddistribution wire.
ConstructionStranded aluminum-alloy conductor
StandardsConforms to ASTM B 399-97
Notes : Class AA - For bare conductors usually used in overhead lines.Class A - For conductors to be covered with weather-resistant materials.
CodeWord
CMILS mm2
CMILSA AWG mm2
ConductorSize
Approx. Aluminum1350 Size having
Equivalent Resistance
Size and Stranding ofACSR with Equal Dia.
Required Construction WeightRated
StrengthResis-tance
Size CMILSA AWG kg/km kips kNClassmm2
in mm
Strand-ing
No. ofWires
lb/1000ft
Dia. of Wires ( /1000ft,20 )
-----GreelyFlintElginDarienCairoCantonButteAllianceAmherstAnaheimAzusaAmesAltonAkron
1,439,2001,348,8001,259,6001,165,1001,077,400927,200740,800652,400559,500465,400394,500312,800246,900195,700155,400123,300
77,47048,69030,580
729.2683.4638.2590.3545.9469.8375.4330.6283.5235.8199.9158.5125.1
99.278.762.539.324.715.5
0000000000246
644.5604.2564.0523.7483.4402.8322.3282.0241.7201.4170.5135.2107.2
85.067.453.533.621.113.3
1,272,0001,192,5001,113,0001,033,500954,000795,000636,000556,500477,000397,500336,400266,800211,600167,800133,100105,60066,36041,74026,240
0000000000246
644.5604.2564.0523.7483.4402.8322.3282.0241.7201.4170.5135.2107.2
85.067.453.533.621.113.3
54/754/754/754/754/726/726/726/726/726/726/726/7
6/16/16/16/16/16/16/1
616161616137371919191919
7777777
0.15360.14870.14370.13820.13290.15830.14150.18530.17160.15650.14410.12830.18780.16720.14900.13270.10520.08340.0661
3.903.783.653.513.384.023.594.714.363.983.663.264.774.253.783.372.672.121.68
AAAAAAAAAAAAAAAAAAAA
AA, AA
AAAA, AAA, AAA, AAA, A
AA
1,3421,2581,1751,0861,005
864.6690.8608.3521.7433.9367.9291.6230.2182.5144.9114.972.2445.4028.52
1,9971,8721,7481,6171,4951,2871,028
905.2776.3645.7547.4434.0342.6271.5215.6171.0107.567.5642.44
46.843.941.037.935.030.524.421.918.815.613.311.0
8.566.795.394.462.801.761.11
208195182169156136108
97.583.669.659.048.838.130.224.019.812.57.844.92
0.01400.01490.01600.01730.01870.02170.02720.03090.03600.04330.05110.06440.08160.103 0.1300.1630.2600.4140.659
1,272,0001,192,5001,113,0001,033,500954,000795,000636,000556,500477,000397,500336,400266,800211,600167,800133,100105,60066,36041,74026,240
(Table 34)
33TAIHAN Overhead Electrical Aluminum Conductors
High-strength Zinc-coated Steel Core Wire for Aluminum and Aluminum-alloy Conductors, Steel ReinforcedH.S-ACSR
Note : The above sizes are those commonly used.
ApplicationThis standard covers round, high-stength, zinc-coated, steel core wirewith class A zinc coating used for mechanical reinforcement in themanufacture of special Al and Al-alloy conductors, steel reinforced.
ConstructionThe center wire or wires are of high-strength galvanized steel and theouter layer or layers of special aluminum.
StandardsConforms to ASTM B 606-93
ACSR CopperEquivalent
(MCM or AWG)
No. and Dia. of Strands
(in)
Diameter
(in)Cross Section
Total
sq in Al StCompleteConductor
SteelCore
Aluminum
sq inMCM or AWG
CodeWord
GrousePetrelMinorcaLeghornGuineaDotterelDorkingBrahmaCochin
80101.8110.8134.6159176.9190.8203.2211.3
0.06280.08000.08700.10570.12490.13890.14990.15960.1660
0.08470.12660.13780.16740.19770.21990.23730.30200.2628
50.3164.1669.784.6
100111.2120.0127.8132.9
0.3670.4610.4810.5300.5760.6070.6310.7140.664
0.16700.27630.28830.31770.34530.36420.37830.48850.3981
8 0.100012 0.092112 0.096112 0.105912 0.115112 0.121412 0.126116 0.112712 0.1327
1 0.16707 0.09217 0.09617 0.10597 0.11517 0.12147 0.1261
19 0.09777 0.1327
(Table 35)
Weight(pound) Total Weight(%)
Ultimate Strength (pound)Zinc-coated Core
CalculatedResistance
at 20°C(68°F)
( /1000ft)
Per 1000ft Per mileCodeWord
Al Total Al Total Al StStandardWeightCoating
Class BCoating
Class CCoating
GrousePetrelMinorcaLeghornGuineaDotterelDorkingBrahmaCochin
75.196.0
104.5127.0150.0166.9180.0191.7199.3
149.0254.1276.6336.0396.8441.5476.3676.6527.5
397507552671792881950
1,0121,052
7871,3421,6401,7742,0952,3312,5253,5732,785
50.437.837.837.837.837.837.828.337.8
49.662.262.262.262.262.262.271.762.2
5,2009,860
10,73012,92015,20016,40017,73027,50019,640
4,6559,615
10,48012,62014,85015,64016,86026,80018,700
4,5509,385
10,22012,31014,88014,83016,00026,10017,700
0.2170.1710.1570.1290.1100.09850.09130.07230.0825
(Table 36)
High-strengthGalvanized steel
Aluminum conductor
34 Overhead Electrical Aluminum Conductors TAIHAN
“EC” Grade Aluminum Conductor Constructions, Weather-resistant Wire and CableHAL-OC
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
ApplicationThis standard covers HAL-OC(for use in 6,600 volts circuits) to be usedas weather-resistant wire and cable for the distribution of electricalenergy under the normal conditions of overhead line service.
ConstructionSolid or stranded hard-drawn aluminum conductor and polyethylenecross linked polyethylene insulation
StandardsConforms to ANSI C 8.35-1975, ICEA S-70-547
Add “HD” to code word to designated high-density polyethylene covering, or “XLPE” to designate cross-linked thermosetting polyethylene covering.
Code WordAWG or MCM
CMILS mm2
Cross Sectional Area No. of Wiresmils mm
Conductor Covering Thickness
CumquatApplePlumPearApricotCherryPeachNectarineQuinceHawOrangeIronwoodFigLemonOlivePomegranateSassafrasCatalpaMulberrySilverbeltBasswoodSycamoreAnonaCrabappleChinquapinGinkgoMollesAshSumacHuckleberryTupeloPaw PawTangerineBreadfruitPersimmonGrapefruitMango
86644221
1/01/02/0 2/0 3/03/04/04/0
250250266.8266.8300300336.4336.4350350397.5400450477500556636636795
1,033.51,590
16,51026,24026,24041,74041,74066,36066,36083,690
105,600105,600133,100133,100167,800167,800211,600211,600
8.36713.3013.3021.1521.1533.6233.6242.4153.4953.4967.4367.4385.0185.01
107.2107.2127127135135152152170170177177201203228242253282322322403523806
SolidSolid
7Solid
7Solid
777
197
197
197
19191919191919191919191919373737373761616161
303030303045454560606060606060606075607560756075607575757575757595959595
110
0.760.760.760.760.761.141.141.141.521.521.521.521.521.521.521.521.521.901.521.901.521.901.521.901.521.901.901.901.901.901.901.902.412.412.412.412.79
(Table 37)
Aluminum conductor
XLPE insulation
35TAIHAN Overhead Electrical Aluminum Conductors
Aluminum, Steel-reinforced(ACSR) Conductor Weather-resistant Insulation WiresACSR/OC
ApplicationThis standard covers ACSR-OC(for use in 6,600 volts circuits) to beused as weather-resistant cable for the distribution of electrical energyunder the normal conditions of overhead line service.
ConstructionAluminum, steel-reinforced conductor and polyethylene or cross-linkedpolyethylene insulation
StandardsConforms to ANSI C 8.35-1975, ICEA S-70-547
Galvanized steel
XLPE insulation
Aluminum conductor
Code WordAWG or MCM
CMILS mm2
Aluminum Cross Sectional Area Strands Al/Stmils mm
Conductor Covering Thickness
WalnutAcornButternutHickoryHazelnutPignutBeechChestnutAlmondPecanCottonwoodFilbertChokeberryBuckeyeGumwoodHackberryRedbudMockernutAspen
65443221
1/02/02/03/03/04/04/0
266.8266.8336.4336.4
26,24033,09041,74041,74052,62066,36066,36083,690
105,600133,100133,100167,800167,800211,600211,600
13.3016.7721.1521.1526.6733.6233.6242.4153.4967.4367.4385.0185.01
107.2107.2135135170170
6/16/16/17/16/16/17/16/16/16/16/16/16/16/16/1
18/118/118/118/1
30303030454545456060756075607560756075
0.760.760.760.761.141.141.141.141.521.521.901.521.901.521.901.521.901.521.90
(Table 38)
Add “HD” to code word to designated high-density polyethylene covering, or “XLPE” to designate cross-linked thermosetting polyolefin covering.
36 Overhead Electrical Aluminum Conductors TAIHAN
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
Electrical Conductors, Covered Line Wire and Multiplex Types Weather-resistant Line Wire
Note : Items shown in colored type are normally used.
(Table 39)
POLYETHYLENE TYPE
Al Total
Code Word CMILS or AWG StrandingCover Thickness
64th(in)
Nominal Weight(pound/1000ft)
Length per Reel
(ft)
Solid Aluminum ConductorApplePearCherry
642
111
223
24.238.461.1
31.748.079.2
12,0008,5005,000
(Table 42)
CROSS-LINKED POLYETHYLENE(XLPE) TYPE
Al Total
Code Word CMILS or AWG StrandingCover Thickness
64th(in)
Nominal Weight(pound/1000ft)
Length per Reel
(ft)
Solid Aluminum ConductorApple/XLPEPear/XLPECherry/XLPE
642
111
223
24.238.461.1
345083
12,0008,5005,000
(Table 41)ACSRWalnutButternutHickoryPignutBeechChestnutAlmondPecanFilbertBuckeyeHackberry
644221
1/02/03/04/0
266,800
6/16/17/16/17/16/16/16/16/16/1
18/1
22233344444
24.539.039.062.062.078.298.6
124.3156.8197.7250.4
47.572.082.0
119.0135.0146.0191.0235.0290.0359.0357.0
8,0005,1006,0006,4005,6005,1004,0003,2003,8003,0002,400
(Table 43)Stranded Aluminum ConductorPlum/XLPEApricot/XLPEPeach/XLPENectarine/XLPEQuince/XLPEOrange/XLPEFig/XLPEOlive/XLPEPomegranate/XLPE
6421
1/02/03/04/04/0
77777777
19
223344444
24.639.262.378.599.1
124.9157.5198.6198.6
375593
113150183223274266
9,4007,0007,5006,0004,7003,7504,4003,5003,800
(Table 40)Stranded Aluminum ConductorPlumApricotPeachNectarineQuinceOrangeFigOlivePomegranateMulberryAnonaCrabappleMollesHuckleberryPaw PawBraedfruitPersimmonGrapefruit
6421
1/02/03/04/04/0
266,800336,400336,400397,500477,000556,500636,000795,000
1,033,500
77777777
19191919193737616161
223344444445555666
24.639.262.378.599.1
124.9157.5198.6198.6250.4315.8315.8372.5447.8522.4597.0746.3970.1
35.053.387.4
107.0140.0172.0211.0260.0255.0315.0390.0404.0471.0550.0635.0740.0900.0
1,150.0
9,4007,0007,5006,0004,7003,7504,4003,5003,8003,0002,4002,0002,0003,3002,8002,5002,2001,700
37TAIHAN Overhead Electrical Aluminum Conductors
Electrical Conductors, Covered Line Wire and Multiplex Types Self-supporting Secondary and Service Drop Cable
(Table 44)
POLYETHYLENE DUPLEX TYPE
Code WordAWG Stranding
AWG Stranding Al TotalInsulation
Thickness 64th
Phase Conductors Bare NeutralMessenger
Nominal Weight(lb/1000ft)
Lengthper Reel
(ft)
All-aluminum Neutral MessengerPekingeseCollieDachshundSpanielDobermanMalemute
66442
1/0
17177
19
333334
66442
1/0
777777
49497878
125198
636695
100152244
3,0002,8002,2002,0002,4001,500
(Table 45)ACSR Neutral MessengerSetterShepherdEskimoTerrierChowBull
66442
1/0
17177
19
333334
66442
1/0
6/16/16/16/16/16/1
49497778
124198
7578
114118181289
3,0002,8002,2002,0002,4001,500
(Table 46)
CROSS-LINKED POLYETHYLENE(XLPE) DUPLEX TYPE
Code WordAWG Stranding
AWG Stranding Al TotalInsulation
Thickness 64th
Phase Conductors Bare NeutralMessenger
Nominal Weight(lb/1000ft)
Lengthper Reel
(ft)
All-aluminum Neutral MessengerPekingese/XLPECollie/XLPEDachshund/XLPESpaniel/XLPEDoberman/XLPEMalemute/XLPE
66442
1/0
17177
19
333334
66442
1/0
777777
49497878
125198
646896
103156246
3,0002,8002,2002,0002,4001,500
(Table 47)ACSR Neutral MessengerSetter/XLPEShepherd/XLPEEskimo/XLPETerrier/XLPEChow/XLPEBull/XLPE
66442
1/0
17177
19
333334
66442
1/0
6/16/16/16/16/16/1
49497778
124198
7580
114121185282
3,0002,8002,2002,0002,4001,500
Note : Items shown in colored type are normally used.
38 Overhead Electrical Aluminum Conductors TAIHAN
AST
MA
NSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
Electrical Conductors, Covered Line Wire and Multiplex Types Self-supporting Secondary and Service Drop Cable
(Table 48)
POLYETHYLENE TRIPLEX TYPE
Code WordAWG Stranding
AWG Stranding Al TotalInsulation
Thickness 64th
Phase Conductors Bare NeutralMessenger
Nominal Weight(lb/1000ft)
Lengthper Reel
(ft)
All-aluminum Neutral Messenger6442
1/01/02/02/03/04/0
11777
197
191919
3333444444
6442
1/01/02/02/03/04/0
77777777
1919
73116118187297297375375473596
100151161240395390486478583722
2,5001,7001,5001,8001,2001,2001,5001,5001,3001,000
HaiotisFususOysterClamMurexPurpuraNassaTrophonMelitaPortunus
(Table 49)ACSR Neutral MessengerPaludinaVolutaWhelkPeriwinkleConchNeritinaCeniaRuncinaTritonMursiaZuzara
66442
1/01/02/02/03/04/0
171777
197
191919
33333444444
6644 2
1/01/02/02/03/04/0
6/16/16/16/16/16/16/16/16/16/16/1
7374
116118187297297374374472596
112120170180270431426544536657814
2,5002,0001,7001,5001,8001,2001,2001,5001,5001,3001,000
(Table 50)
CROSS-LINKED POLYETHYLENE(XLPE) TRIPLEX TYPE
Code WordAWG Stranding
AWG Stranding Al TotalInsulation
Thickness 64th
Phase Conductors Bare NeutralMessenger
Nominal Weight(lb/1000ft)
Lengthper Reel
(ft)
All-aluminum Neutral Messenger6442
1/01/02/02/03/04/0
11777
197
191919
3333444444
6442
1/01/02/02/03/04/0
77777777
1919
73116118187297297375375473596
103154166249400393480483595734
2,5001,7001,5001,8001,2001,2001,5001,5001,3001,000
Haiotis/XLPEFusus/XLPEOyster/XLPEClam/XLPEMurex/XLPEPurpura/XLPENassa/XLPETrophon/XLPEMelita/XLPEPortunus/XLPE
(Table 51)ACSR Neutral MessengerPaludina/XLPEVoluta/XLPEWhelk/XLPEPeriwinkle/XLPEConch/XLPENeritina/XLPECenia/XLPERuncina/XLPETriton/XLPEMursia/XLPEZuzara/XLPE
66442
1/01/02/02/03/04/0
171777
197
191919
33333444444
6644 2
1/01/02/02/03/04/0
6/16/16/16/16/16/16/16/16/16/16/1
7374
116118187297297374374472596
115124172184278446439498541668827
2,5002,0001,7001,5001,8001,2001,2001,5001,5001,3001,000
39TAIHAN Overhead Electrical Aluminum Conductors
Electrical Conductors, Covered Line Wire and Multiplex Types Self-supporting Secondary and Service Drop Cable
(Table 52)
POLYETHYLENE QUADRUPLEX TYPE
Code WordAWG Stranding
AWG Stranding Al TotalInsulation
Thickness 64th
Phase Conductors Bare NeutralMessenger
Nominal Weight(lb/1000ft)
Lengthper Reel
(ft)
All-aluminum Neutral MessengerClydesdalePintoMustangCriolloPercheronHanoverionOldenburg
442
1/02/03/04/0
177
19191919
3334444
442
1/02/03/04/0
77777
1919
154157249396500630795
207220330535655806993
1,7001,5001,8001,1001,5001,3001,000
(Table 53)ACSR Neutral MessengerMorochucaCholaMorganHackneyPalominoCostenaGrulloSuffolkAppaloosa
66442
1/02/03/04/0
17177
19191919
333334444
66442
1/02/03/04/0
6/16/16/16/16/16/16/16/16/1
9798
154157249396499629794
151163225245370580715879
1,087
2,5002,0001,7001,5001,8001,1001,5001,3001,000
(Table 54)
CROSS-LINKED POLYETHYLENE(XLPE) QUADRUPLEX TYPE
Code WordAWG Stranding
AWG Stranding Al TotalInsulation
Thickness 64th
Phase Conductors Bare NeutralMessenger
Nominal Weight(lb/1000ft)
Lengthper Reel
(ft)
All-aluminum Neutral MessengerClydesdale/XLPEPinto/XLPEMustang/XLPECriollo/XLPEPercheron/XLPEHanoverion/XLPEOldenburg/XLPE
442
1/02/03/04/0
177
19191919
3334444
442
1/02/03/04/0
77777
1919
154157249396500630795
202219329521641791977
1,7001,5001,8001,1001,5001,3001,000
(Table 55)ACSR Neutral MessengerMorochuca/XLPEChola/XLPEMorgan/XLPEHackney/XLPEPalomino/XLPECostena/XLPEGrullo/XLPESuffolk/XLPEAppaloosa/XLPE
66442
1/02/03/04/0
17177
19191919
333334444
66442
1/02/03/04/0
6/16/16/16/16/16/16/16/16/1
9798
154157249396499629794
148159221238359568700864
1,070
2,5002,0001,7001,5001,8001,1001,5001,3001,000
One phase wire identified with ridges.
40 Overhead Electrical Aluminum Conductors TAIHAN
International Electrotechnical Commission IEC
41TAIHAN Overhead Electrical Aluminum Conductors
Stranded Hard-drawn Aluminum ConductorAAC
ApplicationThis standard covers stranded hard-drawn circular aluminumconductors to be used mainly for overhead distribution wires, overheadfeeder.
ConstructionStranded hard-drawn aluminum conductors
StandardsConforms to IEC 1089-91
CodeNumber
(No.)
Area
(mm2)
No. ofWires(No.)
LinearMass
(kg/km)
RatedStrength
(kN)
D.C.Resistance
( / km)Wire Conductor
Diameter(mm)
1016254063
100125160200250315400450500560630710800900
1,0001,1201,2501,4001,500
1016254063
100125160200250315400450500560630710800900
1,0001,1201,2501,4001,500
77777
19191919193737373737616161616191919191
1.351.712.132.703.392.592.893.273.664.093.293.713.944.154.393.633.854.094.334.573.964.184.434.58
4.055.126.408.09
10.212.914.516.418.320.523.026.027.529.030.732.634.636.839.041.143.546.048.750.4
27.443.868.4
109.4172.3274.8343.6439.8549.7687.1867.9
1,102.01,239.81,377.61,542.91,738.31,959.12,207.42,483.32,759.23,093.53,452.63,866.94,143.1
1.953.044.506.80
10.3917.0021.2526.4032.0040.0051.9764.0072.0080.0089.60
100.80113.60128.00144.00160.00179.20200.00224.00240.00
2.86331.78961.14530.71580.45450.28770.23020.17980.14390.11510.09160.07210.06410.05770.05150.04580.04070.03610.03210.02890.02580.02310.02070.0193
(Table 56)
42 Overhead Electrical Aluminum Conductors TAIHAN
Stranded Aluminum-alloy ConductorsAAAC
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TEC
CodeNumber
(No.)
Area
(mm2)
No. ofWires(No.)
LinearMass
(kg/km)
RatedStrength
(kN)
D.C.Resistance
( / km)Wire Conductor
Diameter(mm)
16254063
100125160200250315400450500560630710800900
1,0001,120
18.629.046.573.2116145186232290366465523581651732825930
1,0461,1621,301
7777
19191919193737373761616161919191
1.842.302.913.652.793.123.533.954.413.554.004.244.473.693.914.154.403.834.034.27
5.526.908.72
10.914.015.617.619.722.124.828.029.731.333.235.237.339.642.144.446.9
50.879.5
127.1200.2319.3399.2511.0638.7798.4
1,008.41,280.51,440.51,600.61,795.32,019.82,276.22,564.82,888.33,209.33,594.4
6.049.44
15.1023.0637.7647.2058.5673.2091.50
115.29146.40164.70183.00204.96230.58259.86292.80329.40366.00409.92
1.78961.14530.71580.45450.28770.23020.17980.14390.11510.09160.07210.06410.05770.05160.04580.04070.03610.03210.02890.0258
(Table 57)
ApplicationThis standard covers stranded aluminum-alloy conductors of thealuminum-magnesium-silicon type which could high tensile load to beused mainly for overhead distribution wires.
ConstructionStranded aluminum-alloy conductor
StandardsConforms to IEC 1089-91
43TAIHAN Overhead Electrical Aluminum Conductors
Aluminum Conductors, Steel ReinforcedACSR
ApplicationThis standard covers aluminum stranded conductors steel reinforcedwhich could withstand high tensile load to be used mainly for overheadtransmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of steel and the outer layer or layers ofaluminum.
StandardsConforms to IEC 1089-91
CodeNumber
SteelRatio
Areas(mm2)
No. of Wires(No.)
Wire Dia.(mm)
Diameter(mm)
LinearMass
RatedStrength
D.C.Resistance
(No.) (%) Al St Total Al St Al St Core (kg/km) (kN) ( / km)Conductor16254063
100125125160160200200250250315315400400450450500500560560630630710710800800800900900
1,0001,1201,1201,2501,250
1717171717
616
616
6161016
716
713
713
713
713
713
713
48
134844884
16254063
100125125160160200200250250315315400400450450500500560560630630710710800800800900900
1,0001,1201,1201,2501,250
2.674.176.67
10.516.7
6.9420.4
8.8926.111.132.624.640.721.851.327.751.931.158.334.664.838.770.943.679.849.189.934.666.7
10138.975.043.247.391.2
10252.8
18.729.246.773.5
117132145169186211233275291337366428452481508535565599631674710759800835867901939975
1,0431,1671,2111,3521,303
66666
1826182618262226452645544554455445544554455472845472847272848472
1111117171777777777777
197
197
1977
19777
19191919
1.842.302.913.664.612.972.473.362.803.763.133.803.502.993.933.363.073.573.263.763.433.983.634.223.854.484.093.763.484.343.993.694.214.454.124.354.70
1.842.302.913.664.612.971.923.362.183.762.432.112.721.993.052.243.072.383.262.513.432.652.182.812.312.992.452.513.482.612.663.692.801.782.472.611.88
1.842.302.913.664.612.975.773.366.533.767.306.348.165.979.166.739.217.149.777.52
10.37.96
10.98.44
11.68.96
12.37.52
10.413.0
7.9811.1
8.418.90
12.413.1
9.40
5.536.918.74
11.013.814.915.716.817.718.819.821.622.223.924.926.927.628.529.330.130.931.832.733.834.735.936.837.638.339.139.940.642.144.545.347.947.0
64.6100.9161.5254.4403.8397.9503.9509.3644.9636.7806.2880.6
1,007.71,039.61,269.71,320.11,510.31,485.21,699.11,650.21,887.91,848.22,103.42,079.22,366.32,343.22,666.82,480.22,732.73,004.92,790.23,074.23,100.33,464.93,811.54,253.93,867.1
6.089.13
14.4021.6334.3329.1745.6936.1857.6944.2270.1368.7287.6779.03
106.8398.36
123.04107.47138.42119.41153.80133.74172.59150.45191.77169.56216.12167.41205.33243.52188.33226.50209.26234.53283.17316.04261.75
1.79341.14780.71740.45550.28690.23040.23100.18000.18050.14400.14440.11540.11550.09170.09170.07220.07230.06420.06430.05780.05780.05160.05160.04590.04590.04070.04070.03610.03620.03620.03210.03220.02890.02580.02580.02320.0231
(Table 58)
Galvanized steel
Aluminum conductor
44 Overhead Electrical Aluminum Conductors TAIHAN
Aluminum-alloy Conductors, Extra-high Strength Steel ReinforcedAACSR/EST
ASTM
ANSI
IEC
BSAS
CSA
DIN
KSJI
SKE
PCO
TECApplication
This standard covers aluminum-alloy(aluminum-magnesium-silicontype) stranded conductors extra high strength steel with class 1 zinc-coating reinforced which could withstand extra high tensile load to beused mainly for overhead transmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of extra-high strength galvanized steel andthe outer layer or layers of aluminum-alloy.
StandardsConforms to IEC 1089-91
CodeNumber
SteelRatio
Areas(mm2)
No. of Wires(No.)
Wire Dia.(mm)
Diameter(mm)
LinearMass
RatedStrength
D.C.Resistance
(No.) (%) Al St Total Al St Al St Core (kg/km) (kN) ( / km)Conductor16254063
100125125160160200200250250315315400400450450500500560560630630710710800800900900
1,0001,120
1717171766
166
166
161016
716
713
713
713
713
413
413
484888
18.629.046.573.2
116145145186186232232290290366366465465523523581581651651732732825825930930
1,0461,0461,1621,301
3.104.847.75
12.26.468.07
23.710.330.312.937.828.547.325.359.632.160.236.167.840.275.345.082.431.692.735.6
10440.277.545.287.194.6
106
21.733.954.285.4123153169196216245270319338391426497525559591621656696733764825861929970
1,0071,0911,1331,2571,407
6666
1818261826182622264526455445544554455472547254728472848484
1111117171777777777777
197
197
197777
1919
1.992.483.143.942.873.212.673.633.024.053.374.103.773.224.233.633.313.853.514.053.704.293.923.604.153.824.414.053.754.303.984.204.44
1.992.483.143.942.873.212.073.632.354.052.622.282.932.153.292.423.312.563.512.703.702.862.352.402.492.552.652.703.752.873.982.522.66
1.992.483.143.942.873.216.223.637.044.057.876.838.806.449.887.259.937.69
10.58.11
11.18.58
11.87.20
12.57.64
13.28.11
11.38.60
11.912.613.3
5.967.459.42
11.814.316.016.918.119.120.321.423.223.925.726.829.029.830.831.632.433.334.335.336.037.438.239.740.541.343.043.846.248.9
75.1117.3187.7295.6369.9462.3585.4591.8749.4739.8936.7
1,023.21,170.91,207.91,475.31,533.91,754.91,725.61,974.21,917.32,193.62,147.42,444.02,269.42,749.52,557.63,098.62,881.83,175.13,242.03,572.03,954.14,428.6
10.5316.2725.7939.4146.8658.3481.5072.40
103.1190.50
128.89131.72158.21155.64197.55191.71234.19215.67255.52239.63283.91268.39321.17275.18361.32310.12407.20349.43396.60393.11446.17499.40559.33
1.79341.14780.71740.45550.28800.23040.23100.18000.18050.14400.14440.11540.11550.09170.09170.07220.07230.06420.06430.05780.05780.05160.05160.04590.04590.04070.04070.03610.03620.03210.03220.02890.0258
(Table 59)
Extra-high strength galvanized steel
Aluminum-alloy conductor
45TAIHAN Overhead Electrical Aluminum Conductors
Taihan Electric Wire
opening up the happier
world and more enriched future
46 Overhead Electrical Aluminum Conductors TAIHAN
British Standards
Australian Standards
Canadian Standards Association
Deutsches Normen
BS
AS
CSA
DIN
47TAIHAN Overhead Electrical Aluminum Conductors
Stranded All-aluminum ConductorsAAC
Aluminum Wires Used in the Construction of Standard Aluminum Stranded Conductors
ApplicationThis standard covers all-aluminum stranded conductors to be usedmainly for overhead distribution wire, overhead feeders and buses.
ConstructionAll-aluminum stranded conductors
StandardsConforms to BS 215 : part 1/1970
CodeWord
NominalAluminum
Area(mm2)
EquivalentArea
(HDCC)(mm2)
Stranding& Wire
Dia.(mm)
Approx.Overall
Dia.(mm)
TotalArea
(mm2)
Weight
(kg/km)
NominalBreaking
Load(kgf)
Max. D.C.Resistance
( km, 20 ) Temperate Tropical
Rating(amps)
MidgeAphisGnatWeevilMosquitoLadybirdAntFlyBluebottleEarwigGrasshopperCleggWaspBeetleBeeCricketHornetCaterpillarChaferSpiderCockroachButterflyMothDroneLocustCentipedeMaybugScorpionCicadaTarantula
22-----
5060
----
100---
150-
200-
250300
---
400----
14.216.116.119.422.625.832.338.745.248.451.658.164.564.580.696.896.8
113.0129.0145.0161.0194.0226.0226.0258.0258.0290.0323.0387.0484.0
7/2.063/3.357/2.213/3.667/2.597/2.797/3.107/3.407/3.667/3.787/3.917/4.177/4.39
19/2.677/4.907/5.36
19/3.2519/3.5319/3.7819/3.9919/4.2219/4.6519/5.0037/3.5819/5.3637/3.7837/4.0937/4.2737/4.6537/5.23
6.187.26.67.97.88.49.3
10.211.011.411.712.513.1713.414.716.116.2517.718.920.021.123.2525.025.126.826.4628.629.932.636.6
23.3326.426.831.637.042.852.8363.5573.778.584.195.6
106.0106.6132.0157.9157.6186.0213.2236.9265.7322.7373.2373.3428.5415.2486.9529.5628.6794.8
64737386
101117145174202215230262290293361432434512587652731888
1,0271,0291,1791,1451,3421,4601,7332,191
408419468496617701846
1,0101,1581,2181,3031,4821,6321,7762,0832,4322,5192,9203,3043,6724,1204,9665,7485,8586,6016,4347,5478,1569,682
12,247
1.2271.0811.0680.90820.77310.66940.54190.45050.38840.36450.34050.29940.27020.26990.21690.18140.18250.15470.13490.12140.108300.089160.077090.077230.067140.068440.059210.054450.045870.03628
114139124147144159181199219227238256271274308342346380414439470528572572626619676710784899
7287789593
101112124132136141150158172175189190204215224232247256257263262268269266241
(Table 60)
No. of Wiresin Conductor Mass Electrical Resistance
Stranding Constants Practical(final) Modulus of Elasticity(hbar)
Coefficient of Linear(Expansion/ )
71937
7.09119.3437.74
0.14470.053570.02757
5,9005,6005,600
23.0 10-6
23.0 10-6
23.0 10-6
Standard Dia.
(mm)
Mass
(kg/km)
Standard Resistance
( /km,20 )
Min. Breaking Load for Standard Dia. Wire
(N)
Cross Sectional Area ofStandard Dia. Wire
(mm2)
1 2 3 4 5
2.063.103.253.403.784.224.394.65
3.3337.5488.2969.079
11.2213.9915.1416.98
9.00920.4022.4224.5430.3337.8140.9145.90
8.4803.7453.4073.1132.5192.0211.8671.664
6001,2501,3701,4901,8002,2402,4102,700
Note : These values are given for information only. 1 hbar=10MN/m2=10N/mm2
Note : The values given in columns 2 to 5 are given for information olny.
48 Overhead Electrical Aluminum Conductors TAIHAN
Aluminum Conductors, Steel ReinforcedACSR
ASTM
ANSI
IEC
BS
AS
CSA
DIN
KSJI
SKE
PCO
TEC
ApplicationThis standard covers aluminum stranded conductors steel reinforcedwhich could withstand high tensile load to be used mainly for overheadtransmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of steel and the outer layer or layers ofaluminum.
StandardsConforms to BS 215 : part 2/1970
CodeWord
Equiv.Area
(HDCC)(mm2) Al St Al St Total Al St Total N kgf ( /km, 20 ) Temperate Tropical
Stranding and Wire Dia.
(mm)
OverallDia.
(mm)
Area
(mm2)
Weight
(kg/km)
NominalBreaking Load
Rating(amps)
Max. D.C.Resistance
NominalAl
Area(mm2)
MoleSquirrelGopherWeaselFoxFerretRabbitMinkSkunkBeavorHorseRaccoonOtterCatHareDogHyenaLeopardCoyoteCougarTigerWolfDingoLynxCaracalJaguarPantherLionBearBatangGoatSheepAntelopeBisonDeerZebraElkCamelMoose
--
2530
-4050
---
70----
100-----
150150175175200200
-250
-300
----
400---
6.512.916.119.422.625.832.338.738.745.245.248.451.658.164.564.564.580.780.780.780.796.897.9
113.0113.7130129145161194194226226226258258290290323
6/1.506/2.116/2.366/2.596/2.796/3.006/3.356/3.66
12/2.596/3.99
12/2.796/4.106/4.226/4.506/4.726/4.72 7/4.396/5.28
26/2.5418/3.0530/2.3630/2.5918/3.3530/2.7918/3.6118/3.8630/3.0030/3.1830/3.3518/4.7830/3.7130/3.9954/2.9754/3.0030/4.2754/3.1830/4.5054/3.3554/3.53
1/1.501/2.111/2.361/2.591/2.791/3.001/3.351/3.667/2.591/3.997/2.791/4.101/4.221/4.501/4.727/1.577/1.937/1.757/1.911/3.057/2.367/2.591/3.357/2.791/3.611/3.867/3.007/3.187/3.357/1.687/3.717/3.997/2.977/3.007/4.277/3.187/4.507/3.357/3.53
4.506.337.087.778.379.00
10.0510.9812.9511.9713.9512.3012.6613.5014.1614.1514.5715.8115.8915.2516.5218.1316.7519.5318.0519.3021.0022.2623.4524.1625.9727.9326.7327.0029.8928.6231.5030.1531.77
10.6220.9426.2431.6136.6642.4152.8863.1863.4874.8273.3779.2083.8895.40
105.0105.0105.8131.3132.1130.3131.1158.0158.7183.4184.3210.6212.0238.5264.0323.0324.3374.1373.1381.8429.3428.9477.0475.2528.7
1.773.494.375.276.117.078.81
10.5337.0312.4742.8013.2013.9815.9017.5013.5020.4418.8020.097.24
30.5936.888.80
42.7710.2411.6949.4955.6561.6015.5275.6787.2948.3749.49
100.2055.59
111.3061.6068.53
12.3924.4330.6236.8842.7749.4861.7073.71
100.5087.29116.20
92.4097.86
111.30122.50118.5126.2148.1152.2137.5161.7194.9167.5226.2194.5222.3261.5294.2325.6338.52400.0461.4421.5431.3529.5484.5588.3536.8597.2
29587287
101117145173175205203217230262288288290360365362362437437507507580586659730888896
1,0341,0321,0561,1861,1861,3181,3141,462
1427344148556982
29097
33510310912413710616013215726724028069
3358191
388436483121593684379388785435872483537
4385
106128149172214255465302538320339386425394450492522419602726506842588671974
1,0951,2131,0091,4891,7181,4111,4441,9711,6212,1901,7971,999
4,1007,9009,610
11,45013,20015,20018,35021,80053,10025,70061,20027,20028,70032,70036,00032,70040,90040,70046,40029,80058,00069,20035,70079,80041,00046,55092,250
100,600111,100
70,900135,700155,900118,200120,900178,500131,900198,200145,700161,100
418806980
1,1681,3461,5501,8712,2235,4152,6216,2412,7742,9273,3353,6713,3354,1714,1504,7323,0395,9147,0563,6408,1374,1814,7479,407
10,25811,329
7,24013,83815,89712,05312,32818,20213,45020,21114,85716,428
2.7021.3701.0930.90770.78270.67660.54260.45410.45650.38340.39360.36230.34210.30080.27330.27330.27120.21850.21870.22100.22040.18280.18150.15760.15630.136700.13630.12120.10950.08940.089100.077240.077470.075710.067310.067400.060580.060830.05468
67109126134147161185174246193268231240248273278287316311314323355349386383415421448481510542592588595639635679677763
556977849398
112103139110148131137145151153155167164168164162179178205197191195198165200197208208186202165192176
(Table 61)
Galvanized steel
Aluminum conductor
49TAIHAN Overhead Electrical Aluminum Conductors
Aluminum Conductors, Steel ReinforcedACSR
Notes : These values are given for information purpose only.1 hbar = 10 MN/m2 = 10 N/mm2
Aluminum Wires Used in the Construction of Standard AluminumConductors, Steel-reinforced
No. of Wires in Conductor(No.)
Al St Al
Mass ElectricalResistanceSt
Practical (final) Modulus of Elasticity
(hbar)
Coefficientof Linear
(Expansion/ )
Stranding Constants
66
12183054
177177
6.0916.091
12.2618.3430.6755.23
1.0007.0327.0321.0007.0327.032
0.16920.16920.085140.056600.034080.01894
7,9007,500
10,5006,6008,0006,900
19.1 10-6
19.8 10-6
15.3 10-6
21.2 10-6
17.8 10-6
19.3 10-6
Note : The values in column 2 to 5 are given for information only.BS 4565. “Galvanized steel wire for aluminum conductors, steel-reinforced.”
1 2 3 4 5
StandardDia.
(mm)
Cross Sectional Area ofStandard Dia. Wire
(mm2)
Mass
(kg/km)
StandardResistance
( /km,20 )
Min. Breaking Load forStandard Dia. Wire
(N)
2.362.592.793.003.183.353.613.864.72
4.3745.2696.1147.0697.9428.81410.2411.4017.50
11.8214.2416.5319.1121.4723.8227.6731.6347.30
6.4615.3654.6233.9993.5593.2072.7612.4151.615
770906
1,0301,1901,3101,4501,6601,8702,780
Steel Wires Used in the Construction of Standard Aluminum Conductors,Steel-reinforced
Note : The values in column 2 to 4 are given for information only.
1 2 3 4
StandardDia.
(mm)
Cross Sectional Area ofStandard Dia. Wire
(mm2)
Mass
(kg/km)
Min. Load at 1% Elongation forStandard Dia. Wire
(N)
1.572.362.592.793.003.183.353.613.86
1.9364.3745.2696.4147.0697.9428.814
10.2411.70
15.1034.1241.0947.6955.1361.9568.7579.8491.28
2,2804,9906,0106,5708,0608,7409,700
11,26012,870
50 Overhead Electrical Aluminum Conductors TAIHAN
Stranded All-aluminum ConductorsAAC
ASTM
ANSI
IEC
BS
AS
CSA
DIN
KSJI
SKE
PCO
TEC
ApplicationThis standard covers stranded hard-drawn circular aluminumconductors to be used mainly for overhead distribution wires, overheadfeeder.
ConstructionStranded hard-drawn aluminum conductors
StandardsConforms to AS 1531/1991
Notes : 1. The sectional area is the sum of the cross sectional areas of the relevant individual wires.2. For the basis of calculation of columns 4, 5, 6 and 7, see (AS 1531) Appendix A.
CodeWord
Stranding &Wire Dia.
(mm)
ApproxOverall Dia.
(mm)
SectionalArea
(mm2)
CalculatedEquivalent
Al Area(mm2)
Approx.Mass
(kg/km)
Min. CalculatedBreaking Load
(kN)
Calculated D.C.Resistance
( /km, 20 )
1 2 3 4 5 6 7
LeoLeonidsLibraMarsMercuryMoonNeptuneOrionPlutoSaturnSiriusTaurusTritonUranusUrsulaVenus
7/2.507/2.757/3.007/3.757/4.507/4.75
19/3.2519/3.5019/3.7537/3.0037/3.2519/4.7537/3.7561/3.2561/3.5061/3.75
7.508.259.00
11.313.514.316.317.518.821.022.823.826.329.331.533.8
34.3641.5849.4877.28
111.3124.0157.6182.8209.8261.6307.0336.7408.5506.1586.9673.4
33.941.148.976.3
110122154180206256301331400495574659
94.3113135211304339433503576721845924
1,1201,4001,6201,860
5.716.727.98
11.816.918.924.728.731.942.248.251.362.275.287.397.2
0.8330.6890.5790.3700.2580.2320.1830.1570.1370.1100.0940.08570.07060.05720.04930.0493
(Table 62)
51TAIHAN Overhead Electrical Aluminum Conductors
Aluminum Conductors, Galvanized Steel Reinforced (AS 3607/1989)ACSR/GZ
Notes : 1. The sectional area is the sum of the cross sectional areas of the relevant individual wires.2. For the basis of calculation of columns 5, 6, 7 and 8, see (AS 3607) Appendix A.
CodeWord
Al Galvanized St
Stranding and Wire Dia.(mm)
Approx.Overall Dia.
(mm)
SectionalArea
(mm2)
CalculatedEquiv. Al Area
(mm2)
Approx.Mass
(kg/km)
Min. CalculatedBreaking Load
(kN)
Calculated D.C.Resistance
( /km, 20 )
1 2 3 4 5 6 7 8
AlmondApricotAppleBananaCherryGrapeLemonLycheeLimeMangoOrangeOlivePaw Paw
6/2.506/2.756/3.006/3.756/4.75
30/2.5030/3.0030/3.2530/3.5054/3.0054/3.2554/3.5054/3.75
1/2.501/2.751/3.001/3.757/1.607/2.507/3.007/3.257/3.507/3.007/3.257/3.50
19/2.25
7.508.39.00
11.314.317.521.022.824.527.029.331.533.8
34.3641.5849.4877.31
120.4181.6261.5306.9356.0431.2506.0586.9672.0
29.035.141.865.2
105144207243282373438508583
119144171268402677973
1,1401,3201,4401,6901,9602,240
10.512.614.922.733.463.590.4
105122119137159178
0.9750.8050.6770.4330.2710.1960.1360.1160.1000.07580.06460.05570.0485
(Table 63)
Standard High Strength ConductorsQuinceRaisinSultanaWalnut
3/1.753/2.504/3.004/3.75
4/1.754/2.503/3.003/3.75
5.37.509.00
11.3
16.8434.3649.4877.31
8.7417.831.549.2
95195243380
12.724.428.343.9
3.251.590.8970.573
Aluminum Conductors, Aluminized Steel Reinforced (AS 3607/1989)ACSR/AZ
Notes : 1. The sectional area is the sum of the cross sectional areas of the relevant individual wires.2. For the basis of calculation of columns 5, 6, 7 and 8, see (AS 3607) Appendix A.
CodeWord
Al Galvanized St
Stranding and Wire Dia.(mm)
Approx.Overall Dia.
(mm)
SectionalArea
(mm2)
CalculatedEquiv. Al Area
(mm2)
Approx.Mass
(kg/km)
Min. CalculatedBreaking Load
(kN)
Calculated D.C.Resistance
( /km, 20 )
1 2 3 4 5 6 7 8
BarleyBeanCabbageCarrot
6/2.506/3.006/3.756/4.75
1/2.501/3.001/3.757/1.60
7.509.00
11.314.3
34.3649.4877.31
120.4
29.041.865.2
105
118170265399
10.214.521.432.0
0.9750.6770.4330.271
(Table 64)
52 Overhead Electrical Aluminum Conductors TAIHAN
Aluminum Conductors, Steel Reinforced ACSR
ASTM
ANSI
IEC
BS
AS
CSA
DIN
KSJI
SKE
PCO
TEC
ApplicationThis standard covers aluminum stranded conductors steel reinforcedwhich could withstand high tensile load to be used mainly for overheadtransmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of galvanized steel and the outer layer orlayers of aluminum.
StandardsConforms to CSA C49.1
Conductor type means the ratio of steel to aluminum areas in percent.
CodeWord
Al
Al Al St TotalStSt
CoreCompleteConductor
AWGor
CMILS
St CompleteConductor
sq insq in sq in No. Dia. No. Dia. (pound)
( /1000ft,20 )
Nominal Area Stranding No. and Nominal Dia. of Wires
(in)
Nominal Dia.(in)
Nominal Weight(pound/1000ft)
RatedTensile
Strength
D.C.ResistanceCon-
ductorType
WrenTurkeySwanSparrowRobinRavenQuailPigeonPenguinOwlWaxwingPartridgePhoebeOstrichPiperMerlinLinnetOrioleChickadeeIbisLarkPelicanToucanHawkHenHeronSapsuckerDoveEagle-DuckGoldfinchGrosbeakEgret
17171717171717171713
616
61623
61623
61623
6101623231016231013101623
86421
1/03/03/04/0
266,800266,800266,800300,000300,000300,000336,400336,400336,400397,500397,500397,500477,000477,000477,000477,000500,000556,500556,500556,500605,000605,000636,000636,000636,000
0.01300.02060.03280.05210.06570.08290.10450.13180.16620.20950.20950.20950.23560.23560.23560.26420.26420.26420.31220.31220.31220.37460.37460.37460.37460.39270.43710.43710.43710.47520.47520.49950.49950.4995
0.00220.00340.00550.00870.01100.01380.01740.02200.02770.02720.01150.03410.01310.03830.05500.01470.04310.06170.01730.05080.07280.02080.03680.06110.08740.09160.04290.07120.10200.04660.06170.04900.08130.1140
0.01520.02400.03830.06080.07670.09670.12190.15380.19390.23670.221002436
0.24870.27390.29060.278903073
0.32590.32950.36300.38500.39540.41140.43570.46200.48430.48000.50830.53910.52180.53690.54850.58080.6133
0.05250.06610.08340.10520.11810.13270.14890.16720.18780.21090.12170.10130.12910.10740.10000.13670.11370.10590.14860.12360.11510.16280.14720.13540.12610.12910.15900.14630.13620.16580.10580.17000.15640.1456
0.05250.06610.08340.10520.11810.13270.14890.16720.18780.07030.12170.07880.12910.08350.10000.13670.08840.10590.14860.09610.11510.16280.08180.10530.12610.12910.08830.11380.13620.09210.10580.09440.12160.0874
0.05250.06610.08340.10520.11810.13270.14890.16720.18780.21090.12170.23640.12910.25050.30000.13670.26520.31770.14860.28830.34530.16280.24540.31590.37830.38730.26490.34140.40860.27630.31740.28320.36480.4370
0.1580.1980.2500.3160.3540.3980.4470.5020.5630.6330.6090.6420.6460.6800.7000.6840.7200.7410.7430.7830.8060.8140.8340.8580.8830.9040.9010.9270.9530.9400.9520.9630.9901.019
7451,1701,8302,7903,4804,2905,3506,5708,4209,5407,100
11,3007,980
12,60015,400
8,95014,00017,00010,40016,20020,00012,30015,40019,40023,40024,50017,80022,50027,20019,10022,50020,10025,00031,600
1.04520.65770.41340.26010.20620.16340.12970.10280.08160.06470.06490.06510.05770.05790.05790.05150.05160.05170.04360.04370.04370.03630.03640.03640.03640.03480.03120.03120.03120.02870.02870.02730.02730.0273
15.4 24.539.062.078.198.6
124.3156.7197.6249250251281282282315316316373373374447448448448470522523523568569597597598
7.311.618.429.337.046.658.874.193.49239
11644
13018650
1462095817224770
125207296310145241345158209166275387
22.736.157.491.3115.1145.2183.1230.8291.0
341289367325412468365462525431545621517573655744780667764868726778763872985
6666666666
182618263018263018263018222630302226302254222630
111111111717177177177177777777777
19
(Table 65)
Galvanized steel
Aluminum conductor
53TAIHAN Overhead Electrical Aluminum Conductors
Aluminum Conductors, Steel Reinforced ACSR
Conductor type means the ratio of steel to aluminum areas in percent.
CodeWord
Al
Al Al St TotalStSt
CoreCompleteConductor
AWGor
CMILS
St CompleteConductor
sq insq in sq in No. Dia. No. Dia. (pound)
( /1000ft,20 )
Nominal Area Stranding No. and Nominal Dia. of Wires
(in)
Nominal Dia.(in)
Nominal Weight(pound/1000ft)
RatedTensile
Strength
D.C.Resistance
Con-ductorType
GooseGull-StarlingRedwing-CrowDrakeMallardMacawCondor-Crane-CanaryPhoenixCardinalSnowbirdCurlewBeaumontFinch-GrackleScissortailPheasant-Martin-Plover-Parrot-Falcon-
135
13162313131623
513
513
513
513
513
513
513
513
513
513
513
913
4
636,000666,600666,600715,500715,500715,500715,500795,000795,000795,000795,000874,500874,500900,000900,000954,000954,000
1,033,5001,033,5001,113,0001,113,0001,192,5001,192,5001,272,0001,272,0001,351,5001,351,5001,431,0001,431,0001,510,5001,510,5001,590,0001,590,0001,590,000
0.49950.52350.52350.56200.56200.56200.56200.62440.62440.62440.62440.68680.68680.70690.70690.74930.74930.81170.81170.87410.87410.93660.93660.99900.99901.06151.06151.12391.12391.18631.18631.24881.24881.2488
0.06470.02690.06790.09150.12800.02890.07280.10170.14240.03210.08090.03540.08910.03630.09160.03850.09710.04180.10520.04490.11090.04820.11870.05140.12660.05460.13440.05790.14240.06100.15010.11020.15830.0540
0.56420.55040.59140.65350.69000.59090.63480.72610.76680.65650.70530.72220.77590.74320.79850.78780.84640.85350.91690.91900.98500.94841.05531.05041.12561.11611.19591.18181.26631.24731.33641.35901.40711.3028
0.10850.12600.11110.16590.15440.13050.11510.17490.16280.13760.12130.14430.12730.14640.12910.15070.13290.15690.13830.16280.14360.16850.14860.17400.15350.17940.15820.18460.16280.18960.16720.18200.17160.1486
0.10850.07000.11110.12900.09260.07250.11510.13600.09770.07640.12130.08020.12730.08130.12910.08370.13290.08720.13830.09040.08620.09360.08920.09670.09210.09970.09490.10260.09770.10530.10030.14160.10300.0991
0.32550.21000.33330.38700.46300.21750.34530.40800.48850.22920.36390.24060.38190.24390.38730.25110.39870.26160.41490.27120.43100.28080.44600.2901046050.29910.47450.30780.48850.31590.50150.42480.51500.2973
0.9770.9661.0001.0511.0811.0011.0361.1081.1401.0551.0921.1061.1461.1221.1621.1551.1961.2031.2451.2481.2931.2921.3381.3341.3821.3761.4241.4151.4651.4541.5051.5171.5451.486
23,70017,70024,50028,10034,60019,00026,30031,30038,50021,10028,50022,80031,40023,50032,30024,50034,30026,60037,10028,40040,30030,40043,10032,50044,90034,50047,60036,50050,50038,50053,20047,60056,10039,500
0.02730.02610.02610.02430.02430.02430.02430.02180.02190.02190.02190.01990.01990.01930.01930.01820.01820.01680.01680.01560.01560.01460.01460.01370.01370.01290.01290.01210.01220.01150.01150.01090.01090.0109
599627627672673673673747747747748822823846847897898972973
1,0461,0481,1211,1221,1961,1971,2711,2721,3451,3471,4201,4221,4951,4961,496
21991
23031043498
247344484109274120302123310130329141356152376163403174430185456196484206511372537183
818718857982
1,107771920
1,0911,231
8561,022
9421,125
9691,1571,0271,2271,1131,3281,1981,4241,2841,5251,3701,6271,4561,7281,5411,8311,6261,9331,8672,0331,679
54425426304242263042544254425442544254425442544254425442544254485472
7777
19777
1977777777777
197
197
197
197
197
197
197
(Table 65)
54 Overhead Electrical Aluminum Conductors TAIHAN
Compact Aluminum Conductors Steel Reinforced (CSA C49.2)
ASTM
ANSI
IEC
BS
AS
CSA
DIN
KSJI
SKE
PCO
TEC
Conductor type means the ratio of steel to aluminum areas in percent.
CodeWord
Con-ductorType
AWGor
CMILSsq in
St
(sq in)
CompleteConductor
(sq in)
AlNominal Area Nominal Dia.
(in)
Nominal Weight
(pound/1000ft)
RatedTensile
Strength
(pound)
D.C.Resistance
( /1000ft,20 )
No. of Al
Wires St Wire Al St TotalConductor
CodMinnowSardineBassMulletHerringPikePollockFlounderCarpHaddockPickerelShadLampreySoleSculpinHakeCuskScup--
1734531734531734531734531734173417171766
88866644422211
1/01/02/03/04/0
266,800336,400
0.01300.01300.01300.02060.02060.02060.03280.03280.03280.05210.05210.05210.06570.06570.08290.08290.10450.13180.16620.20950.2642
0.00220.00430.00690.00340.00690.01100.00550.01100.01740.00870.01740.02770.01100.02200.01380.02770.01740.02200.02770.01150.0147
0.01520.01730.01990.02400.02750.03160.03830.04380.05020.06080.06950.07980.07670.08770.09670.11060.12190.15380.19390.22100.2789
6666666666666666666
1818
0.05250.07430.09370.06610.09370.11820.08340.11820.14900.10520.14900.18780.11820.16720.13270.18780.14900.16720.18780.12170.1367
0.1450.1540.1650.1820.1930.2080.2290.2430.2640.2900.3080.3310.3260.3460.3650.3880.4100.4610.5170.5590.628
7451,1101,5101,1701,7202,4001,8302,7103,6902,7904,1505,7903,4805,1904,2906,5105,3506,6708,4207,1008,950
1.04521.04521.04520.65770.65770.65770.41340.41340.41340.26010.26010.26010.20620.20620.16340.16340.12970.10280.08160.06470.0515
15.415.415.424.524.524.539.039.039.062.062.062.078.178.198.698.6
124.3156.7197.6
250315
7.314.623.311.623.337.018.437.058.829.358.893.437.074.146.693.458.874.193.4
3950
22.730.038.736.147.861.557.476.097.891.3
120.8155.4115.1152.2145.2192.0183.1230.8291.0
289365
(Table 66)
55TAIHAN Overhead Electrical Aluminum Conductors
Stranded All-aluminum ConductorAAC
ApplicationThis standard covers stranded hard-drawn circular aluminumconductors to be used mainly for overhead distribution wire, overheadfeeder.
ConstructionStranded hard-drawn aluminum conductors
StandardsConforms to DIN 48201
Area
(mm2)
EquivalentArea (HDCC)
Strandingand
Wires Dia.
OverallDia.
Weight NominalBreaking
Load
Max. D.C.Resistance
Rating
(amps)
Nominal Actual (mm2) (mm) (mm) (kg/km) (kp) ( /km, 20 ) Temperate Tropical16253550507095
120150185240300400500625800
1,000
15.8924.2534.3649.4848.3665.8293.27
117.00147.10181.60242.5299.4400.1499.8626.2802.4999.7
101521313041607090
110150155245305385490615
7/1.77/2.17/2.57/3.0
19/1.819/2.1019/2.5019/2.8037/2.2537/2.5061/2.2561/2.5061/2.8961/3.2391/2.9691/3.3591/3.74
5.16.37.59.09.0
10.512.514.015.717.520.222.526.029.132.836.841.1
446794
135133181256322408501670827
1,1051,3811,7332,2192,766
290425585810860
1,1501,5951,9102,5703,1054,0154,8506,1907,6009,690
12,05514,845
1.80171.18060.83320.57860.59480.43700.30840.24590.19600.15880.11920.096510.072220.057820.046250.036110.02897
87112138172172206254291333379448509602689785904
1,027
597489
107107124146160176191207217222211176
52-
(Table 67)
56 Overhead Electrical Aluminum Conductors TAIHAN
Aluminum Conductors, Steel ReinforcedACSR
ASTM
ANSI
IEC
BS
AS
CSA
DIN
KSJI
SKE
PCO
TEC
ApplicationThis standard covers aluminum stranded conductors steel reinforcedwhich could withstand high tensile load to be used mainly for overheadtransmission lines, overhead distribution lines.
ConstructionThe center wire or wires are of steel and the outer layer or layers ofaluminum.
StandardsConforms to DIN 48204
Area (mm2)
Equiv.Area
(HDCC)
Stranding and Wires Dia.
(mm)
OverallDia.
Weight
(kg/km)
NominalBreaking
Load
Max. D.C.Resistance
Rating
(amps)NominalAl St Total
St (mm2)Al Al Al St Total Temperate Tropical(kp)( /km,20 )St (mm)
162535445050709595
105120120125150170185210210230240265300305340380385435450490550560680
2.54.06.0
32.08.0
301215557520703025403035503040355040305035554065705085
15.323.834.344.048.351.269.994.496.5
105.7121.6122.0127.9148.9171.8183.8209.1212.1230.9243.0263.7304.3304.6339.3382.0386.0434.3448.7490.3550.0561.7678.8
2.64.05.7
31.78.0
29.811.415.356.375.519.871.329.824.240.129.834.149.529.839.534.149.539.529.849.534.156.339.563.671.349.586.0
17.927.840.075.756.381.081.3
109.7152.8181.5141.4193.3157.7173.1211.9213.6243.2261.6260.7282.5297.8353.7344.1369.1431.5420.1490.6488.2553.9621.3611.2764.8
9.617.521.627.730.432.244.059.460.866.576.576.780.493.6
108.0116132133145153166191192213240243273282308346353427
6/1.806/2.256/2.70
14/2.006/3.20
12/2.3326/1.8526/2.1512/3.2014/3.1026/2.4412/3.6030/2.3326/2.7030/2.7026/3.0026/3.2030/3.0024/3.5026/3.4524/3.7426/3.8654/2.6848/3.0054/3.0048/3.2054/3.2048/3.4554/3.4054/3.6048/3.8654/4.00
1/1.801/2.251/2.707/2.401/3.207/2.337/1.447/1.677/3.20
19/2.257/1.907/3.607/2.337/2.107/2.707/2.337/2.497/3.007/2.337/2.687/2.497/3.007/2.687/2.337/3.007/2.497/3.207/2.687/3.407/3.607/3.00
19/2.40
5.46.88.1
11.29.6
11.711.713.616.017.515.518.016.117.118.919.020.321.021.021.922.424.524.125.027.026.728.828.730.632.432.236.0
426594
122132141193260266292336337353411475507577587638671728840843938
1,0561,0671,2031,2411,3561,5201,5531,868
203246
25064
23791
123446599158564238194319239273394239316274396317242397277450320510572401702
6297
140372196378284383712891494901591605794746850981877987
1,0021,2361,1601,1801,4581,3441,6531,5611,8662,0921,9542,570
595920
1,2654,5001,7104,3802,6803,5757,935
10,8454,565
10,0005,7605,5257,6756,6207,4909,3907,3108,6408,305
10,7009,9409,290
12,31010,48013,64512,07515,31017,06014,89521,040
85114140170172187217260271289304359309341373386418423442457477521520553594597641650687734742830
587489
10010510912714514214516115416117317918519319019919920420520821320721120020518916817380
1.87931.20280.83530.65730.59460.56440.41300.30580.29920.27360.2374023640.22590.19390.16820.15710.13800.13630.12490.11880.10940.09490.09490.08510.07570.07480.06660.06440.05900.05260.051400.0426
(Table 68)
Galvanized steel
Aluminum conductor
57TAIHAN Overhead Electrical Aluminum Conductors
ReelDesignation
(D) (d) (W1) (W2) (h) (t) (in) (No.) (ft3) (lb)
Flange Dia.
Drum Dia.
OverallWidth
InsideTraverse
ArborHole Dia.
Thickness ofCircumference
Battens
No. of Bolt
Measurement Approx.Weight
Dia. of Bolt
3-13-23-33-43-54-14-24-34-44-54-64-75-15-25-35-45-55-66-16-26-36-46-56-67-17-27-37-47-58-18-28-38-48-58-69-19-29-39-49-59-69-79-8
20.521.722.824.025.224.025.226.427.628.729.931.126.427.628.729.931.132.332.333.534.635.837.038.235.837.038.239.441.337.038.239.441.343.345.343.345.347.245.347.249.251.253.2
11.811.811.811.811.813.813.813.813.813.813.813.815.715.715.715.715.715.717.717.717.717.717.717.719.719.719.719.719.723.623.623.623.623.623.623.623.623.627.627.627.627.627.6
15.715.715.715.715.715.715.715.715.715.715.715.719.719.719.719.719.719.719.719.719.719.719.719.723.623.623.623.623.623.623.623.623.623.623.629.529.529.529.529.529.529.529.5
12.912.912.912.912.912.912.912.912.912.912.912.915.915.915.715.715.715.715.715.715.715.715.715.719.719.719.719.719.719.719.719.719.719.719.724.824.824.824.824.824.824.824.8
2.02.02.02.02.02.02.02.02.02.02.02.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.03.04.34.34.34.34.34.34.34.3
1.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.21.41.41.41.41.41.41.41.41.41.41.41.41.41.41.41.41.41.41.4
0.50.50.50.50.50.50.50.50.50.50.50.50.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.6
4444444444444444444444444444444444444444444
5.15.66.26.87.46.87.48.18.79.4
10.310.910.010.811.712.613.514.514.515.516.617.618.719.921.422.724.225.528.022.724.225.528.030.533.137.741.144.441.144.448.351.755.6
64.066.070.575.079.481.683.888.290.494.8
101.4105.8119.0125.7132.3136.7143.3149.9152.1160.9167.5176.4183.0191.8211.6218.3227.1235.9251.3222.7231.5240.3253.5271.2286.6339.5361.6381.4374.8394.6416.7436.5467.4
(Approx. in inch)Standard Dimensions of Reel for Aluminum Conductor
Packing and Marking
The packing of the conductor is an intergral part of the manufacturing process, and the kind of package must be predetermined beforeproduction can begin.Unless otherwise specified or agreed with in case of order, ACSR shall be shipped on Taihan standard wooden reels having dimensions andweights as given in the table shown below.Taihan standard wooden reels shall have enough condition to stand against the ordinary handling in transportation and shipping and be foundready and handy enough at the time of installation in site. Especially, in case that users require the metal reel, we can serve our standard metalreels which have the same capacity as that of the wooden reel or special designed metal reels.The reels will be stenciled legibly with following information; serial number, size and kind of conductor, length of conductor, and any otherindentification marks specified on the order by the purchaser.
58 Overhead Electrical Aluminum Conductors TAIHAN
ReelDesignation
(D) (d) (W1) (W2) (h) (t) (in) (No.) (ft3) (lb)
Flange Dia.
Drum Dia.
OverallWidth
InsideTraverse
ArborHole Dia.
Thickness ofCircumference
Battens
No. of Bolt
Measurement Approx.Weight
Dia. of Bolt
10-110-210-310-410-510-611-111-211-311-411-512-112-212-312-412-513-113-213-313-413-513-613-714-114-214-314-414-514-614-715-115-215-315-416-116-216-316-417-117-217-317-417-517-618-118-218-318-4
49.251.253.255.157.159.155.157.159.161.063.155.157.159.161.063.059.161.063.065.066.968.970.966.968.970.972.874.876.878.774.876.878.782.778.382.786.690.682.786.690.694.598.4
102.490.694.598.4
102.4
31.531.531.531.531.531.531.531.531.531.531.535.435.435.435.435.439.439.439.439.439.439.439.447.247.247.247.247.247.247.255.155.155.1551
55.155.155.155.162.862.862.962.962.962.970.970.970.970.9
29.529.529.529.529.529.535.435.435.435.435.435.435.435.435.435.435.435.435.435.435.435.435.441.341.341.341.341.341.341.341.341.341.341.347.247.247.247.247.247.247.247.247.247.247.247.247.247.2
24.824.824.824.824.824.829.529.529.529.529.529.529.529.529.529.529.529.529.529.529.529.529.534.334.334.334.334.334.334.334.334.334.334.340.240.240.240.240.240.240.240.240.240.240.240.240.240.2
4.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.34.3
1.41.41.41.41.41.41.41.41.41.41.41.41.41.41.41.41.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.81.8
0.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.60.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.70.7
444444555555555555555556666666666688888888888888
48.2 51.855.659.663.668.171.175.881.086.194.671.175.881.086.192.083.188.493.899.5105111117123130137144152160168152160168184191209228250209229249271293316249271293316
445.3465.2487.2509.3533.5557.8615.5650.4681.2709.9743.0643.7672.4701.1731.9765.0784.8820.1851.0888.5921.5956.8994.3
1,170.61,210.31,258.81,322.81,342.61,391.11,435.21,404.31,459.41,503.51,627.01,607.21,706.41,805.61,913.61,882.71,935.61,995.22,105.42,220.02,341.32,079.02,191.42,306.02,427.3
(Approx. in inch)Standard Dimensions of Reel for Aluminum Conductor
Dimensions of Wooden Reels
���������������
������������
yyyyyyyyyyyy
�����
���
yyy�
��
yyy���
Barrel lagging
W1W1W2W2
tt
Ddh
Center supportBarrel Bolts & Washer
Reinforcement
Circumference Battens
59TAIHAN Overhead Electrical Aluminum Conductors
ItemAluminum Copper
Hard-drawn Al-alloy Hard-drawnAnnealedStandard
Melting Point, Electrical Resistivity at 20 , in
cmConductivity at 20 , % IACSTemperature Coefficient of Resistanace at 20 , per Density at 20 , g/cub, cm
lb/cub, inCoefficient of Linear Expansion per Weight Ratio, Same VolumeResistance Ratio, Same Size
Resistance Ratio, Same Length and Same WeightTensile Strength RatioFor Same Length and Resistance, Cross Sectional Area
DiameterWeightBreaking Strength
6581.112772.8264
610.00402.700.09765
23 10-6
30.371163.93159.01
48.29Approx. 40159.01126.12
48.295Approx. 60
Approx. 6501.305363.3156
520.00362.700.09765
23 10-6
30.371192.30186.54
56.65Approx. 73185.54136.58
56.653Approx. 135
1.0830.699781.7774
970.003818.890.321
17 10-6
100103.09100100100100100100100
1.0830.678791.7241
1000.003938.890.321
17 10-6
100100
Comparison of Aluminum and Copper
Conversion Factors
1in= 25.4mm, 1cmil = 5.067 10-4mm2, 1mil = 2.54 10-2mm, 1 lb/1000ft = 1.488kg/km,1ft = 3.048 10-1m, 1 lb =4.536 10-1kg, 1in3 = 1.639 10-5m3
The metric unit of force in SI(System International) units is the newton. (N), which is defined as that force which, when applied to a body havinga mass of 1kg, gives it an acceleration of 1m/s2.
The derived SI unit for pressure or stress is the newton per square meter(N/m2), which has been named the pascal(Pa) by the GeneralConference of Weights and Measures. Since 1ksi=6894757Pa the metric equivalents are expressed as megapascal(MPa), which is the same asMn/m2 and N/mm2.
1ksi = 103psi 1kgf/mm2 = 1.42ksi1psi = 6.9KPa 1ksi = 0.704kgf/mm2
1ksi = 6.9MPa kgf = 9.80665 newtons(N)
60 Overhead Electrical Aluminum Conductors TAIHAN
Code Word Table No. Page No.AAcorn 38
Akron 34
Alliance 34
Almond 38, 41, 63
Alton 34
Ames 34
Amherst 34
Anaheim 34
Anemone 28
Anona 37, 40
Ant 60
Antelope 61
Aphis 60
Appaloosa 53
Appaloosa/XLPE 55
Apple 37, 39, 63
Apple/XLPE 42
Apricot 37, 40, 63
Apricot/XLPE 43
Arbutus 28
Ash 37
Aspen 38
Aster 28
Azusa 34
BBanana 63
Barley 64
Bass 66
Basswood 37
Batang 61
Bean 64
Bear 61
Beaumont 65
Beavor 61
Bee 60
Beech 38, 41
Beetle 60
Bison 61
Bittern 29
Bitterroot 28
Bluebell 28
Bluebird 29
Bluebonnet 28
Bluebottle 60
Bluejay 29
Bobolink 29
Brahma 35, 36
Brant 29
Breadfruit 37, 41
Buckeye 38, 41
Bull 45
Bull/XLPE 47
Bunting 29
36
33
33
36, 37, 52
33
33
33
33
25
35, 37
48
49
48
40
40
35, 37, 52
37
35, 37, 52
37
25
35
36
24
33
52
52
55
35
49
52
49
54
49
48
36, 37
48
49
27
25
25
27
25
48
27
27
34
26
35, 37
36, 37
38
38
27
Alphabetical List
Code Word Table No. Page No.Butte 34
Butterfly 60
Butternut 38, 41
CCabbage 64
Cairo 34
Camel 61
Camellia 28
Canary 29, 65
Canna 28
Canton 34
Caracal 61
Cardinal 29, 65
Carnation 28
Carp 66
Carrot 64
Cat 61
Catalpa 37
Catbird 29
Caterpillar 60
Cattail 28
Cenia 49
Cenia 51
Centipede 60
Chafer 60
Cherry 37, 39, 63
Cherry/XLPE 42
Chestnut 38, 41
Chickadee 29, 65
Chinquapin 37
Chokeberry 38
Chola 53
Chola/XLPE 55
Chow 45
Chow/XLPE 47
Chukar 29
Cicada 60
Clam 48
Clam/XLPE 50
Clegg 60
Clydesdale 52
Clydesdale/XLPE 54
Cochin 35, 36
Cockroach 60
Cockscomb 28
Cod 66
Collie 44
Collie/XLPE 46
Columbine 28
Conch 49
Conch/XLPE 51
Condor 29, 65
Coot 29
Coreopsis 28
33
48
36, 37
52
33
49
25
27, 54
24
33
49
27, 54
25
55
52
49
35
27
48
25
39
39
48
48
35, 37, 52
37
36, 37
26, 53
35
36
40
40
38
38
27
48
39
39
48
40
40
34
48
25
55
38
38
25
39
39
27, 54
27
25
Code Word Table No. Page No.Cosmos 28
Costena 53
Costena/XLPE 55
Cottonwood 38
Cougar 61
Cowslip 28
Coyote 61
Crabapple 37, 40
Crane 29, 65
Cricket 60
Criollo 52
Criollo/XLPE 54
Crocus 28
Crow 29, 65
Cuckoo 29
Cumquat 37
Curlew 29, 65
Cusk 66
DDachshund 44
Dachshund/XLPE 46
Daffodil 28
Dahlia 28
Daisy 28
Darien 34
Dear 61
Dingo 61
Dipper 29
Doberman 44
Doberman/XLPE 46
Dog 61
Dogwood 28
Dorking 35, 36
Dotterel 35, 36
Dove 29, 65
Drake 29, 65
Drone 60
Duck 65
EEagle 29, 65
Earwig 60
Egret 29, 65
Elk 61
Elgin 34
Eskimo 45
Eskimo/XLPE 47
FFalcon 29, 65
Ferret 61
Fig 37, 40
Fig/XLPE 43
Filbert 38, 41
Finch 29, 65
Flag 28
24
40
40
36
49
25
49
35, 37
27, 54
48
40
40
25
27, 54
27
35
27, 54
55
38
38
24
24
24
33
49
49
27
38
38
49
25
34
34
26, 53
27, 54
48
53
26, 53
48
27, 53
49
33
38
38
27, 54
49
35, 37
37
36, 37
27, 54
24
61TAIHAN Overhead Electrical Aluminum Conductors
Code Word Table No. Page No.Flamingo 29
Flicker 29
Flint 34
Flounder 66
Fly 60
Fox 61
Fusus 48
Fusus/XLPE 50
GGannet 29
Ginkgo 37
Gladiolus 28
Gnat 60
Goat 61
Goldenrod 28
Goldentuft 28
Goldfinch 65
Goose 65
Gopher 61
Grackle 29, 65
Grape 63
Grapefruit 37, 40
Grasshopper 60
Greely 34
Grosbeak 29, 65
Grouse 35, 36
Grullo 53
Grullo/XLPE 55
Guinea 35, 36
Gull 65
Gumwood 38
HHackberry 38, 41
Hackney 53
Hackney/XLPE 55
Haddock 66
Haiotis 48
Haiotis/XLPE 50
Hake 66
Hanoverian 52
Hanoverian/XLPE 54
Hare 61
Haw 37
Hawk 29, 65
Hawkweed 28
Hawthorn 28
Hazelnut 38
Hen 29, 65
Heron 65
Herring 66
Heuchera 28
Hickory 38, 41
Hornet 60
Horse 61
27
26
33
55
48
49
39
39
27
35
25
48
49
25
24
53
54
49
27, 54
52
35, 37
48
33
27, 53
34
40
40
34
54
36
36, 37
40
40
55
39
39
55
40
40
49
35
26, 53
25
25
36
26, 53
53
55
24
36, 37
48
49
Code Word Table No. Page No.Huckleberry 37, 40
Hyacinth 28
Hyena 61
IIbis 29, 65
Iris 28
Ironwood 37
JJaguar 61
Jessamine 28
Joree 29
KKingbird 29
Kiwi 29
LLamprey 66
Ladybird 60
Lapwing 29
Lark 29, 65
Larkspur 28
Laurel 28
Leghorn 35, 36
Lemon 37, 63
Leo 62
Leonids 62
Leopard 61
Libra 62
Lilac 28
Lily 28
Lime 63
Linnet 29, 65
Lion 61
Locust 60
Lupine 28
Lychee 63
Lynx 61
MMacaw 65
Magnolia 28
Malemute 44
Malemute/XLPE 46
Mallard 29, 65
Mango 37, 63
Marigold 28
Mars 62
Martin 29, 65
Maybug 60
Meadowsweet 28
Melita 48
Melita/XLPE 50
Mercury 62
Merlin 29, 65
Midge 60
Mink 61
35, 37
24
49
26, 53
24
35
49
25
27
27
27
55
48
27
26, 53
25
24
34
35, 52
51
51
49
51
25
24
52
26, 53
49
48
25
52
49
54
25
38
38
27, 54
35, 52
25
51
27, 54
48
24
39
39
51
26, 53
48
49
Code Word Table No. Page No.Minnow 66
Minorca 35, 36
Mistletoe 28
Mockernut 38
Mole 61
Molles 37, 40
Moon 62
Moose 61
Morgan 53
Morgan/XLPE 55
Morochuca 53
Morochuca/XLPE 55
Mosquito 60
Moth 60
Mulberry 37, 40
Mullet 66
Murex 48
Murex/XLPE 50
Mursia 49
Mursia/XLPE 51
Mustang 52
Mustang/XLPE 54
NNarcissus 28
Nassa 48
Nassa/XLPE 50
Nasturtium 28
Nectarine 37, 39
Nectarine/XLPE 43
Neptune 62
Neritina 49
Neritina/XLPE 51
Nuthatch 29
OOldenburg 52
Oldenburg/XLPE 54
Olive 37, 40, 63
Olive/XLPE 43
Orange 37, 40, 63
Orange/XLPE 43
Orchid 28
Oriole 29, 65
Orion 62
Ortolan 29
Osprey 29
Ostrich 29, 65
Otter 61
Owl 65
Oxlip 28
Oyster 48
Oyster/XLPE 50
PPalmino 53
Palmino/XLPE 55
55
34
24
36
49
35, 37
51
49
40
40
40
40
48
48
35, 37
55
39
39
39
39
40
40
25
39
39
25
35, 37
37
51
39
39
27
40
40
35, 37, 52
37
35, 37, 52
37
24
26, 53
51
27
26
26, 53
49
53
24
39
39
40
40
62 Overhead Electrical Aluminum Conductors TAIHAN
Code Word Table No. Page No.Paludina 49
Paludina/XLPE 51
Pansy 28
Panther 61
Parakeet 29
Parrot 29, 65
Partridge 29, 65
Paw Paw 37, 40, 63
Peach 37, 40
Peach/XLPE 43
Peachbell 28
Peacock 29
Pear 37, 39
Pear/XLPE 42
Pecan 38, 41
Pekingese 44
Pekingese/XLPE 46
Pelican 29, 65
Penguin 29, 65
Peony 28
Percheron 52
Percheron/XLPE 54
Periwinkle 49
Periwinkle/XLPE 51
Persimmon 37, 40
Petrel 35, 36
Petunia 28
Pheasant 29, 65
Phlox 28
Phoebe 65
Phoenix 65
Pickerel 66
Pigeon 29, 65
Pignut 38, 41
Pike 66
Pinto 52
Pinto/XLPE 54
Piper 65
Plover 29, 65
Plum 37, 40
Plum/XLPE 43
Pluto 62
Pollock 66
Pomegranate 37, 40
Pomegranate/XLPE 43
Poppy 28
Portunus 48
Portunus/XLPE 50
Purpura 48
Purpura/XLPE 50
QQuail 29, 65
Quince 37, 40, 63
Quince/XLPE 43
39
39
24
49
26
27, 54
26, 53
35, 37, 52
35, 37
37
24
26
35, 37
37
36, 37
38
38
26, 53
26, 53
24
40
40
39
39
35, 37
34
25
27, 54
24
53
54
55
26, 53
36, 37
55
40
40
53
27, 54
36, 37
37
51
55
35, 37
37
24
39
39
39
39
26, 53
35, 37, 52
37
Code Word Table No. Page No.RRabbit 61
Raccoon 61
Rail 29
Raisin 63
Raven 29, 65
Redbud 38
Redwing 29, 65
Robin 29, 65
Rook 29
Rose 28
Ruddy 29
Runcina 49
Runcina/XLPE 51
SSagebrush 28
Sapsucker 65
Sardine 66
Sassafras 37
Saturn 62
Scissrotail 65
Scorpion 60
Scoter 29
Sculpin 66
Scup 66
Setter 45
Setter/XLPE 47
Shad 66
Sheep 61
Shepherd 45
Shepherd/XLPE 47
Silverbelt 37
Sirius 62
Skunk 61
Snapdragon 28
Sneezewort 28
Snowbird 65
Sole 66
Spaniel 44
Spaniel/XLPE 46
Sparate 29
Sparrow 29, 65
Spider 60
Squab 29
Squirrel 61
Starling 29, 65
Stilt 29
Suffolk 53
Suffolk/XLPE 55
Sultana 63
Sumac 37
Swallow 29
Swan 29, 65
Swanate 29
49
49
27
52
26, 53
36
27, 54
26, 53
27
24
27
39
39
25
53
55
35
51
54
48
27
55
55
38
38
55
49
38
38
35
51
49
25
24
54
55
38
38
26
26, 53
48
26
49
27, 54
27
40
40
52
35
26
26, 53
26
Code Word Table No. Page No.Swift 29
Sycamore 37
Syringa 28
TTanager 29
Tangerine 37
Tarantula 60
Taurus 62
Teal 29
Tern 29
Terrier 45
Terrier/XLPE 47
Thrasher 29
Thrush 29
Tiger 61
Toucan 65
Trillium 28
Triton 49, 62
Triton/XLPE 51
Trophon 48
Trophon/XLPE 50
Tulip 28
Tupelo 37
Turkey 29, 65
UUranus 62
Ursula 62
VValerian 28
Venus 62
Verbena 28
Violet 28
Voluta 49
Voluta/XLPE 51
WWalnut 38, 41, 63
Wasp 60
Waxwing 29, 65
Weasel 61
Weevil 60
Whelk 49
Whelk/XLPE 51
Wolf 61
Wood Duck 29
Wren 65
ZZebra 61
Zinnia 28
Zuzara 49
Zuzara/XLPE 51
27
35
24
27
35
48
51
26
27
38
38
27
26
49
53
25
39, 51
39
39
39
24
35
26, 53
51
51
24
51
24
24
39
39
36, 37, 52
48
26, 53
49
48
39
39
49
26
53
49
24
39
39
63TAIHAN Overhead Electrical Aluminum Conductors
Head Office
Overseas Sales Team
Domestic Sales Team
Insong Building, 194-15, 1-ga, Hoehyeon-dong, Jung-gu, Seoul, Korea
Tel. 82-2-316-9114 Fax. 82-2-316-9429
Tel. 82-2-316-9433 Fax. 82-2-316-9429
Tel. 82-2-316-9261~4 Fax. 82-2-316-9429
www.taihan.com
R & D Center996, Siheung-dong,Geumcheon-gu, Seoul,Korea
Tel. 82-2-890-9114Fax. 82-2-806-0186
Anyang Plant785, Gwanyang-dong, Dongan-gu, Anyang,Gyeonggi-do, Korea
Tel. 82-31-420-9114Fax. 82-31-423-2685
Sihung Plant113-119, Sihung-dong, Geumchon-gu, Seoul,Korea
Tel. 82-2-890-9114Fax. 82-2-808-6320
Ansan Plant603, Seonggok-dong,Danwon-gu, Ansan,Gyeonggi-do, Korea
Tel. 82-31-490-5114Fax. 82-31-491-3721
R & D CENTER AND PLANTS
Singapore Office
629 Aljunied Road #05-19, Cititech IndustrialBuilding, Singapore389838, Singapore
Tel. 65-6842-5069Fax. 65-6842-5076
Kuala Lumpur Office
15th Floor, KenangaInternational, JL. Sultanlsmail, 50250 KualaLumpur, Malaysia
Tel. 60-3-2161-8017Fax. 60-3-2161-3628
Riyadh Office
Al Akariyah Shopping Center 2, Room No.726,Olaya Road, P.O.Box 201,Riyadh, Saudi Arabia
Tel. 966-1-419-0227Fax. 966-1-419-0262
Shanghai Office
A410 Far East InternationalPlaza 319 Xian Xia RoadChangning District,Shanghai, China
Tel. 86-21-6235-1263Fax. 86-21-6235-1267
Philippines Office
10A Queen’s Street DonaRita Village TalambanCebu City 6000
Tel. 63-32-346-8799Fax. 63-32-344-8581
Dubai Office
Flat no. 705, Al SafaTower, Sheikh ZayedRoad, Dubai, U.A.EP.O.Box 117561
Tel. 97-14-331-7233Fax. 97-14-331-7322
Thailand Office
253, 26th Floor Asoke,Sukhumvit 21 Road,Klongtoeynua, Wattana,Bangkok 10110, Thailand
Tel. 66-2-664-1464Fax. 66-2-664-4002
Malesela Taihan Electric Cable (Pty) Ltd.Vereeniging 1930, Steel Road,Peacehaven Vereeniging 1939,Gauteng, South Africa
Tel. 27-16-450-8200 Fax. 27-16-423-3406http://www.m-tec.co.za
Skytel Co., LtdSkytel Plaza BuildingChinggisKhan Ave-9,Ulaanbaatar 210603, Mongolia
Tel. 976-1-318488Fax. 976-1-318487http://www.skytel.com
OVERSEAS OFFICES
OVERSEAS SUBSIDIARIES
Specifications are subject to improvement or change without notice. Please contact your local agent or TAIHAN to confirm the latest product information. TPE-0501-0506