Bill of Material
MILPOAll Net prices in US$
WIN Proposal #: 652-0733BAlternative BidProposal/Quote Type:
Valued GE Customer,
We are pleased to offer this proposal for your review. Thank you for allowing GE Industrial Solutions - Electrical Distribution the opportunity to participate on this project. Please do not hesitate to contact us with any questions.
_____
Item# Total PriceDescription Unit PriceQty Inches___
1 Evolution Series MCC (GO100)1TAG 6151-201CLinetype E9000Modified NEMA I-A Wiring Class - MCC ExpressUL TYPE 12 Enclosure6" Bottom Mounted WirewayMCC is Front Mounting Only480 Volts 3 Phase 3 Wire 60 HzMain Horz. Bus 600 Amps��Rating 65000 AICMin. Vertical Bus 600 Amps
MiscellaneousEnclosure and Bus (2 Vertical Sections)
2 Built to UL Type 12 standards
Enclosure Modifications
(2) Seismic Bracing Zone 4(2) Low Voltage Wireway BarrierBus System
(2) 600 Amp CU Main Bus(2) 300 Amp CU Ground Bus(2) 600 Amp CU Front Vertical Bus(2) Vertical Unit Ground Bus(2) Vertical Unit Ground LugBus Modifications
(2) 65000 AIC SC Bus Bracing(2) Double Bolted Construction for Main Bus
Main device1 SGL4T Type 400Amps Frame 250 Amps Trip Main C/B
With (1) #2/0 AWG-500 kcmil Cables Per Phase, TOP Feed
42
Accessories(3) Current Transf - <=600:5A(1) LSIG
Sub Total : 42
Feeders3 Feeder C/B SELT Type 150 Amps Frame 15 Amps Trip 18
3 Feeder C/B SELT Type 150 Amps Frame 50 Amps Trip 18
1 Feeder C/B SELT Type 150 Amps Frame 100 Amps Trip 6
1 Feeder C/B SELT Type 100 Amps Frame 100 Amps Trip 12
Page: 1
Date: 02/13/2012Name: MILPOProp: 652-0733B
.InchesDescriptionQtyItem#
.
Accessories(1) Shunt trip
Sub Total : 54
Combination Starter Devices1 Size 1 FVNR Starter 10 Hp 20 Amps Trip SEL C/B Disc. 18
Accessories(1) CPT-150 VA(1) Full-voltage indicating light -RUN-GREEN(1) Full-voltage indicating light -STOP-RED(1) Full-voltage indicating light -TRIP-AMBER(4) Intlks + 1(No Charge)= 5 Total(1) Shunt trip(1) Solid state OL relay(1) Standard 3pos selector switch(1) Std reset pushbutton(2) Std start/stop pushbutton
1 Size 2 FVNR Starter 25 Hp 50 Amps Trip SEL C/B Disc. 18
Accessories(1) CPT-150 VA(1) Full-voltage indicating light -RUN-GREEN(1) Full-voltage indicating light -STOP-RED(1) Full-voltage indicating light -TRIP-AMBER(4) Intlks + 1(No Charge)= 5 Total(1) Shunt trip(1) Solid state OL relay(1) Standard 3pos selector switch(1) Std reset pushbutton(2) Std start/stop pushbutton
Sub Total : 36
Miscellaneous1 12" undrilled device mounting plate 12
1 12" Section of Future space available 12
Sub Total : 24
Units supplied with the following options2 NONE control wire
2 Control wire terminals - NONE
6 High density control terminal board
10 MTW VW1 (STD) power type
10 Stripped Wire (STD) power wire terminal
Wiring Class1 Wiring Class : Express
Order Information(3) Standard Instruction Books(3) Standard Catalog Renewal Parts Books(3) 8 1/2 by 11 Print Customer Prints
7,590.327,590.32Item Sell Price:
1 Evolution Series MCC (GO100)2
Page: 2
Date: 02/13/2012Name: MILPOProp: 652-0733B
.InchesDescriptionQtyItem#
.
TAG 6150-215Linetype E9000Modified NEMA I-A Wiring Class - MCC ExpressUL TYPE 12 Enclosure6" Bottom Mounted WirewayMCC is Front Mounting Only480 Volts 3 Phase 3 Wire 60 HzMain Horz. Bus 1200 Amps��Rating 65000 AICMin. Vertical Bus 600 Amps
MiscellaneousEnclosure and Bus (1 Vertical Sections)
1 Built to UL Type 12 standards
Enclosure Modifications
(1) Seismic Bracing Zone 4(1) Low Voltage Wireway BarrierBus System
(1) 1200 Amp CU Main Bus(1) 300 Amp CU Ground Bus(1) 600 Amp CU Front Vertical Bus(1) Vertical Unit Ground Bus(1) Vertical Unit Ground LugBus Modifications
(1) 65000 AIC SC Bus Bracing(1) Double Bolted Construction for Main Bus
Main device1 SKL12T Type 1200Amps Frame 1200 Amps Trip Main
C/B With (3) 300-750 kcmil Cables Per Phase, BOTTOM Feed
42
Accessories(3) Current Transf - 1200:5A(1) LI Trip Unit
Sub Total : 42
Feeders2 Feeder C/B SELT Type 150 Amps Frame 50 Amps Trip 12
Sub Total : 12
Miscellaneous1 12" undrilled device mounting plate 12
1 12" Section of Future space available 12
Sub Total : 24
Units supplied with the following options2 MTW VW1 (STD) power type
2 Stripped Wire (STD) power wire terminal
Wiring Class1 Wiring Class : Express
Order Information(3) Standard Instruction Books(3) Standard Catalog Renewal Parts Books(3) 8 1/2 by 11 Print Customer Prints
4,358.494,358.49Item Sell Price:
Page: 3
Date: 02/13/2012Name: MILPOProp: 652-0733B
.InchesDescriptionQtyItem#
.
1 Evolution Series MCC (GO100)3TAG 6150-293Linetype E9000Modified NEMA I-A Wiring Class - MCC ExpressUL TYPE 12 Enclosure6" Bottom Mounted WirewayMCC is Front Mounting Only480 Volts 3 Phase 3 Wire 60 HzMain Horz. Bus 1200 Amps��Rating 65000 AICMin. Vertical Bus 600 Amps
MiscellaneousEnclosure and Bus (1 Vertical Sections)
1 Built to UL Type 12 standards
Enclosure Modifications
(1) Seismic Bracing Zone 4(1) Low Voltage Wireway BarrierBus System
(1) 1200 Amp CU Main Bus(1) 300 Amp CU Ground Bus(1) 600 Amp CU Front Vertical Bus(1) Vertical Unit Ground Bus(1) Vertical Unit Ground LugBus Modifications
(1) 65000 AIC SC Bus Bracing(1) Double Bolted Construction for Main Bus
Incoming Power1 1200Amp Terminal Board With (3) #2 AWG-600 kcmil
Lugs Per Phase, BOTTOM Feed Cu/Al Lug30
Accessories(3) Current Transf - 1200:5A
Sub Total : 30
Feeders2 Feeder C/B SELT Type 150 Amps Frame 50 Amps Trip 12
Sub Total : 12
Miscellaneous1 12" undrilled device mounting plate 12
2 12" Section of Future space available 24
Sub Total : 36
Units supplied with the following options2 MTW VW1 (STD) power type
2 Stripped Wire (STD) power wire terminal
Wiring Class1 Wiring Class : Express
Order Information(3) Standard Instruction Books(3) Standard Catalog Renewal Parts Books(3) 8 1/2 by 11 Print Customer Prints
3,713.863,713.86Item Sell Price:
1 Evolution Series MCC (GO100)4
Page: 4
Date: 02/13/2012Name: MILPOProp: 652-0733B
.InchesDescriptionQtyItem#
.
TAG 6151-201BLinetype E9000Modified NEMA I-A Wiring Class - MCC ExpressUL TYPE 12 Enclosure6" Bottom Mounted WirewayMCC is Front Mounting Only480 Volts 3 Phase 3 Wire 60 HzMain Horz. Bus 600 Amps��Rating 65000 AICMin. Vertical Bus 600 Amps
MiscellaneousEnclosure and Bus (2 Vertical Sections)
2 Built to UL Type 12 standards
Enclosure Modifications
(2) Seismic Bracing Zone 4(2) Low Voltage Wireway BarrierBus System
(2) 600 Amp CU Main Bus(2) 300 Amp CU Ground Bus(2) 600 Amp CU Front Vertical Bus(2) Vertical Unit Ground Bus(2) Vertical Unit Ground LugBus Modifications
(2) 65000 AIC SC Bus Bracing(2) Double Bolted Construction for Main Bus
Main device1 SGL4T Type 400Amps Frame 250 Amps Trip Main C/B
With (1) #2/0 AWG-500 kcmil Cables Per Phase, TOP Feed
42
Accessories(3) Current Transf - <=600:5A(1) LSIG
Sub Total : 42
Feeders3 Feeder C/B SELT Type 150 Amps Frame 15 Amps Trip 18
3 Feeder C/B SELT Type 150 Amps Frame 50 Amps Trip 18
1 Feeder C/B SELT Type 150 Amps Frame 100 Amps Trip 6
1 Feeder C/B SELT Type 100 Amps Frame 100 Amps Trip 12
Accessories(1) Shunt trip
Sub Total : 54
Combination Starter Devices1 Size 1 FVNR Starter 10 Hp 20 Amps Trip SEL C/B Disc. 18
Accessories(1) CPT-150 VA(1) Full-voltage indicating light -RUN-GREEN(1) Full-voltage indicating light -STOP-RED(1) Full-voltage indicating light -TRIP-AMBER(4) Intlks + 1(No Charge)= 5 Total(1) Shunt trip(1) Solid state OL relay(1) Standard 3pos selector switch
Page: 5
Date: 02/13/2012Name: MILPOProp: 652-0733B
.InchesDescriptionQtyItem#
.
(1) Std reset pushbutton(2) Std start/stop pushbutton
1 Size 2 FVNR Starter 25 Hp 50 Amps Trip SEL C/B Disc. 18
Accessories(1) CPT-150 VA(1) Full-voltage indicating light -RUN-GREEN(1) Full-voltage indicating light -STOP-RED(1) Full-voltage indicating light -TRIP-AMBER(4) Intlks + 1(No Charge)= 5 Total(1) Shunt trip(1) Solid state OL relay(1) Standard 3pos selector switch(1) Std reset pushbutton(2) Std start/stop pushbutton
Sub Total : 36
Miscellaneous1 12" undrilled device mounting plate 12
1 12" Section of Future space available 12
Sub Total : 24
Units supplied with the following options2 NONE control wire
2 Control wire terminals - NONE
6 High density control terminal board
10 MTW VW1 (STD) power type
10 Stripped Wire (STD) power wire terminal
Wiring Class1 Wiring Class : Express
Order Information(3) Standard Instruction Books(3) Standard Catalog Renewal Parts Books(3) 8 1/2 by 11 Print Customer Prints
7,590.327,590.32Item Sell Price:
Total Lot Price $__________ Price to follow
Page: 6
Date: 02/13/2012Name: MILPOProp: 652-0733B
FACTORY TESTS:
WARRANTY:1. Sales to Authorized GE Distributor: 12 months from GE ship date, or for shipments from Distributors stock 12 monthsfrom Distributor ship date, but not exceeding 18 months from shipment by GE. Sales to Direct-Served Accounts: See Form ES104 (Rev. 4) for warranty terms.2. Additional 12 months available for 2% adder, 24 months for 4% adder. 3. Warranty covers Equipment only, to be repaired or replaced at Manufacturer’s discretion. Contact GE Post Sales Service for warranty assistance at (888) GE RESOLVELimited Warranty for all Core/Standard and Stand-Alone Drive Panels (excluding DV300 DC Drives and 18 Pulse Panel products): 36 months from date of shipment. An additional 12 months (a total of 48 months) are available for 10% Net Price adder, or an additional 24 months (the maximum of 60 months) for 20% Net Price adder. Contact GE 1 Stop when order is placed to include extended warranty on item(s). DV300 DC Drives have a warranty period of 18 months after shipment only��18 Pulse Drive panels have a warranty of 12 months after shipment.For GE Zenith Controls and Power Quality product limited warranty, please refer to GETCPQ, which can be found at http://www.gedigitalenergy.com/PowerQuality/GETCPQ.pdf.Post Sales Service for GE Zenith Products (Automatic Transfer Switches and UPS products) Contact GE Post Sales Service at 800 637 1738 Select Option 3.
TERMS OF PAYMENT:
1.
3.4.
5.
Sales to Authorized GE Distributor: This quotation is offered subject to the Apparatus Distributor Agreement between
This quotation expires in 30 calendar days unless terminated sooner by notice.
ORDER CANCELLATION - SCHEDULE OF CHARGES:
POLICIES AND CONDITIONS OF SALE:
specifically noted herein and GE Zenith Controls/Power Quality products shown on GETCPQ, which can be found at http://www.gedigitalenergy.com/PowerQuality/GETCPQ.pdf.
GE and Distributor. Sales to Direct-Served Accounts: See Form ES104 (Rev. 4), except as
Standard factory test procedures will be performed. Field testing, customer inspections, customer witness tests and any other non-standard test procedures are not included unless specifically noted herein.
All projects are:
10% - Order received and entered on factory, work not started, material not ordered.30% - Drawings for approval submitted.60% - Approved drawings returned. Job released for manufacture and shipment.80% - Material accumulated and production started.100% - Manufacturing completed.
Price(s) quoted are for estimated lead-times given��expedited schedule may require additional charges.
Order must be released for manufacture within 90 days. If drawings are required they must be returned approved for release within 60 days of mailing. If not, and/or shipment is delayed for any reason, the price will increase 1.5% for each partial/full month that shipment is delayed after the 90-day period.
Net 30 daysPrice Clause 1QFor projects up to $250,000 terms of payment are 100% net 30 days from invoice date.
···· If project value exceeds $250,000 net, progress payments are required payable at the following milestones:
-20% upon delivery of drawings -30% upon release of equipment -Balance due upon shipment
DELIVERY AND TRANSPORTATION:
2. To the extent the Buy American Act, Trade Agreements Act, or other domestic preference requirements are applicable to this Contract, the country of origin of Products is unknown unless otherwise specifically stated by Seller in this Contract. The customer (distributor or direct-served customer, as applicable) warrants that there are no governmental contracting requirements or regulations that apply to this transaction (including without limitation any Federal Acquisition Regulations), other than such terms as have been disclosed to Seller and agreed to by Seller in writing prior to Seller agreeing to this transaction.
Page: 7
Date: 02/13/2012Name: MILPOProp: 652-0733B
1.2.
3.
4.
5.
Unless otherwise noted in this quotation, normal transportation and handling, is allowed on orders of $1000 net or more to common-carrier point nearest destination within the Continental US (excluding Alaska and Hawaii). Freight and handling will be prepaid and billed on orders less than $1000 net.
Special Instruction - The Receiving Associate is required to sign, date and note specific visible or concealed damage on Bill of Lading at time of delivery. Freight Company Associate is required to witness Receiver's signature, date and damage claim annotations. GE's Post Sales Service Department must be provided with copy of annotated BOL within five (5) days of delivery or Shipper's responsibility ends.
Exception-GE Zenith ATS and UPS are not shipped freight allowed. Freight charges will be included on Invoice (3.0% of sale for ATS LTL carrier shipments with minimum $70.00 shipping charge on all ATS products).
6.
GE will assume the risk of loss or damage to the destination for a 2% adder (but not less than $500 net) applied to the total price of the equipment. "Destination" is defined as GE's common carrier's delivery point nearest first destination or point of export within the continental U.S.
EXW GE’s facility, place of manufacture or warehouse (Incoterms 2000). Title passes upon shipment.
Shipment via Air or Open -Top/Flatbed/Lift gate truck not included unless specifically listed herein.
The lead-times quoted are for Estimating Purposes Only. Actual drawing and shipping schedules will be based on factory load, receipt of order with complete technical information, and the date GE receives authorized release to manufacture.The accompanying Bill of Material is our interpretation of what is required to meet the intent of the listed Drawings and Specifications. Please review thoroughly for accuracy and completeness, and advise immediately if any revisions are required. This proposal is limited to the attached Bill of Material only. Start-up Services and Training are not included unless specifically noted herein. Changes to scope will require a revised proposal.
The devices listed on this bill of material may have selective coordination over the long time, short time and instantaneous range. GE's selective capabilities are listed in publication DET-537. It is recommended that a qualified engineer be employed to determine selective coordination as required for the project and in accordance with applicable local codes and acceptable engineering practices. Selective coordination may require significant changes to the system design, equipment sizing and cost.
MANUFACTURAS ELECTRICAS S.A.
Page: 8
GE Motor Control CentersProposal Nbr : 652-0733B Job: MILPORequisition Nbr : /LQHW\SH�(������0RGLILHG�1(0$�,�$�:LULQJ�&ODVV���0&&�([SUHVV�
6HFWLRQ�KW�����8/�7<3(����(QFORVXUH�����%RWWRP�0RXQWHG�:LUHZD\0&&�LV�)URQW�0RXQWLQJ�2QO\������9ROWV���3KDVH���:LUH����+]0DLQ�+RU]��%XV�����$PSV��5DWLQJ�������$,&��0LQ��9HUWLFDO�%XV�����$PSV
Item No 1 Pg: 1TAG 6151-201CDate : 02-13-2012
Plan View - Top
A = 3.31" AA ABB=C=F=
17.63"5.12"5.12"
17.63"5.12"5.12"
D = 3.13" , E = 1.25"B - width of top removable cover plate.C,F - depths of top removable cover plates.
Note:For UL TYPE 12 Enclosures with Powerbreak & HPC switch devices rated 800/1000/1200/1600 or 2000A, allow minimum 5” space in front of door for hinged cover
Elevation - Front View Seismic Bracing provided
Note: Lifting Hardware including
steel angles,nut, washers & bolts should be
removed and discarded after MCC is set in
final location.
A-O - Each letter denotes the bottom of a
6" section
Note : 1. Drawings not to be used for installation. Refer to factory for actual drawings. 2. Add 1.5"height for Channel Sill. 3. Top Mounted 4.4" high Fans required for 2500 Amp. Bus and >= 40HP VFDs 4. Filler, if shown allows door swing when a deeper section is on the left.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Plan View - Bottom : Vertical wiring trough area 10.66" - Vert wiring trough Depth
AA ABA=C=D=
4.63"14.19"
6.8"
4.63"14.19"
6.8"
A - width of vertical wiring troughC - width\depth of Conduit EntranceD- depth is Ground only , no neutral or space heater.E = 3.13" , H = 1.25"
B C
A
D
E
AA600 amps
Grnd & Ñ BUS
C D
E
HAA
20"X20"
AAGMAINCB
AAIMTG
AAKSPACE
AANFVNRSize:1
AB600 amps
Grnd & Ñ BUS
AB20"X20"
ABEFVNRSize:2
ABF FDRCB
ABG FDRCB
ABH FDRCB
ABI FDRCB
ABJ FDRCB
ABK FDRCB
ABL FDRCB
ABNFDRCB
GE Motor Control CentersProposal Nbr : 652-0733B Job: MILPORequisition Nbr : /LQHW\SH�(������0RGLILHG�1(0$�,�$�:LULQJ�&ODVV���0&&�([SUHVV�
6HFWLRQ�KW�����8/�7<3(����(QFORVXUH�����%RWWRP�0RXQWHG�:LUHZD\0&&�LV�)URQW�0RXQWLQJ�2QO\������9ROWV���3KDVH���:LUH����+]0DLQ�+RU]��%XV�����$PSV��5DWLQJ�������$,&��0LQ��9HUWLFDO�%XV�����$PSV
Item No 1 Pg: 2TAG 6151-201CDate : 02-13-2012
Unit Loc
Cust Unit#
Circuit Name Function SizeHP, KW, KVA KVAR
CB Or FSW
Trip Fuse Clip
FLA SF RPM Ht PB Sw ILCont. Rly
Prot/ Mtrg
Total Intlk NO
Total Intlk NC
AAG BLANK NP MAINCB SGL(T) 250 42 X
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAI BLANK NP MTG 12
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAK BLANK NP SPACE 12
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAN BLANK NP FVNR 1
10HP SEL(M) 20 11.9 1.25 1800 18 2 1 3 3 2
Push Button: 1 START/STOP, 1 RESET Selector Switch : 1 H-O-AIndicating Light : 1 RUN - GREEN, 1 STOP - RED, 1 TRIP - AMBER
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABE BLANK NP FVNR 2
25HP SEL(M) 50 28 1.15 1800 18 2 1 3 3 2
Push Button: 1 RESET, 1 START/STOP Selector Switch : 1 H-O-AIndicating Light : 1 RUN - GREEN, 1 STOP - RED, 1 TRIP - AMBER
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABF BLANK NP FDRCB SEL(T) 100 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABG BLANK NP FDRCB SEL(T) 50 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABH BLANK NP FDRCB SEL(T) 50 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABI BLANK NP FDRCB SEL(T) 50 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABJ BLANK NP FDRCB SEL(T) 15 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABK BLANK NP FDRCB SEL(T) 15 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABL BLANK NP FDRCB SEL(T) 15 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABN BLANK NP FDRCB SEL(T) 100 12
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
* This unit has a manual entry
GE Motor Control CentersProposal Nbr : 652-0733B Job: MILPORequisition Nbr : /LQHW\SH�(������0RGLILHG�1(0$�,�$�:LULQJ�&ODVV���0&&�([SUHVV�
6HFWLRQ�KW�����8/�7<3(����(QFORVXUH�����%RWWRP�0RXQWHG�:LUHZD\0&&�LV�)URQW�0RXQWLQJ�2QO\������9ROWV���3KDVH���:LUH����+]0DLQ�+RU]��%XV������$PSV��5DWLQJ�������$,&��0LQ��9HUWLFDO�%XV�����$PSV
Item No 2 Pg: 1TAG 6150-215Date : 02-13-2012
Plan View - Top
A = 3.31" AAB=C=F=
17.63"5.12"5.12"
D = 3.13" , E = 1.25"B - width of top removable cover plate.C,F - depths of top removable cover plates.
Note:For UL TYPE 12 Enclosures with Powerbreak & HPC switch devices rated 800/1000/1200/1600 or 2000A, allow minimum 5” space in front of door for hinged cover
Elevation - Front View Seismic Bracing provided
Note: Lifting Hardware including
steel angles,nut, washers & bolts should be
removed and discarded after MCC is set in
final location.
A-O - Each letter denotes the bottom of a
6" section
Note : 1. Drawings not to be used for installation. Refer to factory for actual drawings. 2. Add 1.5"height for Channel Sill. 3. Top Mounted 4.4" high Fans required for 2500 Amp. Bus and >= 40HP VFDs 4. Filler, if shown allows door swing when a deeper section is on the left.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Plan View - Bottom : Vertical wiring trough area 10.66" - Vert wiring trough Depth
AAA=C=D=
4.63"14.19"
6.8"
A - width of vertical wiring troughC - width\depth of Conduit EntranceD- depth is Ground only , no neutral or space heater.E = 3.13" , H = 1.25"
B C
A
D
E
AA600 amps
Grnd & Ñ BUS
C D
E
HAA
20"X20"
AADSPACE
AAFMTG
AAG FDRCB
AAH FDRCB
AAOMAINCB
GE Motor Control CentersProposal Nbr : 652-0733B Job: MILPORequisition Nbr : /LQHW\SH�(������0RGLILHG�1(0$�,�$�:LULQJ�&ODVV���0&&�([SUHVV�
6HFWLRQ�KW�����8/�7<3(����(QFORVXUH�����%RWWRP�0RXQWHG�:LUHZD\0&&�LV�)URQW�0RXQWLQJ�2QO\������9ROWV���3KDVH���:LUH����+]0DLQ�+RU]��%XV������$PSV��5DWLQJ�������$,&��0LQ��9HUWLFDO�%XV�����$PSV
Item No 2 Pg: 2TAG 6150-215Date : 02-13-2012
Unit Loc
Cust Unit#
Circuit Name Function SizeHP, KW, KVA KVAR
CB Or FSW
Trip Fuse Clip
FLA SF RPM Ht PB Sw ILCont. Rly
Prot/ Mtrg
Total Intlk NO
Total Intlk NC
AAD BLANK NP SPACE 12
AAF BLANK NP MTG 12
AAG BLANK NP FDRCB SEL(T) 50 6
AAH BLANK NP FDRCB SEL(T) 50 6
AAO BLANK NP MAINCB SKL(T) 1200 42 X
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
* This unit has a manual entry
GE Motor Control CentersProposal Nbr : 652-0733B Job: MILPORequisition Nbr : /LQHW\SH�(������0RGLILHG�1(0$�,�$�:LULQJ�&ODVV���0&&�([SUHVV�
6HFWLRQ�KW�����8/�7<3(����(QFORVXUH�����%RWWRP�0RXQWHG�:LUHZD\0&&�LV�)URQW�0RXQWLQJ�2QO\������9ROWV���3KDVH���:LUH����+]0DLQ�+RU]��%XV������$PSV��5DWLQJ�������$,&��0LQ��9HUWLFDO�%XV�����$PSV
Item No 3 Pg: 1TAG 6150-293Date : 02-13-2012
Plan View - Top
A = 3.31" AAB=C=F=
17.63"5.12"5.12"
D = 3.13" , E = 1.25"B - width of top removable cover plate.C,F - depths of top removable cover plates.
Note:For UL TYPE 12 Enclosures with Powerbreak & HPC switch devices rated 800/1000/1200/1600 or 2000A, allow minimum 5” space in front of door for hinged cover
Elevation - Front View Seismic Bracing provided
Note: Lifting Hardware including
steel angles,nut, washers & bolts should be
removed and discarded after MCC is set in
final location.
A-O - Each letter denotes the bottom of a
6" section
Note : 1. Drawings not to be used for installation. Refer to factory for actual drawings. 2. Add 1.5"height for Channel Sill. 3. Top Mounted 4.4" high Fans required for 2500 Amp. Bus and >= 40HP VFDs 4. Filler, if shown allows door swing when a deeper section is on the left.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Plan View - Bottom : Vertical wiring trough area 10.66" - Vert wiring trough Depth
AAA=C=D=
4.63"14.19"
6.8"
A - width of vertical wiring troughC - width\depth of Conduit EntranceD- depth is Ground only , no neutral or space heater.E = 3.13" , H = 1.25"
B C
A
D
E
AA600 amps
Grnd & Ñ BUS
C D
E
HAA
20"X20"
AADSPACE
AAFSPACE
AAHMTG
AAI FDRCB
AAJ FDRCB
AAOINCLINE
Amps:1200
GE Motor Control CentersProposal Nbr : 652-0733B Job: MILPORequisition Nbr : /LQHW\SH�(������0RGLILHG�1(0$�,�$�:LULQJ�&ODVV���0&&�([SUHVV�
6HFWLRQ�KW�����8/�7<3(����(QFORVXUH�����%RWWRP�0RXQWHG�:LUHZD\0&&�LV�)URQW�0RXQWLQJ�2QO\������9ROWV���3KDVH���:LUH����+]0DLQ�+RU]��%XV������$PSV��5DWLQJ�������$,&��0LQ��9HUWLFDO�%XV�����$PSV
Item No 3 Pg: 2TAG 6150-293Date : 02-13-2012
Unit Loc
Cust Unit#
Circuit Name Function SizeHP, KW, KVA KVAR
CB Or FSW
Trip Fuse Clip
FLA SF RPM Ht PB Sw ILCont. Rly
Prot/ Mtrg
Total Intlk NO
Total Intlk NC
AAD BLANK NP SPACE 12
AAF BLANK NP SPACE 12
AAH BLANK NP MTG 12
AAI BLANK NP FDRCB SEL(T) 50 6
AAJ BLANK NP FDRCB SEL(T) 50 6
AAO BLANK NP INCLINE 30 X
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
* This unit has a manual entry
GE Motor Control CentersProposal Nbr : 652-0733B Job: MILPORequisition Nbr : /LQHW\SH�(������0RGLILHG�1(0$�,�$�:LULQJ�&ODVV���0&&�([SUHVV�
6HFWLRQ�KW�����8/�7<3(����(QFORVXUH�����%RWWRP�0RXQWHG�:LUHZD\0&&�LV�)URQW�0RXQWLQJ�2QO\������9ROWV���3KDVH���:LUH����+]0DLQ�+RU]��%XV�����$PSV��5DWLQJ�������$,&��0LQ��9HUWLFDO�%XV�����$PSV
Item No 4 Pg: 1TAG 6151-201BDate : 02-13-2012
Plan View - Top
A = 3.31" AA ABB=C=F=
17.63"5.12"5.12"
17.63"5.12"5.12"
D = 3.13" , E = 1.25"B - width of top removable cover plate.C,F - depths of top removable cover plates.
Note:For UL TYPE 12 Enclosures with Powerbreak & HPC switch devices rated 800/1000/1200/1600 or 2000A, allow minimum 5” space in front of door for hinged cover
Elevation - Front View Seismic Bracing provided
Note: Lifting Hardware including
steel angles,nut, washers & bolts should be
removed and discarded after MCC is set in
final location.
A-O - Each letter denotes the bottom of a
6" section
Note : 1. Drawings not to be used for installation. Refer to factory for actual drawings. 2. Add 1.5"height for Channel Sill. 3. Top Mounted 4.4" high Fans required for 2500 Amp. Bus and >= 40HP VFDs 4. Filler, if shown allows door swing when a deeper section is on the left.
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
Plan View - Bottom : Vertical wiring trough area 10.66" - Vert wiring trough Depth
AA ABA=C=D=
4.63"14.19"
6.8"
4.63"14.19"
6.8"
A - width of vertical wiring troughC - width\depth of Conduit EntranceD- depth is Ground only , no neutral or space heater.E = 3.13" , H = 1.25"
B C
A
D
E
AA600 amps
Grnd & Ñ BUS
C D
E
HAA
20"X20"
AAGMAINCB
AAIMTG
AAKSPACE
AANFVNRSize:1
AB600 amps
Grnd & Ñ BUS
AB20"X20"
ABEFVNRSize:2
ABF FDRCB
ABG FDRCB
ABH FDRCB
ABI FDRCB
ABJ FDRCB
ABK FDRCB
ABL FDRCB
ABNFDRCB
GE Motor Control CentersProposal Nbr : 652-0733B Job: MILPORequisition Nbr : /LQHW\SH�(������0RGLILHG�1(0$�,�$�:LULQJ�&ODVV���0&&�([SUHVV�
6HFWLRQ�KW�����8/�7<3(����(QFORVXUH�����%RWWRP�0RXQWHG�:LUHZD\0&&�LV�)URQW�0RXQWLQJ�2QO\������9ROWV���3KDVH���:LUH����+]0DLQ�+RU]��%XV�����$PSV��5DWLQJ�������$,&��0LQ��9HUWLFDO�%XV�����$PSV
Item No 4 Pg: 2TAG 6151-201BDate : 02-13-2012
Unit Loc
Cust Unit#
Circuit Name Function SizeHP, KW, KVA KVAR
CB Or FSW
Trip Fuse Clip
FLA SF RPM Ht PB Sw ILCont. Rly
Prot/ Mtrg
Total Intlk NO
Total Intlk NC
AAG BLANK NP MAINCB SGL(T) 250 42 X
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAI BLANK NP MTG 12
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAK BLANK NP SPACE 12
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
AAN BLANK NP FVNR 1
10HP SEL(M) 20 11.9 1.25 1800 18 2 1 3 3 2
Push Button: 1 START/STOP, 1 RESET Selector Switch : 1 H-O-AIndicating Light : 1 RUN - GREEN, 1 STOP - RED, 1 TRIP - AMBER
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABE BLANK NP FVNR 2
25HP SEL(M) 50 28 1.15 1800 18 2 1 3 3 2
Push Button: 1 RESET, 1 START/STOP Selector Switch : 1 H-O-AIndicating Light : 1 RUN - GREEN, 1 STOP - RED, 1 TRIP - AMBER
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABF BLANK NP FDRCB SEL(T) 100 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABG BLANK NP FDRCB SEL(T) 50 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABH BLANK NP FDRCB SEL(T) 50 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABI BLANK NP FDRCB SEL(T) 50 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABJ BLANK NP FDRCB SEL(T) 15 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABK BLANK NP FDRCB SEL(T) 15 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABL BLANK NP FDRCB SEL(T) 15 6
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
ABN BLANK NP FDRCB SEL(T) 100 12
Legend : Cont.Rly : - nn - Quantity of Control or Timing Relays on the unit Prot/Mtrg : - X - denotes that unit has at least one Meter or Multilin device
* This unit has a manual entry