1 ichs: international conference on hydrogen safety, 8 th september, 2005, pisa, italy
Post on 19-Dec-2015
217 views
TRANSCRIPT
2
Approach to Hydrogen Society
【 R&D of H2&FC Technology 】 ・ Fundamental Research and Breakthrough Technology for Fuel Cell Vehicle and Hydrogen Infrastructure
【 Demonstration & Promotion 】 ・ FCV Introduction by the Government ・ Financial Support for FCV Introduction ・ Hydrogen Infrastructure Promotion
【 Establishment of Social Institutions 】 ・ Regulations, Codes & Standards for FCVs
3
Safety Issues of H2 FCVs
【 Peculiar to H2 FCVs 】 Hydrogen Safety ・ High Pressure Cylinder & Vehicle ・ Leakage and Ignition of Hydrogen ・ Fire Fighting & Rescue at the accident【 Same as Conventional Vehicles 】 Crash Safety High Voltage Safety Electromagnetic Compatibility (EMC)
4
Vehicle Fire Test
H2 Upward(35MPa, Two 34L Tanks) H2 Downward(35MPa, Two 34 L Tanks)
CNG(20MPa, Two 34L Tanks)Gasoline(40L in a Steel Tank)
5
H2 Upward(35MPa, Two 34L Tanks) H2 Downward(35MPa, Two 34 L Tanks)
CNG(20MPa, Two 34L Tanks)Gasoline(40L in a Steel Tank)
Vehicle Fire Test
6
Heat Irradiation Comparison
0
50
100
150
200
250
300
350
10 15 20 25 30
[ ]時間 分
[KW/m
輻射
2 ]
Many peaksMax 200kW/m2
Time (min.)
Irra
diat
ion
(kW
/m2 )
0
50
100
150
200
250
300
350
10 15 20 25 30
[ ]時間 分
[KW/m
輻射
2 ]
Many peaksMax 200kW/m2
Time (min.)
Irra
diat
ion
(kW
/m2 )
0
50
100
150
200
250
0 5 10 15 20
[ ]時間 分
[KW/m
輻射
2 ] at the peakMax 186kW/m2
First PRD operated
Second PRD operated
Time (min.)
Irra
diat
ion
(kW
/m2 )
0
50
100
150
200
250
0 5 10 15 20
[ ]時間 分
[KW/m
輻射
2 ] at the peakMax 186kW/m2
First PRD operated
Second PRD operated
Time (min.)
Irra
diat
ion
(kW
/m2 )
0
50
100
150
200
250
0 5 10 15 20
[ ]時間 分
[KW/m
輻射
2 ] No heat irradiation peakMax25kW/m2
Time (min.)
Irra
diat
ion
(kW
/m2 )
0
50
100
150
200
250
0 5 10 15 20
[ ]時間 分
[KW/m
輻射
2 ] No heat irradiation peakMax25kW/m2
Time (min.)
Irra
diat
ion
(kW
/m2 )
0
50
100
150
200
250
0 5 10 15 20
[ ]時間 分
[KW/m
輻射
2 ]
CNG release duration is longer and the peak is larger than hydrogen Max 231kW/m2
Time (min.)
Irra
diat
ion
(kW
/m2 )
0
50
100
150
200
250
0 5 10 15 20
[ ]時間 分
[KW/m
輻射
2 ]
CNG release duration is longer and the peak is larger than hydrogen Max 231kW/m2
Time (min.)
Irra
diat
ion
(kW
/m2 )
Gasoline Vehicleintermittent large flame, long duration
CNG Vehicle (Downward)large flame area, highest irradiation peak
longer duration than hydrogen
H2 Vehicle (Downward)short duration
H2 Vehicle (Upward)no measurable irradiation peak
7
Subjects of Hydrogen Fire Safety Test
Higher Pressure: 35MPa to 70MPaLarger Capacity: Passenger Car to Bus ApplicationTank Number: Single Tank System, Multi-tank SystemStorage Technologies Liquefied Hydrogen Tank Combination of Metal Hydride and High Pressure Tank Chemical Hydrides Carbon Adsorption etc.
Comprehensive Hydrogen Safety Evaluation Facility
9
Explosion Resistant Fire Test Cell
Air Air
Exhaust
Silencer
Air Air
Exhaust
Silencer
Exhaust EmissionsAfter Treatment Equipment
Silencer
Air SupplyBlower
Exhaust Blower
External Appearance of the FacilityInternal Structure of Fire Test Cell
10
Specification of Fire Test Cell
Inside Dimensions: 16m Height, 18m Diameter, Enough Space to Observe the Flame Propagation AreaWall Thickness: 1.2m Wall, 1.4m Ceiling, 4.0m Ground Floor Enough Strength Against Possible Explosions Suppose the Explosion of 260 liter and 70MPa Tank Air Supply and Exhaust Blower: 750 m3/min. Enough Air Supply to Maintain a Vehicle FireExhaust Gas After Treatment: Ceramic Filter and Dry Adsorption by a Mixed Agent (Diatomite, Hydrated Lime, Activated Charcoal) Clean Exhaust Emission without Smoke or Harmful SubstancesSilencer: Reducing the Noise Level by 80 dB
11
1. The repeatability of the tests. Not depending on the climate ( wind, rain, snow etc.)
2. Easy to provide the high technology measurement equipments
3. Environmental friendly. Doesn’t emits sound, smoke, broken parts to the outside. 4. Comfortable for the workers.
The Advantages of Indoor Test Facility
13
Bonfire Test of Hydrogen Tank
In every test, PRD was operated and no explosion, no blow-off was occurred.
16
Hydraulic Pressure Test 120MPa Intensifier
270MPa Intensifire
300MPa Intensifire
Pressure Cycle Test: Max 120MPaBurst Test: Max 300MPa
17
High Pressure Hydrogen Test Equipment
Oil-lessAir-CooledReciprocated PistonFive StagesMaximum Pressure: 110MPaCapacity: 200Nm3/h
Material: Cr-Mo-Alloy SteelCylinder Thickness: 65mmFilling Pressure: 110MPaCapacity: 72L
Maximum Tank Size: 260LTemperature Range: -40oC ~ +85oC
Hydrogen Compressor Storage TanksAir-tight TemperatureControl Chamber
18
Utilization of Hy-SEF
1.Fire Safety of H2 Storage Tank ・ High Pressure Cylinder ・ Liquid Hydrogen Tank ・ Metal Hydride Tank ・ New Hydrogen Storage Technics
2.Fire Safety of H2 Vehicles ・ Safe Method of PRD Hydrogen Release3.Measures of Fire Fighting4.Hydrogen Diffusion and Ignition
19
Summary
1. A Comprehensive hydrogen safety evaluation facility, called Hy-SEF, was constructed as a Japanese national project supported by NEDO and METI.
2. This facility can provide high quality information about hydrogen safety, and will serve the revision and/or establishment of regulations, codes and standards for hydrogen vehicles.
3. This facility can also support the development of hydrogen storage and utilization technologies.