1 insulation coordination “the selection of insulation strength”
TRANSCRIPT
1
Insulation CoordinationInsulation Coordination
“the selection of insulation “the selection of insulation strength”strength”
2
Kiski Valley Substation - 1938
3
Luxor substation – 1933…………….before lightning arresters
4
InsulationInsulation
Self restoringSelf restoring insulation recovers after a insulation recovers after a flashover – external such as air switches, flashover – external such as air switches, insulators, external surfaces of bushings insulators, external surfaces of bushings (defined at standard atmospheric (defined at standard atmospheric conditions)conditions)
Non-self restoringNon-self restoring insulation does not insulation does not recover after a flashover – enclosed oil, recover after a flashover – enclosed oil, paper, gas, air systems such as transformers paper, gas, air systems such as transformers and circuit breakersand circuit breakers
5
Standards Standards http://www.techstreet.com/info/astm.http://www.techstreet.com/info/astm.
Voltages: ANSI C84.1- 1995 System VoltagesVoltages: ANSI C84.1- 1995 System Voltages Voltages: IEEE 1312 – 1987 AC Electrical Systems and Equipment Operating Voltages above 230kvVoltages: IEEE 1312 – 1987 AC Electrical Systems and Equipment Operating Voltages above 230kv BILs: ANSI 92 defines BILs for the equipment manufacturers to useBILs: ANSI 92 defines BILs for the equipment manufacturers to use IEEE std 4 – 1995 Standard Techniques for High Voltage TestingIEEE std 4 – 1995 Standard Techniques for High Voltage Testing Circuit Breakers: ANSI C-37.06 1997Circuit Breakers: ANSI C-37.06 1997 Transformers: ANSI C57.12 – 1993 Liquid Immersed Distribution, Power and Regulating Power Transformers: ANSI C57.12 – 1993 Liquid Immersed Distribution, Power and Regulating Power
Transformers Transformers Switches: IEEE C37.34 Standard Test Code for High Voltage SwitchesSwitches: IEEE C37.34 Standard Test Code for High Voltage Switches Insulators: ANSI C29.8 & C29.9 Cap and Pin Type & Post Type InsulatorsInsulators: ANSI C29.8 & C29.9 Cap and Pin Type & Post Type Insulators Arresters: IEEE C62.11 Metal Oxide surge arresters for AC Power CircuitsArresters: IEEE C62.11 Metal Oxide surge arresters for AC Power Circuits Arresters: IEEE C62.22 Guide for application of Metal Oxide surge arresters for Alternating Current Arresters: IEEE C62.22 Guide for application of Metal Oxide surge arresters for Alternating Current
SystemsSystems
6
Impulse Voltages and Equipment Impulse Voltages and Equipment RequirementsRequirements
Over-voltagesOver-voltages Transient WaveshapesTransient Waveshapes Equipment testingEquipment testing
7
Over-voltagesOver-voltageswhat causes over-voltages on the system?what causes over-voltages on the system?
LightningLightning Switching – breakers clearing faultsSwitching – breakers clearing faults Increases in power frequency voltageIncreases in power frequency voltage
8
Transient WaveformsTransient Waveforms
Lightning - 1.2 x 50 u-secondLightning - 1.2 x 50 u-second Front of WaveFront of Wave Chopped WavesChopped Waves Switching - 250 x 2500 u-secondSwitching - 250 x 2500 u-second 60 hertz waves60 hertz waves
9
Peak or RMSPeak or RMS
60hz voltages are expressed in rms60hz voltages are expressed in rmsph-ph ph-ph
Duty cycle and MCOV are in rms phase-groundDuty cycle and MCOV are in rms phase-ground Lightning, chopped wave and switching surges are Lightning, chopped wave and switching surges are
expressed in expressed in peakpeak volts phase to ground: volts phase to ground:
Peak = 2 rmsrmsph-phph-ph
3
Peak = 2 145kv = 118.4kv 3
10
Lightning ImpulsesLightning Impulses Very fast rise can cause line insulation to failVery fast rise can cause line insulation to fail
– ““backflashes” - rise in the 500-2000KV per u-second range and backflashes” - rise in the 500-2000KV per u-second range and 10-20 u-sec tail (cfo of line - positive polarity waves) 10-20 u-sec tail (cfo of line - positive polarity waves)
– Direct strokes to phase wires (cfo due to negative polarity Direct strokes to phase wires (cfo due to negative polarity waves) slightly slower rise and longer tail than backflashwaves) slightly slower rise and longer tail than backflash
BIL: BIL: BBasic asic IImpulse mpulse LLevel is the electrical strength of insulation to evel is the electrical strength of insulation to the crest value of the standard lightning impulse (for dry the crest value of the standard lightning impulse (for dry conditions)conditions)– BIL = CFO – 1.28 x BIL = CFO – 1.28 x oof f (10% probability of flashover)(10% probability of flashover)
Test wave doesn’t reflect actual lightning but its easily reproduced Test wave doesn’t reflect actual lightning but its easily reproduced in test labin test lab
Lightning can be positive or negative compared to the earth – most Lightning can be positive or negative compared to the earth – most strokes are negative. The insulation withstand can be different for strokes are negative. The insulation withstand can be different for each type each type
11
Lightning Impulse 1.2 x 50 u-seconds
BIL = 1.0
.5
t2
Virtual tail = 50 micro-seconds
IEEE std 4-1995 Standard Techniques for High Voltage Testing
Virtual front = 1.2 micro-seconds
.9
.3 A
B
t1
Virtual Zero
v
t
Tolerances:Front: +/- 30%Tail: +/- 20%
12
Impulse Generators:Impulse Generators:
•Impulse generators are stacks of capacitors and resistors•Initially the capacitors are connected in parallel and charged up•Then the capacitors are re-connected in series•Then they are discharged to provide the high voltage impulse wave•Resistors are used to shape the front and tail of the wave
+
-
+-
Charging circuit
Discharging circuit
13
Chopped Wave ImpulsesChopped Wave Impulses
Allows a faster front wave to be applied without Allows a faster front wave to be applied without flashover occurring on the tail of the waveflashover occurring on the tail of the wave
Chopped wave impulses are standard lightning Chopped wave impulses are standard lightning waves that are shunted or “chopped” to zero on the waves that are shunted or “chopped” to zero on the tail of the wave within 2 or 3 u-secondstail of the wave within 2 or 3 u-seconds
Chopped wave tests are only used in ANSI (not Chopped wave tests are only used in ANSI (not IEC) standards and are meant to model surges IEC) standards and are meant to model surges created by the flashover of a post insulator or an created by the flashover of a post insulator or an arrester operationarrester operation
Stresses transformer turn to turn insulationStresses transformer turn to turn insulation Model the need for arresters at the “open breaker”Model the need for arresters at the “open breaker”
14
Chopped Wave Impulse 1.2 x 3 u-seconds
BIL = 1.0
IEEE std 4-1995 Standard Techniques for High Voltage Testing
v
t
1.1 - 1.29 x BIL
t
15
Switching ImpulsesSwitching Impulses
BSL: BSL: BBasic asic SSwitching witching LLevel is the electrical evel is the electrical strength of insulation to the crest value of the strength of insulation to the crest value of the standard switching impulse (wet conditions)standard switching impulse (wet conditions)
– BSL = CFO – 1.28 x BSL = CFO – 1.28 x oof f (10% probability of (10% probability of flashover)flashover)
Switching impulses are longer duration both on Switching impulses are longer duration both on the front and the tail (hundreds of u-seconds)the front and the tail (hundreds of u-seconds)
Low line surge impedance (> 138kv overhead Low line surge impedance (> 138kv overhead lines, also cable circuits)lines, also cable circuits)
Re-closing into trapped charge on lineRe-closing into trapped charge on line
16
Switching Switching Surges:Surges:
Z0= L/C
Voltage doubles when closing in on an open line = 2 P.U. at open line terminal
Assume that High Speed Re-closing traps a negative 1 P.U. charge on the Assume that High Speed Re-closing traps a negative 1 P.U. charge on the line. Then when the breaker re-closes the maximum voltage at the open end line. Then when the breaker re-closes the maximum voltage at the open end
can approach a maximum of can approach a maximum of 3.5 - 4.0 P.U.3.5 - 4.0 P.U. for multiple reflections depending for multiple reflections depending on damping (R):on damping (R):
Trapped charge = -1.0 P.U.Trapped charge = -1.0 P.U.
3.5 P.U.
17
50% Critical Flashover Voltage CFO
Strike Distance
Switching Switching Surges:Surges:
1.2x5
0 lig
htnin
g
Positive switching
surge
Insulation strength of air gaps:
At operating voltages above 230kv switching transients become the constraint that drives system design
Breakers & switches are only tested for switching surge at 345kv and above. Transformers 115kv & above.
18
Switching Impulse 250 x 2500 u-seconds
1.0
.5
t2 = 2500 u-sec
IEEE std 4-1995 Standard Techniques for High Voltage Testing
v
tt1 = 250 u-sec
Tolerances:Front: +/- 20%Tail: +/- 60%
19
Power Frequency (60hz) Power Frequency (60hz) Maximum 60Hz Operating Maximum 60Hz Operating
VoltageVoltage
Nominal + 5% 500kv system is nominal + 10%
20
System Voltages ANSI C84.1 - 1995
21
System Voltages ANSI C84.1 - 1995
22
Power Frequency (60hz) Power Frequency (60hz) OvervoltagesOvervoltages
Rise on unfaulted phases for a line-ground fault Rise on unfaulted phases for a line-ground fault (X/R and co-efficient of grounding)(X/R and co-efficient of grounding)
Loss of ground (backfeed)Loss of ground (backfeed) Ferro-resonance – line or cable capacitance with Ferro-resonance – line or cable capacitance with
transformer inductancetransformer inductance Load rejectionLoad rejection Ferranti effect – long unloaded transmission linesFerranti effect – long unloaded transmission lines Transformer inrushTransformer inrush
23
Coefficient of GroundingCoefficient of Grounding
24
25
Potential Rise on the LinePotential Rise on the Line
Voltage
Breaker open
..
26
27
Equipment InsulationEquipment Insulation
Bus InsulatorsBus Insulators Air SwitchesAir Switches Circuit BreakersCircuit Breakers TransformersTransformers BushingsBushings Equipment External ClearancesEquipment External Clearances
28
BIL/BSL Testing
1.0
.5
CFO
BIL or BSL = 1.28 ooff
Pro
babi
lity
of F
lash
over
KV
.1
29IEEE 1313.1 1996
Equipment BILs (Class one equipment):
30
Equipment BILs/BSLs for EHV (Class two):
31
Equipment InsulationEquipment Insulation60 hz testing:60 hz testing:
60 hz tests – wet tests are done on insulators, air 60 hz tests – wet tests are done on insulators, air switches and cijrcuit breakers to understand switches and cijrcuit breakers to understand response during rain (IEEE std 4 – 1995)response during rain (IEEE std 4 – 1995)
and dew conditions (ANSI C-29.1 – 1988 section and dew conditions (ANSI C-29.1 – 1988 section 4.6)4.6)
32
Equipment InsulationEquipment Insulation
Bus InsulatorsBus Insulators Air SwitchesAir Switches Circuit BreakersCircuit Breakers TransformersTransformers BushingsBushings
33
Bus Supports & AirSwitches ANSI C37.32
Withstand (10%)
34
Standard Atmospheric Standard Atmospheric ConditionsConditions
Ambient temperature = 20 deg CAmbient temperature = 20 deg C Air Pressure = 760mm mercury (1 atmosphere)Air Pressure = 760mm mercury (1 atmosphere) Absolute humidity = 11 gms water/MtrAbsolute humidity = 11 gms water/Mtr3 3 airair The test voltages are adjusted as needed when The test voltages are adjusted as needed when
conditions vary from the standardconditions vary from the standard
35
Equipment InsulationEquipment Insulation
Bus InsulatorsBus Insulators Air SwitchesAir Switches Circuit BreakersCircuit Breakers TransformersTransformers BushingsBushings
36
Bus Supports & Air SwitchesANSI C37.32
37
EHV Switches:
Air SwitchesANSI C37.32
38
39
Air Switch Coordination
- Gap flashover - Gap withstand - Insulator flashover - Insulator withstand
Make the gap withstand 10% higher than the insulator flashover!
40
Bus Supports & Air SwitchesANSI C37.32
41
Passing the 3+9 test:
Air Switches
AP’s switch specification MS 1100-10 requires transmission switches to withstand 15 impulses without flashover for the gap withstand and also flashover for 15 impulses to establish the insulator flashover value.
42
Circuit Switcher Coordination
In the model Mark V circuit switcherthe interrupter closes when theswitch blade reaches the full openposition so the open blade must coordinate with the post insulator.In the series 2000 the interrupter staysOpen when the blade opens!
43
Equipment InsulationEquipment Insulation
Bus InsulatorsBus Insulators Air SwitchesAir Switches Circuit BreakersCircuit Breakers TransformersTransformers BushingsBushings
44
ABB 550 PMABB 550 PM
45
Circuit Breaker CoordinationBreaker closed
Weakest point is typicallythe throat shield to ground
46
ABB 550 PM ABB 550 PM
47
ABB 550 PM Failure ABB 550 PM Failure Doubs DL-55, July 8, 2000 – Tube Flashover Doubs DL-55, July 8, 2000 – Tube Flashover
48
Circuit Breaker CoordinationBreaker openSwitching surge values are higher for the gap than for phase to ground
49
Circuit Breaker Design TestsCircuit Breaker Design Tests
Breaker switching surgewithstand is higher across
the interrupter than to ground!
50
Circuit BreakerCircuit Breaker500kv PM Design Tests500kv PM Design Tests
One minute dry withstandOne minute dry withstand 60hz60hz 860kv860kv Ten second wet withstandTen second wet withstand 60hz60hz 775kv775kv Full wave impulse (BIL)Full wave impulse (BIL) 1800kv1800kv Chop wave impulse – 2 u-sec to chopChop wave impulse – 2 u-sec to chop 2320kv2320kv Chop wave impulse – 3 u-sec to chopChop wave impulse – 3 u-sec to chop 2070kv2070kv Switching impulse – terminal to gnd 1175kv Switching impulse – terminal to gnd 1175kv
(breaker open)(breaker open) Switching impulse – terminal to gnd Switching impulse – terminal to gnd 1175kv 1175kv
(breaker closed) (breaker closed) Switching impulse – terminal to terminal 1300kv Switching impulse – terminal to terminal 1300kv
(breaker open)(breaker open)
51
Breaker ApplicationsBreaker Applications
Closing resistorsClosing resistors are used to reduce the are used to reduce the switching surge created at the far end of switching surge created at the far end of a transmission line when it is energizeda transmission line when it is energized– Once breaker is closed the resistor is removed Once breaker is closed the resistor is removed
from the circuit.from the circuit.– Not designed to handle continuous load current Not designed to handle continuous load current
or fault current.or fault current.– AP uses closing resistors on EHV breakersAP uses closing resistors on EHV breakers– Typical value: 400-450 ohms.Typical value: 400-450 ohms.
52
Closing resistorsClosing resistors::
Z0= L/CRc
Rc
Z0 V0
Z0
(Rc + Z0)V0 = VS
bypass
VS
53
Equipment InsulationEquipment Insulation
Bus InsulatorsBus Insulators Air SwitchesAir Switches Circuit BreakersCircuit Breakers TransformersTransformers BushingsBushings
54
Transformer BIL Levels
55
Transformer Test Levels
56
Transformers:Transformers:138-12kv delta-wye138-12kv delta-wye
low
volage wintding
Gas Space - N2
highvoltagewinding
HV & LV BILs determine the amount of line end
insulation of the windings
57
Turn-Turn failure at line end
138kv disk winding – 30/40/50mva
58
TransformerTransformer
low
volage wintding
Gas Space - N2
highvoltagewinding
HV BIL determinesthe distance between the high-low windingsand H-L insulation
59
TransformerTransformer
low
volage wintding
Gas Space - N2
highvoltagewinding
Induced test determines the high-groundinsulation
60
TransformerTransformer
low
volage wintding
Gas Space - N2
highvoltagewinding
LV BIL and thru-fault mechanical forces stress low-groundinsulation
61
62
63
Equipment InsulationEquipment Insulation
Bus InsulatorsBus Insulators Air SwitchesAir Switches Circuit BreakersCircuit Breakers TransformersTransformers BushingsBushings
64
BushingsBushings
Condenser type Condenser type
bushings are built to bushings are built to
grade the voltage from grade the voltage from
line to ground evenly.line to ground evenly.
““creep” and creep” and
contaminationcontamination
SF6 weathershedsSF6 weathersheds
65
500 kV Bushing Type O500 kV Bushing Type O
66
500 kV Bushing Type O500 kV Bushing Type O
67
500 kV Bushing Type O500 kV Bushing Type O
68
External Equipment Clearances:External Equipment Clearances:
Need to compare external equipment withstands with bus Need to compare external equipment withstands with bus support and air switch clearancessupport and air switch clearances
Compare phase-to-ground and phase-to-phase equipment Compare phase-to-ground and phase-to-phase equipment dimensions with the bus designdimensions with the bus design
Equipment manufacturers will set phase-phase and phase-Equipment manufacturers will set phase-phase and phase-ground dimensions to pass equipment test standards but ground dimensions to pass equipment test standards but these are not coordinated with bus dimensionsthese are not coordinated with bus dimensions
Typically the clearances between live parts on the Typically the clearances between live parts on the equipment are too small! Flashovers will occur at the equipment are too small! Flashovers will occur at the equipment before the bus. equipment before the bus.
Need to specify equipment clearances that will Need to specify equipment clearances that will coordinate with bus clearancescoordinate with bus clearances
69
Transformer Clearances: 138-12kv138-12kv
xfmrxfmr
PhasePhase
To phaseTo phase
PhasePhase
To groundTo ground
138kv138kv 49 in.49 in. 49 in.49 in.
12kv12kv 6.5 in.6.5 in. 6.5 in.6.5 in.
70
AP TransformerDesign Clearances:
71
Proper Insulation Coordination
If lightning strikes the phase conductor and it generates enough voltage to flash the insulation I want it flashing over the cheapest, self restoring insulation first and I want it to go to ground
72
Transformer Terminated LinesTransformer Terminated Lines
Initial Switching surge
..Breaker openWhen you close this breaker
a switching transient is createdthat doubles at the other end of
the line because the transformer is open on the low side
Reflected wave
Close line breaker first
Then close thexfmr air switch