1 safety instructions 2 device componentsknx/eib weather station standard mounting and connecting...

6
Weather station Standard Order No. : 2150 04 Operating instructions 1 Safety instructions Electrical equipment may only be installed and fitted by electrically skilled persons. Failure to observe the instructions may cause damage to the device and result in fire and other hazards. These instructions are an integral part of the product, and must remain with the end customer. 2 Device components Figure 1: View (1) Sensor head (2) Angular arm (3) Terminal box (4) Temperature and wind sensors (5) Light and twilight sensors (6) Rain sensor 3 Function System information This device is a product of the KNX system and complies with the KNX directives. Detailed technical knowledge obtained in KNX training courses is a prerequisite to proper understanding. The function of this device depends upon the software. Detailed information on loadable software and attainable functionality as well as the software itself can be obtained from the manufacturer´s product database. Planning, installation and commissioning of the device are carried out with the aid of KNX-certified software. The latest versions of product database and the technical descriptions are available on our website. Intended use - Measurement and evaluation of the weather data: Wind speed, Precipitation, Twilight, Temperature and brightness - Vertical installation on the outside of buildings, preferable in the roof and facade area 1/6 82562832 19.02.2014 Weather station Standard KNX/EIB

Upload: others

Post on 16-Feb-2021

0 views

Category:

Documents


0 download

TRANSCRIPT

  • Weather station StandardOrder No. : 2150 04

    Operating instructions

    1 Safety instructionsElectrical equipment may only be installed and fitted by electrically skilled persons.Failure to observe the instructions may cause damage to the device and result in fire andother hazards.These instructions are an integral part of the product, and must remain with the endcustomer.

    2 Device components

    Figure 1: View

    (1) Sensor head(2) Angular arm(3) Terminal box(4) Temperature and wind sensors(5) Light and twilight sensors(6) Rain sensor

    3 FunctionSystem informationThis device is a product of the KNX system and complies with the KNX directives. Detailedtechnical knowledge obtained in KNX training courses is a prerequisite to proper understanding. The function of this device depends upon the software. Detailed information on loadablesoftware and attainable functionality as well as the software itself can be obtained from themanufacturer´s product database. Planning, installation and commissioning of the device arecarried out with the aid of KNX-certified software. The latest versions of product database andthe technical descriptions are available on our website.

    Intended use- Measurement and evaluation of the weather data: Wind speed, Precipitation, Twilight,

    Temperature and brightness- Vertical installation on the outside of buildings, preferable in the roof and facade area

    1/682562832 19.02.2014

    Weather station StandardKNX/EIB

  • Product characteristics- Integrated KNX bus coupling unit- Measurement data acquisition and limit value monitoring- Integrated heatingi The measured values apply to the mounting location. Variations to other weather services

    – e.g. through local turbulence or areas with build-ups of air – are possible.

    4 Information for electrically skilled persons4.1 Fitting and electrical connection

    DANGER!Electrical shock on contact with live parts in the installation environment.Electrical shocks can be fatal.Before working on the device, disconnect the power supply and cover up liveparts in the working environment.

    Selecting the installation location

    Figure 2: Minimum distance to surfaces

    82562832 19.02.2014 2/6

    KNX/EIBWeather station Standard

  • Figure 3: Avoid spray water

    Figure 4: Maximum load on the angular arm

    Select a mounting selection in which the weather station is not influenced by local obstacles orshading, such as surrounding trees, chimneys, awnings, etc. The sensor must be able to detectwind, rain and ambient brightness without impedance. Do not mount it below or next to building sections, from which water can drip onto the device.Select the mounting location so that the weather station will be accessible for maintenancepurposes.In the case of flat roofs, locate the weather station as close to the centre of the roof as possible. Minimum distance to surfaces below the weather station: 0.6 m (Figure 2). Otherwise, thesensors on the underside may get damaged by penetrating spray water (Figure 3). Direct sunlight, chimneys or other waste gas or ventilation systems affect the temperaturemeasurement.Do not operate in the vicinity of radio transmitter systems. Doing so will compromise function.Installation on tubular mast with separate mast fastening (see accessories).

    82562832 19.02.2014 3/6

    KNX/EIBWeather station Standard

  • Mounting and connecting the device

    Figure 5: Terminal box opened

    o Open terminal box.o Route the cables for the power supply and bus connection through one of the two cable

    entries (11) and into the terminal box (3).o Fasten lower part of terminal box e.g. to a building wall, tubular mast.o Connect supply voltage to connecting terminal (9).o Connect KNX bus line to connecting terminal (10).o Connect connecting plug of the sensor head (1) to sensor terminal (8) in terminal box (3).i The angular arm (2) may break when the terminal box is closed. The angular arm must not

    be used as a lever (Figure 4). o Set device on lower part of terminal box from above and snap in at bottom.

    Aligning the device

    Figure 6: Orienting the weather station

    o Align the sensor head in the appropriate direction or - depending on the detailed on-sitecircumstances - according to the alignment of the facade (Figure 6).

    82562832 19.02.2014 4/6

    KNX/EIBWeather station Standard

  • Dismantling the deviceo Insert screwdriver into the notch on the underside of the terminal box and carefully lift the

    device upwards.o Remove sensor connector from sensor terminal (8).

    4.2 CommissioningCommissioning the device

    Figure 7: Position of the programming LED and reed contact

    o Switch on the bus voltage.o Switch on supply voltage.o Hold the supplied programming magnet by the integrated reed contact (13).

    The programming LED (14) shows the programming state red.o Assign physical addresses and load application software into the device.o Note physical address on adhesive labels in terminal box (12) and in cover of the terminal

    box (Figure 5).The device is ready for operation.

    5 Appendix5.1 Technical dataKNX medium TP1Commissioning mode S-modeRated voltage KNX DC 21 ... 32 V SELVPower consumption KNX typical 450 mWConnection mode KNX Connection terminalExternal supplyRated voltage 24 V AC/DC SELVPower consumption typical 7.5 WConnection of power supply Connection terminalAmbient conditionsAmbient temperature -20 ... +55 °C (free of ice and dirt)Storage/transport temperature -40 ... +70 °CHousingDegree of protection IP 44 (in position for use)Protection class III

    82562832 19.02.2014 5/6

    KNX/EIBWeather station Standard

  • Dimensions W × H × D approx. 88 ×170 ×204 mm (with assemblyarm)

    Weight approx. 240 gTemperature sensorMeasuring range for temperature -20 ... +55 °CAccuracy ± 1 C (for wind speeds > 0.5 m/s)Wind sensorMeasuring range for wind 0 ... 40 m/sAccuracy 2 m/sPrecipitation sensorMeasuring range for precipitation Yes/No (binary)Sensitivity to precipitation Fine drizzleBrightness sensorsCompass directions east, south, westSpectral range 700 ... 1050 nmMeasuring range for brightness 1 ... 110 klxAccuracy 10 % (fm. ET)Twilight sensorDirection southSpectral range 700 ... 1050 nmMeasuring range for twilight 0 ... 674 lxAccuracy 10 % (fm. ET)

    5.2 AccessoriesPower supply Order No. 1024 00Additional power supply Order No. 2570 00Mast attachment for installation on free-standing masts

    Order No. 0848 00

    5.3 WarrantyThe warranty is provided in accordance with statutory requirements via the specialist trade.Please submit or send faulty devices postage paid together with an error description to yourresponsible salesperson (specialist trade/installation company/electrical specialist trade). Theywill forward the devices to the Gira Service Center.

    GiraGiersiepen GmbH & Co. KGElektro-Installations-Systeme

    Industriegebiet MermbachDahlienstraße42477 Radevormwald

    Postfach 12 2042461 Radevormwald

    Deutschland

    Tel +49(0)21 95 - 602-0Fax +49(0)21 95 - 602-191

    [email protected]

    82562832 19.02.2014 6/6

    KNX/EIBWeather station Standard

    1 Safety instructions2 Device components3 Function4 Information for electrically skilled persons4.1 Fitting and electrical connection4.2 Commissioning