1 shining the light on leds robert ebbert, lc led sales project manager – streetworks lighting...
TRANSCRIPT
1
Shining the Light on LEDs
Robert Ebbert, LC LED Sales Project Manager – Streetworks™
Lighting Certified by the National Council on Qualifications for the Lighting Professions
Member of the Illuminating Engineering Society
2
A History of Light Sources ~400,000 BCE - Fire is discovered. ~3000 BCE - Oil lamps are open bowls with a spout to hold the wick. ~400 - The candle is invented. 1809 - Sir Humphrey Davey demonstrates electrical discharge lighting
to the Royal Institution in London, using an open-air arc between two carbon rods. The result is a very intense, and very pure white light. Unfortunately, as the arc runs, carbon boils off and the rods wear away: constant attention must be paid to readjusting the arc, feeding more carbon in.
1841 - Frederick DeMoleyns patented incandescent lamp using filaments of platinum and carbon, protected by a vacuum.
1880 - Thomas Edison receives U.S. patent #223,898 for the carbon filament incandescent lamp.
1932 - Low pressure sodium lamps are first used commercially. 1934 - The high-pressure mercury lamp is introduced. 1938 - First commercial sale of the fluorescent lamp 1957 - The quartz halogen lamp (A.K.A. tungsten halogen lamp) is
invented. In conventional tungsten lamps, the filament metal slowly evaporates and condenses on the glass envelope, leaving a black stain. In this case, the halogen removes the deposited tungsten and puts it back on the filament.
1962 - First light emitting diode (LED) 1966 - Commercial introduction of the high pressure sodium lamp 1969 - A new form of metal halide lamp, the HMI lamp (mercury
medium arc iodides) is introduced. The H stands for mercury (atomic symbol "Hg"), M is for Metals and the I is for halogen components (iodide, bromide). It provides a daylight type spectrum.
LED vs Traditional Light Sources
No filaments like incandescent lamps. No electrodes like gas discharge lamps (HPS, Metal
Halide, and Fluorescent). No Mercury in the Light Source Instant On, Full Color, 100% Light; Cold Start Capable Promise of Long Life – Reduced Maintenance Costs
3
Strengths
Weakness High initial cost compared to traditional sources. Electronic LED driver life can be drastically reduced if
exposed to high heat levels. Electronic LED drivers provide only a fraction of the surge
protection that is offered by HID core and coil ballasts.
LED Luminaire and Component Testing
4
Reliability System Testing
– Humidity
– Salt Spray
– Water IPX6
– Dust IP6X
– Vibration testing
– Thermal testing on luminaires at -30°C (-30°F) degree to 40°C(104°F) standard, -
40°C to 50°C for certain models.
– Thermal testing on components from -40°C to 90°C
– Require UL accredited test laboratory
5
6
Light Control
HID vs. LED with overlay
Optics
0°
90°
100% Aimable Light0°
70° of Light Escapes Unaimed
70°
Point-By-Point (20’ MH, 80’ Spacing)
Ave Max Min Max/Min
1.6 4.3 0.35 12.3
Point-By-Point (20’ MH, 80’ Spacing)
Ave Max Min Max/Min
1.8 3.6 0.47 7.7
190W 11,000 lms 155W 9,500 lms
0°
0°
LED Chip
Lens
Photometric Testing
7
Integrating SphereIs used to measure the
color metrics (chromaticity, CCT, and CRI).
IES LM-79-08 Electrical and Photometric Measurements of
Solid-State Lighting Products– Luminaire based absolute photometry
• Total Luminous Flux• Luminous Intensity Distribution• Electrical Power• Luminous Efficacy (LPW - calculated)• Color Characteristics• Chromaticity• CCT• CRI
8Common product performance metricsCommon product performance metrics
GoniophotometerAn apparatus for measuring
the directional light distribution characteristics of
light sources, luminaires, media, and surfaces.
PLAN VIEW Luminaire
Mirror
Photocell
IndirectLight
Shield
Measuring Luminaire Performance
10
150 WATTS
Why the “lumens per watt method” of calculating lighting fixture performance alone does notequate to energy efficiency.
Although the luminaire on the left is 27% higher in fixture LPW, it produces less than half the average illumination on the ground
To give the same illumination as the lower LPW fixtures, over twice as many of the higher LPW fixtures would be needed, resulting in a net energy increase of 102%
150 WATTS
Same source, same ballast, different performance
25’
0.46 Average Illuminance 0.93 Average Illuminance
85 Lumens per Watt 67 Lumens per Watt
Three dimension rendering of light distributions and relative footcandles on groundHigh LWP post top on left, lower LPW shoebox on right
Luminaire Dirt Depreciation?
13
How much light is coming out of this HID luminaire?
HID (High Pressure Sodium) LED with IP66 optical enclosure
14
HID │LED LIGHT LOSS FACTORS
LDD (Luminaire Dirt Depreciation) 0.90 LDD (LUMINAIRE DIRT DEPRECIATION) 0.95
LLD (Lamp Lumen Depreciation) 0.90 LLD (Lamp Lumen Depreciation) 0.96
LLF = 0.9 * 0.90 = 0.81 LLF = 0.95 * 0.96 = 0.912
LLD = Mean Lumens (@ 50% of lamp life) / Initial Lumens (12,000 hours)
LLD = Mean Lumens (@ 50,000+ hours) / Initial Lumens
LLF = BF * LDD * LLDBF (Ballast Factor) 1.0 BF (Ballast Factor)
1.0
15
HID │LED Lumens 100 HPS (125 watts) 54 watt LED
100W HPS 9,500 lumens 1 square ~3,700 lumens
~70% optic eff. 6,650 lumens Included per LM-79 ~3,700 lumens
Street Side Lumens (53%) 3,524 lumens Street Side lumens (80%) 2,960 lumens
0.81 LLF 2,854 lumens 0.912 LLF 2,699 lumens
LED Product Providing Equal Task Lumens While Saving 57% Energy.
LED Product Providing Equal Task Lumens While Saving 57% Energy.
16
Quality of Light
Excellent Light Quality, No Sacrifice in PerformanceExcellent Light Quality, No Sacrifice in Performance
COLD LED (6000-6500K)High Pressure Sodium (2000K)
Metal Halide (Quartz, Ceramic)
(4000K)
Task Lumens and Light Distribution
17
100 watt HPS and 175MV OVX Cobra Head.
Large amount of spill light, hot spots under the pole and low light
levels between the poles.
54 watt LED with 2,643 lumens and AccuLED™ optics with majority of
light on the roadway.
Low amount of spill light with lower light levels below the poles
and higher minimum levels (3 times the HPS level) between the poles. Even distribution of light.
AccuLED™ LED 100 HPS 175 MV
Light control and distribution is the key to great lighting
25’ Mounting height, 150’ spacing, 6’ arm, 5’ setback, 30’ wide roadway
160’ between poles (320’ same side), staggered spacing 30’ MH.
18
The luminaires in the above photo feature an internal mirror optical system with initial lumen output of 6,959 lumens. Eliminating hot spots, raising minimum light levels and
controlling backlight produces amazing results. Optical distribution and control is the key to a great lighting project.
LED luminaires installed in Nebraska
External Shields
19
Controlled Optic Advantage Over External Shields
20
Type 2 Short , 7928 lumens, 78 lumens per watt, with light
more than 40’ behind the pole.
Internal Mirror Type 2 Short SL2 optics, 7403 lumens, 73 lumens per watt with light evenly dispersed 10’ to 23’ behind the pole for sidewalk
illumination.
Type 2 Short with an external shield, 6090 lumens, 60 lumens per watt, light
reduced to 20’ behind the pole.
40’ Grid
25’ MH
External shields can reduce luminaire efficiency by as much as 23%. Internal Mirror optics maintain luminaire efficiency by re-directing the
light evenly along the roadway.
21
Light control at night is an important health issue.
Unplug! Too Much Light at Night May Lead to
DepressionMood disorders join a long list of ailments linked
to late-night exposure to artificial lighting, TVs and computer screens
By Laura Blue | July 24, 2012 | 9
22
LED Type 3 Photometric Comparison
Type 3 short - 9,600 lumens Internal Mirror Type 3 short- 9,063 lumens
Comparison summary: Superior distribution patterns lead to increased pole spacing. High percentage of street side lumens, more light on the road. Reduced hot spot beneath the pole, even illumination along the
roadway.
40 foot grid, 25’ mounting height
Type 3 short - 9,354 lumens
Compare .5 FC lines, less lumens with better distribution.
23
LED luminaire with 13,730 lumens
Internal Mirror 10,999 lumens
How much light is on the roadway?24
Internal mirror LED with Type 2 Short optics, 7403 lumens (103 watts), 73 delivered lumens per
watt with light evenly dispersed 10’ to 23’ behind the luminaire for
sidewalk illumination.
Competitors 165 watt Induction luminaire (180 total watts)Type 3
Short with 8414 delivered lumens, 47 lumens per watt. Light behind
the pole for over 40’.
40’ Grid
25’ MH
LED vs Induction
Why field rotatable optics on a roadway fixture?
25
Single 2 square LED with one optical square
rotated 90
Illuminate the intersection and
roadway with a single luminaire.
30’ Mounting Height
LED post top comparison to 100 watt HPS and 175 watt MV
26
25’ Grid, 15’ Mounting Height
51 watts UTR 100 watt HPS (125 watts)
UTR 175 watt MV (205 watts)~50,000 hrs ~12,000 hrs
~12,000 hrs
Post Top LED comparison
27
25’ Grid, 15’ Mounting Height
51 watts (86 watts)
4,350 lumens3,880 lumens With 10% less lumens
the luminaire on the left is outperforming the competitors product
The optic on the left provides even
illumination along the sidewalk and roadway.
This competitor provides only 2 optical
distributions. The UTLD is available with 10
optical distributions to meet all your lighting
requirements.
Street side Street sideHouse side House side
IES LM-80-08 Measuring Lumen Maintenance of LED Light
Sources– Approved method for measuring lumen
depreciation of solid-state (LED) light sources, arrays and modules
– Does not cover measurement of luminaires– Does not define or provide methods for
estimation of life.• 55C, 85C and 3rd LED mfg
selected temperature• 6000 hours min testing
period. 10K preferred.• Minimum at least
every 1000 hours– Separate estimation
method (TM-21)
28
Consistent way to measure life-timeConsistent way to measure life-time
LM-80-08
LM-80 -- LED test standard to define Lumen Maint. Life:– L90 (hours): 90% lumen maintenance
– L70 (hours): 70% lumen maintenance
Does not consider ‘catastrophic’ failures. Does not cover predictive estimations or extrapolation. Test Method: Min. of 20 samples Testing (aging) at the LED case temperatures 55°C, 85°C, and a
3rd temp. selected by mfr., for 0 to 6000 h or longer, at every 1000 h. Ambient temperature within - 5°C from the case temperature.
Measured color and any failures shall also be reported. The ambient temperature during lumen and chromaticity
measurements shall be 25°C ± 1°C.
Rebel LED Flux Output at 1.0081 after 10,000 hours
30
Note 85°C case temperature lumen depreciation.
Delta UV at .0004 after 10,000 hours
31
Minimal kelvin temperature shift means white light over the life of the LED
32
This LED is showing 4.6 % depreciation after 6,000 hours at the 700mA drive current at a
case temperature of 85°C
33
This LED is showing a depreciation of 4% at 10,000 hours with a chromaticity shift of .0034 at the 85°C case
temperature at 460mA .
TM-21-11
LM-80 -- only an LED testing standard IES TM-21-11 -- mathematical framework for LM-80 data
and making useful LED lifetime projections
Key points of TM-21: Developed by major LED suppliers with support of
NIST, PNNL Projection limited to 6x the available LM-80 data set Projection algorithm: least squares fit to the data set L70, L80, L90, Lxx projections easily possible
Nomenclature: Lp(Yk)where p is Lumen Maintenance percentage and Y is length of LM-80 data set in thousands of hours ie: L85(10k)
TM-21 – Use the latest data
Initial data variability (i.e. “hump”) is difficult for models to evaluate (0-1000 hr)
Later data exhibits more characteristic decay curve of interest
• Non-chip decay (encapsulant, etc.) occurs early and with varying effects on decay curve
• Later decay is chip-driven and relatively consistent with exponential curve
• Verification with long duration data sets (>10,000 hr) shows better model to reality
fit with last 5,000 hours of 10,000 hour data
For 6,000 hours of data (LM-80 minimum) and up to 10,000 hours: Use last 5,000 hours
For > 10,000 hours: Use the last ½ of the collected data
TM-21, L70, L80, L90
36
Description of LED light source tested (Manufacturer, model, catalog number) LumiLeds Rebel ES
Sample Size 25
Number of Failures 0LED Drive Current Used in Test (mA) 1000
Test Duration (Hours) 10,000 Test Duration Used For Projection (Hours) 10,000
Projected Case Temperature (C) 67
1.2275E-06
B 1.0131
Calculated L70 (Hours) 301,194
Reported L70 (Hours) 60000
TM-21 limits reported L70 hours to 6 times the LED test data and combines the Luminaire thermal report information with the LED manufactures LM-80 data to
provide accurate prediction of lumen maintenance.
• L70 = 70% of initial light output. • L80 = 80% of the initial light output.
• L90 = 90% of the initial light output.
Zonal distribution of the fixture are broken up into 10 distinct sections.
Values are often in terms of a percentage of overall lamp lumens.
UH
UL
FVH
FH
FM
FL
BH
BVH
BM
BL
0° 30°
60°
80°
90°
180°
100°
30°
60°
80°
90°
100°
Luminaire Classification System (B.U.G.)
Any one rating is determined by the maximum rating obtained for that table. For example, if the BH zone is rated B1, the BM zone is
rated B2, and the BL zone is rated B1, then the backlight rating for the luminaire is B2.
Ingress Protection (IP) Ratings
38
ANSI C136 Exterior Label
C136.15 - American National Standard for Roadway and Area Lighting Equipment – Luminaire Field Identification
39
40
Class 2 LED Driver
41
Class 2 drivers =
low voltage to the LED
Class 1 LED Driver
42
Class 1 LED luminaires will require impact testing on the
LED due to high voltage to the
LED
Cool running drivers last longer.
43
Driver T case temperature will affect longevity.
→
44
Make sure the SPD meets UL1449
46
Check the kA rating of the SPD
47
48
Insufficient protection will reduce fixture life.Insufficient protection will reduce fixture life.
Does not display a UL or CSA marking; non-compliance with
Article 285.5
Does not describe short circuit current rating; non-compliance
with Article 285.6
Does not incorporate fusing such that SPD becomes
disconnected after MOV failure; non-compliance with Article
285.27
May not be 14AWG Wires; possible non-compliance with
Article 285.26
What to Look For on a Surge Protector
IES RP8 Table
49
Recommended minimum illuminance levels and maximum uniformity levels for roadways
50
The IES file will provide the most
information on the luminaire.
• IES classification •Total lumens • Wattage
51
Street Side Lumens vs House Side Lumens and BUG Ratings
LED Control Options
LED Luminaire integral motion sensor – bi-level dimming and continuous dimming.
Luminaire mounted photo controls. Multiple circuits for bi-level dimming. Wireless monitoring and dimming.
52
Wireless remote monitoring and dimming
53
NEMA – Metal Halide Rulemaking
Expect requirement for lower wattage Metal Halide to have requirements between 88 – 92%. This could push to electronics on most products less than 200 Watt.
Requirement on the higher wattages could possibly be 92 – 94%. This will likely require a redesign of current HID Magnetic designs.
It is possible that this will drive the price of Metal Halide up at a time when LED products are becoming more affordable. This action could expedite the acceptance of Solid State Lighting
HID Lamp Rulemaking
Expect Final Rule to be set in 2013
Expect Effective date to be 2016
Focus will be on Probe Start Metal Halide Lamps - Likely in wattages from 150 – 500 W
Will also include Mercury Lamp Phase out in the event Legislation does not pass
55
Improper installation leads to poor performance
56
How not to install the LED luminaire.
Make sure the proper brackets are provided for proper luminaire orientation and installation.
PTC Parking Lot-HID
57
Before: HID Source Calculation Summary Unit Avg Max Min Avg/Min Ratio Max/Min
Parking Lot Illuminance FC 1.4 4.3 .26 5.38 16.53
400W Metal Halide 452 Watts (4000K, 65 CRI)
PTC Parking Lot -LED
After: LED Source Calculation Summary Unit AverageMaximu
mMinimu
m Average/Minimum Ratio Maximum/Minimum Ratio
Parking Lot Illuminance FC 2.53 4.1 1.4 1.81 2.93
58
After: LED Source Calculation Summary Unit Avg Max Min Avg/Min Ratio Max/Min Ratio
Parking Lot Illuminance FC 2.5 4.1 1.4 1.81 2.93
309W LED (4000K, Nominal 70 CRI)32% Energy Saving
PTC Parking Lot -LED
After: LED Source Calculation Summary Unit AverageMaximu
mMinimu
m Average/Minimum Ratio Maximum/Minimum Ratio
Parking Lot Illuminance FC 2.53 4.1 1.4 1.81 2.93
59
After: LED Source Calculation Summary Unit Avg Max Min Avg/Min Ratio Max/Min Ratio
Parking Lot Illuminance FC 1.9 3.1 1.1 1.81 2.93
206 W LED (4000K, nominal 70 CRI)54% Energy Saving
PTC Parking Lot -LED
After: LED Source Calculation Summary Unit AverageMaximu
mMinimu
m Average/Minimum Ratio Maximum/Minimum Ratio
Parking Lot Illuminance FC 2.53 4.1 1.4 1.81 2.93
60
After: LED Source Calculation Summary Unit Avg Max Min Avg/Min Ratio Max/Min Ratio
Parking Lot Illuminance FC 1.4 2.3 .8 1.81 2.93
103 W LED (4000K, nominal 70 CRI)77% Energy Saving
Existing 400 (464 watt) HPS Luminaire
61
Existing HPS luminaires with 2100K, 22 CRI provide high footcandle levels, but poor visibility and poor color rendition.
260 watt LED luminaire
62
Retrofitting with the premium LED optical system with 4000K color temperature and nominal 70 CRI LEDs provides visual clarity and energy
savings using existing pole positions and mounting heights. Even distribution of light is the key to great lighting.
63
175 watt Metal Halide Luminaire
Media companyAtlanta, Georgia
Before
210W per fixture
64
LED Luminaire
Media companyAtlanta, Georgia
After
53W per fixture
65
HPS to LED conversion on the New Jersey Turnpike
66
241 watt LED Luminaires on 40’ poles New Jersey
Turnpike
Questions?
67