Introduction

A Utility Breaker is a spare breaker that can be used as a:

Feeder replacement breaker Totalizing breaker Bus tie breaker

Page 3: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

3

History

Mid 1960’s-CPL began installing utility breakers

1994- Utility breakers removed from substation design standard

Today- 41 Utility breakers available for service in TCC (old CPL)

0 Utility breakers in TNC (old WTU)

Page 4: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

4

SCADA 1-LINE OUT OF SERVICE

Page 5: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

5

SCADA 1-LINE AS FDR REPLACEMENT

Page 6: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

6

SCADA 1-LINE AS TOTALIZER

Page 7: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

7

SCADA 1-LINE AS BUS TIE

Page 8: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

8

PICTURE OF SWITCHES

Page 9: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

9

PICTURE OF SWITCHES

Page 10: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

10

PICTURE OF SWITCHES

Page 11: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

11

Page 12: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

12

Page 13: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

13

PICTURE OF CONTROL PANEL

Page 14: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

14

PICTURE OF SELECTOR SWITCH

Page 15: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

15

Relay Transfer Switch

Page 16: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

16

Relay Transfer Switch Operations

Utility Breaker CT secondaries are switched to Utility Breaker overcurrent relays.

Utility Breaker relay trips are switched to Utility Breaker trip coil.

Page 17: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

17

Relay Transfer Switch Operations

Utility Breaker CT secondaries are switched to #3 Transformer Differential Relays and #3 Transformer Totalizing relays.

#3 Differential trips and Totalizing trips are switched to Utility Breaker trip coil.

Page 18: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

18

Relay Transfer Switch Operations

Utility Breaker CT secondaries are shorted.

Utility Breaker overcurrent relay trips remain switched to Utility Breaker trip coil.

Page 19: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

19

Utility Breaker Cost

Installation costs is 40%-50% higher than feeder breaker due to: 1- Utility Breaker or 2- Feeder

Breakers can fit in standard 20’x20’ bay

Breaker, risers, and switches rated for 2000 amps vs. 1200 amps

More cable work for CT and trip circuits

Page 20: 1 The Utility Breaker Tim Heard DDC Engineer AEP Texas SWEDE 2006

20

BENEFITS

Huge impact on SAIDI/ CAIDI when dealing with Substation related outages

Time/ Labor savings in switching for routine maintenance