    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    Voltage & Frequency Relay 7RW600

  • 7/28/2019 10-7RW600E.pdf

    2/10

    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    Voltage and frequency relay 7RW600

    ?Based on 7SJ600, with 2 voltage inputs

    ? Implemented functions/ options

    ? U>>; U>; U; f>; U>; U: f(4-step frequency and df/dt supervision)

    ? U>>; U>; U>

    ?Local and remote operation with DIGSI

    ?Display of measured values,stored annunciations

    ?Fault recording (momentary and RMS values)

  • 7/28/2019 10-7RW600E.pdf

    3/10

    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    4-step frequency supervision (f>, f

  • 7/28/2019 10-7RW600E.pdf

    4/10

    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    Over- and undervoltage supervision (U>, U

  • 7/28/2019 10-7RW600E.pdf

    5/10

    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    Rate-of-change-of-frequency supervision df/dt>

    ?Frequency calculations via filter algorithms; calculation of themomentary frequency change

    ?Suppression of interferences

    ?4-step rate-of change-of frequency supervision responding to

    frequency reduction + additional frequency release?Range of frequency change: 1 - 10 Hz/s;

    ?Connection of voltage measurement input U (terminal 7-8)to the line-to-line voltage of the VTs

    ?Blocking of frequency measurement on occurance of undervoltage

    ?

    Application: load sheddingnetwork disconnection

  • 7/28/2019 10-7RW600E.pdf

    6/10

    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    Overfluxing (overexcitation) protection U/f>

    ?Frequency and voltage calculation via filter algorithms;calculation of the overexcitation U/f (proport. induction B)

    ?Suppression of interferences

    ?one definable inverse-time characteristic (thermal replica)

    and one definite-time stage?Frequency range: 25 Hz to 70 Hz

    ?Connection of voltage measurement input U (terminal 7-8)to the line-to-line voltage of the VTs

    ?Correction of VT mismatching

    ?

    Application: overexcitation protection fortransformers and generators

  • 7/28/2019 10-7RW600E.pdf

    7/10

    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    7RW600 connection diagramHousing for panel flush mounting

    BE 1

    11

    12

    14

    15

    13

    RS 485

    27

    28

    29

    7

    8

    9

    10

    U

    Ux

    U >, U >>, U , f , df/dt >

    Ux >, Ux >>, Ux , Ux >>, Ux < )

    U

    Ux

    7RW600

    .

    . . .. ...

  • 7/28/2019 10-7RW600E.pdf

    9/10

    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    7RW600 Connection example 2

    L 1 L 2 L 3

    7RW600

    U

    protection functionacc. version

    ( e.g. U, f, df/dt, U/f )

    Ux

    .

    .

    .

    ...

    .

    voltage supervision

    only

    ( e.g. Ux > )

    e

    n.

    Input Ux can also be connected to a different VT

  • 7/28/2019 10-7RW600E.pdf

    10/10

    Voltage/ frequency relay7RW600

    EV SProtection and Substation Control Systems

    7RW600 Technical data

    Auxiliary voltage 24/ 48 V DC60/ 110/ 125 V DC220/ 250 V DC; 115 V AC

    Rated voltage UN 100 - 125 V

    Voltage protection:U>, t; U>>, t

    U, t

    7 pts U/f preselected t: 0 - 20000sin steps of 1s

    U/f: 1.00-1.40; t: 0.00 - 60.00 sin steps of 0.01 in steps of 10ms