    10 Important Definitions Applied To Low Voltage Fuses

    Low-voltage disconnect switch with fuses max. 800A, 690V (photo credit: DirectIndustry.com)

    Low Voltage Fuses //

    The simplest overcurrent protective devices

    The simplest of all overcurrent protective devices are fuses. A fuse is an overcurrent protective device with a circuit-opening fusible part that is heated and severed by the passage of the overcurrent through it.

    Let’s talk about ten important definitions that are of interest for low voltage fuses //

    1.  Ampere rating

    2. Current-limiting fuse

    3. Dual-element fuse

    4. I2t

    5. Interrupting rating

    http://electrical-engineering-portal.com/10-important-definitions-applied-to-low-voltage-fuses?utm_source=Technical+Articles&utm_campaign=f2f6b68e2a-RSS_EMAIL_CAMPAIGN_MAILCHIMP&utm_medium=email&utm_term=0_ae069f0d91-f2f6b68e2a-315493569&mc_cid=f2f6b68e2a&mc_eid=07c67c9d97http://electrical-engineering-portal.com/10-important-definitions-applied-to-low-voltage-fuses?utm_source=Technical+Articles&utm_campaign=f2f6b68e2a-RSS_EMAIL_CAMPAIGN_MAILCHIMP&utm_medium=email&utm_term=0_ae069f0d91-f2f6b68e2a-315493569&mc_cid=f2f6b68e2a&mc_eid=07c67c9d97http://electrical-engineering-portal.com/

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    2/10

    6. Melting time

    7. Peak let-through current (Ip)

    8. Time delay

    9. Total clearing time

    10. Voltage rating

    1. Ampere rating

    The RMS current that the fuse can carry continuously without deterioration and without exceeding temperature rise

    limits. In accordance with NEC article 210.20 a fuse (or any branch-circuit overcurrent device) should not be loaded

    continuously to over 80% of its ampere rating unless the assembly, including the fuse and enclosure, is listed for 

    operation at 100% of its rating.

    http://electrical-engineering-portal.com/download-center/books-and-guides/power-substations/technical-considerations-lv-switchboards

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    3/10

    NH low-voltage fuse 400A, 120kA, 400- 1000V (photo credit: DirectIndustry.com)

    Go back to LV Fuse Definitions ↑

    2. Current-limiting fuse

     A current-limiting fuse interrupts all available currents its threshold current and below its maximum interrupting

    rating.

     A current-limiting fuse limits the clearing time at rated voltage to an interval equal to or less than the first major or 

    symmetrical loop duration. It limits peak let-through current to a value less than the peak current that would be

    possible with the fuse replaced by a solid conductor of the same impedance.

    Go back to LV Fuse Definitions ↑

    3. Dual-element fuse

     A cartridge fuse having two or more current-responsive elements in series in a single cartridge. The dual-element

    design is a construction technique frequently used to obtain a desired time-delay response characteristic.

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    4/10

    Fusetron Dual-Element Fuse 35A 250VAC

    Go back to LV Fuse Definitions ↑

    4. I2t

     A measure of heat energy developed within a circuit during the fuse’s melting or arcing . The sum of melting and

    arcing I2t is generally stated as total clearing I2t.

    Go back to LV Fuse Definitions ↑

    5. Interrupting rating

    The rating based upon the highest RMS current that the fuse is tested to interrupt under the conditions specified.

    Go back to LV Fuse Definitions ↑

    6. Melting time

    The time required to melt the current-responsive element on a specified overcurrent.

    Go back to LV Fuse Definitions ↑

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    5/10

    7. Peak let-through current (Ip)

    The maximum instantaneous current through a current-limiting fuse during the total clearing time.

    Go back to LV Fuse Definitions ↑

    8. Time delay

    For Class H, K, J, and R fuses, a minimum opening time of 10s to an overload current five times the ampere rating

    the fuse, except for Class H, K, and R fuses rated 0-30 A, 250 V, in which case the opening time can be reduced to 8

    For Class G, Class CC, and plug fuses, a minimum time delay of 12s on an overload of twice the fuses’

    ampere rating.

    Time delay low voltage fuses (photo credit: ife-p.org)

    Go back to LV Fuse Definitions ↑

    9. Total Clearing time

    The total time between the beginning of the specified overcurrent and the final interruption of the circuit, at rated

    voltage.

    Go back to LV Fuse Definitions ↑

    10. Voltage Rating

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    6/10

    The RMS voltage at which the fuse is designed to operate. All low voltage fuses will operate at any lower voltage

    (note that this is characterized as AC or DC, or both).

    Go back to LV Fuse Definitions ↑

    Low voltage fuses are classified according to the standard to which they are designed. The 1 table lists the various

    fuse classes and pertinent data for each class.

    Fuses, like most protective devices, exhibit inverse time-current characteristics. A typical fuse time-current

    characteristic is shown in Figure 1.

    Figure 1 – Typical class J fuse time-current characteristic

    Logarithmic scales are used for both the time and current axes, in order to cover a wide range.

    The characteristic represents a band of operating times for which the lower boundary is the minimum melting time

    https://en.wikipedia.org/wiki/IEC_60269

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    7/10

    curve, above which the low voltage fuses can be damaged. The upper boundary is the total clearing time curve, abov

    which the fuse will open. For a given fault current, the actual fuse opening time will be within this band.

    Table 1 – Low Voltage fuse classes //

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    8/10

    Table 1 – Low Voltage fuse classes

    In some cases the fuse average melting time only is given.  This can be treated as the fuse opening time with atolerance of ±15%. The -15% boundary is the minimum melting time and the +15% boundary is the total clearing

    time. Note that the time-current characteristic does not extend below 0.01 seconds. This is due to the fact that below

    0.01 seconds the fuse is operating in its current-limiting region and the fuse I2t is of increasing importance.

    The time-current characteristic curves are used to demonstrate the coordination between protective

    devices in series. The basic principle of system protection is that for a given fault current ideally only the

    device nearest the fault opens, minimizing the effect of the fault on the rest of the system.

    This principle is known as selective coordination and can be analyzed with the use of the device time-currentcharacteristic curves.

     As an example, consider a 480 V system with two sets of low voltage fuses in series, with a system available fault

    current of 30,000 A . Bus “A” is protected using 400 A class J fuses which supply, among others, bus “B.” Bus “B” is

    protected using 100 A class J fuses. Coordination between the 400 A and 100 A fuses  can is shown via the time-

    current curves of figure 2, along with a one-line diagram of the part of the system under consideration.

    Because the time bands for the two fuses do not overlap, these are coordinated for all operating times above 0.01

    seconds.

    It can also be stated that these two sets of fuses are coordinated through approximately 4200 A, since at 4200 A Fu

     A has the potential to begin operating in its current-limiting region. Fuse B has the potential to begin operating its

    current-limiting region at 1100 A. For currents above approximately 4000 A , therefore, both sets of fuses have the

    potential to be operating in the current-limiting region.

    When both sets of fuses are operating the current-limiting region the time-current curves cannot be

    used to the determine coordination between them.

    Instead, for a given fault current the minimum melting I2t for Fuse A must be greater than the maximum clearing I 2t fo

    http://electrical-engineering-portal.com/selective-coordination-with-circuit-breakers

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    9/10

    Fuse B. In practice, instead of publishing I2t data fuse manufacturers typically publish ratio tables showing the

    minimum ratios of fuses of a given type that will coordinate with each other.

    Figure 2 – Fuse coordination example

    Low voltage fuse AC interrupting ratings  are based upon a maximum power factor of 0.2, corresponding to amaximum X/R ratio of 4.899. In order to evaluate a low voltage fuse’s interrupting rating on a system with a higher 

    X/R ratio the system symmetrical fault current must be multiplied by a multiplying factor:

  • 8/16/2019 10 Important Definitions Applied to Low Voltage Fuses

    10/10

    where:

    The available symmetrical fault current multiplied by the multiplying factor (MULT) per formula above can be compare

    to the fuse interrupting rating.

    The use of low voltage fuses requires a holder  and a switching device in addition to the fuses themselves. Because

    they are single-phase devices, a single blown fuse from a three-phase set will cause a single-phasing condition, whic

    can lead to motor damage.

    Replacing fuses typically requires opening equipment doors and/or removing cover panels.

     Also, replacement low voltage fuses must be stocked to get a circuit with a blown fuse back on-line quickly. For these

    reasons, the use of low voltage fuses in modern power systems is generally discouraged. For circuit breakers that

    have a short-time rating.

    Reference //  System Protection – Bill Brown, P.E., Square D Engineering Services