10 Important Definitions Applied To Low Voltage Fuses
Low-voltage disconnect switch with fuses max. 800A, 690V (photo credit: DirectIndustry.com)
Low Voltage Fuses //
The simplest overcurrent protective devices
The simplest of all overcurrent protective devices are fuses. A fuse is an overcurrent protective device with a circuit-opening fusible part that is heated and severed by the passage of the overcurrent through it.
Let’s talk about ten important definitions that are of interest for low voltage fuses //
1. Ampere rating
2. Current-limiting fuse
3. Dual-element fuse
4. I2t
5. Interrupting rating
http://electrical-engineering-portal.com/10-important-definitions-applied-to-low-voltage-fuses?utm_source=Technical+Articles&utm_campaign=f2f6b68e2a-RSS_EMAIL_CAMPAIGN_MAILCHIMP&utm_medium=email&utm_term=0_ae069f0d91-f2f6b68e2a-315493569&mc_cid=f2f6b68e2a&mc_eid=07c67c9d97http://electrical-engineering-portal.com/10-important-definitions-applied-to-low-voltage-fuses?utm_source=Technical+Articles&utm_campaign=f2f6b68e2a-RSS_EMAIL_CAMPAIGN_MAILCHIMP&utm_medium=email&utm_term=0_ae069f0d91-f2f6b68e2a-315493569&mc_cid=f2f6b68e2a&mc_eid=07c67c9d97http://electrical-engineering-portal.com/
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
2/10
6. Melting time
7. Peak let-through current (Ip)
8. Time delay
9. Total clearing time
10. Voltage rating
1. Ampere rating
The RMS current that the fuse can carry continuously without deterioration and without exceeding temperature rise
limits. In accordance with NEC article 210.20 a fuse (or any branch-circuit overcurrent device) should not be loaded
continuously to over 80% of its ampere rating unless the assembly, including the fuse and enclosure, is listed for
operation at 100% of its rating.
http://electrical-engineering-portal.com/download-center/books-and-guides/power-substations/technical-considerations-lv-switchboards
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
3/10
NH low-voltage fuse 400A, 120kA, 400- 1000V (photo credit: DirectIndustry.com)
Go back to LV Fuse Definitions ↑
2. Current-limiting fuse
A current-limiting fuse interrupts all available currents its threshold current and below its maximum interrupting
rating.
A current-limiting fuse limits the clearing time at rated voltage to an interval equal to or less than the first major or
symmetrical loop duration. It limits peak let-through current to a value less than the peak current that would be
possible with the fuse replaced by a solid conductor of the same impedance.
Go back to LV Fuse Definitions ↑
3. Dual-element fuse
A cartridge fuse having two or more current-responsive elements in series in a single cartridge. The dual-element
design is a construction technique frequently used to obtain a desired time-delay response characteristic.
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
4/10
Fusetron Dual-Element Fuse 35A 250VAC
Go back to LV Fuse Definitions ↑
4. I2t
A measure of heat energy developed within a circuit during the fuse’s melting or arcing . The sum of melting and
arcing I2t is generally stated as total clearing I2t.
Go back to LV Fuse Definitions ↑
5. Interrupting rating
The rating based upon the highest RMS current that the fuse is tested to interrupt under the conditions specified.
Go back to LV Fuse Definitions ↑
6. Melting time
The time required to melt the current-responsive element on a specified overcurrent.
Go back to LV Fuse Definitions ↑
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
5/10
7. Peak let-through current (Ip)
The maximum instantaneous current through a current-limiting fuse during the total clearing time.
Go back to LV Fuse Definitions ↑
8. Time delay
For Class H, K, J, and R fuses, a minimum opening time of 10s to an overload current five times the ampere rating
the fuse, except for Class H, K, and R fuses rated 0-30 A, 250 V, in which case the opening time can be reduced to 8
For Class G, Class CC, and plug fuses, a minimum time delay of 12s on an overload of twice the fuses’
ampere rating.
Time delay low voltage fuses (photo credit: ife-p.org)
Go back to LV Fuse Definitions ↑
9. Total Clearing time
The total time between the beginning of the specified overcurrent and the final interruption of the circuit, at rated
voltage.
Go back to LV Fuse Definitions ↑
10. Voltage Rating
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
6/10
The RMS voltage at which the fuse is designed to operate. All low voltage fuses will operate at any lower voltage
(note that this is characterized as AC or DC, or both).
Go back to LV Fuse Definitions ↑
Low voltage fuses are classified according to the standard to which they are designed. The 1 table lists the various
fuse classes and pertinent data for each class.
Fuses, like most protective devices, exhibit inverse time-current characteristics. A typical fuse time-current
characteristic is shown in Figure 1.
Figure 1 – Typical class J fuse time-current characteristic
Logarithmic scales are used for both the time and current axes, in order to cover a wide range.
The characteristic represents a band of operating times for which the lower boundary is the minimum melting time
https://en.wikipedia.org/wiki/IEC_60269
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
7/10
curve, above which the low voltage fuses can be damaged. The upper boundary is the total clearing time curve, abov
which the fuse will open. For a given fault current, the actual fuse opening time will be within this band.
Table 1 – Low Voltage fuse classes //
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
8/10
Table 1 – Low Voltage fuse classes
In some cases the fuse average melting time only is given. This can be treated as the fuse opening time with atolerance of ±15%. The -15% boundary is the minimum melting time and the +15% boundary is the total clearing
time. Note that the time-current characteristic does not extend below 0.01 seconds. This is due to the fact that below
0.01 seconds the fuse is operating in its current-limiting region and the fuse I2t is of increasing importance.
The time-current characteristic curves are used to demonstrate the coordination between protective
devices in series. The basic principle of system protection is that for a given fault current ideally only the
device nearest the fault opens, minimizing the effect of the fault on the rest of the system.
This principle is known as selective coordination and can be analyzed with the use of the device time-currentcharacteristic curves.
As an example, consider a 480 V system with two sets of low voltage fuses in series, with a system available fault
current of 30,000 A . Bus “A” is protected using 400 A class J fuses which supply, among others, bus “B.” Bus “B” is
protected using 100 A class J fuses. Coordination between the 400 A and 100 A fuses can is shown via the time-
current curves of figure 2, along with a one-line diagram of the part of the system under consideration.
Because the time bands for the two fuses do not overlap, these are coordinated for all operating times above 0.01
seconds.
It can also be stated that these two sets of fuses are coordinated through approximately 4200 A, since at 4200 A Fu
A has the potential to begin operating in its current-limiting region. Fuse B has the potential to begin operating its
current-limiting region at 1100 A. For currents above approximately 4000 A , therefore, both sets of fuses have the
potential to be operating in the current-limiting region.
When both sets of fuses are operating the current-limiting region the time-current curves cannot be
used to the determine coordination between them.
Instead, for a given fault current the minimum melting I2t for Fuse A must be greater than the maximum clearing I 2t fo
http://electrical-engineering-portal.com/selective-coordination-with-circuit-breakers
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
9/10
Fuse B. In practice, instead of publishing I2t data fuse manufacturers typically publish ratio tables showing the
minimum ratios of fuses of a given type that will coordinate with each other.
Figure 2 – Fuse coordination example
Low voltage fuse AC interrupting ratings are based upon a maximum power factor of 0.2, corresponding to amaximum X/R ratio of 4.899. In order to evaluate a low voltage fuse’s interrupting rating on a system with a higher
X/R ratio the system symmetrical fault current must be multiplied by a multiplying factor:
-
8/16/2019 10 Important Definitions Applied to Low Voltage Fuses
10/10
where:
The available symmetrical fault current multiplied by the multiplying factor (MULT) per formula above can be compare
to the fuse interrupting rating.
The use of low voltage fuses requires a holder and a switching device in addition to the fuses themselves. Because
they are single-phase devices, a single blown fuse from a three-phase set will cause a single-phasing condition, whic
can lead to motor damage.
Replacing fuses typically requires opening equipment doors and/or removing cover panels.
Also, replacement low voltage fuses must be stocked to get a circuit with a blown fuse back on-line quickly. For these
reasons, the use of low voltage fuses in modern power systems is generally discouraged. For circuit breakers that
have a short-time rating.
Reference // System Protection – Bill Brown, P.E., Square D Engineering Services
http://electrical-engineering-portal.com/fuse-in-low-voltage-systems