BY: VIJAY SHARMA ENGINEER 120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS Excerpt from G4 InverCharge Series Manual

Upload: trinhnhu

Post on 01-Feb-2018

227 views

Category:

Documents


3 download

TRANSCRIPT

Page 1: 120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE - · PDF file1.1Service Entrance panel For 120 / 240 VAC Split phase AC power Distribution ... 120 / 240 VAC SINGlE SplIt phASE MultI-WIrE

BY:

VIJAY SHARMA ENGINEER

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITSExcerpt from G4 InverCharge Series Manual

Page 2: 120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE - · PDF file1.1Service Entrance panel For 120 / 240 VAC Split phase AC power Distribution ... 120 / 240 VAC SINGlE SplIt phASE MultI-WIrE

| SAMLEX AMERICA SAMLEX AMERICA |

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS

1

i INFO

For purposes of explaining the concept of Multi-wire Branch Circuits, Neutral to Ground bonding and Equipment Grounding Conductor (EGC) have not been shown in the schematic diagrams.

1.0 120/240 VAC SINGlE SplIt phASE SyStEM Inverters and Inverter Chargers are frequently connected to a building / structure / house that has been previously completely wired for 120 / 240

VAC Single Split Phase System and has a standard Service Entrance Panel / Load Center / Distribution Panel – See Fig. 1.

120/240 VAC Single Split Phase Utility Power to the building / structure / house is fed from a Distribution Transformer that is either mounted on a utility pole (feeds through overhead lines) or on the ground on a concrete pad (Pad mounted, feeding through underground lines). This power enters the building / structure / house through the Service Entrance Panel for further internal distribution.

1.1 Service Entrance panel For 120 / 240 VAC Split phase AC power Distribution

Fig. 1 below illustrates the residential 120 / 240 VAC, Single Split Phase, 3- Pole, 4 Wire Grounding System, which was inherited from Edison's early DC distribution networks.

120 / 240 VAC Split Phase Electrical power from the utility (called Service)is fed through an electrical power meter to a load center / breaker panel for further distribution. This panel is called the Service Entrance Panel. This panel normally has the following components:

• MainIncomingCircuitBreaker–e.g.200Acapacity

• CircuitBreakersfeedingvariousbranchcircuits– e.g. 15 A , 20 A, 30 A, 50 A capacities

• BusbarforGroundedConductor(GC)/Neutral

• BusbarforEquipmentGroundingConductors(EGC)

• BusbarforconnectiontoGroundingElectrode(GE)

• SystemBondingJumper(SBJ)

Fig. 1: 120 / 240 VAC Single Split Phase, 3-Wire Distribution System

ABABABABABAB

BABABABABABA

Circuit Breakers ‘A’ connected to Hot Leg L1 (Phase A)

Circuit Breakers ‘B’ connected to Hot Leg L2 (Phase B)

SERVICE ENTRANCE PANEL

Distribution Voltage*

Distribution Transformer

* Distribution Voltage may be 2.4 kV, 7.2 kV or 12.47 kV** NOTE: The phase of Hot Leg 2 (Phase B) is in the opposite direction - i.e., 180° apart from the phase of Hot Leg L1 (Phase A)

Hot Leg L1 (Phase A), Red Wire

Hot Leg L2 (Phase B), Black Wire

Neutral, White Wire

GND

Neutral Terminal Bar

N

L1

N

L2

L1

L2

120 VACBranch Circuit 1

120 VACBranch Circuit 2

240 VACBranch Circuit 3

**120 VAC 240 VAC

**120 VAC

Main Breaker

GND

Page 3: 120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE - · PDF file1.1Service Entrance panel For 120 / 240 VAC Split phase AC power Distribution ... 120 / 240 VAC SINGlE SplIt phASE MultI-WIrE

SAMLEX AMERICA |

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS

2

The primary side of the Distribution Transformer is connected between Ground and one of the 2400V, 7.2 kV, 12.47 kV, 13.2 kV or 13.8 kV phasesoftheutilitycompany's3-PhaseDistributionNetwork.ThesecondaryoftheDistributionTransformerhasagroundedcentertapandiswound in a manner that supplies two 120 VAC phases which are 180° out of phase with each other (Split Phases). In urban areas, one Distribution Transformer typically supplies 1-6 residences.

The center-tapped configuration of the secondary side of the Distribution Transformer provides following voltages to the Service Entrance Panel:

• 120VACbetweentheHotLegL1(PhaseA,Redwire)andthegrounded,centertappedNeutral(Whitewire).TheoscilloscopetraceofthevoltagewaveformbetweentheHotLegL1andNeutralshowsthevoltagerisinginthePositivedirectionatthestartofthewaveform

• 120VACbetweentheHotLegL2(PhaseB,Blackwire)andthegrounded,centertappedNeutral(Whitewire).PleasenotethatthecorrespondingoscilloscopetraceofthevoltagewaveformbetweentheHotLegL2andNeutralshowsthevoltagerisingintheNegativedirection at the start of the waveform. this indicates that the two 120 VAC voltages are 180 degrees out of phase

• 240VACbetweentheHotLegL1(PhaseA,Redwire)andtheHotLegL2(PhaseB,Blackwire)

A part of a typical Service Entrance Panel with interleaved type of bus bar arrangement with 2-columns of branch circuit breakers (marked “A” and“B”)isshowninFig.8.1.EachFullSizedBreaker(marked“A”or“B”)originatesontheoppositephasefromtheoneaboveorbelowit.Breakersmarked“A”areconnectedtotheHotLegL1(PhaseA)andbreakersmarked“B”areconnectedtotheHotLegL2(PhaseB).GoingdownacolumnofFullSizeBreakers,theywillbeinaphasesequenceofA-B-A-B…

• 120VACbranchcircuitloadsareconnectedbetweenabreakeronPhaseA(HotLegL1,Redwire)andNeutral(N,Whitewire)asshownforBranchCircuit1orbetweenabreakeronPhaseB(HotLegL2,Blackwire)andNeutral(N,Whitewire)asshownforBranchCircuit2

• 240VbranchcircuitloadsareconnectedbetweenabreakeronPhaseA(HotLegL1,Redwire)andPhaseB(HotLegL2,Blackwire)asshownforBranchCircuit3.

2.0 MultI-WIrE BrANCh CIrCuItS As explained above, in a utility-connected, 120 / 240 VAC Single Split Phase System, the 120 / 240 VAC power consists of two 120 VAC lines

viz.HotL1(PhaseA,Redwire)andHotL2(PhaseB,Blackwire)thatare180degreesoutofphasewithrespecttothecentertapped,groundedNeutral(Whitewire)–seeFig.1

Itispossibletowiretwoseparate120VACBranchCircuitsfedfromthe2splitphasesHotL1(PhaseA,Redwire)andHotL2(PhaseB,Blackwire)usingasinglecommonNeutral(Whitewire)insteadoftwoseparateNeutrals(Whitewires)–Seethetwo15ABranchCircuitsfeedingthe2receptaclesshowninFigs.8.4.ThistypeofconnectioniscalledaMulti-wireBranchCircuit.Asthephasesofthetwo15A,120VACBranchCircuitsfeedingthe2receptaclesare180degreesapartandopposeeachother,thenetcurrentflowinginthecommonNeutral(Whitewire)willbeequaltothedifferenceofthecurrentsinthetwoBranchCircuits(15A–15A=0A).ThemaximumcurrentflowinginthecommonNeutralwillbelimitedtothebreakercapacity(MaximumcurrentwillflowinthecommonNeutralwhenoneofthesplitphasebranchcircuitsisnotloadedandtheloadedsplitphasebranchcircuitisdrawingitsfullratedcapacity).PropersafetyguidelinesforMulti-wireBranchCircuitsaretobeadheredtoaslaiddowninSection100oftheNationalElectricalCode(NEC).

WArNING!

Never remove the Neutral (White wire) from the Neutral terminal Bar in the Service Entrance panel / load Center / Distribution panel if the phase conductors are energized — it could be part of a Multi-wire Branch Circuit, and removing it could damage the connected electrical loads / cause a fire.

removal of the Neutral wire will amount to the two 120 VAC loads being connected in series across 240 VAC. If the impedances of the two 120 VAC loads are not equal (have different Watt ratings), the load with the higher impedance (higher watt rating) will see a dangerous over voltage condition > 120 VAC and may reach 240 VAC in case the other load is shorted (please see example in Fig 2 on page 3).

2.1 Examples Of Multi-Wire Branch Circuits

ThemostcommonMulti-wireBranchCircuitisforthedishwasheranddisposalcircuits.Othercommonusesareforlightingcircuits,forthetwosmall appliance branch circuits required at the kitchen counters and for “home runs” back to a panel. The idea is that the electrician can save the costofinstallinganotherwirebyusingtheMulti-wireBranchCircuitfor2circuitsgoingtoapproximatelythesameareainthehouse

2.2 recognizing Multi-Wire Branch Circuits

TheNECrequiresthatMulti-wireBranchCircuitsinsome,butnotall,casesuseatwo-polecircuitbreakersothatbothcircuitsaredeadatthesame time under fault conditions and for servicing. This two-pole, side-by-side circuit breaker rated at 15 or 20 amps may be one indication that

Page 4: 120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE - · PDF file1.1Service Entrance panel For 120 / 240 VAC Split phase AC power Distribution ... 120 / 240 VAC SINGlE SplIt phASE MultI-WIrE

| SAMLEX AMERICA SAMLEX AMERICA |

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS

Multi-wireBranchCircuitshavebeenused.Commonhandle(ganged)circuitbreakersratedat30ampsandhigherareusuallydedicatedto 240 Volt circuits for ranges, hot water heaters, dryers, and the like.

Examination of the wiring in the Service Entrance Panel / Load Center / Distribution Panel may show a three-wire cable (14 or 12 AWG red, black, andwhiteconductors)withbaregroundleavingtheServiceEntrancePanel/LoadCenter/DistributionPanel.ThismaybeconnectedtoaMulti-wireBranchCircuit.ThecircuitbreakersconnectedtothiscableandtheoutputsofthiscableshouldbetracedtodeterminethepresenceorabsenceofaMulti-wireBranchCircuit.

3.0 OVEr-lOADING OF COMMON NEutrAl CONDuCtOr IN thE MultI-WIrE BrANCh CIrCuItS

3.1 When An Inverter Is Connected Directly to 120 / 240 VAC Service Entrance panel / load Center / Distribution panel

Asexplainedabove,aMulti-wireBranchCircuitoperatesnormallyandsafelyonlywhenthetwoseparate120VACBranchCircuitsarefedfromthe2splitphasesL1(PhaseA,Redwire)andL2(PhaseB,Blackwire)thatare180degreesapartandwhichresultsinalowercurrentflowinthesinglecommonNeutral(thiscurrentwillbe=thedifferenceinthecurrentsinthetwoindividualSplitPhaseBranchCircuits).

Each branch circuit in the Service Entrance Panel / Load Center / Distribution Panel is protected by a circuit breaker in the hot, ungrounded current carryingconductorfedfromtheHotLegL1/L2.Thisungrounded,currentcarryingconductorissizedbasedontheAmpereratingofthecircuitbreaker.TheNeutral,groundedcurrentcarryingconductorisusuallythesamesizeastheHotungroundedcurrentcarryingconductorfedfromtheHotLegL1/L2.ThisNeutralconductorwillbeoverloaded/overheatedifitisforcedtocarrycurrenthigherthantheAmpereratingofthecircuitbreakerresultinginfireandsafetyhazard.

TheNeutralwiringinaMulti-wireBranchCircuitmaygetoverloadedwhenasingle120VACinverterisdirectlyconnectedtoboththeHotLegsL1and L2 on the 120 / 240 VAC Service Entrance Panel / Load Center / Distribution Panel as in shown in Fig. 3. Please note that both the L1 and L2 HotinputterminalsoftheMainBreakerintheServiceEntrancePanel/LoadCenter/DistributionPanelhavebeenbonded(shorted)toenergizeboththeHotL1andL2legstogetherinparallelwiththeHotoutputwireoftheinverter.Inthiscase,thetwo120VACHotLegsL1andL2arebeingdeliveredvoltagefromasingle120VACinverterandthisvoltageisinphaseonboththeHotLegsL1andL2ofthepanel.Fig3showstwo15ABranchCircuitsfeedingtwo15AreceptaclesthathavebeenwiredasMulti-wireBranchCircuits.EachBranchCircuitisdelivering15Aandthevoltages/currentsinthetwobranchesareinphase.Hence,thereturncurrentinthecommonNeutralfromthetwoBranchCircuitswilladdto30Aandnotsubtractto0A.Thus,the15AratedNeutralconductorwillbeforcedtocarry30AwhichisdoubleitsratedAmperecapacityandhence,willgetoverheatedresultinginasafetyandfirehazard(seeFig3).

3

Fig. 2: Multi-wire Branch Circuit – Danger of open Neutral

Multiwire Branch CircuitDanger of Open Neutral

Multiwire Branch Circuitwith proper connection

Multiwire Branch Circuitwith an open Neutral

Operating Voltages:Hair Dryer = 120 VACTelevision = 120 VAC

Operating Voltages:Hair Dryer = 77 VACTelevision = 163 VAC

The TV may get burnt as it will see 163 VAC if the Neutral gets opened

240 VAC

240 VACSeries

120 VAC

120 VAC

1275WHair Dryer

600WTelevision

77 VACHair Dryer

163 VACTelevision

Hot Leg, L1

Hot Leg, L2

Hot Leg, L1

Hot Leg, L2

Page 5: 120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE - · PDF file1.1Service Entrance panel For 120 / 240 VAC Split phase AC power Distribution ... 120 / 240 VAC SINGlE SplIt phASE MultI-WIrE

SAMLEX AMERICA |

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS

4

4.0 OptIONS FOr OVErCOMING OVEr-lOADING OF COMMON NEutrAl CONDuCtOr IN thE MultI-WIrE BrANCh CIrCuItS

When An Inverter Is Connected Directly to 120 / 240 V Service Entrance panel / load Center / Distribution panel

The following options are suggested for dealing with this problem:

• DisconnectorrewiretheMulti-wireBranchCircuitsasseparatecircuits(alsocalled“homerun”)fromtheServiceEntrancePanel/LoadCenter / Distribution Panel.

• Connectboth"Hot"(ungrounded)conductorsoftheMulti-wireBranchCircuittoasinglecircuitbreakerratedfortheampacityoftheNeutralconductor.

• LimittheoutputoftheinverterwithacircuitbreakerratedattheampacityoftheNeutralconductor(usually15amps).Placeawarningnearthis circuit breaker stating that the rating must not be increased.

• AsuitabletransformerwithaSplitPhaseoutput(IsolatedorAuto-Transformer)ofsuitablepowerrating(25%morethantheSurgePower(VA) rating of the inverter) with Primary of 120 VAC and Secondary of 120 / 240 VAC (Two 120 VAC Split Phases 180 degrees apart) should beused.TheHotandNeutralofthe120VACoutputofthisunitshouldbefedtothePrimaryofthistrans¬formerandthe2Hotoutputs(120VACSplitPhases)andtheNeutralfromtheSecondaryofthistransformershouldbeconnectedtothetwoHotLegsL1andL2ofthe120 / 240 VAC Service Entrance Panel / Load Center / Distribution Panel (see Fig. 4 page 5).

Section 690-10 of the NEC provides requirements and allowances on connecting a single inverter to a code-compliant AC wiring system.

120 VACInverter

Neutral output wire of the inverter

Hot L1*

Hot L2*

*NOTE: The Hot L1 & L2 of the input terminal on the main breaker have been bonded to feed the inverter output to both the Hot Legs L1 & L2 of the panel.

Main Breaker

Neutral Terminal Bar

30 A

Equipment Grounding Terminal Bar 15 A

Breaker(Ganged)

15 A

Breaker(Ganged)

The voltages in both the Hot Legs L1 & L2 are in phase

As the currents have the same phase,the value adds up to 30 A in the commonNeutral. This exceeds the rated capacity of 15 A of the Neutral and may lead to overheating / �re.

Bare equipment grounding wire Bare equipmentgrounding wire splice

White Neutral splice

15 A

Common Neutral, White Wire

From Hot Leg L2, Black Wire

From Hot Leg L1, Red Wire

15 A

Hot output wire of the inverter

120 VAC 120 VAC

SERVICE ENTRANCE PANEL

N L

G

N L

G

15 A

Fig 3: 120 VAC, Single Phase Inverter Directly Feeding a Multi-Wire Branch Circuit in a 120 / 240 Service Entrance Panel / Load Center / Distribution Panel

Page 6: 120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE - · PDF file1.1Service Entrance panel For 120 / 240 VAC Split phase AC power Distribution ... 120 / 240 VAC SINGlE SplIt phASE MultI-WIrE

| SAMLEX AMERICA SAMLEX AMERICA |

120 / 240 VAC SINGLE SPLIT PHASE & MULTI-WIRE BRANCH CIRCUITS

5

Fig. 4: Connecting inverter to the Service Entrance Panel / Load Center / Distribution Panel through a transformer to accommodate Multi-wire Branch Circuits

N L

G

N L

G

Hot L1

Hot L2

Main Breaker

Neutral Terminal Bar

0 A

Equipment Grounding Terminal Bar 15 A

Breaker(Ganged)

15 A

Breaker(Ganged)

Bare equipment grounding wire Bare equipment grounding wire splice

White Neutralsplice

Single White - Neutral

From Hot Leg L1, Red Wire

From Hot Leg L2, Black Wire 15 A

15 A

120 VAC 120 VAC

120 VACInverter

Isolated / Auto Transformer

White-Neutral

Neutral, NHot, L

* Note: The phases of Hot Legs L1 & L2 are 180 degrees apart.

Phase of Hot Wire, L2*

Phase of Hot Wire, L1*

Phase of Hot Leg, L1*

Hot Leg, L2

Hot Leg, L1

15 A

+ = 015 A, Phase L1

15 A, Phase L2

SERVICE ENTRANCE PANEL

Phase of Hot Leg, L2*

For more information, visit: www.samlexamerica.com