  • 8/13/2019 1394_TCT

    1/2pag.128 - Product range 2010

    * Units Series

    Unit type

    TCT-H horizontalunit

    TCT-V verticalunit

    Configuration

    2R with 2-row coil

    4R with 4-row coil

    6R with 6-row coil

    4-2R 4 pipes systems with 4+2-row

    coil

    6-2R 4 pipes systems with 6+2-row

    coil

    * Unit specifications

    Large capacity fan coil, complying with

    Machine Directive 89/392 EEC and

    amendments 91/368 EEC, 93/44 EEC,

    93/68 EEC, Low-Voltage Directives 72/23

    EEC and Electromagnetic Compatibility Di-

    rectives EMC 89/36 EEC.

    Fan coil unit terminal for the treatment of

    room air in the summer season (coil supplied

    with cold water) and in winter (coil supplied

    with hot water).

    These units are suitable for indoor installa-

    tion, very compact and amply configurable

    to meet the requirements of highly qualified

    designers.

    The careful design of the main components,refined styling and the versatility of the pro-

    duct make it suitable for any type of installa-

    tion in commercial or industrial context.

    Installation therefore only requires the electri-

    cal and hydraulic connections.

    Construction characteristics of versions

    SUPPORT STRUCTURE: the frame of

    the units is in UNI9006/1 Anticorodal 63

    extruded aluminium alloy profiles, con-

    nected with three-way joints in preloaded

    nylon and sandwich closure panels, with

    exposed side in white-grey pre-painted

    steel and internal side in galvanised steel

    sheet; unit thermal insulation/soundpro-

    ofing is obtained through the injection of

    polyurethane of density not less than 45

    kg/m3.

    AIR FILTER: removable sideways, it can

    be regenerated simply by washing, and is

    G3 efficiency class.

    HEAT EXCHANGE COIL: made with

    copper pipes arranged in staggered rows

    and with corrugated aluminium finning,

    locked by mechanical expansion of the pi-

    pes. Complete with water inlet/outlet ma-

    nifolds. The coil holding section provided

    for on the TCT units is arranged to house

    heating and/or cooling coils: the section

    is designed to hold two coils in horizontal

    and vertical models. The hot water coils

    are 2-row or 4-row whereas for cooling

    they can be 4-row or 6-row with chilled

    water. The standard executions provide

    for oblique fitting of the cooling coil in ver-

    tical models and horizontal fitting of the

    heating coil, and vertical fitting of both

    coils in horizontal models.CONDENSATE TRAY: in stainless steel

    sheet, complete with section for connec-

    tion to the discharge line.

    FAN MOTOR: ventilating section desig-

    ned to limit fan noise as much as possible.

    The motor-fan assembly is isolated from

    the structure by means of suitable shock-

    absorbers on the base and is complete

    with neoprene vibration-mounting joint.

    The centrifugal fans installed are dual-

    intake with forward blades, statically and

    dynamically balanced. Coupled-type fansare installed for sizes 100, 130 and 175.

    Motor-fan coupling is by means of varia-

    ble-pitch pulleys and V belts for all sizes.

    Careful selection has enabled high effi-

    ciencies to be obtained. The electric mo-

    tors are 4-pole, externally ventilated and

    class F isolated with IP55 protection ra-

    ting, fixed on special guides enabling belt

    tension adjustment. The use of variable-

    pitch drive pulleys enables the number of

    revolutions and therefore the pressure to

    be adjusted to system requirements.

    * Main accessories/Options

    Inlet grill

    Air inlet damper

    Inlet plenum for vertical execution

    Plenum with 1 damper

    Plenum with 2 dampers

    Outlet plenum

    > TCT LARGE CAPACITY FAN COIL

  • 8/13/2019 1394_TCT

    2/2Product range 2010 - pag.129

    Model 30 50 70 100 130 180

    A mm 1180 1420 1660 1780 1940 2300

    B mm 770 770 770 920 1100 1100

    C/H mm 1290 1290 1290 1290 1290 1290

    C/V mm 1540 1540 1540 1830 2010 2090

    D1 mm 418 505 625 222 383 392

    D2 mm 418 505 625 428 427 568

    E mm 344 410 410 1130 1130 1340

    F mm 304 354 354 354 354 417

    G/H mm 360 390 390 390 390 410

    G/V mm 150 150 150 105 105 105

    I mm 700 700 700 850 1030 1030

    L mm 1110 1350 1590 1710 1870 2230

    UNIT TCT/H - TCT/V 30 50 70 100 130 180

    Air flow (MIN MAX) 2300-3800 3900-6700 6300-8100 8200-11000 11000-15000 15000-20000 m3/h

    Air flow rate nominal 3000 5300 7200 9600 13000 17500 m3/h

    Total static pressure () 150-370 180-350 250-340 250-375 260-350 250-400 Pa

    Sound pressure level(*) 58 73 70 68 71 69 dB(A)

    Horizontal unit weight TCT-H 197 240 260 360 380 580 Kg

    Vertical unit weight TCT-V 220 268 290 380 410 550 Kg

    FanPower input 0,75 1,5 2,2 2,2 4 5,5 kW

    N Fans / Poles 1/4 1/4 1/4 1/4 1/4 1/4 n

    Power supply 400 / 3 / 50 V/ph/Hz

    TCT 2R 30 53 72 95 130 175

    Heating Capacity (*) 35,2 53 69,9 95,8 130 178 kW

    Water flow rate 3,09 4,66 6,13 8,42 11,3 15,6 m3/h

    Water pressure drop 9 4 8 10 12 23 kPa

    Air pressure drop 18 32 38 35 35 39 Pa

    Water connection 11/2 11/2 11/2 11/2 11/2 11/2 Gas

    TCT 4R 30 50 70 100 130 180

    Heating

    Heating Capacity (*) 52,7 84,8 112 153 206 283 kW

    Water flow rate 4,63 7,44 9,91 13,4 18,1 24,8 m3/h

    Water pressure drop 15 15 27 33 41 45 kPa

    Air pressure drop 32 52 57 51 53 58 Pa

    Cooling

    Cooling capacity total/sens (**) 31,2 / 17,8 46,5 / 27 62,7 / 36,4 86,9 / 50,5 117 / 68,1 161 / 91,8 kW

    Water flow rate 5,2 7,8 10,5 14,5 19,6 26,9 m3/h

    Water pressure drop 24 20 35 40 45 80 kPa

    Air pressure drop 51 75 90 82 85 86 Pa

    Water connection 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 Gas

    TCT 6R 30 50 70 100 130 180

    Cooling capacity total/sens (**) 36,2 / 19,9 60,7 / 34 78,3 / 43,9 108 / 60,6 146 / 81,8 200 / 110 kW

    Water flow rate 6 10,1 13,1 18,1 24,4 33,5 m3/h

    Water pressure drop 15 42 27 35 44 71 kPaAir pressure drop 60 90 95 95 96 90 Pa

    Water connection 1 1/2 1 1/2 1 1/2 1 1/2 1 1/2 2 Gas

    Dimensions

    () Inlet air 0 C, water IN/OUT 70/60 C. max speed air fow.

    () Inlet air 32 C, RH 50%. water IN/OUT 7/12 C. max speed air fow.

    (*) Referred to the fan: deduct the pressure drop of the

    selected components in order to get the external static pressure.

    (**) Sound pressure level: data referred to 1,5 metres from inlet in free field. Theactual operation noise level generally differs from the values shown in the table,depending on operating conditions, reflected noise and surrounding noise.

    > TCT LARGE CAPACITY FAN COIL