Mani Project V(kV) 0.38 Panel name: MCC-CH PF 0.80 Panel enclosure: EPC Type: Indoor IP: 54/20 Kt 1.5 Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500 Connected Load Branch Breaker Power Current Operation Cable No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR Main MCCB ACB 4 5000 5000 2,192.5 2740.6 4,163.9 1 CH-1 Roof MCCB 3 1,000 1,000 500.0 625.0 949.6 þ 2 CH-2 MCCB 3 1,000 1,000 500.0 625.0 949.6 þ 3 CH-3 MCCB 3 1,000 1,000 510.0 637.5 968.6 þ 4 DB-CT-P MCCB 3 2,000 1,500 682.5 853.1 1,296.2 5 Spare MCCB 3 100 100 0.0 0.0 6 Spare MCCB 3 100 100 0.0 0.0 7 Spare MCCB 3 100 100 0.0 0.0 8 Spare MCCB 3 800 800 0.0 0.0

Upload: giang-lam

Post on 01-Feb-2016

215 views

Category:

Documents


0 download

DESCRIPTION

Mani project

TRANSCRIPT

Page 1: 151016.Mechanical Power Supply Table

Mani ProjectV(kV) 0.38

Panel name: MCC-CH PF 0.80Panel enclosure: EPC Type: Indoor IP: 54/20 Kt 1.5Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB ACB 4 5000 5000 2,192.5 2740.6 4,163.9

1 CH-1

Roof

MCCB 3 1,000 1,000 500.0 625.0 949.6 þ Method of starting: S/D2 CH-2 MCCB 3 1,000 1,000 500.0 625.0 949.6 þ

3 CH-3 MCCB 3 1,000 1,000 510.0 637.5 968.6 þ

4 DB-CT-P MCCB 3 2,000 1,500 682.5 853.1 1,296.2

5 Spare MCCB 3 100 100 0.0 0.0

6 Spare MCCB 3 100 100 0.0 0.0

7 Spare MCCB 3 100 100 0.0 0.0

8 Spare MCCB 3 800 800 0.0 0.0

Page 2: 151016.Mechanical Power Supply Table

Mani ProjectV(kV) 0.38PF 0.80Kt 1.5

Panel name: MCC-PAU-1Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 250 225 114.0 142.5 216.5 CXV 4cx95sq+E35sq

1 PAU-1-2-1-Fan

1FL Chemical Grinding Room

MCCB 3 50 30 7.5 9.4 21.4 þ CXV 4cx6sq+E2.5sq Method of starting: S/D2 PAU-1-2-1-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL3 PAU-1-2-2-Fan MCCB 3 50 30 7.5 9.4 21.4 þ CXV 4cx6sq+E2.5sq Method of starting: S/D4 PAU-1-2-2-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL5 PAU-1-2-3-Fan MCCB 3 50 30 7.5 9.4 21.4 þ CXV 4cx6sq+E2.5sq Method of starting: S/D6 PAU-1-2-3-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL7 PAU-1-2-4-Fan MCCB 3 50 30 7.5 9.4 21.4 þ CXV 4cx6sq+E2.5sq Method of starting: S/D8 PAU-1-2-4-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL

Panel name: MCC-AHU-1Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 150 125 61.5 76.9 116.8 CXV 4cx70sq+E35sq

1 AHU-1-1-1-Fan

1FL Laser Hole Room

MCCB 3 50 20 5.5 6.9 10.4 þ CXV 4cx4sq+E2.5sq Method of starting: DOL2 AHU-1-1-1-EH MCCB 3 50 30 15.0 18.8 28.5 þ CXV 4cx6sq+E2.5sq Method of starting: DOL3 AHU-1-1-2-Fan MCCB 3 50 20 5.5 6.9 10.4 þ CXV 4cx4sq+E2.5sq Method of starting: DOL4 AHU-1-1-2-EH MCCB 3 50 30 15.0 18.8 28.5 þ CXV 4cx6sq+E2.5sq Method of starting: DOL5 AHU-1-1-3-Fan MCCB 3 50 20 5.5 6.9 10.4 þ CXV 4cx4sq+E2.5sq Method of starting: DOL6 AHU-1-1-3-EH MCCB 3 50 30 15.0 18.8 28.5 þ CXV 4cx6sq+E2.5sq Method of starting: DOL

Page 3: 151016.Mechanical Power Supply Table

Mani ProjectV(kV) 0.38PF 0.80Kt 1.5

Panel name: MCC-PAU-2Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 150 150 71.5 89.4 135.8 CXV 4cx70sq+E35sq

1 PAU-2-3-Fan

2FL

RD RoomMCCB 3 100 100 22.0 27.5 62.7 þ CXV 4cx35sq+E10sq Method of starting: S/D

2 PAU-2-3-EH MCCB 3 100 60 27.0 33.8 51.3 þ CXV 4cx10sq+E4sq Method of starting: DOL3 AHU-2-1-1-Fan

Sterilizer Area

MCCB 3 50 20 7.5 9.4 14.2 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D4 AHU-2-1-2-Fan MCCB 3 50 20 7.5 9.4 14.2 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D5 AHU-2-1-3-Fan MCCB 3 50 20 7.5 9.4 14.2 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D

Panel name: MCC-AHU-2Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 250 250 135.0 168.8 256.4 CXV 4cx95sq+E35sq

1 AHU-2-2-1-Fan

2FL

Locker Rm 01 &Clearn Rm 01

MCCB 3 50 50 15.0 18.8 42.7 þ CXV 4cx10sq+E4sq Method of starting: S/D2 AHU-2-2-1-EH MCCB 3 50 50 18.0 22.5 34.2 þ CXV 4cx10sq+E4sq Method of starting: DOL3 AHU-2-2-2-Fan MCCB 3 50 50 15.0 18.8 42.7 þ CXV 4cx10sq+E4sq Method of starting: S/D4 AHU-2-2-2-EH MCCB 3 50 50 18.0 22.5 34.2 þ CXV 4cx10sq+E4sq Method of starting: DOL5 AHU-2-3-1-Fan

Locker Rm 02 &Clearn Rm 02

MCCB 3 50 50 15.0 18.8 42.7 þ CXV 4cx10sq+E4sq Method of starting: S/D6 AHU-2-3-1-EH MCCB 3 50 50 18.0 22.5 34.2 þ CXV 4cx10sq+E4sq Method of starting: DOL7 AHU-2-3-2-Fan MCCB 3 50 50 15.0 18.8 42.7 þ CXV 4cx10sq+E4sq Method of starting: S/D8 AHU-2-3-2-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL

Panel name: MCC-AHU-3Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 200 200 88.0 110.0 167.1 CXV 4cx95sq+E35sq

1 AHU-2-4-1-Fan

2FL

Locker Rm 03&Clearn Rm 03

MCCB 3 50 50 15.0 18.8 42.7 þ CXV 4cx10sq+E4sq Method of starting: S/D2 AHU-2-4-1-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL3 AHU-2-4-2-Fan MCCB 3 50 30 11.0 13.8 31.3 þ CXV 4cx10sq+E4sq Method of starting: S/D4 AHU-2-4-2-EH MCCB 3 50 30 15.0 18.8 28.5 þ CXV 4cx10sq+E4sq Method of starting: DOL5 AHU-2-5-Fan

Aseptic RoomMCCB 3 50 30 11.0 13.8 31.3 þ CXV 4cx10sq+E4sq Method of starting: S/D

6 AHU-2-5-EH MCCB 3 50 30 15.0 18.8 28.5 þ CXV 4cx10sq+E4sq Method of starting: DOL

Page 4: 151016.Mechanical Power Supply Table

Panel name: MCC-PAU-4Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 400 250 139.0 173.8 264.0 CXV 4cx95sq+E35sq

1 AHU-2-6-Fan

2FL

Set & Coating Room MCCB 3 50 30 11.0 13.8 31.3 þ CXV 4cx6sq+E2.5sq Method of starting: S/D2 AHU-2-7-1-Fan

Dry Room

MCCB 3 50 30 11.0 13.8 31.3 þ CXV 4cx6sq+E2.5sq Method of starting: S/D3 AHU-2-7-1-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL4 AHU-2-7-2-Fan MCCB 3 50 30 11.0 13.8 31.3 þ CXV 4cx6sq+E2.5sq Method of starting: S/D5 AHU-2-7-2-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL6 AHU-2-7-3-Fan MCCB 3 50 30 11.0 13.8 31.3 þ CXV 4cx6sq+E2.5sq Method of starting: S/D7 AHU-2-7-3-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL8 AHU-2-7-4-Fan MCCB 3 50 30 11.0 13.8 31.3 þ CXV 4cx6sq+E2.5sq Method of starting: S/D9 AHU-2-7-4-EH MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL

Page 5: 151016.Mechanical Power Supply Table

Mani ProjectV(kV) 0.38PF 0.80Kt 1.5

Panel name: MCC-PAU-7Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 400 350 169.0 211.3 321.0 CXV 3x1cx240sq+E240sq

1 PAU-1-1-Fan

Roof

Room 1FLMCCB 3 100 100 30.0 37.5 85.5 þ CXV 4cx35sq+E10sq Method of starting: S/D

2 PAU-1-1-EH MCCB 3 100 100 51.0 63.8 96.9 þ CXV 4cx35sq+E10sq Method of starting: DOL3 PAU-2-1-Fan

Clear Rm 1&2&3 and Aseptic RmMCCB 3 100 60 18.5 23.1 52.7 þ CXV 4cx10sq+E4sq Method of starting: S/D

4 PAU-2-1-EH MCCB 3 50 50 21.0 26.3 39.9 þ CXV 4cx10sq+E4sq Method of starting: DOL5 PAU-2-2-Fan

Test Rm, QA Rm, Dry Rm, StorageMCCB 3 100 60 18.5 23.1 52.7 þ CXV 4cx10sq+E4sq Method of starting: S/D

6 PAU-2-2-EH MCCB 3 100 60 30.0 37.5 57.0 þ CXV 4cx10sq+E4sq Method of starting: DOL

Page 6: 151016.Mechanical Power Supply Table

Mani ProjectV(kV) 0.38

Panel name: MCC-PAU-3 PF 0.80Panel enclosure: EPC Type: Indoor IP: 54/20 Kt 1.5Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 2000 1500 693.0 866.3 1,316.1

1 PAU-1-1-Fan Roof MCCB 3 100 100 30.0 37.5 85.5 þ Method of starting: S/D2 PAU-1-1-EH Roof MCCB 3 100 100 51.0 63.8 96.9 þ Method of starting: DOL3 PAU-1-2-1-Fan 1FL MCCB 3 50 30 7.5 9.4 21.4 þ Method of starting: S/D4 PAU-1-2-1-EH 1FL MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL5 PAU-1-2-2-Fan 1FL MCCB 3 50 30 7.5 9.4 21.4 þ Method of starting: S/D6 PAU-1-2-2-EH 1FL MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL7 PAU-1-2-3-Fan 1FL MCCB 3 50 30 7.5 9.4 21.4 þ Method of starting: S/D8 PAU-1-2-3-EH 1FL MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL9 PAU-1-2-4-Fan 1FL MCCB 3 50 30 7.5 9.4 21.4 þ Method of starting: S/D

10 PAU-1-2-4-EH 1FL MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL11 PAU-2-1-Fan Roof MCCB 3 100 60 18.5 23.1 52.7 þ Method of starting: S/D12 PAU-2-1-EH Roof MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL13 PAU-2-2-Fan Roof MCCB 3 100 60 18.5 23.1 52.7 þ Method of starting: S/D14 PAU-2-2-EH Roof MCCB 3 100 60 30.0 37.5 57.0 þ Method of starting: DOL15 PAU-2-3-Fan 2FL MCCB 3 100 100 22.0 27.5 62.7 þ Method of starting: S/D16 PAU-2-3-EH 2FL MCCB 3 100 60 27.0 33.8 51.3 þ Method of starting: DOL17 AHU-1-1-1-Fan 1FL MCCB 3 50 20 5.5 6.9 10.4 þ Method of starting: DOL18 AHU-1-1-1-EH 1FL MCCB 3 50 30 15.0 18.8 28.5 þ Method of starting: DOL19 AHU-1-1-2-Fan 1FL MCCB 3 50 20 5.5 6.9 10.4 þ Method of starting: DOL20 AHU-1-1-2-EH 1FL MCCB 3 50 30 15.0 18.8 28.5 þ Method of starting: DOL21 AHU-1-1-3-Fan 1FL MCCB 3 50 20 5.5 6.9 10.4 þ Method of starting: DOL22 AHU-1-1-3-EH 1FL MCCB 3 50 30 15.0 18.8 28.5 þ Method of starting: DOL23 AHU-2-1-1-Fan 2FL MCCB 3 50 20 7.5 9.4 14.2 þ Method of starting: S/D24 AHU-2-1-2-Fan 2FL MCCB 3 50 20 7.5 9.4 14.2 þ Method of starting: S/D25 AHU-2-1-3-Fan 2FL MCCB 3 50 20 7.5 9.4 14.2 þ Method of starting: S/D26 AHU-2-2-1-Fan 2FL MCCB 3 50 50 15.0 18.8 42.7 þ Method of starting: S/D27 AHU-2-2-1-EH 2FL MCCB 3 50 50 18.0 22.5 34.2 þ Method of starting: DOL28 AHU-2-2-2-Fan 2FL MCCB 3 50 50 15.0 18.8 42.7 þ Method of starting: S/D29 AHU-2-2-2-EH 2FL MCCB 3 50 50 18.0 22.5 34.2 þ Method of starting: DOL30 AHU-2-3-1-Fan 2FL MCCB 3 50 50 15.0 18.8 42.7 þ Method of starting: S/D31 AHU-2-3-1-EH 2FL MCCB 3 50 50 18.0 22.5 34.2 þ Method of starting: DOL32 AHU-2-3-2-Fan 2FL MCCB 3 50 50 15.0 18.8 42.7 þ Method of starting: S/D33 AHU-2-3-2-EH 2FL MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL34 AHU-2-4-1-Fan 2FL MCCB 3 50 50 15.0 18.8 42.7 þ Method of starting: S/D35 AHU-2-4-1-EH 2FL MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL36 AHU-2-4-2-Fan 2FL MCCB 3 50 30 11.0 13.8 31.3 þ Method of starting: S/D37 AHU-2-4-2-EH 2FL MCCB 3 50 30 15.0 18.8 28.5 þ Method of starting: DOL38 AHU-2-5-Fan 2FL MCCB 3 50 30 11.0 13.8 31.3 þ Method of starting: S/D39 AHU-2-5-EH 2FL MCCB 3 50 30 15.0 18.8 28.5 þ Method of starting: DOL40 AHU-2-6-1-Fan 2FL MCCB 3 50 30 11.0 13.8 31.3 þ Method of starting: S/D41 AHU-2-6-2-Fan 2FL MCCB 3 50 30 11.0 13.8 31.3 þ Method of starting: S/D42 AHU-2-7-Fan 2FL MCCB 3 50 30 11.0 13.8 31.3 þ Method of starting: S/D43 AHU-2-7-EH 2FL MCCB 3 50 50 21.0 26.3 39.9 þ Method of starting: DOL

Page 7: 151016.Mechanical Power Supply Table

Mani ProjectV(kV) 0.38

Panel name: DB-CT-P PF 0.80Panel enclosure: EPC Type: Indoor IP: 54/20 Kt 1.5Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 1200 1200 622.5 778.1 1,182.2 CXV 12x4cx240sq+E240sq

1 CWP-1

Roof

Cooling Tower System

MCCB 3 250 225 75.0 93.8 213.7 þ CXV 4cx95sq+E35sq Method of starting: S/D2 CWP-2 MCCB 3 250 225 75.0 93.8 213.7 þ CXV 4cx95sq+E35sq Method of starting: S/D3 CWP-3 MCCB 3 250 225 75.0 93.8 213.7 þ CXV 4cx95sq+E35sq Method of starting: S/D4 CHWP-1

Chiller System

MCCB 3 200 150 55.0 68.8 156.7 þ CXV 4cx50sq+E25sq Method of starting: S/D5 CHWP-2 MCCB 3 200 150 55.0 68.8 156.7 þ CXV 4cx50sq+E25sq Method of starting: S/D6 CHWP-3 MCCB 3 200 150 55.0 68.8 156.7 þ CXV 4cx50sq+E25sq Method of starting: S/D7 CHWP-4 MCCB 3 200 150 55.0 68.8 156.7 þ CXV 4cx50sq+E25sq Method of starting: S/D8 CHWP-5 MCCB 3 200 150 55.0 68.8 156.7 þ CXV 4cx50sq+E25sq Method of starting: S/D9 CHWP-6 MCCB 3 200 150 55.0 68.8 156.7 þ CXV 4cx50sq+E25sq Method of starting: S/D

10 CTF-1

Cooling Tower System

MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D11 CTF-2 MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D12 CTF-3 MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D13 CTF-4 MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D14 CTF-5 MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D15 CTF-6 MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D16 CTF-7 MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D17 CTF-8 MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D18 CTF-9 MCCB 3 50 20 7.5 9.4 21.4 þ CXV 4cx2.5sq+E2.5sq Method of starting: S/D

Page 8: 151016.Mechanical Power Supply Table

Mani ProjectV(kV) 0.38PF 0.80Kt 1.5

Panel name: DB-SWIT-1Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 50 50 23.5 29.4 44.7 CXV 4cx10sq+E4sq

1 SWIT-01

1FL

Surface Grinding Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

2 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

3 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

4 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

5 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

6 SWIT-06 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

7 SWIT-01

Bending Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

8 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

9 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

10 SWIT-01 Storage(X8-X11,Y19-Y21) MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

11 SWIT-01Measurement ST

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

12 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

Panel name: DB-SWIT-2Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 100 80 41.2 51.4 78.2 CXV 4cx16sq+E4sq

1 SWIT-07

1FL

Surface Grinding Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

2 SWIT-08 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

3 SWIT-09 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

4 SWIT-10 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

5 SWIT-11 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

6 SWIT-12 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

7 SWIT-04

Bending Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

8 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

9 SWIT-06 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

10 SWIT-01 Storage(X8-X11,Y14-Y15) MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

11 SWIT-01

Press Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

12 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

13 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

14 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

15 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

16 SWIT-06 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

17 SWIT-01

Intermediate Test Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

18 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

19 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

20 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

21 SWIT-01 Blade Grind Room MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

Page 9: 151016.Mechanical Power Supply Table

Panel name: DB-SWIT-3Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 50 50 17.6 22.1 33.5 CXV 4cx10sq+E4sq

1 SWIT-01

1FL

Discharge Hole Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

2 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

3 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

4 SWIT-01

Drill Hole Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

5 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

6 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

7 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

8 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

9 SWIT-01 One Cycle Rinsing MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

Panel name: DB-SWIT-4Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 100 80 27.4 34.3 52.1 CXV 4cx16sq+E4sq

1 SWIT-01

1FL

Electrolytic Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

2 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

3 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

4 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

5 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

6 SWIT-01

Auto Line

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

7 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

8 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

9 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

10 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

11 SWIT-01 TP Storage (X14-X19,Y9-Y12) MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

12 SWIT-01 Storage (X14-X15,Y6-Y7) MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

13 SWIT-01Cut Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

14 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

Panel name: DB-SWIT-5Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 50 30 15.7 19.6 29.8 CXV 4cx6sq+E2.5sq

1 SWIT-01

1FL

Storage (X14-X19,Y4-Y5)

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

2 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

3 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

4 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

5 SWIT-01

Working Space

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

6 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

7 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

8 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

Page 10: 151016.Mechanical Power Supply Table

Mani ProjectV(kV) 0.38PF 0.80Kt 1.5

Panel name: DB-SWIT-6Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 50 30 15.7 19.6 29.8 CXV 4cx6sq+E2.5sq

1 SWIT-01

2FL

Test Room MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

2 SWIT-01 Storage(X9-X11,Y14-Y17) MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

3 SWIT-01ET Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

4 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

5 SWIT-01Set & Sillicone Check

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

6 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

7 SWIT-01Storage(X15-X19,Y4-Y14)

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

8 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

Panel name: DB-SWIT-7Panel enclosure: EPC Type: Indoor IP: 54/20Dimesion: W1600xH1800xD500xL20 Base: W1600xH100xD500

Connected Load Branch Breaker Power Current Operation CableRemark

No. Load name Model Location Service area Type (P) (AF) (AT) kW kVA Amp On/Off Inv SCR

Main MCCB MCCB 3 100 80 27.4 34.3 52.1 CXV 4cx16sq+E4sq

1 SWIT-01

2FL

QA Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

2 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

3 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

4 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

5 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

6 SWIT-01

Test/Packing Room

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

7 SWIT-02 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

8 SWIT-03 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

9 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

10 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

11 SWIT-03

Storage(X15-X19,Y4-Y14)

MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

12 SWIT-04 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

13 SWIT-05 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq

14 SWIT-06 MCB 3 10 6 1.96 2.4 3.7 þ CXV 4cx2.5sq+E2.5sq