1539 structural design df reinforced masonry lintels · pdf filestructural design df...
TRANSCRIPT
1539
STRUCTURAL DESIGN DF REINFORCED MASONRY LINTELS
OR. ARMIN OHLER German Masonry Association
Schaumburg-Lippe-Str . 4, 5300 Bonn 1, West Germany
ABSTRACT
lhe paper outlines the practical design of reinforced masonry lintels in bending and shear. Oesign charts are developed which enable the designer to easily determine the dimensions of the lintel as well as the amount of rebars required for a given span and loading . lhe structural detailing is explained, and examples are given demonstrating the design of reinforced masonry lintels.
INTROOUCTION
In Germany, as well as in many other countries, among architects and structural engineers the use of reinforced masonry lintels as structural elements in loadbearing walls is not common practice. lhough being widely used in facade walls loadbearing beams supporting roofs, floors or gable walls tend to be designed in reinforced concrete or steel. However, mixed structures, i . e. concrete or steel members as part of a masonry wall, are characterised by considerable disadvantages in terms of the thermal conductivity of the wall. The good insulation provided by the masonry is undermined by zones of high thermal conductivity of other structural materials; in consequence, additional insulating measures causing costs are required.
Although masonry is regarded to be weak in tension it may well be used in members subjected to bending if, with analogy to reinforced concrete structures, the tension forces are taken by the steel reinforcement.
In the following the structural design of reinforced masonry lintels in bending and shear is outlined. The design is based on the Building Guide line 111 which, in the absence of appropriate rules in the current German masonry code of practice, gives guidance on the design and construction of reinforced masonry beams.
DEFINITION
Reinforced masonry lintels complying with 111 are lintels with limited dimensions in height and length. lhey are mainly used in normal houses, dewellings, and low rise industrial buildings. lhey are characterised by a U-shaped tension flange carrying the reinforcing steel. For good corrosion protection the steel rods are embedded in concrete. lhe masonry is traditionally exected on top of the flange featuring horizontal bed joints and vertical partly or completely filled mortar joints. Fig . 1 shows a typical example of a reinforced masonry lintel. lhe material of the U-shaped unit corresponds to that of the masonry forming the compression zone and may be clay, calcium silicate, light-weight concrete
1540
layer
I.. li=I-2~ .1 I;A~115cm I s 3.0m
Figure 1. Side view of a reinforced masonry lintel
pumice) or aerated concrete. In case of light-weight concrete the tension lange may also consist of precast bulk concrete elements. In case of lay bricks soldier units may be used with rebars passing through the erforations and holes of the bricks (fig. 2).
---..lI 11 11 II 1/ IL ~DDDDDDCJDDCJC::= ~I 11 II 11 IC~[
::Jn 000[]] QLJ D[
[ reinforcement
I
Figure 2. Lintel with soldier clay bricks
1541
According to / 1/ reinforced masonry 1inte1s sha11 meet the fo11owing requirements:
tension flange: - minimum width of 115 mm - minimum height of 60 mm - type BSt 400 S or BSt 500 S exc1usive1y
concrete infi11 of the UZshaped unit having a minimum averaêe compressive strength of 30 N/ mm (concrete c1ass B 25) and 29 N/ mm (light-weight concrete c1ass LB 25), respective1y .
- minimum concrete cover of 20 mm
compression zone: 2 - minimum average compressiv2 strength of units 15 N/ mm (unit strength
c1ass 12), and of 2,5 N/mm (mortar c1ass MG 11) foZ mortar - design compressive strengh of masonry BR = 2,5 N/ mm . - maximum effective height taken for the structura1 design 1/ 2,4 (1 = 1in-
te1 span, cf. fig o 1) - a1though undesirab1e it may be necessary to use concrete for constructing
the compression zone, e.g. if the structura1 design requires a very low height of the 1inte1. In this case guide1ine /1/ refers to the design of concrete structures. Detai1s on this may be obtained from /2/ and /3 / .
FLEXURAL DESIGN
In princip1e, the design of reinforced masonry 1inte1s is carried out in ana10gy to reinforced concrete structures. However, both different u1timate strains and a11owab1e design compressive strengths have to be taken into account. According to test resu1ts obtained by / 5, 6/ an u1timate strain of E = 3,5%0 is adopted being conservative for a11 common types of masonry~WFig . 3 shows the stress-strain-re1ationship used as a basis of the designo Assuming a cracked tension zone for the masonry subjected to bending the compressive force taken by the masonry compression zone at u1timate is expressed by (cf. figo 4)
x
Dmwu S bomw(y)dy = bXC{RBR (1 ) being o
é (2 ) ~ = ~ (6 -é )
12 mw
b width of linte1 BR design compressive strength of masonry
As is th '2 case for concrete /4/ eqn . (2) expresses the coefficient Oi- as a function ~" the strain at the upper side of the 1inte1 t describ~ng th2 parabo1ic shape of the compression area An0 The distancWwx of the neutra1 axis from the upper side of the beam mày be expressed as a function of the strains of the masonry and the stee1:
x . h (3) E +E mw s
1542
O'mw
fi R
( Emw2) (}'mw=fiR cmw - -4-
-2%0 1Emwl
Figure 3. Stress-strain relationship of masonry
LH ___ k Emwu r ... O"'mwu ~ f3 R
J -o
Dmwu )
As O"'su Zs
Mu l Z =kz·h
-Figure 4. Stress / strain distribution; inner forces of cross section
In order to determine the inner lever arm
z k· h h - a z (4)
the distance a, too, may be expressed as a function of the strains (cf. i 4i for concrete)
a 8 - Emw
k a . x 4 (6 - é mw)
From eqns. (4), (5) and (3)
k z 1 _ ! = 1 _ ka • x
h h 1 - ka kx f (Emw ' E. s )
(5 )
(6 )
is obtained, which means that also the inner lever arm z is a function ofe and ES' respeç~l~ely. This leads to the inner moment mw
1543
M O z u mw,u (7)
and, wit ~ t he inserti on of eqns. ( 1) , ( 3) , (4 )
M u bh 2B R Rkxk z =~. M (8)
with M = acting moment t = safety factor 1,75
Fr om eqn. (8)
(9)
is obtained which den otes the degree of exp10itation of the section as a function of the strains of masonry é and stee 1 ES' 111 prescr ibes that max E = 5%0 and due to fi g . 3 ma~wE = 2%0. EConomi ca 1 use of a gi ven 1 i nt~l sect i on i s made for é léS-vWfues as 1 i sted in tab 1 e 1. mw
TABLE 1
Design coefficients for reinforced masonry 1inte1s
~R = 2,5 1.IN / m2
ESt 420 S BS t 500 S - E: mw / E: s
kh
k k k k e,o I 'c o] s s x z
29, 74 4, 25 3,57 0,06 0,98 0, 3 1 5,0
18 . ó2 4,30 3, 61 0, 09 0,97 0,5 I 5, 0
13,87 4,35 3, 65 0,12 0, 96 0, 7 I 5, 0
i 1 , 26 4,40 3, 70 0,15 0,9 5 0, 9 I 5,0
9, 61 4, 45 3, 74 0,1 8 0, 94 1,1 I 5,0
8 ,48 4, 50 3,78 0, 21 0, 93 1,3 I 5,0
7, 67 4, 55 3,82 0, 23 0,92 1,5 / 5, 0
7. 07 4, 59 3,86 0,25 0, 91 1, 7 I 5, 0
6, 42 4,67 3,9 2 0,29 0,89 2,0 I 5,0
6,2 1 4,71 3, 96 0,31 0, 89 2,0 I 4,5
6,00 4,7 6 4,00 0 , 33 0, 88 2,0 I 4,0
5. 78 4, 82 4,05 0 , 36 0, 86 2,0 I 3,5
5. 56 4, 90 4,12 0 , 40 0, 85 2,0 I 3,0
1544
The size of the rebar needed is determined by
M u _ toM _ Z -----A B ( 10) s k oh s s z z
yielding As ~ !:! = k M ( 11 ) s B ok h h s z
For a given cross section of a beam and the acting bending moment M the kh-coefficient is calculated with eqn. (9), and then the k -coefficient is obtained from table 1. If there is an additional normalsforce N M is replaced by
MS d M - N (h - - ) 2
( 12)
SHEAR DESIGN
The shear failure mode of masonry lintels differs substantially from that of concrete lintels. As illustrated in figo 5 load transfer to the support is achieved by an inclined compressive force producing shear failure in the bed joint. The shear resistance required is dependent on the inclination of the compression force D; as a measure for this the shear ratio
À max bendíng moment M max shear force o effectlve helaht ~
(13 )
may be taken. As qualitatively illustrated in figo 6 the shear resistance decreases with increas in g À. If À falls below 0,6 failure is governed by the vertical compressive strength of the masonry rather than the shear strength of the unit/mortar bo nd.
p p
tendon
i Imox M/z I z
.r - I : mox MIz I I
mox Q
L~:}·mQXO O H =mox a· z
Fi gure 5. I nterp 1 ay of force s in 1 i nte 1 and support
1545
In order to determine the allowable shear resistance of a masonry lintel, the guideline / 1/ gives the formula
with 't'uJ 6,11 À
r-- À+O,4 lulQ=L ·b·h--lul À-O,4
allowable shear st rength = 0,1 N/ mm 2
width, effective height of lintel shear ratio according to eqn. (13)
( 14 )
In practice live load on the lintel in most cases will be uniformly distributed and the statical system will be simply spanned. Hence, eqn . ( 13) becomes
and eqn. (14)
lU 1 q
4 h "
h' h+ 1,6--1 2Z ·b --lul 1-1,6h
being lul q = allowable uniformly d{stributed load on lintel 1 = lintel span
( 1::.)
( 16)
As shown in fig , 6 À shall not fall below 0,6 to avoid compression failure of the masonry. Therefore, guideline / 1/ limits the maximum effective height to
Q) u
~ c:
'" '" Q)-I-' .c:'" "' ....
'" Q) ~
max h
0,5
1
2,4
compression failure of masonry
failure of unit/mortar bond
-shear ratio À
Figure 6, Ultimate shear force versus shear ratio
( 171
1546
The insertion of eqn . (17) in eqn. (16) 1eads to an upper 1imit of lu1 q
grenzq 4,161: 'b zul
which, together with the a11owab1e 10ad lu1 q is eva1uated in figo /7/ for the 1inte1 width of b = 115 mm.
Fig./7/a11ows for easily determining the a11owab1e 10ad taken by a masonry 1inte1 as a function of 1ength, height, and width, respective1y.
zulq [kN/mJ
1" Azul q ~ ----'-_ l 1
5 O I I --.---, grenz q =479 kN (h = 112,4)' m
40,-
30
20 If 1intel width
10 multiply lul q
0,5 1,0 1,5 2,0 2,5 3.0 1 [mJ
Figure 7. Admissib1e shear 10ad of 1inte1
STRUCTURAL DETAILING
h
b " 115 llITl
b by-115
To provide adequate anchoring at the supports of the 1inte1 the tension force
FsR 0,75 max Q + N < max M k ·h
l
resu1ting in a minimum required amount of stee1
with
or
BS BS
erf As
i s determi ned.
erf As FsR
B s 24,0 N/mm~ (BSt 420 S) 28,6 N/mm (BSt 500 S)
design amount of stee1, whichever is the greater 3
( 19)
(20)
1547
The bond length required between the edge of the support and the end of the rebar is
12 ~ 1 > 6 d > 40 mm 3 1 s -
(21 )
\'iith bar diameter basic bond length of reinforcement in concrete taken from tab 1 e 2
The support length of the lintel lA (cf. fiC]. 1) shall be at least 115 mm, the lintel shall be supported on a mortar layer. During construction auxiliary supports at a maximum of 1,25 m centers shall be provided; the supports shall not be removed until the masonry compression zone of lintel has been sufficiently hardened and cured. This can be generally assumed to have happened within a week's time. Parallel placing of more than one tension flanges is possible if the width of the masonry compression is not less than the sum of the widths of the flanges.
TABLE 2 Basic bond length l} of reinforcing steel rods in concrete according
to the German Code of practice for concrete structures 131
rebar Basic bond length 11 [mm] for diameter concrete strength classes
d B 25 B 35 B 45 B 55 s [mm]
6 200 170 140 120 8 270 220 180 160
10 340 280 230 200 12 400 330 280 240 14 470 390 320 280 16 540 440 370 320 18 600 500 420 360 20 670 550 400 400
EXAMPLES DF STRUCTURAL DESIGN
In two examples the practical design of masonry lintels using the design method developed in this paper is demonstrated (fig. 8).
POSo 1 Lintel at third floor level:
Sum of loads including floor and roof supports span (cf. fig o 1) given effective height (The concrete floor may be structurally used but not the masonry wall on top .) width (excluding the insulation material)
vorh q 1 h
b'
22,0 kN/m 1,78 m
660 - 105 = 555 mm
240 - 60 180 mm
1548
cross section poso 1
(j)
~~ I f
l 5,0 l 5,0 l 1 1 1
I I [ml
Pos.l 1)0 Figure 8 . Design example
Pos.2 2,18
Shear design
From figo 7 for 1 and h is obtained::
zu 1 q 22. 18 34,4 kN/m :> vorh q
Flexural design
Acting moment
from table 1:
steel required
M
kh
ks
erf AS
11,5
22,0 • 1,782/8
55,5N 8,7 / 0,18
4,55 (BSt 420 S)
4,55 • 8,7/55,5
design amount of stee1 2 0 10 mm ~ 1, 6 cm2
Structural detailing
8,7 kNm
8,0
k z = 0,92
0,7 cm2
FsR
= 0,75' 22,0' 1,78 2
14,7 kN ~ 8,7 0,92 • 0,555
17,0 kN
IA [m]
0,12
0,12
LO
tIl
'"
--r
'"
1549
erf AS = 14,7 /2 4 0,61 em2 , max AS/3 0,53 em2
minimum bond 1ength of rebars
0,61 , 34 em 1,6
8,6 em 7 6 . 1, O em
12 7 - em
3
chosen support 1engt h of 1inte1 = 120 mm . Auxi1iary support at mid-span of 1inte1.
Poso 2 Lintel at first floor level:
Sum of loads vorh q = 71,0 kN/m
Cross seet ion: in analogy to Po s o 1 wit h 2 U-shaped units havin g a wid th of 175 mm and a 15 mm insulation in between .
Shear design
Vir tual load
Henee, b' = 365 - 60 = 305 mm span 1 = 2,18 + 0 ,08 = 2,26 m
q' 71 ,O • ~6',~ = 26 o kN / , :J m,
from fig o 7 for q and 1 the required effeetive height h ~ 760 ·mm ehosen h ~i ght = 805 mm whieh equals 4 eou rses above tension flange.
Flexural design
Ae ting moment
from table 1
steel requi red
desig n amount
of steel
Structural detailing
M 71,0 • 2,26 2/8 = 45,3 kNm
kh 80,5/\/ 45,3 / 0,305 = 6,6
ks 4,67 (BSt 420 S); ~z 0,89
erf AS = 4,67 • 45,3/80,5 = 2,6 em2
2 0 10 mm eaeh U-shape - 3,1 em 2
0,75' 71, O - 2,26 2
60,0 kN == 45,3 63,2 kN
0,89 -0,805
erf AS 60,0 / 24
minimum bond length of rebars
12
2 • 1,0 • 3
1550
0.2 . 34 em 3,1
18,2 em 7 6 • 1, O > ]1 em 3
ehosen support length of lintel = 200 mm (must exeeed bond length of rebars). Auxil iary support at mid -span of lintel.
REFERENCES
/ 1/ German Institute for Standardization, Richtlinie für die Bemessung
und Ausführung von Flachstürzen, Mauerwerk-Kalender 1980, Ernst & Sohn,
Berlin, p . 469-475.
/2/ Ohler, A., Bemessung von Flachstürzen, Mauerwerk-Kalende r 1988, Ernst
& Sohn, Berlin, p. 497-505.
/ 3/ German Institute for Standardization, OIN 1045 - Beton- und Stahlbe
ton, Bemessung und Ausführung, Beton-Kalender 1987, Teil ~, Ernst
& Sohn, Berlin, p. 164-260.
/ 4/ Leonhardt, F. , Vorlesung über Massivbau, Teil 1, Springer-Verlag 1973.
/ 5/ Sehubert, P., and Glitza. H., E-Modul-Werte, Querdehnungszahlen und
Bruchdehnungswerte von Mauerwerk, Oie Bauteehnik 1981, No. 6,
p. 181-185.
/ 6/ Metje, W.-R., Zum EinfluB der Steinfeuchtigkeit bei der Verarbeitung
auf das Trag- und Verformungsverhalten von Mauerwerk, Mitteilungen
~ dem Institut für Baustoffkunde und Materialprüfung TU Hannover,
No . 50, 1983.