175052675-gp004-id-3200-mc-el-0001-anexo-3-estudio-carga (1).pdf
TRANSCRIPT
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
1/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 1
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Electrical Transient Analyzer Program
Load Flow Analysis
Number of Buses:
Swing V-Control Load Total
Number of Branches:
XFMR2 Reactor Line/Cable Impedance Tie PDXFMR3 Total
1 0 12 13
3 0 0 8 0 1 12
Loading Category (1): Design
Generation Category (1): Design
Load Diversity Factor: None
Maximum No. of Iteration: 99
System Frequency: 50 Hz
Unit System: Metric
Project Filename: ATA_CHILE_EB2
Output Filename: B:\ETAP 700\ATA_CHILE_EB2\Untitled.lfr
Precision of Solution: 0.0001000
Method of Solution: Newton-Raphson Method
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
2/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 2
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Adjustments
Transformer Impedance:
Reactor Impedance:
Adjustments
Apply
/Global
Individual
PercentTolerance
Overload Heater Resistance:
Transmission Line Length:
Cable Length:
Temperature Correction
Transmission Line Resistance:
Cable Resistance:
Apply
Adjustments
Individual
/Global Degree C
Individual
Individual
Individual
Individual
Yes
Yes
No
No
No
Yes
Yes
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
3/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 3
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Bus Input Data
Sub-sys
GenericConstant IConstant ZConstant kVAInitial VoltageBus
MvarMWMvarMWMvarMWMvarMWAng.% Mag.kVID
Load
110.000Bus3 1 100.0 0.0
4.160Bus5 1 100.0 0.0
4.160Bus7 1 100.0 0.0
1.999 0.9764.160Bus8 1 100.0 0.0
4.160Bus9 1 100.0 0.0
110.000Bus13 1 100.0 0.0
110.000Bus14 1 100.0 0.0
4.160Bus15 1 100.0 0.0
0.400Bus16 1 100.0 0.0
220.000Bus ST Cerro Negro Norte 1 100.0 0.0
4.160C.D.C (MC-3201) 1 100.0 0.0
0.230 0.1430.380CCM BT (MC-3102) 1 100.0 0.0
220.000ST-Tapp off 1 100.0 0.0
0.1430.976 0.230Total Number of Buses: 13 1.999 0.000 0.000 0.000 0.000
ID kV
Generation Bus
Sub-sysType
Voltage
% Mag. Angle MW Mvar Max Min
Generation Mvar Limits
% PF
Bus ST Cerro Negro Norte 1220.000 Swing 100.0 0.0
0.000 0.000
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
4/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 4
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Line/Cable Input Data
ID Library Size T (C)
Line/Cable
Ohms or Siemens/1000 m per Conductor (Cable) or per Phase (Line)
Adj. (m) #/Phase% Tol.
Length
YR X
Cable B.T. (BP21V01) 0,6NCUN1 250 25.0 2 0.177493 0.108268750.0
Cable MT (MR20U01) 5,0NCUS1 500 50.0 2 0.093176 0.115103750.0
Cable MT (MR20U02) 5,0NCUS1 2 25.0 1 0.636740 0.216667750.0
Cable MT (MR20U03) 5,0NCUS1 250 30.0 2 0.179462 0.124672750.0
Cable MT (MR20U04) 5,0NCUS1 250 25.0 1 0.179462 0.124672750.0
Lnea AT-110 KV 115NCUS1 500 50.0 2 0.109521 0.215989750.0
LAT-110KV-Flint 741 66500.0 1 0.105648 0.360647 0.0000032750.0
LAT-220KV-Flint 741 66500.0 1 0.105648 0.360647 0.0000032750.0
Line / Cable resistances are listed at the specified temperatures.
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
5/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 5
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
2-Winding Transformer Input Data
ID MVA Prim. kV Sec. kV % Z X/R Prim. Sec.
Transformer % Tap Setting
% Tol.
Rating Z Variation
+ 5% - 5%
Phase Shift
Type Angle% Z
Adjusted
Trafo (TF-3201) 7.000 110.000 4.160 8.50 13.55 0 000 0 Std Pos. Seq. 0.0008.5000
Trafo (TF-3202) 0.300 4.160 0.400 4.80 4.70 0 000 0 Std Pos. Seq. 0.0004.8000
TR-Tap Off 20.000 220.000 110.000 10.00 18.60 0 000 0 Std Pos. Seq. 0.00010.0000
2-Winding Transformer Load Tap Changer (LTC) Settings
ID Secondary Bus IDPrimary Bus ID Tap % Step Regulated Bus ID
Transformer Connected Buses ("*" LTC Side)
Tap % V kV
Transformer Load Tap Changer Setting
% Min. % Max.
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
6/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 6
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Branch Connections
ID From Bus To Bus R X ZType
CKT/Branch % Impedance, Pos. Seq., 100 MVA BaseConnected Bus ID
Y
Trafo (TF-3201) Bus14 8.94 121.10 121.43Bus52W XFMR
Trafo (TF-3202) Bus15 332.97 1564.97 1600.00Bus162W XFMR
TR-Tap Off ST-Tapp off 2.68 49.93 50.00Bus32W XFMR
Cable B.T. (BP21V01) Bus16 138.67 84.58 162.43CCM BT (MC-3102)Cable
Cable MT (MR20U01) Bus5 1.35 1.66 2.14C.D.C (MC-3201)Cable
Cable MT (MR20U02) C.D.C (MC-3201) 9.20 3.13 9.72Bus15Cable
Cable MT (MR20U03) Bus7 1.56 1.08 1.89Bus8Cable
Cable MT (MR20U04) Bus7 2.59 1.80 3.16Bus9Cable
Lnea AT-110 KV Bus13 0.00 0.00 0.01Bus14Cable
LAT-110KV-Flint Bus13 5.81 19.82 20.65 2.5805200Bus3Line
LAT-220KV-Flint ST-Tapp off 1.45 4.96 5.16 10.3220800Bus ST Cerro Negro NorteLine
Disyuntor bombas (52) C.D.C (MC-3201) Bus7Tie Breakr
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
7/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 7
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
LOAD FLOW REPORT
Bus
ID kV
Voltage
Ang.% Mag.
Generation
MW Mvar
Load
MW Mvar
Load Flow
MW Mvar AmpID % PF
XFMR
% Tap
Bus3 110.000 -0.8100.919 Bus13 2.246 -1.403 13.8 -84.80 0 0 0
ST-Tapp off -2.246 1.403 13.8 -84.8
Bus5 4.160 -2.599.188 C.D.C (MC-3201) 2.237 1.135 351.0 89.20 0 0 0
Bus14 -2.237 -1.135 351.0 89.2
Bus7 4.160 -2.599.138 Bus8 2.000 0.976 311.5 89.90 0 0 0
Bus9 0.000 0.000 0.0 0.0
C.D.C (MC-3201) -2.000 -0.976 311.5 89.9
Bus8 4.160 -2.599.096 0.9761.999 Bus7 -1.999 -0.976 311.5 89.90 0
Bus9 4.160 -2.599.138 Bus7 0.000 0.000 0.0 0.00 0 0 0
Bus13 110.000 -1.0100.809 Bus14 2.243 1.212 13.3 88.00 0 0 0
Bus3 -2.243 -1.212 13.3 88.0
Bus14 110.000 -1.0100.809 Bus13 -2.243 -1.212 13.3 88.00 0 0 0
Bus5 2.243 1.212 13.3 88.0
Bus15 4.160 -2.599.111 C.D.C (MC-3201) -0.236 -0.157 39.7 83.20 0 0 0
Bus16 0.236 0.157 39.7 83.2
Bus16 0.400 -4.495.886 CCM BT (MC-3102) 0.233 0.145 413.2 85.00 0 0 0
Bus15 -0.233 -0.145 413.2 85.0
Bus ST Cerro Negro Norte* 220.000 0.0100.000 -11.6982.254 ST-Tapp off 2.254 -11.698 31.3 -18.90 0
C.D.C (MC-3201) 4.160 -2.599.138 Bus5 -2.236 -1.134 351.0 89.20 0 0 0
Bus15 0.236 0.157 39.7 83.2
Bus7 2.000 0.976 311.5 89.9
CCM BT (MC-3102) 0.380 -4.4100.443 0.1440.232 Bus16 -0.232 -0.144 413.2 85.00 0
ST-Tapp off 220.000 -0.1100.291 Bus ST Cerro Negro Norte -2.247 1.369 6.9 -85.40 0 0 0
Bus3 2.247 -1.369 6.9 -85.4
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
8/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 8
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Bus Loading Summary Report
ID
Bus
kV
Directly Connected Load
MW Mvar MVA % PF AmpRated Amp LoadingMW Mvar MW Mvar
Constant kVA Constant Z Constant IPercent
Generic
MW Mvar
Total Bus Load
Bus3 110.000 2.648 13.884.80 0 0 0 0 0 0 0
Bus5 4.160 2.508 351.089.20 0 0 0 0 0 0 0
Bus7 4.160 2.225 311.589.90 0 0 0 0 0 0 0
Bus8 4.160 2.225 311.589.91.999 0.976 0 0 0 0 0 0
Bus9 4.160 0 0.00.00 0 0 0 0 0 0 0
Bus13 110.000 2.549 13.388.00 0 0 0 0 0 0 0
Bus14 110.000 2.549 13.388.00 0 0 0 0 0 0 0
Bus15 4.160 0.284 39.783.20 0 0 0 0 0 0 0
Bus16 0.400 0.274 413.285.00 0 0 0 0 0 0 0
Bus ST Cerro Negro Norte 220.000 11.913 31.318.90 0 0 0 0 0 0 0
C.D.C (MC-3201) 4.160 2.507 351.089.20 0 0 0 0 0 0 0
CCM BT (MC-3102) 0.380 0.273 413.285.00 0 0.232 0.144 0 0 0 0
ST-Tapp off 220.000 2.632 6.985.40 0 0 0 0 0 0 0
*Indicates operating load of a bus exceeds the bus critical limit ( 100.0% of the Continuous Ampere rating).
#Indicates operating load of a bus exceeds the bus marginal limit ( 95.0% of the Continuous Ampere rating).
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
9/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 9
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Branch Loading Summary Report
ID Type
Loading
Amp %
Capability
(MVA) MVA %
Loading (output)
CKT / Branch Cable & Reactor
Transformer
Loading (input)
%MVA
Ampacity
(Amp)
Cable B.T. (BP21V01) Cable 449.99 413.19 91.82
Cable MT (MR20U01) Cable 994.55 350.96 35.29
Cable MT (MR20U03) Cable 549.57 311.55 56.69
Lnea AT-110 KV Cable 994.55 13.27 1.33
Trafo (TF-3201) Transformer 7.000 2.549 36.4 2.508 35.8
Trafo (TF-3202) Transformer 0.300 0.284 94.6 0.274 91.5
TR-Tap Off Transformer 20.000 2.648 13.2 2.632 13.2
* Indicates a branch with operating load exceeding the branch capability.
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
10/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 10
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Branch Losses Summary Report
ID MW Mvar MW Mvar kW kvar From To
CKT / Branch From-To Bus Flow To-From Bus Flow Losses % Bus Voltage% Drop
Vd
in Vmag
2 .246 -1.403 -2.243 -1.212 2.9 -2615.5 100.9 100.8 0.11LAT-110KV-Flint
-2.246 1.403 2.247 -1.369 1.8 34.4 100.9 100.3 0.63TR-Tap Off
2.237 1.135 -2.236 -1.134 0.9 1.1 99.2 99.1 0.05Cable MT (MR20U01)
-2.237 -1.135 2.243 1.212 5.7 77.4 99.2 100.8 1.62Trafo (TF-3201)
2.000 0.976 -1.999 -0.976 0.8 0.5 99.1 99.1 0.04Cable MT (MR20U03)
99.1 99.1 0.00Cable MT (MR20U04)
2.243 1.212 -2.243 -1.212 0.0 0.0 100.8 100.8 0.00Lnea AT-110 KV
-0.236 -0.157 0.236 0.157 0.1 0.0 99.1 99.1 0.03Cable MT (MR20U02)
0.236 0.157 -0.233 -0.145 2.7 12.8 99.1 95.9 3.23Trafo (TF-3202)
0.233 0.145 -0.232 -0.144 1.1 0.7 95.9 100.4 0.46Cable B.T. (BP21V01)
2.254 -11.698 -2.247 1.369 6.9 -10328.5 100.0 100.3 0.29LAT-220KV-Flint
23.0 -12817.0
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
11/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 11
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
Alert Summary Report
Cable 95.0100.0
Bus
MarginalCritical
95.0100.0
Loading
% Alert Settings
95.0100.095.0100.0
95.0100.0
LineTransformer
Reactor
Panel
95.0100.0
95.0 98.0
102.0105.0
95.0100.0
95.0100.0
95.0100.0
100.0
Generator Excitation
Bus Voltage
UnderExcited (Q Min.)
OverExcited (Q Max.)
UnderVoltage
OverVoltage
Protective Device
Generator
Marginal Report
Device ID Type Rating/LimitCondition Unit Operating % Operating Phase Type
0.400 kV 0.384 95.9 3-PhaseUnder VoltageBus16 Bus
-
8/10/2019 175052675-GP004-ID-3200-MC-EL-0001-Anexo-3-Estudio-Carga (1).pdf
12/12
Location:
Engineer:Study Case: LF
7.0.0
Page: 12
SN: 12345678
Filename: ATA_CHILE_EB2
Project: ETAP
Contract:
Date: 12-07-2013
Revision: Base
Config.: Normal
0.0000.0000.000
0.0000.0000.000
Lagging85.000.273
Total Generic Load:
Total Constant I Load:
0.0000.000
-12.8170.023
Number of Iterations: 3
System Mismatch:
Apparent Losses:
SUMMARY OF TOTAL GENERATION , LOADING & DEMAND
Lagging89.872.225
Leading
Leading
0.1440.232
0.9761.999
18.9211.913-11.6982.254
0.0000.0000.000
18.9211.913-11.6982.254
% PFMVAMvarMW
Total Static Load:
Total Motor Load:
Total Demand:
Source (Non-Swing Buses):
Source (Swing Buses):