August 29 & 30,
2018
19th National Award for Excellence in Energy Management
Data Centre, Hyderabad
About ICICI Bank
84000+
Employee
s
19
Countrie
s
4867
Branches
Data Centre Overview
Commissione
d
2011
Plot area
1.30 lakh sft
Floors
G + 1
Built up area
22000 sft
Orientation
North South
Density
200 Racks
with 4kW
Load Distribution
66%5%
27%
2%
IT Power Cooling Others
PUE Category
CategoryPUE
Category 0*
PUE
Category 1
PUE
Category 2
PUE
Category 3
IT Energy
measuremen
t location
UPS output UPS outputPDU
Output
Server
input
Definition of
IT energy
Peak IT
electric
demand
IT annual
energy
IT annual
energy
IT annual
energy
Definition of
total energy
Peak total
electric
demand
Total
annual
energy
Total
annual
energy
Total
annual
energy
* For PUE Category 0 the measurements are electric demand (kW)
PUE (Power Usage Effectiveness)
4.5% improvement
2016 2017 2018 2019
1.60
1.53
1.57
1.52
(Projections)
Encon Projects
Cold Aisle Containment
37% CRAC consumption reduced
Focused cooling for efficient enthalpy management
P
R
O
J
E
C
T
1
P
R
O
J
E
C
T
2
Real Time Equipment Monitoring &
Control
Waste elimination
Data collection
Opportunity for improvement
Innovation Projects
Implementation of DCiM
Hot spot and low air flowHot spot alarm triggered
through DCiM and immediately
actioned to install air boosters
Device Failure Averted
Implementation of DCiM
• Data Centre efficiency metrics including PUE
• Energy consumption including cost (kWh)
• Measure efficiency of subsystem
• Identify area of inefficiency and opportunity for improvements
5% optimization in enthalpy
management
Road Map Temp Optimization - PAC
Project Start
220C
01
Blanking panels
230C
02
03
Cold Aisle Containment
270C
04
Active Tiles
290C
Increase 15%
on fan speed
330C
05
Improve
PAC return
temp
350C
(2019)
06
Plans for improvement in PUE
ActivityAnnual Savings Lac
Units
Chiller replacement & plant room
revamp3.2
Revamp high side chilled water
distribution system0.2
Target to achieve PUE of 1.52
S No. Activity Status
1 Air side Economiser Dropped
2New IT equipment with improved
efficiencyOngoing
Project Status of FY 2018
Best Practices
Vulnerability Audit
• Proactively engaged
consultant for
vulnerability audit
• All systems were
thoroughly audited
• High and medium
risks were
immediately actioned
B
E
S
T
P
R
A
C
T
I
C
E
Fire Prevention Trench
• Wild fire during dry
summer was
perennial issue
• Providing fire hydrant
not viable solution
• A trench along the
boundary was created
to cut the fire
B
E
S
T
P
R
A
C
T
I
C
E
GHG Emission Audit & Certification
FY 2018
10485 tCO2e
FY 2017
9220 tCO2e
FY 2016
8862 tCO2e
Audited & Certified
Green Initiatives
NextGen DC
Commissione
d
2017
Floors
G + 2
Built up area
15475 sft
Density
200 Racks
with 9kW
Floor to ceiling height
reduction by 10%
30% Space
Optimized
Construction Material
Pre-cast structure construction
70% construction
waste reduced
Dust pollution reduced
Construction schedule
reduced by 25%
Natural topography maintained
Replantation of tress from construction
area
Top soil carefully
removed and reused
Solar Reflective paints
Exterior wall –reduction in
thermal conduction
Terrace –Reduction of heat island
effect
Construction Images
Bio STP
Capacity - 5000 LPD
Average treated water
2000 LPD
Power consumption - 5
kwh per day
85% power consumption reduction
over conventional STP
Sustainable Site
Efficient water management
Low flow water fixtures
Water meter at 3 locations
Reuse of treated STP water
Thermal conduction prevented through
Use of hollow core slab
Heat reflective paints on side walls
Onsite Renewable Energy
20 kWp solar PV on facade
13316 kWh
Awards & Certification
India’s first IGBC Platinum rated Green
Data Centre
Uptime III certified for Design & Operation
CII – Excellence in Energy Efficiency
TIA 942 tier II
DCD Global – Smart DC award
DCD India – winner smart Data Centre
Data Centre Summit Award
Design management
Energy efficient design
IOT
ISO 27001
OHSAS 18001