194_voltage reduction in supermarkets
TRANSCRIPT
-
7/28/2019 194_Voltage Reduction in Supermarkets
1/5
Voltage reduction
in
supermarkets
Feb 2012
Martin Braun
-
7/28/2019 194_Voltage Reduction in Supermarkets
2/5
- 2 -
Voltage reduction in supermarket
Abstract
A few decades ago experiments were conducted to see if a reduction in voltage also reduced the demand for
energy. Interest in this approach has increased over recent years in different quarters including supermarkets.
This project examines the potential for energy savings for supermarkets by reducing the supply voltage and
focused on two of their major consumers of electricity: Lighting and centralised refrigeration. It was found that
for lighting energy savings depends on the actual light fittings installed and that for centralised refrigeration no
energy savings could be verified.
1. IntroductionThe idea of saving energy by reducing voltage is not new.
For instance in the 1970s and 1980s, there were various
trials conducted in the US to prove its feasibility [1-3].
Therefore it is not surprising that now, when the
reduction of electricity consumption is an important topic,
this approach is being investigated again. Generic
guidance is available on the appropriateness of voltage
management [4] and specific appliances have also been
examined (e.g. domestic appliances [5]).
The investigation here focuses on the retail sector in the
UK, which uses about 3% of total electrical energy [6], in
particular on supermarkets. Therefore more efficient use
of electricity will not only benefit this industry, but the UK
at large. Hence this sector is looking at various ways to
achieve this end. For example, Morrisions expects to
reduce the total store energy demand by up to 7%
through voltage optimisation [7].
The scope of the experiments includes two of the major
categories of electrical equipment found in a supermarket:lighting and centralised refrigeration. How they were
tested and their test results are described in the sections
Lighting and Refrigeration, but, first, an introduction to
the idea of voltage optimising is given. The section on
conclusions discusses the findings and puts them into the
wider context.
2. TheoryThe consumed electrical energy is the time integral of
power. Hence, to reduce energy consumption, either the
time or the power (or both) needs to be reduced while, at
the same time, the other component must not increase
proportionally (or even disproportionately).
Voltage reduction as a means of saving energy in the UK
relies on the large voltage tolerance of 10% (i.e. from
207V to 253V) [8]. For historic reasons, the voltage is
frequently considerably above the lower limit [4] at which
CE marked equipment should be able to operate.
Therefore reducing the voltage may also lower the power
consumption as power is a function of voltage, current
and the power factor. However, as these three factors are
load-dependent, they may not be independent of each
other. Hence the load has to be investigated to get the
real picture.
3. LightingThe lamps examined here include different types of
fluorescent lamps, i.e. with an external ballast and
compact lamps. The compact lamps came from three
different brands (including one unbranded CFL). The
experiments also examined metal halide and LED lamps
(see Table 1).
Technology Description
Fluorescent 58W linear with inductive ballast
Fluorescent 58W linear with electronic ballast
Fluorescent 3 x 24W linear with electronic ballast
Fluorescent Compact 9W
Fluorescent Compact 11W
Fluorescent Compact 18W
Fluorescent Compact 20W
Fluorescent Compact 21W
Metal Halide 4 x 35W with inductive ballast
Metal Halide 1 x 35W with electronic ballast
Metal Halide 1 x 70W with electronic ballast
LED 10W tube
LED 22W tubeTable 1: Lamps examined
Remarks: Blue lines - test leads,
Black lines - Power to lamp
Figure 1: Test set-up Lighting
The schematic of the test set-up in Figure 1 shows that the
voltage was varied through an autotransformer. Multi
meter No 2 logged both the voltage and the power (multi
meter No 1 was used for indication only). The lux meter
measured any relative change in light output. In addition,
the current and voltage wave forms were recorded with a
storage oscilloscope.
1.1 Results External ballastFor ease of comparison the lamps tested here are broken
down into three different categories. The first relates to
-
7/28/2019 194_Voltage Reduction in Supermarkets
3/5
- 3 -
fluorescent and metal halide lamps with external ballasts.
The graphs in Figure 2 indicate that there is virtually a
linear relationship between the relative voltage and
relative power for the inductive ballast and no
dependence on the input voltage for the electronic ballast
(all values are normalised to 230V). The same relationship
also holds for metal halide lamps. In addition to this, one
finds that illuminance behaves essentially the same as thecorresponding power.
Figure 2: 58W linear fluorescent lamp Power consumption
The power consumption of lamps with an inductive ballast
is 10% (metal halide) to 16% (58W linear fluorescent)
higher than the equivalent lamp with an electronic ballast.
1.2 Results Compact fluorescent
Figure 3: Compact fluorescent lamps - Power consumption
Based on voltage-power graphs compact fluorescent
lamps can be sub-divided into those around 10W (i.e. 9W
and 11W) and the higher power lamps. The lower
powered devices behave in a very non linear way as can
be seen in Figure 3. At some point below 230V (100% of
voltage) the power consumption rises as the voltage is
reduced. This behaviour is not observed with the
remaining three lamps with a higher power rating. They
show a relative linear relationship.
Looking at the test results further it can also be seen thatcompact fluorescent lamps consume about 30% more
than their rating at 230V. Additionally, the data also
reveals that, for compact lamps, the illuminance falls
linearly between 0.67 (9W) to 1.35 percentage point (21W)
per 1 percentage point of voltage reduction.
1.3 Results LED lampsFigure 4, relating to the two LED lamps, shows not only
the power graphs, but also includes the plot for the
illuminance of the 10W lamp and shows that the light
output is independent of voltage (this is also true for the22W lamp). Furthermore the figure shows that for the
smaller of the two lamps the voltage reduction results in a
reduction in power demand below 230V. The power
consumption of the larger lamp exhibits virtually no
dependency on the input voltage.
Figure 4: LED lamps - Power and illuminance
4. RefrigerationThis section describes the experiments performed on a
centralised refrigeration plant installed in a training facility;
therefore the cooling load is smaller than would be
expected for a system of this size (under unforced, normal
condition the plant uses about 25% of its maximum power.
Maximum means all compressors and fans running). As
Figure 5 shows, for this series of experiments, the electric
part of the system was fed through a voltage optimisation
system which allows control of the voltage between 220V
and the mains voltage level. The set-up has two main
meters (9F08 for all compressors and 912 for the fans)
and three sub-meters, one for each compressor.
Compressor No 3 is supplied through a variable speed
drive; the others are directly fed.
The test programme included three parts which lead to
three data sets relating to:
1. Time intervals before and after the installation of thevoltage optimisation equipment.
2. The variation of the voltage at normal operationconditions.
3. The variation of the voltage under full loadconditions (i.e. all three compressors and all four
fans running simultaneously).
As meter 908 did not read I3 correctly after the
installation, only the power consumption of phases 1 and2 were examined to see if there was a reduction in energy
consumption. With this in mind the energy consumed
75%
80%
85%
90%
95%
100%
105%
110%
115%
120%
125%
90% 95% 100% 105% 110%
Relativepower(%)
Relative voltage (%)
Inductive ballast Electronic ballast
75%
80%
85%
90%
95%
100%
105%
110%
115%
120%
125%
90% 95% 100% 105% 110%
Relativepower(%)
Relative voltage (%)9W 11W 18W 20W 21W
75%
80%
85%
90%
95%
100%
105%
110%
115%
120%
125%
90% 95% 100% 105% 110%
Relativepower
,illuminance(%)
Relative voltage (%)
10W - Pow (%) 10W - Illu (%) 22W - Pow (%)
-
7/28/2019 194_Voltage Reduction in Supermarkets
4/5
- 4 -
before and after installation was compared and the
results are summarized in Figure 6. Although the data is
not entirely consistent, it does not support a claim of
reduced energy demand. The case for the fans metered
through 912 is similar so that no overall energy savings
were found.
Remarks: Black lines: Power
Blue lines: Measuring total through 908 or 912Purple lines: Sub-metering components
Figure 5: Test set up Refrigeration
As meter 908 did not read I3 correctly after the
installation, only the power consumption of phases 1 and
2 were examined to see if there was a reduction in energy
consumption. With this in mind the energy consumed
before and after installation was compared and the
results are summarized in Figure 6. Although the data is
not entirely consistent, it does not support a claim of
reduced energy demand. The case for the fans metered
through 912 is similar so that no overall energy savings
were found.
Time Average Energy 1 Average Energy 2
27 Jan 07
9:00-12:00 1.01kWh/h 0.94kWh/h
15:00-18:00 1.23kWh/h 1.07kWh/h
Change (%) 22.14% 14.01%
11:00-12:00 1.19kWh 1.12kWh
16:00-17:00 1.27kWh 1.08kWh
Change (%) 6.71% -3.81%
26 Jan 02
16:00-17:00 1.09kWh 0.98kWh
Change (%) 16.5% 10%Figure 6: 908 - Comparing before and after
To verify these findings the data set relating to the voltage
variations under normal conditions was also analysed and
the data is visualised in Figure 7. This figure displays the
star voltages and the energy meter reading. If the gradient
of the energy reading is constant, then there is no change
in energy consumption, which is the case not only for 908
(average energy consumption per phase: 1.5kWh/h), but
also 912 (not displayed here, average energy consumption:
0.8kWh/h).
Finally, the system was tested under full load conditions
by adjusting the refrigeration plant settings accordinglyand then increasing the voltage from 220V to about 240V
in 5-Volt steps. At each step the power readings were
taken and then the system was allowed to recover before
proceeding. The top ten power readings in each interval
were averaged and then analysed. It was found that the
overall power consumption drops slightly when the
voltage is reduced. The graphs for the individual motors
are displayed in Figure 8. This figure that the VSD driven
motor is essentially voltage independent, the fans seem to
consume less power at reduced voltage (r=0.8) and thatpower demand of compressor No 1 increases as the
voltage drops, but that the behaviour of compressor No 2
is not so clear.
Figure 7: Energy reading under normal load conditions for 908
Figure 8: Power vs voltage graph of components
5. ConclusionsHere, the question of whether a reduction in voltage on
lighting and centralised refrigeration saves energy in a
supermarket was investigated. The findings show that for
lighting it depends on the actual light fitting (see Table 2)and that for the refrigeration plant no energy savings
were observed.
The colour coding in Table 2 helps to break down the
results with regards to saving potentials. Highlighted in
green are light fittings which show a reduction of about 2
percentage per percentage of voltage reduction. These
findings also agree with guidance given in [4].
Furthermore it was found that, not only is the power
demand of the actual lamp voltage dependent [9], but
also the inductive components add to the power
consumption. For the fluorescent lamp and the metal
halide they add 16% and 10%, respectively. The savings ofthe higher rated CFLs are greater than observed in [5]
which may be because the components of the actual CFLs
95%
100%
105%
110%
220 225 230 235 240
P
ower(%)
Voltage (V)909 910 911 912
-
7/28/2019 194_Voltage Reduction in Supermarkets
5/5
- 5 -
tested might have been different. Incidentally, the power
ratings of CFLs were about a third below their real power
consumption (at 230V) measured during the experiments
here.
The yellow shaded rows indicate small savings or a more
complex case. For instance, the power demand drops for
the 10W LED tube below 230W by just over one
percentage point for every percentage point of voltagereduction whilst keeping its light output virtually constant.
Such a relationship is to be expected because the light
output of an LED depends on the drive current (for an
example see [10]). A less straightforward case is the lower
rated CFLs where, unlike their higher powered
counterparts, the power demand can actually increase
with voltage reduction. The difference may stem from
different values of the circuit components. If, for example,
all CFLs used the VK05CFL IC, then some of the
component values would be different for the lower power
CFLs.
Technology Description
Fluorescent 58W linear with inductive ballast
Fluorescent Compact 20W
Metal Halide 4 x 35W with inductive ballast
Fluorescent Compact 18W
Fluorescent Compact 21W
LED 10W tube
Fluorescent Compact 9W
Fluorescent Compact 11W
Fluorescent 58W linear with electronic ballast
Fluorescent 3 x 24W linear with electronic ballast
Metal Halide 1 x 35W with electronic ballastMetal Halide 1 x 70W with electronic ballast
LED 22W tubeTable 2: Result Lighting
Finally, pink denotes that power demand is voltage
independent and therefore voltage optimisation measures
are not effective. Apart from the 22W LED tube, these
light fittings use relatively sophisticated external
electronic ballast, which, not only makes the light fitting
voltage independent, but also corrects the power factor
so that an almost pure current sine wave is produced.
During the second set of experiments relating to the
refrigeration plant no energy savings were observed
through voltage reduction. If this plant can be treated as a
thermostat controlled device, then the findings here are
consistent with [4] and [5]. Thermostat controlled devices
can be thought of as consuming the same energy even if
the input power is reduced as energy is not necessarily
proportional to the power input. (One notable exception
is where the load is permanently on; as frequently is the
case with lighting).
To verify these findings it would have been ideal to
conduct the same experiment more than once, but,
because of time constraints, is was not possible. It was
also unfortunate that the data normally stored in the
voltage optimisation equipment could not be retrieved.
The examinations of the individual compressors and fans
showed that the behaviour of a given motor depends,
amongst other things, upon its load and mode of control.
The power demand of compressor No 3, for instance.
which is controlled through a VSD, is independent of the
input voltage [4]. On the other hand, for compressors No
1 and No 2, which are directly mains fed, the power
consumption actually increases as the voltage is reduced(albeit it that the relationship is relatively weak for
compressor No 2). A possible explanation is that these
compressors have to deliver the same mechanical output
power regardless of its input voltage. So, as the voltage
drops the current increases driving up the electric losses
in the motor disproportionately (as Ploss = I2
* R).
The case for the fans is different again. Here both the fan
speed and fan torque are reduced with decreased voltage
(the relationship between load torque and speed is
relatively complex) [11], (page 206). Therefore, as the
output power is proportional to torque and speed, the
power demand drops as the voltage is brought down.
Acknowledgments
The author wishes to gratefully acknowledge the helpful
guidance of Dr David Stone, University of Sheffield, as well
as Mr Keith Bertie and Mr Matthew Maaer, Oaksmere and
the staff from iVolt for their help.
References
1. Scalley, B.R. and D.G. Kasten, The effects of distribution
voltage reduction on power and energy consumption.
IEEE Transactions on Education, 1981. 24(3): p. 210-
216.2. Gustafson, M.W., Residental End Use Load Affected by
Voltage Reduction. IEEE Transactions on Power
Apparatus and Systems, 1981. PAS-100(11): p. 4381-
4388.
3. Kirshner, D. and P. Giorsetto, Statistical Test of Energy
Saving Due to Voltage Reduction. Power Apparatus
and Systems, IEEE Transactions on, 1984. PAS-103(6):
p. 1205-1210.
4. Trust, C., Voltage management, 2011, Carbon Trust:
London.
5. Hood, G.K. The effects of voltage variation on the
power consumption and running cost of domestic
appliances. in Australasian Universities Power
Engineering Conference. 2004. Brisbane, Australia.
6. Tassou, S.A., et al., Energy consumption and
conservation in food retailing. Applied Thermal
Engineering, 2011. 31(2-3): p. 147-156.
7. Morrisons, Corporate responsibility review 2011/11,
2011.
8. BSI, BS7697:1993 Nominal voltage for low voltage
pulbic electricity supply systems, 2003, BSI: London.
9. Simpson, R.S., Lighting control : technology and
applications2003, Oxford Focal.
10. Mobicon, Data sheet for 5mm super white LED,
Surplustronics, Editor, Surplustronics: Auckland City.
11. Hughes, A., Electric motors and drives. 3rd ed2006,
Oxford: Elsevier.