194_voltage reduction in supermarkets

Upload: anonymous-ngxdt2bx

Post on 03-Apr-2018

216 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/28/2019 194_Voltage Reduction in Supermarkets

    1/5

    Voltage reduction

    in

    supermarkets

    Feb 2012

    Martin Braun

  • 7/28/2019 194_Voltage Reduction in Supermarkets

    2/5

    - 2 -

    Voltage reduction in supermarket

    Abstract

    A few decades ago experiments were conducted to see if a reduction in voltage also reduced the demand for

    energy. Interest in this approach has increased over recent years in different quarters including supermarkets.

    This project examines the potential for energy savings for supermarkets by reducing the supply voltage and

    focused on two of their major consumers of electricity: Lighting and centralised refrigeration. It was found that

    for lighting energy savings depends on the actual light fittings installed and that for centralised refrigeration no

    energy savings could be verified.

    1. IntroductionThe idea of saving energy by reducing voltage is not new.

    For instance in the 1970s and 1980s, there were various

    trials conducted in the US to prove its feasibility [1-3].

    Therefore it is not surprising that now, when the

    reduction of electricity consumption is an important topic,

    this approach is being investigated again. Generic

    guidance is available on the appropriateness of voltage

    management [4] and specific appliances have also been

    examined (e.g. domestic appliances [5]).

    The investigation here focuses on the retail sector in the

    UK, which uses about 3% of total electrical energy [6], in

    particular on supermarkets. Therefore more efficient use

    of electricity will not only benefit this industry, but the UK

    at large. Hence this sector is looking at various ways to

    achieve this end. For example, Morrisions expects to

    reduce the total store energy demand by up to 7%

    through voltage optimisation [7].

    The scope of the experiments includes two of the major

    categories of electrical equipment found in a supermarket:lighting and centralised refrigeration. How they were

    tested and their test results are described in the sections

    Lighting and Refrigeration, but, first, an introduction to

    the idea of voltage optimising is given. The section on

    conclusions discusses the findings and puts them into the

    wider context.

    2. TheoryThe consumed electrical energy is the time integral of

    power. Hence, to reduce energy consumption, either the

    time or the power (or both) needs to be reduced while, at

    the same time, the other component must not increase

    proportionally (or even disproportionately).

    Voltage reduction as a means of saving energy in the UK

    relies on the large voltage tolerance of 10% (i.e. from

    207V to 253V) [8]. For historic reasons, the voltage is

    frequently considerably above the lower limit [4] at which

    CE marked equipment should be able to operate.

    Therefore reducing the voltage may also lower the power

    consumption as power is a function of voltage, current

    and the power factor. However, as these three factors are

    load-dependent, they may not be independent of each

    other. Hence the load has to be investigated to get the

    real picture.

    3. LightingThe lamps examined here include different types of

    fluorescent lamps, i.e. with an external ballast and

    compact lamps. The compact lamps came from three

    different brands (including one unbranded CFL). The

    experiments also examined metal halide and LED lamps

    (see Table 1).

    Technology Description

    Fluorescent 58W linear with inductive ballast

    Fluorescent 58W linear with electronic ballast

    Fluorescent 3 x 24W linear with electronic ballast

    Fluorescent Compact 9W

    Fluorescent Compact 11W

    Fluorescent Compact 18W

    Fluorescent Compact 20W

    Fluorescent Compact 21W

    Metal Halide 4 x 35W with inductive ballast

    Metal Halide 1 x 35W with electronic ballast

    Metal Halide 1 x 70W with electronic ballast

    LED 10W tube

    LED 22W tubeTable 1: Lamps examined

    Remarks: Blue lines - test leads,

    Black lines - Power to lamp

    Figure 1: Test set-up Lighting

    The schematic of the test set-up in Figure 1 shows that the

    voltage was varied through an autotransformer. Multi

    meter No 2 logged both the voltage and the power (multi

    meter No 1 was used for indication only). The lux meter

    measured any relative change in light output. In addition,

    the current and voltage wave forms were recorded with a

    storage oscilloscope.

    1.1 Results External ballastFor ease of comparison the lamps tested here are broken

    down into three different categories. The first relates to

  • 7/28/2019 194_Voltage Reduction in Supermarkets

    3/5

    - 3 -

    fluorescent and metal halide lamps with external ballasts.

    The graphs in Figure 2 indicate that there is virtually a

    linear relationship between the relative voltage and

    relative power for the inductive ballast and no

    dependence on the input voltage for the electronic ballast

    (all values are normalised to 230V). The same relationship

    also holds for metal halide lamps. In addition to this, one

    finds that illuminance behaves essentially the same as thecorresponding power.

    Figure 2: 58W linear fluorescent lamp Power consumption

    The power consumption of lamps with an inductive ballast

    is 10% (metal halide) to 16% (58W linear fluorescent)

    higher than the equivalent lamp with an electronic ballast.

    1.2 Results Compact fluorescent

    Figure 3: Compact fluorescent lamps - Power consumption

    Based on voltage-power graphs compact fluorescent

    lamps can be sub-divided into those around 10W (i.e. 9W

    and 11W) and the higher power lamps. The lower

    powered devices behave in a very non linear way as can

    be seen in Figure 3. At some point below 230V (100% of

    voltage) the power consumption rises as the voltage is

    reduced. This behaviour is not observed with the

    remaining three lamps with a higher power rating. They

    show a relative linear relationship.

    Looking at the test results further it can also be seen thatcompact fluorescent lamps consume about 30% more

    than their rating at 230V. Additionally, the data also

    reveals that, for compact lamps, the illuminance falls

    linearly between 0.67 (9W) to 1.35 percentage point (21W)

    per 1 percentage point of voltage reduction.

    1.3 Results LED lampsFigure 4, relating to the two LED lamps, shows not only

    the power graphs, but also includes the plot for the

    illuminance of the 10W lamp and shows that the light

    output is independent of voltage (this is also true for the22W lamp). Furthermore the figure shows that for the

    smaller of the two lamps the voltage reduction results in a

    reduction in power demand below 230V. The power

    consumption of the larger lamp exhibits virtually no

    dependency on the input voltage.

    Figure 4: LED lamps - Power and illuminance

    4. RefrigerationThis section describes the experiments performed on a

    centralised refrigeration plant installed in a training facility;

    therefore the cooling load is smaller than would be

    expected for a system of this size (under unforced, normal

    condition the plant uses about 25% of its maximum power.

    Maximum means all compressors and fans running). As

    Figure 5 shows, for this series of experiments, the electric

    part of the system was fed through a voltage optimisation

    system which allows control of the voltage between 220V

    and the mains voltage level. The set-up has two main

    meters (9F08 for all compressors and 912 for the fans)

    and three sub-meters, one for each compressor.

    Compressor No 3 is supplied through a variable speed

    drive; the others are directly fed.

    The test programme included three parts which lead to

    three data sets relating to:

    1. Time intervals before and after the installation of thevoltage optimisation equipment.

    2. The variation of the voltage at normal operationconditions.

    3. The variation of the voltage under full loadconditions (i.e. all three compressors and all four

    fans running simultaneously).

    As meter 908 did not read I3 correctly after the

    installation, only the power consumption of phases 1 and2 were examined to see if there was a reduction in energy

    consumption. With this in mind the energy consumed

    75%

    80%

    85%

    90%

    95%

    100%

    105%

    110%

    115%

    120%

    125%

    90% 95% 100% 105% 110%

    Relativepower(%)

    Relative voltage (%)

    Inductive ballast Electronic ballast

    75%

    80%

    85%

    90%

    95%

    100%

    105%

    110%

    115%

    120%

    125%

    90% 95% 100% 105% 110%

    Relativepower(%)

    Relative voltage (%)9W 11W 18W 20W 21W

    75%

    80%

    85%

    90%

    95%

    100%

    105%

    110%

    115%

    120%

    125%

    90% 95% 100% 105% 110%

    Relativepower

    ,illuminance(%)

    Relative voltage (%)

    10W - Pow (%) 10W - Illu (%) 22W - Pow (%)

  • 7/28/2019 194_Voltage Reduction in Supermarkets

    4/5

    - 4 -

    before and after installation was compared and the

    results are summarized in Figure 6. Although the data is

    not entirely consistent, it does not support a claim of

    reduced energy demand. The case for the fans metered

    through 912 is similar so that no overall energy savings

    were found.

    Remarks: Black lines: Power

    Blue lines: Measuring total through 908 or 912Purple lines: Sub-metering components

    Figure 5: Test set up Refrigeration

    As meter 908 did not read I3 correctly after the

    installation, only the power consumption of phases 1 and

    2 were examined to see if there was a reduction in energy

    consumption. With this in mind the energy consumed

    before and after installation was compared and the

    results are summarized in Figure 6. Although the data is

    not entirely consistent, it does not support a claim of

    reduced energy demand. The case for the fans metered

    through 912 is similar so that no overall energy savings

    were found.

    Time Average Energy 1 Average Energy 2

    27 Jan 07

    9:00-12:00 1.01kWh/h 0.94kWh/h

    15:00-18:00 1.23kWh/h 1.07kWh/h

    Change (%) 22.14% 14.01%

    11:00-12:00 1.19kWh 1.12kWh

    16:00-17:00 1.27kWh 1.08kWh

    Change (%) 6.71% -3.81%

    26 Jan 02

    16:00-17:00 1.09kWh 0.98kWh

    Change (%) 16.5% 10%Figure 6: 908 - Comparing before and after

    To verify these findings the data set relating to the voltage

    variations under normal conditions was also analysed and

    the data is visualised in Figure 7. This figure displays the

    star voltages and the energy meter reading. If the gradient

    of the energy reading is constant, then there is no change

    in energy consumption, which is the case not only for 908

    (average energy consumption per phase: 1.5kWh/h), but

    also 912 (not displayed here, average energy consumption:

    0.8kWh/h).

    Finally, the system was tested under full load conditions

    by adjusting the refrigeration plant settings accordinglyand then increasing the voltage from 220V to about 240V

    in 5-Volt steps. At each step the power readings were

    taken and then the system was allowed to recover before

    proceeding. The top ten power readings in each interval

    were averaged and then analysed. It was found that the

    overall power consumption drops slightly when the

    voltage is reduced. The graphs for the individual motors

    are displayed in Figure 8. This figure that the VSD driven

    motor is essentially voltage independent, the fans seem to

    consume less power at reduced voltage (r=0.8) and thatpower demand of compressor No 1 increases as the

    voltage drops, but that the behaviour of compressor No 2

    is not so clear.

    Figure 7: Energy reading under normal load conditions for 908

    Figure 8: Power vs voltage graph of components

    5. ConclusionsHere, the question of whether a reduction in voltage on

    lighting and centralised refrigeration saves energy in a

    supermarket was investigated. The findings show that for

    lighting it depends on the actual light fitting (see Table 2)and that for the refrigeration plant no energy savings

    were observed.

    The colour coding in Table 2 helps to break down the

    results with regards to saving potentials. Highlighted in

    green are light fittings which show a reduction of about 2

    percentage per percentage of voltage reduction. These

    findings also agree with guidance given in [4].

    Furthermore it was found that, not only is the power

    demand of the actual lamp voltage dependent [9], but

    also the inductive components add to the power

    consumption. For the fluorescent lamp and the metal

    halide they add 16% and 10%, respectively. The savings ofthe higher rated CFLs are greater than observed in [5]

    which may be because the components of the actual CFLs

    95%

    100%

    105%

    110%

    220 225 230 235 240

    P

    ower(%)

    Voltage (V)909 910 911 912

  • 7/28/2019 194_Voltage Reduction in Supermarkets

    5/5

    - 5 -

    tested might have been different. Incidentally, the power

    ratings of CFLs were about a third below their real power

    consumption (at 230V) measured during the experiments

    here.

    The yellow shaded rows indicate small savings or a more

    complex case. For instance, the power demand drops for

    the 10W LED tube below 230W by just over one

    percentage point for every percentage point of voltagereduction whilst keeping its light output virtually constant.

    Such a relationship is to be expected because the light

    output of an LED depends on the drive current (for an

    example see [10]). A less straightforward case is the lower

    rated CFLs where, unlike their higher powered

    counterparts, the power demand can actually increase

    with voltage reduction. The difference may stem from

    different values of the circuit components. If, for example,

    all CFLs used the VK05CFL IC, then some of the

    component values would be different for the lower power

    CFLs.

    Technology Description

    Fluorescent 58W linear with inductive ballast

    Fluorescent Compact 20W

    Metal Halide 4 x 35W with inductive ballast

    Fluorescent Compact 18W

    Fluorescent Compact 21W

    LED 10W tube

    Fluorescent Compact 9W

    Fluorescent Compact 11W

    Fluorescent 58W linear with electronic ballast

    Fluorescent 3 x 24W linear with electronic ballast

    Metal Halide 1 x 35W with electronic ballastMetal Halide 1 x 70W with electronic ballast

    LED 22W tubeTable 2: Result Lighting

    Finally, pink denotes that power demand is voltage

    independent and therefore voltage optimisation measures

    are not effective. Apart from the 22W LED tube, these

    light fittings use relatively sophisticated external

    electronic ballast, which, not only makes the light fitting

    voltage independent, but also corrects the power factor

    so that an almost pure current sine wave is produced.

    During the second set of experiments relating to the

    refrigeration plant no energy savings were observed

    through voltage reduction. If this plant can be treated as a

    thermostat controlled device, then the findings here are

    consistent with [4] and [5]. Thermostat controlled devices

    can be thought of as consuming the same energy even if

    the input power is reduced as energy is not necessarily

    proportional to the power input. (One notable exception

    is where the load is permanently on; as frequently is the

    case with lighting).

    To verify these findings it would have been ideal to

    conduct the same experiment more than once, but,

    because of time constraints, is was not possible. It was

    also unfortunate that the data normally stored in the

    voltage optimisation equipment could not be retrieved.

    The examinations of the individual compressors and fans

    showed that the behaviour of a given motor depends,

    amongst other things, upon its load and mode of control.

    The power demand of compressor No 3, for instance.

    which is controlled through a VSD, is independent of the

    input voltage [4]. On the other hand, for compressors No

    1 and No 2, which are directly mains fed, the power

    consumption actually increases as the voltage is reduced(albeit it that the relationship is relatively weak for

    compressor No 2). A possible explanation is that these

    compressors have to deliver the same mechanical output

    power regardless of its input voltage. So, as the voltage

    drops the current increases driving up the electric losses

    in the motor disproportionately (as Ploss = I2

    * R).

    The case for the fans is different again. Here both the fan

    speed and fan torque are reduced with decreased voltage

    (the relationship between load torque and speed is

    relatively complex) [11], (page 206). Therefore, as the

    output power is proportional to torque and speed, the

    power demand drops as the voltage is brought down.

    Acknowledgments

    The author wishes to gratefully acknowledge the helpful

    guidance of Dr David Stone, University of Sheffield, as well

    as Mr Keith Bertie and Mr Matthew Maaer, Oaksmere and

    the staff from iVolt for their help.

    References

    1. Scalley, B.R. and D.G. Kasten, The effects of distribution

    voltage reduction on power and energy consumption.

    IEEE Transactions on Education, 1981. 24(3): p. 210-

    216.2. Gustafson, M.W., Residental End Use Load Affected by

    Voltage Reduction. IEEE Transactions on Power

    Apparatus and Systems, 1981. PAS-100(11): p. 4381-

    4388.

    3. Kirshner, D. and P. Giorsetto, Statistical Test of Energy

    Saving Due to Voltage Reduction. Power Apparatus

    and Systems, IEEE Transactions on, 1984. PAS-103(6):

    p. 1205-1210.

    4. Trust, C., Voltage management, 2011, Carbon Trust:

    London.

    5. Hood, G.K. The effects of voltage variation on the

    power consumption and running cost of domestic

    appliances. in Australasian Universities Power

    Engineering Conference. 2004. Brisbane, Australia.

    6. Tassou, S.A., et al., Energy consumption and

    conservation in food retailing. Applied Thermal

    Engineering, 2011. 31(2-3): p. 147-156.

    7. Morrisons, Corporate responsibility review 2011/11,

    2011.

    8. BSI, BS7697:1993 Nominal voltage for low voltage

    pulbic electricity supply systems, 2003, BSI: London.

    9. Simpson, R.S., Lighting control : technology and

    applications2003, Oxford Focal.

    10. Mobicon, Data sheet for 5mm super white LED,

    Surplustronics, Editor, Surplustronics: Auckland City.

    11. Hughes, A., Electric motors and drives. 3rd ed2006,

    Oxford: Elsevier.