1.converter transformer

Upload: pezic

Post on 05-Apr-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 7/31/2019 1.Converter Transformer

    1/33

    Converter Transformer

  • 7/31/2019 1.Converter Transformer

    2/33

    HVDC Systems for

    Energy Transmission over long distances

    Asynchronous coupling between AC Regional networks

    Power Electronic circuits are used to convert AC to DC (Rectifier circuits) or

    convert DC to AC (Inverter Circuits). Both of these circuits are also called

    converter circuits.

    A transformer that has one of its windings connected to one of these

    circuits, as a dedicated transformer, is a Converter Transformer

  • 7/31/2019 1.Converter Transformer

    3/33

    Converter Transformer in HVDC system.

    Supply of AC voltages into two separate circuits feeding the

    rectifier bridges with a phase shift of 30 electrical degrees for

    reduction of low order harmonics esp. 5th & 7th harmonics.

    As a galvanic barrier between AC and DC systems to prevent

    DC potential entering into the AC system

    Reactive Impedance in the AC supply to reduce short circuit

    currents and to control the rate of rise in valve current during

    commutation.

  • 7/31/2019 1.Converter Transformer

    4/33

    Converter Transformers for 12 pulse rectification.

    Primary: Star 400 kV AC

    Secondary: Two windings connected to converter (Thyristors)

    connected in series to build up required level of DC voltage

  • 7/31/2019 1.Converter Transformer

    5/33

    transport restrictions (dimensions and weight)

    number of necessary spare transformers

    technical possible solutions for core and windings

    Choice of transformer design is mainlyruled by.

  • 7/31/2019 1.Converter Transformer

    6/33

    Converter Transformers for 12 pulse rectification

    Type of Connections No. of design X No.of units

    Sparesrequired

    3 Phase Star-Delta & Star-Star

    2 X 2 2

    Single phase 2 winding 2 X 6 2

    Singe phase 3 winding 2 x 3 1

    Extended delta-connection

    2 X 2 1

    3 Phase 3 winding 2 X 2 1

  • 7/31/2019 1.Converter Transformer

    7/33

    Converter Transformer....

    Designactive part

    Valve Winding (D)Valve Winding (Y)

    Line Winding

    Tap Winding

    HV-Terminal

    Neutral-Terminal

    Simplified connection of

    line windings and tap windings

    Winding and core arrangement

  • 7/31/2019 1.Converter Transformer

    8/33

    Converter Xmer & Normal AC Xmer..

    Polarity Reversal

    Voltage Distribution in Oil Barrier System

    Impedance variation influence On load Tap Changer

    Harmonic Currents

    Losses

    DC Magnetisation Short Circuit Forces

    DC Bushings

  • 7/31/2019 1.Converter Transformer

    9/33

    Beginning voltage stress distributions capacitive Oil is stressed

    more than PB

    Successively change over to Resistive distribution PB is

    stressed more (almost all stress across solid insulation)

    PD stresses under DC Sporadic pulses at random intervals

    -Discharges in oil gaps under rapid changes in voltage

    -Discharges in cellulose insulation due to imperfections ininsulation

    -Discharges at the oil-cellulose interface

    . To meet above, special oil-barrier insulation system is required

    Under Polarity Reversal..

  • 7/31/2019 1.Converter Transformer

    10/33

    Voltage Distribution in Oil-Barrier System...

  • 7/31/2019 1.Converter Transformer

    11/33

    Main duct in HVDC transformers require more PB barriers than normalAC transformers as DC voltage is taken mainly by PB. Voltagedistribution is by resistivity in steady state.

    - Transient DC voltages:

    Start up of converter when full DC potential from bridgesis developed almost instantaneously

    - DC Voltage Polarity Reversal: When direction of power flow is changed in HVDC system, current

    direction remains the same while polarity of the voltage will be reversed.

    This is done within a few number of power cycles. A sudden change in DC voltage is capacitive. Time constant for the transition from capacitive to resistive distribution

    is about an hour.

    Voltage Distribution in Oil-Barrier System...

  • 7/31/2019 1.Converter Transformer

    12/33

    AC DC

    Voltage Distribution in Oil-Barrier System...

  • 7/31/2019 1.Converter Transformer

    13/33

  • 7/31/2019 1.Converter Transformer

    14/33

    Valve windings to withstand AC voltages, superimposed DC

    voltages on AC voltages, DC Voltage Polarity Reversal

    Composite insulation of Pressboard or Paper (Solid) and

    oil (liquid)

    Voltage distribution between paper & oil under AC conditions

    depends on inverse ratio of dielectric constants of

    PB/ Oil (2:1)

    Voltage distribution between oil & paper under steady state

    DC voltage depends on direct ratio of resistivities (1:10 ~ 500),

    depends on oil quality, moisture content and temperature

    Insulation Design

  • 7/31/2019 1.Converter Transformer

    15/33

    Closer Tolerance in Impedance is required between three phases andalso between upper & lower bridges (star-star, star-delta circuits)

    ( 6% on special tolerance and 2-3% variation between units (Normal transformers 10%)

    The above is necessary : To reduce distortion in DC voltage wave form To reduce non-characteristic harmonics, thereby cost of AC filters To reduce residual currents between three phases, which can act

    as DC magnetization on the core.

    To achieve close tolerance on impedance variation Close dimensional tolerances in windings Proper stabilization of windings before assembly Better insulating material Good winding machines

    Influence of Impedance variation

  • 7/31/2019 1.Converter Transformer

    16/33

    Large voltage control requirements at converter & inverter ends.

    Tapping range is large (25 ~ 30%) with small steps to give

    necessary adjustments in supply voltage.

    High frequency of operation Mechanical aspects of OLTC

    should be reviewed to ensure a robust design (Contacts wear,

    linkages, motor, relays, contactors, interlocks). Derating

    necessary compared to normal transformer applications.

    Small step voltage permit small variation in DC voltage, valve

    firing angles and reactive power demand

    On Load Tap Changer.

  • 7/31/2019 1.Converter Transformer

    17/33

    There is need to compensate for the reactive voltage drop inthe conversion between AC & DC by changing taps.

    In OLTC, switchover from one tap to another is carried out by

    the diverter switch.

    When changing over from one tap to next, the current in the leavingtap has to be broken during the normal current zero passage.

    In star-star connected windings, the current is zero for a long timeand the change over is smooth.

    But in star-delta connected windings, the current change frompositive to negative is abrupt with very little time at zero current.

    This puts strain on diverter switch.

    On Load Tap Changer

  • 7/31/2019 1.Converter Transformer

    18/33

  • 7/31/2019 1.Converter Transformer

    19/33

    Additional losses due to harmonic currents in valve windings

    Stray flux from harmonic currents can heat up structuralmembers like Yoke Clamps, Tank

    Yoke shunts are used to contain and direct the above leakageflux to core

    Harmonic stray flux can induce larger currents than powerfrequency stray flux

    Higher Harmonic Currents.

  • 7/31/2019 1.Converter Transformer

    20/33

  • 7/31/2019 1.Converter Transformer

    21/33

    No-Load losses Depends on applied AC voltage, same as normal transformer

    Load Losses I2R + Stray loss from circulating currents in windings & metallic parts

    from leakage flux

    Circulating current depend on rate of change in winding current and thus leakage

    flux. With stepwise change in load current during commutation from one valve to

    another, the induced voltages will be fairly high to create circulating currents. So

    stray losses are increased compared to conventional power transformers.

    Stray losses in windings Increase as square of harmonic number

    At 150 Hz, Stray losses (150/50)2

    more than at 50 Hz current Stray losses in metal- varies as 0.8 of harmonic number

    High percentage of harmonic currents in the load current causes higher load losses

    compared to normal transformers

    Losses.

  • 7/31/2019 1.Converter Transformer

    22/33

    Due to inaccuracies in valve firing.

    Results in a small residual DC current oscillating around zero.

    DC components in magnetizing current lead to core saturation, which

    results in -

    high levels of vibration

    increased sound level in transformers

    marginal increase in no-load loss.

    DC Magnetization.

  • 7/31/2019 1.Converter Transformer

    23/33

    A short circuit across a valve or phase to ground on a valve side terminal

    can result in a completely asymmetrical current for a few cycles.

    Resulting forces on the winding can be larger than for the normal power

    transformers where the asymmetry decays rapidly.

    Short Circuit Forces.

  • 7/31/2019 1.Converter Transformer

    24/33

    Mechanical forces during a shortcircuit may reach critical values

    An inner winding buckles underradial forces

  • 7/31/2019 1.Converter Transformer

    25/33

    Excessive axial force inwinding will cause tiltingof conductor

  • 7/31/2019 1.Converter Transformer

    26/33

    DC withstand voltage of contaminated insulator is 20 ~ 30% of that of AC.

    To meet this, bushings creepage used are 40 mm/kV or more (Normal

    bushings are with 25mm / kV of service maximum voltage)

    To avoid chances of phase to ground short circuits, valve side bushings are

    located inside the valve hall. This also reduces the pollution related

    flashovers and consequent short circuit.

    IEC & IEEE standards for the DC bushings.

    DC Bushing.

  • 7/31/2019 1.Converter Transformer

    27/33

    Converter Transformer

    DesignInterface: DC bushings (Basslink)

  • 7/31/2019 1.Converter Transformer

    28/33

    Converter Transformer

    Few Formula..

    ddIL

    3cos35.1U = U

    )IL3

    cos35.1(Udd

    = U

    Rectifier mode

    Inverter mode

    Overlap

    U

    IL2cos)cos( d

    =+

    =++

  • 7/31/2019 1.Converter Transformer

    29/33

    Converter Transformer

    Testsrequired acc. to IEC 60076-1, ~-3, IEC61378-2

    routinetests

    meas of DC wind. res. IEC 60076-1, 10.2meas. of voltage ratio and check of phasedisplacement

    IEC 60076-1, 10.3

    meas. of s/c imp. and load loss IEC 60076-1, 10.4meas. of no load loss and current at fr and Ur IEC 60076-1, 10.5

    dielectric routine tests (forUm>300kV)

    IEC 60076-3

    LI (for line & neutral, principal and extr.taps)

    neg. Ut IEC 60076-3, cl.13 & 14

    SI IEC 60076-3, cl.15ACLD (AC long duration), sine wave>>fr,100%Utrms(60s)

    IEC 60076-3, cl.12.4

    seperate source AC (applied potentialtest)

    IEC 60076-3, cl.11

    seperate source DC volt. withstand inclPD meas.

    IEC 601378-2, cl.10

    polarity reversal test IEC 601378-2, cl.10

    (aux.wiring IEC60076-3, cl.10: 2kV rms)tests on on-load tap- changer (where appropriate) IEC 60076-1, 10.8meas. insulation resistance IEC 601378-2, cl.10test of magn. circuit insulation and associated ins. IEC 601378-2, cl.10

  • 7/31/2019 1.Converter Transformer

    30/33

    Converter Transformer

    Teststypetests

    temp.risetest

    IEC 60076-2, also 5.2.3

    dielectric type tests n.a., all tests are routinetests

    IEC 60076-3

    soundpower level

    IEC 60076-10

    sound power level of coolingequipment

    IEC 60076-10

    special

    testsdielectric special tests (for Um>300kV) (to be agreedabout)

    see routine tests IEC 60076-3

    ACSD (AC short duration), 1ph transformer: ph- gr only,100%Utest for 60s

    1-ph.:U2=1.5*Um/Wurzel(3)

    IEC 60076-3, cl.12.2 &12.3

    det.of cap. windings-to-earth and between windingsdet. of transient volt. transfercharacteristicsmeas. of zero-seq. imp. on 3-ph.transformers

    IEC 60076-1, 10.7

    s/c withstand test (test or calc.) calc.: 4.1.2...4.1.5 IEC 60076-5det. of sound levels IEC 60551meas. of harmonics of the no

    load current

    IEC 60076-1, 10.6

    meas of power taken by fan andoil pump motorsmeas. of ins. res. to earth ofwindingsmeas of tan(delta) of the ins. sys.capacitanceslosses and imp.(other taps) IEC 60076-1, 10.4+10.5,

    IEC 61378-1load currenttest

    IEC 601378-2, cl.10

  • 7/31/2019 1.Converter Transformer

    31/33

    Standards:

    1) IEC 61378-1 (1.0) 1997-09 Converter Transformers Part I Transformers for Industrial Applications

    2) IEC 61378-2 (1.0) 2001-02 Converter Transformers Part 2 Transformers for HVDC Applications.

    3) IEC 61378-3 (under issue) Converter Transformers Part 3 Application Guide for Converter Transformers

    4) IEC 62199: 2004-05 Bushings for DC Application

    5) IEEE Std. C57.129-1999 General Requirements andTest code for Oil Immersed HVDC Converter Transformers.

  • 7/31/2019 1.Converter Transformer

    32/33

    Standards:

    6) IEEE Std. 1158-1991 (R 1996) Recommended Practice forDetermination of Power losses in HVDC converter stations.

    7) IEEE Std. C57.19.03 - 1996 Standard Requirements,Terminology and Test Code for Bushings for DC applications.

  • 7/31/2019 1.Converter Transformer

    33/33

    THANK YOU