1mrb520308-ben en numerical station protection system reb500-reb500sys

Upload: vsrikala68

Post on 02-Jun-2018

224 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    1/50

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    2/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    ABB Switzerland LtdPower Technology Systems

    REB500 / REB500sys1MRB520308-Ben

    Page 2

    Main featuresREB500 / REB500sys(contd)

    Options Breaker failure protection (also separately

    operable without busbar protection)

    End fault protection Definite time overcurrent protection

    Breaker pole discrepancy

    Overcurrent and voltage check feature

    Disturbance recording for power systemvoltages

    Separate I0measurement for impedance-

    grounded networks

    Communication with substation monitoring

    and control system (IEC 61850-8-1 /IEC 60870-5-103 / LON)

    Internal user-friendly human machine inter-face with display

    Redundant power supply for central unitsand/or bay units.

    Addi tional

    main features

    REB500sys

    REB500sys combines the well-proven numer-ical busbar and breaker failure protectionREB500 of ABB with Main 2 or back-up pro-tection for line or transformer feeders. TheMain 2 / Group 1 or back-up protection is

    based on the well-proven protection functionlibrary of REL316*4 / RET316*4 from ABB for50 and 60 Hz.

    Main 2 / back-up bay protection Definite- and inverse time over and under-

    current protection

    Directional overcurrent definite- andinverse time protection

    Inverse time earth fault overcurrent protec-tion

    Definite time over and undervoltage protec-tion

    Three-phase current and three-phase volt-age plausibility

    Main 2 / back-up bay protection: Line pro-tection High-speed distance protection

    Directional sensitive earth fault protectionfor grounded systems against high resis-tive faults in solidly grounded networks

    Directional sensitive earth fault protectionfor ungrounded or compensated systems

    Autoreclosure for

    - single-pole / three-pole reclosure

    - up to four reclosure sequences

    Synchrocheck with

    - measurement of amplitudes, phaseangles and frequency of two voltagevectors

    - checks for dead line, dead bus, deadline and bus

    Group 1 / back-up bay protection: Trans-former protection

    High-speed transformer differential protec-tion for 2- and 3-winding and auto-trans-formers

    Thermal overload

    Peak value over and undercurrent protec-tion

    Independent T-Zone protection with trans-former differential protection

    Appl ication

    REB500

    The numerical busbar protection REB500 isdesigned for the high-speed, selective protec-tion of MV, HV and EHV busbar installationsat a nominal frequency of 50, 60 and 16.7 Hz.

    The structure of both hardware and softwareis modular enabling the protection to be eas-ily configured to suit the layout of the pri-mary system.

    The flexibility of the system enables all con-figurations of busbars from single busbars toquadruple busbars with transfer buses, ring

    busbars and 1 breaker schemes to be pro-tected.

    In 1 breaker schemes the busbars and theentire diameters, including Stub/T-Zone can

    be protected. An integrated tripping schemeallows to save external logics as well as wir-ing.

    The capacity is sufficient for up to 60 feeders(bay units) and a total of 32 busbar zones.

    The numerical busbar protection REB500detects all phase and earth faults in solidlygrounded and resistive-grounded power sys-tems and phase faults in ungrounded systemsand systems with Petersen coils.

    The main CTs supplying the currents to thebusbar protection have to fulfil only modestperformance requirements (see page16).Theprotection operates discriminatively for allfaults inside the zone of protection and

    remains reliably stable for all faults outsidethe zone of protection.

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    3/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 3

    ABB Switzerland LtdPower Technology Systems

    Appl icat ionREB500sys

    The REB500sys is foreseen in MV, HV andEHV substations with nominal frequencies of50 Hz resp. 60 Hz to protect the busbars and

    their feeders. The bay protection functionsincluded in REB500sys are used as Main 2 /Group 1 - or back-up protection.

    The system REB500sys is foreseen for allsingle or double busbar configurations (Linevariants L-V1 to L-V5 and Transformer vari-ant T-V1). In 1 breaker configurations, vari-ant L-V5 can be used for the bay levelfunctions autoreclosure and synchrocheck.The capacity is sufficient for up to 60 feeders(bay units) and a total of 32 busbar zones.

    The REB500sys detects all bus faults in sol-idly and low resistive-grounded power sys-tems, all kind of phase faults in ungroundedand compensated power systems as well asfeeder faults in solidly, low resistive-grounded, compensated and ungrounded

    power systems.

    The protection operates selectively for allfaults inside the zone of protection andremains reliably stable for all faults outsidethe zone of protection.

    REB500sys is perfectly suited for retrofitconcepts and stepwise upgrades. The bay unitis used as a stand-alone unit for bay protec-

    tion functions (e.g. line protection, autoreclo-sure and synchrocheck or 2- and 3 windingtransformer protection or autonomous T-zone

    protection). The central unit can be added at alater stage for full busbar and breaker failure

    protection functionality.

    Depending on the network voltage level andthe protection philosophy the following pro-tection concepts are generally applied:

    Two main protection schemes per bayand one busbar protection.With REB500sys the protection concept

    can be simplified. Due to the higher inte-gration of functionality one of the mainprotection equipment can be eliminated.

    One main protection and one back-upprotection scheme per bay, no busbarprotection.With REB500sys a higher availability ofthe energy delivery can be reached, due tothe implementation of busbar and breakerfailure protection schemes where it hasn't

    been possible in the past because of eco-nomical reasons.

    Six standard options are defined for Main 2 /Group 1 or back-up bay level functions:

    Line protection- Line variant 1 (L-V1)

    directional, non-directional overcurrentprotection and directional earth fault prot.

    - Line variant 2 (L-V2)as Line variant L-V1 plus distance prot.

    - Line variant 3 (L-V3)as Line variant L-V2 plus autoreclosure

    - Line variant 4 (L-V4)

    as Line variant L-V3 plus synchrocheck- Line variant 5 (L-V5)

    as Line variant L-V1 plus autoreclosure andsynchrocheck.

    Transformer ProtectionTransformer Variant 1 (T-V1) as 2- or 3 wind-ing transformer differential protection, ther-mal overload, current functions; applicablealso as autonomous T-Zone protection.

    Fig. 1

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    4/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    ABB Switzerland LtdPower Technology Systems

    REB500 / REB500sys1MRB520308-Ben

    Page 4

    Table 1 Overview of the func tionalities REB500 / REB500sys

    Main functionality IEEE

    Protectionfunction

    IEC61850

    Standard

    Option

    Special*onRequest

    LineVariant1

    (L-V1)

    LineVariant2

    (L-V2)

    LineVariant3

    (L-V3)

    LineVariant4

    (L-V4)

    LineVariant5

    (L-V5)

    TransformerVariant1

    (T-V1)

    BayUnitHardware

    Busbar protection 87B BBP PDIF Measurement of neutral current / detection I0 87BN I0 PDIF Breaker failure protection 50BF BFP RBRF End-fault protection 51/62EF EFP PTOC Breaker pole discrepancy 51/62PD PDF PTOC Overcurrent check feature 51 PTOC

    Voltage check feature 59/27 PTOV/PTUV Check zone 87CZ BBP CZ PDIF Overcurrent protection (def. time) 51 OCDT PTOC Trip command re-direction 94RD - Software Matrix for Inputs / Outputs / Trip matrix - - Event recording up to 1000 events - ER - Disturbance recorder (4 x I) 95DR DR RDRE Disturbance recorder (4 x I, 5 x U) up to 10 sec. at 2400 Hz 95DR DR RDRE Communication interface IEC61850-8-1/ LON / IEC60870-5-103 - Com - Time synchronization - - Redundant power supply for central- and/or bay units - - Isolator supervision - - Differential current supervision - - Comprehensive self-supervision - - Dynamic Busbar replica with display of currents - - Testgenerator for commissioning & maintenance - - Remote-HMI - -

    Delay / Integrator function - -

    Binary logic and Flip-Flop functions - - Definite time over and undercurrent protection 51 OCDT PTOC Inverse time overcurrent protection 51 OCINV PTOC Definite time over and undervoltage protection 59/27 OVDT PTOV/PTUV Inverse time earth fault overcurrent protection 51N I0INV PTOC Directional overcurrent definite time protection 67 DIROCDT PTOC Directional overcurrent inverse time protection 67 DIROCINV PTOC Three phase current plausibility 46 CHKI3PH PTOC Three phase voltage plausibility 47 CHKU3PH PTUV Test Sequenzer - - Direct. sensitive EF prot. for grounded systems 67N DIREFGND PDEF Direct. sensit ive EF prot. for ungrounded or compensated systems 32N DIREFISOL PSDE Distance protection 21 DIST PDIS Autoreclosure 79 AR RREC Synchrocheck 25 SYNC RSYN Transformer differential protection 2 winding 87T DIFTRA PDIF Transformer differential protection 3 winding 87T DIFTRA PDIF

    Thermal overload 49 TH PTTR Peak value over and undercurrent protection 50 OCINST PIOC

    * only for special applications500BU03: bay unit

    500BU03for50Hz,

    60Hz

    500BU03for50Hz,

    60Hz,

    16.7

    Hz

    Functionality

    REB

    500/REB500sys

    REB500

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    5/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 5

    ABB Switzerland LtdPower Technology Systems

    Mode ofinstallationREB500 /

    REB500sys

    There are three versions of installing the numerical busbar protection REB500 and the numeri-cal station protection REB500sys:

    Distributed installationIn this case, the bay units (see Fig. 21) areinstalled in casings or cubicles in the indivi-dual switchgear bays distributed around the

    station and are connected to the central pro-cessing unit by optical fibre cables. The cen-tral processing unit is normally in a centrallylocated cubicle or in the central relay room.

    Fig. 2 Distributed installation

    Centralized installation19"mounting plates with up to three bayunits each, and the central processing unit aremounted according to the size of the busbar

    system in one or more cubicles (see Fig. 20).A centralized installation is the ideal solution

    for upgrading existing stations, since verylittle additional wiring is required and com-

    pared with older kinds of busbar protection,much more functionality can be packed into

    the same space.

    Fig. 3 Centralized installation

    Combined centralized and distributedinstallation

    Basically, the only difference between a dis-tributed and a centralized scheme is themounting location of the bay units and there-fore it is possible to mix the two philosophies.

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    6/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    ABB Switzerland LtdPower Technology Systems

    REB500 / REB500sys1MRB520308-Ben

    Page 6

    System designREB500 /REB500sys

    Bay unit (500BU03)The bay unit (see Fig. 4) is the interface

    between the protection and the primary sys-

    tem process comprising the main CTs, isola-tors and circuit-breaker and performs theassociated data acquisition, pre-processing,control functions and bay level protectionfunctions. It also provides the electrical insu-lation between the primary system and theinternal electronics of the protection.

    The input transformer module contains fourinput CTs for measuring phase and neutralcurrents with terminals for 1 A and 5 A.Additional interposing CTs are not required,

    because any differences between the CTratios are compensated by appropriately con-

    figuring the software of the respective bayunits.

    Optional input transformer module also con-tains five input voltage transformers for themeasurement of the three-phase voltages andtwo busbar voltages and recording of voltagedisturbances or 6 current transformers fortransformer differential protection. (seeFig. 12).

    In the analogue input and processing module,the analogue current and voltage signals areconverted to numerical signals at a samplingrate of 48 samples per period and then numer-ically preprocessed and filtered accordingly.Zero-sequence voltage and zero-current sig-nals are also calculated internally. The Pro-

    cess data are transferred at regular intervalsfrom the bay units to the central processingunit via the process bus.

    Every bay unit has 20 binary inputs and 16relay outputs. The binary I/O module detectsand processes the positions of isolators andcouplers, blocking signals, starting signals,external resetting signals, etc. The binaryinput channels operate according to a pat-ented pulse modulation principle in a nominalrange of 48 to 250 V DC. The PC-based HMI

    program provides settings for the thresholdvoltage of the binary inputs. All the binaryoutput channels are equipped with fast oper-ating relays and can be used for either signal-ing or tripping purposes (see contact data in

    Table 8).A software logic enables the input and outputchannels to be assigned to the various func-tions. A time stamp is attached to all the datasuch as currents, voltages, binary inputs,events and diagnostic information acquired

    by a bay unit.

    Where more binary and analogue inputs areneeded, several bay units can be combined toform a feeder/bus coupler bay (e.g. a bus cou-

    pler bay with CTs on both sides of the bus-tiebreaker requires two bay units).

    The bay unit is provided with local intelli-gence and performs local protection (e.g.

    breaker failure, end fault, breaker pole dis-crepancy), bay protection (Main 2 or back-up

    bay protections) as well as the event and dis-turbance recording.

    Fig. 4 Block diagram of a bay unit and a central unit

    CIM

    DC

    CPUModule

    CPUModule

    CPU

    Module

    SAS/SMSInterface

    RS 232Interface

    Real-timeClock

    Star-coupler

    BinaryI/O

    Starcoupler

    Local HMI

    Electrical

    insulation

    Process-bus

    Filter

    Binary in/outputregisters

    A/D

    Filter

    CPU

    Optical

    Interface

    DC

    DC

    DSPDP

    Mem

    Central Unit (500CU03)Bay Uni t (500BU03)

    Local HMI

    DC

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    7/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 7

    ABB Switzerland LtdPower Technology Systems

    In the event that the central unit is out ofoperation or the optical fibre communicationis disrupted an alarm is generated, the bay

    unit will continue to operate, and all local andbay protection as well as the recorders (eventand disturbance) will remain fully functional(stand-alone operation).

    The hardware structure is based on a closed,monolithic casing and presented in twomounting solutions:

    Without local HMI: ideal solution if con-venient access to all information via thecentral unit or by an existing substationautomation system is sufficient.

    With local HMI and 20 programmable

    LEDs (Fig. 5): ideal solution for decentraland kiosk mounting (AIS), since all infor-mation is available in the bay.

    For the latter option it is possible to have theHMI either built in or connected via a flexiblecable to a fixed mounting position (seeFig. 25).

    In the event of a failure, a bay unit can be eas-ily replaced. The replacement of a bay unitcan be handled in a simple way. During sys-tem start-up the new bay unit requests itsaddress, this can be entered directly via its

    local HMI. The necessary setting values andconfiguration data are then downloaded auto-matically.

    Addi tional p lug-and-play functionali tyBay units can be added to an existingREB500 system in a simple way.

    Fig. 5 Built-in HMI directly on the bay unit500BU03.

    Central unit (500CU03)The hardware structure is based on standardracks and only a few different module typesfor the central unit (seeFig. 4).

    The modules actually installed in a particularprotection scheme depend on the size, com-plexity and functionality of the busbar sys-tem.

    A parallel bus on a front-plate motherboardestablishes the interconnections between themodules in a rack. The modules are insertedfrom the rear.

    The central unit is the system manager, i.e. itconfigures the system, contains the busbarreplica, assigns bays within the system, man-

    ages the sets of operating parameters, acts asprocess bus controller, assures synchroniza-tion of the system and controls communica-tion with the station control system.

    The variables for the busbar protection func-tion are derived dynamically from the processdata provided by the bay units.

    The process data are transferred to the centralprocessor via a star coupler module. Up to 10bay units can be connected to the first centralprocessor and 10 to the others. Central pro-cessors and star coupler modules are added

    for protection systems that include more than10 bay units. In the case of more than 30 bayunits, additional casings are required foraccommodating the additional central proces-sors and star coupler modules required.

    All modules of the central unit have a plug-and-play functionality in order to minimizemodule configuration.

    One or two binary I/O modules can be con-nected to a central processing unit.

    The central unit comprises a local HMI with

    20 programmable LEDs (Fig. 6), a TCP/IPport for very fast HMI500-REBWIN connec-tion within the local area network.

    Fig. 6 Central unit

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    8/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    ABB Switzerland LtdPower Technology Systems

    REB500 / REB500sys1MRB520308-Ben

    Page 8

    Functionality ofREB500 /REB500sys

    Busbar protectionThe protection algorithms are based on twowell-proven measuring principles which have

    been applied successfully in earlier ABB low-impedance busbar protection systems:

    a stabilized differential current measure-ment

    the determination of the phase relationshipbetween the feeder currents (phase com-parison).

    The algorithms process complex current vec-tors which are obtained by Fourier analysisand only contain the fundamental frequencycomponent. Any DC component and harmon-ics are suppressed.

    The first measuring principle uses a stabilizeddifferential current algorithm.The currents are evaluated individually foreach of the phases and each section of busbar(protection zone).

    Fig. 7 Tripping characteristic of the stabilizeddifferential current algorithm.

    In Fig. 7, the differential current is

    and the restraint current

    where Nis the number of feeders. The fol-lowing two conditions have to be accom-

    plished for the detection of an internal fault:

    wherekst stabilizing factor

    kst max stabilization factor limit.

    A typical value is kst max= 0.80

    IK min differential current pick-up value

    The above calculations and evaluations areperformed by the central unit.

    The second measuring principle determinesthe direction of energy flow and involvescomparing the phases of the currents of allthe feeders connected to a busbar section.

    The fundamental frequency current phasors1..n (5) are compared. In the case of an in-ternal fault, all of the feeder currents have al-most the same phase angle, while in normal

    operation or during an external fault at leastone current is approximately 180 out of

    phase with the others.

    The algorithm detects an internal fault whenthe difference between the phase angles of allthe feeder currents lies within the trippingangle of the phase comparator (see Fig. 8).

    ( | | )

    0Restraint current

    ( | | ) 0

    IKmin

    k = 1

    Ksetting =kstmaxTr

    ipping

    area

    Differentialcurrent

    Restraintarea

    =

    = N

    n

    LnI1

    DiffI (1)

    =

    =N

    n

    LnI

    1

    RestI(2)

    max

    Rest

    DiffIstst k

    Ik >= (3)

    minKDiff II > (4)

    ( )( )

    =

    LnIRe

    LnIIm

    arctann

    (5)

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    9/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 9

    ABB Switzerland LtdPower Technology Systems

    Fig. 8 Characteristic of the phase comparator for

    determining energy direction.

    The task of processing the algorithms isshared between the bay units and the central

    processing unit. Each of the bay units contin-uously monitors the currents of its own fee-der, preprocesses them accordingly and thenfilters the resulting data according to a Fou-rier function. The analogue data filtered inthis way are then transferred at regular inter-vals to the central processing unit running the

    busbar protection algorithms.

    Depending on the phase-angle of the fault,the tripping time varies at Idiff/Ikmin5 bet-ween 20 and 30 ms including the auxiliarytripping relay.

    Optionally, the tripping signal can be inter-locked by a current or voltage check featurein the bay unit that enables tripping onlywhen a current above a certain minimum isflowing, respectively the voltage is below acertain value.

    Breaker failure protectionThe breaker failure functions in the bay units

    monitor the phase currents independently ofthe busbar protection. They have two timerswith individual settings.

    Operation of the breaker failure function isenabled either:

    internally by the busbar protection algo-rithm (and, if configured, also by the inter-nal line protection, overcurrent or polediscrepancy protection features) of the baylevel

    externally via a binary input, e.g. by theline protection, transformer protection etc.

    After the delay of the first timer has expired,a tripping command can be applied to a sec-ond tripping coil on the circuit-breaker and a

    remote tripping signal transmitted to the sta-tion at the opposite end of the line.

    This first timer operates in a stand-alonemode in the bay unit.

    If the fault still persists at the end of the sec-ond time delay, the breaker failure functionuses the busbar replica to trip all the otherfeeders supplying the same section of busbarvia their bay units.

    A remote tripping signal can be configured inthe software to be transmitted after the first or

    second timer.

    Phase-segregated measurements in each bayunit cope with evolving faults.

    End fault protection

    In order to protect the dead zone betweenan open circuit-breaker and the associatedCTs, a signal derived from the breaker posi-tion and the close command is applied.

    The end fault protection is enabled a certaintime after the circuit-breaker has been open-ed. In the event of a short circuit in the deadzone the nearest circuit-breakers are tripped.

    This function is performed in a stand-alonemode in the bay unit.

    Overcurrent funct ionA definite time overcurrent back-up protec-tion scheme can be integrated in each bayunit. (The operation of the function, if para-meterized, may start the local breaker failure

    protection scheme).

    This function is performed in a stand-alone

    mode in the bay unit.

    Overcurrent check feature

    The overcurrent check feature is only per-formed in the bay unit. It is effective for a

    busbar protection trip and for an intertrippingsignal (including end fault and breaker fail-ure) and prevents those feeders from beingtripped that are conducting currents lowerthan the setting of the overcurrent check fea-ture.

    Voltage check featureThe voltage criterion is measured in the bay

    unit. The function can be configured asrelease criterion per zone through internal

    Phase-shift

    74

    0 12

    = 36

    12

    = 144

    Restraint area

    Case 1 2

    max = 74

    Tripping area

    Busbar

    Operating characteristic

    Re

    Im

    I1

    I2

    Im

    ReI1

    I2

    180

    Case 1: External fault = 144

    Case 2: Internal fault = 36

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    10/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 10

    Functionality ofREB500 / REB500sys(contd)

    Functionality ofREB500 / REB500sys(contd)

    ABB Switzerland LtdPower Technology Systems

    linking in the central unit. This necessitatesthe existence of one set of voltage transform-ers per zone in one of the bay units. Tripping

    is only possible if the voltage falls short of(U) the set value.

    Additionally this release criterion can be con-figured for each feeder (voltage transformersmust be installed). For details see Table 22.

    Check zone CriterionThe check zone algorithm can be used as arelease criterion for the zone-discriminatinglow-impedance busbar protection system. Itis based on a stabilized differential currentmeasurement, which only acquires the feedercurrents of the complete busbar. The isolator /

    breaker positions are not relevant for this cri-terion.

    Neutral current detection I0Earth fault currents in impedance-groundedsystems may be too low for the stabilized dif-ferential current and phase comparison func-tions to detect. A function for detecting theneutral current is therefore also available, butonly for single phase-to-earth faults.

    Pole discrepancyA pole discrepancy protection algorithmsupervises that all three poles of a circuit-

    breakers open within a given time.

    This function monitors the discrepancy bet-ween the three-phase currents of the circuit-

    breaker.

    When it picks up, the function does not sendan intertripping signal to the central unit, but,if configured, it starts the local breaker failure

    protection (BFP logic 3).

    This function is also performed in a stand-alone mode in the bay unit.

    Event recordingThe events are recorded in each bay unit. Atime stamp with a resolution of 1ms is attach-ed to every binary event. Events are dividedinto the three following groups:

    system events

    protection events

    test events.

    The events are stored locally in the bay unitor in the central unit.

    Disturbance recordingThis function registers the currents and the

    binary inputs and outputs in each bay. Volt-ages can also be optionally registered (seeTable 14).

    A disturbance record can be triggered byeither the leading or lagging edges of all

    binary signals or by events generated by theinternal protection algorithms. Up to 10 gen-eral-purpose binary inputs may be configuredto enable external signals to trigger a distur-

    bance record. In addition, there is a binaryinput in the central and the bay unit for start-ing the disturbance recorders of all bay units.

    The number of analogue channels that can be

    recorded, the sampling rate and the recordingperiod are given in Table 14. A lower sam-pling rate enables a longer period to berecorded.

    The total recording period can be divided intoa maximum of 15 recording intervals per bayunit.

    Each bay unit can record a maximum of 32binary signals, 12 of which can be configuredas trigger signals.

    The function can be configured to record thepre-disturbance and post-disturbance states ofthe signals.

    The user can also determine whether the re-corded data is retained or overwritten by thenext disturbance (FIFO = First In, First Out).

    This function is performed in a stand-alonemode in the bay unit (see page6).

    Note:

    Stored disturbance data can be transferred viathe central unit to other computer systems for

    evaluation by programs such as PSM505(E_wineve)[4].Files are transferred in theCOMTRADE format.

    After retrieving the disturbance recorder data,it is possible to display them graphically withPSM505 (E_wineve) directly.

    Communication interface

    Where the busbar protection has to communi-cate with a station control or station monitor-ing system (SAS/SMS), a communicationmodule is added to the central unit. The mod-ule supports the interbay bus protocols IEC61850-8-1, IEC 60870-5-103 and LON.

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    11/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 11

    ABB Switzerland LtdPower Technology Systems

    The IEC 61850-8-1 interbay bus transfers viaeither optical or electrical connection:

    differential current of each protection zone

    monitoring information from REB500central unit and bay units

    binary events (signals, trips and diagnos-tic)

    trip reset command

    disturbance recording data (via MMS filetransfer protocol)

    time synchronization with Simple Net-work Time Protocol (SNTP)

    two independent time servers are sup-ported. Server 2 as backup time.

    The LON interbay bus transfers via opticalconnection:

    differential currents of each protectionzone

    binary events (signals, trips and diagnos-tic)

    trip reset command

    disturbance recording data (via HMI500-REBWIN)

    time synchronization.

    The IEC 60870-5-103 interbay bus transfersvia either optical or electrical connection:

    time synchronization

    selected events listed in the public part

    all binary events assigned to a private part

    all binary events in the generic part

    trip reset command

    Test generatorThe HMI program (HMI500-REBWIN)

    which runs on a PC connected to either a bayunit or the central processing unit includes atest generator.

    During commissioning and system mainte-nance, the test generator function enables theuser to:

    activate binary input and output signals

    monitor system response.

    test the trip circuit up to and including thecircuit-breaker

    test the reclosure cycles

    establish and perform test sequences withvirtual currents and voltages for the bay

    protection of the REB500sys.

    The test sequencer enables easy testing of thebay protection without the need to decommis-sion the busbar protection. Up to seven se-quences per test stage can be started. Thesequences can be saved and reactivated forfuture tests.

    Isolator supervision

    The isolator replica is a software feature with-out any mechanical switching elements. Thesoftware replica logic determines dynami-cally the boundaries of the protected busbarzones (protection zones). The system moni-tors any inconsistencies of the binary inputcircuits connected to the isolator auxiliarycontacts and generates an alarm after a settime delay.

    In the event of an isolator alarm, it is possibleto select the behavior of the busbar protec-tion:

    blocked

    zone-selective blocked

    remain in operation.

    Table 2

    N/O

    contact:

    Isolator

    CLOSED

    N/C

    contact:

    Isolator

    OPEN

    Isolator position

    open open Last position stored+ delayed isolator alarm,

    + switching prohibitedsignal

    open closed OPEN

    closed open CLOSED

    closed closed CLOSED+ delayed isolator alarm,+ switching prohibited

    signal

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    12/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    ABB Switzerland LtdPower Technology Systems

    REB500 / REB500sys1MRB520308-Ben

    Page 12

    Functionality ofREB500 / REB500sys(contd)

    Differential current supervisionThe differential current is permanently super-vised. Any differential current triggers a

    time-delayed alarm. In the event of a differ-ential current alarm, it is possible to select thebehavior of the busbar protection:

    blocked

    zone-selective blocked

    remain in operation.

    Trip redirection

    A binary input channel can be provided towhich the external signal monitoring the cir-cuit-breaker air pressure is connected. Trip-

    ping is not possible without active signal.When it is inactive, a trip generated by therespective bay unit is automatically redirectedto the station at the opposite end of the lineand also to the intertripping logic to trip allthe circuit-breakers connected to the samesection of busbar.

    The trip redirection can also be configuredwith a current criterion (overcurrent checkfeature).

    Human machine interface (HMI)The busbar protection is configured andmaintained with the aid of human machine

    interfaces at three levels.

    Local HMIThe local display interface installed in thecentral unit and in the bay units comprises:

    a four-line LCD with 16 characters eachfor displaying system data and error mes-sages

    keys for entering and display as well as 3LEDs for the display of trips, alarms andnormal operation.

    in addition 20 freely programmable LEDsfor user-specific displays on the bay unit

    500BU03 and central unit 500CU03.

    The following information can be displayed:

    measured input currents and voltages

    measured differential currents (for the bus-bar protection)

    system status, alarms

    switchgear and isolator positions (withinthe busbar protection function)

    starting and tripping signals of protectionfunctions.

    External HMI (HMI500-REBWIN)More comprehensive and convenient controlis provided by the external HMI software run-ning on a PC connected to an optical interfaceon the front of either the central processingunit or a bay unit. The optical interface iscompletely immune to electrical interfer-ence. The PC software facilitates configura-tion of the entire busbar protection, the set-ting of parameters and full functional check-ing and testing. The HMI500-REBWIN canalso be operated via the LON Bus onMicroSCADA for example, thus eliminatinga separate serial connection to the centralunit.

    The HMI runs under MS WINDOWS NT,WINDOWS 98, WINDOWS 2000 and WIN-

    DOWS XP. The HMI500-REBWIN isequipped with a comfortable on-line helpfunction. A data base comparison functionenables a detailed comparison between twoconfiguration files (e.g. between the PC andthe central unit or between two files on thePC).

    Remote HMI

    A second serial interface at the rear of thecentral unit provides facility for connecting aPC remotely via either an optical fibre, TCP/IP or modem link. The operation and functionof HMI500-REBWIN is the same whether the

    PC is connected locally or remotely.

    Addi tional

    functionalities

    REB500sys

    Bay level functionsThese functions are based on the well estab-lished and well-proven functions built in theABB line and protection REL316*4 /RET316*4. The bay level functions containall the relevant additional functions, whichare normally requested of a line and trans-former protection scheme. The line protection

    is described in the data sheet REL316*4 [1]and the transformer protection is described inthe data sheet RET316*4[5].

    The line protection functions (L-V1 - L-V5)are used as Main 2 or back-up for lines aswell as for transformer bays.

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    13/50

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    14/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    ABB Switzerland LtdPower Technology Systems

    REB500 / REB500sys1MRB520308-Ben

    Page 14

    Additional functional-ities REB500sys(contd)

    tion with an inverse time earth fault overcur-rent function. In both cases the neutral currentand voltage can be derived either externally

    or internally. This function works either with-the same communication channel as the dis-tance protection scheme or with anindependent channel.

    Directional sensitive earth fault protectionfor ungrounded or compensated systemsThe sensitive earth fault protection functionfor ungrounded systems and compensatedsystems with Petersen coils can be set foreither forwards or reverse measurement. Thecharacteristic angle is set to 90(U0 I0 sin ) in ungrounded systems and to0 or 180 (U0 I0 cos ) for systems with

    Petersen coils. The neutral current is alwaysused for measurement in the case of systemswith Petersen coils, but in ungrounded sys-tems its use is determined by the value of thecapacitive current and measurement is per-formed by a core-balance CT to achieve therequired sensitivity. To perform this functionthe BU03 with 3I, 1MT and 5U is required.

    Definite time over and undercurrent pro-tectionThis function is used as Main 2 or as back-upfunction respectively for lines, transformer or

    bus-tie bays. This function can be activated in

    the phase- and/or the neutral current circuit.

    Inverse time overcurrent protectionThe operating time of the inverse time over-current function reduces as the fault currentincreases and it can therefore achieve shorteroperating times for fault locations closer tothe source. Four different characteristicsaccording to British Standard 142 designatednormal inverse, very inverse, extremely

    inverse and long time inverse but with anextended setting range are provided. Thefunction can be configured for single phase

    measurement or a combined three-phase mea-surement with detection of the highest phasecurrent.

    Inverse time earth fault overcurrent protec-tionThe inverse time earth fault overcurrent func-tion monitors the neutral current of the sys-tem. Four different characteristics accordingto British Standard 142 designated normalinverse, very inverse, extremely inverse andlong time inverse but with an extended set-ting range are provided.

    Directional overcurrent definite / inversetime protectionThe Directional overcurrent definite timefunction is available either with inverse timeor definite time overcurrent characteristic.This function comprises a voltage memoryfor faults close to the relay location. Thefunction response after the memory time haselapsed can be selected (trip or block).

    Definite time over and undervoltage pro-tectionThis function works with a definite timedelay with either single or three-phase mea-

    surement.

    Three-phase current p lausibilityThis function is for checking the sum and the

    phase sequence of the three-phase currents.

    Three-phase voltage plausibilityThis function is used for checking the sumand the phase sequence of the three-phasevoltages.

    Addi tional

    features ofREB500 /

    REB500sys

    Self-supervision

    All the system functions are continuouslymonitored to ensure the maximum reliabilityand availability of the protection. In the eventof a failure, incorrect response or inconsis-tency, the corresponding action is taken toestablish a safe status, an alarm is given andan event is registered for subsequent diagnos-tic analysis.

    Important items of hardware (e.g. auxiliarysupplies, A/D converters and main and pro-gram memories) are subjected to various testswhen the system is switched on and also dur-ing operation. A watchdog continuously

    monitors the integrity of the software func-

    tions and the exchange of data via the processbus is also continuously supervised.

    The processing of tripping commands is oneof the most important functions from the reli-ability and dependability point of view.Accordingly, every output channel comprisestwo redundant commands, which have to beenabled at regular intervals by a watchdog. Ifthe watchdog condition is not satisfied, thechannels are blocked.

    Extension of the systemThe system functions are determined by soft-

    ware, configured using the software configu-ration tool.

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    15/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 15

    ABB Switzerland LtdPower Technology Systems

    The system can be completely engineered inadvance to correspond to the final state of thestation. The software modules for new bays

    or features can be activated using the HMIwhen the primary plant is installed or the fea-tures are needed.

    Additional system functions, e.g. breaker fail-ure, end fault protection or bay level

    back-up / Main 2 functions can be easily acti-vated at any time without extra hardware.

    Resetting the trip commands/-signalsThe following resetting modes can be selec-ted for each binary output (tripping or signaloutputs):

    Latches until manually reset

    Resets automatically after a delay.

    Inspection/maintenanceA binary input is provided that excludes a bayunit from evaluation by the protection sys-tem. It is used while performing maintenancerespectively inspection activities on the pri-mary equipment.

    Redundant power supplies (Option)Two power supply modules can be fitted in aredundant arrangement, e.g. to facilitatemaintenance of station batteries. This is anoption for the central unit as well as for the

    bay unit.

    Time synchronizationThe absolute time accuracy with respect to anexternal time reference depends on themethod of synchronization used:

    no external time synchronization:accuracy approx. 1 min. per month

    periodic time telegram with minute pulse(radio or satellite clock or station controlsystem): accuracy typically 10 ms

    periodic time telegram as above with sec-ond pulse: accuracy typically 1 ms.

    a direct connection of a GPS or DCF77 tothe central unit is possible: accuracy typi-cally 1 ms.

    The system time may also be synchronizedby a 1 minute pulse applied to a binary inputon the central unit.

    Requirements Optical fibre cablesA distributed busbar protection layout re-

    quires optical fibre cables and connectorswith the following characteristics:

    2 optical fibre cores per bay unit

    glass fibres with gradient index

    diameter of core and sheath 62.5,respectively 125 m

    maximum permissible attenuation 5 dB

    FST connector (for 62.5 m optical fibres)

    rodent protected and longitudinally water-proof if in cable ducts

    Please observe the permissible bending radiuswhen laying the cables.

    The following attenuation figures are typicalvalues which may be used to determine anapproximate attenuation balance for each

    bay:

    Fig. 9 Attenuation

    Isolator auxiliary contact

    Auxiliary contacts on the isolators are con-nected to binary inputs on the bay units and

    control the status of the busbar replica in the

    numerical busbar protection.

    Optical equipmentTypical

    attenuation

    for gradient index (840 nm) 3.5 dB/km

    per connector 0.7 dB

    per cable joint 0.2 dB

    Central unit Bay unit1200 m1 m1 m

    FST connector

    5 dB

    FST connector

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    16/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 16

    Requirements (contd)Requirements (contd)

    ABB Switzerland LtdPower Technology Systems

    One potentially-free N/O and N/C contact arerequired on each isolator. The N/O contactsignals that the isolator is CLOSED and the

    N/C contact that the isolator is OPEN. Dur-ing the closing movement, the N/O contactmust close before the isolator main contactgap reaches its flashover point.

    Conversely, during the opening movement,the N/O contact must not open before the iso-lator main contact gap exceeds its flashover

    point.If this is not the case, i.e. the contact signalsno longer closed beforehand, then the N/Ccontact may not signal OPEN before theflashover point has been exceeded.

    Fig. 10 Switching sequence of the auxiliary contacts that control the busbar replica

    Circuit-breaker replicaWhen the circuit-breaker replica is read in thefeeder or the bus-tie breaker, the circuit-

    breaker CLOSE command must also be con-nected.

    Main current transformerThe algorithms and stabilization features usedmake the busbar protection largely insensitiveto CT saturation phenomena. Main CTs typesTPS (B.S. class x), TPX, TPY, 5P.. or 10P..are permissible.

    TPX, TPY and TPZ CTs may be mixed

    within one substation in phase-fault schemes.The relatively low CT performance neededfor the busbar protection makes it possible forit to share protection cores with other protec-tion devices.

    Current transformer requirements for sta-bility during external faults (Busbar protec-tion)The minimum CT requirements for 3-phasesystems are determined by the maximumfault current.

    The effective accuracy limit factor (n') must

    be checked to ensure the stability of the bus-bar protection during external faults.

    The rated accuracy limit factor is given by theCT manufacturer. Taking account of the bur-den and the CT losses, the effective accuracylimit factor n' becomes:

    where:

    n = rated accuracy limit factorPN = rated CT powerPE = CT lossesPB = burden at rated current

    In the case of schemes with phase-by-phasemeasurement, n' must satisfy the followingtwo relationships:

    where:

    IKmax = max. primary through-fault current

    I1N = rated primary CT current

    Taking the DC time constant of the feederinto account, the effective n' becomes:

    Close isolator

    Flashover gap

    must be closed

    must be open

    may be closed

    Isolator

    CLOSEDnormally-open

    OPENnormally-closed

    Closedend-position

    Openend-position

    Open isolator

    Auxiliary contacts :

    EB

    EN

    PP

    PPnn'

    ++

    =

    n1 IKmax5 I1N

    -------------------(1)

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    17/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 17

    ABB Switzerland LtdPower Technology Systems

    (2) n' 10for TN120 ms, orn' 20for 120 ms

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    18/50

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    19/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 19

    ABB Switzerland LtdPower Technology Systems

    Table 5 Mechanical tests

    Hardware modules

    Vibration and shock

    Resonance investigation 2 to 150 Hz / 0.5 gn EN 60255-21-1 (1996),

    IEC 60255-21-1 (1988), IEEE 344-1987

    Permanent strength 10 to 150 Hz / 1 gn EN 60255-21-1 (1996),IEC 60255-21-1 (1988)

    Seismic 2 to 33 Hz, 2 gn EN 60255-21-3 (1995),IEC 60255-21-3 (1995), IEEE 344-1987

    Shock test Cl.1; A = 15 gn; D = 11 ms;pulse/axis = 3 EN 60255-21-2 (1996), IEC 60255-21-2

    (1988), IEC 60068-2-27 (1987)

    Bump test Cl.1; A = 10 gn; D = 16 ms;pulse/axis = 1000 EN 60255-21-2 (1996), IEC 60255-21-2

    (1988), IEC 60068-2-29 (1987)

    Table 6 Enclosure protection classes

    Bay unit 19" central unit Cubicle (see Table 12)

    IP40 IP20 IP40-50

    Table 7 Analogue inpu ts (Bay unit )

    Currents

    4 /

    9 input channels

    I1, I2, I3, I4 /

    I1, I2, I3, I4, I5, I6, I7, I8, I9

    Rated current (IN) 1 A or 5 A by choice of terminals,adjustable CT ratio via HMI500-REBWIN

    Thermal ratings:continuous

    for 10 sfor 1 s

    1 half-cycle

    4 x IN

    30 xIN100 x IN

    250 x IN(50/60 Hz) (peak)

    EN 60255-6 (1994),IEC 60255-6 (1988),VDE 0435, part 303

    EN 60255-6 (1994),IEC 60255-6 (1988),VDE 0435, Part 303

    Burden per phase 0.02 VA at IN = 1 A0.10 VA at IN = 5 A

    Voltages (optional)

    5 input channels U1, U2, U3, U4, U5 500BU03

    Rated voltage (UN) 100 V, 50/60 Hz, 16.7 Hz200 V, 50/60 HzVT ratio adjustable via HMI500-REBWIN

    Thermal ratings:continuous

    for 10 s

    2 x UN

    3 x UN

    EN 60255-6 (1994),IEC 60255-6 (1988),VDE 0435, part 303

    Burden per phase 0.3 VA at UN

    Common data

    Rated frequency (fN) 50 Hz, 60 Hz 16.7 Hz

    adjustable via HMI500-REBWIN

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    20/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 20

    Technical data (contd)Technical data (contd)

    ABB Switzerland LtdPower Technology Systems

    Table 9 Auxil iary supply

    Table 8 Binary inputs/outputs (Bay uni t, Central unit )

    Binary outputs

    General

    Operating time 3 ms (typical)

    Max. operating voltage 300 V AC/DC

    Max. continuous rating 8 A

    Max. make and carry for 0.5 s 30 A

    Max. making power at 110 V DC 3300 W

    Binary output reset response, pro-grammable per output

    - latched- automatic reset (delay 0...60 s)

    Heavy-duty N/O contacts CR08...CR16, 500BU03

    Heavy-duty N/O contacts CR01...CR04, CR07...CR09 - 500CU03

    Breaking current for (L/R = 40 ms)1 contact

    2 contacts in series

    U

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    21/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 21

    ABB Switzerland LtdPower Technology Systems

    Table 10 Optical interfaces

    Table 12 Cubicle design

    Number of cores 2 fibre cores per bay unit

    Core/sheath diameter 62.5/125m (multi-mode)

    Max. permissible attenuation 5 dB (seeFig. 9)

    Max. length approx. 1200 m

    Connector Type FST for 62.5m optical fibre cables

    Table 11 Mechanical design

    Mounting

    Bay unit flush mounting on frames or in cubiclesHMI integrated or separately mounted

    Central unit flush mounting on frames or in cubicles

    Cubicle Standard type RESP97 (for details see 1MRB520159-Ken)

    Dimensions w x d x h 800 x 800 x 2200 mm (single cubicle)1600 x 800 x 2200 mm (double cubicle)2400 x 800 x 2200 mm (triple cubicle) *)

    *) largest shipping unit

    Total weight (with all units inserted) approx. 400-600 kg per cubicle

    Terminals Terminal type Connection data

    Solid Strand

    CTs Phoenix URTK/S 0.5 - 10 mm2 0.5 - 6 mm2

    VTs Phoenix URTK/S 0.5 - 10 mm2 0.5 - 6 mm2

    Power supply Phoenix UK 6 N 0.2 - 10 mm2 0.2 - 6 mm2

    Tripping Phoenix UK 10-TWIN 0.5 - 16 mm2 0.5 - 10 mm2

    Binary I/Os Phoenix UKD 4-MTK-P/P 0.2 - 4 mm2 0.2 - 2.5 mm2

    Internal wiring gauges

    CTs 2.5 mm2 stranded

    VTs 1.5 mm2 stranded

    Power supply 1.5 mm2 stranded

    Binary I/Os 1.5 mm2 stranded

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    22/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 22

    Technical data (contd)Technical data (contd)

    ABB Switzerland LtdPower Technology Systems

    Recording facilities

    Table 13 Event recorder

    Table 15 Interbay bus protocols

    Event recorder Bay unit Central unitSystem eventsProtection eventsTest events

    100 total 1000 total

    Table 14 Disturbance recorder

    Analog channel Recording periodSample rate selectable

    Options 4 currentsor9 currents

    4 currentsand5 voltages

    802 Hz (16.7 Hz)2400 Hz (50 Hz)2880 Hz (60 Hz)

    401 Hz (16.7 Hz)1200 Hz (50 Hz)1440 Hz (60 Hz)

    600 Hz (50 Hz)720 Hz (60 Hz)

    Standard X X*) 1.5 s 3 s 6 s

    Option 1 X X 6 s 12 s 24 s

    Option 2 X X 10 s 20 s 40 s

    Number of disturbance records = total recording time / set recording period (max.15)

    Independent settings for pre-fault and post-fault period (min. setting 200 ms).

    Format: COMTRADE 91 and COMTRADE 99

    *) in Standard, voltage channels are recorded, if existing

    IEC 61850-8-1 IBB protocol

    IEC 61850-8-1 interbay bus supports: - Time synchronization via SNTP: typical accuracy +/- 1ms- Two independent timeservers are supported. Server 2 as

    backup time- Optical or electrical connection- Differential current of each protection zone- Monitoring information from REB500 central unit and bay unit- Binary events (signals, trips and diagnostic)- Trip reset command- Single connection point to REB500 central unit- Disturbance recorder access via MMS file transfer protocol- Export of ICD - file, based on Substation Configuration

    Language SCL

    LON IBB protocol

    LON interbay bus supports - Time synchronization: typical accuracy 1 ms- Optical connection- Differential currents of each protection zone

    - Binary events (signals, trips and diagnostic)- Trip reset commands- Single connection point to REB500 central unit- Disturbance recorder data (via HMI500- REBWIN)

    IEC 60870-5-103 IBB protocol

    IEC 60870-5-103 interbay bus sup-ports

    - Time synchronization: typical accuracy 5 ms- Optical or electrical connection- Subset of binary events as specified in IEC

    Private range: Support of all binary eventsGeneric mode: Support of all binary events

    - Trip reset command- Disturbance recording data

    Address setting of station address 0...254

    Sub address setting, common addressof ADSU

    0...255 (CAA)CAA per bay unit freely selectable

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    23/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 23

    ABB Switzerland LtdPower Technology Systems

    Software modules

    Station level functions

    (Applicable for nominal frequencies of 50, 60 and 16.7 Hz)

    Table 16 Busbar protection (87B)

    Min. fault current pick-up setting (Ikmin)Neutral current detection

    500 to 6000 A in steps of 100 A100 to 6000 A

    Stabilizing factor (k) 0.7 to 0.9 in steps of 0.05

    Differential current alarmscurrent settingtime delay setting

    5 to 50% x Ikminin steps of 5%2 to 50 s in steps of 1 s

    Isolator alarmtime delay 0.5 to 90 s

    Typical tripping time 20 to 30 ms at Idiff/Ikmin5 incl. tripping relays; for fN= 50, 60 Hz30 to 40 ms at Idiff/Ikmin5 incl. tripping relays; for fN= 16.7 Hz

    CT ratio per feeder 50 to 10 000/1 A,50 to 10 000/5 A, adjustable via HMI

    Reset time 30 to 96 ms (at 1.2

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    24/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 24

    Technical data (contd)Technical data (contd)

    ABB Switzerland LtdPower Technology Systems

    Table 19 Overcurrent protection (51)

    Characteristic definite time

    Measurement:

    Setting range 0.1 to 20 x IN in steps of 0.1 x IN

    Setting range time delay 10 ms to 20 s in steps of 10 ms

    Reset ratio typically 95%

    Reset time 20 to 60 ms (at 1.2 or in combination.

    Table 23 Check zone cri terion (87CZ)

    Min. fault current pick-up setting (Ikmin) 500 to 6000 A in steps of 100 A

    Stabilizing factor (k) 0.0 to 0.90 in steps of 0.05

    CT ratio per feeder Feeder 50 to 10 000/1 A,50 to 10 000/5 A, adjustable via HMI

    The check zone is used as an additional release criterion for busbar protection and operates zone-inde-pendent.

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    25/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 25

    ABB Switzerland LtdPower Technology Systems

    Table 24 Delay/integrator

    Table 25 Log ic

    Bay level funct ions for Back-up/Main 2 REB500sys

    (Applicable for nominal frequencies of 50, 60 Hz)

    For delaying pick-up or reset or for integrating 1 binary signal Provision for inverting the input

    4 independent parameter sets.Settings:

    Pick-up or reset time 0 to 300 s in steps of 0.01 s

    Integration yes/no

    Logic for 4 binary inputs with the following 3 configurations:1. OR gate2. AND gate3. Bistable flip-flop with 2 set and 2 reset inputs (both OR gates), resetting takes priority

    4 independent parameter sets.

    All configurations have an additional blocking input.Provision for inverting all inputs.

    Table 26 Definite time over and undercurrent protection (51)

    Over and undercurrent detection Single or three-phase measurement with detection of the highest, respectively lowest phase current

    2nd harmonic restraint for high inrush currents. 4 independent parameter sets.

    Settings:

    Pick-up current 0.2 to 20 IN in steps of 0.01 IN

    Delay 0.02 to 60 s in steps of 0.01 s

    Accuracy of the pick-up setting (at fN) 5%

    Reset ratioovercurrentundercurrent

    >94% (for max. function)

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    26/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 26

    Technical data (contd)Technical data (contd)

    ABB Switzerland LtdPower Technology Systems

    Number of phases 1 or 3

    Base current IB 0.04 to 2.5 INin steps of 0.01 IN

    Pick-up current Istart

    1 to 4 IB

    in steps of 0.01 IB

    Min. time setting tmin 0 to 10 s in steps of 0.1 s

    k1setting 0.01 to 200 s in steps of 0.01 s

    Accuracy classes for the operating timeaccording to B.S. 142, IEC 60255-3RXIDG characteristic

    E 5.04% (1 - I/80 IB)

    Reset ratio 95%

    Table 28 Definite time over and undervol tage protection (59/27)

    Over and undervoltage detection

    Single or three-phase measurement with detection of the highest, respectively lowest phase voltage 4 independent parameter sets.

    Settings:

    Pick-up voltage 0.01 to 2.0 UNin stepsof 0.01 UN

    Delay 0.02 to 60 s in steps of 0.01 s

    Accuracy of the pick-up setting (at fN) 2% or 0.005 UN

    Reset ratio (U 0.1 UN)overvoltageundervoltage

    >96% (for max. function)

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    27/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 27

    ABB Switzerland LtdPower Technology Systems

    Table 30 Directional overcur rent definite time protection (67)

    Directional overcurrent protection with detection of power flow direction Back-up protection

    4 independent parameter sets Three-phase measurementSuppression of DC and HF componentsDefinite time characteristic Voltage memory for near faults Selectable response when power direction no longer valid (trip or block)

    Settings:

    Current 0.02 to 20 INin steps of 0.01 IN

    Angle -180 to +180 in steps of 15

    Delay 0.02 to 60 s in steps of 0.01 s

    Wait time 0.02 to 20 s in steps of 0.01 s

    Memory duration 0.2 to 60 s in steps of 0.01 s

    Accuracies:Measuring accuracies are defined by:

    Frequency range 0.91.05 fNSinusoidal voltage including 3., 5., 7. and 9. harmonic

    Accuracy of pick-up valueReset ratio

    Accuracy of angle measurement (at 0.971.03 fN)

    5%95%5

    Voltage input rangeVoltage memory rangeAccuracy of angle measurement at voltage memoryFrequency dependence of angle measurement at

    voltage memoryResponse time without delay

    0.005 to 2 UN

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    28/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 28

    Technical data (contd)Technical data (contd)

    ABB Switzerland LtdPower Technology Systems

    Accuracies:Measuring accuracies are defined by:

    Frequency range 0.91.05 fN

    Accuracy of pick-up valueReset ratio

    Accuracy of angle measurement (at 0.971.03 fN)

    5%95%5

    Voltage input rangeVoltage memory rangeAccuracy of angle measurement at voltage memoryFrequency dependence of angle measurement at

    voltage memoryResponse time without delay

    0.005 to 2 UN95% (at U >0.1 UN or I >0.1 IN)Current plausibility settings:

    Pick-up differential for sum of internal summation cur-rent 0.05 to 1.00 INin stepsof 0.05 IN

    Amplitude compensation for summation CT -2.00 to +2.00 in steps of 0.01

    Delay 0.1 to 60 s in steps of 0.1 s

    Voltage plausibility settings:

    Pick-up differential for sum of internal summation volt-age 0.05 to 1.2 UNin steps of 0.05 UN

    Amplitude compensation for summation VT -2.00 to +2.00 in steps of 0.01

    Delay 0.1 to 60 s in steps of 0.1 s

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    29/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 29

    ABB Switzerland LtdPower Technology Systems

    Remark: Distance protection operating times on next page

    Table 34 Directional sensiti ve earth fault protection for grounded systems (67N)

    Detection of high-resistance earth faults Current enabling setting 3I0

    Direction determined on basis of neutral variables (derived externally or internally) Permissive or blocking directional comparison scheme Echo logic for weak infeeds Logic for change of energy direction 4 independent parameter sets.

    Settings:

    Current pick-up setting 0.1 to 1.0 INin steps of 0.01 IN

    Voltage pick-up setting 0.003 to 1 UNin steps of 0.001 UN

    Characteristic angle -90 to +90 in steps of 5

    Delay 0 to 1 s in steps of 0.001 s

    Accuracy of the current pick-up setting 10% of setting

    Table 35 Distance protection (21)

    Five measuring stages with polygonal impedance characteristic forward and backwardAll values of settings referred to the secondaries, every zone can be set independently of the others 4 independent parameter sets.

    Impedance measurement -300 to 300 /ph in steps of 0.01 /ph

    Zero-sequence current compensation 0 to 8 in steps of 0.01,-180 to +90 in steps of 1

    Mutual impedance for parallel circuit lines 0 to 8 in steps of 0.01,-90 to +90 in steps of 1

    Time step setting range 0 to 10 s in steps of 0.01 s

    Underimpedance starters -999 to 999 /ph in steps of 0.1 /ph

    Overcurrent starters 0.5 to 10 IN in steps of 0.01 IN

    Min. operating current 0.1 to 2 INin steps of 0.01 IN

    Back-up overcurrent 0 to 10 IN in steps of 0.01 IN

    Neutral current criterion 0.1 to 2 INin steps of 0.01 IN

    Neutral voltage criterion 0 to 2 UNin steps of 0.01 UN

    Low-voltage criterion for detecting, for exam-ple, a weak infeed

    0 to 2 UNin steps of 0.01 UN

    VT supervisionNPS/neutral voltage criterionNPS/neutral current criterion

    0.01 to 0.5 UNin steps of 0.01 UN0.01 to 0.5 INin steps of 0.01 IN

    Accuracy (applicable for current time con-stants between 40 and 150 ms)

    amplitude errorphase errorSupplementary error for- frequency fluctuations of +10%- 10% third harmonic- 10% fifth harmonic

    5% for U/UN >0.12 for U/UN >0.1

    5%10%10%

    Operating times of the distance protectionfunction (including tripping relay)

    minimumtypical(see also isochrones)

    20 ms25 ms

    Typical reset time 25 ms

    VT-MCB auxiliary contact requirementsOperation time

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    30/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 30

    Technical data (contd)Technical data (contd)

    ABB Switzerland LtdPower Technology Systems

    Distance protection operating times

    Isochrones

    Abbreviations: ZS = source impedanceZF = fault impedanceZL = zone 1 impedance setting

    Single phase fault (min)

    0

    0.2

    0.4

    0.6

    0.8

    1

    0.1 1 10 100 1000

    18ms

    Single phase fault (max)

    0

    0.2

    0.4

    0.6

    0.8

    1

    0.1 1 10 100 1000

    31ms

    29ms

    SIR (ZS/ZL)

    ZF/ZL

    ZF/ZL

    SIR (ZS/ZL)

    18ms17ms

    Two phase fault (min)

    0

    0.2

    0.4

    0.6

    0.8

    1

    0.1 1 10 100 1000

    Two phase fault (max)

    0

    0.2

    0.4

    0.6

    0.8

    1

    0.1 1 10 100 1000

    29ms

    32ms

    ZF/ZL

    ZF/ZL

    SIR (ZS/ZL)SIR (ZS/ZL)

    18ms17ms

    19ms

    Three phase fault (min)

    0

    0.2

    0.4

    0.6

    0.8

    1

    0.1 1 10 100 1000

    20ms

    Three phase fault (max)

    0

    0.2

    0.4

    0.6

    0.8

    1

    0.1 1 10 100 1000

    29ms

    33ms

    ZF/ZL

    ZF/ZL

    SIR (ZS/ZL) SIR (ZS/ZL)

    18ms17ms

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    31/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 31

    ABB Switzerland LtdPower Technology Systems

    Table 36 Autoreclosure (79)

    Single and three-phase autoreclosure. Operation in conjunction with distance, overcurrent and synchrocheck functions and also with external

    protection and synchrocheck relays. Logic for 1st and 2nd main protections, duplex and master/follower schemes. Up to four fast or slow reclosure shots. Detection of evolving faults 4 independent parameter sets.

    Settings:

    1st reclosure none1P fault - 1P reclosure1P fault - 3P reclosure1P/3P fault - 3P reclosure1P/3P fault - 1P/3P reclosure

    2nd to 4th reclosure nonetwo reclosure cyclesthree reclosure cycles

    four reclosure cyclesSingle phase dead time 0.05 to 300 s

    Three-phase dead time 0.05 to 300 s

    Dead time extension by ext. signal 0.05 to 300 s

    Dead times for 2nd, 3rd and 4th reclosures 0.05 to 300 s

    Fault duration time 0.05 to 300 s

    Reclaim time 0.05 to 300 s

    Blocking time 0.05 to 300 s

    Single and three-phase discrimination times 0.1 to 300 s

    All settings in steps of 0.01 s

    Table 37 Synchrocheck (25)

    Determination of synchronismSingle phase measurement. The differences between the amplitudes, phase-angles and frequen-cies of two voltage vectors are determined.

    Voltage supervisionSingle or three-phase measurementEvaluation of instantaneous values and therefore wider frequency rangeDetermination of maximum and minimum values in the case of three-phase inputs

    Phase selection for voltage inputs Provision for switching to a different voltage input (double busbar systems) Remote selection of operating mode

    4 independent parameter sets.Settings:

    Max. voltage difference 0.05 to 0.4 UNin steps of 0.05 UN

    Max. phase difference 5 to 80 in steps of 5

    Max. frequency difference 0.05 to 0.4 Hz in steps of 0.05 Hz

    Min. voltage 0.6 to 1 UN in stepsof 0.05 UN

    Max. voltage 0.1 to 1 UN in stepsof 0.05 UN

    Supervision time 0.05 to 5 s in steps of 0.05 s

    Resetting time 0 to 1 s in steps of 0.05 s

    AccuracyVoltage difference

    Phase differenceFrequency difference

    for 0.9 to 1.1 fN5% UN

    50.05 Hz

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    32/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 32

    Technical data (contd)Technical data (contd)

    ABB Switzerland LtdPower Technology Systems

    Table 38 Transformer dif ferential protection (87T)

    Features:

    For two- and three-winding transformers

    Three-phase functionCurrent-adaptive characteristicHigh stability for external faults and current transformer saturationNo auxiliary transformers necessary because of vector group and CT ratio compensationInrush restraint using 2nd harmonic

    Settings:

    g-setting 0.1 to 0.5 INin steps of 0.05 IN

    v-setting 0.25 or 0.5 or 0.7

    b-setting 1.25 to 2.5 in steps of 0.25 IN

    Max. trip time (protected transformer loaded)- for I>2 IN- for I2 IN

    30 ms50 ms

    Accuracy of pick-up value 5% IN(at fN)

    Reset conditions I

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    33/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 33

    ABB Switzerland LtdPower Technology Systems

    Table 40 Peak value over and undercurrent protect ion (50)

    Features:Maximum or minimum function (over- and undercurrent)

    Single or three-phase measurements Wide frequency range (0.04 to 1.2 fN) Peak value evaluation

    Settings:

    Current 0.1 to 20 IN in steps of 0.1 IN

    Delay 0 to 60 s in steps of 0.01s

    Accuracy of pick-up value (at 0.08 to 1.1 fN) 5% or 0.02 IN

    Reset ratio >90% (for max. function)

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    34/50

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    35/50

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    36/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 36

    Connection diagrams(contd)Connection diagrams(contd)

    ABB Switzerland LtdPower Technology Systems

    Bay unit 500BU03 connection diagrams

    A detailed description of each variant is given in the application description[3].

    Fig. 13 Bay unit connection diagram 500BU03, 4I, 5U

    Bay unit Protection functions

    500BU03 Stat ion level Bay level Measurement value

    Analogueinputs

    Busbarprotection

    Breakerfailureprotection

    Endfaultprotection

    Breakerpolediscrepancyprotec

    tion

    Voltagecheck

    Disturbancerecorder

    Distanceprotection

    Definitetimecurrentprotection

    Inversedefiniteminimumt

    imeovercurrentprotection

    Definitetimedirectionalovercurrentprotection

    Inversedefiniteminimumt

    imedirectionalovercurrentprotection

    Definitetimevoltageprotection

    Synchrocheck

    Direct.sensitiveEFprot.forgroundedsystems

    Direct.sensitiveEFprot.forung

    r.orcomp.systems

    Inversedefiniteminimumt

    imegroundfaultovercurrentprotection

    Currentplausibilitycheck

    Voltageplausibilitycheck

    Currents

    I1

    Phase current L1

    (Line)

    I2

    Phase current L2(Line)

    I3

    Phase current L3

    (Line)

    I4

    Residual current Lo (Y)(Line)

    Residual current derived

    internally Io= IL1+IL2+IL3

    Voltages

    U1

    Phase voltage L1(Line)

    U2

    Phase voltage L2

    (Line)

    U3

    Phase voltage L3

    (Line)

    U4

    Phase voltage L2

    (Bus 1)

    1ph -> L2-E

    U5

    Phase voltage L2

    (Bus 2)

    1ph -> L2-E

    Residual voltage derived

    internally Uo= UL1+UL2+UL3

    Current transformer/voltage transformer fixed assignmentRecommended setting (configured via software HMI500-REBWIN)Only for busbar protection Io-measurement (optional function)Bay unit types with metering (core balance) CT on input I4

    Derived

    internally

    Derived

    internally

    10

    12

    0

    1

    5

    1

    2

    3

    0

    4

    5

    1

    5

    6

    0

    7

    5

    1

    8

    9

    0

    5

    1

    11

    2 0

    1

    5 0

    4

    8 0

    7

    11 0

    10

    13

    14 0

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    37/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 37

    ABB Switzerland LtdPower Technology Systems

    Fig. 14 Bay unit connection diagram 500BU03, 9 I

    Bay unit Protection functions

    500BU03 Stat ion level Bay level Measurement value

    Analogueinputs

    Busbarprotection

    Bre

    aker-failureprotection

    End-faultprotection

    Bre

    aker-polediscrepancyprotection

    Dis

    turbancerecorder

    Tra

    nsformerdiffferentialprotection

    The

    rmaloverload

    Pea

    kvalueoverandundercurrentprotection

    Inversetimeovercurrentprotection

    Inversetimeearthfaultovercurrentprotection

    Definitetimeoverandundercurrentprotection

    Thr

    eephasecurrentplausibility

    Currents

    I1

    Phase current L1A-Side

    I2

    Phase current L2A-Side

    I3

    Phase current L3

    A-Side

    Residual current derived

    internally Io= IL1+IL2+IL3

    Currents

    I4

    Phase current L1

    B-Side

    I5

    Phase current L2B-Side

    I6

    Phase current L3B-Side

    Residual current derived

    internally Io= IL1+IL2+IL3

    Currents

    I7

    Phase current L1C-Side (if existing)

    I8

    Phase current L2C-Side (if existing)

    I9

    Phase current L3C-Side (if existing)

    Residual current derived

    internally Io= IL1+IL2+IL3

    Derivedinternally

    A-Sid e

    B-Side

    C-Side

    Transformer primary sideTransformer secondary sideTransformer tertiary side

    Derivedinternally

    Derivedinternally

    Current transformer, fixed assignmentRecommended setting (configured via software HMI500-REBWIN)Only for busbar protection Io-measurement (optional function)Io for earth fault protection

    0

    1

    5

    1

    2

    3

    0

    4

    5

    1

    5

    6

    0

    7

    5

    1

    8

    9

    I

    0

    1

    5

    1

    2

    3

    0

    4

    5

    1

    5

    6

    0

    7

    5

    1

    8

    9

    J

    0

    10

    5

    1

    11

    12

    0

    13

    5

    1

    14

    15

    0

    16

    5

    1

    17

    18

    J

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    38/50

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    39/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 39

    ABB Switzerland LtdPower Technology Systems

    REB500sys: Typical assignment of the in/outputs

    Fig. 17 REB500sys: Typical assignment of the in/outputs of line variant L-V4 for 500BU03(See[3]Application description)

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    CR01

    CR02

    CR03

    CR04

    CR05

    CR06

    CR07

    CR08

    CR09

    CR10

    CR11

    CR12

    CR13

    CR14

    CR15

    CR16

    C

    D

    In service

    Block close command

    AR close command

    Remote trip, channel 1

    Carrier send, distance prot.

    Remote trip, channel 2

    Carrier send, DEF prot.

    Start L1L2L3 to AR in main 1

    Trip CB 3-pole to AR in main 1

    Trip CB to AR in main 1

    Trip phase L1, trip coil 1

    Trip phase L2, trip coil 1

    Trip phase L3, trip coil 1

    Trip phase L1, trip coil 2

    Trip phase L2, trip coil 2

    Trip phase L3, trip coil 2

    Binary outputsLine Variant 4

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    1213

    14

    15

    OC01

    OC02

    OC03

    OC04

    OC05

    OC06

    OC07

    OC08

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    OC10

    OC11

    OC12

    OC13

    OC14

    OC15

    OC16

    A

    B

    16

    17

    18OC09

    OC17

    OC18

    OC19

    OC20

    16

    17

    18

    Binary inputsLine Variant 4

    Bus 1 VT MCB fail

    Bus 2 VT MCB fail

    Prepare 1-pole trip from main 1

    Main 1 healthy/in service mode (Blk. AR)

    OCO ready for AR release

    Carrier receive, distance prot.

    Carrier receive, DEF prot.

    CB all poles closed, DEF prot.

    Line VT MCB fail

    Start BFP Phase L1

    Start BFP Phase L2

    Start BFP Phase L3Start BFP Phase L1L2L3

    Q0 Manual Close Command +AR CLOSE Command CB

    Breaker Q0 open

    Breaker Q0 closed

    Bus 1 Isolator Q1 open

    Bus 1 Isolator Q1 closed

    Bus 2 Isolator Q2 open

    Bus 2 Isolator Q2 closed

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    40/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 40

    Connection diagrams(contd)Connection diagrams(contd)

    ABB Switzerland LtdPower Technology Systems

    Fig. 18 REB500sys: Typical assignment of the in/outputs of transformer variant T-V1 for 500BU03(See[3] application description)

    Start BFP phase L1L2L3from back-up prot. TRIP

    Start BFP phase L1L2L3from prot. group 2 TRIP 1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    OC01

    OC02

    OC03

    OC04

    OC05

    OC06

    OC07

    OC08

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    OC10

    OC11

    OC12

    OC13

    OC14

    OC15

    OC16

    A

    B

    16

    17

    18OC09

    OC17

    OC18

    OC19

    OC20

    16

    17

    18

    Binary inputs

    Transformer

    Variant 1

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    12

    13

    14

    15

    CR01

    CR02

    CR03

    CR04

    CR05

    CR06

    CR07

    CR08

    CR09

    CR10

    CR11

    CR12

    CR13

    CR14

    CR15

    CR16

    C

    D

    Binary outputs

    Transformer

    Variant 1

    Block transformerdiff. protection

    Transformer diff. inrush input

    Transformer diff. high-set

    A-side breaker Q0manual close command

    A-side breaker Q0 open

    A-side breaker Q0 closed

    A-side bus 1 isolator Q1 open

    A-side bus 1 isolator Q1 closed

    A-side bus 2 isolator Q2 open

    A-side bus 2 isolator Q2 closed

    Mechanic protection TRIP 2

    Mechanic protection alarm 2

    Spare

    Spare

    In service

    Block close commandbreaker Q0 A-side

    Transf. prot. trip start BFPon B-side

    Remote Trip 1 to C-side *)

    Trip phase L2Trip phase L3

    Remote trip 1 to B-side

    Mechanic protection TRIP 1

    Mechanic protection alarm 1

    Spare

    External start BFPfrom mechanic prot. TRIP

    Legend:

    A-side Transformer primary sideB-side Transformer secondary sideC-side Transformer tertiary side *)

    *) C-side, if existing

    trip breaker

    Q0 coil 1 A-side

    Trip phase L1

    Trip phase L2

    Trip phase L3

    trip breakerQ0 coil 2 A-side

    Trip phase L1

    Transf. prot. trip L1L2L3 group 2Tripping relay (94-2)trip CB A/B/Cside *)

    Remote trip 2 to B-side

    Transf. prot. trip L1L2L3 group 1Tripping relay (94-1)trip CB A/B/Cside *)

    Transf. prot. trip start BFPon C-side *)

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    41/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 41

    ABB Switzerland LtdPower Technology Systems

    Dimensioneddrawings (in mm)

    Bay uni t 500BU03

    Fig. 19 Bay unit casing for flush mounting, enclosure protection class IP 40(without local HMI)

    Fig. 20 Centralized version based on a 19'' mounting plate with up to three bay units.Optionally with local HMI.

    Caution

    Achtung

    Atencion

    Attention

    Cross section: max. 2.5 mm2

    max. 4.0 mm2

    Spaceforwiring

    Cross section: max. 2.5 mm2

    max. 4.0 mm2

    Spaceforwiring

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    42/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 42

    Dimensioned draw-ings (in mm) (contd)Dimensioned draw-ings (in mm) (contd)

    ABB Switzerland LtdPower Technology Systems

    Bay uni t 500BU03

    Fig. 21 Dimensional drawing of the bay unit with local HMI, classical mountingProtection type IP40

    Central unit

    Fig. 22 Dimensional drawing of the central unit, protection type IP20

    Cross section max. 2.5 mm

    max. 4.0 mm2

    Space for wiring

    Panel cutout

    223

    276

    app

    rox.

    100

    189

    204 ,50

    6U=265,8

    200

    0,

    5

    267

    +

    ,1

    0 0

    25

    210

    Rear viewapprox.

    70

    212

    482.6

    6U=265.8

    approx.

    235

    30

    443

    465.6

    6U=265.8

    57.1

    57.1

    76.2

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    43/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 43

    ABB Switzerland LtdPower Technology Systems

    Fig. 23 Front view of REB500 (example only) Fig. 24 Hinged frame and rear wall

    Example with 9 bay units

    The cubicles are equipped with gratings for the fixation of incoming cables. For space reasonsthere are no cable ducts.

    Table 41 Maximum number of units per cubicle (central version)

    Unit Quantity of 500BU03Cross-section

    ext. cable

    Quantity of

    system cables

    per bay

    Current transformer per bay 4 9 2,5 mm2- 6 mm2 1

    Voltage transformer per bay 5 - 1,5 mm2- 6 mm2 1

    Binary inputs per bay 20 1,5 mm2- 2,5 mm2 1 - 3

    Binary outputs per bay 16 1,5 mm2- 2,5 mm2 1 - 3

    Max. number of bays percubicle with central unit

    9* * number of bays per cubicle(2200 x 800 x 800 mm)based on the min. cross-section and anaverage quantity of cables

    Max. number of bays percubicle without central unit

    12*

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    44/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    ABB Switzerland LtdPower Technology Systems

    REB500 / REB500sys1MRB520308-Ben

    Page 44

    Basic version Basic version Classical mounting

    Fig. 25 Possible arrangement of the bay unit with HMI

    Table 42 Unit weights

    Unit Weight

    Bay unit 4l, classic (incl. HMI) 5,1 kg

    Bay unit 4l, 5U, red. power supply, classic (incl. HMI)Bay unit 3l, 1MT, 5U, red. power supply, classic (incl. HMI)

    6,2 kg

    Bay unit 4l, basic version 3,9 kg

    Bay unit 4l, 5U, red. power supply, basic versionBay unit 3l, 1MT, 5U, red. power supply, basic version

    5.0 kg

    Bay unit 9I, red. power supply, classic (incl. HMI) 6.7 kg

    Bay unit 9I, red. power supply, basic version 5.5 kg

    Central unit 9,0 kg (Average weight => here 11 feedersplus communication interface)

    Central unit with redundant power supply 10,0 kg

  • 8/11/2019 1MRB520308-BEN en Numerical Station Protection System REB500-REB500sys

    45/50

    Numerical Station Protection SystemBusbar Protection with integrated BreakerFailure, Line and Transformer Protection

    REB500 / REB500sys1MRB520308-Ben

    Page 45

    ABB Switzerland LtdPower Technology Systems

    Samplespecification

    Combined numerical bay and station protec-tion with extensive self-monitoring and ana-logue/digital conversion of all input

    quantities.

    The architecture shall be decentralized, withbay units and a central unit.

    It shall be suitable for the protection of singleand double busbar as well as for the protec-tion (Main 2 or back-up) of incoming andoutgoing bays, lines, cables or transformer

    bays.

    The hardware shall allow functions to be acti-vat