1vap420001-tg utilityitrefguide revl dec2012

118
Instrument Transformer Reference Guide Meter and Relay Applications for the Electrical Industry

Upload: franz-erwin-gabriel-fuentes

Post on 08-Nov-2014

217 views

Category:

Documents


5 download

TRANSCRIPT

Instrument Transformer Reference GuideMeter and Relay Applications for the Electrical Industry

ABB reference guide | Instrument Transformer Reference Guide 3

General Index Guide600 Volt Current TransformersPrimary current Type Product bulletin Page

50 thru 1000 IMC 1VAP428101-DB 8-9

100 thru 800 CBT-S, CBT/1 1VAP428111-DB 10-11

100 thru 800 CBT-H 1VAP428111-DB 12-13

200 thru 600 CSF 1VAP428131-DB 14-15

200 thru 800 CSH 1VAP428141-DB 16

200 thru 300 CMS 1VAP428151-DB 17

50 thru 1200 CMF-S, CMF 1VAP428181-DB 18-21

100 thru 4000 CMV-S, CMV 1VAP428201-DB 22-23

200 thru 4000 CMV-Hi Temp 1VAP428201-DB 24-25

600 thru 4000 CLC 1VAP428241-DB 26-35

50 thru 4000 DEH-705 1VAP701011-DB 36-37

1000 thru 6000 CLE 1VAP428261-DB 38-39

100 thru 6000 CEH-636 1VAP701031-DB 40-41

600 thru 4000 RLC 1VAP428281-DB 42-45

50 thru 6000 SCT-983 1VAP701051-DB 46-47

200 thru 4000 RMB(X)-644 1VAP701081-DB 48-49

600 Volt Voltage TransformersPrimary Voltage Type Product bulletin Page

240 thru 600 PPW, PPD 1VAP428711-DB 50-51

120 thru 600 PPM 1VAP428731-DB 52-53

60 thru 480 PPX 1VAP428731-DB 52-53

5 kV - 36 kV Current TransformersClass Type Product bulletin Page

5 kV Indoor KIR-60 1VAP429141-DB 54-55

5 kV Indoor TD-994 1VAP701141-DB 56-57

5 kV Indoor RMB(X)-631 1VAP701131-DB 58-59

5 kV Indoor KIT-60 1VAP429151-DB 60-61

5 kV Outdoor KOR-60 1VAP429201-DB 62-63

5 kV Outdoor KOT-60 42-930 64-65

8.7 kV Indoor HSB-994 1VAP701151-DB 66-67

8.7 kV Indoor HTD-994 1VAP701161-DB 68-69

8.7 kV Indoor STBB-991/992 1VAP701171-DB 70-71

8.7 kV Indoor KIR-75 1VAP429141-DB 72-73

8.7 kV Indoor KIT-75 1VAP429151-DB 74-75

8.7 kV Outdoor KOR-75 1VAP429201-DB 76-77

8.7 kV Outdoor KOT-75 42-930 78-79

15 kV Indoor KIR-11, 11E 1VAP429141-DB 80-83

15 kV Indoor KIT-11 1VAP429151-DB 84-85

15 kV Outdoor KON-11ER 1VAP429242-DB 86-87

15 kV Outdoor KON-11 1VAP429241-DB 86-87

15 kV Outdoor KOR-11, 11E 1VAP429221-DB 88-91

Instrument Transformer Reference Guide | ABB reference guide

4 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 5

5 kV - 36 kV Voltage Transformers (cont’d)Class Type Product bulletin Page

25 kV Outdoor VOY-15, 15G 1VAP429701-DB 172-173

25 kV Outdoor VOZ-15, 15E 1VAP429711-DB 172-173

25 kV Outdoor VOZZ-15, 15G 1VAP429781-DB 174-175

34.5 kV Indoor VIZ-20, 20G 1VAP429601-DB 176-177

34.5 kV Outdoor VOY-20, 20G 1VAP429741-DB 178-179

34.5 kV Outdoor VOZ-20 1VAP429751-DB 180-181

34.5 kV Outdoor VOHD-200, 200G 42-977 182-183

34.5 kV Outdoor VOZZ-20, 20G 1VAP429791-DB 182-183

15-36 kV Combined Current and Voltage TransformersClass Type Product bulletin Page

15 kV Outdoor CVC-110ER (PUR) 1VAP429992-DB 184-185

15 kV Outdoor CVC-110ER (HCEP) 1VAP429993-DB 184-185

25 kV Outdoor SCC-125 1VAP429996-DB 186-187

25 kV Outdoor CVC-150/CVC-200 1VAP429991-DB 188-189

5 kV - 36 kV Current Transformers (cont’d)Class Type Product bulletin Page

15 kV Outdoor KOT-11 42-930 92-93

15 kV Outdoor LG(X)-15-5851VAP701181-DB 1VAP701182-DB

94-95

15 kV Outdoor LG(X)-15-683 1VAP701191-DB 96-97

15 kV Outdoor LG-15-879 1VAP701201-DB 98-99

15 kV Outdoor LG(X)-15-6513 1VAP701211-DB 100-101

15 kV Outdoor KOTD-110 42-940 102-105

25 kV Indoor KIT-15 1VAP429151-DB 106-107

25 kV Outdoor KOT-15 42-930 108-109

25 kV Outdoor KOR-12 1VAP429221-DB 110-111

25 kV Outdoor KON-12 - 112-113

25 kV Outdoor KOR-15CER 1VAP429272-DB 114-115

25 kV Outdoor KOR-15C 1VAP429271-DB 116-117

25 kV Outdoor KOTD-150 42-940 118-121

25 kV Outdoor LG(X)-25-5851VAP701221-DB 1VAP701222-DB

122-123

25 kV Outdoor LG-25-879 1VAP701231-DB 124-125

25 kV Outdoor LG(X)-25-6513 1VAP701241-DB 126-127

34.5 kV Outdoor KOR-20ER 1VAP429283-DB 128-129

34.5 kV Outdoor KOR-20 1VAP429282-DB 130-131

34.5 kV Outdoor LG(X)-34-8791VAP701251-DB 1VAP701252-DB

132-133

34.5 kV Outdoor KOTD-200 42-940 134-137

5 kV - 36 kV Voltage TransformersClass Type Product bulletin Page

5 kV Indoor VIY-60 1VAP429511-DB 138-139

5 kV Outdoor VOY-60 1VAP429611-DB 140-141

8.7 kV Indoor VIZ-75, 75E 1VAP429551-DB 142-145

8.7 kV Outdoor VOZ-75, 75E 1VAP429631-DB 146-147

15 kV Indoor VIL-95, 95S 1VAP429581-DB 148-149

15 kV Indoor VIZ-11, 11E 1VAP429551-DB 150-155

15 kV Outdoor VOZ-11E - 156-157

15 kV Outdoor VOY-11 1VAP429631-DB 156-157

15 kV Outdoor VOG-11 1VAP429651-DB 158-159

15 kV Outdoor VOZ-11 1VAP429631-DB 160-161

15 kV Outdoor VOZ-11M 1VAP429632-DB 160-161

25 kV Indoor VIL-12, 12S 1VAP429581-DB 162-163

25 kV Indoor VIZ-12, 12G 1VAP429762-DB 164-165

25 kV Indoor VIZ-15, 15G 1VAP429761-DB 166-167

25 kV Indoor VIZZ-15, 15G 1VAP429591-DB 168-169

25 kV Outdoor VOY-12 1VAP429661-DB 170-171

25 kV Outdoor VOG-12 1VAP429671-DB 170-171

Custom Engineered DesignsClass Type Product bulletin Page

Multi-Ratio A-Auto 42-852 190-191

600 Volt FSR-983 1VAP701061-DB 190-191

600 Volt PSH-993 1VAP701071-DB 192-193

Multi-Ratio Auxiliary 1VAP428501-DB 194-195

600 Volt ACT-983 1VAP701111-DB 196-197

600 Volt ACT-633/645 1VAP701101-DB 198-199

600 Volt APT-646/733 1VAP701091-DB 200-201

600 Volt BYZ-863/865 1VAP701291-DB 202

600 Volt PSZ-981 1VAP701281-DB 202

600 Volt BCT-605/BH-001 1VAP428582-DB 203

600 Volt SP-061 1VAP701301-DB 203

600 Volt CO-9740 1VAP701121-DB 204-205

600 Volt SCADA-BEH 1VAP701001-DB 206-207

600 Volt SCADA-DEH 1VAP701021-DB 208-209

600 Volt SCADA-CEH 1VAP701041-DB 210-211

600 Volt PS-981/PH-982 1VAP701261-FL 210-211

600 Volt ACCUSlipTM 1VAP701261-FL 212-213

600 Volt PSG-981 - 214

600 Volt

GCT-848/HW-945/ GCT-802 & ISO-Phase Bus

-

215

6 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 7

The transformers listed in this guide represent those most commonly built for the electric utility industry but are a small sample of what we actually offer. For special designs or units not listed, please contact your local ABB representative.

VT Voltage Designations

14400/24940Y This unit is rated for 14400 operating volts. It can be connected at 14400 volts line-to-ground on a 24940 volt system (line-to-line Volts are 24940 V) OR it can be connected line-to-line on a system with 14400 V line-to-line. This unit is not suitable for operation at 24940 volts. The "Y" indicates it has two fully insulated bushings, suitable for line-to-line connection.

14400/24940GY This unit is rated for 14400 operating volts. It can be connected at 14400 volts line-to-ground on a 24940 V system (line-to-line volts are 24940 V). It CANNOT be connected line-to-line. The “GY” indicates it only has one fully insulated bushing, making it suitable for line-to-ground connection only.

14400/14400Y This unit is rated for 14400 operating volts. It can be connected at 14400 V line-to-line.

14400/14400GY This unit is rated for 14400 operating volts; however, it can only be connected line-to-ground on a 14400 V system. Therefore, the actual operating voltage of the unit is 14400/1.73. The accuracy and thermal ratings of this unit are based on 14400 V. This is typical where there is a relay connected to the unit which should operate when there is a single line-to-ground fault. In this condition, the line-to-ground voltage becomes equal to the line-to-line voltage. This unit is not suitable for line-to-line connection as indicated by the “GY”.

CT Rating Factors: Rating factors given in this brochure are standard at 30º C. See the thermal loading guide on page 225 for derating for higher average ambient temperatures.

Transformers in this booklet conform to the following standards where applicable: - IEEE Standard Requirements for Instrument Transformers,

C57.13–1993.- IEEE Standard for Instrument Transformers for Metering Purposes,

15 kV and less, C12.11–1987.- IEEE Standard for High Accuracy Instrument Transformers,

C57.13.6–2005.

Application data 222-225

Accuracy standards 226-227

Type designations 228-229

Cross-reference of commonly used types 230

Testing services 231

HCEP material 231

IEC Current and Voltage TransformersClass Type Product bulletin Page

12 & 17.5 kV Outdoor KON-17 1VAP429803-DB 216-217

12 & 17.5 kV Outdoor VOG-17 1VAP429802-DB 218-219

12 & 17.5 kV Outdoor VOY-17 1VAP429801-DB 220-221

8 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 9

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5

Window Diam. (in.)

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

50 7524A98G11 2.4 – – 2.5 2.0 1.5 5.47 4.72 2.0 3.5

100 7524A98G01 1.2 – – 2.5 2.0 1.5 5.47 4.72 2.0 3.5

150 7524A98G02 1.2 1.2 – 2.5 2.0 1.5 5.47 4.72 2.0 3.5

200 7524A98G03 0.6 1.2 2.4 2.5 2.0 1.5 5.47 4.72 2.0 3.5

250 7524A98G04 0.6 1.2 2.4 2.5 2.0 1.5 5.47 4.72 2.0 3.5

300 7524A98G05 0.6 0.6 0.6 2.5 2.0 1.5 5.47 4.72 2.0 3.5

400 7524A98G06 0.6 0.6 0.6 2.5 2.0 1.5 5.47 4.72 2.0 3.5

500 7524A98G07 0.3 0.3 0.6 2.5 2.0 1.5 5.47 4.72 2.0 3.5

600 7524A98G08 0.3 0.3 0.6 2.5 1.5 1.2 5.47 4.72 2.0 3.5

800 7524A98G09 0.3 0.3 0.3 2.5 1.33 1.0 5.47 4.72 2.0 3.5

1000 7524A98G10 0.3 0.3 0.3 2.5 1.0 0.75 5.47 4.72 2.0 3.5

Rating Factor

600 V Current Transformers

TYPE IMC600 volts Indoor/outdoor 10 kV BIL25-400 Hertz

TYPE IMC

IEEE Metering Accuracy*

Optional accessories: Mounting feet (set of 2), style 9628A05G01

* Stated accuracies are applicable for 60 Hz

1VAP428101-DB

UL Recognized Component

10 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 11

600 V Current Transformers1VAP428112-DB and 1VAP428111-DB

TYPES CBT-S and CBT/1600 volts Indoor/outdoor 10 kV BIL25-60 Hertz

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5

Window Diam. (in.)

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

100 7882A77G01 0.3 – – – 4.0 3.0 4.51 3.31 11.87 2.8

200 7882A77G04 0.3 0.3 – – 2.0 1.5 4.51 3.31 11.87 2.8

300 7882A77G07 0.3 0.3 – – 2.0 1.5 4.51 3.31 11.87 3.1

400 7882A77G10 0.3 0.3 – – 2.0 1.5 4.51 3.31 11.87 3.1

500 7882A77G13 0.3 0.3 – – 2.0 1.5 4.51 3.31 12.12 3.8

600 7882A77G16 0.3 0.3 – – 2.0 1.5 4.51 3.31 12.12 4.0

800 7882A77G19 0.3 0.3 – – 1.5 1.2 4.51 3.31 12.12 4.0

100 7882A77G02 0.3 – – – 4.0 3.0 4.60 3.37 11.87 2.8

200 7882A77G05 0.3 0.3 – – 2.0 1.5 4.60 3.37 11.87 2.8

300 7882A77G08 0.3 0.3 – – 2.0 1.5 4.60 3.37 11.87 3.1

400 7882A77G11 0.3 0.3 – – 2.0 1.5 4.60 3.37 11.87 3.1

500 7882A77G14 0.3 0.3 – – 2.0 1.5 4.60 3.37 12.12 3.8

600 7882A77G17 0.3 0.3 – – 2.0 1.5 4.60 3.37 12.12 4.0

800 7882A77G20 0.3 0.3 – – 1.5 1.2 4.60 3.37 12.12 4.0

100 7882A77G03 0.3 – – – 4.0 3.0 6.50 5.25 11.87 3.0

200 7882A77G06 0.3 0.3 – – 2.0 1.5 6.50 5.25 11.87 3.0

300 7882A77G09 0.3 0.3 – – 2.0 1.5 6.50 5.25 11.87 3.3

400 7882A77G12 0.3 0.3 – – 2.0 1.5 6.50 5.25 11.87 3.3

500 7882A77G15 0.3 0.3 – – 2.0 1.5 6.50 5.25 12.12 4.0

600 7882A77G18 0.3 0.3 – – 2.0 1.5 6.50 5.25 12.12 4.2

800 7882A77G21 0.3 0.3 – – 1.5 1.2 6.50 5.25 12.12 4.2

No base

Flat base

High base

TYPE CBT/1

Primary Amps

Style

NumberIEEE Metering

AccuracyBase type

Window Diam. (in.)

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A496G01 0.15SB-0.2 None With bar 2.0 1.5 4.51 3.31 12.12 6.5

600 923A496G02 0.15SB-0.2 Flat With bar 2.0 1.5 4.60 3.37 12.12 6.5

600 923A496G03 0.15SB-0.2 High With bar 2.0 1.5 6.50 5.25 12.12 6.7

600 923A516G01 0.15SB-0.2 None 1.07 2.0 1.5 4.51 3.31 4.63 4.0

600 923A516G02 0.15SB-0.2 Flat 1.07 2.0 1.5 4.60 3.37 4.63 4.0

600 923A516G03 0.15SB-0.2 High 1.07 2.0 1.5 6.50 5.25 4.63 4.2

Rating Factor

TYPE CBT-S

The CBT-S is part of ABB's AccuRange™ current transformer portfolio of products.

IEEE Metering Accuracy* Rating Factor

12 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 13

100 7882A78G23 0.3 0.3 – - 4.0 3.0 4.62 3.37 11.87 4.2

200 7882A78G05 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 11.87 4.2

300 7882A78G08 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 11.87 3.4

400 7882A78G11 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 11.87 3.4

500 7882A78G14 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 12.12 4.3

600 7882A78G17 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 12.12 4.4

800 7882A78G20 0.3 0.3 0.3 - 1.5 1.2 4.62 3.37 12.12 4.4

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5

Window Diam. (in.)

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

100 7882A78G22 0.3 0.3 – - 4.0 3.0 4.62 3.37 11.87 4.2

200 7882A78G04 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 11.87 4.2

300 7882A78G07 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 11.87 3.4

400 7882A78G10 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 11.87 3.4

500 7882A78G13 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 12.12 4.3

600 7882A78G16 0.3 0.3 0.3 - 2.0 1.5 4.62 3.37 12.12 4.4

800 7882A78G19 0.3 0.3 0.3 - 1.5 1.2 4.62 3.37 12.12 4.4

Rating Factor

1VAP428111-DB

100 7882A78G24 0.3 0.3 – - 4.0 3.0 6.63 5.25 11.87 4.2

200 7882A78G06 0.3 0.3 0.3 - 2.0 1.5 6.63 5.25 11.87 4.3

300 7882A78G09 0.3 0.3 0.3 - 2.0 1.5 6.63 5.25 11.87 3.5

400 7882A78G12 0.3 0.3 0.3 - 2.0 1.5 6.63 5.25 11.87 3.5

500 7882A78G15 0.3 0.3 0.3 - 2.0 1.5 6.63 5.25 12.12 4.4

600 7882A78G18 0.3 0.3 0.3 - 2.0 1.5 6.63 5.25 12.12 4.5

800 7882A78G21 0.3 0.3 0.3 - 1.5 1.2 6.63 5.25 12.12 4.5

100 7882A87G08 0.3 0.3 – + NB 1.07 4.0 3.0 4.62 3.37 3.0 2.8

100 7882A87G09 0.3 0.3 – + FB 1.07 4.0 3.0 4.62 3.37 3.0 2.8

100 7882A87G10 0.3 0.3 – + HB 1.07 4.0 3.0 4.62 3.37 3.0 2.8

600 V Current Transformers

Flat base

High base

TYPE CBT-H600 Volts Indoor/outdoor10 kV BIL60 Hertz

No base

Without primary bar

+ NB = No Base, FB = Flat Base, HB = High Base

* Stated accuracies are applicable for 60 Hz

IEEE Metering Accuracy*

14 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 15

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5

Window Diam. (in.)

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 7524A85G01 0.3 0.3 – 1.5 3.0 2.0 4.85 3.5 3.32 3.75

300 7524A85G02 0.3 0.3 – 1.5 2.0 1.5 4.85 3.5 3.32 3.75

400 7524A83G02 0.3 0.3 – 2.0 2.0 1.5 4.85 3.5 3.32 2.25

600 7524A83G03 0.3 0.3 – 2.0 1.5 1.2 4.85 3.5 3.32 2.25

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5

Window Diam. (in.)

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 7524A85G03 0.3 0.3 – 1.5 3.0 2.0 4.94 3.5 5.25 4.0

300 7524A85G04 0.3 0.3 – 1.5 2.0 1.5 4.94 3.5 5.25 4.0

400 7524A83G05 0.3 0.3 – 2.0 2.0 1.5 4.94 3.5 5.25 2.5

600 7524A83G06 0.3 0.3 – 2.0 1.5 1.2 4.94 3.5 5.25 2.5

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5

Window Diam. (in.)

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 7524A85G05 0.3 0.3 – 1.5 3.0 2.0 6.54 5.25 4.50 4.0

300 7524A85G06 0.3 0.3 – 1.5 2.0 1.5 6.54 5.25 4.50 4.0

400 7524A83G08 0.3 0.3 – 2.0 2.0 1.5 6.54 5.25 4.50 2.5

600 7524A83G09 0.3 0.3 – 2.0 1.5 1.2 6.54 5.25 4.50 2.5

1VAP428131-DB

Rating Factor

Optional accessories:Primary bar for 1.5" window 9628A05G09Primary bar for 2.0" window 9628A05G10

Rating Factor

Rating Factor

TYPE CSF600 Volts Indoor/outdoor 10 kV BIL25-60 Hertz

600 V Current Transformers

IEEE Metering Accuracy*

No base

Flat base

IEEE Metering Accuracy*

IEEE Metering Accuracy*

High base* Stated accuracies are applicable for 60 Hz

16 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 17

200 7526A90G11 0.3 0.3 0.3 1.5 C20 3.0 2.2 5.53 5.62 3.87 7.50

300 7526A90G12 0.3 0.3 0.3 1.5 C30 2.0 1.5 5.53 5.62 3.87 7.50

400 7526A90G13 0.3 0.3 0.3 2.0 C30 2.0 1.5 5.53 5.62 3.87 6.25

500 7526A90G14 0.3 0.3 0.3 2.0 C30 2.0 1.5 5.53 5.62 3.87 5.75

600 7526A90G15 0.3 0.3 0.3 2.0 C10 2.0 1.5 5.53 5.62 3.87 5.45

800 7526A90G16 0.3 0.3 0.3 2.0 C10 1.5 1.2 5.53 5.62 3.87 5.25

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 7526A90G01 0.3 0.3 0.3 1.5 C20 3.0 2.2 5.41 4.0 3.87 7.25

300 7526A90G02 0.3 0.3 0.3 1.5 C30 2.0 1.5 5.41 4.0 3.87 7.25

400 7526A90G03 0.3 0.3 0.3 2.0 C30 2.0 1.5 5.41 4.0 3.87 6.0

500 7526A90G04 0.3 0.3 0.3 2.0 C30 2.0 1.5 5.41 4.0 3.87 5.5

600 7526A90G05 0.3 0.3 0.3 2.0 C10 2.0 1.5 5.41 4.0 3.87 5.2

800 7526A90G06 0.3 0.3 0.3 2.0 C10 1.5 1.2 5.41 4.0 3.87 5.0

Rating Factor

1VAP428151-DB

TYPE CMS600 Volts Indoor/outdoor 10 kV BIL25-60 Hertz

200 7526A90G21 0.3 0.3 0.3 1.5 C20 3.0 2.2 7.09 5.25 4.50 7.50

300 7526A90G22 0.3 0.3 0.3 1.5 C30 2.0 1.5 7.09 5.25 4.50 7.50

400 7526A90G23 0.3 0.3 0.3 2.0 C30 2.0 1.5 7.09 5.25 4.50 6.25

500 7526A90G24 0.3 0.3 0.3 2.0 C30 2.0 1.5 7.09 5.25 4.50 5.75

600 7526A90G25 0.3 0.3 0.3 2.0 C10 2.0 1.5 7.09 5.25 4.50 5.45

800 7526A90G26 0.3 0.3 0.3 2.0 C10 1.5 1.2 7.09 5.25 4.50 5.25

200 7524A79G03 0.3 0.3 – 2.0 C10 3.0 2.00 5.59 5.25 3.87 5.75

300 7524A79G04 0.3 0.3 0.3 2.0 C10 2.0 1.50 5.59 5.25 3.87 5.75

200 7524A79G05 0.3 0.3 – 2.0 C10 3.0 2.00 7.09 5.25 4.50 5.75

300 7524A79G06 0.3 0.3 0.3 2.0 C10 2.0 1.50 7.09 5.25 4.50 5.75

200 7524A79G01 0.3 0.3 – 2.0 C10 3.0 2.00 5.50 4.00 3.87 5.50

300 7524A79G02 0.3 0.3 0.3 2.0 C10 2.0 1.50 5.50 4.00 3.87 5.50

600 V Current Transformers

TYPE CSH

IEEE Metering Accuracy*

1VAP428141-DB

Flat base

High base

TYPE CSH600 Volts Indoor/outdoor10 kV BIL25-60 Hertz

No base

No base

Flat base

High base* Stated accuracies are applicable for 60 Hz

TYPE CMS

18 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 19

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-1.8Window

Diam. (in.)Relay*

Accuracy

30°C

55°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

50 4460A30G26 1.2 – – – 2.50 – 4.0 3.0 7.91 5.25 4.50 12.3

100 4460A30G24 0.3 – – – 2.50 C10 4.0 3.0 7.91 5.25 4.50 12.3

200 4460A30G02 0.3 0.3 0.3 – 2.50 C30 4.0 3.0 7.91 5.25 4.50 12.3

400 4460A30G04 0.3 0.3 0.3 – 3.06 C30 4.0 3.0 7.91 5.25 4.50 8.5

500 4460A30G06 0.3 0.3 0.3 – 3.06 C30 3.0 2.2 7.91 5.25 4.50 8.5

600 4460A30G08 0.3 0.3 0.3 – 3.06 C30 2.0 1.5 7.91 5.25 4.50 8.5

800 4460A30G10 0.3 0.3 0.3 – 3.06 C20 2.0 1.5 7.91 5.25 4.50 8.3

1000 4460A30G22 0.3 0.3 0.3 – 3.06 C30 2.0 1.5 7.91 5.25 4.50 8.3

1200 4460A30G20 0.3 0.3 0.3 0.3 3.06 C30 1.5 1.2 7.91 5.25 4.50 8.3

200/400 4460A30G12 0.3/0.3 0.3/0.3 0.3/0.3 – 2.50 C30/C50 4.0/2.0 3.0/1.5 7.91 5.25 4.50 12.4

300/600 4460A30G14 0.3/0.3 0.3/0.3 0.3/0.3 – 3.06 C20/C50 3.0/2.0 2.2/1.5 7.91 5.25 4.50 9.7

400/800 4460A30G16 0.3/0.3 0.3/0.3 0.3/0.3 – 3.06 C20/C50 2.0/2.0 1.5/1.5 7.91 5.25 4.50 8.7

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-1.8Window

Diam. (in.)Relay*

Accuracy

30°C

55°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

50 4460A30G25 1.2 – – – 2.50 – 4.0 3.0 7.12 5.62 4.50 12.3

100 4460A30G23 0.3 – – – 2.50 C10 4.0 3.0 7.12 5.62 4.50 12.3

200 4460A30G01 0.3 0.3 0.3 – 2.50 C30 4.0 3.0 7.12 5.62 4.50 12.3

400 4460A30G03 0.3 0.3 0.3 – 3.06 C30 4.0 3.0 7.12 5.62 4.50 8.5

500 4460A30G05 0.3 0.3 0.3 – 3.06 C30 3.0 2.2 7.12 5.62 4.50 8.5

600 4460A30G07 0.3 0.3 0.3 – 3.06 C30 2.0 1.5 7.12 5.62 4.50 8.5

800 4460A30G09 0.3 0.3 0.3 – 3.06 C20 2.0 1.5 7.12 5.62 4.50 8.3

1000 4460A30G21 0.3 0.3 0.3 – 3.06 C30 2.0 1.5 7.12 5.62 4.50 8.3

1200 4460A30G19 0.3 0.3 0.3 0.3 3.06 C30 1.5 1.2 7.12 5.62 4.50 8.3

200/400 4460A30G11 0.3/0.3 0.3/0.3 0.3/0.3 – 2.50 C30/C50 4.0/2.0 3.0/1.5 7.12 5.62 4.50 12.4

300/600 4460A30G13 0.3/0.3 0.3/0.3 0.3/0.3 – 3.06 C20/C50 3.0/2.0 2.2/1.5 7.12 5.62 4.50 9.7

400/800 4460A30G15 0.3/0.3 0.3/0.3 0.3/0.3 – 3.06 C20/C50 2.0/2.0 1.5/1.5 7.12 5.62 4.50 8.7

Rating Factor

1VAP428182-DB and 1VAP428181-DB

Rating Factor

600 V Current Transformers

IEEE Metering Accuracy*

TYPES CMF-S and CMF600 Volts Indoor/outdoor 10 kV BIL25-60 Hertz

With window and flat base

Conduit box available

With window and high base

IEEE Metering Accuracy*

* Stated accuracies are applicable for 60 Hz

Primary Amps

Style

NumberIEEE Metering

AccuracyBase type

Window Diam. (in.)

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A497G01 0.15SB-0.5 Flat 3.06 2.0* 1.5 7.12 5.62 4.50 8.5

600 923A497G02 0.15SB-0.5 High 3.06 2.0* 1.5 7.91 5.25 4.50 8.5

600 923A517G01 0.15SB-0.5 Flat With bar 2.0* 1.5 7.91 5.25 11.88 10.5

600 923A517G02 0.15SB-0.5 High With bar 2.0* 1.5 7.91 5.25 11.88 10.5

Rating Factor

TYPE CMF-S

The CMF-S is part of ABB's AccuRange™ current transformer portfolio of products.

TYPE CMF

TYPE CMF

*RF = 3.0 for 0.15S B-0.2

20 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 21

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

100 7525A01G26 0.3 – – – 2.50 C10 4.0 3.0 7.91 5.25 11.88 14.3

200 7525A01G02 0.3 0.3 0.3 – 2.50 C30 4.0 3.0 7.91 5.25 11.88 14.3

400 7525A01G04 0.3 0.3 0.3 – 3.06 C30 4.0 3.0 7.91 5.25 11.88 12.5

500 7525A01G06 0.3 0.3 0.3 – 3.06 C30 3.0 2.2 7.91 5.25 11.88 12.5

600 7525A01G08 0.3 0.3 0.3 – 3.06 C30 2.0 1.5 7.91 5.25 11.88 12.5

800 7525A01G10 0.3 0.3 0.3 – 3.06 C20 2.0 1.5 7.91 5.25 11.88 12.3

1000 7525A01G24 0.3 0.3 0.3 – 3.06 C30 2.0 1.5 7.91 5.25 11.88 12.3

1200 7525A01G20 0.3 0.3 0.3 0.3 3.06 C30 1.5 1.2 7.91 5.25 11.88 12.3

200/400 7525A01G12 0.3/0.3 0.3/0.3 0.3/0.3 – 2.50 C30/C50 4.0/2.0 3.0/1.5 7.91 5.25 11.88 14.4

300/600 7525A01G14 0.3/0.3 0.3/0.3 0.3/0.3 – 3.06 C20/C50 3.0/2.0 2.2/1.5 7.91 5.25 11.88 13.7

400/800 7525A01G16 0.3/0.3 0.3/0.3 0.3/0.3 – 3.06 C20/C50 2.0/2.0 1.5/1.5 7.91 5.25 11.88 12.7

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

100 7525A01G25 0.3 – – – 2.50 C10 4.0 3.0 7.12 5.62 11.88 14.3

200 7525A01G01 0.3 0.3 0.3 – 2.50 C30 4.0 3.0 7.12 5.62 11.88 14.3

400 7525A01G03 0.3 0.3 0.3 – 3.06 C30 4.0 3.0 7.12 5.62 11.88 12.5

500 7525A01G05 0.3 0.3 0.3 – 3.06 C30 3.0 2.2 7.12 5.62 11.88 12.5

600 7525A01G07 0.3 0.3 0.3 – 3.06 C30 2.0 1.5 7.12 5.62 11.88 12.5

800 7525A01G09 0.3 0.3 0.3 – 3.06 C20 2.0 1.5 7.12 5.62 11.88 12.3

1000 7525A01G23 0.3 0.3 0.3 – 3.06 C30 2.0 1.5 7.12 5.62 11.88 12.3

1200 7525A01G19 0.3 0.3 0.3 0.3 3.06 C30 1.5 1.2 7.12 5.62 11.88 12.3

200/400 7525A01G11 0.3/0.3 0.3/0.3 0.3/0.3 – 2.50 C30/C50 4.0/2.0 3.0/1.5 7.12 5.62 11.88 14.4

300/600 7525A01G13 0.3/0.3 0.3/0.3 0.3/0.3 – 3.06 C20/C50 3.0/2.0 2.2/1.5 7.12 5.62 11.88 13.7

400/800 7525A01G15 0.3/0.3 0.3/0.3 0.3/0.3 – 3.06 C20/C50 2.0/2.0 1.5/1.5 7.12 5.62 11.88 12.7

Rating Factor

1VAP428181-DB

1.000

.750

.501.000.750

Ø.563 HOLE(2 TOTAL) R.281

10.87511.875

.500

PrimaryAmps A

A

B

B0.25"0.38"

2.0"2.5"

50 - 200> 200

Bus bar dimensions (in)

Rating FactorIEEE Metering Accuracy*

600 V Current Transformers

IEEE Metering Accuracy*

TYPE CMF (cont’d)600 Volts Indoor/outdoor 10 kV BIL25-60 HertzWith primary bar

With primary bar and high base

Conduit box available

With primary bar and flat base

* Stated accuracies are applicable for 60 Hz

22 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 23

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

100 7524A75G17 1.2 – – – – 3.5 x 4.5 – 4.0 3.0 9.17 6.00 2.19 6.0

200 7524A75G01 0.3 – – – – 3.5 x 4.5 C20 4.0 3.0 9.17 6.00 2.19 6.0

300 7524A75G02 0.3 0.3 – – – 3.5 x 4.5 C20 4.0 3.0 9.17 6.00 2.19 6.0

400 7524A75G03 0.3 0.3 – – – 3.5 x 4.5 C20 4.0 3.0 9.17 6.00 2.19 6.0

500 7524A75G12 0.3 0.3 0.3 – – 3.5 x 4.5 C20 3.0 2.2 9.17 6.00 2.19 6.0

600 7524A75G04 0.3 0.3 0.3 – – 3.5 x 4.5 C20 3.0 2.2 9.17 6.00 2.19 6.0

800 7524A75G05 0.3 0.3 0.3 – – 3.5 x 4.5 C20 3.0 2.2 9.17 6.00 2.19 6.0

1000 7524A75G06 0.3 0.3 0.3 – – 3.5 x 4.5 C30 2.0 1.5 9.17 6.00 2.19 6.0

1200 7524A75G07 0.3 0.3 0.3 0.3 – 3.5 x 4.5 C40 2.0 1.5 9.17 6.00 2.19 6.0

1500 7524A75G08 0.3 0.3 0.3 0.3 – 3.5 x 4.5 C50 2.0 1.5 9.17 6.00 2.19 6.0

2000 7524A75G09 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C50 1.5 1.2 9.17 6.00 2.19 6.0

3000 7524A75G10 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C30 1.33 1.0 9.17 6.00 2.19 6.0

4000 7524A75G11 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C20 1.0 0.75 9.17 6.00 2.19 6.0

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

100 7524A73G17 1.2 – – – – 3.5 x 4.5 – 4.0 3.0 8.75 6.00 2.19 6.5

200 7524A73G01 0.3 – – – – 3.5 x 4.5 C20 4.0 3.0 8.75 6.00 2.19 6.5

300 7524A73G02 0.3 0.3 – – – 3.5 x 4.5 C20 4.0 3.0 8.75 6.00 2.19 6.5

400 7524A73G03 0.3 0.3 – – – 3.5 x 4.5 C20 4.0 3.0 8.75 6.00 2.19 6.5

500 7524A73G12 0.3 0.3 0.3 – – 3.5 x 4.5 C20 3.0 2.2 8.75 6.00 2.19 6.5

600 7524A73G04 0.3 0.3 0.3 – – 3.5 x 4.5 C20 3.0 2.2 8.75 6.00 2.19 6.5

800 7524A73G05 0.3 0.3 0.3 – – 3.5 x 4.5 C20 3.0 2.2 8.75 6.00 2.19 6.5

1000 7524A73G06 0.3 0.3 0.3 – – 3.5 x 4.5 C30 2.0 1.5 8.75 6.00 2.19 6.5

1200 7524A73G07 0.3 0.3 0.3 0.3 – 3.5 x 4.5 C40 2.0 1.5 8.75 6.00 2.19 6.5

1500 7524A73G08 0.3 0.3 0.3 0.3 – 3.5 x 4.5 C50 2.0 1.5 8.75 6.00 2.19 6.5

2000 7524A73G09 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C50 1.5 1.2 8.75 6.00 2.19 6.5

3000 7524A73G10 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C30 1.33 1.0 8.75 6.00 2.19 6.5

4000 7524A73G11 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C20 1.0 0.75 8.75 6.00 2.19 6.5

1VAP428202-DB and 1VAP428201-DB

Optional accessories for tapered bottom styles:Bus bar adapter (picture below): 9628A05G17 (supplied with style 7524A75GXX and 923A231GXX; to order without, use style 7524A76GXX)

Optional accessories for wide bottom styles:Mounting feet (kit of 4) : 9628A05G15One-piece base: 9628A05G16

Optional bus bar accessory: (ordering information above)Bus bar adapter fits the following bus bar sizes: 1/4", 3/8"+ 1/2"+

Rating Factor

Rating Factor

TYPES CMV-S and CMV600 Volts Indoor/Outdoor 10 kV BIL25-60 Hertz

Tapered bottom

600 V Current Transformers

Wide bottom

* Stated accuracies are applicable for 60 Hz

IEEE Metering Accuracy*

IEEE Metering Accuracy*

Primary Amps

Style

NumberIEEE

Metering Accuracy

Window Diam. (in.)

Rating Factor@ 85°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

1000 923A498G02 0.15SB-0.5 3.5 x 4.5 2.0 9.17 6.00 2.19 6.0

(tapered bottom) 2000 923A498G03 0.15SB-0.5 3.5 x 4.5 2.0 9.17 6.00 2.19 6.0

TYPE CMV-S

The CMV-S is part of ABB's AccuRange™ current transformer portfolio of products.

TYPE CMV

TYPE CMV

24 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 25

1VAP428201-DB

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

Rating Factor

@ 85°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

200 923A231G01 0.3 – – – – 3.5 x 4.5 C20 4.0 9.17 6.00 2.19 6.0

300 923A231G02 0.3 0.3 – – – 3.5 x 4.5 C20 4.0 9.17 6.00 2.19 6.0

400 923A231G03 0.3 0.3 – – – 3.5 x 4.5 C20 4.0 9.17 6.00 2.19 6.0

600 923A231G04 0.3 0.3 0.3 – – 3.5 x 4.5 C20 3.0 9.17 6.00 2.19 6.0

800 923A231G05 0.3 0.3 0.3 – – 3.5 x 4.5 C20 3.0 9.17 6.00 2.19 6.0

1000 923A231G06 0.3 0.3 0.3 – – 3.5 x 4.5 C30 2.0 9.17 6.00 2.19 6.0

1200 923A231G07 0.3 0.3 0.3 0.3 – 3.5 x 4.5 C40 2.0 9.17 6.00 2.19 6.0

1500 923A231G08 0.3 0.3 0.3 0.3 – 3.5 x 4.5 C50 2.0 9.17 6.00 2.19 6.0

2000 923A231G09 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C20 1.5 9.17 6.00 2.19 6.0

3000 923A231G10 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C30 1.33 9.17 6.00 2.19 6.0

4000 923A231G11 0.3 0.3 0.3 0.3 0.3 3.5 x 4.5 C20 1.0 9.17 6.00 2.19 6.0

Optional accessories for tapered bottom styles:Bus bar adapter (pictured below) 9628A05G17(supplied with style 7524A75GXX and 923A231GXX; to order without, use style 7524A76GXX)

Optional bus bar accessory:Bus bar adapter fits the following bus bar sizes:1/4", 3/8"+ 1/2"+

+ with modification

600 Volts Indoor/outdoor 10 kV BIL25-60 Hertz

This CT is designed for high temperature environments. Refer to product bulletin for details.

TYPE CMV-Hi Temp

Tapered bottom

IEEE Metering Accuracy*

600 V Current Transformers

* Stated accuracies are applicable for 60 Hz

26 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 27

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 7524A58G21 0.3 0.3 – – – 5.50 C20 3.0 2.2 9.75 8.25 2.63 11.0

500 7524A58G19 0.3 0.3 0.3 – – 5.50 – 4.0 3.0 9.75 8.25 2.63 11.0

600 7524A58G16 0.3 0.3 0.3 – – 5.50 C30 3.0 2.2 9.75 8.25 2.63 11.0

800 7524A58G01 0.3 0.3 0.3 – – 5.50 C30 2.0 1.5 9.75 8.25 2.63 11.0

1000 7524A58G02 0.3 0.3 0.3 – – 5.50 C50 2.0 1.5 9.75 8.25 2.63 11.0

1200 7524A58G03 0.3 0.3 0.3 0.3 – 5.50 C30 2.0 1.5 9.75 8.25 2.63 11.0

1500 7524A58G04 0.3 0.3 0.3 0.3 – 5.50 C30 3.0 2.2 9.75 8.25 2.63 11.0

2000 7524A58G05 0.3 0.3 0.3 0.3 0.3 5.50 C50 2.0 1.5 9.75 8.25 2.63 11.0

3000 7524A58G06 0.3 0.3 0.3 0.3 0.3 5.50 C10 1.5 1.2 9.75 8.25 2.63 11.0

4000 7524A58G07 0.3 0.3 0.3 0.3 0.3 5.50 – 1.33 1.0 9.75 8.25 2.63 11.0

600/1200 7524A58G080.3 0.3 – – –

+ 5.50C10 3.0 2.2

9.75 8.25 2.63 11.00.3 0.3 0.3 0.3 – C30 2.0 1.5

800/1600 7524A58G090.3 0.3 – – –

+ 5.50C30 3.0 2.2

9.75 8.25 2.63 11.00.3 0.3 0.3 0.3 0.3 C60 2.0 1.5

1000/2000 7524A58G100.3 0.3 0.3 – –

+ 5.50C30 3.0 2.2

9.75 8.25 2.63 11.00.3 0.3 0.3 0.3 0.3 C50 2.0 1.5

1500/3000 7524A58G110.3 0.3 0.3 0.3 –

+ 5.50– 2.0 1.5

9.75 8.25 2.63 11.00.3 0.3 0.3 0.3 0.3 C10 1.5 1.2

2000/4000 7524A58G120.3 0.3 0.3 0.3 0.3

+ 5.50– 2.0 1.5

9.75 8.25 2.63 11.00.3 0.3 0.3 0.3 0.3 – 1.33 1.0

Rating Factor

1VAP428241-DB

Optional accessories:Mounting feet,set of four with hardware 9628A05G20One-piece base 9628A05G21Window plate (one required) 9628A05G22Primary bar assemblies:800-1500 amps 1 bar 9628A05G232000 amps 2 bars 9628A05G243000 amps 3 bars 9628A05G254000 amps 4 bars 9628A05G26UL Recognized Component

TYPE CLC600 Volts Indoor/outdoor 10 kV BIL25-60 Hertz

Without hardware

IEEE Metering Accuracy*

600 V Current Transformers

+ Tap Connection X2-X3

* Stated accuracies are applicable for 60 Hz

28 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 29

1VAP428241-DB

Optional accessories:Mounting feet,set of four with hardware 9628A05G20One-piece base 9628A05G21Window plate (one required) 9628A05G22Primary bar assemblies:800-1500 amps 1 bar 9628A05G232000 amps 2 bars 9628A05G243000 amps 3 bars 9628A05G254000 amps 4 bars 9628A05G26

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 7524A59G16 0.3 0.3 0.3 – – 5.50 C30 3.0 2.2 9.88 8.25 6.37 11.5

800 7524A59G01 0.3 0.3 0.3 – – 5.50 C30 2.0 1.5 9.88 8.25 6.37 11.5

1000 7524A59G02 0.3 0.3 0.3 – – 5.50 C50 2.0 1.5 9.88 8.25 6.37 11.5

1200 7524A59G03 0.3 0.3 0.3 0.3 – 5.50 C30 2.0 1.5 9.88 8.25 6.37 11.5

1500 7524A59G04 0.3 0.3 0.3 0.3 – 5.50 C30 3.0 2.2 9.88 8.25 6.37 11.5

2000 7524A59G05 0.3 0.3 0.3 0.3 0.3 5.50 C50 2.0 1.5 9.88 8.25 6.37 11.5

3000 7524A59G06 0.3 0.3 0.3 0.3 0.3 5.50 C10 1.5 1.2 9.88 8.25 6.37 11.5

4000 7524A59G07 0.3 0.3 0.3 0.3 0.3 5.50 – 1.33 1.0 9.88 8.25 6.37 11.5

600/1200 7524A59G080.3 0.3 – – –

+ 5.50C10 3.0 2.2

9.88 8.25 6.37 11.50.3 0.3 0.3 0.3 – C30 2.0 1.5

800/1600 7524A59G090.3 0.3 – – –

+ 5.50C30 3.0 2.2

9.88 8.25 6.37 11.50.3 0.3 0.3 0.3 0.3 C60 2.0 1.5

1000/2000 7524A59G100.3 0.3 0.3 – –

+ 5.50C30 3.0 2.2

9.88 8.25 6.37 11.50.3 0.3 0.3 0.3 0.3 C50 2.0 1.5

1500/3000 7524A59G110.3 0.3 0.3 0.3 –

+ 5.50– 2.0 1.5

9.88 8.25 6.37 11.50.3 0.3 0.3 0.3 0.3 C10 1.5 1.2

2000/4000 7524A59G120.3 0.3 0.3 0.3 0.3

+ 5.50– 2.0 1.5

9.88 8.25 6.37 11.50.3 0.3 0.3 0.3 0.3 – 1.33 1.0

Rating Factor

UL Recognized Component

TYPE CLC (cont’d)600 Volts Indoor/outdoor 10 kV BIL25-60 Hertz

600 V Current Transformers

Withmounting feet (4-piece)

+ Tap Connection X2-X3

* Stated accuracies are applicable for 60 Hz

IEEE Metering Accuracy*

30 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 31

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 7524A60G18 0.3 0.3 – – – 5.50 C30 3.0 2.2 9.88 10.50 2.62 11.0

500 7524A60G19 0.3 0.3 0.3 – – 5.50 - 4.0 3.0 9.88 10.50 2.62 11.0

600 7524A60G16 0.3 0.3 0.3 – – 5.50 C30 3.0 2.2 9.88 10.50 2.62 11.0

800 7524A60G01 0.3 0.3 0.3 – – 5.50 C30 2.0 1.5 9.88 10.50 2.62 11.0

1000 7524A60G02 0.3 0.3 0.3 – – 5.50 C50 2.0 1.5 9.88 10.50 2.62 11.0

1200 7524A60G03 0.3 0.3 0.3 0.3 – 5.50 C30 2.0 1.5 9.88 10.50 2.62 11.0

1500 7524A60G04 0.3 0.3 0.3 0.3 – 5.50 C30 3.0 2.2 9.88 10.50 2.62 11.0

2000 7524A60G05 0.3 0.3 0.3 0.3 0.3 5.50 C50 2.0 1.5 9.88 10.50 2.62 11.0

3000 7524A60G06 0.3 0.3 0.3 0.3 0.3 5.50 C10 1.5 1.2 9.88 10.50 2.62 11.0

4000 7524A60G07 0.3 0.3 0.3 0.3 0.3 5.50 – 1.33 1.0 9.88 10.50 2.62 11.0

600/1200 7524A60G080.3 0.3 – – –

+ 5.50C10 3.0 2.2

9.88 10.50 2.62 11.00.3 0.3 0.3 0.3 – C30 2.0 1.5

800/1600 7524A60G090.3 0.3 – – –

+ 5.50C30 3.0 2.2

9.88 10.50 2.62 11.00.3 0.3 0.3 0.3 0.3 C60 2.0 1.5

1000/2000 7524A60G100.3 0.3 0.3 – –

+ 5.50C30 3.0 2.2

9.88 10.50 2.62 11.00.3 0.3 0.3 0.3 0.3 C50 2.0 1.5

1500/3000 7524A60G110.3 0.3 0.3 0.3 –

+ 5.50– 2.0 1.5

9.88 10.50 2.62 11.00.3 0.3 0.3 0.3 0.3 C10 1.5 1.2

2000/4000 7524A60G120.3 0.3 0.3 0.3 0.3

+ 5.50– 2.0 1.5

9.88 10.50 2.62 11.00.3 0.3 0.3 0.3 0.3 – 1.33 1.0

Rating Factor

1VAP428241-DB

Optional accessories:Mounting feet-set of four with hardware 9628A05G20One-piece base 9628A05G21Window plate (one required) 9628A05G22Primary bar assemblies:800-1500 amps 1 bar 9628A05G232000 amps 2 bars 9628A05G243000 amps 3 bars 9628A05G254000 amps 4 bars 9628A05G26

TYPE CLC (cont'd)600 Volts Indoor/outdoor 10 kV BIL25-60 Hertz

With one piece base

IEEE Metering Accuracy*

600 V Current Transformers

UL Recognized Component

+ Tap Connection X2-X3

* Stated accuracies are applicable for 60 Hz

32 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 33

1VAP428241-DB

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 7524A61G18 0.3 0.3 – – – 5.50 C20 3.0 2.2 9.75 8.25 2.88 11.5

600 7524A61G16 0.3 0.3 0.3 – – 5.50 C30 3.0 2.2 9.75 8.25 2.88 11.5

800 7524A61G01 0.3 0.3 0.3 – – 5.50 C30 2.0 1.5 9.75 8.25 2.88 11.5

1000 7524A61G02 0.3 0.3 0.3 – – 5.50 C50 2.0 1.5 9.75 8.25 2.88 11.5

1200 7524A61G03 0.3 0.3 0.3 0.3 – 5.50 C30 2.0 1.5 9.75 8.25 2.88 11.5

1500 7524A61G04 0.3 0.3 0.3 0.3 – 5.50 C30 3.0 2.2 9.75 8.25 2.88 11.5

2000 7524A61G05 0.3 0.3 0.3 0.3 0.3 5.50 C50 2.0 1.5 9.75 8.25 2.88 11.5

3000 7524A61G06 0.3 0.3 0.3 0.3 0.3 5.50 C10 1.5 1.2 9.75 8.25 2.88 11.5

4000 7524A61G07 0.3 0.3 0.3 0.3 0.3 5.50 – 1.33 1.0 9.75 8.25 2.88 11.5

600/1200 7524A61G080.3 0.3 – – –

+ 5.50C10 3.0 2.2

9.75 8.25 2.88 11.50.3 0.3 0.3 0.3 – C30 2.0 1.5

800/1600 7524A61G090.3 0.3 – – –

+ 5.50C30 3.0 2.2

9.75 8.25 2.88 11.50.3 0.3 0.3 0.3 0.3 C60 2.0 1.5

1000/2000 7524A61G100.3 0.3 0.3 – –

+ 5.50C30 3.0 2.2

9.75 8.25 2.88 11.50.3 0.3 0.3 0.3 0.3 C50 2.0 1.5

1500/3000 7524A61G110.3 0.3 0.3 0.3 –

+ 5.50– 2.0 1.5

9.75 8.25 2.88 11.50.3 0.3 0.3 0.3 0.3 C10 1.5 1.2

2000/4000 7524A61G120.3 0.3 0.3 0.3 0.3

+ 5.50– 2.0 1.5

9.75 8.25 2.88 11.50.3 0.3 0.3 0.3 0.3 – 1.33 1.0

Optional accessories:Mounting feet-set of four with hardware 9628A05G20One-piece base 9628A05G21Window plate (one required) 9628A05G22Primary bar assemblies:800-1500 amps 1 bar 9628A05G232000 amps 2 bars 9628A05G243000 amps 3 bars 9628A05G254000 amps 4 bars 9628A05G26

Rating Factor

TYPE CLC (cont'd)600 Volts Indoor/outdoor 10 kV BIL25-60 Hertz

600 V Current Transformers

UL Recognized Component

With window plate

+ Tap Connection X2-X3

* Stated accuracies are applicable for 60 Hz

IEEE Metering Accuracy*

34 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 35

Primary Amps

Style Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Number of bars

Relay* Accuracy 30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 7526A85G16 0.3 0.3 0.3 – – 1 – 3.0 2.2 9.75 8.25 2.62 15

800 7526A85G01 0.3 0.3 0.3 – – 1 – 2.0 1.5 9.75 8.25 2.62 15

1000 7526A85G02 0.3 0.3 0.3 – – 1 – 2.0 1.5 9.75 8.25 2.62 15

1200 7526A85G03 0.3 0.3 0.3 0.3 – 2 – 2.0 1.5 9.75 8.25 2.62 15

1200 7526A85G17 0.3 0.3 0.3 0.3 0.3 2 – 2.0 1.5 9.75 8.25 2.62 15

1500 7526A85G04 0.3 0.3 0.3 0.3 – 4 – 3.0 2.2 9.75 8.25 2.62 15

2000 7526A85G05 0.3 0.3 0.3 0.3 0.3 3 – 2.0 1.5 9.75 8.25 2.62 15

3000 7526A85G06 0.3 0.3 0.3 0.3 0.3 4 – 1.5 1.2 9.75 8.25 2.62 15

4000 7526A85G07 0.3 0.3 0.3 0.3 0.3 4 – 1.25 1.0 9.75 8.25 2.62 15

600/1200 7526A85G080.3 0.3 0.3 0.3 –

2–

3.0/2.0 2.2/1.5 9.75 8.25 2.62 150.3 0.3 – – – –

800/1600 7526A85G090.3 0.3 0.3 0.3 0.3

2–

3.0/2.0 2.2/1.5 9.75 8.25 2.62 150.3 0.3 – – – –

1000/2000 7526A85G100.3 0.3 0.3 0.3 0.3

3–

3.0/2.0 2.2/1.5 9.75 8.25 2.62 150.3 0.3 0.3 – – –

1500/3000 7526A85G110.3 0.3 0.3 0.3 0.3

4–

2.0/1.5 1.5/1.2 9.75 8.25 2.62 150.3 0.3 0.3 0.3 – –

2000/4000 7526A85G120.3 0.3 0.3 0.3 0.3

4–

2.0/1.25 1.5/0.9 9.75 8.25 2.62 150.3 0.3 0.3 0.3 0.3 –

4.00

1.75

4.25

11.75

14.50

1.75

.250 THICK BAR Ø.563 HOLES8-TOTAL

Ø.281 HOLES4-TOTAL

Bar assemblies

Bars used are .250" thick by 4" wide. On multi-bar assemblies, there is .250" spacing between bars. Assembly can be mounted with bars horizontal or vertical.

Rating Factor

TYPE CLC (cont'd)600 Volts Indoor/outdoor 10 kV BIL25-60 HertzBar-type

IEEE Metering Accuracy*

600 V Current Transformers

UL Recognized Component

* Stated accuracies are applicable for 60 Hz

1VAP428241-DB

36 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 37

2.12[54]

Primary Amps

Style

Number Metering* Relay

WindowDiam. (in.)

Rating Factor

@ 30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

200 A0302S08-570 0.6B-0.1 C5 5.75 2.0 10.25 8.50 2.12 14-15

300 A0303S08-570 0.3B-0.1 C10 5.75 2.0 10.25 8.50 2.12 14-15

400 A0304S08-570 0.3B-0.2 C15 5.75 2.0 10.25 8.50 2.12 14-15

500 A0305S08-570 0.3B-0.5 C20 5.75 2.0 10.25 8.50 2.12 14-15

600 A0306S08-570 0.3B-0.5 C25 5.75 2.0 10.25 8.50 2.12 14-15

800 A0308S08-570 0.3B-0.9 C30 5.75 2.0 10.25 8.50 2.12 14-15

1000 A0310S08-570 0.3B-0.9 C30 5.75 2.0 10.25 8.50 2.12 14-15

1200 A0312S08-570 0.3B-0.9 C40 5.75 2.0 10.25 8.50 2.12 14-15

1500 A0315S08-570 0.3B-1.8 C30 5.75 2.0 10.25 8.50 2.12 14-15

2000 A0320S08-570 0.3B-1.8 C40 5.75 2.0 10.25 8.50 2.12 14-15

2500 A0325S08-570 0.3B-1.8 C30 5.75 1.5 10.25 8.50 2.12 14-15

3000 A0330S08-570 0.3B-1.8 C40 5.75 1.5 10.25 8.50 2.12 14-15

4000 A0340S08-570 0.3B-1.8 C50 5.75 1.0 10.25 8.50 2.12 14-15

600 V Current Transformers

TYPE DEH-705600 Volts Indoor/outdoor 10 kV BIL60 Hertz

Thermal rise:55°C @ 30°C ambient

Accuracy/Burden

Available in dual and multi-ratio designs

One second thermal/mechanical ratings: 80 x full winding Inom / unlimited mechanical.

Units available with mounting feet. Change “08” of style number to “18”

* Units can be certified for revenue metering. Change “570" of style number to “590”

Higher accuracies available in some ratings. Contact the factory.

1VAP701011-DB

38 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 39

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2000 7524A64G01 0.3 0.3 0.3 0.3 – 8.25 C50 2.0 1.5 13.00 11.38 6.37 17.0

3000 7524A64G02 0.3 0.3 0.3 0.3 1.8 8.25 C100 2.0 1.5 13.00 11.38 6.37 17.0

4000 7524A64G03 0.3 0.3 0.3 0.3 0.3 8.25 C100 1.5 1.2 13.00 11.38 6.37 17.0

5000 7524A64G04 0.3 0.3 0.3 0.3 0.3 8.25 C100 1.33 1.0 13.00 11.38 6.37 17.0

6000 7524A64G05 0.3 0.3 0.3 0.3 0.3 8.25 – 1.0 0.75 13.00 11.38 6.37 17.0

1000/2000 7524A64G060.3 0.3 0.3 – –

+ 8.25C30 3.0 2.2

13.00 11.38 6.37 17.00.3 0.3 0.3 0.3 – C50 2.0 1.5

1500/3000 7524A64G070.3 0.3 0.3 – –

+ 8.25C50 3.0 2.2

13.00 11.38 6.37 17.00.3 0.3 0.3 0.3 0.3 C100 2.0 1.5

2000/4000 7524A64G080.3 0.3 0.3 0.3 –

+ 8.25C50 2.0 1.5

13.00 11.38 6.37 17.00.3 0.3 0.3 0.3 0.3 C100 1.5 1.2

2500/5000 7524A64G090.3 0.3 0.3 0.3 0.3

+ 8.25C100 2.0 1.5

13.00 11.38 6.37 17.00.3 0.3 0.3 0.3 0.3 C200 1.33 1.0

3000/6000 7524A64G100.3 0.3 0.3 0.3 0.3

+ 8.25– 1.33 1.0

13.00 11.38 6.37 17.00.3 0.3 0.3 0.3 0.3 – 1.0 0.75

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2000 7524A63G01 0.3 0.3 0.3 0.3 – 8.25 C50 2.0 1.5 12.88 11.38 2.63 16.0

3000 7524A63G02 0.3 0.3 0.3 0.3 0.3 8.25 C100 2.0 1.5 12.88 11.38 2.63 16.0

4000 7524A63G03 0.3 0.3 0.3 0.3 0.3 8.25 C100 1.5 1.2 12.88 11.38 2.63 16.0

5000 7524A63G04 0.3 0.3 0.3 0.3 0.3 8.25 C100 1.33 1.0 12.88 11.38 2.63 16.0

6000 7524A63G05 0.3 0.3 0.3 0.3 0.3 8.25 – 1.0 0.75 12.88 11.38 2.63 16.0

1000/2000 7524A63G060.3 0.3 0.3 – –

+ 8.25C30 3.0 2.2

12.88 11.38 2.63 16.00.3 0.3 0.3 0.3 – C50 2.0 1.5

1500/3000 7524A63G070.3 0.3 0.3 – –

+ 8.25C50 3.0 2.2

12.88 11.38 2.63 16.00.3 0.3 0.3 0.3 0.3 C100 2.0 1.5

2000/4000 7524A63G080.3 0.3 0.3 0.3 –

+ 8.25C50 2.0 1.5

12.88 11.38 2.63 16.00.3 0.3 0.3 0.3 0.3 C100 1.5 1.2

2500/5000 7524A63G090.3 0.3 0.3 0.3 0.3

+ 8.25C100 2.0 1.5

12.88 11.38 2.63 16.00.3 0.3 0.3 0.3 0.3 C200 1.33 1.0

3000/6000 7524A63G100.3 0.3 0.3 0.3 0.3

+ 8.25– 1.33 1.0

12.88 11.38 2.63 16.00.3 0.3 0.3 0.3 0.3 – 1.0 0.75

Rating Factor

Optional accessories:Mounting feet (set of 2 with hardware) 9628A05G27Window plates (set of 2 with hardware) 9628A05G28

1VAP428261-DB

TYPE CLE600 Volts Indoor/outdoor 10 kV BIL25-400 Hertz

IEEE Metering Accuracy*

600 V Current Transformers

Without mounting feet

With mounting feet(2-piece)

+ Tap connection X2-X3

UL Recognized Component

IEEE Metering Accuracy*

* Stated accuracies are applicable for 60 Hz

40 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 41

1VAP701031-DB

NAMEPLATE3.00

[75.00]

YYYY:5 XXXX:5

Primary Amps

Style

Number Metering* Relay

WindowDiam. (in.)

Rating Factor

@ 30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

100 A0101S08-570 ±10% - 1VA – 8.13 2.0 13.0 11.0 3.0 18-20

200 A0102S08-570 1.2B-0.1 – 8.13 2.0 13.0 11.0 3.0 18-20

300 A0103S08-570 0.6B-0.1 C5 8.13 2.0 13.0 11.0 3.0 18-20

400 A0104S08-570 0.3B-0.1 C10 8.13 2.0 13.0 11.0 3.0 18-20

500 A0105S08-570 0.3B-0.2 C15 8.13 2.0 13.0 11.0 3.0 18-20

600 A0106S08-570 0.3B-0.2 C15 8.13 2.0 13.0 11.0 3.0 18-20

800 A0108S08-570 0.3B-0.5 C20 8.13 2.0 13.0 11.0 3.0 18-20

1000 A0110S08-570 0.3B-0.5 C30 8.13 2.0 13.0 11.0 3.0 18-20

1200 A0112S08-570 0.3B-0.9 C40 8.13 2.0 13.0 11.0 3.0 18-20

1500 A0115S08-570 0.3B-0.9 C50 8.13 2.0 13.0 11.0 3.0 18-20

1600 A0116S08-570 0.3B-0.9 C50 8.13 2.0 13.0 11.0 3.0 18-20

2000 A0120S08-570 0.3B-1.8 C35 8.13 2.0 13.0 11.0 3.0 18-20

2500 A0125S08-570 0.3B-1.8 C40 8.13 1.5 13.0 11.0 3.0 18-20

3000 A0130S08-570 0.3B-1.8 C50 8.13 1.33 13.0 11.0 3.0 18-20

4000 A0140S08-570 0.3B-1.8 C50 8.13 1.0 13.0 11.0 3.0 18-20

5000 A0150S08-570 0.3B-1.8 – 8.13 1.0 13.0 11.0 3.0 18-20

6000 A0160S08-570 0.3B-1.8 – 8.13 1.0 13.0 11.0 3.0 18-20

600 V Current Transformers

TYPE CEH-636600 Volts Indoor/outdoor 10 kV BIL60 Hertz

Thermal rise:55°C @ 30°C ambient

Accuracy/Burden

Available in dual and multi-ratio designs

One second thermal/mechanical ratings: 60 x full winding Inom / unlimited mechanical.

Units available with mounting feet. Change “08” of style number to “18”

* Units can be certified for revenue metering. Change "570" of style number to "590"

42 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 43

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

500 7524A52G23 0.3 0.3 0.3 – – 5.5 C50 2.0 1.5 11.25 10.50 4.12 21.0

600 7524A52G17 0.3 0.3 0.3 – – 5.5 C100 2.0 1.5 11.25 10.50 4.12 21.0

750 7524A52G01 0.3 0.3 0.3 – – 5.5 C100 2.0 1.5 11.25 10.50 4.12 21.0

800 7524A52G02 0.3 0.3 0.3 0.3 – 5.5 C100 2.0 1.5 11.25 10.50 4.12 21.0

900 7524A52G03 0.3 0.3 0.3 0.3 – 5.5 C100 2.0 1.5 11.25 10.50 4.12 21.0

1000 7524A52G04 0.3 0.3 0.3 0.3 – 5.5 C100 2.0 1.5 11.25 10.50 4.12 21.0

1200 7524A52G05 0.3 0.3 0.3 0.3 0.3 5.5 C200 2.0 1.5 11.25 10.50 4.12 21.0

1500 7524A52G06 0.3 0.3 0.3 0.3 0.3 5.5 C200 2.0 1.5 11.25 10.50 4.12 21.0

2000 7524A52G07 0.3 0.3 0.3 0.3 0.3 5.5 C200 1.5 1.2 11.25 10.50 4.12 21.0

3000 7524A52G08 0.3 0.3 0.3 0.3 0.3 5.5 C200 1.33 1.0 11.25 10.50 4.12 21.0

4000 7524A52G09 0.3 0.3 0.3 0.3 0.3 5.5 C200 1.33 1.0 11.25 10.50 4.12 21.0

600/1200 7524A52G100.3 0.3 0.3 – –

+ 5.5C100 2.0 1.5

11.25 10.50 4.12 21.00.3 0.3 0.3 0.3 0.3 C200 2.0 1.5

800/1600 7524A52G110.3 0.3 0.3 – –

+ 5.5C100 2.0 1.5

11.25 10.50 4.12 21.00.3 0.3 0.3 0.3 0.3 C200 1.5 1.2

1000/2000 7524A52G120.3 0.3 0.3 0.3 –

+ 5.5C100 2.0 1.5

11.25 10.50 4.12 21.00.3 0.3 0.3 0.3 0.3 C200 1.5 1.2

1500/3000 7524A52G130.3 0.3 0.3 0.3 0.3

+ 5.5C100 1.5 1.2

11.25 10.50 4.12 21.00.3 0.3 0.3 0.3 0.3 C200 1.33 1.0

2000/4000 7524A52G140.3 0.3 0.3 0.3 0.3

+ 5.5C100 1.5 1.2

11.25 10.50 4.12 21.00.3 0.3 0.3 0.3 0.3 C200 1.33 1.0

Rating Factor

1VAP428281-DB

4.50

4.88

10.50

1.00

4.13

Ø.313 HOLE4-TOTAL

.375 x 1.250 SLOTW .750 HOLE

2-TOTAL

TYPE RLC600 Volts Indoor/outdoor 10 kV BIL25-60 HertzContact factory for bar designs

IEEE Metering Accuracy*

600 V Current Transformers

300 9625A21G10 0.3 – – – – 5.5 C100 2.0 1.5 11.25 10.50 4.12 29.0

800 9625A21G11 - - - - - 5.5 C200 2.0 1.5 11.25 10.50 4.12 29.0

1000 9625A21G01 0.3 0.3 0.3 0.3 0.3 5.5 C200 2.0 1.5 11.25 10.50 4.12 29.0

2000 9625A21G02 0.3 0.3 0.3 0.3 0.3 5.5 C400 1.5 1.2 11.25 10.50 4.12 29.0

3000 9625A21G03 0.3 0.3 0.3 0.3 0.3 5.5 C400 1.5 1.2 11.25 10.50 4.12 29.0

4000 9625A21G04 0.3 0.3 0.3 0.3 0.3 5.5 C400 1.5 1.2 11.25 10.50 4.12 29.0

1000/2000 9625A21G050.3 0.3 0.3 0.3 –

+ 5.5C200 2.0 1.5

11.25 10.50 4.12 29.00.3 0.3 0.3 0.3 0.3 C400 1.5 1.2

1500/3000 9625A21G060.3 0.3 0.3 0.3 0.3

+ 5.5C200 1.5 1.2

11.25 10.50 4.12 29.00.3 0.3 0.3 0.3 0.3 C400 1.33 1.0

2000/4000 9625A21G070.3 0.3 0.3 0.3 0.3

+ 5.5C200 1.5 1.2

11.25 10.50 4.12 29.00.3 0.3 0.3 0.3 0.3 C400 1.33 1.0

UL Recognized Component

Standard RLC

High relay accuracy RLC

+ Tap connection X2-X3

* Stated accuracies are applicable for 60 Hz

44 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 45

1VAP428281-DB

13.36

9.50

4.63

2.66

4.28

.25

Ø5.50

MOUNTING HOLESFOR .38 BOLTS4-TOTAL

NAMEPLATE

RATINGDECALBOTHSIDES

CLAMP TYPE SECONDARY TERMINALSFOR #14 TO #3 WIRE

1" STD. PIPE TAPBOTH SIDED

5.31

8.56

4.13

Rating FactorPrimary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam. (in.)

Relay* Accuracy

30°C

55°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

750 7524A54G01 0.3 0.3 0.3 – – 5.5 C100 2.0 1.5 13.36 10.50 4.12 22

800 7524A54G02 0.3 0.3 0.3 0.3 – 5.5 C100 2.0 1.5 13.36 10.50 4.12 22

900 7524A54G03 0.3 0.3 0.3 0.3 – 5.5 C100 2.0 1.5 13.36 10.50 4.12 22

1000 7524A54G04 0.3 0.3 0.3 0.3 – 5.5 C100 2.0 1.5 13.36 10.50 4.12 22

1200 7524A54G05 0.3 0.3 0.3 0.3 0.3 5.5 C200 2.0 1.5 13.36 10.50 4.12 22

1500 7524A54G06 0.3 0.3 0.3 0.3 0.3 5.5 C200 2.0 1.5 13.36 10.50 4.12 22

2000 7524A54G07 0.3 0.3 0.3 0.3 0.3 5.5 C200 1.5 1.2 13.36 10.50 4.12 22

3000 7524A54G08 0.3 0.3 0.3 0.3 0.3 5.5 C200 1.33 1.0 13.36 10.50 4.12 22

4000 7524A54G09 0.3 0.3 0.3 0.3 0.3 5.5 C200 1.33 1.0 13.36 10.50 4.12 22

600/1200 7524A54G100.3 0.3 0.3 – –

+ 5.5 C100/C200 2.0/2.0 1.5/1.5 13.36 10.50 4.12 220.3 0.3 0.3 0.3 0.3

800/1600 7524A54G110.3 0.3 0.3 – –

+ 5.5 C100/C200 2.0/1.5 1.5/1.2 13.36 10.50 4.12 220.3 0.3 0.3 0.3 0.3

1000/2000 7524A54G120.3 0.3 0.3 0.3 –

+ 5.5 C100/C200 2.0/1.5 1.5/1.2 13.36 10.50 4.12 220.3 0.3 0.3 0.3 0.3

1500/3000 7524A54G130.3 0.3 0.3 0.3 0.3

+ 5.5 C100/C200 1.5/1.33 1.2/1.0 13.36 10.50 4.12 220.3 0.3 0.3 0.3 0.3

2000/4000 7524A54G140.3 0.3 0.3 0.3 0.3

+ 5.5 C100/C200 1.5/1.33 1.2/1.0 13.36 10.50 4.12 220.3 0.3 0.3 0.3 0.3

IEEE Metering Accuracy*

TYPE RLC (cont’d)600 Volts Indoor/outdoor 10 kV BILWith junction box25-400 HertzContact factory for bar designs

600 V Current Transformers

UL Recognized Component

+ Tap connection X2-X3

Mechanical rating: 180 x normal

* Stated accuracies are applicable for 60 Hz

46 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 47

Top view into terminal box and mounting footprint

Bar detail

X1X5 X4 X3 X2

4.50

11.00 [279]

8.88 [225]

3.00[76] [114]

Ø0.56 [Ø14.3] HOLE

1.75 [44]

1.75 [44]

1.13 [28.5]

Primary Amps

Style

Number Metering Relay

WindowDiam. (in.)

Rating Factor

@ 30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

50 A49S5005010 ±5% - 2.5VA C10 5.0 4.0 13.5 9.38 4.63 45-50

100 A49S1015029 1.2B-0.1 C20 5.0 4.0 13.5 9.38 4.63 45-50

200 A49S2015049 0.6B-0.1 C40 5.0 4.0 13.5 9.38 4.63 45-50

300 A49S3015069 0.3B-0.1 C60 5.0 4.0 13.5 9.38 4.63 45-50

400 A49S4015089 0.3B-0.2 C75 5.0 4.0 13.5 9.38 4.63 45-50

500 A49S5015109 0.3B-0.5 C100 5.0 4.0 13.5 9.38 4.63 45-50

600 A49S6015109 0.3B-0.9 C100 5.0 4.0 13.5 9.38 4.63 45-50

800 A49S8015159 0.3B-1.8 C150 5.0 3.0 13.5 9.38 4.63 45-50

1000 A49S1025209 0.3B-1.8 C200 5.0 2.0 13.5 9.38 4.63 45-50

1200 A49S1225259 0.3B-1.8 C250 5.0 2.0 13.5 9.38 4.63 45-50

1500 A49S1525259 0.3B-1.8 C250 5.0 1.5 13.5 9.38 4.63 45-50

2000 A49S2025409 0.3B-1.8 C400 5.0 1.5 13.5 9.38 4.63 45-50

2500 A49S2525409 0.3B-1.8 C400 5.0 1.0 13.5 9.38 4.63 45-50

3000 A49S3025409 0.3B-1.8 C400 5.0 1.0 13.5 9.38 4.63 45-50

4000 A49S4025409 0.3B-1.8 C400 5.0 1.0 13.5 9.38 4.63 45-50

5000 A49S5025409 0.3B-1.8 C400 5.0 1.0 13.5 9.38 4.63 45-50

6000 A49S6025409 0.3B-1.8 C400 5.0 1.0 13.5 9.38 4.63 45-50

600 V Current Transformers

TYPE SCT-983600 Volts Indoor/outdoor 10 kV BIL60 Hertz

Window diameter options: SCT-983: 5.0" SCT-983C: 4.0" SCT-983A: 6.0" SCT-983D: 2.0" SCT-983B: 7.0" SCT-983E: 3.0"

Accuracy/Burden

Available in dual and multi-ratio designs.

Available with a secondary terminal box for outdoor use. Add a “T” as the last digit of style number.

IC Approval (AE-1470) is noted by bold catalog number.

One second thermal/mechanical ratings: 80 x full winding Inom / unlimited mechanical.

1VAP701051-DB

48 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 49

Primary Amps

Style

Number B-0.1

B-0.2 B-0.5 B-0.9

B-1.8

Window Diam.*

(in.)Relay

Accuracy

Rating Factor

@ 30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

200 A120200S1 – 0.3 – – – 3.5 C100 3.0 20.3 13.0 11.50 100

300 A120300S1 – – 0.3 – – 3.5 C200 3.0 20.3 13.0 11.50 100

400 A120400S1 – – – 0.3 – 3.5 C250 3.0 20.3 13.0 11.50 100

500 A120500S1 – – – – 0.3 3.5 C300 3.0 20.3 13.0 11.50 100

600 A120600S1 – – – – 0.3 3.5 C400 3.0 20.3 13.0 11.50 100

800 A120800S1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

1000 A121000S1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

1200 A121200S1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

1500 A121500S1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

2000 A122000S1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

2500 A122500S1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

3000 A123000S1 – – – – 0.3 3.5 C800 2.0 20.3 13.0 11.50 100

4000 A124000S1 – – – – 0.3 3.5 C800 1.5 20.3 13.0 11.50 100

600MR A120600M1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

1200MR A121200M1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

2000MR A122000M1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

3000MR A123000M1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

4000MR A124000M1 – – – – 0.3 3.5 C400 2.0 20.3 13.0 11.50 100

X2 X1X3X5 X4 N/P 8.25 11.505.50

10.75 [273]

13.0 [330]

[140] [210] [292]MAX

Primary Amps

Style

Number0.15/0.3 @

Burden0.15/0.3

Accuracy Range

Window Diam.*

(in.)Rating Factor

@ 30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

400 A120400X1 B-0.5/B-0.9 400/4 to 1200A 3.5 3.0 20.3 13.0 11.50 100

500 A120500X1 B-0.5/B-1.8 500/5 to 2000A 3.5 4.0 20.3 13.0 11.50 100

600 A120600X1 B-0.9/B-1.8 600/6 to 2400A 3.5 4.0 20.3 13.0 11.50 100

800 A120800X1 B-0.9/B-1.8 800/8 to 3200A 3.5 4.0 20.3 13.0 11.50 100

1000 A121000X1 B-1.8 10 to 4000A 3.5 4.0 20.3 13.0 11.50 100

1200 A121200X1 B-1.8 12 to 4800A 3.5 4.0 20.3 13.0 11.50 100

1500 A121500X1 B-1.8 15 to 4500A 3.5 3.0 20.3 13.0 11.50 100

2000 A122000X1 B-1.8 20 to 4000A 3.5 2.0 20.3 13.0 11.50 100

600 V Current Transformers

TYPE RMB(X)-644600 Volts Indoor/outdoor 10 kV BIL60 Hertz Thermal rise:55°C @ 30°C ambient

TYPE RMB-644

IEEE Metering Accuracy

Units can also be supplied with C800 ratings (add “-512” to the end of the style number)

* Additional window sizes available.

Available in dual-ratio designs (ratings same as single ratio above, change catalog digit “S” to “D”)

TYPE RMBX-644High accuracy

One second thermal/mechanical ratings: 80 x full winding Inom / unlimited mechanical.

1VAP701081-DB

50 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 51

Primary Voltage

Style Number Ratio

IEEE MeteringAccuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

115/200Y 7526A04G10 1.061:1 0.3W, 0.6X 4.56 4.50 5.00 9

120/208Y 7526A04G07 1:1 0.6W 4.56 4.50 5.00 9

240/416Y 7526A04G01 2:1 0.3W, 0.6X 4.56 4.50 5.00 9

276/478Y 7526A04G09 2.3:1 0.3W, 0.6X 4.56 4.50 5.00 9

288/500Y 7526A04G02 2.4:1 0.3W, 0.6X 4.56 4.50 5.00 9

300/520Y 7526A04G03 2.5:1 0.3W, 0.6X 4.56 4.50 5.00 9

400/400Y 7526A04G06 3.33:1 0.3W, 0.6X 4.56 4.50 5.00 9

480/480Y 7526A04G04 4:1 0.3W, 0.6X 4.56 4.50 5.00 9

480/480Y 7526A04G08 2:1 [email protected] 4.56 4.50 5.00 9

500/500Y 7526A04G11 4.167:1 0.3W, 0.6X 4.56 4.50 5.00 9

600/600Y 7526A04G05 5:1 0.3W, 0.6X 4.56 4.50 5.00 9

600/600Y 7526A04G12 2.5:1 0.3W, 0.6X 4.56 4.50 5.00 9

1VAP428711-DB

3.875

4.563

2.2812.281

2.50

5.00

4.376

2.188

RATING DECAL

RATING DECAL

Primary Voltage

Style Number Ratio

IEEE MeteringAccuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

69.4/120Y 7526A05G06 0.58:1 0.6W, 1.2X 4.56 4.50 5.00 9

120/208Y 7526A05G07 1:1 0.6W, 1.2X 4.56 4.50 5.00 9

208/208Y 7526A05G08 1.73:1 0.6W, 1.2X 4.56 4.50 5.00 9

240/416Y 7526A05G01 2:1 0.6W, 1.2X 4.56 4.50 5.00 9

288/500Y 7526A05G02 2.4:1 0.6W, 1.2X 4.56 4.50 5.00 9

300/520Y 7526A05G03 2.5:1 0.6W, 1.2X 4.56 4.50 5.00 9

380/380Y 7526A05G09 3.17:1 0.6W, 1.2X 4.56 4.50 5.00 9

480/480Y 7526A05G04 4:1 0.6W, 1.2X 4.56 4.50 5.00 9

600/600Y 7526A05G05 5:1 0.6W, 1.2X 4.56 4.50 5.00 9

TYPES PPW and PPD

600 V Voltage Transformers

600 Volts Indoor/outdoor 10 kV BIL60 Hertz

Thermal rating:150 VA @ 30°C ambient100 VA @ 55°C ambient

TYPE PPW

TYPE PPD

* Stated accuracies are applicable for 60 Hz.

For 50 Hz designs contact factory.

UL Recognized Component

52 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 53

Primary Voltage

Style Number Ratio

IEEE MeteringAccuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

240/416Y 7526A10G01 2:1 0.3Y 5.97 5.87 6.12 19

288/500Y 7526A10G02 2.4:1 0.3Y 5.97 5.87 6.12 19

300/520Y 7526A10G03 2.5:1 0.3Y 5.97 5.87 6.12 19

480/480Y 7526A10G04 4:1 0.3Y 5.97 5.87 6.12 19

600/600Y 7526A10G05 5:1 0.3Y 5.97 5.87 6.12 19

120/208Y 7526A10G06 1:1 0.3Y 5.97 5.87 6.12 19

1VAP428731-DB

Primary Voltage

Style Number Ratio

IEEE MeteringAccuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

40/70Y 7525A16G06 .3333:1 0.3W, 0.6X 5.97 5.87 6.12 19

48/83Y 7525A16G07 0.4:1 0.3W, 0.6X, 1.2Y 5.97 5.87 6.12 19

60/104Y + 7525A16G10 0.5:1 0.6Y 5.97 5.87 6.12 19

69.3/120Y 7525A16G03 0.578:1 0.3W, 0.6Y 5.97 5.87 6.12 19

120/208Y + 7525A16G01 1:1 0.6Y 5.97 5.87 6.12 19

120/208Y* + 7525A16G05 1.7143:1 0.3X 5.97 5.87 6.12 19

207.8/360Y 7525A16G09 1.7317:1 0.3Y 5.97 5.87 6.12 19

346/600Y 7525A16G08 2.8833:1 0.3Y 5.97 5.87 6.12 19

400/400Y + 7525A16G04 3.33:1 0.3W, 0.6X 5.97 5.87 6.12 19

X1 X2LV

.750 .750

2.871

5.741

NAMEPLATE

RATINGDECAL

RATINGDECAL

4.903

5.840

2.313 2.313

5.968

COMPRESSION TYPE TERMINAL FOR #14THROUGH #3 WIRE4-TOTAL

TYPES PPM and PPX

600 V Voltage Transformers

600 Volts Indoor/outdoor 10 kV BIL60 Hertz

Thermal rating:500 VA @ 30°C ambient350 VA @ 55°C ambient

TYPE PPM

TYPE PPX

+ Thermal rating: 350 VA @ 30°C Ambient (50 Hz)

* 70 V Secondary

UL Recognized Component

54 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 55

Primary Amps

Style Number

IEEE Metering Accuracy

RelayAccuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 7524A01G01 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

10 7524A01G02 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

15 7524A01G03 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

20 7524A01G04 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

25 7524A01G05 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

30 7524A01G06 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

40 7524A01G07 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

50 7524A01G08 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

75 7524A01G09 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

100 7524A01G10 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

150 7524A01G11 0.3B-1.8 T100 1.5 8.06 6.13 15.0 35

200 7524A01G12 0.3B-1.8 T100 1.5 8.06 6.13 15.0 38

300 7524A01G13 0.3B-1.8 T100 1.5 8.06 6.13 15.0 38

400 7524A01G14 0.3B-1.8 T100 1.5 8.06 6.13 15.0 38

600 7524A01G15 0.3B-1.8 T100 1.5 8.06 6.13 15.0 38

800 7524A01G16 0.3B-1.8 T100 1.33 8.06 6.13 15.0 38

1000 7524A01G21 0.3B-1.8 T100 1.2 8.06 6.13 15.0 38

1200 7524A01G20 0.3B-1.8 T100 1.0 8.06 6.13 15.0 38

1VAP429141-DB

7.13

8.63

.75

4.75

.38

5.50

1.66

5.00 1.81

4.25

Mounting base dimensions (in)TYPE KIR-60

5 kV - 36 kV Current Transformers

Indoor 60 kV BIL50/60 Hertz*

* Accuracy 20% less at 50 Hz

Mechanical rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal Thermal rating:5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second

56 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 57

Primary Amps

Style Number

IEEE Metering Accuracy

Window Diam. (in.)

Relay Accuracy

Rating Factor @

30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

100 B130100S1 0.3B-0.1 3.44 C10 2.0 12.0 9.75 9.0 40

200 B130200S1 0.3B-0.2 3.44 C20 2.0 12.0 9.75 9.0 40

300 B130300S1 0.3B-0.2 3.44 C50 2.0 12.0 9.75 9.0 40

400 B130400S1 0.3B-0.5 3.44 C75 2.0 12.0 9.75 9.0 40

500 B130500S1 0.3B-0.5 3.44 C100 2.0 12.0 9.75 9.0 40

600 B130600S1 0.3B-0.5 3.44 C100 2.0 12.0 9.75 9.0 40

800 B130800S1 0.3B-0.9 3.44 C150 2.0 12.0 9.75 9.0 40

1000 B131000S1 0.3B-1.8 3.44 C200 2.0 12.0 9.75 9.0 40

1200 B131200S1 0.3B-1.8 3.44 C200 2.0 12.0 9.75 9.0 40

1500 B131500S1 0.3B-1.8 3.44 C200 2.0 12.0 9.75 9.0 40

2000 B132000S1 0.3B-1.8 3.44 C200 2.0 12.0 9.75 9.0 40

2500 B132500S1 0.3B-1.8 3.44 C200 2.0 12.0 9.75 9.0 40

3000 B133000S1 0.3B-1.8 3.44 C200 1.0 12.0 9.75 9.0 40

4000 B134000S1 0.3B-1.8 3.44 C200 1.0 12.0 9.75 9.0 40

200/400 B130200D1 0.3B-0.2/0.3B-0.5 3.44 C20/C40 2.0/2.0 12.0 9.75 9.0 40

300/600 B130300D1 0.3B-0.2/0.3B-0.5 3.44 C50/C100 2.0/2.0 12.0 9.75 9.0 40

400/800 B130400D1 0.3B-0.5/0.3B-0.9 3.44 C75/C150 2.0/2.0 12.0 9.75 9.0 40

600/1200 B130600D1 0.3B-0.5/0.3B-1.8 3.44 C100/C200 2.0/2.0 12.0 9.75 9.0 40

1000/2000 B131000D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/2.0 12.0 9.75 9.0 40

1500/3000 B131500D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/1.0 12.0 9.75 9.0 40

2000/4000 B132000D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/1.0 12.0 9.75 9.0 40

6.75 [171] 0.63[16]

CL0.56[14.2]

8.56 [217]

3.50[89]

Mounting base dimensions (in. [mm])

5 kV - 36 kV Current Transformers

TYPE TD-9945000 volts Indoor/outdoor 60 kV BIL60 Hertz

IC Approval AE-1335 is noted by bold catalog number

Available with a 14" primary bar kit (maximum 4000 A). Change last digit of style from 1 to 3.

Available in multi-ratio designs (full tap ratings same as single ratio above)

One second thermal/mechanical ratings: 60 x full winding Inom / unlimited mechanical.

1VAP701141-DB

58 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 59

X2 X1X3X5 X4 N/P 8.25 11.505.50

10.75 [273]13.0 [330]

[140] [210] [292]MAX

Primary Amps

Style

Number*IEEE Metering

Accuracy

Window Diam. (in.)

Relay Accuracy

Rating Factor @

30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

200 B180200S1 0.3B-0.2 3.44 C100 3.0 20.3 13.0 11.50 100

300 B180300S1 0.3B-0.5 3.44 C200 3.0 20.3 13.0 11.50 100

400 B180400S1 0.3B-0.9 3.44 C250 3.0 20.3 13.0 11.50 100

500 B180500S1 0.3B-1.8 3.44 C300 3.0 20.3 13.0 11.50 100

600 B180600S1 0.3B-1.8 3.44 C400 3.0 20.3 13.0 11.50 100

800 B180800S1 0.3B-1.8 3.44 C400 2.0 20.3 13.0 11.50 100

1000 B181000S1 0.3B-1.8 3.44 C400 2.0 20.3 13.0 11.50 100

1200 B181200S1 0.3B-1.8 3.44 C400 2.0 20.3 13.0 11.50 100

1500 B181500S1 0.3B-1.8 3.44 C400 2.0 20.3 13.0 11.50 100

2000 B182000S1* 0.3B-1.8 3.44 C400* 2.0 20.3 13.0 11.50 100

2500 B182500S1* 0.3B-1.8 3.44 C400* 2.0 20.3 13.0 11.50 100

3000 B183000S1* 0.3B-1.8 3.44 C400* 2.0 20.3 13.0 11.50 100

4000 B184000S1* 0.3B-1.8 3.44 C400* 2.0 20.3 13.0 11.50 100

600 MR B180600M1 0.3B-1.8 3.44 C400 2.0 20.3 13.0 11.50 100

1200 MR B181200M1 0.3B-1.8 3.44 C400 2.0 20.3 13.0 11.50 100

2000 MR B182000M1* 0.3B-1.8 3.44 C400* 2.0 20.3 13.0 11.50 100

3000 MR B183000M1* 0.3B-1.8 3.44 C400* 2.0 20.3 13.0 11.50 100

4000 MR B184000M1* 0.3B-1.8 3.44 C400* 2.0 20.3 13.0 11.50 100

Primary Amps

Style

Number0.15/0.3 @

Burden0.15/0.3

Accuracy Range

Window Diam. (in.)

Rating Factor @

30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

400 B180400X1 B-0.5/B-0.9 400/4 to 1200A 3.44 3.0 20.3 13.0 11.50 100

500 B180500X1 B-0.5/B-1.8 500/5 to 2000A 3.44 4.0 20.3 13.0 11.50 100

600 B180600X1 B-0.9/B-1.8 600/6 to 2400A 3.44 4.0 20.3 13.0 11.50 100

800 B180800X1 B-0.9/B-1.8 800/8 to 3200A 3.44 4.0 20.3 13.0 11.50 100

1000 B181000X1 B-1.8 10 to 4000A 3.44 4.0 20.3 13.0 11.50 100

1200 B181200X1 B-1.8 12 to 4800A 3.44 4.0 20.3 13.0 11.50 100

1500 B181500X1 B-1.8 15 to 4500A 3.44 3.0 20.3 13.0 11.50 100

2000 B182000X1 B-1.8 20 to 4000A 3.44 2.0 20.3 13.0 11.50 100

Mounting base dimensions (in. [mm])TYPE RMB(X)-631

5000 Volts Indoor/outdoor 60 kV BIL60 Hertz

5 kV - 36 kV Current Transformers

* Units can also be supplied with C800 ratings (add “-512” to the end of the style number)

Available with a 19.5" primary bar kit (maximum 4000 A). Change last digit of style from 1 to 3.

Available in dual-ratio designs (ratings same as single ratio above, change style digit “S” to “D”

TYPE RMBX-631Highaccuracy

TYPE RMB-631

One second thermal/mechanical ratings: 80 x full winding Inom / unlimited mechanical.

1VAP701131-DB

60 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 61

1VAP429151-DB

2.134.25

8.25

4.00

3.25

5.75

7.00

4.88

9.75

2.007.00

Primary Amps

Style Number

IEEE Metering Accuracy

Rating Factor

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 7524A42G01 0.3B-0.9 3.0 C100 15.37 10.50 10.25 42

1200 7524A42G02 0.3B-1.8 2.0 C200 15.37 10.50 10.25 42

1500 7524A42G03 0.3B-1.8 2.0 C200 15.37 10.50 10.25 42

2000 7524A42G04 0.3B-1.8 2.0 C200 15.37 10.50 10.25 42

3000 7524A42G05 0.3B-1.8 1.5 C200 15.37 10.50 10.25 42

4000 7524A42G06 0.3B-1.8 1.5 C200 15.37 10.50 10.25 42

600/1200 7524A42G07 0.3B-1.8/0.3B-1.8 2.0 C100/C200 15.37 10.50 10.25 42

1000/2000 7524A42G08 0.3B-0.9/0.3B-1.8 2.0 C100/C200 15.37 10.50 10.25 42

2000/4000 7524A42G09 0.3B-1.8/0.3B-1.8 1.5 C100/C200 15.37 10.50 10.25 42

Primary Amps

Style Number

IEEE Metering Accuracy

Rating Factor

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 923A272G01 0.3B-0.9 2.0 C100 15.38 10.50 19.62 66

1200 923A272G02 0.3B-1.8 2.0 C200 15.38 10.50 19.62 66

1500 923A272G03 0.3B-1.8 2.0 C200 15.38 10.50 19.62 66

2000 923A272G04 0.3B-1.8 1.5 C200 15.38 10.50 19.62 66

3000 923A272G05 0.3B-1.8 1.33 C200 15.38 10.50 19.62 66

4000 923A272G06 0.3B-1.8 1.0 C200 15.38 10.50 19.62 66

600/1200 923A272G07 0.3B-0.5/0.3B-1.8 2.0 C100/C200 15.38 10.50 19.62 66

1000/2000 923A272G08 0.3B-0.9/0.3B-1.8 1.5 C100/C200 15.38 10.50 19.62 66

2000/4000 923A272G09 0.3B-1.8/0.3B-1.8 1.0 C200/C200 15.38 10.50 19.62 66

Mounting base dimensions (in)TYPE KIT-60

5 kV - 36 kV Current Transformers

Indoor 60 kV BIL60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical Rating:All units effectively unlimitedThermal Rating:800 and 1200 amps: 80 x normal, 1 second1500 amps & above: 100 x normal, 1 second

Contact factory for 0.15S accuracy class

TYPE KIT-60 Bar type

TYPE KIT-60 Tube type3.25" ID

Primary Terminals1200 Amperes and Below

Primary TerminalsAbove 1200 Amperes

1.75

1.75

2.50

2.50

.50 1.75

.25

.25

1.75.50

.88.883.00

.25.25

.25

Bar dimensions:

62 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 63

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 E-7524A10G01 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

10 E-7524A10G02 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

15 E-7524A10G03 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

20 E-7524A10G04 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

25 E-7524A10G05 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

30 E-7524A10G06 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

40 E-7524A10G07 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

50 E-7524A10G08 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

75 E-7524A10G09 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

100 E-7524A10G10 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

150 E-7524A10G11 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

200 E-7524A10G12 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

300 E-7524A10G13 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

400 E-7524A10G14 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

600 E-7524A10G15 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

800 E-7524A10G16 0.3B-1.8 T100 1.33 12.44 9.63 10.95 40

1000 E-7524A10G17 0.3B-1.8 T70 1.33 12.44 9.63 10.95 40

1VAP429201-DB

8.51[216]

9.39[238]

6.63[168]7.89[200]

NAMEPLATE

.44 X 1.88[11 X 22] SLOTS2-TOTAL

.44[11]

.82 [21]

Ø.44 HOLE2-TOTAL

Mounting base dimensions (in. [mm])TYPE KOR-60

5 kV - 36 kV Current Transformers

Outdoor 5 kV, 60 kV BIL50/60 Hertz*Mechanical Rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal 1000 Amps, 150 x normal

Thermal Rating:5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second1000 Amps, 50 x normal for 1 second Creep:13.3" (338 mm)

Note: These units encapsulated with HCEP material; also available with polyurethane.

64 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 65

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 7524A32G01 0.3B-0.9 C100 2.0 17.25 10.50 10.25 40

1200 7524A32G02 0.3B-1.8 C200 2.0 17.25 10.50 10.25 40

1500 7524A32G03 0.3B-1.8 C200 2.0 17.25 10.50 10.25 40

2000 7524A32G04 0.3B-1.8 C200 2.0 17.25 10.50 10.25 40

3000 7524A32G05 0.3B-1.8 C200 1.5 17.25 10.50 10.25 40

4000 7524A32G06 0.3B-1.8 C200 1.5 17.25 10.50 10.25 40

600/1200 7524A32G07 0.3B-0.5/B-1.8 C100/C200 3.0/2.0 17.25 10.50 10.25 40

1000/2000 7524A32G08 0.3B-0.9/B-1.8 C100/C200 3.0/2.0 17.25 10.50 10.25 40

2000/4000 7524A32G09 0.3B-1.8/B-1.8 C100/C200 2.0/1.5 17.25 10.50 10.25 40

42-930

5.75

7.00

7.00

8.25

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 923A271G01 0.3B-0.9 C100 2.0 17.25 10.50 19.62 62

1200 923A271G02 0.3B-1.8 C200 2.0 17.25 10.50 19.62 62

1500 923A271G03 0.3B-1.8 C200 2.0 17.25 10.50 19.62 62

2000 923A271G04 0.3B-1.8 C200 1.50 17.25 10.50 19.62 62

3000 923A271G05 0.3B-1.8 C200 1.33 17.25 10.50 19.62 73

4000 923A271G06 0.3B-1.8 C200 1.00 17.25 10.50 19.62 73

600/1200 923A271G07 0.3B-0.5/B-1.8 C100/C200 3.0/2.0 17.25 10.50 19.62 62

1000/2000 923A271G08 0.3B-0.9/B-1.8 C100/C200 2.0/1.5 17.25 10.50 19.62 62

2000/4000 923A271G09 0.3B-1.8/B-1.8 C100/C200 1.5/1.0 17.25 10.50 19.62 73

Mounting base dimensions (in)TYPE KOT-60

5 kV - 36 kV Current Transformers

Outdoor 5 kV, 60 kV BIL50/60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical rating:All units effectively unlimited

Thermal rating:800 and 1200 Amps: 80 x normal, 1 second1500 Amps and above: 100 x normal, 1 second

TYPE KOT-60Tube type3.25" ID

Contact factory for 0.15S accuracy class

Primary terminals:1200 amperes and below

Primary terminals:Above 1200 amperes

1.75

1.75

2.50

2.50

.50 1.75

.25

.25

1.75.50

.88.883.00

.25.25

.25

TYPE KOT-60Bar type

Bar dimensions:

66 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 67

Primary Amps

Style

NumberIEEE Metering

Accuracy

Window Diam. (in.)

Relay Accuracy

Rating Factor @

30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

100 C170100S1 0.3B-0.1 3.44 C10 2.0 12.0 9.0 9.75 40

200 C170200S1 0.3B-0.2 3.44 C20 2.0 12.0 9.0 9.75 40

300 C170300S1 0.3B-0.2 3.44 C50 2.0 12.0 9.0 9.75 40

400 C170400S1 0.3B-0.5 3.44 C75 2.0 12.0 9.0 9.75 40

500 C170500S1 0.3B-0.5 3.44 C100 2.0 12.0 9.0 9.75 40

600 C170600S1 0.3B-0.5 3.44 C100 2.0 12.0 9.0 9.75 40

800 C170800S1 0.3B-0.9 3.44 C150 2.0 12.0 9.0 9.75 40

1000 C171000S1 0.3B-1.8 3.44 C200 2.0 12.0 9.0 9.75 40

1200 C171200S1 0.3B-1.8 3.44 C200 2.0 12.0 9.0 9.75 40

1500 C171500S1 0.3B-1.8 3.44 C200 2.0 12.0 9.0 9.75 40

2000 C172000S1 0.3B-1.8 3.44 C200 2.0 12.0 9.0 9.75 40

2500 C172500S1 0.3B-1.8 3.44 C200 2.0 12.0 9.0 9.75 40

3000 C173000S1 0.3B-1.8 3.44 C200 1.0 12.0 9.0 9.75 40

4000 C174000S1 0.3B-1.8 3.44 C200 1.0 12.0 9.0 9.75 40

200/400 C170200D1 0.3B-0.2/0.3B-0.5 3.44 C20/C40 2.0/2.0 12.0 9.0 9.75 40

300/600 C170300D1 0.3B-0.2/0.3B-0.5 3.44 C50/C100 2.0/2.0 12.0 9.0 9.75 40

400/800 C170400D1 0.3B-0.5/0.3B-0.9 3.44 C75/C150 2.0/2.0 12.0 9.0 9.75 40

600/1200 C170600D1 0.3B-0.5/0.3B-1.8 3.44 C100/C200 2.0/2.0 12.0 9.0 9.75 40

1000/2000 C171000D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/2.0 12.0 9.0 9.75 40

1500/3000 C171500D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/1.0 12.0 9.0 9.75 40

2000/4000 C172000D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/1.0 12.0 9.0 9.75 40

6.75 [171] 0.63[16]

CL0.56[14.2]

8.56 [217]

3.50[89]

Mounting base dimensions (in. [mm])

5 kV - 36 kV Current Transformers

TYPE HSB-9948700 Volts Indoor/outdoor 75 kV BIL60 Hertz

Available with a 14" primary bar kit (maximum 4000 A). Change last digit of style from 1 to 3.

Available in multi-ratio designs (full tap ratings same as single ratio above).

One second thermal/mechanical ratings: 60 x full winding Inom / unlimited mechanical.

1VAP701151-DB

68 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 69

6.75 [171] 0.63[16]

CL0.56[14.2]

8.56 [217]

3.50[89]

Primary Amps

Style

NumberIEEE Metering

Accuracy

Window Diam. (in.)

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

100 C130100S1 - 3.44 C10 2.0 14.88 9.0 9.75 45

200 C130200S1 0.3B-0.2 3.44 C20 2.0 14.88 9.0 9.75 45

300 C130300S1 0.3B-0.2 3.44 C50 2.0 14.88 9.0 9.75 45

400 C130400S1 0.3B-0.5 3.44 C75 2.0 14.88 9.0 9.75 45

500 C130500S1 0.3B-0.5 3.44 C100 2.0 14.88 9.0 9.75 45

600 C130600S1 0.3B-0.5 3.44 C100 2.0 14.88 9.0 9.75 45

800 C130800S1 0.3B-0.9 3.44 C150 2.0 14.88 9.0 9.75 45

1000 C131000S1 0.3B-1.8 3.44 C200 2.0 14.88 9.0 9.75 45

1200 C131200S1 0.3B-1.8 3.44 C200 2.0 14.88 9.0 9.75 45

1500 C131500S1 0.3B-1.8 3.44 C200 2.0 14.88 9.0 9.75 45

2000 C132000S1 0.3B-1.8 3.44 C200 2.0 14.88 9.0 9.75 45

2500 C132500S1 0.3B-1.8 3.44 C200 2.0 14.88 9.0 9.75 45

3000 C133000S1 0.3B-1.8 3.44 C200 1.0 14.88 9.0 9.75 45

4000 C134000S1 0.3B-1.8 3.44 C200 1.0 14.88 9.0 9.75 45

200/400 C130200D1 0.3B-0.2/0.3B-0.5 3.44 C20/C40 2.0/2.0 14.88 9.0 9.75 45

300/600 C130300D1 0.3B-0.2/0.3B-0.5 3.44 C50/C100 2.0/2.0 14.88 9.0 9.75 45

400/800 C130400D1 0.3B-0.5/0.3B-0.9 3.44 C75/C150 2.0/2.0 14.88 9.0 9.75 45

600/1200 C130600D1 0.3B-0.5/0.3B-1.8 3.44 C100/C200 2.0/2.0 14.88 9.0 9.75 45

1000/2000 C131000D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/2.0 14.88 9.0 9.75 45

1500/3000 C131500D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/1.0 14.88 9.0 9.75 45

2000/4000 C132000D1 0.3B-1.8/0.3B-1.8 3.44 C100/C200 2.0/1.0 14.88 9.0 9.75 45

Mounting base dimensions (in. [mm])

5 kV - 36 kV Current Transformers

TYPE HTD-9948700 VoltsIndoor/outdoor75 kV BIL60 Hertz

Available with a 14" primary bar kit (maximum 4000 A). Change last digit of style from 1 to 3.

Available in multi-ratio designs (full tap ratings same as single ratio above).

One second thermal/mechanical ratings: 60 x full winding Inom / unlimited mechanical.

1VAP701161-DB

70 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 71

X1X5 X4 X3 X2

J K L

B

FD

CE

A

H

G

G

TYP.

N/P

Unit Dimensions

STBB A B C D E F

-991 10.25 10.25 21.0 21.0 18.0 18.0

-992 12.25 12.25 23.0 23.0 20.0 20.0

STBB G H J K L

-991 1.5 24.0 * J + 3.0 J + 6.0

-992 1.5 27.0 * J + 3.0 J + 6.0

*Dimensions listed below

Ratio STBB-991 STBB-992IEEE Metering

AccuracyRelay

AccuracyRating Factor

@ 30°C

600:5 C150600S1 C160600S1 0.3B-0.2 C100 2.0

800:5 C150800S1 C160800S1 0.3B-0.2 C100 2.0

1000:5 C151000S1 C161000S1 0.3B-0.5 C150 2.0

1200:5 C151200S1 C161200S1 0.3B-0.9 C200 2.0

1500:5 C151500S1 C161500S1 0.3B-0.9 C200 2.0

2000:5 C152000S1 C162000S1 0.3B-1.8 C200 2.0

2500:5 C152500S1 C162500S1 0.3B-1.8 C300 2.0

3000:5 C153000S1 C163000S1 0.3B-1.8 C400 2.0

4000:5 C154000S1 C164000S1 0.3B-1.8 C400 2.0

5000:5 C155000S1 C165000S1 0.3B-1.8 C600 1.5

6000:5 C156000S1 C166000S1 0.3B-1.8 C800 1.5

8000:5 C158000S1 C168000S1 0.3B-1.8 C800 1.5

9000:5 C159000S1 C169000S1 0.3B-1.8 C800 1.5

10000:5 C1510000S1 C1610000S1 0.3B-1.8 C800 1.5

12000:5 C1512000S1 C1612000S1 0.3B-1.8 C800 1.5

1000/2000:5 C151000D1 C161000D1 0.3B-0.5/0.3B-1.8 C100/C200 2.0/2.0

2000/4000:5 C152000D1 C162000D1 0.3B-1.8/0.3B-1.8 C200/C400 2.0/1.5

3000/6000:5 C153000D1 C163000D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/1.5

4000/8000:5 C154000D1 C164000D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/1.5

5000/10000:5 C155000D1 C165000D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/1.0

6000/8000:5 C156080D1 C166080D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/1.5

6000/10000:5 C1560100D1 C1660100D1 0.3B-1.8/0.3B-1.8 C400/C800 1.5/1.0

6000/12000:5 C156000D1 C166000D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/1.5

8000/12000:5 C1580120D1 C1680120D1 0.3B-1.8/0.3B-1.8 C400/C800 1.5/1.0

10000/12000:5 C1510012D1 C1610012D1 0.3B-1.8/0.3B-1.8 C600/C800 1.0/1.0

5 kV - 36 kV Current Transformers

TYPE STBB-991/9928700 VoltsIndoor/outdoor 75 kV BIL60 Hertz

Style Number

Available in multi-ratio designs (full tap ratings same as single ratio above).

One second thermal/mechanical ratings: 80 x full winding Inom / unlimited mechanical.

Window sizes:STBB-991: 10.25" x 10.25"STBB-992: 12.25" x 12.25"

* 3.5" [89] minimum, 8.5" [216] maximum. Based on ratio and accuracy. Note: For dimensions A and B, window is geometrically centered.

1VAP701171-DB

72 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 73

1VAP429141-DB

7.13

7.88

.38

4.75

.38

5.50

1.66

5.00 1.44

4.25

1.38

1.38

Primary Amps

Style Number

IEEE Metering Accuracy

RelayAccuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 7524A02G01 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

10 7524A02G02 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

15 7524A02G03 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

20 7524A02G04 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

25 7524A02G05 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

30 7524A02G06 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

40 7524A02G07 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

50 7524A02G08 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

75 7524A02G09 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

100 7524A02G10 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

150 7524A02G11 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

200 7524A02G12 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

300 7524A02G13 0.3B-1.8 T100 1.5 10.31 6.13 16.0 35

400 7524A02G14 0.3B-1.8 T100 1.5 10.31 6.13 16.0 39

600 7524A02G15 0.3B-1.8 T100 1.5 10.31 6.13 16.0 39

800 7524A02G16 0.3B-1.8 T100 1.33 10.31 6.13 16.0 39

1200 7524A02G19 0.3B-1.8 T100 1.0 10.31 6.13 16.0 39

Mounting base dimensions (in)TYPE KIR-75

5 kV - 36 kV Current Transformers

Indoor 75 kV BIL50/60 Hertz*

Mechanical rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal

Thermal rating:5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second

* Accuracy 20% less at 50 Hz

74 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 75

Mounting base dimensions (in)

1VAP429151-DB

2.134.25

8.25

4.00

3.25

5.75

7.00

4.88

9.75

2.007.00

Primary Amps

Style Number

IEEE Metering Accuracy

Rating Factor

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 7524A43G01 0.3B-0.9 3.0 C100 15.37 10.50 13.25 44

1200 7524A43G02 0.3B-1.8 2.0 C200 15.37 10.50 13.25 44

1500 7524A43G03 0.3B-1.8 2.0 C200 15.37 10.50 13.25 44

2000 7524A43G04 0.3B-1.8 2.0 C200 15.37 10.50 13.25 44

3000 7524A43G05 0.3B-1.8 1.5 C200 15.37 10.50 13.25 44

4000 7524A43G06 0.3B-1.8 1.5 C200 15.37 10.50 13.25 44

600/1200 7524A43G07 0.3B-1.8/0.3B-1.8 2.0 C100/C200 15.37 10.50 13.25 44

1000/2000 7524A43G08 0.3B-0.9/0.3B-1.8 2.0 C100/C200 15.37 10.50 13.25 44

2000/4000 7524A43G09 0.3B-1.8/0.3B-1.8 1.5 C100/C200 15.37 10.50 13.25 44

Primary Amps

Style Number

IEEE Metering Accuracy

Rating Factor

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 923A274G01 0.3B-0.9 2.0 C100 15.38 10.50 22.62 70

1200 923A274G02 0.3B-1.8 2.0 C200 15.38 10.50 22.62 70

1500 923A274G03 0.3B-1.8 2.0 C200 15.38 10.50 22.62 70

2000 923A274G04 0.3B-1.8 1.5 C200 15.38 10.50 22.62 70

3000 923A274G05 0.3B-1.8 1.33 C200 15.38 10.50 22.62 70

4000 923A274G06 0.3B-1.8 1.0 C200 15.38 10.50 22.62 70

600/1200 923A274G07 0.3B-0.5/0.3B-1.8 2.0 C100/C200 15.38 10.50 22.62 70

1000/2000 923A274G08 0.3B-0.9/0.3B-1.8 1.5 C100/C200 15.38 10.50 22.62 70

2000/4000 923A274G09 0.3B-1.8/0.3B-1.8 1.0 C200/C200 15.38 10.50 22.62 70

TYPE KIT-75

5 kV - 36 kV Current Transformers

Indoor 75 kV BIL60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical Rating:All units effectively unlimited

Thermal Rating:800 and 1200 amps: 80 x normal, 1 sec1500 amps & above: 100 x normal, 1 sec

Contact factory for 0.15S accuracy class

TYPE KIT-75 Tube type3.25" ID

Primary Terminals1200 Amperes and Below

Primary TerminalsAbove 1200 Amperes

1.75

1.75

2.50

2.50

.50 1.75

.25

.25

1.75.50

.88.883.00

.25.25

.25

TYPE KIT-75 Bar type

Bar dimensions:

76 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 77

1VAP429201-DB

8.51[216]

9.39[238]

6.63[168]7.89[200]

NAMEPLATE

.44 X 1.88[11 X 22] SLOTS2-TOTAL

.44[11]

.82 [21]

Ø.44 HOLE2-TOTAL

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 E-7524A11G01 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

10 E-7524A11G02 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

15 E-7524A11G03 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

20 E-7524A11G04 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

25 E-7524A11G05 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

30 E-7524A11G06 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

40 E-7524A11G07 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

50 E-7524A11G08 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

75 E-7524A11G09 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

100 E-7524A11G10 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

150 E-7524A11G11 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

200 E-7524A11G12 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

300 E-7524A11G13 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

400 E-7524A11G14 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

600 E-7524A11G15 0.3B-1.8 T100 1.5 12.44 9.63 10.95 40

800 E-7524A11G16 0.3B-1.8 T100 1.33 12.44 9.63 10.95 40

1000 E-7524A11G17 0.3B-1.8 T70 1.33 12.44 9.63 10.95 40

Mounting base dimensions (in. [mm])TYPE KOR-75

5 kV - 36 kV Current Transformers

Outdoor 8.7 kV, 75 kV BIL50/60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical Rating:

5 thru 600 Amps, 150 x normal

800 Amps, 110 x normal

1000 Amps, 150 x normal

Thermal Rating:

5 thru 600 Amps, 100 x normal for 1 second

800 Amps, 75 x normal for 1 second

1000 Amps, 50 x normal for 1 second

Creep:

13.3" (338 mm)

Note: These units encapsulated with HCEP material; also available with polyurethane.

78 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 79

42-930

5.75

7.00

7.00

8.25

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 7524A33G01 0.3B-0.9 C100 2.0 17.25 10.50 13.25 43

1200 7524A33G02 0.3B-1.8 C200 2.0 17.25 10.50 13.25 43

1500 7524A33G03 0.3B-1.8 C200 2.0 17.25 10.50 13.25 43

2000 7524A33G04 0.3B-1.8 C200 2.0 17.25 10.50 13.25 43

3000 7524A33G05 0.3B-1.8 C200 1.5 17.25 10.50 13.25 43

4000 7524A33G06 0.3B-1.8 C200 1.5 17.25 10.50 13.25 43

600/1200 7524A33G07 0.3B-0.5/B-1.8 C100/C200 3.0/2.0 17.25 10.50 13.25 43

1000/2000 7524A33G08 0.3B-0.9/B-1.8 C100/C200 3.0/2.0 17.25 10.50 13.25 43

2000/4000 7524A33G09 0.3B-1.8/B-1.8 C100/C200 2.0/1.5 17.25 10.50 13.25 43

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 923A273G01 0.3B-0.9 C100 2.0 17.25 10.50 22.62 67

1200 923A273G02 0.3B-1.8 C200 2.0 17.25 10.50 22.62 67

1500 923A273G03 0.3B-1.8 C200 2.0 17.25 10.50 22.62 67

2000 923A273G04 0.3B-1.8 C200 1.50 17.25 10.50 22.62 67

3000 923A273G05 0.3B-1.8 C200 1.33 17.25 10.50 22.62 79

4000 923A273G06 0.3B-1.8 C200 1.00 17.25 10.50 22.62 79

600/1200 923A273G07 0.3B-0.5/B-1.8 C100/C200 3.0/2.0 17.25 10.50 22.62 67

1000/2000 923A273G08 0.3B-0.9/B-1.8 C100/C200 2.0/1.5 17.25 10.50 22.62 67

2000/4000 923A273G09 0.3B-1.8/B-1.8 C100/C200 1.5/1.0 17.25 10.50 22.62 79

Mounting base dimensions (in)TYPE KOT-75

5 kV - 36 kV Current Transformers

Outdoor 8.7 kV,75 kV BIL50/60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical rating:All units effectively unlimited

Thermal rating:800 and 1200 Amps: 80 x normal, 1 second1500 Amps and above: 100 x normal, 1 second

Contact factory for 0.15S accuracy class

TYPE KOT-75Tube type3.25" ID

Primary terminals:1200 amperes and below

Primary terminals:Above 1200 amperes

1.75

1.75

2.50

2.50

.50 1.75

.25

.25

1.75.50

.88.883.00

.25.25

.25

Type KOT-75Bar type

Bar dimensions:

80 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 81

Primary Amps

Style Number

IEEE Metering Accuracy

RelayAccuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5/10 7524A04G01 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 56

10/20 7524A04G02 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 56

20/40 7524A04G03 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 56

25/50 7524A04G04 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 56

50/100 7524A04G05 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 56

75/150 7524A04G06 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 56

100/200 7524A04G07 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 56

150/300 7524A04G08 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 61

200/400 7524A04G09 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 61

300/600 7524A04G10 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 61

400/800 7524A04G11 0.3B-1.8/0.3B-0.9 T100/T200 2.0/1.33 9.87 6.75 23 61

600/1200 7524A04G14 0.3B-1.8/0.3B-0.9 T90/T200 2.0/1.5 9.87 6.75 23 62

Primary Amps

Style Number

IEEE Metering Accuracy

RelayAccuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 7524A03G01 0.3B-1.8 T200 1.5 9.87 6.75 23 56

10 7524A03G02 0.3B-1.8 T200 1.5 9.87 6.75 23 56

15 7524A03G03 0.3B-1.8 T200 1.5 9.87 6.75 23 56

20 7524A03G04 0.3B-1.8 T200 1.5 9.87 6.75 23 56

25 7524A03G05 0.3B-1.8 T200 1.5 9.87 6.75 23 56

30 7524A03G06 0.3B-1.8 T200 1.5 9.87 6.75 23 56

40 7524A03G07 0.3B-1.8 T200 1.5 9.87 6.75 23 56

50 7524A03G08 0.3B-1.8 T200 1.5 9.87 6.75 23 56

75 7524A03G09 0.3B-1.8 T200 1.5 9.87 6.75 23 56

100 7524A03G10 0.3B-1.8 T200 1.5 9.87 6.75 23 56

150 7524A03G11 0.3B-1.8 T200 1.5 9.87 6.75 23 56

200 7524A03G12 0.3B-1.8 T200 1.5 9.87 6.75 23 56

300 7524A03G13 0.3B-1.8 T200 1.5 9.87 6.75 23 56

400 7524A03G14 0.3B-1.8 T200 1.5 9.87 6.75 23 61

500 7524A03G15 0.3B-1.8 T200 1.5 9.87 6.75 23 61

600 7524A03G16 0.3B-1.8 T200 1.5 9.87 6.75 23 61

800 7524A03G17 0.3B-1.8 T200 1.33 9.87 6.75 23 61

1000 7524A03G21 0.3B-1.8 T200 1.0 9.87 6.75 23 61

1200 7524A03G18 0.3B-1.8 T200 1.0 9.87 6.75 23 62

1VAP429141-DB

9.63 .44

10.50

5.13

.44

2.75

1.66

5.00

.87

4.25

6.00

4.25

Mounting base dimensions (in)TYPE KIR-11

5 kV - 36 kV Current Transformers

Indoor 15 kV, 110 kV BIL50/60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical Rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal

Thermal Rating:5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second

TYPE KIR-11Single ratio

TYPE KIR-11Double ratio

82 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 83

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 923A285G01 0.15B-0.5 T200 1.5 9.87 6.75 23 56

10 923A285G02 0.15B-0.5 T200 1.5 9.87 6.75 23 56

15 923A285G03 0.15B-0.5 T200 1.5 9.87 6.75 23 56

20 923A285G04 0.15B-0.5 T200 1.5 9.87 6.75 23 56

25 923A285G05 0.15B-0.5 T200 1.5 9.87 6.75 23 56

30 923A285G06 0.15B-0.5 T200 1.5 9.87 6.75 23 56

40 923A285G07 0.15B-0.5 T200 1.5 9.87 6.75 23 56

50 923A285G08 0.15B-0.5 T200 1.5 9.87 6.75 23 56

75 923A285G09 0.15B-0.5 T200 1.5 9.87 6.75 23 56

100 923A285G10 0.15B-0.5 T200 1.5 9.87 6.75 23 56

150 923A285G11 0.15B-0.5 T200 1.5 9.87 6.75 23 56

200 923A285G12 0.15B-0.5 T200 1.5 9.87 6.75 23 56

300 923A285G13 0.15B-0.5 T200 1.5 9.87 6.75 23 56

400 923A285G14 0.15B-0.5 T200 1.5 9.87 6.75 23 61

500 923A285G15 0.15B-0.5 T200 1.0 9.87 6.75 23 61

600 923A285G16 0.15B-0.5 T200 1.5 9.87 6.75 23 61

800 923A285G17 0.15B-0.5 T200 1.33 9.87 6.75 23 61

1000 923A285G21 0.15B-0.5 T200 1.0 9.87 6.75 23 61

1200 923A285G18 0.15B-0.5 T200 1.0 9.87 6.75 23 62

9.63 .44

10.50

5.13

.44

2.75

1.66

5.00

.87

4.25

6.00

4.25

Mounting base dimensions (in)TYPE KIR-11E

5 kV - 36 kV Current Transformers

Indoor 15 kV, 110 kV BIL60 Hertz*Special High Accuracy

* Accuracy 20% less at 50 Hertz

Mechanical Rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal

Thermal Rating:5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second

Contact factory for 0.15S accuracy class

84 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 85

Mounting base dimensions (in)

1VAP429151-DB

2.134.25

8.25

4.00

3.25

5.75

7.00

4.88

9.75

2.007.00

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 7524A44G01 0.3B-0.9 3.0 C100 15.37 10.50 17.75 48

1200 7524A44G02 0.3B-1.8 2.0 C200 15.37 10.50 17.75 48

1500 7524A44G03 0.3B-1.8 2.0 C200 15.37 10.50 17.75 48

2000 7524A44G04 0.3B-1.8 2.0 C200 15.37 10.50 17.75 48

3000 7524A44G05 0.3B-1.8 1.5 C200 15.37 10.50 17.75 48

4000 7524A44G06 0.3B-1.8 1.5 C200 15.37 10.50 17.75 48

600/1200 7524A44G07 0.3B-1.8/0.3B-1.8 2.0 C100/C200 15.37 10.50 17.75 48

1000/2000 7524A44G08 0.3B-0.9/0.3B-1.8 2.0 C100/C200 15.37 10.50 17.75 48

2000/4000 7524A44G09 0.3B-1.8/0.3B-1.8 1.5 C100/C200 15.37 10.50 17.75 48

TYPE KIT-11

5 kV - 36 kV Current Transformers

Indoor 110 kV BIL60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical Rating:All units effectively unlimited

Thermal Rating:800 and 1200 amps: 80 x normal, 1 sec1500 amps & above: 100 x normal, 1 sec

Contact factory for 0.15S accuracy class

TYPE KIT-11 Tube type3.25" ID

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 923A277G01 0.3B-0.9 2.0 C100 15.38 10.50 27.12 78

1200 923A277G02 0.3B-1.8 2.0 C200 15.38 10.50 27.12 78

1500 923A277G03 0.3B-1.8 2.0 C200 15.38 10.50 27.12 78

2000 923A277G12 0.3B-1.8 2.0 C400 15.38 10.50 27.12 78

3000 923A277G05 0.3B-1.8 1.33 C200 15.38 10.50 27.12 78

4000 923A277G06 0.3B-1.8 1.0 C200 15.38 10.50 27.12 78

600/1200 923A277G07 0.3B-0.5/0.3B-1.8 2.0 C100/C200 15.38 10.50 27.12 78

1000/2000 923A277G08 0.3B-0.9/0.3B-1.8 1.5 C100/C200 15.38 10.50 27.12 78

2000/4000 923A277G14 0.3B-1.8/0.3B-1.8 1.33 C200/C200 15.38 10.50 27.12 78

TYPE KIT-11 Bar type

Primary Terminals1200 Amperes and Below

Primary TerminalsAbove 1200 Amperes

1.75

1.75

2.50

2.50

.50 1.75

.25

.25

1.75.50

.88.883.00

.25.25

.25

Bar dimensions:

86 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 87

1VAP429242-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 E-923A427G01 0.15B-1.8 + 1.5 13.81 10.88 12.41 44

1000 E-923A427G02 0.15B-1.8 + 1.5 13.81 10.88 12.41 44

1VAP429241-DB

10.88 [276]

10.00 [254]

.44[11]

8.19[208]

9.50[241]

.66 [17]

.44 x .88[11 x 22]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])

10.88 [276]

10.00 [254]

.44[11]

8.19[208]

9.50[241]

.66 [17]

.44 x .88[11 x 22]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])TYPE KON-11ER

5 kV - 36 kV Current Transformers

* Accuracy 20% less at 50 Hertz

+ Not to be used for relay applications

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 E-7524A25G16 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

10 E-7524A25G01 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

15 E-7524A25G02 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

20 E-7524A25G03 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

25 E-7524A25G04 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

30 E-7524A25G05 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

40 E-7524A25G06 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

50 E-7524A25G07 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

75 E-7524A25G08 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

100 E-7524A25G09 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

150 E-7524A25G10 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

200 E-7524A25G11 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

300 E-7524A25G12 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

400 E-7524A25G13 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

600 E-7524A25G14 0.3B-0.5 C40 2.0 13.81 10.88 12.41 44

800 E-7524A25G15 0.3B-0.5 C40 1.5 13.81 10.88 12.41 44

1000 E-7524A25G18 0.3B-0.5 C40 1.2 13.81 10.88 12.41 44

1200 E-7524A25G19 0.3B-0.5 C40 1.0 13.81 10.88 12.41 44

Outdoor 15 kV, 110 kV BIL50/60 HertzExtended Range(0.15% accuracy from 1% of Inom thru rating factor)

Mechanical Rating:All Ratings 270 x normal

Thermal Rating:All Ratings 190 x normal, 1 second

Creep:19.5" (495 mm)

Note: These units encapsulated with HCEP material; also available with polyurethane.

TYPE KON-11Outdoor 15 kV, 110 kV BIL50/60 HertzMechanical Rating:All Ratings 270 x normal

Thermal Rating:All Ratings 190 x normal, 1 second

Creep:19.5" (495 mm)

88 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 89

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5/10 E-7524A13G01 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

10/20 E-7524A13G02 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

20/40 E-7524A13G03 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

25/50 E-7524A13G04 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

50/100 E-7524A13G05 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

75/150 E-7524A13G06 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

100/200 E-7524A13G07 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

150/300 E-7524A13G08 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

200/400 E-7524A13G09 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

300/600 E-7524A13G10 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

400/800 E-7524A13G11 0.3B-0.9/0.3B-1.8 T100/T200 2.0/1.5 15.75 11.0 12.48 67

600/1200 E-7524A13G12 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

1VAP429221-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 E-7524A12G01 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

10 E-7524A12G02 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

15 E-7524A12G03 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

20 E-7524A12G04 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

25 E-7524A12G05 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

30 E-7524A12G06 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

40 E-7524A12G07 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

50 E-7524A12G08 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

75 E-7524A12G09 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

100 E-7524A12G10 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

150 E-7524A12G11 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

200 E-7524A12G12 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

300 E-7524A12G13 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

400 E-7524A12G14 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

600 E-7524A12G15 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

800 E-7524A12G16 0.3B-1.8 T200 1.33 15.75 11.0 12.48 67

1000 E-7524A12G18 0.3B-1.8 T150 1.5 15.75 11.0 12.48 67

1200 E-7524A12G17 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

10.86[276]

9.98[253]

.44[11]

8.18[208]

9.48[241]

.66[17]

NAMEPLATE

.44 X .88[11 X 22]SLOTS4-TOTAL

Mounting base dimensions (in. [mm])TYPE KOR-11

5 kV - 36 kV Current Transformers

* Accuracy 20% less at 50 Hertz

Outdoor 15 kV, 110 kV BIL50/60 Hertz

Mechanical Rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal1000 Amps, 180 x normal1200 Amps, 150 x normal

Thermal Rating:5 thru 600 Amps, 100 x normal for 1 second800 Amps, 75 x normal for 1 second

Creep: 20.8" (528 mm)

Note: These units encapsulated with HCEP material; also available with polyurethane.

KOR-11Single ratio

KOR-11Double ratio

90 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 91

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 7881A92G01 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

10 7881A92G02 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

15 7881A92G03 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

20 7881A92G04 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

25 7881A92G05 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

30 7881A92G06 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

40 7881A92G07 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

50 7881A92G08 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

75 7881A92G09 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

100 7881A92G10 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

150 7881A92G11 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

200 7881A92G12 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

300 7881A92G13 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

400 7881A92G14 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

600 7881A92G15 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

800 7881A92G16 0.15B-0.5 T200 1.33 15.75 11.0 12.48 67

1200 7881A92G17 0.15B-0.5 T200 1.5 15.75 11.0 12.48 67

1000 7881A92G18 0.15B-0.5 T150 1.5 15.75 11.0 12.48 67

10.86[276]

9.98[253]

.44[11]

8.18[208]

9.48[241]

.66[17]

NAMEPLATE

.44 X .88[11 X 22]SLOTS4-TOTAL

Mounting base dimensions (in. [mm])TYPE KOR-11E

5 kV - 36 kV Current Transformers

* Accuracy 20% less at 50 Hertz

Outdoor 15 kV, 110 kV BIL50/60 HertzMechanical Rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal1000 Amps, 180 x normal1200 Amps, 150 x normal

Thermal Rating:5 thru 600 Amps, 150 x normal for 1 second800 Amps, 110 x normal for 1 second1000 Amps, 180 x normal for 1 second1200 Amps, 150 x normal for 1 second

Creep: 20.0" (508 mm)

KOR-11ESingle RatioSpecial highaccuracy

Note: This unit insulated with polyurethane

92 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 93

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 7524A34G01 0.3B-0.9 C100 2.0 17.25 10.50 17.75 47

1200 7524A34G02 0.3B-1.8 C200 2.0 17.25 10.50 17.75 47

1500 7524A34G03 0.3B-1.8 C200 2.0 17.25 10.50 17.75 47

2000 7524A34G04 0.3B-1.8 C200 2.0 17.25 10.50 17.75 47

3000 7524A34G05 0.3B-1.8 C200 1.5 17.25 10.50 17.75 47

4000 7524A34G06 0.3B-1.8 C200 1.5 17.25 10.50 17.75 47

600/1200 7524A34G07 0.3B-0.5/B-1.8 C100/C200 3.0/2.0 17.25 10.50 17.75 47

1000/2000 7524A34G08 0.3B-0.9/B-1.8 C100/C200 3.0/2.0 17.25 10.50 17.75 47

2000/4000 7524A34G09 0.3B-1.8/B-1.8 C100/C200 2.0/1.5 17.25 10.50 17.75 47

42-930

5.75

7.00

7.00

8.25

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 923A275G01 0.3B-0.9 C100 2.0 17.25 10.50 27.12 75

1200 923A275G02 0.3B-1.8 C200 2.0 17.25 10.50 27.12 75

1500 923A275G03 0.3B-1.8 C200 2.0 17.25 10.50 27.12 75

2000 923A275G04 0.3B-1.8 C200 1.50 17.25 10.50 27.12 75

3000 923A275G05 0.3B-1.8 C200 1.33 17.25 10.50 27.12 89

4000 923A275G06 0.3B-1.8 C200 1.00 17.25 10.50 27.12 89

600/1200 923A275G07 0.3B-0.5/B-1.8 C100/C200 3.0/2.0 17.25 10.50 27.12 75

1000/2000 923A275G08 0.3B-0.9/B-1.8 C100/C200 2.0/1.5 17.25 10.50 27.12 75

2000/4000 923A275G09 0.3B-1.8/B-1.8 C100/C200 1.5/1.0 17.25 10.50 27.12 89

Mounting base dimensions (in. [mm])TYPE KOT-11

5 kV - 36 kV Current Transformers

Outdoor 15 kV, 110 kV BIL50/60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical rating:All units effectively unlimited

Thermal rating:800 and 1200 Amps: 80 x normal, 1 second1500 Amps and above: 100 x normal, 1 second

Contact factory for 0.15S accuracy class

TYPE KOT-11Tube type3.25" ID

TYPE KOT-11Bar type

94 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 95

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 D030200S1 0.3B-0.2 C50 3.0 20.75 18.0 13.50 125

300 D030300S1 0.3B-0.5 C100 2.0 20.75 18.0 13.50 125

400 D030400S1 0.3B-0.9 C100 2.0 20.75 18.0 13.50 125

500 D030500S1 0.3B-1.8 C150 2.0 20.75 18.0 13.50 125

600 D030600S1 0.3B-1.8 C200 2.0 20.75 18.0 13.50 125

800 D030800S1 0.3B-1.8 C200 2.0 20.75 18.0 13.50 125

1000 D031000S1 0.3B-1.8 C250 2.0 20.75 18.0 13.50 125

1200 D031200S1 0.3B-1.8 C250 2.0 20.75 18.0 13.50 125

1500 D031500S1 0.3B-1.8 C300 2.0 20.75 18.0 13.50 125

2000 D032000S1 0.3B-1.8 C400 2.0 20.75 18.0 13.50 125

2500 D032500S1 0.3B-1.8 C400 2.0 20.75 18.0 13.50 125

3000 D033000S1 0.3B-1.8 C400 2.0 20.75 18.0 13.50 125

4000 D034000S1 0.3B-1.8 C800 1.5 20.75 18.0 13.50 125

5000 D035000S1 0.3B-1.8 C800 1.1 20.75 18.0 13.50 125

200/400 D030200D1 0.3B-0.5/0.3B-0.9 C50/C100 3.0/3.0 20.75 18.0 13.50 125

300/600 D030300D1 0.3B-0.5/0.3B-1.8 C100/C200 2.0/2.0 20.75 18.0 13.50 125

400/800 D030400D1 0.3B-0.9/0.3B-1.8 C100/C200 2.0/2.0 20.75 18.0 13.50 125

600/1200 D030600D1 0.3B-1.8/0.3B-1.8 C150/C300 2.0/2.0 20.75 18.0 13.50 125

1000/2000 D031000D1 0.3B-1.8/0.3B-1.8 C200/C400 2.0/2.0 20.75 18.0 13.50 125

1500/3000 D031500D1 0.3B-1.8/0.3B-1.8 C300/C600 2.0/2.0 20.75 18.0 13.50 125

1VAP701181-DB & 1VAP701182-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 D030200X1NC0.15SB-0.1 (1-400% Inom)

0.3B-0.2 (1-300% Inom)4.0/3.0 20.75 18.0 13.50 125

300 D030300X1NC0.15SB-0.2 (1-400% Inom)

0.3B-0.5 (1-300% Inom)4.0/3.0 20.75 18.0 13.50 125

400 D030400X1NC0.15SB-0.5 (1-400% Inom)

0.3B-0.9 (1-300% Inom)4.0/3.0 20.75 18.0 13.50 125

500 D030500X1NC0.15SB-0.5 (1-400% Inom)

0.3B-0.9 (1-300% Inom)4.0/3.0 20.75 18.0 13.50 125

600 D030600X1NC0.15SB-0.9 (1-400% Inom)

0.3B-1.8 (1-300% Inom)4.0/3.0 20.75 18.0 13.50 125

800 D030800X1NC0.15SB-0.9 (1-400% Inom)

0.3B-1.8 (1-300% Inom)4.0/3.0 20.75 18.0 13.50 125

1000 D031000X1NC 0.15SB-1.8 4.0 20.75 18.0 13.50 125

1200 D031200X1NC 0.15SB-1.8 4.0 20.75 18.0 13.50 125

1500 D031500X1NC 0.15SB-1.8 3.0 20.75 18.0 13.50 125

2000 D032000X1NC 0.15SB-1.8 2.0 20.75 18.0 13.50 125

.50

.753.256.508.00

4.00

8.00

4.88

9.75

9/16" DIA. (4) PLACES

Mounting base dimensions (in. [mm])

5 kV - 36 kV Current Transformers

TYPE LG(X)-15-585Outdoor15 kV, 110 kV BIL60 HertzTube type: 4.5" ID

Consult factory for designs up to four secondaries.

TYPE LG-15-585

TYPE LGX- 15-585High accuracy

Available in multi-ratio designs (full tap ratings same as single ratios)

One second thermal/mechanical rating: 100 x full winding Inom /unlimited mechanical.

Available with a 30.5" primary bar kit (maximum 5500 A). Change last digit of style from 1 to 3.

IC Approval AE-0703 is noted by bold style number.

One second thermal/mechanical rating: 80 x full winding Inom /unlimited mechanical.

96 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 97

Primary Amps

Style Number

0.15/0.3 @ burden

0.15/0.3 accuracy range

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 D100400X1 B-0.5/B-0.9 400/4 to 1200 A 4.0 20.25 13.0 22.0 120

500 D100500X1 B-0.5/B-1.8 500/5 to 2000 A 4.0 20.25 13.0 22.0 120

600 D100600X1 B-0.9/B-1.8 600/6 to 2400 A 4.0 20.25 13.0 22.0 120

800 D100800X1 B-0.9/B-1.8 800/8 to 3200 A 4.0 20.25 13.0 22.0 120

1000 D101000X1 B-1.8 10 to 4000 A 4.0 20.25 13.0 22.0 120

1200 D101200X1 B-1.8 12 to 4800 A 4.0 20.25 13.0 22.0 120

1500 D101500X1 B-1.8 15 to 4500 A 3.0 20.25 13.0 22.0 120

2000 D102000X1 B-1.8 20 to 4000 A 2.0 20.25 13.0 22.0 120

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 D100200S1 0.3B-0.2 C50 3.0 20.25 13.0 22.0 120

300 D100300S1 0.3B-0.5 C100 3.0 20.25 13.0 22.0 120

400 D100400S1 0.3B-0.9 C100 3.0 20.25 13.0 22.0 120

500 D100500S1 0.3B-1.8 C150 3.0 20.25 13.0 22.0 120

600 D100600S1 0.3B-1.8 C200 3.0 20.25 13.0 22.0 120

800 D100800S1 0.3B-1.8 C200 2.0 20.25 13.0 22.0 120

1000 D101000S1 0.3B-1.8 C250 2.0 20.25 13.0 22.0 120

1200 D101200S1 0.3B-1.8 C250 2.0 20.25 13.0 22.0 120

1500 D101500S1 0.3B-1.8 C300 2.0 20.25 13.0 22.0 120

2000* D102000S1 0.3B-1.8 C400 2.0 20.25 13.0 22.0 120

2500 D102500S1 0.3B-1.8 C400 2.0 20.25 13.0 22.0 120

3000 D103000S1 0.3B-1.8 C800 2.0 20.25 13.0 22.0 120

4000 D104000S1 0.3B-1.8 C800 1.5 20.25 13.0 22.0 120

5000 D105000S1 0.3B-1.8 C800 1.1 20.25 13.0 22.0 120

200/400 D100200D1 0.3B-0.2/0.3B-0.9 C50/C100 3.0/3.0 20.25 13.0 22.0 120

300/600 D100300D1 0.3B-0.5/0.3B-1.8 C100/C200 3.0/3.0 20.25 13.0 22.0 120

400/800 D100400D1 0.3B-0.9/0.3B-1.8 C100/C200 2.0/2.0 20.25 13.0 22.0 120

600/1200 D100600D1 0.3B-1.8/0.3B-1.8 C200/C400 2.0/2.0 20.25 13.0 22.0 120

1000/2000 D101000D1 0.3B-1.8/0.3B-1.8 C200/C400 2.0/2.0 20.25 13.0 22.0 120

1500/3000 D101500D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 20.25 13.0 22.0 120

E

CORONAT

T E D

FREE

S

8.25 [210]

22.0 [559]

N/P

[279]11.0

11.25 [286]

Mounting base dimensions (in. [mm])

TYPE LGX-15-683High accuracy

5 kV - 36 kV Current Transformers

TYPE LG(X)-15-683Outdoor15 kV, 110 kV BIL60 HertzTube type: 4.5" ID

Consult factory for designs up to four secondaries.

TYPE LG-15-683

Available in multi-ratio designs (full tap ratings same as single ratio above).

One second thermal/mechanical rating: 100 x full winding Inom / unlimited mechanical.

Available with a 34.5" primary bar kit (maximum 5500 A). Change last digit of style from 1 to 3.

* IC Approval AE-0745 for 2000:5 MR

1VAP701191-DB

One second thermal/mechanical rating: 80 x full winding Inom / unlimited mechanical.

98 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 99

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 D092015S159-1 0.3B-0.2 C150 2.0 23.5 18.0 17.75 210

300 D093015S209-1 0.3B-0.5 C200 2.0 23.5 18.0 17.75 210

400 D094015S309-1 0.3B-0.9 C300 2.0 23.5 18.0 17.75 210

600 D096015S409-1 0.3B-1.8 C400 2.0 23.5 18.0 17.75 210

800 D098015S609-1 0.3B-1.8 C600 2.0 23.5 18.0 17.75 210

1000 D091025S809-1 0.3B-1.8 C600 2.0 23.5 18.0 17.75 210

1200 D091225S809-1 0.3B-1.8 C800 2.0 23.5 18.0 17.75 210

1500 D091525S809-1 0.3B-1.8 C800 2.0 23.5 18.0 17.75 210

2000 D092025S809-1 0.3B-1.8 C800 2.0 23.5 18.0 17.75 210

2500 D092525S809-1 0.3B-1.8 C800 2.0 23.5 18.0 17.75 210

3000 D093025S809-1 0.3B-1.8 C800 1.5 23.5 18.0 17.75 210

4000 D094025S809-1 0.3B-1.8 C800 1.5 23.5 18.0 17.75 210

5000 D095025S809-1 0.3B-1.8 C800 1.5 23.5 18.0 17.75 210

6000 D096025S809-1 0.3B-1.8 C800 1.5 23.5 18.0 17.75 210

8000 D098025S809-1 0.3B-1.8 C800 1.25 23.5 18.0 17.75 210

10000 D091035S809-1 0.3B-1.8 C800 1.0 23.5 18.0 17.75 210

200/400 D092015D159-1 0.3B-0.2/0.3B-0.9 C150/C300 2.0/2.0 23.5 18.0 17.75 210

300/600 D093015D209-1 0.3B-0.5/0.3B-1.8 C200/C400 2.0/2.0 23.5 18.0 17.75 210

400/800 D094015D309-1 0.3B-0.9/0.3B-1.8 C300/C600 2.0/2.0 23.5 18.0 17.75 210

600/1200 D096015D409-1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 23.5 18.0 17.75 210

1000/2000 D091025D409-1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 23.5 18.0 17.75 210

1500/3000 D091525D809-1 0.3B-1.8/0.3B-1.8 C800/C800 2.0/1.5 23.5 18.0 17.75 210

1VAP701201-DB

Mounting base dimensions (in)

.50

.753.256.508.00

4.00

8.00

4.88

9.75

9/16" DIA. (4) PLACES

5 kV - 36 kV Current Transformers

TYPE LG-15-879Outdoor15 kV, 110 kV BIL60 HertzTube type: 4.5" ID

Consult factory for designs up to four secondaries.

TYPE LG-15-879

Available in multi-ratio designs (full tap ratings same as single ratio above).

One second thermal/mechanical rating: 80 x full winding Inom / unlimited mechanical.

Available with a 30.5" primary bar kit (maximum 5500 A). Change last digit of style from 1 to 3.

100 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 101

Primary Amps

Style Number

0.15/0.3 @ burden

0.15/0.3 accuracy range

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 D040400X1 B-0.5 400/4 to 1200 A 4.0 23.63 18.0 17.75 150

600 D040600X1 B-0.9 600/6 to 2400 A 4.0 23.63 18.0 17.75 150

800 D040800X1 B-0.9 800/8 to 3200 A 4.0 23.63 18.0 17.75 150

1000 D041000X1 B-0.9 100/10 to 3000 A 3.0 23.63 18.0 17.75 150

1200 D041200X1 B-1.8 120/12 to 3600 A 3.0 23.63 18.0 17.75 150

1500 D041500X1 B-1.8 100/15 to 3000 A 2.0 23.63 18.0 17.75 150

2000 D042000X1 B-1.8 200/20 to 3000 A 2.0 23.63 18.0 17.75 150

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 D040200S1 0.3B-0.2 C50 2.0 23.63 18.0 17.75 150

300 D040300S1 0.3B-0.5 C100 2.0 23.63 18.0 17.75 150

400 D040400S1 0.3B-0.5 C100 2.0 23.63 18.0 17.75 150

600 D040600S1 0.3B-0.9 C200 2.0 23.63 18.0 17.75 150

800 D040800S1 0.3B-0.9 C200 2.0 23.63 18.0 17.75 150

1000 D041000S1 0.3B-1.8 C250 2.0 23.63 18.0 17.75 150

1200 D041200S1 0.3B-1.8 C400 2.0 23.63 18.0 17.75 150

1500 D041500S1 0.3B-1.8 C400 2.0 23.63 18.0 17.75 150

2000 D042000S1 0.3B-1.8 C500 2.0 23.63 18.0 17.75 150

2500 D042500S1 0.3B-1.8 C600 2.0 23.63 18.0 17.75 150

3000 D043000S1 0.3B-1.8 C800 2.0 23.63 18.0 17.75 150

4000 D044000S1 0.3B-1.8 C800 1.5 23.63 18.0 17.75 150

5000 D045000S1 0.3B-1.8 C800 1.5 23.63 18.0 17.75 150

6000 D046000S1 0.3B-1.8 C800 1.0 23.63 18.0 17.75 150

8000 D048000S1 0.3B-1.8 C800 1.0 23.63 18.0 17.75 150

10000 D041000S1 0.3B-1.8 C800 1.0 23.63 18.0 17.75 150

200/400 D040200D1 0.3B-0.2/0.3B-0.5 C50/C100 2.0/2.0 23.63 18.0 17.75 150

300/600 D040300D1 0.3B-0.5/0.3B-0.9 C100/C200 2.0/2.0 23.63 18.0 17.75 150

400/800 D040400D1 0.3B-0.5/0.3B-0.9 C100/C200 2.0/2.0 23.63 18.0 17.75 150

600/1200 D040600D1 0.3B-0.9/0.3B-1.8 C200/C400 2.0/2.0 23.63 18.0 17.75 150

1000/2000 D041000D1 0.3B-1.8/0.3B-1.8 C250/C500 2.0/2.0 23.63 18.0 17.75 150

1500/3000 D041500D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 23.63 18.0 17.75 150

2000/4000 D042000D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/1.5 23.63 18.0 17.75 150

3000/6000 D043000D1 0.3B-1.8/0.3B-1.8 C800/C800 1.5/1.0 23.63 18.0 17.75 150

Mounting base dimensions (in)

.50

.753.256.508.00

4.00

8.00

4.88

9.75

9/16" DIA. (4) PLACES

TYPE LGX-15-6513

5 kV - 36 kV Current Transformers

TYPE LG(X)-15-6513Outdoor15 kV, 110 kV BIL60 HertzTube type: 8.75" ID

Consult factory for designs up to four secondaries.

TYPE LG-15- 6513

IC Approval (AE-1104) is noted by bold catalog number.

Available in multi-ratio designs (full tap ratings same as single ratio above).

One second thermal/mechanical rating: 100 x full winding Inom / unlimited mechanical.

1VAP701211-DB

One second thermal/mechanical rating: 80 x full winding Inom / unlimited mechanical.

102 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 103

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 923A141G01 2.0 0.3B-0.5 C200 20 14.7 17 225

600 923A141G02 2.0 0.3B-0.9 C200 20 14.7 17 225

800 923A141G03 2.0 0.3B-1.8 C400 20 14.7 17 225

1000 923A141G04 2.0 0.3B-1.8 C400 20 14.7 17 225

1200 923A141G05 2.0 0.3B-1.8 C400 20 14.7 17 225

1600 923A141G06 2.0 0.3B-1.8 C400 20 14.7 17 225

2000 923A141G07 2.0 0.3B-1.8 C800 20 14.7 17 225

3000 923A141G08 1.5 0.3B-1.8 C800 20 14.7 17 225

4000 923A141G09 1.25 0.3B-1.8 C800 20 14.7 17 225

5000 923A141G10 1.0 0.3B-1.8 C800 20 14.7 17 225

Mounting base dimensions (in)

42-940

7.50

.75

9.00

13.50 .75

15.00

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200/400 923A142G01 2.0/2.0 0.6B-0.2/0.3B-0.5 C100/C200 20 14.7 17 240

300/600 923A142G02 2.0/2.0 0.3B-0.2/0.3B-0.9 C100/C200 20 14.7 17 240

400/800 923A142G03 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 20 14.7 17 240

500/1000 923A142G04 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 20 14.7 17 240

600/1200 923A142G05 2.0/2.0 0.3B-0.9/0.3B-1.8 C200/C400 20 14.7 17 240

800/1600 923A142G06 2.0/2.0 0.3B-0.9/0.3B-1.8 C200/C400 20 14.7 17 240

1000/2000 923A142G07 2.0/2.0 0.3B-1.8/0.3B-1.8 C400/C800 20 14.7 17 240

1500/3000 923A142G08 2.0/1.5 0.3B-1.8/0.3B-1.8 C400/C800 20 14.7 17 240

2000/4000 923A142G09 2.0/1.25 0.3B-1.8/0.3B-1.8 C400/C800 20 14.7 17 240

2500/5000 923A142G10 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 20 14.7 17 240

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A143G01 2.0 0.3B-0.9 C200 20 14.7 17 225

1200 923A143G02 1.5 0.3B-1.8 C400 20 14.7 17 225

2000 923A143G03 1.0 0.3B-1.8 C800 20 14.7 17 225

3000 923A143G04 1.33 0.3B-1.8 C800 20 14.7 17 225

4000 923A143G05 1.0 0.3B-1.8 C800 20 14.7 17 225

5000 923A143G06 1.0 0.3B-1.8 C800 20 14.7 17 225

TYPE KOTD-110

5 kV - 36 kV Current Transformers

15 kV, 110 kV BILSingle, double, & multi-ratio50/60 HertzTube type 5" IDConsult factory for 4" ID and for designs up to four secondaries.

TYPE KOTD-110Tube typeSingle ratio

TYPEKOTD-110 Tube typeDouble ratio

TYPE KOTD-110Tube typeMulti ratio

* Accuracy 20% less at 50 Hertz

104 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 105

Primary Amps

Style Number

No. of Bars

Rating Factor

IEEE Metering Accuracy

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 923A206G01 1 2.0 0.3B-0.5 C200 20 14.7 25 240

600 923A206G02 1 2.0 0.3B-0.9 C200 20 14.7 25 240

800 923A206G03 1 2.0 0.3B-1.8 C400 20 14.7 25 240

1000 923A206G04 1 2.0 0.3B-1.8 C400 20 14.7 25 240

1200 923A206G05 1 1.5 0.3B-1.8 C400 20 14.7 25 240

1600 923A206G06 1 1.25 0.3B-1.8 C400 20 14.7 25 240

2000 923A206G07 1 1.0 0.3B-1.8 C800 20 14.7 25 240

3000 923A206G08 2 1.33 0.3B-1.8 C800 20 14.7 25 240

4000 923A206G09 2 1.0 0.3B-1.8 C800 20 14.7 25 240

5000 923A206G10 3 1.0 0.3B-1.8 C800 20 14.7 25 240

Bar dimensions (in)

42-940

Primary Amps

Style Number

No. of Bars

Rating Factor

IEEE Metering Accuracy

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200/400 923A148G01 1 2.0/2.0 0.6B-0.2/0.3B-0.5 C100/C200 20 14.7 25 240

300/600 923A148G02 1 2.0/2.0 0.3B-0.2/0.3B-0.9 C100/C200 20 14.7 25 240

400/800 923A148G03 1 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 20 14.7 25 240

500/1000 923A148G04 1 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 20 14.7 25 240

600/1200 923A148G05 1 2.0/1.5 0.3B-0.9/0.3B-1.8 C200/C400 20 14.7 25 240

800/1600 923A148G06 1 2.0/1.25 0.3B-0.9/0.3B-1.8 C200/C400 20 14.7 25 240

1000/2000 923A148G07 1 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 20 14.7 25 240

1500/3000 923A148G08 2 2.0/1.33 0.3B-1.8/0.3B-1.8 C400/C800 20 14.7 25 240

2000/4000 923A148G09 2 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 20 14.7 25 240

2500/5000 923A148G10 3 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 20 14.7 25 240

Primary Amps

Style Number

No. of Bars

Rating Factor

IEEE Metering Accuracy

Relay Accuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A149G01 1 2.0 0.3B-0.9 C200 20 15.3 25 240

1200 923A149G02 1 1.5 0.3B-1.8 C400 20 15.3 25 240

2000 923A149G03 1 1.0 0.3B-1.8 C800 20 15.3 25 240

3000 923A149G04 2 1.33 0.3B-1.8 C800 20 15.3 25 240

4000 923A149G05 2 1.0 0.3B-1.8 C800 20 15.3 25 240

5000 923A149G06 3 1.0 0.3B-1.8 C800 20 15.3 25 240

Note: Base dimensions same as tube type KOTD

25.00

4.00

1.12

1.75

1.75

23.88

.56

Ø.56 8-TOTAL

.50

3.00

TYPE KOTD-110

5 kV - 36 kV Current Transformers

15 kV, 110 kV BILSingle, double, & multi-ratio50/60 HertzBar type 5" IDConsult factory for designs up to four secondaries.

TYPE KOTD-110Bar typeSingle ratio

TYPE KOTD-110Bar typeDouble ratio

TYPE KOTD-110Bar typeMulti ratio

* Accuracy 20% less at 50 Hertz

106 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 107

1VAP429151-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 7524A45G01 0.3B-0.9 3.0 C100 15.37 10.50 26.75 50

1200 7524A45G02 0.3B-1.8 2.0 C200 15.37 10.50 26.75 50

1500 7524A45G03 0.3B-1.8 2.0 C200 15.37 10.50 26.75 50

2000 7524A45G04 0.3B-1.8 2.0 C200 15.37 10.50 26.75 50

3000 7524A45G05 0.3B-1.8 1.5 C200 15.37 10.50 26.75 50

4000 7524A45G06 0.3B-1.8 1.5 C200 15.37 10.50 26.75 50

600/1200 7524A45G07 0.3B-1.8/0.3B-1.8 2.0 C100/C200 15.37 10.50 26.75 50

1000/2000 7524A45G08 0.3B-0.9/0.3B-1.8 2.0 C100/C200 15.37 10.50 26.75 50

2000/4000 7524A45G09 0.3B-1.8/0.3B-1.8 1.5 C100/C200 15.37 10.50 26.75 50

2.134.25

8.25

4.00

3.25

5.75

7.00

4.88

9.75

2.007.00

Mounting base dimensions (in)

Primary Terminals1200 Amperes and Below

Primary TerminalsAbove 1200 Amperes

1.75

1.75

2.50

2.50

.50 1.75

.25

.25

1.75.50

.88.883.00

.25.25

.25

TYPE KIT-15

5 kV - 36 kV Current Transformers

Indoor 150 kV BIL60 Hertz*

* Accuracy 20% less at 50 Hertz

Mechanical Rating:All units effectively unlimited

Thermal Rating:800 and 1200 amps: 80 x normal, 1 sec1500 amps and above: 100 x normal, 1 sec

Contact factory for 0.15S accuracy class

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 923A279G01 0.3B-0.9 2.0 C100 15.38 10.50 36.12 89

1200 923A279G02 0.3B-1.8 2.0 C200 15.38 10.50 36.12 89

1500 923A279G03 0.3B-1.8 2.0 C200 15.38 10.50 36.12 89

2000 923A279G12 0.3B-1.8 1.5 C200 15.38 10.50 36.12 89

3000 923A279G05 0.3B-1.8 1.33 C200 15.38 10.50 36.12 89

4000 923A279G06 0.3B-1.8 1.0 C200 15.38 10.50 36.12 89

600/1200 923A279G07 0.3B-0.5/0.3B-1.8 2.0 C100/C200 15.38 10.50 36.12 89

1000/2000 923A279G08 0.3B-0.9/0.3B-1.8 1.5 C100/C200 15.38 10.50 36.12 89

2000/4000 923A279G14 0.3B-1.8/0.3B-1.8 1.0 C200/C200 15.38 10.50 36.12 89

TYPE KIT-15 Bar type

TYPE KIT-15 Tube type3.25" ID

Bar dimensions:

108 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 109

42-930

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 923A270G01 0.3B-0.9 C100 2.0 17.25 10.50 36.12 75

1200 923A270G02 0.3B-1.8 C200 2.0 17.25 10.50 36.12 75

1500 923A270G03 0.3B-1.8 C200 2.0 17.25 10.50 36.12 75

2000 923A270G04 0.3B-1.8 C200 1.50 17.25 10.50 36.12 75

3000 923A270G05 0.3B-1.8 C200 1.33 17.25 10.50 36.12 107

4000 923A270G06 0.3B-1.8 C200 1.00 17.25 10.50 36.12 107

600/1200 923A270G07 0.3B-0.5/B-1.8 C100/C200 3.0/2.0 17.25 10.50 36.12 75

1000/2000 923A270G08 0.3B-0.9/B-1.8 C100/C200 2.0/1.5 17.25 10.50 36.12 75

2000/4000 923A270G09 0.3B-1.8/B-1.8 C100/C200 1.5/1.0 17.25 10.50 36.12 107

Primary Amps

Style Number

IEEE Metering Accuracy

Relay* Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

800 7524A35G01 0.3B-0.9 C100 2.0 17.25 10.50 26.75 52

1200 7524A35G02 0.3B-1.8 C200 2.0 17.25 10.50 26.75 52

1500 7524A35G03 0.3B-1.8 C200 2.0 17.25 10.50 26.75 52

2000 7524A35G04 0.3B-1.8 C200 2.0 17.25 10.50 26.75 52

3000 7524A35G05 0.3B-1.8 C200 1.5 17.25 10.50 26.75 52

4000 7524A35G06 0.3B-1.8 C200 1.5 17.25 10.50 26.75 52

600/1200 7524A35G07 0.3B-0.5/B-1.8 C100/C200 3.0/2.0 17.25 10.50 26.75 52

1000/2000 7524A35G08 0.3B-0.9/B-1.8 C100/C200 3.0/2.0 17.25 10.50 26.75 52

2000/4000 7524A35G09 0.3B-1.8/B-1.8 C100/C200 2.0/1.5 17.25 10.50 26.75 52

Mounting base dimensions (in)

2.134.25

8.25

4.00

3.25

5.75

7.00

4.88

9.75

2.007.00

Primary terminals:1200 amperes and below

Primary terminals:Above 1200 amperes

1.75

1.75

2.50

2.50

.50 1.75

.25

.25

1.75.50

.88.883.00

.25.25

.25

TYPE KOT-15

5 kV - 36 kV Current Transformers

Outdoor 25 kV, 150 kV BIL50/60 Hertz

* Accuracy 20% less at 50 Hertz

Contact factory for 0.15S accuracy class

TYPE KOT-15Bar type

TYPE KOT-15Tube type3.25" ID

Bar dimensions:

Mechanical rating:All units effectively unlimited

Thermal rating:800 and 1200 Amps: 80 x normal, 1 sec1500 amps and above: 100 x normal, 1 sec

110 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 111

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5/10 E-7524A16G01 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

10/20 E-7524A16G02 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

20/40 E-7524A16G03 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

25/50 E-7524A16G04 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

50/100 E-7524A16G05 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

75/150 E-7524A16G06 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

100/200 E-7524A16G07 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

150/300 E-7524A16G08 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

200/400 E-7524A16G09 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

300/600 E-7524A16G10 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

400/800 E-7524A16G11 0.3B-0.9/0.3B-1.8 T100/T200 2.0/1.5 15.75 11.0 12.48 67

600/1200 E-7524A16G12 0.3B-0.9/0.3B-1.8 T90/T200 2.0/1.5 15.75 11.0 12.48 67

1VAP429222-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 E-7524A15G01 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

10 E-7524A15G02 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

15 E-7524A15G03 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

20 E-7524A15G04 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

25 E-7524A15G05 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

30 E-7524A15G06 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

40 E-7524A15G07 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

50 E-7524A15G08 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

75 E-7524A15G09 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

100 E-7524A15G10 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

150 E-7524A15G11 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

200 E-7524A15G12 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

300 E-7524A15G13 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

400 E-7524A15G14 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

600 E-7524A15G15 0.3B-1.8 T200 1.5 15.75 11.0 12.48 67

800 E-7524A15G16 0.3B-1.8 T200 1.33 15.75 11.0 12.48 67

10.86[276]

9.98[253]

.44[11]

8.18[208]

9.48[241]

.66[17]

NAMEPLATE

.44 X .88[11 X 22]SLOTS4-TOTAL

Mounting base dimensions (in)TYPE KOR-12

5 kV - 36 kV Current Transformers

Outdoor 25 kV, 125 kV BIL50/60 HertzMechanical Rating:5 thru 600 Amps, 150 x normal800 Amps, 110 x normal1000 Amps, 180 x normal1200 Amps, 150 x normal

Thermal Rating:5 thru 600 Amps, 150 x normal for 1 sec800 Amps, 110 x normal for 1 sec

Creep: 20.8" (528 mm)

KOR-12Single ratio

* Accuracy 20% less at 50 Hertz

KOR-12Double ratio

Note: These units encapsulated with HCEP material; also available with polyurethane.

112 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 113

1VAP429242-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 E-7524A28G16 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

10 E-7524A28G01 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

15 E-7524A28G02 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

20 E-7524A28G03 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

25 E-7524A28G04 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

30 E-7524A28G05 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

40 E-7524A28G06 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

50 E-7524A28G07 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

75 E-7524A28G08 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

100 E-7524A28G09 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

150 E-7524A28G10 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

200 E-7524A28G11 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

300 E-7524A28G12 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

400 E-7524A28G13 0.3B-0.5 C40 3.0 13.81 10.88 12.41 44

600 E-7524A28G14 0.3B-0.5 C40 2.0 13.81 10.88 12.41 44

800 E-7524A28G15 0.3B-0.5 C40 1.5 13.81 10.88 12.41 44

1000 E-7524A28G18 0.3B-0.5 C40 1.2 13.81 10.88 12.41 44

1200 E-7524A28G19 0.3B-0.5 C40 1.0 13.81 10.88 12.41 44

10.88 [276]

10.00 [254]

.44[11]

8.19[208]

9.50[241]

.66 [17]

.44 x .88[11 x 22]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])TYPE KON-12

5 kV - 36 kV Current Transformers

Outdoor 25 kV, 125 kV BIL50/60 Hertz

Mechanical Rating:All Ratings 270 x normal

Thermal Rating:All Ratings 190 x normal, 1 second

Creep: 19.5" (495 mm)

* Accuracy 20% less at 50 Hertz

Note: These units encapsulated with HCEP material; also available with polyurethane.

114 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 115

1VAP429272-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 E-923A432G01 0.15B-1.8 + 1.5 20.0 13.0 14.59 110

1000 E-923A432G02 0.15B-1.8 + 1.5 20.0 13.0 14.59 110

11.25 [286]

10.00 [254]

8.63 [219]

10.50 [267]

.44 [11]

.72 [18]

.63 [16]

.44 X .88[11 X 22]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])TYPE KOR-15CER

5 kV - 36 kV Current Transformers

Outdoor 25 kV, 150 kV BIL50/60 Hertz

Extended Range(0.15% accuracy from 1% of Inom thru rating factor)

Thermal Rating:All styles 100 x normal, 1 second Creep: 36.5" (927 mm)

+ Not to be used for relay applications.

Note: These units encapsulated with HCEP material.

116 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 117

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5/10 E-923A186G01 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

10/20 E-923A186G02 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

20/40 E-923A186G03 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

25/50 E-923A186G04 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

50/100 E-923A186G05 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

75/150 E-923A186G06 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

100/200 E-923A186G07 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

150/300 E-923A186G08 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

200/400 E-923A186G09 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

300/600 E-923A186G10 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

400/800 E-923A186G11 0.3B-0.9/ 0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

600/1200 E-923A186G12 0.3B-0.9/ 0.3B-1.8 C100/C200 2.0/1.0 20.0 13.0 14.59 110

1VAP429271-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 E-923A185G01 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

10 E-923A185G02 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

15 E-923A185G03 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

20 E-923A185G04 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

25 E-923A185G05 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

30 E-923A185G06 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

40 E-923A185G07 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

50 E-923A185G08 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

75 E-923A185G09 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

100 E-923A185G10 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

150 E-923A185G11 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

200 E-923A185G12 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

300 E-923A185G13 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

400 E-923A185G14 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

500 E-923A185G15 0.3B-0.9 C100 2.0 20.0 13.0 14.59 110

600 E-923A185G16 0.3B-0.9 C100 2.0 20.0 13.0 14.59 110

800 E-923A185G17 0.3B-0.9 C100 1.5 20.0 13.0 14.59 110

1200 E-923A185G18 0.3B-0.9 C100 1.0 20.0 13.0 14.59 110

11.25 [286]

10.00 [254]

8.63 [219]

10.50 [267]

.44 [11]

.72 [18]

.63 [16]

.44 X .88[11 X 22]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])TYPE KOR-15C

5 kV - 36 kV Current Transformers

Outdoor 25 kV, 150 kV BIL50/60 HertzMechanical Rating:All styles single ratio: 290 x normal All styles double ratio: 290 TAP, 145 FULL

Thermal Rating:All styles 100 x normal, 1 second

Creep: 36.5" (927 mm)

KOR-15CSingle ratio

* Accuracy 20% less at 50 Hertz

KOR-15CDouble ratio

Note: These units encapsulated with HCEP material; also available with polyurethane.

Higher metering and relaying accuracies available.

118 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 119

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A157G01 2.0 0.3B-0.9 C200 22.5 14.7 17 245

1200 923A157G02 2.0 0.3B-1.8 C400 22.5 14.7 17 245

2000 923A157G03 1.0 0.3B-1.8 C800 22.5 14.7 17 245

3000 923A157G04 1.33 0.3B-1.8 C800 22.5 14.7 17 245

4000 923A157G05 1.0 0.3B-1.8 C800 22.5 14.7 17 245

5000 923A157G06 1.0 0.3B-1.8 C800 22.5 14.7 17 245

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200/400 923A156G01 2.0/2.0 0.6B-0.2/0.3B-0.5 C100/C200 22.5 14.7 17 245

300/600 923A156G02 2.0/2.0 0.3B-0.2/0.3B-0.9 C100/C200 22.5 14.7 17 245

400/800 923A156G03 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 22.5 14.7 17 245

500/1000 923A156G04 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 22.5 14.7 17 245

600/1200 923A156G05 2.0/2.0 0.3B-0.9/0.3B-1.8 C200/C400 22.5 14.7 17 245

800/1600 923A156G06 2.0/2.0 0.3B-0.9/0.3B-1.8 C200/C400 22.5 14.7 17 245

1000/2000 923A156G07 2.0/2.0 0.3B-1.8/0.3B-1.8 C400/C800 22.5 14.7 17 245

1500/3000 923A156G08 2.0/1.5 0.3B-1.8/0.3B-1.8 C400/C800 22.5 14.7 17 245

2000/4000 923A156G09 2.0/1.25 0.3B-1.8/0.3B-1.8 C400/C800 22.5 14.7 17 245

2500/5000 923A156G10 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 22.5 14.7 17 245

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 923A155G01 2.0 0.3B-0.5 C200 22.5 14.7 17 245

600 923A155G02 2.0 0.3B-0.9 C200 22.5 14.7 17 245

800 923A155G03 2.0 0.3B-1.8 C400 22.5 14.7 17 245

1000 923A155G04 2.0 0.3B-1.8 C400 22.5 14.7 17 245

1200 923A155G05 2.0 0.3B-1.8 C400 22.5 14.7 17 245

1600 923A155G06 2.0 0.3B-1.8 C400 22.5 14.7 17 245

2000 923A155G07 2.0 0.3B-1.8 C800 22.5 14.7 17 245

3000 923A155G08 1.5 0.3B-1.8 C800 22.5 14.7 17 245

4000 923A155G09 1.25 0.3B-1.8 C800 22.5 14.7 17 245

5000 923A155G10 1.0 0.3B-1.8 C800 22.5 14.7 17 245

Mounting base dimensions (in)

42-940

7.50

.75

9.00

13.50 .75

15.00

TYPE KOTD-150

5 kV - 36 kV Current Transformers

25 kV, 150 kV BILSingle, double, & multi-ratio50/60 HertzTube type 5" IDConsult factory for 4" ID and for designs up to four secondaries.

TYPE KOTD-150Tube typeSingle ratio

TYPE KOTD-150Tube typeDouble ratio

TYPE KOTD-150Tube typeMulti ratio

* Accuracy 20% less at 50 Hertz

120 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 121

Primary Amps

Style Number

No. of Bars

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A163G01 1 2.0 0.3B-0.9 C200 22.5 14.7 25 260

1200 923A163G02 1 1.5 0.3B-1.8 C400 22.5 14.7 25 260

2000 923A163G03 1 1.0 0.3B-1.8 C800 22.5 14.7 25 260

3000 923A163G04 2 1.33 0.3B-1.8 C800 22.5 14.7 25 260

4000 923A163G05 2 1.0 0.3B-1.8 C800 22.5 14.7 25 260

5000 923A163G06 3 1.0 0.3B-1.8 C800 22.5 14.7 25 260

Primary Amps

Style Number

No. of Bars

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200/400 923A162G01 1 2.0/2.0 0.6B-0.2/0.3B-0.5 C100/C200 22.5 14.7 25 260

300/600 923A162G02 1 2.0/2.0 0.3B-0.2/0.3B-0.9 C100/C200 22.5 14.7 25 260

400/800 923A162G03 1 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 22.5 14.7 25 260

500/1000 923A162G04 1 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 22.5 14.7 25 260

600/1200 923A162G05 1 2.0/1.5 0.3B-0.9/0.3B-1.8 C200/C400 22.5 14.7 25 260

800/1600 923A162G06 1 2.0/1.25 0.3B-0.9/0.3B-1.8 C200/C400 22.5 14.7 25 260

1000/2000 923A162G07 1 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 22.5 14.7 25 260

1500/3000 923A162G08 2 2.0/1.33 0.3B-1.8/0.3B-1.8 C400/C800 22.5 14.7 25 260

2000/4000 923A162G09 2 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 22.5 14.7 25 260

2500/5000 923A162G10 3 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 22.5 14.7 25 260

Primary Amps

Style Number

No. of Bars

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A161G01 1 2.0 0.3B-0.9 C200 22.5 14.7 25 260

1200 923A161G02 1 1.5 0.3B-1.8 C400 22.5 14.7 25 260

2000 923A161G03 1 1.0 0.3B-1.8 C800 22.5 14.7 25 260

3000 923A161G04 2 1.33 0.3B-1.8 C800 22.5 14.7 25 260

4000 923A161G05 2 1.0 0.3B-1.8 C800 22.5 14.7 25 260

5000 923A161G06 3 1.0 0.3B-1.8 C800 22.5 14.7 25 260

1500 923A161G07 1 2.0 0.3B-1.8 C800 22.5 14.7 25 260

6000 923A161G08 3 1.0 0.3B-1.8 C800 22.5 14.7 25 260

600 923A161G09 1 2.0 0.3B-0.9 C800 22.5 14.7 25 260

3200 923A161G10 2 1.0 0.3B-1.8 C800 22.5 14.7 25 260

Bar dimensions (in)

42-940

Note: Base dimensions same as tube type KOTD

25.00

4.00

1.12

1.75

1.75

23.88

.56

Ø.56 8-TOTAL

.50

3.00

TYPE KOTD-150

5 kV - 36 kV Current Transformers

25 kV, 150 kV BILSingle, double, & multi-ratio50/60 HertzBar type 5" IDConsult factory for designs up to four secondaries. 1VAP701211

TYPE KOTD-150Bar typeSingle ratio

TYPE KOTD-150Bar typeDouble ratio

TYPE KOTD-150Bar typeMulti ratio

* Accuracy 20% less at 50 Hertz

122 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 123

1VAP701221-DB & 1VAP701222-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 F030200X1NC 0.15SB-0.1 (1-400% Inom) 0.3B-0.2 (1-300% Inom)

4.0/3.0 20.75 34.5 13.50 133

300 F030300X1NC 0.15SB-0.2 (1-400% Inom) 0.3B-0.5 (1-300% Inom)

4.0/3.0 20.75 34.5 13.50 133

400 F030400X1NC 0.15SB-0.5 (1-400% Inom) 0.3B-0.9 (1-300% Inom)

4.0/3.0 20.75 34.5 13.50 133

500 F030500X1NC 0.15SB-0.5 (1-400% Inom) 0.3B-0.9 (1-300% Inom)

4.0/3.0 20.75 34.5 13.50 133

600 F030600X1NC 0.15SB-0.9 (1-400% Inom) 0.3B-1.8 (1-300% Inom)

4.0/3.0 20.75 34.5 13.50 133

800 F030800X1NC 0.15SB-0.9 (1-400% Inom) 0.3B-1.8 (1-300% Inom)

4.0/3.0 20.75 34.5 13.50 133

1000 F031000X1NC 0.15SB-1.8 (1-400% Inom) 4.0 20.75 34.5 13.50 133

1200 F031200X1NC 0.15SB-1.8 (1-400% Inom) 4.0 20.75 34.5 13.50 133

1500 F031500X1NC 0.15SB-1.8 (1-300% Inom) 3.0 20.75 34.5 13.50 133

2000 F032000X1NC 0.15SB-1.8 (1-200% Inom) 2.0 20.75 34.5 13.50 133

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 F030200S1 0.3B-0.2 C60 3.0 20.75 22.0 13.50 133

300 F030300S1 0.3B-0.5 C100 3.0 20.75 22.0 13.50 133

400 F030400S1 0.3B-0.9 C120 3.0 20.75 22.0 13.50 133

500 F030500S1 0.3B-1.8 C150 3.0 20.75 22.0 13.50 133

600 F030600S1 0.3B-1.8 C200 3.0 20.75 22.0 13.50 133

800 F030800S1 0.3B-1.8 C300 2.0 20.75 22.0 13.50 133

1000 F031000S1 0.3B-1.8 C350 2.0 20.75 22.0 13.50 133

1200 F031200S1 0.3B-1.8 C400 2.0 20.75 22.0 13.50 133

1500 F031500S1 0.3B-1.8 C500 2.0 20.75 22.0 13.50 133

2000 F032000S1 0.3B-1.8 C600 2.0 20.75 22.0 13.50 133

2500 F032500S1 0.3B-1.8 C800 2.0 20.75 22.0 13.50 133

3000 F033000S1 0.3B-1.8 C800 2.0 20.75 22.0 13.50 133

4000 F034000S1 0.3B-1.8 C800 1.5 20.75 22.0 13.50 133

5000 F035000S1 0.3B-1.8 C800 1.1 20.75 22.0 13.50 133

200/400 F030200D1 0.3B-0.5/0.3B-0.9 C60/C120 3.0/3.0 20.75 34.5 13.50 133

300/600 F030300D1 0.3B-0.5/0.3B-1.8 C100/C200 3.0/3.0 20.75 34.5 13.50 133

400/800 F030400D1 0.3B-0.9/0.3B-1.8 C150/C300 2.0/2.0 20.75 34.5 13.50 133

600/1200 F030600D1 0.3B-1.8/0.3B-1.8 C200/C400 2.0/2.0 20.75 34.5 13.50 133

1000/2000 F031000D1 0.3B-1.8/0.3B-1.8 C300/C600 2.0/2.0 20.75 34.5 13.50 133

1500/3000 F031500D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 20.75 34.5 13.50 133

.50

.753.256.508.00

4.00

8.00

4.88

9.75

9/16" DIA. (4) PLACES

Mounting base dimensions (in. [mm])

TYPE LGX-25-585Highaccuracy

5 kV - 36 kV Current Transformers

TYPE LG(X)-25-585Outdoor25 kV, 150 kV BIL60 HertzTube type4.5" ID

Consult factory for designs up to four secondaries.

TYPE LG-25-585

One second thermal/mechanical rating: 80x full winding Inom unlimited mechanical.

IC Approval AE-0703 is noted by bold style number.

Available in multi-ratio designs (full tap ratings same as single ratio above).

Available with a primary bar kit (maximum 5500 A). Change last digit of style from 1 to 3.

One second thermal/mechanical rating: 100x full winding Inom unlimited mechanical.

124 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 125

1VAP701231-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 F092015S159-1 0.3B-0.1 C150 2.0 23.0 22.0 17.75 218

300 F093015S209-1 0.3B-0.5 C200 2.0 23.0 22.0 17.75 218

400 F094015S309-1 0.3B-0.9 C300 2.0 23.0 22.0 17.75 218

600 F096015S409-1 0.3B-1.8 C400 2.0 23.0 22.0 17.75 218

800 F098015S609-1 0.3B-1.8 C600 2.0 23.0 22.0 17.75 218

1000 F091025S809-1 0.3B-1.8 C800 2.0 23.0 22.0 17.75 218

1200 F091225S809-1 0.3B-1.8 C800 2.0 23.0 22.0 17.75 218

1500 F091525S809-1 0.3B-1.8 C800 2.0 23.0 22.0 17.75 218

2000 F092025S809-1 0.3B-1.8 C500 2.0 23.0 22.0 17.75 218

2500 F092525S809-1 0.3B-1.8 C800 2.0 23.0 22.0 17.75 218

3000 F093025S809-1 0.3B-1.8 C800 1.5 23.0 22.0 17.75 218

4000 F094025S809-1 0.3B-1.8 C800 1.5 23.0 22.0 17.75 218

5000 F095025S809-1 0.3B-1.8 C800 1.5 23.0 22.0 17.75 218

6000 F096025S809-1 0.3B-1.8 C800 1.5 23.0 22.0 17.75 218

8000 F098025S809-1 0.3B-1.8 C800 1.25 23.0 22.0 17.75 218

10000 F091035S809-1 0.3B-1.8 C800 1.0 23.0 22.0 17.75 218

200/400 F092015D159-1 0.3B-0.5/0.3B-0.9 C150/C300 2.0/2.0 23.0 22.0 17.75 218

300/600 F093015D209-1 0.3B-0.5/0.3B-0.9 C200/C400 2.0/2.0 23.0 22.0 17.75 218

400/800 F094015D309-1 0.3B-0.9/0.3B-1.8 C300/C600 2.0/2.0 23.0 22.0 17.75 218

600/1200 F096015D409-1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 23.0 22.0 17.75 218

1000/2000 F091025D409-1 0.3B-1.8/0.3B-1.8 C250/C500 2.0/2.0 23.0 22.0 17.75 218

1500/3000 F091525D809-1 0.3B-1.8/0.3B-1.8 C800/C800 2.0/1.5 23.0 22.0 17.75 218

Mounting base dimensions (in)

.50

.753.256.508.00

4.00

8.00

4.88

9.75

9/16" DIA. (4) PLACES

5 kV - 36 kV Current Transformers

TYPE LG-25-879Outdoor25 kV, 150 kV BIL60 HertzTube type4.5" ID

Consult factory for designs up to four secondaries.

One second thermal/mechanical rating: 80x full winding Inom unlimited mechanical

Available in multi-ratio designs (full tap ratings same as single ratio above).

Available with a primary bar kit (maximum 5500 A). Change last digit of style from 1 to 3.

126 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 127

Primary Amps

Style Number

0.15/0.3 accuracy range

IEEE Metering Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight(lbs.)

400 F040400X1NC 400/4 to 1200 A 0.15B-0.5 4.0 23.63 22.0 17.75 160

600 F040600X1NC 600/6 to 2400 A 0.15B-0.9 4.0 23.63 22.0 17.75 160

800 F040800X1NC 800/8 to 3200 A 0.15B-0.9 4.0 23.63 22.0 17.75 160

1000 F041000X1NC 100/10 to 3000 A 0.15B-0.9 3.0 23.63 22.0 17.75 160

1200 F041200X1NC 120/12 to 3600 A 0.15B-1.8 3.0 23.63 22.0 17.75 160

1500 F041500X1NC 100/15 to 3000 A 0.15B-1.8 2.0 23.63 22.0 17.75 160

2000 F042000X1NC 200/20 to 3000 A 0.15B-1.8 2.0 23.63 22.0 17.75 160

Mounting base dimensions (in)

.50

.753.256.508.00

4.00

8.00

4.88

9.75

9/16" DIA. (4) PLACES

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 F040200S1 0.3B-0.2 C50 2.0 23.63 22.0 17.75 160

300 F040300S1 0.3B-0.5 C100 2.0 23.63 22.0 17.75 160

400 F040400S1 0.3B-0.5 C100 2.0 23.63 22.0 17.75 160

600 F040600S1 0.3B-0.9 C200 2.0 23.63 22.0 17.75 160

800 F040800S1 0.3B-0.9 C200 2.0 23.63 22.0 17.75 160

1000 F041000S1 0.3B-1.8 C250 2.0 23.63 22.0 17.75 160

1200 F041200S1 0.3B-1.8 C400 2.0 23.63 22.0 17.75 160

1500 F041500S1 0.3B-1.8 C400 2.0 23.63 22.0 17.75 160

2000 F042000S1 0.3B-1.8 C500 2.0 23.63 22.0 17.75 160

2500 F042500S1 0.3B-1.8 C600 2.0 23.63 22.0 17.75 160

3000 F043000S1 0.3B-1.8 C800 2.0 23.63 22.0 17.75 160

4000 F044000S1 0.3B-1.8 C800 1.5 23.63 22.0 17.75 160

5000 F045000S1 0.3B-1.8 C800 1.5 23.63 22.0 17.75 160

6000 F046000S1 0.3B-1.8 C800 1.0 23.63 22.0 17.75 160

8000 F048000S1 0.3B-1.8 C800 1.0 23.63 22.0 17.75 160

10000 F0410000S1 0.3B-1.8 C800 1.0 23.63 22.0 17.75 160

200/400 F040200D1 0.3B-0.2/0.3B-0.5 C50/C100 2.0/2.0 23.63 22.0 17.75 160

300/600 F040300D1 0.3B-0.5/0.3B-0.9 C100/C200 2.0/2.0 23.63 22.0 17.75 160

400/800 F040400D1 0.3B-0.5/0.3B-0.9 C100/C200 2.0/2.0 23.63 22.0 17.75 160

600/1200 F040600D1 0.3B-0.9/0.3B-1.8 C200/C400 2.0/2.0 23.63 22.0 17.75 160

1000/2000 F041000D1 0.3B-1.8/0.3B-1.8 C250/C500 2.0/2.0 23.63 22.0 17.75 160

1500/3000 F041500D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 23.63 22.0 17.75 160

2000/4000 F042000D1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/1.5 23.63 22.0 17.75 160

3000/6000 F043000D1 0.3B-1.8/0.3B-1.8 C800/C800 1.5/1.0 23.63 22.0 17.75 160

TYPE LGX-25-6513Highaccuracy

5 kV - 36 kV Current Transformers

TYPE LG(X)-25-6513Outdoor25 kV, 150 kV BIL60 HertzTube type8.75" ID

Consult factory for designs up to four secondaries.

TYPE LG-25-6513

One second thermal/mechanical rating: 100x full winding Inom unlimited mechanical

Available in multi-ratio designs (full tap ratings same as single ratio above).

IC Approval (AE-1104) is noted by bold style number.

1VAP701241-DB

One second thermal/mechanical rating: 80x full winding Inom unlimited mechanical

128 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 129

1VAP429283-DB

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200 E-923A433G01 0.15B-1.8 + 1.5 20.0 13.0 14.59 110

1000 E-923A433G02 0.15B-1.8 + 1.5 20.0 13.0 14.59 110

11.25 [286]

10.00 [254]

8.63 [219]

10.50 [267]

.44 [11]

.72 [18]

.63 [16]

.44 X .88[11 X 22]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])TYPE KOR-20ER

Outdoor 34.5 kV, 200 kV BIL50/60 Hertz

Extended Range(0.15% accuracy from 1% of Inom thru rating factor)

Thermal Rating:All styles 100 x normal, 1 second Creep: 36.5" (927 mm)

+ Not to be used for relay applications.

5 kV - 36 kV Current Transformers

Note: These units encapsulated with HCEP material.

130 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 131

1VAP429282-DB

Mounting base dimensions (in. [mm])

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

10 E-7524A22G01 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

15 E-7524A22G02 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

20 E-7524A22G03 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

25 E-7524A22G04 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

30 E-7524A22G05 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

40 E-7524A22G06 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

50 E-7524A22G07 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

75 E-7524A22G08 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

100 E-7524A22G09 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

150 E-7524A22G10 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

200 E-7524A22G11 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

300 E-7524A22G12 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

400 E-7524A22G13 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

500 E-7524A22G14 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

600 E-7524A22G15 0.3B-0.9 C100 3.0 20.0 13.0 14.59 110

800 E-7524A22G16 0.3B-0.9 C200 1.5 20.0 13.0 14.59 110

1200 E-7524A22G17 0.3B-0.9 C200 1.0 20.0 13.0 14.59 110

11.25 [286]

10.00 [254]

8.63 [219]

10.50 [267]

.44 [11]

.72 [18]

.63 [16]

.44 X .88[11 X 22]SLOTS4-TOTAL

NAMEPLATE

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy*

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5/10 E-7524A21G01 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

10/20 E-7524A21G02 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

20/40 E-7524A21G03 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

25/50 E-7524A21G04 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

50/100 E-7524A21G05 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

75/150 E-7524A21G06 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

100/200 E-7524A21G07 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

150/300 E-7524A21G08 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

200/400 E-7524A21G09 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

300/600 E-7524A21G10 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

400/800 E-7524A21G11 0.3B-0.9/0.3B-1.8 C100/C200 3.0/1.5 20.0 13.0 14.59 110

600/1200 E-7524A21G12 0.3B-0.9/0.3B-1.8 C100/C200 2.0/1.0 20.0 13.0 14.59 110

TYPE KOR-20

5 kV - 36 kV Current Transformers

Outdoor 36 kV, 200 kV BIL50/60 Hertz

Mechanical Rating:All styles single ratio: 290 x normalAll styles double ratio: 290 TAP, 145 FULL

Thermal Rating:All styles 100 x normal, 1 second

Creep: 36.5" (927 mm)

KOR-20Single ratio

KOR-20Double ratio

Note: These units encapsulated with HCEP material; also available with polyurethane.

Higher metering and relaying accuracies available.

* Accuracy 20% less at 50 Hertz.

132 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 133

Primary Amps

Style Number

IEEE Metering Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 G094015X050-1 0.15B-0.5/0.3B-0.9 3.0 25.38 31.0 17.75 232

600 G096015X090-1 0.15B-0.9/0.3B-1.8 4.0 25.38 31.0 17.75 232

800 G098015X090-1 0.15B-0.9/0.3B-1.8 4.0 25.38 31.0 17.75 232

1000 G091025X180-1 0.15B-1.8/0.3B-1.8 4.0 25.38 31.0 17.75 232

1200 G091225X180-1 0.15B-1.8/0.3B-1.8 4.0 25.38 31.0 17.75 232

1500 G091525X180-1 0.15B-1.8/0.3B-1.8 3.0 25.38 31.0 17.75 232

2000 G092025X180-1 0.15B-1.8/0.3B-1.8 2.0 25.38 31.0 17.75 232

Primary Amps

Style Number

IEEE Metering Accuracy

Relay Accuracy

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs)

200 G092015S159-1 0.3B-0.1 C150 2.0 25.38 31.0 17.75 232

300 G093015S209-1 0.3B-0.2 C200 2.0 25.38 31.0 17.75 232

400 G094015S309-1 0.3B-0.5 C300 2.0 25.38 31.0 17.75 232

600 G096015S409-1 0.3B-1.8 C400 2.0 25.38 31.0 17.75 232

800 G098015S609-1 0.3B-1.8 C600 2.0 25.38 31.0 17.75 232

1000 G091025S809-1 0.3B-1.8 C800 2.0 25.38 31.0 17.75 232

1200 G091225S809-1 0.3B-1.8 C800 2.0 25.38 31.0 17.75 232

1500 G091525S809-1 0.3B-1.8 C800 2.0 25.38 31.0 17.75 232

2000 G092025S809-1 0.3B-1.8 C800 2.0 25.38 31.0 17.75 232

2500 G092525S809-1 0.3B-1.8 C800 2.0 25.38 31.0 17.75 232

3000 G093025S809-1 0.3B-1.8 C800 1.5 25.38 31.0 17.75 232

4000 G094025S809-1 0.3B-1.8 C800 1.5 25.38 31.0 17.75 232

5000 G095025S809-1 0.3B-1.8 C800 1.5 25.38 31.0 17.75 232

6000 G096025S809-1 0.3B-1.8 C800 1.5 25.38 31.0 17.75 232

8000 G098025S809-1 0.3B-1.8 C800 1.25 25.38 31.0 17.75 232

10000 G091035S809-1 0.3B-1.8 C800 1.0 25.38 31.0 17.75 232

200/400 G092015D109-1 0.3B-0.5/0.3B-0.9 C100/C200 2.0/2.0 25.38 31.0 17.75 232

300/600 G093015D209-1 0.3B-0.5/0.3B-1.8 C200/C400 2.0/2.0 25.38 31.0 17.75 232

400/800 G094015D309-1 0.3B-0.9/0.3B-1.8 C300/C600 2.0/2.0 25.38 31.0 17.75 232

600/1200 G096015D409-1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 25.38 31.0 17.75 232

1000/2000 G091025D409-1 0.3B-1.8/0.3B-1.8 C400/C800 2.0/2.0 25.38 31.0 17.75 232

1500/3000 G091525D809-1 0.3B-1.8/0.3B-1.8 C800/C800 2.0/1.5 25.38 31.0 17.75 232

1VAP701252-DB & 1VAP701252-DB

Mounting base dimensions (in)

.50

.753.256.508.00

4.00

8.00

4.88

9.75

9/16" DIA. (4) PLACESNote: Metric dimensions are displayed in [mm].

TYPE LGX-34-879Highaccuracy

5 kV - 36 kV Current Transformers

TYPE LG(X)-34-87934500 VoltsOutdoor200 kV BIL60 HertzTube type4.5" ID

Consult factory for designs up to four secondaries.

TYPE LG-34-879

One second thermal/mechanical rating: 100x full winding Inom unlimited mechanical.

Available in multi-ratio designs (full tap ratings same as single ratio above).

One second thermal/mechanical rating: 80x full winding Inom unlimited mechanical.

Available with a primary bar kit (maxiumum 5500 A). Change last digit of style from 1 to 3.

134 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 135

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A171G01 2.0 0.3B-0.9 C200 25 15.3 17 260

1200 923A171G02 2.0 0.3B-1.8 C400 25 15.3 17 260

2000 923A171G03 1.0 0.3B-1.8 C800 25 15.3 17 260

3000 923A171G04 1.33 0.3B-1.8 C800 25 15.3 17 260

4000 923A171G05 1.0 0.3B-1.8 C800 25 15.3 17 260

5000 923A171G06 1.0 0.3B-1.8 C800 25 15.3 17 260

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200/400 923A170G01 2.0/2.0 0.6B-0.2/0.3B-0.5 C100/C200 25 14.7 17 260

300/600 923A170G02 2.0/2.0 0.3B-0.2/0.3B-0.9 C100/C200 25 14.7 17 260

400/800 923A170G03 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 25 14.7 17 260

500/1000 923A170G04 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 25 14.7 17 260

600/1200 923A170G05 2.0/2.0 0.3B-0.9/0.3B-1.8 C200/C400 25 14.7 17 260

800/1600 923A170G06 2.0/2.0 0.3B-0.9/0.3B-1.8 C200/C400 25 14.7 17 260

1000/2000 923A170G07 2.0/2.0 0.3B-1.8/0.3B-1.8 C400/C800 25 14.7 17 260

1500/3000 923A170G08 2.0/1.5 0.3B-1.8/0.3B-1.8 C400/C800 25 14.7 17 260

2000/4000 923A170G09 2.0/1.25 0.3B-1.8/0.3B-1.8 C400/C800 25 14.7 17 260

2500/5000 923A170G10 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 25 14.7 17 260

Primary Amps

Style Number

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 923A203G01 2.0 0.3B-0.5 C200 25 14.7 17 260

600 923A203G02 2.0 0.3B-0.9 C200 25 14.7 17 260

800 923A203G03 2.0 0.3B-1.8 C400 25 14.7 17 260

1000 923A203G04 2.0 0.3B-1.8 C400 25 14.7 17 260

1200 923A203G05 1.5 0.3B-1.8 C400 25 14.7 17 260

1600 923A203G06 1.25 0.3B-1.8 C400 25 14.7 17 260

2000 923A203G07 1.0 0.3B-1.8 C800 25 14.7 17 260

3000 923A203G08 1.33 0.3B-1.8 C800 25 14.7 17 260

4000 923A203G09 1.0 0.3B-1.8 C800 25 14.7 17 260

5000 923A203G10 1.0 0.3B-1.8 C800 20 14.7 17 260

Mounting base dimensions (in)

42-940

7.50

.75

9.00

13.50 .75

15.00

TYPE KOTD-200

5 kV - 36 kV Current Transformers

36 kV, 200 kV BILSingle, double, & multi-ratio50/60 HertzTube type 5" IDConsult factory for 4" ID and for designs up to four secondaries.

TYPE KOTD-200Tube typeSingle ratio

TYPE KOTD-200Tube typeDouble ratio

TYPE KOTD-200Tube typeMulti ratio

* Accuracy 20% less at 50 Hertz

136 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 137

Primary Amps

Style number

No. of bars

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

600 923A177G01 1 2.0 0.3B-0.9 C200 25 14.7 25 275

1200 923A177G02 1 1.5 0.3B-1.8 C400 25 14.7 25 275

2000 923A177G03 1 1.0 0.3B-1.8 C800 25 14.7 25 275

3000 923A177G04 2 1.33 0.3B-1.8 C800 25 14.7 25 275

4000 923A177G05 2 1.0 0.3B-1.8 C800 25 14.7 25 275

5000 923A177G06 3 1.0 0.3B-1.8 C800 25 14.7 25 275

Primary Amps

Style number

No. of bars

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

200/400 923A176G01 1 2.0/2.0 0.6B-0.2/0.3B-0.5 C100/C200 25 14.7 25 275

300/600 923A176G02 1 2.0/2.0 0.3B-0.2/0.3B-0.9 C100/C200 25 14.7 25 275

400/800 923A176G03 1 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 25 14.7 25 275

500/1000 923A176G04 1 2.0/2.0 0.3B-0.5/0.3B-1.8 C200/C400 25 14.7 25 275

600/1200 923A176G05 1 2.0/1.5 0.3B-0.9/0.3B-1.8 C200/C400 25 14.7 25 275

800/1600 923A176G06 1 2.0/1.25 0.3B-0.9/0.3B-1.8 C200/C400 25 14.7 25 275

1000/2000 923A176G07 1 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 25 14.7 25 275

1500/3000 923A176G08 2 2.0/1.33 0.3B-1.8/0.3B-1.8 C400/C800 25 14.7 25 275

2000/4000 923A176G09 2 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 25 14.7 25 275

2500/5000 923A176G10 3 2.0/1.0 0.3B-1.8/0.3B-1.8 C400/C800 25 14.7 25 275

Primary Amps

Style number

No. of bars

Rating Factor

IEEE Metering Accuracy

Relay* Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

400 923A175G01 1 2.0 0.3B-0.5 C200 25 14.7 25 275

600 923A175G02 1 2.0 0.3B-0.9 C200 25 14.7 25 275

800 923A175G03 1 2.0 0.3B-1.8 C400 25 14.7 25 275

1000 923A175G04 1 2.0 0.3B-1.8 C400 25 14.7 25 275

1200 923A175G05 1 1.5 0.3B-1.8 C400 25 14.7 25 275

1600 923A175G06 1 1.25 0.3B-1.8 C400 25 14.7 25 275

2000 923A175G07 1 1.0 0.3B-1.8 C800 25 14.7 25 275

3000 923A175G08 2 1.33 0.3B-1.8 C800 25 14.7 25 275

4000 923A175G09 2 1.0 0.3B-1.8 C800 25 14.7 25 275

5000 923A175G10 3 1.0 0.3B-1.8 C800 25 14.7 25 275

Bar dimensions (in)

42-940

Note: Base dimensions same as tube type KOTD

25.00

4.00

1.12

1.75

1.75

23.88

.56

Ø.56 8-TOTAL

.50

3.00

TYPE KOTD-200

5 kV - 36 kV Current Transformers

36 kV, 200 kV BILSingle, double, & multi-ratio50/60 HertzBar type 5" IDConsult factory for designs up to four secondaries.

TYPE KOTD-200Bar typeSingle ratio

TYPE KOTD-200Bar type Double ratio

TYPE KOTD-200Bar typeMulti ratio

* Accuracy 20% less at 50 Hertz

138 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 139

Primary VoltageStyle

Number RatioIEEE Metering

Accuracy 1Height

(in.)Width (in.)

Length (in.)

Weight (lbs.)

2400/4160Y 7525A50G01 20:1 0.3W, X, M Y 6.90 6.37 9.63 32

4200/4200Y 7525A50G02 35:1 0.3W, X, M Y 6.90 6.37 9.63 32

4800/4800Y 7525A50G03 40:1 0.3W, X, M Y 6.90 6.37 9.63 32

1VAP429511-DB

Mounting base dimensions (in)

9.31

5.50

7.388.44

6.38

Indicating fuses are Type CLE-PT, 1.0, 5.5 kV, Style number 50C5225G06

Non-indicating fuses are Type CLE-PT, 2.0, 5.5 kV, Style number 9626A33H03

2400/4160Y 7525A51G01 20:1 0.3W, X, M Y 8.25 6.75 10.00 36

4200/4200Y 7525A51G02 35:1 0.3W, X, M Y 8.25 6.75 10.00 36

4800/4800Y 7525A51G03 40:1 0.3W, X, M Y 8.25 6.75 10.00 36

2400/4160GY 7525A52G01 20:1 0.3W, X, M Y 8.56 6.37 10.00 34

4200/4200GY 2 7525A52G02 35:1 0.3W, X, M Y 8.56 6.37 10.00 34

4800/4800GY 2 7525A52G03 40:1 0.3W, X, M Y 8.56 6.37 10.00 34

2400/4160Y 7525A54G01 20:1 0.3W, X, M Y 6.90 6.37 9.63 32

4200/4200Y 7525A54G02 35:1 0.3W, X, M Y 6.90 6.37 9.63 32

4800/4800Y 7525A54G03 40:1 0.3W, X, M Y 6.90 6.37 9.63 32

2400/4160GY 7525A55G01 20:1 0.3W, X, M Y 6.90 6.37 9.63 32

4200/4200GY 2 7525A55G02 35:1 0.3W, X, M Y 6.90 6.37 9.63 32

4800/4800GY 2 7525A55G03 40:1 0.3W, X, M Y 6.90 6.37 9.63 32

2400/4160GY 4 9628A11G01 20:1 0.3W, X, M Y 8.51 6.38 9.63 37

4200/4200GY 4 9628A11G01 35:1 0.3W, X, M Y 8.51 6.38 9.63 37

4800/4800GY 4 9628A11G01 40:1 0.3W, X, M Y 8.51 6.38 9.63 37

2400/4160Y 9628A12G01 20:1 0.3W, X, M Y 8.20 6.38 9.63 39

4200/4200Y 9628A12G02 35:1 0.3W, X, M Y 8.20 6.38 9.63 39

4800/4800Y 9628A12G03 40:1 0.3W, X, M Y 8.20 6.38 9.63 39

TYPE VIY-60

5 kV - 36 kV Voltage Transformers

Indoor 60 kV BIL60 Hertz*

Contact factory for 50 Hz designs.

Thermal Rating: 1

1000 VA at 30°C700 VA at 55°C

Unfused

2 fuses

1 fuse4

Switchgear style3

Switchgear style3 4

1 fuse,non-indicating

2 fuses,non-indicating1 Thermal and accuracy ratings for 120 V secondary voltage.

UL Recognized Component

One fuse

Two fuses

Unfused

2 Fluxed for line-to-line voltage; when connected line-to-ground, normal secondary voltage is 69.3 volts.

3 Switchgear style is similar to fused style except fuse, fuse clips, and secondary terminal cover are omitted.

4 One fully insulated primary terminal for line-to-ground connection only.

140 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 141

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2400/4160Y 20:1 E-7525A85G01 0.3W, X, M, Y 12.39 11.25 10.61 40

4200/4200Y 35:1 E-7525A85G02 0.3W, X, M, Y 12.39 11.25 10.61 40

4800/4800Y 40:1 E-7525A85G03 0.3W, X, M, Y 12.39 11.25 10.61 40

1VAP429611-DB

9.36[238]

8.49[216]

.44[11]

6.24[158]7.61[193]

.68[17]

.44 x .88[11 x 22]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])TYPE VOY-60

5 kV - 36 kV Voltage Transformers

Outdoor60 kV BIL60 Hertz

Thermal rating:1000 VA @ 30°C ambient

Creep: 15.8" (401 mm)

Contact factory for 50 Hz designs.

Note: These units encapsulated with HCEP material; also available with polyurethane.

142 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 143

2400/4160Y 7525A67G01 20:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

4200/7280Y 7525A67G02 35:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

4800/8320Y 7525A67G03 40:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

7200/7200Y 7525A67G04 60:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2400/4160Y 7525A66G01 20:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

4200/7280Y 7525A66G02 35:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

4800/8320Y 7525A66G03 40:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

7200/7200Y 7525A66G04 60:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

1VAP429551-DB

Mounting base dimensions (in)

13.13

8.00

12.25

10.25

9.00

2400/4160GY 7525A68G01 20:1 0.3W, X, M Y, Z 12.18 9.25 15.50 67

4200/7280GY 7525A68G02 35:1 0.3W, X, M Y, Z 12.18 9.25 15.50 67

4800/8320GY 7525A68G03 40:1 0.3W, X, M Y, Z 12.18 9.25 15.50 67

7200/7200GY 7525A68G04 60:1 0.3W, X, M Y, Z 12.18 9.25 15.50 67

Accessories for line-to-line units:Fuse kit to convert unfused VIZ-75 to fused style (two fuses and hardware): 7527A98G01

Accessories for line-to-ground units:Fuse kit to convert unfused VIZ-75 to fused style (one fuse and hardware): 7527A98G02

2400/4160Y 7525A70G01 20:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

4200/7280Y 7525A70G02 35:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

4800/8320Y 7525A70G03 40:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

7200/7200Y 7525A70G04 60:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

2400/4160GY 7525A71G01 20:1 0.3W, X, M Y, Z 9.81 9.25 13.12 65

4200/7280GY 7525A71G02 35:1 0.3W, X, M Y, Z 9.81 9.25 13.12 65

4800/8320GY 7525A71G03 40:1 0.3W, X, M Y, Z 9.81 9.25 13.12 65

7200/7200GY 7525A71G04 60:1 0.3W, X, M Y, Z 9.81 9.25 13.12 65

2400/4160Y 9628A17G01 20:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

4200/7280Y 9628A17G02 35:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

4800/8320Y 9628A17G03 40:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

7200/7200Y 9628A17G04 60:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

Replacement fuses:CLE-PT, 0.5, 15.5 kV: 50C5225G03CLE-PT, 1.0, 15.5 kV: 50C5225G08

TYPE VIZ-75

5 kV - 36 kV Voltage Transformers

Indoor 75 kV BIL60 Hertz

Contact factory for 50 Hz designs.

Thermal Rating: 1500 VA at 30°C1000 VA at 55°C

VIZ-7575 kV BILUnfused

VIZ-7575 kV BIL2 fuses

VIZ-7575 kV BIL1 fuse

UL Recognized Component

One fuse

Two fuses

VIZ-7575 kV BILSwitchgear style 3

VIZ-7575 kV BILSwitchgear style 3 4

VIZ-7575 kV BILFuse clips onlyFour terminals

144 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 145

Mounting base dimensions (in)

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2400/4160Y 923A125G01 20:1 0.15W thru Y 11.25 9.25 15.50 69

4160/4160Y 923A125G12 34:67:1 0.15W thru Y 11.25 9.25 15.50 69

4200/7280Y 923A125G02 35:1 0.15W thru Y 11.25 9.25 15.50 69

4800/8320Y 923A125G03 40:1 0.15W thru Y 11.25 9.25 15.50 69

7200/7200Y 923A125G04 60:1 0.15W thru Y 11.25 9.25 15.50 69

13.13

8.00

12.25

10.25

9.00

TYPE VIZ-75E

5 kV - 36 kV Voltage Transformers

VIZ-75E75 kV BIL2 fusesSpecial high accuracy

Indoor 75 kV BIL60 Hertz

Thermal Rating: 1500 VA at 30°C1000 VA at 55°C

Contact factory for 50 Hz designs.

146 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 147

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2400/4160Y 20:1 7881A94G010.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

4200/7280Y 35:1 7881A94G020.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

4800/8320Y 40:1 7881A94G030.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

7200/7200Y 60:1 7881A94G040.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

Mounting base dimensions (in. [mm])

12.25 [311]

.44 [11]

10.00 [254]

.44 [11]

8.63[219]

10.75 [273]

1.25 [32]

.44 X 1.69[11 X 43]SLOTS4-TOTAL

NAMEPLATE

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2400/4160Y 20:1 E-7525A89G01 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

4200/7280Y 35:1 E-7525A89G02 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

4800/8320Y 40:1 E-7525A89G03 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

7200/7200Y 60:1 E-7525A89G04 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

1VAP429631-DB

12.25 [311]

.44 [11]

10.00 [254]

.44 [11]

8.63[219]

10.75 [273]

1.25 [32]

.44 X 1.69[11 X 43]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])

TYPE VOZ-75EOutdoor75 kV BIL60 Hertz

Thermal Rating:1500 VA @ 30°C Ambient

VOZ-75E75 kV BILSpecial high accuracy

5 kV - 36 kV Voltage Transformers

TYPE VOZ-75

Outdoor75 kV BIL60 Hertz

Note: These units encapsulated with HCEP material; also available with polyurethane.

Thermal rating:1500 VA @ 30°C ambient

Creep: 28.2" (716 mm)

148 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 149

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2400/4160Y 7883A12G01 20:1 0.3Y 13.94 12.38 12.0 105

4200/7280Y 7883A12G02 35:1 0.3Y 13.94 12.38 12.0 105

4800/8320Y 7883A12G03 40:1 0.3Y 13.94 12.38 12.0 105

7200/12470Y 7883A12G04 60:1 0.3Y 13.94 12.38 12.0 105

7620/13200Y 7883A12G05 63.5:1 0.3Y 13.94 12.38 12.0 105

8400/14560Y 7883A12G06 70:1 0.3Y 13.94 12.38 12.0 105

12000/12000Y 7883A12G07 100:1 0.3Y 13.94 12.38 12.0 105

7970/13800Y 7883A12G08 110:1 0.3Y 13.94 12.38 12.0 105

6928/12000Y 7883A12G09 120:1 0.3Y 13.94 12.38 12.0 105

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2400/4160Y 7881A93G01 20:1 0.3Z 13.94 15.55 12.0 105

4200/7280Y 7881A93G02 35:1 0.3Z 13.94 15.55 12.0 105

4800/8320Y 7881A93G03 40:1 0.3Z 13.94 15.55 12.0 105

7200/12470Y 7881A93G04 60:1 0.3Z 13.94 15.55 12.0 105

7620/13200Y 7881A93G05 63.5:1 0.3Z 13.94 15.55 12.0 105

8400/14560Y 7881A93G06 70:1 0.3Z 13.94 15.55 12.0 105

12000/12000Y 7881A93G07 100:1 0.3Z 13.94 15.55 12.0 105

13200/13200Y 7881A93G08 110:1 0.3Z 13.94 15.55 12.0 105

14400/14400Y 7881A93G09 120:1 0.3Z 13.94 15.55 12.0 105

1VAP429581-DB

Mounting base dimensions (in)

.438 x 1.188 SLOT2-TOTAL

12.38 10.75

.44

11.1312.00

Ø.442-TOTAL

.44

TYPES VIL-95 and VIL-95S

5 kV - 36 kV Voltage Transformers

Indoor 95 kV BIL60 Hertz

Thermal Rating: VIL-95: VIL-95S:1500 VA at 30°C 750 VA at 30°C1000 VA at 55°C 500 VA at 55°C

TYPE VIL-95(junction box)

TYPE VIL-95S(cable leads)

Contact factory for 50 Hz designs.

UL Recognized Component

150 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 151

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 9628A17G05 60:1 0.3W, X, M, Y, Z 11.25 9.25 15.50 69

7620/13200Y 9628A17G06 63.5:1 0.3W, X, M, Y, Z 11.25 9.25 15.50 69

8400/14560Y 9628A17G07 70:1 0.3W, X, M, Y, Z 11.25 9.25 15.50 69

12000/12000Y 9628A17G08 100:1 0.3W, X, M, Y, Z 11.25 9.25 15.50 69

13200/13200Y 9628A17G09 110:1 0.3W, X, M, Y, Z 11.25 9.25 15.50 69

14400/14400Y 9628A17G10 120:1 0.3W, X, M, Y, Z 11.25 9.25 15.50 69

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470GY 7525A71G05 60:1 0.3W, X, M Y, Z 9.81 9.25 13.12 65

8400/14560GY 7525A71G07 70:1 0.3W, X, M Y, Z 9.81 9.25 13.12 65

12000/12000GY 7525A71G08 100:1 0.3W, X, M Y, Z 9.81 9.25 13.12 65

14400/14400GY 7525A71G10 120:1 0.3W, X, M Y, Z 9.81 9.25 13.12 65

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 7525A70G05 60:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

8400/14560Y 7525A70G07 70:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

12000/12000Y 7525A70G08 100:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

14400/14400Y 7525A70G10 120:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 7525A66G05 60:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

8400/14560Y 7525A66G07 70:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

12000/12000Y 7525A66G08 100:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

14400/14400Y 7525A66G10 120:1 0.3W, X, M Y, Z 9.00 9.25 13.12 65

1VAP429551-DB

Mounting base dimensions (in)

13.13

8.00

12.25

10.25

9.00

Optional accessories for line-to-line units:Fuse kit to convert unfused VIZ-11 to fused style: (two fuses and hardware) 7527A98G01

Optional accessories for line-to-ground units:Fuse kit to convert unfused VIZ-11 to fused style: (one fuse and hardware) 7527A98G02

Replacement fuses:CLE-PT, 0.5, 15.5 kV 50C5225G03CLE-PT, 1.0, 15.5 kV 50C5225G08

TYPE VIZ-11

5 kV - 36 kV Voltage Transformers

Indoor 110 kV BIL60 Hertz

Contact factory for 50 Hz designs.

Thermal Rating:1500 VA at 30°C1000 VA at 55°C

VIZ-11110 kV BILUnfused

UL Recognized Component

One fuse

Two fuses

VIZ-11110 kV BILSwitchgear style

VIZ-11110 kV BILSwitchgear style

VIZ-11110 kV BILFuse clips onlyFour terminals

152 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 153

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470GY 7525A68G05 60:1 0.3W, X, M Y, Z 12.18 9.25 15.50 67

8400/14560GY 7525A68G07 70:1 0.3W, X, M Y, Z 12.18 9.25 15.50 67

12000/12000GY 7525A68G08 100:1 0.3W, X, M Y, Z 12.18 9.25 15.50 67

14400/14400GY 7525A68G10 120:1 0.3W, X, M Y, Z 12.18 9.25 15.50 67

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 7525A67G05 60:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

8400/14560Y 7525A67G07 70:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

12000/12000Y 7525A67G08 100:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

14400/14400Y 7525A67G10 120:1 0.3W, X, M Y, Z 11.25 9.25 15.50 69

1VAP429551-DB

Mounting base dimensions (in)

13.13

8.00

12.25

10.25

9.00

Optional accessories for line-to-line units:Fuse kit to convert unfused VIZ-11 to fused style: (two fuses and hardware) 7527A98G01

Optional accessories for line-to-ground units:Fuse kit to convert unfused VIZ-11 to fused style: (one fuse and hardware) 7527A98G02

Replacement fuses:CLE-PT, 0.5, 15.5 kV 50C5225G03CLE-PT, 1.0, 15.5 kV 50C5225G08

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

2400/4160GY 7525A65G02 20:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

4200/7280GY 7525A65G03 35:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

4800/8320GY 7525A65G05 40:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

7200/12470GY 7525A65G13 60:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

7620/13200GY 7525A65G16 63.5:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

8400/14560GY 7525A65G09 70:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

12000/12000GY 7525A65G12 100:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

13200/13200GY 7525A65G15 110:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

14400/14400GY 7525A65G18 120:1 0.3W, X, M, Y, Z 12.18 9.25 13.12 67

TYPE VIZ-11 (cont’d)

5 kV - 36 kV Voltage Transformers

Indoor 110 kV BIL60 Hertz

Thermal Rating:1500 VA at 30°C1000 VA at 55°C

UL Recognized Component

VIZ-11110 kV BIL2 fuses

VIZ-11110 kV BIL1 fuse

VIZ-11110 kV BILFuse clips onlyTwo terminals

154 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 155

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 923A125G05 60:1 0.15W thru Y 11.25 9.25 15.50 69

7620/13200Y 923A125G06 63.5:1 0.15W thru Y 11.25 9.25 15.50 69

8400/14560Y 923A125G07 70:1 0.15W thru Y 11.25 9.25 15.50 69

12000/12000Y 923A125G08 100:1 0.15W thru Y 11.25 9.25 15.50 69

13200/13200Y 923A125G09 110:1 0.15W thru Y 11.25 9.25 15.50 69

14400/14400Y 923A125G10 120:1 0.15W thru Y 11.25 9.25 15.50 69

Mounting base dimensions (in)

13.13

8.00

12.25

10.25

9.00

TYPE VIZ-11E

5 kV - 36 kV Voltage Transformers

Indoor 75 kV and 110 kV BIL60 Hertz

Thermal Rating:1500 VA at 30°C1000 VA at 55°C

UL Recognized Component

VIZ-11E110 kV BIL2 FusesSpecial high accuracy

156 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 157

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 60:1 7881A94G050.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

7620/13200Y 63.5:1 7881A94G060.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

8400/14560Y 70:1 7881A94G070.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

12000/12000Y 100:1 7881A94G080.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

13200/13200Y 110:1 7881A94G090.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

14400/14400Y 120:1 7881A94G100.15W, X, M, Y0.3W, X, M, Y, Z 15.82 12.87 14.04 75

12.25 [311]

.44 [11]

10.00 [254]

.44 [11]

8.63[219]

10.75 [273]

1.25 [32]

.44 X 1.69[11 X 43]SLOTS4-TOTAL

NAMEPLATE

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 60:1 E-7525A23G05 0.3W, X, M, Y 15.89 12.86 14.04 75

7620/13200Y 63.5:1 E-7525A23G06 0.3W, X, M, Y 15.89 12.86 14.04 75

8400/14560Y 70:1 E-7525A23G07 0.3W, X, M, Y 15.89 12.86 14.04 75

12000/12000Y 100:1 E-7525A23G08 0.3W, X, M, Y 15.89 12.86 14.04 75

13200/13200Y 110:1 E-7525A23G09 0.3W, X, M, Y 15.89 12.86 14.04 75

14400/14400Y 120:1 E-7525A23G10 0.3W, X, M, Y 15.89 12.86 14.04 75

1VAP429631-DB

Mounting base dimensions (in. [mm])

12.25 [311]

.44 [11]

10.00 [254]

.44 [11]

8.63[219]

10.75 [273]

1.25 [32]

.44 X 1.69[11 X 43]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])

Contact factory for 50 Hz designs.

5 kV - 36 kV Voltage Transformers

TYPE VOZ-11EOutdoor 110 kV BIL60 HertzSpecial high accuracy

TYPE VOY-11

Thermal Rating:1500 VA @ 30°C Ambient

Creep:28.2" (716 mm)

Note: These units encapsulated with HCEP material; also available with polyurethane.

Outdoor110 kV BIL60 Hertz

158 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 159

1VAP429651-DB

0.44 x 1.69 SLOTS4 TOTAL [11 x 43]

10.75 [273]

10.87 [276]

10.00 [254]

0.44 [11]

0.44 [11]

8.63 [219]

NAMEPLATE

Mounting base dimensions (in. [mm])

Contact factory for 50 Hz designs.

5 kV - 36 kV Voltage Transformers

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470GY 60:1 E-7525A95G01 0.3W, X, M, Y 15.82 10.87 13.75 40

7620/13200GY 63.5:1 E-7525A95G02 0.3W, X, M, Y 15.82 10.87 13.75 40

8400/14560GY 70:1 E-7525A95G03 0.3W, X, M, Y 15.82 10.87 13.75 40

TYPE VOG-11Outdoor110 kV BIL60 Hertz

Thermal Rating:1000 VA @ 30°C Ambient

Creep:24.7" (627 mm)

Note: These units encapsulated with HCEP material; also available with polyurethane.

160 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 161

1VAP429632-DB

Mounting base dimensions (in. [mm])

12.25 [311]

.44 [11]

10.00 [254]

.44 [11]

8.63[219]

10.75 [273]

1.25 [32]

.44 X 1.69[11 X 43]SLOTS4-TOTAL

NAMEPLATE

1VAP429631-DB

12.25 [311]

.44 [11]

10.00 [254]

.44 [11]

8.63[219]

10.75 [273]

1.25 [32]

.44 X 1.69[11 X 43]SLOTS4-TOTAL

NAMEPLATE

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 60:1 E-7525A89G05 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

7620/13200Y 63.5:1 E-7525A89G06 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

8400/14560Y 70:1 E-7525A89G07 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

12000/12000Y 100:1 E-7525A89G08 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

13200/13200Y 110:1 E-7525A89G09 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

14400/14400Y 120:1 E-7525A89G10 0.3W, X, M, Y, Z 15.82 12.87 14.04 75

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470GY 60:1 E-7525A91G05 0.3W, X, M, Y, Z 15.89 12.86 14.04 70

7620/13200GY 63.5:1 E-7525A91G06 0.3W, X, M, Y, Z 15.89 12.86 14.04 70

8400/14560GY 70:1 E-7525A91G07 0.3W, X, M, Y, Z 15.89 12.86 14.04 70

Mounting base dimensions (in. [mm])

5 kV - 36 kV Voltage Transformers

Contact factory for 50 Hz designs.

TYPE VOZ-11MOutdoor110 kV BIL60 Hertz

Thermal Rating:1500 VA @ 30°C Ambient

Creep:25.0" (635 mm)Note: These units encapsulated with HCEP

material; also available with polyurethane.

TYPE VOZ-11Outdoor 110 kV BIL60 Hertz

Note: These units encapsulated with HCEP material; also available with polyurethane.

Contact factory for additional designs.

Contact factory for 50 Hz designs.

Contact factory for additional designs.

Thermal Rating:1500 VA @ 30°C Ambient

Creep:28.2" (716 mm)

162 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 163

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 923A363G01 60:1 0.3Y 16.00 15.25 15.25 210

7620/13200Y 923A363G02 63.5:1 0.3Y 16.00 15.25 15.25 210

8400/14560Y 923A363G03 70:1 0.3Y 16.00 15.25 15.25 210

12000/20780Y 923A363G04 100:1 0.3Y 16.00 15.25 15.25 210

14400/24940Y 923A363G05 120:1 0.3Y 16.00 15.25 15.25 210

18000/18000Y 923A363G06 150:1 0.3Y 16.00 15.25 15.25 210

24000/24000Y 923A363G07 200:1 0.3Y 16.00 15.25 15.25 210

Primary Voltage

Style Number Ratio

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7200/12470Y 923A362G01 60:1 0.3Z 16.00 15.25 17.75 210

7620/13200Y 923A362G02 63.5:1 0.3Z 16.00 15.25 17.75 210

8400/14560Y 923A362G03 70:1 0.3Z 16.00 15.25 17.75 210

12000/20780Y 923A362G04 100:1 0.3Z 16.00 15.25 17.75 210

14400/24940Y 923A362G05 120:1 0.3Z 16.00 15.25 17.75 210

18000/18000Y 923A362G06 150:1 0.3Z 16.00 15.25 17.75 210

24000/24000Y 923A362G07 200:1 0.3Z 16.00 15.25 17.75 210

1VAP429581-DB

Mounting base dimensions (in)

Ø.44 x 1.25 SLOT4-TOTAL

15.25

15.2514.38

12.75

TYPES VIL-12 and VIL-12S

5 kV - 36 kV Voltage Transformers

Indoor 125 kV BIL60 Hertz

Thermal Rating: VIL-12: VIL-12S:1500 VA at 30°C 1000 VA at 30°C1000 VA at 55°C 500 VA at 55°C

TYPE VIL-12(junction box)

TYPE VIL-12S(cable leads)

Contact factory for 50 Hz designs.

UL Recognized Component

164 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 165

Primary Voltage

Winding Ratio

Style Number

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

18000/18000Y 150:1 9628A33G01 1.1 10.50 10.25 13.0 110

21000/21000Y 175:1 9628A33G02 1.1 10.50 10.25 13.0 110

24000/24000Y 200:1 9628A33G03 1.1 10.50 10.25 13.0 110

1VAP429762-DB

Mounting base dimensions (in)

Primary Voltage

Winding Ratio

Style Number

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20780GY 100:1 7881A72G01 1.25 12.13 8.0 16.0 102

14400/24940GY 120:1 7881A72G02 1.25 12.13 8.0 16.0 102

16000/27600GY 133.33:1 7881A72G03 1.25 12.13 8.0 16.0 102

18000/18000GY 150:1 7881A72G04 1.1 12.13 8.0 16.0 102

1VAP429762-DB

Mounting base dimensions (in)

16.00

7.87

15.00

5.62

.44 X 1.19SLOT4-TOTAL

12000/20780GY 100:1 7881A64G01 1.25 14.88 8.0 19.0 105

14400/24940GY 120:1 7881A64G02 1.25 14.88 8.0 19.0 105

13.0012.00

8.00

10.25

8.75

.44 X 1.94SLOT4-TOTAL

.44 X 1.19SLOT4-TOTAL

TYPE VIZ-12

5 kV - 36 kV Voltage Transformers

Indoor 125 kV BIL60 HertzUnfused

Thermal Rating: 2000 VA @ 30°C ambient1500 VA @ 55°C ambientUnfused

IEEE Metering Accuracy: 0.3W, X, M, Y, Z & 1.2 ZZ

Contact factory for 50 Hz designs.

Fuse kit: Style # 9628A05G72 (for remote mounting) Contains two CLE-PT fuses-0.5, 25.5 kV (style # 50C5225G04) and hardware)

TYPE VIZ-12GIndoor 125 kV BIL60 Hertz

Thermal Rating: 1500 VA @ 30°C Ambient750 VA @ 55°C Ambient

IEEE Metering Accuracy: 0.3W, X, M, Y, & Z

TYPE VIZ-12G Unfused

TYPE VIZ-12G Fused

Fuse kit: Style # 9628A05G68 to convert unfused VIZ-12G to fused style Contains one CLE-PT fuse-0.5, 25.5 kV (style # 50C5225G04) and hardware

166 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 167

Primary Voltage

Winding Ratio

Style Number

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

27600/27600Y 240:1 9628A34G01 1.1 12.10 10.25 13.0 120

34500/34500Y 300:1 9628A34G02 1.1 12.10 10.25 13.0 120

24940/24940Y 207.83:1 9628A34G03 1.1 12.10 10.25 13.0 120

24000/24000Y 200:1 9628A34G05 1.1 12.10 10.25 13.0 120

26400/26400Y 220:1 9628A34G06 1.1 12.10 10.25 13.0 120

1VAP429761-DB

Mounting base dimensions (in)

Primary Voltage

Winding Ratio

Style Number

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20780GY 100:1 9629A81G01 1.1 12.10 10.25 13.57 120

14400/24940GY 120:1 9629A81G02 1.1 12.10 10.25 13.57 120

19920/34500GY 166:1 9629A81G03 1.1 12.10 10.25 13.57 120

24000/24000GY 200:1 9629A81G04 1.1 12.10 10.25 13.57 120

1VAP429761-DB

Mounting base dimensions (in)

12000/20780GY 100:1 9629A82G01 1.1 14.82 10.25 17.9 122

14400/24940GY 120:1 9629A82G02 1.1 14.82 10.25 17.9 122

16100/27900GY 140:1 9629A82G03 1.1 14.82 10.25 17.9 122

24000/24000GY 200:1 9629A82G04 1.1 14.82 10.25 17.9 122

13.0012.00

8.00

10.25

8.75

.44 X 1.94SLOT4-TOTAL

.44 X 1.19SLOT4-TOTAL

13.0012.00

8.00

10.25

8.75

.44 X 1.94SLOT4-TOTAL

.44 X 1.19SLOT4-TOTAL

TYPE VIZ-15

5 kV - 36 kV Voltage Transformers

Indoor 150 kV BIL60 HertzUnfused

Thermal Rating: 2000 VA @ 30°C ambient1500 VA @ 55°C ambient

IEEE Metering Accuracy: 0.3W, X, M, Y, Z & 1.2 ZZ

Contact factory for 50 Hz designs.

Fuse kit: Style # 9628A05G86 (for remote mounting) Contains two CLE-PT fuses-0.5, 25.5 kV (style # 50C5225G04) and hardware

TYPE VIZ-15GIndoor 150 kV BIL60 Hertz

Thermal Rating: 2000 VA @ 30°C Ambient1500 VA @ 55°C Ambient

IEEE Metering Accuracy: 0.3W, X, M, Y, and Z

TYPE VIZ-15G Unfused

Fuse kit: style # 9628A05G89 to convert unfused VIZ-15G to fused style Contains one CLE-PT fuse-0.5, 25.5 kV (style # 50C5225G04) and hardware

TYPE VIZ-15G Fused

168 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 169

11500/20000GY 166.67&166.67:1 7883A29G03* 1000 1.2 22.3 15.6 18.6 205

13800/23900GY 200 & 200:1 7883A29G02* 2000 1.9 22.3 15.6 18.6 205

16800/29100GY 140 & 240:1 7883A29G01* 3000 1.9 22.3 15.6 18.6 205

Primary Voltage

Winding Ratio

Style Number

Thermal Rating

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20800Y 100:1 7525A81G01 3000 1.1 22.3 16 18.6 205

14400/24940Y 120:1 7525A81G02 3000 1.1 22.3 16 18.6 205

15600/15600Y 130:1 7525A81G12 3000 1.1 22.3 16 18.6 205

18000/18000Y 150:1 7525A81G03 3000 1.1 22.3 16 18.6 205

20000/20000Y 166.67:1 7525A81G05 3000 1.1 22.3 16 18.6 205

24000/24000Y 200:1 7525A81G04 3000 1.1 22.3 16 18.6 205

1VAP429591-DB

Mounting base dimensions (in)

12000/20800Y 100 & 100:1 7526A47G02 3000 1.1 22.3 16 18.6 205

14400/24940Y 120 & 120:1 7526A47G03 3000 1.1 22.3 16 18.6 205

18000/18000Y 150 & 150:1 7526A47G04 3000 1.1 22.3 16 18.6 205

24000/24000Y 200 & 200:1 7526A47G05 3000 1.1 22.3 16 18.6 205

.75 .75

1.75

1.25 1.25

1.25

1.25

1.25 1.25

1.38

.50

.75 1.13

.44

14.50

.44

15.00

.438 x 1.688 SLOTWITH .219 RADIUS6-TOTAL

Ø.438 HOLE6-TOTAL

.438 x .938 SLOTWITH .219 RADIUS4-TOTAL

.50

12000/20800Y 100:1 7525A82G01 3000 1.1 22.3 16 18.6 205

14400/24940Y 120:1 7525A82G02 3000 1.1 22.3 16 18.6 205

18000/18000Y 150:1 7525A82G03 3000 1.1 22.3 16 18.6 205

24000/24000Y 200:1 7525A82G04 3000 1.1 22.3 16 18.6 205

12000/20800GY 100:1 7525A83G01 3000 1.1 22.3 15.6 18.6 205

14400/24940GY 120:1 7525A83G02 3000 1.1 22.3 15.6 18.6 205

20000/20000GY 166.67:1 7525A83G04 3000 1.1 22.3 15.6 18.6 205

22000/22000GY 183.3:1 7525A83G06 3000 1.1 22.3 15.6 18.6 205

12000/20800GY 100:1 7525A84G01 3000 1.1 22.3 15.6 18.6 205

14400/24940GY 120:1 7525A84G02 3000 1.1 22.3 15.6 18.6 205

18000/18000GY 150:1 7525A84G05 3000 1.1 22.3 15.6 18.6 205

20000/20000GY 166.67:1 7525A84G03 3000 1.1 22.3 15.6 18.6 205

24000/24000GY 200:1 7525A84G04 3000 1.1 22.3 15.6 18.6 205

TYPES VIZZ-15 and VIZZ-15G

5 kV - 36 kV Voltage Transformers

Indoor/outdoor 150 kV BIL60 Hertz

Available at other ratios and single tapped secondary or double secondary

IEEE Metering Accuracy:0.3W, X, M, Y, Z and ZZ(except where noted*)

Consult factory if replacement for PT-25 is desired

VIZZ-15 Two bushingsStud terminalSingle secondary

VIZZ-15 Two bushings Stud terminal Double secondary

Contact factory for 50 Hz designs.

VIZZ-15 Two bushingsClamp terminalSingle secondary

VIZZ-15G One bushingStud terminalSingle secondary

VIZZ-15G One bushingStud terminalDouble secondary

VIZZ-15G One bushingClamp terminalSingle secondary

* IEEE metering accuracy: 0.3W, X, M, Y, Z

170 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 171

1VAP429671-DB

Mounting base dimensions (in. [mm])

0.44 x 1.69 SLOTS4 TOTAL [11 x 43]

10.75 [273]

10.87 [276]

10.00 [254]

0.44 [11]

0.44 [11]

8.63 [219]

NAMEPLATE

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20780Y 100:1 E-7525A87G01 0.3W, X, M, Y 15.89 12.86 14.04 75

14400/24940Y 120:1 E-7525A87G02 0.3W, X, M, Y 15.89 12.86 14.04 75

18000/18000Y 150:1 E-7525A87G03 0.3W, X, M, Y 15.89 12.86 14.04 75

24000/24000Y 200:1 E-7525A87G04 0.3W, X, M, Y 15.89 12.86 14.04 75

1VAP429661-DB

12.25 [311]

.44 [11]

10.00 [254]

.44 [11]

8.63[219]

10.75 [273]

1.25 [32]

.44 X 1.69[11 X 43]SLOTS4-TOTAL

NAMEPLATE

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20780GY 100:1 E-7525A97G01 0.3W, X, M, Y 15.82 10.87 13.75 40

14400/24940GY 120:1 E-7525A97G02 0.3W, X, M, Y 15.82 10.87 13.75 40

Mounting base dimensions (in. [mm])

5 kV - 36 kV Voltage Transformers

Contact factory for 50 Hz designs.

TYPE VOG-12Outdoor125 kV BIL60 Hertz

Thermal Rating:750 VA @ 30°C Ambient

Creep:24.7" (627 mm)

TYPE VOY-12

Outdoor125 kV BIL60 Hertz

Thermal Rating:1000 VA @ 30°C Ambient

Creep:28.2" (716 mm)

Note: These units encapsulated with HCEP material; also available with polyurethane.

172 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 173

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20780Y 100:1 E-7526A62G01 0.3W, X, M, Y 19.00 15.97 16.94 125

14400/24940Y 120:1 E-7526A62G02 0.3W, X, M, Y 19.00 15.97 16.94 125

18000/18000Y 150:1 E-7526A62G03 0.3W, X, M, Y 19.00 15.97 16.94 125

20000/20000Y 166.7:1 E-7526A62G04 0.3W, X, M, Y 19.00 15.97 16.94 125

24000/24000Y 200:1 E-7526A62G05 0.3W, X, M, Y 19.00 15.97 16.94 125

1VAP429701-DB

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20780Y 100:1 E-7525A90G01 0.3W, X, M, Y, Z 19.00 15.97 16.94 125

14400/24940Y 120:1 E-7525A90G02 0.3W, X, M, Y, Z 19.00 15.97 16.94 125

18000/18000Y 150:1 E-7525A90G03 0.3W, X, M, Y, Z 19.00 15.97 16.94 125

24000/24000Y 200:1 E-7525A90G04 0.3W, X, M, Y, Z 19.00 15.97 16.94 125

1VAP429711-DB

Mounting base dimensions (in. [mm])

12.00 [305]

.44 [11]

1.25 [32]

.44 [11]

10.00 [254]

12.88 [327]

1.25 [32]

.44 X 1.69[11 X 43]

SLOT WITH.22 [6] RADIUS

4-TOTAL

Ø.44 [11]4-TOTAL

NAMEPLATE

8.63[219]

12000/20780GY 100:1 E-7526A63G01 0.3W, X, M, Y 19.00 15.41 16.94 120

14400/24940GY 120:1 E-7526A63G02 0.3W, X, M, Y 19.00 15.41 16.94 120

12000/20780Y 100:1 923A398G01 0.15W, X, Y 19.00 15.87 16.94 125

14400/24940Y 120:1 923A398G02 0.15W, X, Y 19.00 15.87 16.94 125

18000/18000Y 150:1 923A398G03 0.15W, X, Y 19.00 15.87 16.94 125

24000/24000Y 200:1 923A398G04 0.15W, X, Y 19.00 15.87 16.94 125

12.00 [305]

.44 [11]

1.25 [32]

.44 [11]

10.00 [254]

12.88 [327]

1.25 [32]

.44 X 1.69[11 X 43]

SLOT WITH.22 [6] RADIUS

4-TOTAL

Ø.44 [11]4-TOTAL

NAMEPLATE

8.63[219]

Note: Metric dimensions are displayed in [mm].

Mounting base dimensions (in. [mm])TYPES VOY-15 and VOY-15G

5 kV - 36 kV Voltage Transformers

Outdoor150 kV BIL60 Hertz

Thermal Rating:1000 VA @ 30°C Ambient

Creep:VOY-15: 38.0" (965 mm)VOY-15G: 33.6" (853 mm)

Contact factory for 50 Hz designs.

TYPES VOZ-15 and VOZ-15EOutdoor150 kV BIL60 Hertz

Thermal Rating:2000 VA @ 30°C Ambient

Creep:38.0" (965 mm)

VOY-15G

Note: These units encapsulated with HCEP material; also available with polyurethane.

VOY-15

VOZ-15

VOZ-15E Special High Accuracy (Only available in polyurethane)

174 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 175

Primary Voltage Ratio

Style Number1 Thermal VA

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20800GY 100:1 7525A98G01 3000 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

14400/24940GY 120:1 7525A98G02 3000 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

13200/22860GY 110:1 7525A98G03 3000 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

14400/24940GY 120:1 7525A98G04 1200 0.3W, X, M, Y, Z, Z 23.0 15.6 17.6 202

7200/12470GY 60:1 7525A98G05 3000 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

8000/13860GY 66.67:1 7525A98G06 3000 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

24000/24000GY 200:1 7525A98G07 3000 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

12000/20800GY 100:1 7525A98G08 1000 0.3W, X, M, Y, Z, ZZ 23.0 15.6 17.6 202

Primary Voltage Ratio

Style Number1 Thermal VA

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

12000/20800Y 100:1 7525A93G01 3000 0.3W, X, M, Y, Z, ZZ 23.0 16.1 17.6 205

14400/24940Y 120:1 7525A93G02 3000 0.3W, X, M, Y, Z, ZZ 23.0 16.1 17.6 205

18000/18000Y 150:1 7525A93G03 3000 0.3W, X, M, Y, Z, ZZ 23.0 16.1 17.6 205

24000/24000Y 200:1 7525A93G04 3000 0.3W, X, M, Y, Z, ZZ 23.0 16.1 17.6 205

21000/21000Y 175 :1 7525A93G12 3000 0.3W, X, M, Y, Z, ZZ 23.0 16.1 17.6 205

19920/19920Y 166 :1 7525A93G13 3000 0.3W, X, M, Y, Z, ZZ 23.0 16.1 17.6 205

Mounting base dimensions (in)

1VAP429781-DB

.75 .75

1.75

1.25 1.25

1.25

1.25

1.25 1.25

1.38

.50

.75 1.13

.44

14.50

.44

15.00

.438 x 1.688 SLOTWITH .219 RADIUS6-TOTAL

Ø.438 HOLE6-TOTAL

.438 x .938 SLOTWITH .219 RADIUS4-TOTAL

.50

1Style includes clamp type primary terminals. Stud type available for spade terminals.

TYPES VOZZ-15 and VOZZ-15G

5 kV - 36 kV Voltage Transformers

Outdoor150 kV BIL60 Hertz

VOZZ-15GOne bushing

Available with double secondaries and tapped double secondaries.

VOZZ-15Two bushings

176 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 177

Primary Voltage

Winding Ratio

Style Number

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

20125/34500GY 175:1 7883A61G01 1.4 16.5 10.0 19.13 148

34500/34500GY 300:1 7883A61G02 1.1 16.5 10.0 19.13 148

19942/34500GY 289:1 7883A61G04 1.1 16.5 10.0 19.13 148

16100/27900GY 240:1 7883A61G05 1.4 16.5 10.0 19.13 148

Primary Voltage

Winding Ratio

Style Number

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

20125/34500Y 175:1 7883A60G03 1.1 16.5 16.26 19.13 161

27600/27600Y 240:1 7883A60G02 1.1 16.5 16.26 19.13 161

34500/34500Y 300:1 7883A60G01 1.1 16.5 16.26 19.13 161

1VAP429601-DB

Mounting base dimensions (in)

Primary Voltage

Winding Ratio

Style Number

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

20125/34500Y 175:1 7883A40G03 1.1 16.5 16.26 19.13 165

27600/27600Y 240:1 7883A40G02 1.1 16.5 16.26 19.13 165

34500/34500Y 300:1 7883A40G01 1.1 16.5 16.26 19.13 165

Primary Voltage

Winding Ratio

Style Number

Rated Voltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

20125/34500GY 175:1 7883A41G01 1.4 16.5 10.0 19.13 150

34500/34500GY 300:1 7883A41G02 1.1 16.5 10.0 19.13 150

24000/24000GY 200:1 7883A41G05 1.4 16.5 10.0 19.13 150

25000/25000GY 208.33:1 7883A41G06 1.1 16.5 10.0 19.13 150

26400/26400GY 220:1 7883A41G07 1.1 16.5 10.0 19.13 150

24900/24900GY 207.5:1 7883A41G08 1.1 16.5 10.0 19.13 150

28800/28800GY 240:1 7883A41G09 1.1 16.5 10.0 19.13 150

27600/27600GY 240:1 7883A41G10 1.1 16.5 10.0 19.13 150

10.00

19.13

8.75

12.81

NAMEPLATE

Ø.554-TOTAL

TYPES VIZ-20 and VIZ-20G

5 kV - 36 kV Voltage Transformers

Indoor200 kV BIL60 Hertz

Thermal Rating:1000 VA @ 30°C Ambient750 VA @ 55°C Ambient

IEEE Metering Accuracy:0.3W, X, M, Y, Z and ZZ

VIZ-20 Unfused

VIZ-20 Fused

Contact factory for 50 Hz designs.

VIZ-20G Unfused

VIZ-20G Fused

Fuse kit: Style # 9628A05G90 (to convert unfused VIZ-20 to fused style) Contains two CLE-PT fuses (0.5, 38 kV, style # 50C5225G05) and hardware

Fuse kit: Style # 9628A05G83 (to convert unfused VIZ-20G to fused style) Contains one CLE-PT fuse (0.5, 38 kV style # 50C5225G05) and hardware

178 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 179

1VAP429741-DB

12.00 [305]

.44 [11]

1.25 [32]

.44 [11]

10.00 [254]

12.88 [327]

1.25 [32]

.44 X 1.69[11 X 43]

SLOT WITH.22 [6] RADIUS

4-TOTAL

Ø.44 [11]4-TOTAL

NAMEPLATE

8.63[219]

Mounting base dimensions (in. [mm])

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

27600/27600Y 240:1 E-7881A82G03 0.3 W, X, M, Y 19.0 15.97 16.94 125

34500/34500Y 275:1 E-7881A82G04 0.3 W, X, M, Y 19.0 15.97 16.94 125

Contact factory for 50 Hz designs.

TYPES VOY-20 and VOY-20G

TYPE VOY-20

Note: These units encapsulated with HCEP material; also available with polyurethane.

5 kV - 36 kV Voltage Transformers

TYPE VOY-20G

Outdoor200 kV BIL60 HertzThermal Rating:1000 VA @ 30°C Ambient

Creep:VOY-20: 38.0" (965 mm)VOY-20G: 33.6" (853 mm)

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

20125/34500GY 175/300:1 E-7526A55G01 0.3 W, X, M, Y 19.0 15.41 16.93 120

20125/34500GY 175:1 E-9629A74G01 0.3 W, X, M, Y 19.0 15.41 16.93 120

180 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 181

Primary Voltage Ratio

Style Number

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

20125/34500Y 175/300:1 E-7525A92G01 0.3 W, X, M, Y, Z 19.0 15.97 16.94 125

27600/27600Y 240/400:1 E-7525A92G02 0.3 W, X, M, Y, Z 19.0 15.97 16.94 125

34500/34500Y 300/500:1 E-7525A92G03 0.3 W, X, M, Y, Z 19.0 15.97 16.94 125

20125/34500Y 175:1 E-7526A33G05 0.3 W, X, M, Y, Z 19.0 15.97 16.94 125

1VAP429751-DB

12.00 [305]

.44 [11]

1.25 [32]

.44 [11]

10.00 [254]

12.88 [327]

1.25 [32]

.44 X 1.69[11 X 43]

SLOT WITH.22 [6] RADIUS

4-TOTAL

Ø.44 [11]4-TOTAL

NAMEPLATE

8.63[219]

Mounting base dimensions (in. [mm])

5 kV - 36 kV Voltage Transformers

Contact factory for 50 Hz designs.

TYPE VOZ-20Outdoor200 kV BIL60 Hertz

Thermal rating:2000 VA @ 30°C Ambient

Creep:38.0" (965 mm)

Note: These units encapsulated with HCEP material; also available with polyurethane.

182 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 183

20125/34500GY175/300:1

& 175/300:19629A97G01 0.3W, X, M, Y, Z, ZZ 27.54 17.0 24.3 380

20125/34500GY 175/300:1 7882A42G01 0.3W, X, M, Y, Z, ZZ 27.54 17.0 24.3 380

Primary Voltage Ratio

Style Number1

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

20125/34500Y 175/300:1 7882A31G01 0.3W, X, M, YFull and Tap

22.6 18.9 20.0 255

27600/27600Y 240/400:1 7882A31G02 0.3W, X, M, YFull and Tap

22.6 18.9 20.0 255

34500/34500Y 300/500:1 7882A31G03 0.3W, X, M, YFull and Tap

22.6 18.9 20.0 255

Mounting base dimensions (in)

20125/34500GY 175/300:1 9629A95G01 0.3W, X, M, YFull and Tap

23.3 16.1 20.0 245

42-977

7.37

14.74

5.12

4.79

12.75

16.75

17.50

Primary Voltage Ratio

Style Number1

IEEE Metering Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

27600/27600Y 240 & 240:1 9629A96G02 0.3W, X, M, Y, Z, ZZ 26.13 18.1 24.3 380

34500/34500Y 300 & 300:1 9629A96G01 0.3W, X, M, Y, Z, ZZ 26.13 18.1 24.3 380

Mounting base dimensions (in)

1VAP429791-DB

15.50

17.87

8.2516.5020.50

TYPES VOHD-200 & VOHD-200G

5 kV - 36 kV Voltage Transformers

Outdoor200 kV BIL60 Hertz

Thermal Rating:1000 VA @ 30°C Ambient

Creep:VOHD-200: 37.5" (953 mm)VOHD-200G: 37.75" (959 mm)

TYPES VOZZ-20 and VOZZ-20GOutdoor200 kV BIL60 HertzThermal Rating:3000 VA @ 30°C Ambient

Creep:VOZZ-20: 41.0" (1041 mm)VOZZ-20G: 41.875" (1063 mm)Tapped and single secondaries available.

1Style includes clamp type primary terminals. Stud type available for spade terminals.

Contact factory for 50 Hz designs.

VOHD-200Two bushings

VOHD-200GOne bushing

VOZZ-20Two bushings

VOZZ-20GOne bushing

184 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 185

Style Number Ratio

Rating Factor @ 30°C Accuracy

One sec. thermal/ mechanical

rating Ratio Accuracy

RatedVoltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

E-923A464G01 200:5 3.0 0.15B-0.5 190/270 7200/12470GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

E-923A464G02 200:5 1.5 0.15B-1.8 150/215 7200/12470GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

E-923A464G03 1000:5 1.5 0.15B-1.8 150/215 7200/12470GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

E-923A464G04 200:5 3.0 0.15B-0.5 190/270 7620/13200GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

E-923A464G05 200:5 1.5 0.15B-1.8 150/215 7620/13200GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

E-923A464G06 1000:5 1.5 0.15B-1.8 150/215 7620/13200GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

E-923A464G07 200:5 3.0 0.15B-0.5 190/270 8400/14560GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

E-923A464G08 200:5 1.5 0.15B-1.8 150/215 8400/14560GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

E-923A464G09 1000:5 1.5 0.15B-1.8 150/215 8400/14560GY to 120 0.3Y 1.2 21.5 12.0 14.42 90

Style Number Ratio

Rating Factor @ 30°C Accuracy

One sec. thermal/ mechanical

rating Ratio Accuracy

RatedVoltage Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

923A428G01 200:5 3.0 0.15B-0.5 190/270 60:1 0.3Y 1.9 23.34 16.64 15.63 164

923A428G02 200:5 1.5 0.15B-1.8 150/215 60:1 0.3Y 1.9 23.34 16.64 15.63 164

923A428G03 1000:5 1.5 0.15B-1.8 150/215 60:1 0.3Y 1.9 23.34 16.64 15.63 164

923A428G04 200:5 3.0 0.15B-0.5 190/270 63.5:1 0.3Y 1.9 23.34 16.64 15.63 164

923A428G05 200:5 1.5 0.15B-1.8 150/215 63.5:1 0.3Y 1.9 23.34 16.64 15.63 164

923A428G06 1000:5 1.5 0.15B-1.8 150/215 63.5:1 0.3Y 1.9 23.34 16.64 15.63 164

923A428G07 200:5 3.0 0.15B-0.5 190/270 70:1 0.3Y 1.9 23.34 16.64 15.63 164

923A428G08 200:5 1.5 0.15B-1.8 150/215 70:1 0.3Y 1.9 23.34 16.64 15.63 164

923A428G09 1000:5 1.5 0.15B-1.8 150/215 70:1 0.3Y 1.9 23.34 16.64 15.63 164

1VAP429992-DB

GROUND LUG1.13 x .44 SLOTS4-TOTAL[29] x [11]

NAMEPLATE

10.00[254]

12.25[311]

4.62[117] 10.0

[254]15.63[397]

1.13 [29]

Voltage Transformer

Voltage Transformer

Mounting base dimensions (in. [mm])

10.00 [254]

1.00 [25]

12.00 [305]

0.50 [13]

10.00 [254]

11.00 [279]

1.13 x .44 SLOTS 4-TOTAL[29 x 11]

NAMEPLATE

Mounting base dimensions (in. [mm])

1VAP429993-DB

TYPE CVC-110ER

15-36 kV Combined Current and Voltage Transformers

Outdoor, 110 kV BIL60 Hertz

Extended Range(0.15% accuracy from 1% of Inom thru rating factor)

VT Thermal Rating: 750 VACreep: 26.0" (660 mm)

Current Transformer

Contact factory for 50 Hz designs.

Note: Encapsulated in polyurethane

Current Transformer

TYPE CVC-110EROutdoor, 110 kV BIL60 Hertz

Extended Range(0.15% accuracy from 1% of Inom thru rating factor)

VT Thermal Rating: 500 VACreep: 28.1" (715 mm)

Note: Encapsulated in HCEP

186 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 187

Style Number Ratio

Rating Factor @ 30°C Accuracy

One sec. thermal/ mechanicalrating (kA)

Primary Voltage Ratio Accuracy Thermal VA

Rated Voltage Factor

E-923A470G01 600:5 2.0 0.3B-0.3 31.5/85 13200/22860GY 110:1 0.3Y 500 1.2

E-923A470G03 600:5 2.0 0.3B-0.3 31.5/85 14400/24940GY 120:1 0.3Y 500 1.2

E-923A470G04 600:5 2.0 0.3B-0.3 31.5/85 7200/12470GY 60:1 0.3Y 500 1.2

E-923A470G05 600:5 2.0 0.3B-0.3 31.5/85 7620/13200GY 63.5:1 0.3Y 500 1.2

E-923A470G06 600:5 2.0 0.3B-0.3 31.5/85 8400/14560GY 70:1 0.3Y 500 1.2

E-923A470G07 600:5 2.0 0.3B-0.3 31.5/85 12000/20780GY 100:1 0.3Y 500 1.2

Voltage Transformer

12.5[318]

10.0[254]

10.0[254]12.0[305]

NAMEPLATE

0.44 x 1.44 SLOTS4 TOTAL [11x37]

1VAP429996-DB

Mounting base dimensions (in. [mm])TYPE SCC-125

15-36 kV Combined Current and Voltage Transformers

Outdoor125 kV BIL60 HertzSplit-core combination sensor

Creep: 32" (813 mm)

Current Transformer

Unit dimensions

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

17.44 15.5 16.55 130

188 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 189

1VAP429991-DB

[422]16.63

[254]10.00

[254]10.00

[311]12.25

NAMEPLATE

[143]5.63

[32]1.25

GROUND LUG

1.13 x .44 SLOTS 4-TOTAL[29] x [11]

Voltage Transformer

Accuracy

Mounting base dimensions (in. [mm])

Style Number Ratio

Rating Factor @ 30°C C1-C3 C2-C3

MechanicalRating Ratio V1-V3 V2-V3

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7883A71G01 10/20 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

7883A71G02 25/50 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

7883A71G03 50/100 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

7883A71G04 75/150 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

7883A71G05 100/200 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

7883A71G06 150/300 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

7883A71G07 200/400 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

7883A71G08 300/600 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

7883A71G09 400/800 3.0/1.5 0.3B-2.0 0.3B-0.9 270/140 60/120:1 0.3X 0.3Y 27.5 16.63 16.63 225

TYPES CVC-150 and CVC-200*Outdoor150 kV BIL60 Hertz

VT Thermal Rating:400/750 VA

Creep:47.5" (1209 mm)

Accuracy

Current Transformer

15-36 kV Combined Current and Voltage Transformers

Contact factory for 50 Hz designs.

*Note: Contact factory for CVC-200 (200 kV BIL, 60 Hertz)

190 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 191

Volt-Ampere Rating

Style Number

Ratio Adjustment Range

50 7881A17G01 from 10.8:5 to 5:5 Amps

100 7881A17G02 from 10.8:5 to 5:5 Amps

42-852

Winding Development

Dimensions and weights

50 VA 100 VA

Height 7.00 7.00

Width 6.50 6.50

Length 6.75 7.75

Weight 20.00 24.00

Mounting base dimensions

6.50

1.25

2.255.006.75

1 2 6 87

1 2 3 10 1611

9 15 1614

40turns

70 taps @10 turn steps

taps @1 turn steps

95turns

taps @10 turn steps

28 27 taps @ 1 turn steps

4 4

- to -

- to - - to -

Main Winding Buck-Boost Winding

Stated VA are applicable for 60 Hz

240

115

COM

24V 24V RLY 240V RLY

6.88 [175]

9.00[229]

3.00[76]

4.50[114]

Application Voltage

Style Number

DC resistance (Ohms)

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

115 469-0649-951 0.5 13.5 9.38 4.63 55

120 469-0649-952 0.5 13.5 9.38 4.63 55

240 469-0649-952 1.0 13.5 9.38 4.63 55

115/240 469-0649-954 0.5/1.0 13.5 9.38 4.63 55

120/240 469-0649-955 0.5/1.0 13.5 9.38 4.63 55

TYPE A Current Balancing Auto

Custom Engineered Designs

Indoor test voltage: 2500 volts25-60 HertzType A transformers provide a large number of fine ratio adjustment taps for establishing an exact current ratio balance between the CTs on the input and output sides of power transformers.

TYPE FSR-983600 Volts Outdoor10 kV BIL60 HertzSaturable reactor

1VAP701061-DB

192 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 193

Custom Engineered Designs

TYPE PSH-993600 Volts Indoor/outdoor10 kV BIL60 Hertz

1VAP701071-DB

Digit 12Secondary5 = 5 A, xxx:51 = 1 A, xxx:1

194 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 195

Style Number Ratio

RelayAccuracy*

IEEE MeteringAccuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7881A02G01 3,4,5:0.5-1 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A02G02 3,4,5:2-4 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A02G03 6,8,10:0.5-1 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A02G04 6,8,10:0.5-1 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A02G05 6,8,10:1-2 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A02G06 6,8,10:4-8 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A02G07 4,4.62,4.8:4-8 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A03G01 4,5.33,6.4:16-32 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A03G02 3,4,5:10-20 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A03G03 3,4,5:5-10 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

7881A03G04 3,4,5:1-2 T50 0.3B-0.5, 0.6B-1.8 7.0 5.5 8.50 23

Style Number Ratio

RelayAccuracy*

IEEE MeteringAccuracy*

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

7881A01G01 5:5 T50 0.3B-0.5, 0.6B-1.8 6.37 5.75 7.75 23

7881A01G02 10:5 T50 0.3B-0.5, 0.6B-1.8 6.37 5.75 7.75 23

7881A01G03 15:5 T50 0.3B-0.5, 0.6B-1.8 6.37 5.75 7.75 23

1VAP428501-DB

Multi-ratio winding development

Tapped winding

Single ratio winding development

Auxiliary

Multi-ratio Auxiliary

Single-ratio Auxiliary

IndoorTest voltage: 1200 volts25-60 Hertz

Custom Engineered Designs

* Stated accuracies are applicable for 60 Hz.

Contact the factory for additional styles.

Two-part winding

1 2 3 4

5 6 7 8

H1 X2X1H2

196 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 197

H1X2 X1 H2

4.50

11.00 [279]

8.88 [225]

3.00[76] [114]

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

13.5 9.38 4.63 Varies

Mounting base dimensions (in. [mm])TYPE ACT-983

600 VoltsIndoor/outdoor 10 kV BIL60 Hertz

Thermal rise:55°C @ 30°C ambient

Custom Engineered Designs

When ordering ACT Auxiliary CTs, include the following information: − Current ratio: _____ (primary:secondary, i.e. 5:3.33 − Type of circuit: _____ (i.e., primary or secondary) − Accuracy and burden requirements, for example

Metering: _____ (0.3B-0.1 through B-1.8) Relaying: _____ (C100, C200, C400, or C800 or other) If IEC ratings, list class and burden _____ (e.g. class 0.2-20 VA, 5P20-40VA)

− Continuous rating factor: _____ (std. is RF=1.5) − Frequency: _____ (std is 60 Hz) − OPTIONAL - Conduit box hub size: _____ (std is 1" NPT)

Note: Units are custom manufactured to customer specifications. Contact factory to discuss other options.

1VAP701111-DB

198 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 199

1VAP701101-DB

Style Number Ratio

RelayAccuracy

Rating Factor Dim A Dim C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

A1400710-570 5:1 T100 1.5 4.0 5.9 5.63 5.75 5.9 23

A1431220-570 6:1 T100 1.5 2.0 4.2 5.63 5.75 4.2 14

A1403310-570 7.25:5 T100 1.5 4.0 6.6 5.63 5.75 6.6 25

A1400810-570 8:1 T100 1.5 3.0 4.9 5.63 5.75 4.9 19

A1403810-570 9.09:5 T100 1.5 4.0 6.6 5.63 5.75 6.6 26

A1400910-570 10:1 T100 1.5 3.0 5.4 5.63 5.75 5.4 21

A1410010-570 11.6:5 T100 1.5 4.0 6.5 5.63 5.75 6.5 23

A1404010-570 12:5 T100 1.5 4.0 6.4 5.63 5.75 6.4 24

A1422510-570 13.33:1 T100 1.5 3.5 6.0 5.63 5.75 6.0 20

A1412210-570 14:5 T100 1.5 5.0 7.4 5.63 5.75 7.4 28

Style Number Ratio

RelayAccuracy

Rating Factor Dim A Dim C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

A1509840-570 5:1 T400 1.5 2.5 5.4 7.75 7.5 5.4 31

A1507140-570 6:2 T400 1.5 4.0 7.2 7.75 7.5 7.2 49

A1504640-570 7.5:5 T400 1.5 5.0 8.2 7.75 7.5 8.2 60

A1502040-570 8:5 T400 1.5 4.63 7.9 7.75 7.5 7.9 56

A1503540-570 9.375:5 T400 1.5 5.0 8.4 7.75 7.5 8.4 61

A1509540-570 10:1 T400 1.5 5.0 7.7 7.75 7.5 7.7 56

A1511140-570 11:6 T400 1.5 6.0 8.9 7.75 7.5 8.9 68

A1513440-570 12:1 T400 1.5 5.25 9.0 7.75 7.5 9.0 56

A1514240-570 13.33:5 T400 1.5 5.0 7.9 7.75 7.5 7.9 58

A1506140-570 15:5 T400 1.5 4.0 7.2 7.75 7.5 7.2 50

Dimensions (in.) ACT-633 ACT-645

A see table above see table above

B A + 1.25 A + 2.0

C see table above see table above

D 5.0 6.50

E 5.75 7.50

F 4.38 6.38

G 5.63 7.75

Custom Engineered Designs

TYPE ACT-633/645600 Volts Indoor 10 kV BIL60 Hertz

Additional styles available upon request. Contact factory for multiple tap requirements.

TYPE ACT-633

TYPE ACT-645

A B C

D

F

G

E

N/P

ALTERNATE N/P LOCATIONWHEN DIM "A" IS LESS

N/P

THAN 3.63 [92].

H1 H2 X1 X2

200 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 201

1VAP701091-DB

Primary Voltage

Secondary Voltage

Style Number

Thermal VA

IEEE MeteringAccuracy* Dim A Dim C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

70 120 A2300030-570 500 0.6X 4.0 6.6 7.75 7.50 6.6 41

120 120 A2300018-570 500 0.6X 3.0 5.9 7.75 7.50 5.9 31

480 220 A2300016-570 2000 0.6X 6.0 8.6 7.75 7.50 8.6 61

1075 120 A2300017-570 150 0.6X 2.63 5.0 7.75 7.50 5.1 27

1200 120 A2300014-570 150 0.6X 4.0 6.0 7.75 7.50 6.0 42

Dimensions (in.) APT-646 APT-733

A see table above see table above

B A + 1.25 A + 2.0

C see table above see table above

D 5.0 6.50

E 5.75 7.50

F 4.38 6.38

G 5.63 7.75

TYPE APT-646/733600 Volts Indoor, 10 kV BIL60 Hertz

Primary Voltage

Secondary Voltage

Style Number

Thermal VA

IEEE MeteringAccuracy* Dim A Dim C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

115 115 A2900090-570 150 0.6X 2.5 5.7 5.63 5.75 5.70 15

120 120 A2900310-570 150 0.6X 2.63 5.8 5.63 5.75 5.8 15

208 120 A2900660-570 150 0.6X 3.5 6.2 5.63 5.75 6.2 20

240 240 A2900360-570 150 0.6X 4.0 7.2 5.63 5.75 7.2 23

300 120 A2900860-570 250 0.6X 4.0 6.2 5.63 5.75 6.2 21

480 120 A2900870-570 250 0.6X 3.5 5.9 5.63 5.75 5.9 19

Custom Engineered Designs

TYPE APT-646

TYPE APT-733

A B C

D

F

G

E

N/P

ALTERNATE N/P LOCATIONWHEN DIM "A" IS LESS

N/P

THAN 3.63 [92].

H1 H2 X1 X2

202 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 203

TYPE BCT-605/BH-001600 Volts Indoor60 Hertz

When ordering BCTs, include the following information: − Min. inside diameter (ID): _____ in. [mm] − Max. outside diameter (OD): _____ in. [mm] − Max. allowable height (HT): _____ in. [mm] − Current ratio and taps, if any: _____ (:5A or :1A / SR, DR, MR) − Accuracy and burden requirements, for example -

Metering: _____ (0.3B0.1 through B1.8) High accuracy: _____ (0.15) Relaying: _____ (C100, C200, C400, or C800, or other) If IEC ratings, list class and burden _____ (e.g. class 0.2-20 VA, 5P20-40 VA)

− Continuous rating factor: _____ (std. is RF=2.0) − Frequency: _____ (std is 60 Hz) − Lead length and type: _____, size - _____ (std is

#10 AWG THHN) − Used - Above oil: _____ (y/n) or Dry surroundings: _____ (y/n)

Note: Mounting hardware not supplied. Units are custom manufactured to customer specifications. Contact factory to discuss other options.

TYPE SP-061600 VoltsOutdoor10 kV BIL60 Hertz

When ordering split-core CTs, include the following information: − Min. inside diameter (ID): _____ in. [mm] − Max. outside diameter (OD): _____ in. [mm] − Max. allowable height (HT): _____ in. [mm] − Current ratio and taps, if any: _____ (:5A or :1A / SR, DR, MR) − Accuracy and burden requirements, for example -

Metering: _____ (0.3B-0.1 through B-1.8) Relaying: _____ (C100, C200, C400, or C800, or other) If IEC ratings, list class and burden _____ (e.g. class 0.2-20 VA, 5P20-40 VA)

− Continuous rating factor: _____ (std. is RF=2.0) − Frequency: _____ (std is 60 Hz) − Conduit box hub size: _____ (std is 1" NPT)

Note: Split-core CTs must be mounted flat using resin pads or mounting brackets. Units are custom manufactured to customer specifications. Contact factory to discuss other options.

Custom Engineered Designs

TYPE PSZ-981

TYPE BYZ-863/865

600 VoltsIndoor/outdoor 10 kV BIL60 Hertz

15000 & 25000 Volts Indoor/outdoor 110 kV & 150 kV BIL60 HertzPrimary current ratios:50:5 to 200:5

When ordering a 15 kV or 25 kV rated zero-sequence CT, include the following information:

− Min. inside diameter (ID): _____ in. [mm] (std min is 4.5"/phase) − Max. outside diameter (OD): _____ in. [mm] (std min. is 26") − Current ratio: _____ (standards are 50:5, 100:5, or 200:5 SR) − Accuracy and burden requirements, for example -

Relaying: _____ (standards are C50, C100, or C200) If IEC ratings, list class and burden _____ (e.g. class 5P20-40 VA)

− Continuous rating factor: _____ (std. is RF=2.0) − Frequency: _____ (std is 60 Hz) − Conduit box hub size: _____ (std is 1" NPT)

When ordering zero-sequence CT, include the following: − Min. inside diameter (ID): _____ in. [mm] − Max. outside diameter (OD): _____ in. [mm] − Max. allowable height (HT): _____ in. [mm] − Current ratio: _____ (standards are 50:5, 100:5, or 200:5 SR) − Accuracy and burden requirements, for example -

Relaying: _____ (standards are C50, C100, or C200) If IEC ratings, list class and burden _____ (e.g. class 5P20-40 VA)

− Continuous rating factor: _____ (std. is RF=2.0) − Frequency: _____ (std is 60 Hz) − Conduit box hub size: _____ (std is 1" NPT)

Note: Additional mounting options offered for zero-sequence CTs. Units are custom manufactured to customer specifications. Contact factory to discuss other options.

Note: Additional mounting options offered for zero-sequence CTs. Units are custom manufactured to customer specifications. Contact factory to discuss other options.

1VAP428582-DB

204 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 205

1VAP701121-DB

Primary Amps

Style

NumberIEEE Metering

AccuracyRelay

Accuracy

Rating factor @

30°C

Dim E Height

(in.)

Dim D Width (in.)

Dim C Length

(in.)Weight (lbs.)

2.75" x 2.75" window (Dim A and B)

300 A19R27S03-570 1.2B-0.1 C20 1.5 6.0 6.0 4.50 20

400 A19R27S04-570 1.2B-0.1 C50 1.5 6.0 6.0 4.50 20

500 A19R27S05-570 1.2B-0.1 C50 1.5 6.0 6.0 4.50 20

600 A19R27S06-570 1.2B-0.1 C75 1.5 6.0 6.0 4.50 20

800 A19R27S08-570 0.6B-0.2 C100 1.5 6.0 6.0 4.50 20

5.5" x 5.5" window (Dim A and B)

300 A19R55S03-570 1.2B-0.1 C20 1.5 8.75 8.75 4.50 27

400 A19R55S04-570 1.2B-0.1 C50 1.5 8.75 8.75 4.50 27

500 A19R55S05-570 1.2B-0.1 C50 1.5 8.75 8.75 4.50 27

600 A19R55S06-570 1.2B-0.1 C75 1.5 8.75 8.75 4.50 27

800 A19R55S08-570 0.6B-0.2 C100 1.5 8.75 8.75 4.50 27

1000 A19R55S10-570 0.6B-0.2 C100 1.5 8.75 8.75 4.50 27

1200 A19R55S12-570 0.3B-0.5 C150 1.5 8.75 8.75 4.50 27

1500 A19R55S15-570 0.3B-0.9 C150 1.5 8.75 8.75 4.50 27

1600 A19R55S16-570 0.3B-0.9 C200 1.5 8.75 8.75 4.50 27

2000 A19R55S20-570 0.3B-1.8 C200 1.5 8.75 8.75 4.50 27

9.0" x 9.0" window (Dim A and B)

600 A19R90S06-570 1.2B-0.1 C75 1.5 12.63 12.63 4.50 40

800 A19R90S08-570 0.6B-0.2 C100 1.5 12.63 12.63 4.50 40

1000 A19R90S10-570 0.6B-0.2 C100 1.5 12.63 12.63 4.50 40

1200 A19R90S12-570 0.3B-0.5 C150 1.5 12.63 12.63 4.50 40

1500 A19R90S15-570 0.3B-0.9 C150 1.5 12.63 12.63 4.50 40

1600 A19R90S16-570 0.3B-0.9 C200 1.5 12.63 12.63 4.50 40

2000 A19R90S20-570 0.3B-1.8 C200 1.5 12.63 12.63 4.50 40

3000 A19R90S30-570 0.3B-1.8 C300 1.5 12.63 12.63 4.50 40

4000 A19R90S40-570 0.3B-1.8 C400 1.0 12.63 12.63 4.50 40

D

EA

B

C

NAMEPLATE

TYPE CO-9740600 Volts Indoor10 kV BIL60 Hertz

Custom Engineered Designs

One second thermal/mechanical ratings: 80 x full winding Inom / unlimited mechanical.

206 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 207

1VAP701001-DB

1 2 3 4

7.75[197]

2.10[53]

2.30[58]

0.83 [21]

0.83 [21]

1.80+0.005-0.000

Ø 716 " 1/16" CHAMFER2-CORNERS

1.00[25]

FULL SLOT

TYPE SCADA-BEH600 Volts Indoor/outdoor 10 kV BIL60 Hertz

Primary Amps

Style Number Accuracy/Burden

Window Diam. (in.)

Rating Factor @ 30°C

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

100 A370100S47 + 10% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

150 A370150S47 + 10% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

200 A370200S47 + 5% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

250 A370250S47 + 5% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

300 A370300S47 + 3% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

300 MR A370300M47 + 2.5% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

300 MR A370300M55 TBD 4.75 2.0 10.5 8.0 2.1 8-9

400 A370400S47 + 3% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

450 A370450S47 + 3% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

450 MR A370450M47 + 2.5% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

500 A370500S47 + 3% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

600 A370600S47 + 3% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

600 A370600S55 + 3% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

600 MR A370600M55 + 2.5% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

800 A370800S55 + 3% - 2.5 VA 4.75 2.0 10.5 8.0 2.1 8-9

1000 A371000S55 + 3% - 2.5 VA 4.75 1.5 10.5 8.0 2.1 8-9

1200 A371200S55 + 3% - 2.5 VA 4.75 1.5 10.5 8.0 2.1 8-9

MR = multi ratioOne second thermal/mechanical ratings: 80 x full winding Inom / unlimited mechanical.

Catalog numbers ending in “47” have a 4¾" window; ending in “55” have a 5½" window.

Custom Engineered Designs

208 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 209

1VAP701021-DB

n = TAPS

n ------------ 1

4.75 [121]2.75 [70]

2.12

8.50

6.75

1.0 [25]

[171]

[216]

1.50 [38] .44 [11][54]

TYPE SCADA-DEH600 Volts Indoor/outdoor 10 kV BIL60 HertzPrimary current ratios:50:5 to 4000:5

Primary Amps

Style

Number Metering* Relay

WindowDiam. (in.)

Rating Factor

@ 30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

300 MR A03S0001-570 - C10 5.75 2.0 11.12 8.50 2.12 16-17

450 MR A03S0002-570 - C15 5.75 2.0 11.12 8.50 2.12 16-17

600 A03S0009-570 0.3B-0.5 – 5.75 2.0 11.12 8.50 2.12 16-17

600 MR A03S0012-570 - C25 5.75 2.0 11.12 8.50 2.12 16-17

600 A03S0014-570 0.3B-0.2 – 5.75 2.0 11.12 8.50 2.12 16-17

800 MR A03S0020-570 - C30 5.75 2.0 11.12 8.50 2.12 16-17

1200 MR A03S0018-570 - C50 5.75 2.0 11.12 8.50 2.12 16-17

MR = multi ratio. Available in single, dual, and multi-ratio designs.

Accuracy/Burden

Custom Engineered Designs

One second thermal/mechanical ratings: 80 x full winding Inom / unlimited mechanical.

* Units can be certified for revenue metering. Change “570” of catalog number to “590”.

210 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 211

8.50[216]

11.00[279]

X1X2X3X5 X4

3.00

[32]

[76]

1.25

When ordering slip-over CTs, include the following information: − Min. inside diameter (ID): _____ in. [mm] − Max. outside diameter (OD): _____ in. [mm] − Max. allowable height (HT): _____ in. [mm] − Current ratio and taps, if any: _____ (:5A or :1A / SR, DR, MR) − Accuracy and burden requirements, for example

Metering: _____ (0.3B-0.1 through B1.8) High accuracy: _____ (0.15) Relaying: _____ (C100, C200, C400, or C800, or other) If IEC ratings, list class and burden _____ (e.g. class 0.2-20 VA, 5P20-40 VA)

− Continuous rating factor: _____ (std. is RF=2.0) − Frequency: _____ (std is 60 Hz) − Conduit box hub size: _____ (std. is 1" NPT)

TYPE SCADA-CEH600 Volts Indoor/outdoor 10 kV BIL60 Hertz

Primary Amps

Style

Number Metering* Relay

WindowDiam. (in.)

Rating Factor

@ 30°CHeight

(in.)Width (in.)

Length (in.)

Weight (lbs.)

100 A0101S01-570 ±10% - 1VA - 8.13 2.0 13.8 11.0 3.0 20-22

200 A0102S01-570 1.2B-0.1 - 8.13 2.0 13.8 11.0 3.0 20-22

300 A0103S01-570 0.6B-0.1 C5 8.13 2.0 13.8 11.0 3.0 20-22

400 A0104S01-570 0.3B-0.1 C10 8.13 2.0 13.8 11.0 3.0 20-22

500 A0105S01-570 0.3B-0.2 C15 8.13 2.0 13.8 11.0 3.0 20-22

600 A0106S01-570 ±3% - 5VA C15 8.13 2.0 13.8 11.0 3.0 20-22

800 A0108S01-570 0.3B-0.5 C20 8.13 2.0 13.8 11.0 3.0 20-22

1000 A0110S01-570 0.3B-0.5 C30 8.13 2.0 13.8 11.0 3.0 20-22

1200 A0112S01-570 0.3B-0.9 C40 8.13 2.0 13.8 11.0 3.0 20-22

1500 A0115S01-570 0.3B-0.9 C50 8.13 2.0 13.8 11.0 3.0 20-22

1600 A0116S01-570 0.3B-0.9 C50 8.13 2.0 13.8 11.0 3.0 20-22

2000 A0120S01-570 0.3B-1.8 C35 8.13 2.0 13.8 11.0 3.0 20-22

2500 A0125S01-570 0.3B-1.8 C40 8.13 1.5 13.8 11.0 3.0 20-22

3000 A0130S01-570 0.3B-1.8 C50 8.13 1.33 13.8 11.0 3.0 20-22

4000 A0140S01-570 0.3B-1.8 C50 8.13 1.0 13.8 11.0 3.0 20-22

5000 A0150S01-570 0.3B-1.8 - 8.13 1.0 13.8 11.0 3.0 20-22

6000 A0160S01-570 0.3B-1.8 - 8.13 1.0 13.8 11.0 3.0 20-22

Available in dual and multi-ratio designs.

Accuracy/Burden

TYPES PS-981/PH-982600 Volts Indoor/outdoor 10 kV BIL60 Hertz

Note: Many mounting options offered. Units are custom manufactured to customer specifications. Contact factory to discuss other options.

Custom Engineered Designs

One second thermal/mechanical ratings: 60 x full winding Inom / unlimited mechanical.

* Units can be certified for revenue metering. Change “570” of catalog number to “590”.

1VAP701041-DB

1VAP701261-DB

212 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 213

Nominal current ratio

ID x OD 100:5 150:5 200:5 300:5 400:5 500:5 600:5 800:5 1000:5 1200:5 & up

RF 2.0 2.0 2.0 3.0-4.0 4.0 4.0 4.0 4.0 3.0 see note

HT 8.75" 8.75" 8" 6"-8" 6"-8" 6"-8" 6" 6" 6" 3"-6"

6 x 16

0.3B-0.1 class only

0.3B-0.2 class only

0.15B-0.2 - 5% 0.3B-0.9

0.15B-0.5 0.3B-0.9 - 10%

0.15B-0.5 - 5% 0.3B-0.9 - 10%

0.15B-0.5 - 5% 0.15B-0.9 0.3B-1.8

0.15B-1.8 - 5%

0.15B-0.9 - 5% 0.3B1.8 - 5%

0.15B-0.9 - 5% 0.15B-1.8 - 10%

0.15B-0.9 - 5% 0.15B-1.8 - 10% May be lower as ratio increases - will possibly hold accuracy down

to 1%

8 x 18

10 x 20 0.15B-0.9 - 5% 0.15B-1.8 - 10%12 x 22

0.15B-0.2 - 10% 0.3B-0.9

14 x 24

0.15B-0.5 - 5% 0.15B-0.9 0.3B-1.8

16 x 26

0.15B-0.2 0.3B-0.9

18 x 280.15B-0.2 0.3B-0.9

20 x 30

22 x 32

24 x 34

0.3B-0.1 - 5% 0.3B-0.2/B-0.4

0.6B-0.5

0.15B-0.2 - 5% 0.15B-0.5 0.3B-0.9 0.15B-0.5 - 5%

0.3B-0.9 - 10% 0.3B-1.8

0.15B-0.9 - 10%0.3B-1.8

0.15B-0.5 - 5% 0.15B-0.9 0.3B-1.8

26 x 36

28 x 38

0.15B-0.5 - 5% 0.15B-0.9 0.3B-1.8

30 x 40 0.15B-0.2 - 5% 0.3B-0.5 0.6B-0.932 x 42

34 x 44

36 x 46

This table provides the lowest measurable range obtainable, based on actual test data, the CT will deliver to the rated burden. If a percentage is missing, it is assumed to respond as defined. For stated percentages, the accuracy will be maintained from that percentage of rated current through its rating factor. For other sizes and special burden requirements, consult the factory. Non-standard burdens or adjustment to fixed burdens are possible. No units will be available with build-ups and/or heights less than 2.25".

Custom Engineered Designs

TYPE ACCUSlip™ 600 VoltsIndoor/outdoor 10 kV BIL60 Hertz

Notes:Rating factor: unless otherwise noted -1000:5 through 2000:5, RF 3.0 -2500:5 through 3000:5, RF 2.0 -4000:5 and above, RF 1.5

This is intended to assist the engineer in selecting the metering range desired by CT size and current ratio. The standard accuracy class as defined by IEEE C57.13 states that the accuracy at 10% rated current can be twice the accuracy class by which it is rated at nominal current, and must be in that same class from 100% rated current through the CT rating factor. This table is based on test results of various designs produced and is subject to change. It is to be used as a guide only; for actual performance, contact the factory.

1VAP701261-DB

214 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 215

TYPES GCT-848/HW-945/ GCT-802 and ISO-Phase Bus Current Transformers

600 Volts Indoor/outdoor 10 kV BIL50 and/or 60 Hertz

Primary current ratios:Available up to 50000:5

When ordering generator CTs, include the following information: − Min. inside diameter (ID): _____ in. [mm] − Max. outside diameter (OD): _____ in. [mm] − Max. allowable height (HT): _____ in. [mm] − Current ratio: _____ (:5A or :1A) − Number of cores: _____ (1 - GCT-848; 2, 3, 4, or 5 - HW-945) − Accuracy and burden requirements, for example -

Metering: _____ (IEEE C57.13 or IEC 60044-1) Relaying: _____ (IEEE C57.13 or IEC 60044-1)

− Continuous rating factor: _____ (std. is RF=1.0 @ 55°C) − Mounting hole arrangement: _____, size - _____ (e.g. 34" BC,

(4) 3/4" diameter holes − For GCT-802, lead length and type: _____, size _____ (std is

#10 AWG) − Frequency: _____ (50, 60 Hz, or other) − Conduit box hub size: _____ (std is 1" NPT) − Specify with or without mounting board

Note: Units are custom manufactured to customer specifications. Contact factory to discuss other options.

Options:These units can be provided in a pre-assembled array of two (2) to five (5) GCTs (HW-945). The unit can also be provided without an insulating board and #10 TEFZEL leads (GCT-802). Through careful calculation, steel selection, and testing, existing current transformer characteristics can be matched. Existing characteristic curve is required. Contact factory for other needs.

Custom Engineered Designs

TYPE PSG-981

600 VoltsIndoor/outdoor 10 kV BIL60 Hertz

When ordering molded resin generator CTs, include the following information:

− Min. inside diameter (ID): _____ in. [mm] − Max. outside diameter (OD): _____ in. [mm] − Max. allowable height (HT): _____ in. [mm] − Current ratio: _____ (:5A or :1A) − Number of cores: _____ (1, 2, or 3) − Accuracy and burden requirements, for example -

Metering: _____ (IEEE C57.13 or IEC 60044-1) Relaying: _____ (IEEE C57.13 or IEC 60044-1)

− Continuous rating factor: _____ (std. is RF=1.0 @ 55°C) − Mounting hole arrangement: _____, size - _____ (e.g. 34" BC,

(4) 3/4" diameter holes − Frequency: _____ (50, 60 Hz, or other) − Conduit box hub size: _____ (std is 1" NPT)

Options:These units can be stacked on top of one another, but it is highly recommended that some space exists to allow for air circulation and cooling. Through careful calculation, steel selection, and testing, existing current transformer characteristics can be matched. Existing characteristic curve is required. Contact factory for other needs.

Note: Units are custom manufactured to customer specifications. Contact factory to discuss other options.

216 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 217

1VAP429803-DB

Primary Amps 50 Hz 60 Hz 50 Hz 60 Hz 50 Hz 60 Hz

Rating Factor

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

5 E-923A471G01 E-923A481G01 15 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

10 E-923A471G02 E-923A481G0215 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

15 E-923A471G03 E-923A481G0315 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

20 E-923A471G04 E-923A481G0415 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

25 E-923A471G05 E-923A481G0515 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

30 E-923A471G06 E-923A481G0615 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

40 E-923A471G07 E-923A481G0715 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

50 E-923A471G08 E-923A481G0815 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

75 E-923A471G09 E-923A481G0915 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

100 E-923A471G10 E-923A481G1015 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

150 E-923A471G11 E-923A481G1115 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

200 E-923A471G12 E-923A481G1215 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

300 E-923A471G13 E-923A481G1315 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

400 E-923A471G14 E-923A481G1415 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P201.5 13.81 10.88 12.41 44

600 E-923A471G15 E-923A481G1515 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P202.0 13.81 10.88 12.41 44

800 E-923A471G16 E-923A481G1615 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P201.5 13.81 10.88 12.41 44

1000 E-923A471G17 E-923A481G1715 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P201.2 13.81 10.88 12.41 44

1200 E-923A471G18 E-923A481G1815 VA, CL 0.2

30 VA, CL 0.5

20 VA, CL 0.2

45 VA, CL 0.5

20 VA, CL 5P10

10 VA, CL 10P20

25 VA, CL 5P10

12 VA, CL 10P201.0 13.81 10.88 12.41 44

10.88 [276]

10.00 [254]

.44[11]

8.19[208]

9.50[241]

.66 [17]

.44 x .88[11 x 22]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])

Protective accuracy

IEC Current Transformers

TYPE KON-17Outdoor 12 and 17.5 kV, 110 kV BIL50 and 60 Hertz

Thermal Rating:All Ratings 80 x normal, 1 second

Creep:19.5" (495 mm)

Style number Measuring accuracy

Note: These units encapsulated with HCEP material

218 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 219

1VAP429802-DB

0.44 x 1.69 SLOTS4 TOTAL [11 x 43]

10.75 [273]

10.87 [276]

10.00 [254]

0.44 [11]

0.44 [11]

8.63 [219]

NAMEPLATE

Mounting base dimensions (in. [mm])

Rated voltage factor: 1.2

Contact the factory for additional designs.

IEC Voltage Transformers

Primary Voltage 50 Hz 60 Hz

Secondary Voltage

Winding Ratio

Measuring Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

11000/√3 E-923A472G06 E-923A479G06 100/√3 110:1 0.2, 50 VA 15.82 10.87 13.75 45

11400/√3 E-923A472G07 E-923A479G07 100/√3 114:1 0.2, 50 VA 15.82 10.87 13.75 45

12470/√3 E-923A472G08 E-923A479G08 100/√3 124.7:1 0.2, 50 VA 15.82 10.87 13.75 45

13200/√3 E-923A472G09 E-923A479G09 100/√3 132:1 0.2, 50 VA 15.82 10.87 13.75 45

13800/√3 E-923A472G10 E-923A479G10 100/√3 138:1 0.2, 50 VA 15.82 10.87 13.75 45

11000/√3 E-923A472G16 E-923A479G16 110/√3 100:1 0.2, 50 VA 15.82 10.87 13.75 45

11400/√3 E-923A472G17 E-923A479G17 110/√3 103.64:1 0.2, 50 VA 15.82 10.87 13.75 45

12470/√3 E-923A472G18 E-923A479G18 110/√3 113.36:1 0.2, 50 VA 15.82 10.87 13.75 45

13200/√3 E-923A472G19 E-923A479G19 110/√3 120:1 0.2, 50 VA 15.82 10.87 13.75 45

13800/√3 E-923A472G20 E-923A479G20 110/√3 125.45:1 0.2, 50 VA 15.82 10.87 13.75 45

TYPE VOG-17Outdoor 12 and 17.5 kV, 110 kV BIL50 and 60 Hertz

Thermal Rating:500 VA @ 30°C Ambient

Creep:24.7" (627 mm)

Note: These units encapsulated with HCEP material

Style number

220 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 221

1VAP429801-DB

12.25 [311]

.44 [11]

10.00 [254]

.44 [11]

8.63[219]

10.75[273]

1.25 [32]

.44 X 1.69[11 X 43]SLOTS4-TOTAL

NAMEPLATE

Mounting base dimensions (in. [mm])

IEC Voltage Transformers

TYPE VOY-17Outdoor 12 and 17.5 kV, 110 kV BIL50 and 60 Hertz

Thermal Rating:500 VA @ 30°C Ambient

Creep:28.2" (716 mm)

Primary Voltage 50 Hz 60 Hz

Secondary Voltage

Winding Ratio

Measuring Accuracy

Height (in.)

Width (in.)

Length (in.)

Weight (lbs.)

11000 E-923A473G01 E-923A480G01 100 110:1 0.2, 50 VA 15.82 12.87 14.04 75

11400 E-923A473G02 E-923A480G02 100 114:1 0.2, 50 VA 15.82 12.87 14.04 75

12470 E-923A473G03 E-923A480G03 100 124.7:1 0.2, 50 VA 15.82 12.87 14.04 75

13200 E-923A473G04 E-923A480G04 100 132:1 0.2, 50 VA 15.82 12.87 14.04 75

13800 E-923A473G05 E-923A480G05 100 138:1 0.2, 50 VA 15.82 12.87 14.04 75

11000 E-923A473G06 E-923A480G06 110 100:1 0.2, 50 VA 15.82 12.87 14.04 75

11400 E-923A473G07 E-923A480G07 110 103.64:1 0.2, 50 VA 15.82 12.87 14.04 75

12470 E-923A473G08 E-923A480G08 110 113.36:1 0.2, 50 VA 15.82 12.87 14.04 75

13200 E-923A473G09 E-923A480G09 110 120:1 0.2, 50 VA 15.82 12.87 14.04 75

13800 E-923A473G10 E-923A480G10 110 125.45:1 0.2, 50 VA 15.82 12.87 14.04 75

11000 E-923A473G11 E-923A480G11 115 95.65:1 0.2, 50 VA 15.82 12.87 14.04 75

11400 E-923A473G12 E-923A480G12 115 99.13:1 0.2, 50 VA 15.82 12.87 14.04 75

12470 E-923A473G13 E-923A480G13 115 108.4:1 0.2, 50 VA 15.82 12.87 14.04 75

13200 E-923A473G14 E-923A480G14 115 114.8:1 0.2, 50 VA 15.82 12.87 14.04 75

13800 E-923A473G15 E-923A480G15 115 120:1 0.2, 50 VA 15.82 12.87 14.04 75

11000 E-923A473G16 E-923A480G16 120 91.7:1 0.2, 50 VA 15.82 12.87 14.04 75

11400 E-923A473G17 E-923A480G17 120 95:1 0.2, 50 VA 15.82 12.87 14.04 75

12470 E-923A473G18 E-923A480G18 120 103.9:1 0.2, 50 VA 15.82 12.87 14.04 75

13200 E-923A473G19 E-923A480G19 120 110:1 0.2, 50 VA 15.82 12.87 14.04 75

13800 E-923A473G20 E-923A480G20 120 115:1 0.2, 50 VA 15.82 12.87 14.04 75

Style number

Rated voltage factor: 1.2

Contact the factory for additional designs.

222 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 223

INS

TRU

ME

NT

TRA

NS

FOR

ME

RS

is

olat

e m

eter

s or

ot

her

inst

rum

ents

from

hig

h vo

ltage

s an

d cu

rren

ts a

nd

tran

sfor

ms

them

(i.e

., st

ep-d

own)

to v

alue

s w

here

they

ca

n be

mea

sure

d by

sta

ndar

d m

eter

s.

All

inst

rum

ent

tran

sfor

mer

s ar

e cl

assi

fied

as

eith

er

curr

ent

tran

sfor

mer

s or

vol

tage

tra

nsfo

rmer

s. T

hey

are

used

for

rev

enue

met

erin

g an

d al

so w

ith r

elay

s an

d in

dica

ting

inst

rum

ents

.

Cur

rent

Tra

nsfo

rmer

s (C

T)

The

prim

ary

win

ding

s of

cu

rren

t tr

ansf

orm

ers

are

conn

ecte

d in

ser

ies

with

the

line

and

thei

r se

cond

arie

s co

nnec

ted

to t

he c

urre

nt c

oils

or

elem

ents

of

met

ers,

re

lays

or i

nstr

umen

ts. A

ll st

anda

rd c

urre

nt tr

ansf

orm

ers

have

a 5

Am

pere

rat

ed s

econ

dary

reg

ardl

ess

of t

heir

prim

ary

curr

ent.

Eac

h cu

rren

t tr

ansf

orm

er h

as s

peci

ficat

ions

bas

ed o

n co

ntin

uous

cur

rent

, sho

rt ti

me

curr

ent,

and

mec

hani

cal

stre

ss.

Ther

e ar

e tw

o ac

cura

cy c

lass

ifica

tions

: on

e fo

r m

eter

ing

and

one

for

rela

ying

. Th

e m

eter

ing

accu

racy

clas

sific

atio

n te

lls w

hat

erro

r in

tra

nsfo

rmat

ion

can

be

expe

cted

at

norm

al c

urre

nts.

The

rel

ayin

g ac

cura

cy

clas

sific

atio

n te

lls

wha

t pe

rcen

t ac

cura

cy

can

be

expe

cted

whe

n th

e se

cond

ary

is c

alle

d up

on to

indu

ce

a ce

rtai

n vo

ltage

.

The

seco

ndar

y of

th

e cu

rren

t tr

ansf

orm

er

shou

ld

alw

ays

be

conn

ecte

d to

a

load

(b

urde

n)

or

shor

t ci

rcui

ted.

If

the

seco

ndar

y is

op

en

circ

uite

d,

the

tran

sfor

mer

may

dev

elop

a d

ange

rous

ly h

igh

seco

ndar

y vo

ltage

.

Rat

ing

Fact

or:

The

fact

or b

y w

hich

the

nam

epla

te

prim

ary

curr

ent o

f a C

T is

mul

tiplie

d to

obt

ain

max

imum

pr

imar

y cu

rren

t th

at

can

be

carr

ied

cont

inuo

usly

w

ithou

t ex

ceed

ing

the

limiti

ng t

empe

ratu

re r

ise.

The

ac

cura

cy c

lass

at

the

ratin

g fa

ctor

poi

nt s

houl

d be

the

sa

me

as a

t nam

epla

te r

atin

g.

Volta

ge

Tran

sfo

rmer

s (V

T)

The

prim

ary

win

ding

s of

vo

ltage

tr

ansf

orm

ers

are

conn

ecte

d ac

ross

the

lin

e. T

hey

step

dow

n th

e lin

e

volta

ge

to

a va

lue

suita

ble

for

stan

dard

m

eter

s,

norm

ally

115

Vol

ts o

r 12

0 Vo

lts.

In b

asic

con

stru

ctio

n, v

olta

ge tr

ansf

orm

ers

are

muc

h lik

e di

strib

utio

n tr

ansf

orm

ers

exce

pt t

hat

the

curr

ent

and

the

kVA

cap

acity

are

ver

y lo

w. T

hey

are

desi

gned

to

giv

e an

acc

urat

e vo

ltage

tran

sfor

mat

ion.

Sel

ectio

n

A n

umbe

r of

con

side

ratio

ns a

re in

volv

ed in

sel

ectin

g pr

oper

in

stru

men

t tr

ansf

orm

ers

incl

udin

g:

syst

em

volta

ge, B

IL, l

oad

curr

ent,

ratin

g fa

ctor

and

acc

urac

y cl

ass

at s

peci

fied

burd

ens.

Phy

sica

l re

quire

men

ts

such

as

indo

or o

r ou

tdoo

r in

stal

latio

n, w

indo

w o

r ba

r ty

pe (

for

600

V C

Ts),

and

win

dow

dia

met

er a

re a

lso

impo

rtan

t. M

any

of th

e tr

ansf

orm

er ty

pes

liste

d in

this

ca

talo

g ha

ve s

ome

char

acte

ristic

s th

at a

re d

uplic

ated

in

oth

er ty

pes

liste

d, b

ut e

ach

type

has

its

own

uniq

ue

com

bina

tion

of fe

atur

es th

at b

est m

eet t

he a

pplic

atio

n fo

r w

hich

it w

as d

esig

ned.

Application Data

Line

Volta

ge

Prim

ary

Sec

onda

ry

Volta

ge T

rans

form

er

Prim

ary

Sec

onda

ry

R

R

Voltm

eter

Volta

ge R

elay

Wat

t-Hou

r Met

er

Cur

rent

Rel

ay

Am

met

er

Pol

arity

Mar

k

Load

Cur

rent

Cur

rent

Tra

nsfo

rmer

To L

oad

Po

lari

ty: D

esig

natio

n of

the

rela

tive

inst

anta

neou

s di

rect

ions

of t

he c

urre

nts

ente

ring

the

prim

ary

lead

s an

d le

avin

g th

e se

cond

ary

lead

s. W

hen

curr

ent i

s flo

win

g to

war

d th

e m

arke

d pr

imar

y le

ad, i

t is

flow

ing

away

fro

m

the

tran

sfor

mer

in th

e m

arke

d se

cond

ary

lead

.

224 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 225

0 10 20 30 40 50 600

50

100

150

200

250

300

350

400

450

500

1.0

1.331.5

2.0

3.0

4.0

Per

cent

of r

ated

prim

ary

curr

ent

Curve designations arecontinuous thermal current rating factorsat 30°C ambient air temperature.

Average Ambient Cooling air temperature for 24 hour period, degrees C

(Maximum ambient air temperature shall not exceed average by more than 10°C.)

Typical burden value (per stator) ELSTER Type AB Poltphase Meters Class 20 transformer rated

Potential coil (per stator) at the rated Voltage. 4.2 VA at 0.18 x PF lagging

Current coil (per stator) 1.1 VA at 0.22 x PF lagging

Resistance of copper secondary wire in ohms per 1000 feet at 68°F (20°C).

Wire Size Ohms

14 2.5250

12 1.5880

10 0.9989

8 0.6282

Common Electrical Terms

Ampere Volt Ohm Ohm's Law Volt Amperes Kilovolt Amperes Watt Kilowatt Power Factor Watthour Kilowatthour Horsepower Demand Factor Diversity Factor Load Factor

(I) (E) (R) E

(VA)

(kVA) W

(kW) (p-f)

(WHR)

(kWHR) (hp)

= Unit of current or rate of flow of electricity = Unit of electromotive force = Unit of resistance = IR = Unit of apparent power = EI (single phase) = E x I x 1.73 (3 phase) = 1000 Volt-Amperes = Unit of true power = VA x p-f = .00134 hp = 1000 watts = ratio of true to apparent power = W or kW VA kVA = Unit of electrical work = One watt for one hour = 3.413 Btu = 2.655 ft. lbs. = 1000 watthours = Measure of time rate of doing work = Equicalent of raising 33,000 lbs. one ft. in one minute = 746 watts = Ratio of maximum demand to the total connected load =Ratio of the sum of individual maximum demands of the carious subdivisions of a system to the maximum demand of the whole system = Ratio of the average load over a designated period of time to the peak load occurring in that period

Application Data

Ampere capacity of insulated conductors

Size AWG

or MCM

Approxi-mate

Diameter (inches)

Types

RUW T

TW Types

RH RHW RUH THW

Cu Al Cu Al

6 .397 80 60 95 75

4 .452 105 80 125 100

3 .481 120 95 145 115

2 .513 140 110 170 135

1 .588 165 130 195 155

0 .629 195 150 230 180

00 .675 225 175 265 210

000 .727 260 200 310 240

0000 .785 300 230 360 280

250 .868 340 265 405 315

300 .933 375 290 445 350

350 .985 420 330 505 395

400 1.032 455 355 545 425

500 1.119 515 405 620 485

600 1.233 575 455 690 545

700 1.304 630 500 755 595

750 1.339 655 515 785 620

800 1.372 680 535 815 645

900 1.435 700 580 870 700

1000 1.494 780 625 935 750

1250 1.676 890 710 1065 855

1500 1.801 980 795 1175 950

1750 1.916 1070 875 1280 1050

2000 2.021 1155 960 1385 1150

Single conductor in free air at 30°C (86° F)

Calculation of line amperes on polyphase circuits

Amps = Load kVA x 1000 1.732 x line-to-line voltage

Applicable to both 3-phase, 3-wire delta and 3-phase, 4-wire wye.

Required diameter of CT window for multiple conductor

Number of primary conductors Minimum Window Diameter

2 2.00 x conductor O.D.

3 2.16 x conductor O.D.

4 2.42 x conductor O.D.

5 2.70 x conductor O.D.

226 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 227

Voltage transformers The accuracy classification of voltage transformers for metering service includes a correlation between ratio correction factor and phase angle so as to show the overall effect on watthour meter registration. The classification is based on the requirement that the transformer correction factor (the correction for overall error due to both ratio error and phase angle) be within the limits specified. For any particular accuracy class the ratio correction factor and phase angle must fall within the parallelogram. These limits apply over the voltage range of ± 10% of the rated voltage at rated frequency.

For example, the overall correction will never exceed .3% for a transformer in the 0.3 accuracy class. If the ratio correction factor is 1.003 the maximum allowable phase angle is - 15.6 minutes. The transformer correction factor is:

The corresponding ratio correction factor and phase angle for any point inside the 0.3 class parallelogram will always give a transformer correction factor between .997 and 1.003.

*TCF =

=

=

RCF + γ

2600

1.003 +2600-15.6

.997

Equivalent parallelogram

Standard burdens

Burden Designation Secondary Volt-Amperes Burden Power Factor

W 12.5 0.10

X 25.0 0.70

M 35.0 0.20

Y 75.0 0.85

Z 200.0 0.85

ZZ 400.0 0.85

phase angleminutes-lagging

phase angleminutes-leading

0.6 accuracy classparallelogram

0.15 accuracy classparallelogram

0.3 accuracy classparallelogram

ratio correction factor (RCF)

.994

1.006

1.003

1.0015

0

.997

.9985

-30 -20 -10 +30+20+10

Accuracy Class Minimum Maximum

Limits of Power Factor of Metered Load-Lagging

Minimum Maximum

1.2 0.988 1.012 0.6 1.0

0.6 0.994 1.006 0.6 1.0

0.3 0.997 1.003 0.6 1.0

Limits of Transformer Correction Factor (TCF)

Accuracy StandardsCurrent transformers The accuracy classification of current transformers for metering service includes a correlation between ratio correction factor and phase angle so as to show the overall effect on watthour meter registration. The classification is based on the requirement that the transformer correction factor (the correction for overall error due to both ratio error and phase angle) be within the limits specified. For any particular accuracy class the ratio correction factor and phase angle must fall within the parallelograms for 100% and 10% current respectively.

For example, the overall correction will never exceed .3% at 100% rated current for a transformer in the 0.3 accuracy class. If the ratio correction factor is 1.003 the maximum allowable phase angle is +15.6 minutes. The transformer correction factor is:

*TCF =

=

=

RCF - β

2600

1.003 -260015.6

.997

The corresponding ratio correction factor and phase angle for any point inside the 0.3 class parallelogram for 100% rated current will always give a transformer correction factor between .997 and 1.003.

0.3 class-10%rated current

0.3 class-100%rated current

0.6 class-100%rated current

to meet 0.3 accuracy class, the ratio and phase angle at the given burden must fallwithin this parallelogramat 100% rated currentand within this parallelogram at 10% rated current

ratio correction factor (RCF)

phase angleminutes-lagging

phase angleminutes-leading

0.15 class- 5%rated current

0.15 class- 100%rated current

0.15S class- 5% and100% rated current

+10

1.00

+20 +30-10-20-30

.997

.9985

0

1.003

1.006

.994

1.0015

Equivalent parallelogram

Standard burden characteristics (60 Hz and 5 ampere secondary)

Burden Designation

Resistance (ohms)

Inductance (millihenrys)

Impedance (ohms)

Volt- Amperes

Power Factor

Metering burdens

E-0.04 0.04 0.0 0.04 1.0 1.0

E-0.2 0.20 0.0 0.20 5.0 1.0

B-0.1 0.09 0.116 0.1 2.5 0.9

B-0.2 0.18 0.232 0.2 5.0 0.9

B-0.5 0.45 0.580 0.5 12.5 0.9

B-0.9 0.81 1.040 0.9 22.5 0.9

B-1.8 1.62 2.080 1.8 45.0 0.9

Relaying burdensB-1 0.5 2.3 1.0 25 0.5

B-2 1.0 4.6 2.0 50 0.5

B-4 2.0 9.2 4.0 100 0.5

B-8 4.0 18.5 8.0 200 0.5

228 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 229

IT Type Designations Key to Type Designations

ABB Westinghouse 1st position 2nd position (window size)

3rd position(Letters SCALE give a closer approximation of window diameter in inches)

600 Volt

CTs IMC ECI C=CT, 600 V, metering accuracy S C A L E

CBT-1 RTM S = Small 1"-2" 1.0 1.25 1.5 1.75 2.0

CBT-H None I=CT, 600 V, indicating M = Medium 2"-5" 2.0 2.5 3.25 4.0 5.0

CMV CRA L = Large 5"-8.25" 5.0 5.5 6.5 7.5 8.25

CMF CTRR=CT, 600 V, relaying G = > 8.25" F = family of window sizes; i.e., CMF with 2.5"

and

3 1/16" windowsCSF CSB(burden capability exceeds normal metering requirements)

CSH None B = Bar V = oval

CMS CSB (Lg.) T = thru type

CLC CLA H = 0.5 (half) Ohm burden

CLE CLARLC EMC

VTs PPW PPI/EMP P = VT, 600 Volt P = Performace I = Indicating

PPM PXA (+) M = 0.3 accuracy at 35 VA

5 kV - 25 kV 4th & 5th positions

CTs KIR-60, 11 CTM 5-15 K = CT, > 600 Volt I = Indoor N = 0.3B-0.5 Perf 60 = 60 kV BIL

KIT-60, 11 UP 5-15 O = Outdoor P = 0.3B-0.9 Perf 75 = 75 kV BIL

KOR-60, 11 CTOM 5-15 R = 0.3B-1.8 Perf 11 = 110 kV BIL

KON-11 CTOM 110 T = Thru type 15 = 150 kV BIL

KOR-15 CCO 15020 = 200 kV BIL

KOT-60, 11 EMC 5-15

VTs VIY-60 PC 60 V = VT, > 600 Volt I = Indoor Y = 0.3 accuracy at 75 VA Same as above

VOY-60 PCO 60 O = Outdoor Z = 0.3 accracy at 200 VA

VIZ-75, 11 PTM 75, 100G = Single bushing for line-

to-ground connection

VOZ-75, 11 PTOM 75, 110

VOG-11 None

VOZ-15 PTOM 150

VIZZ-15 PT 25

230 Instrument Transformer Reference Guide | ABB reference guide ABB reference guide | Instrument Transformer Reference Guide 231

Testing services Instrument transformer on-site testing

With market deregulation expanding throughout the United States and Canada, there is an increased need for metering of power facilities and transmission points. This has increased focus on upgrading metering at these locations to provide reliable data for power flow. ABB has developed tests specific to each site situation and has test equipment and standards certified traceable to National Institute of Standard and Technology (NIST) and National Research Council of Canada (NRCC).

With state-of-the-art equipment and knowledgeable experts in instrument transformer design and instrumentation engineering, ABB is uniquely positioned to provide customers with testing options in order to meet requirements for revenue metering certification, excitation verification, and actual burden measurement and/or instrumentation system performance.

ABB testing services include on-site testing, in-service on-site testing, or de-energized on-site testing. Contact the factory at 252-827-3212 for more information.

The HCEP material Hydrophobic cycloaliphatic epoxy (HCEP)

ABB‘s portfolio of outdoor medium voltage instrument transformers has been redesigned using cutting edge 3D simulation software. The units are now encapsulated in hydrophobic cycloaliphatic epoxy (HCEP) and manufactured using the automatic pressure gelation (APG) process.

Advanced 3D simulation models combine optimized electrical and mechanical design features and provide the most effective molded designs for reliability and performance. HCEP offers improved weatherability and outdoor aging, better performance in heavily polluted environments, and a longer service life. The global APG process effectively shortens manufacturing cycle times and ensures product consistency. The overall result is improved quality and reliability in outdoor performance!

For more information, contact your ABB Sales Representative or call the factory +1-252-827-3212.

Cross Reference of most commonly used types

ABB GEC Durham GE Itron

600 V current transformers

IMC - JCH-0C -

CBT/1 TCB JGT-0C R6BA

CBT-H TAB JCM-0C R6B

CSF TCW JCR-0C R6SA

CSH TFW JCW-0C R6S

CMF AB JAK-0C R6M

CMV AP JAB-0C R6P

CLC AD JAD-0C R6L

CLE ACL JCD-0C -

RLC AD JCP-0C -

600 V voltage transformers

PPW DF - T5R

PPM DA JVA-0 (0.3M only) T6R

ABB GE Kuhlman

5 - 36 kV current transformers

KIR-60 JKM-3 -

KIR-75 JKM-4 -

KIR-11, 11E JKM-5, 5A -

KOR-60, 75 JKW-3, 4 -

KOR-11 JKW-5 -

KON-11 JCK-5 -

KOR-15C JKW-6 -

KOT-60, 75, 11 JCD-3, 4, 5 LG(X)

KIT-60, 75, 11 JCM-3, 4, 5 LG(X)

KOR-20 JKW-7 -

KOTD-150, 200 JKW-150, 200 LG(X)

KOTD-250 JKW-250 -

5 - 36 kV voltage transformers

VIY-60 JVM-3 -

VIZ-75, 11 JVM-4, 5 -

VOY-60 JVW-3 -

VOY-11 JVW-110 -

VOZ-75, 11 JVW-4, 5 -

VOG-11 JVW-110 -

VOZ-11M JVW-5 -

VOY, VOG-12 JVW-6 -

VOY-15, 15G JVW-6 -

VOY-20, 20G JVW-7 -

VOHD-200, 200G JVW-7 -

VOZZ-15, 20 JVT-150, 200 -

VOZZ-15G, 20G JVS-150, 200 -

Notes:

1VA

P42

0001

-TG

Dec

embe

r 20

12 R

ev. LFor more information please contact:

ABB Inc.Medium Voltage Distribution Components3022 NC 43 NorthPinetops, NC 27864 USA Phone: +1 252 827 3212Fax: +1 252 827 4286

www.abb.com/mediumvoltage

Contact us