Step by step, from raw material to final product, quality constitutes a major concern toLiban Cables.

Raw material are continuously and repetitively tested from trial orders till the last batchreceived afterwards.

Products are tested within two simultaneous procedures :

- A built in quality control system carried out by the production itself at any step of workin process.

- A parallel and contradictory procedure is also carried out on the same stages andproducts by independent inspectors reporting to the quality control service.

End users and/or third part inspection authorities are also constantly commissioning thefinished products and assessing the strict conformity to ordered specifications.

In fact, our ISO certification stated in February 1997 and renewed in February 2000 bythe International Certification Network (EQNET) is certified by the French A s s o c i a t i o nfor Quality Assurance (AFAQ), the well known rigourous and independant A c c r e d i t e dEuropean assessor. This certification, under reference A FAQ Nº QUAL / 1997 / 7034,confirms the soudness and the performance of the Quality System we apply for theDesign, the Development, the Manufacturing and the Marketing & Sales of all ourproducts.

For prompt quotation / supplies please make sure your inquiries and your orders are

securing the following data:

1 - International or Special Standard. (Alternatively, the precise usage of the cable.)

2 - Rated voltage.

3 - Copper or Aluminium conductors.

4 - Size of each conductor.

5 - Insulation material : general purpose PVC, special PVC, XLPE or others.

6 - Insulation colour :

- Usual colour are : grey for the neutral and black, red and blue for the phases.

-Any other colour is available on request.

7 - Number of conductors.

8 - Othre requirements.

9 - Packing.

10 - Required delivery time.

11 - Required validity.

2 QUALITY

3 RECOMMENDED ORDERING PARAMETERS

As this catalogue is not intended to cover all of LIBAN CABLES S A L possibilities inLow Tension cables manufacturing, the hereafter listing of the types of cables is notrestrictive but only indicative of the main and most current types we manufacture.

On the other hand, our specification sheets are inspired mainly from InternationalElectrotechnical Commision Specification (IEC) only in order to conform with thesustained trend, noticed both regionally and worlwide, towards these same IEC supposedto inspire any further standardization approaches.

Whereas, in fact, some Low Tension cables may require special conception, fully withinthe capabilities of LIBAN CABLES S A L, ISO 9001 certified, precisely because inposition to conceive / tailor your special needs.

That is why, while consulting this catalogue, it is important to take into account that anycombination or change of the constructional details mentioned in this catalogue remainfeasible, on base of special conception / development, matching any special or diff e r e n tspecifications.

F i n a l l y, and within our policy of constant improvement, we reserve the right to alter anypart of the information contained in this publication without incurring any obligation.In all cases this brochure being only indicative, and unless expressly agreed upon, itcannot be considered by any mean as contractual document.

NOTICE

INDUSTRIAL and DISTRIBUTIONLOW TENSION CABLES

INTRODUCTION

QUALITY ASSURANCE

RECOMMENDED ORDERING PARAMETERS

GENERALITIES :

Conductors

Properties of Insulating Materials

Determination of the cross sectional area

Current carrying capacities

Buried cables

Cables laid in the air

Voltage Drop

Conductors short circuit current

Minimum bending radius

INDUSTRY AND DISTRIBUTION 0.6/1KV POWER CABLES

Unarmoured PVC or XLPE insulated and PVC sheathed cables

Armoured PVC or XLPE insulated and PVC sheathed cables

Concentric conductors, PVC insulated and sheathed cables

Self supported, aerial cables

Control multicore cables

Aerial Bundled Conductors (TORSADES)

3 phases + Neutral / messenger + Street lighting conductor

2 and 4 aluminium conductors + Pilot copper conductor

TECHNICAL INFORMATION

Formulae

Conversion factors and units

5

4

3

2

1

P a g e

CONTENTS

4.1

4.2

4.3

4.4

5.1

5.2

5.3

5.4

5.5

5.6

1

2

2

3

3

4

4

4

4

6

7

8

8

10

10

20

40

42

47

52

52

54

56

56

57

6.1

6.2

6

4.5

4.6

4.7

4.4.1

4.4.2

5.6.1

5.6.2

NOTICE

1

Devoted to the manufacturing of electric and telecomcables, Liban Cables is the first and largest supplier inLebanon and a leader in the Middle-East region.

Liban Cables was founded in 1968 by a group ofLebanese industrialists backed up by the technicalassistance of two international leading firms :

- Les Cables de Lyon - France (became ALCATEL afterwards)

- Phelps Dodge - U.S.A

Staffed with qualified engineers and highly skilledtechnicians, our plant is located in Nahr-Ibrahim at 30Km from Beirut, where cables are designed andmanufactured according to all internationalspecifications : IEC, VDE, UTE, BS, and others oncustomer request.

Early after its foundation, Liban Cables has become themajor supplier of the Lebanese market in both thepublic and private sectors. The product range of LibanCables covers all electric cables up to 36 KV,communications cables (copper and optical fiber) inaddition to a wide variety of special cablesmanufactured on customer request.

High quality cables, continuous developments of theproduction range, direct and fast shipments havecontributed in rendering Liban Cables an importantexporter for many countries on the three limitrophecontinents (Asia, Europe, Africa). Liban Cablesproducts are particularly appreciated by administrationsand international contractors operating in the region andseeking reliable and direct supplies of power andcommunication cables.

INTRODUCTION

11

2

Step by step, from raw material to final product, quality constitutes a major concern toLiban Cables.

Raw material are continuously and repetitively tested from trial orders till the last batchreceived afterwards.

Products are tested within two simultaneous procedures :

- A built in quality control system carried out by the production itself at any step ofwork in process.

- A parallel and contradictory procedure is also carried out on the same stages andproducts by independent inspectors reporting to the quality control service.

End users and/or third part inspection authorities are also constantly commissioning thefinished products and assessing the strict conformity to ordered specifications.

QUALITY ASSURANCE

2

3 RECOMMENDED ORDERING PARAMETERS

For prompt quotation / supplies please make sure your inquiries and your orders aresecuring the following data :

1 - International or Special Standard. (Alternatively, the precise usage of thecable.)

2 - Rated voltage.

3 - Copper or Aluminium conductors.

4 - Size of each conductor.

5 - Insulation material : general purpose PVC, special PVC, XLPE or others.

6 - Number of conductors.

7 - Other requirements.

8 - Packing.

9 - Required delivery time.

10 - Required validity.

N.B.: Liban Cables certification to ISO 9001 is planned for January 1997.

4.1 CONDUCTORS

The commonly used conductors materials are copper and aluminium meeting therequirements of IEC 60228.

Theoretical characteristics of copper and aluminium are as follows :

4 GENERALITIES

Copper(mm2)

Aluminium(mm2)

610162535507095120150185

10162535507095150185240300

3

Equivalent standardized cross sectional area at equal voltage drop

Specific Gravity (kg/dm3)

Resistivity at 20˚C (Ohm. mm2/m)

Breaking Load (daN/mm2)

Elongation at break (%)

Annealed Copper Annealed Aluminium

8.9

17.241 x 10-3

23 to 25

20 to 40

2.7

28.264 x 10-3

12 to 15

1 to 4

4.3 DETERMINATION OF THE CROSS SECTIONAL AREA

The determination of the cross sectional area depends on the :

- Current carrying capacities in continuous loading,- Voltage drop in continuous loading- Permissible short-circuit current,- Conditions of installation (temperature, spacing, ...).

4.4 CURRENT CARRYING CAPACITIES

The heat produced by the cable under the set conditions must be able to dissipate to theambient environment at any point of the cable installation; therefore the loading of thecable must be limited accordingly. The current carrying capacities shown in theelectrical characteristics tables are calculated according to the internationally adoptedmethod of the IEC publication 60287 for a maximum core temperature of 70˚C forPVC insulated cables and 90˚C for XLPE insulated cables, at the following installationconditions :

4.4.1. BURIED CABLES

The stated values are for cables or ducts placed in the ground at a depth of 600 mm ofaverage thermal resistivity of 100˚C.cm/w and spaced so that the temperature rise ineach duct has no effect on the other ducts ( space being greater than 1 meter ), for a soiltemperature of 20˚C.

4.2 PROPERTIES OF INSULATING MATERIALS

PVC PE XLPE

Specific gravity (kg/dm3)

Dielectric constant

Breaking load (bars) min.

Elongation at break min.

Max. continuous operatingtemperature (˚C)

Max. short circuittemperature (˚C)

Moisture proof

Flame proof

Flexibility

Insulation resistance constant, Kiat 20˚C (Megohm x km)

MATERIAL

1.3 - 1.5

5 - 8

100 - 200

150 %

70 - 105

160

Good

Very good

Good

5000

0.92 - 0.97

2.3

100

350 %

70

150

Very good

Poor

Poor

> 20.000

0.92 - 1.18

2.5

125 - 150

200 %

90

250

Very good

Poor

Poor

> 20.000

4

DIMENSIONAL CHARACTERISTICS

DOUBLE STEEL TAPE ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35

0.80.81.01.01.01.01.21.2

1.81.81.81.81.81.81.81.8

1.381.782.252.953.824.836.027.15

2.983.384.254.955.826.838.429.55

1415161820222527

274470

107179284450624

259302390485625805

11201410

...

...

...

...5587

138191

...

...

...

...500610810975

100010001000100010001000500500

mm mm

InnerSheath

1.01.01.01.01.01.01.01.0

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

1.81.81.81.81.81.81.81.81.92.12.32.42.52.72.93.1

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.983.384.254.955.826.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

14151719212326263033394248515763

4066

105160269426675945

12791848256232423978499065578226

285338448560730975

139015301990272039904800590071509100

11200

...

...

...

...82

130206289391565783990

1216152520042514

...

...

...

...545680920875

11001440221025503140369045505500

100010001000100010001000500500500500500250250250250250

THREE CORE

1.01.01.01.01.01.01.01.01.01.21.21.21.41.41.41.6

34

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

FOUR CORE

mm mm

InnerSheath

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

1.81.81.81.81.81.81.81.92.12.22.42.52.72.93.13.3

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.983.384.254.955.826.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

5388

140213358568900

12591705246434174323530566548743

10969

322388520660875

118017101970262038605100625075509300

1185014600

...

...

...

...110174275385521754

104413201621202326723352

...

...

...

...625785

1090110014402150273032503870468058007000

100010001000100010001000500500500500500250250250250250

1.01.01.01.01.01.01.01.01.21.21.21.41.41.61.61.6

15161820222528303439444852586470

Ph.1.21.21.41.41.61.61.82.02.22.4

1.81.82.02.12.32.42.62.72.93.1

28283236424649546066

817108615042163298938584594584576389552

16001740232031404570565066508200

1045012850

249333460662914

11791404178623342919

1030925

12801640250029703460414051506200

500500500500500250250250250250

FOUR CORE WITH REDUCED NEUTRAL

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.1.01.01.21.21.41.41.41.61.61.8

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.8.42shapedshaped

N.6.836.838.42

shapedshapedshapedshapedshapedshapedshaped

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available

1.01.01.01.21.21.41.41.41.61.6

DIMENSIONAL CHARACTERISTICS

35

DOUBLE STEEL TAPE ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Current carrying capacity (3)

mm2 Ω/Km Amp Amp Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C(1)

Underground CableCopper Alu Copper Alu

CopperCables in air

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.54610162535507095120150185240300400

...

...

...

...3.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

3041536791

115146176212261313358400451522590680

...

...

...

...6790

114137165204244279312352407460530

23.314.2

9.06.13.72.31.51.10.90.60.50.40.40.30.30.20.2

...

...

...

...6.13.82.41.71.41.00.70.60.50.40.30.30.2

223040527196

127157190242293339390444522595695

...

...

...

...557599

125151192232269309353415472552

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) a) Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w

- In air : Ambient temperature 30˚Cb) In three phase system decrease above listed current ratings by 10%

36

DOUBLE STEEL TAPE ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

DIMENSIONAL CHARACTERISTICS

DOUBLE STEEL TAPE ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35

0.70.70.70.70.70.70.90.9

1.81.81.81.81.81.81.81.8

1.381.782.252.953.824.836.027.15

2.783.183.654.355.226.237.828.95

1414151719212426

274470

107179284450624

251293348434570735

10401340

...

...

...

...5587

138191

...

...

...

...446540730905

100010001000100010001000500500

mm mm

InnerSheath

1.01.01.01.01.01.01.01.0

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.92.02.12.32.42.62.83.0

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.783.183.654.355.226.237.82

shapedshapedshapedshapedshapedshapedshapedshapedshaped

14151617192225252831354046495559

4066

105160269426675945

12781848256232423978499065578325

274326395500675895

128014301850254033904560570068008700

10650

...

...

...

...82

130206289391565783990

1216152520042514

...

...

...

...490600810775965

1260161023102940334041504840

100010001000100010001000500500500500500250250250250250

THREE CORE

1.01.01.01.01.01.01.01.01.01.01.21.21.41.41.61.6

37

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

FOUR CORE

mm mm

InnerSheath

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.92.12.32.42.62.83.03.2

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.783.183.654.355.226.237.82

shapedshapedshapedshapedshapedshapedshapedshapedshaped

5388

140213358568900

12591705246434174323530566548743

10969

307371457585790

109015801830238033304790590071508850

1130013900

...

...

...

...110174275385521754

104413201621203326723352

...

...

...

...540695955955

12001620242029003470423052506300

100010001000100010001000500500500500500250250250250250

1.01.01.01.01.01.01.01.01.01.21.21.21.41.41.61.6

15161719212327273136414550556167

Ph.0.90.91.01.11.11.21.41.61.71.8

1.81.81.92.12.22.42.52.72.93.0

26272934394347525863

817108615042163298938584594584576389552

14701630214029704260535063007850

1000012000

249333460662914

11791404178623342919

900875

11001470219026703110379047005550

500500500500500250250250250250

FOUR CORE WITH REDUCED NEUTRAL

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.0.70.70.90.91.01.11.11.11.21.4

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.7.82shapedshaped

N.6.236.237.82

shapedshapedshapedshapedshapedshapedshaped

1.01.01.01.21.21.21.41.41.61.6

DIMENSIONAL CHARACTERISTICS

38

DOUBLE STEEL TAPE ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available

Current carrying capacity (3)

mm2 Ω/Km Amp Amp Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C(1)

Underground CableCopper Alu Copper Alu

CopperCables in air

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.54610162535507095120150185240300400

...

...

...

...3.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

34465974

101128162195235290347397444500578655754

...

...

...

...79

100126152183226271310346390452512588

24.814.8

9.26.23.72.41.61.20.870.640.480.400.350.290.240.230.22

...

...

...

...6.13.92.51.91.41.00.750.600.500.420.330.300.28

2737506488

119157194235299362419481549645735859

...

...

...

...6993

122151183234282327375428503575670

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) a) Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w

- In air : Ambient temperature 30˚Cb) In three phase system decrease above listed current ratings by 10%

39

DOUBLE STEEL TAPE ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper con-ductors, solid, circular stranded, or sec-toral stranded conforming to the ap-plicable requirements of IEC 60228.

2.2 Insulation

PVC based thermoplastic material con-forming to the applicable requirementsof VDE 0209.

2.3 Assembly

Insulated conductors are laid up, filledwhere necessary with non-hygroscopicmaterial and covered with an additionallayer of extruded thermoplastic materi-al or a PVC binding tape.

2.4 Concentric Conductor

Bare, plain, annealed electrolytic cop-per wires are layed over the commoncovering of cores with a counter helixof copper tape on top.

2.5 Sheath

PVC based thermoplastic material, con-forming to the applicable requirementsof VDE 0209.

2.6 TESTS

Conforming to the applicable re-quirements of relative specifications.

5.3 CONCENTRIC CONDUCTOR, PVC INSULATED AND SHEATHED 0.6 / 1 KV POWER CABLES

4 2 1

3 2 1

3

54

4 PVC sheath

5 Bedding

3 Concentric copper wires

2 PVC insulation

1 Stranded circular copper conductor

40

1. SCOPE

This specification covers circular, single, twin, three or four PVC insulatedconductors with a concentric conductor over the assembly of cores, rated 0.6/1KV,type NYCY to VDE 0271; for use in aerial, direct burial, conduit, open tray andundergroud duct installations, These cables offer high resistance to ageing,abrasion, moisture, chemicals, oils and acids and afford protection of phasecoductors against external ingress.

Where the thermal resistivity is different (not 100˚ C.cm/w) the current rating shouldbe multiplied by the correction factors shown in the following table.

Nature of the soil Soil thermal resistivity˚C.cm/w Correction factor

405070

1.251.211.13

Very wet soil

85100

1.051.00

Normal soil

120150

0.940.86

Dry soil

200250300

0.760.700.65

Very dry soil

05

10

1520253035404550

Soiltemperature

(˚C)

651.201.151.11

1.0510.940.880.820.750.670.58

701.181.141.10

1.0510.950.890.840.770.710.63

Carrying core temperature (˚C)

751.171.131.09

1.0410.950.900.850.800.740.67

801.151.121.08

1.0410.960.910.870.820.760.71

851.141.111.07

1.0410.960.920.880.830.780.73

901.131.101.07

1.0410.960.930.890.850.800.76

951.131.101.06

1.0310.970.930.890.860.820.77

1001.121.091.06

1.0310.970.940.900.870.830.79

1051.111.081.06

1.0310.970.940.910.870.840.80

Correction factor for different soil thermal resistivity

Correction factor for different soil temperatures

Where the temperature of the soil is different (not 20˚C) the current rating should bemultiplied by the following correction factors.

5

When several cables or ducts are laid underground with less than one meter spacing thecurrent rating values should be multiplied by the following correction factors :

Number ofcircuits

Touchingcables

One diameterspaced cables

a = D

2

3

4

5

6

0.76

0.64

0.57

0.52

0.49

0.79

0.67

0.61

0.56

0.53

0.84

0.74

0.69

0.65

0.60

0.88

0.79

0.75

0.71

0.69

0.92

0.85

0.82

0.80

0.78

a = 0.25m a = 0.5m a = 1.0m

4.4. 2. CABLES LAID “ IN AIR ” :

The stated values are for cables or ducts laid “ in air ” with an ambient temperature of30˚C and out of direct sunlight, spaced so that the temperature rise of individual cableshas no influence on others. The spacing between adjacent cables is at least twice thecable or duct diameter.When the ambient temperature is different ( not 30˚C ) the current rating values shouldbe multiplied by the following correction factors :

Ambienttemperature (˚C)

05

101520253035404550556065707580859095

100

Carrying core temperature (˚C)

1.361.311.251.201.131.0710.930.850.760.650.530.38

1.321.271.221.171.121.0610.940.870.790.710.610.500.35

1.291.251.201.151.111.0510.940.880.820.750.670.580.470.33

1.261.221.181.141.101.0510.950.890.840.770.710.630.550.450.32

1.241.211.171.131.091.0410.950.900.850.800.740.670.600.520.430.30

1.221.191.151.121.081.0410.960.910.870.820.760.710.650.580.500.410.29

1.211.181.141.111.071.0410.960.920.880.830.780.730.680.620.550.480.390.28

1.201.161.131.101.071.0410.960.930.890.850.800.760.710.650.600.530.460.380.27

1.181.151.131.101.061.0310.970.930.890.860.820.770.730.680.630.580.520.450.370.26

65 70 75 80 85 90 95 100 105

Correction factor of proximity effect for underground cables

D = overall outer sheath diameter a = Space between cables

Correction factor for different ambient temperatures

Single or multicore cables

6

When several cables are grouped, the current ratings values should be corrected asfollows :

ad

H

a & HNumber of layers

1234561

Number of cables

1

1.000.920.850.820.800.791.00

Distance

≥ 2d

1/4d to 2d

≤ 1/4d

No proximity effect2

0.940.870.810.780.760.750.80

3

0.910.840.780.740.720.710.70

4

0.880.810.760.730.710.700.65

5

0.870.800.750.720.700.690.60

6

0.860.790.740.720.700.680.57

Correction of proximity effect for Cables in air

4.5 VOLTAGE DROP

In addition to the current rating, the determination of the cross sectional area shouldensure that the selected cable size is capable to carry the required current betweensending and receiving ends of line with a maximum of 3 % in voltage drop for lightingpurpose circuits and 5 % for others.

The voltage drop values shown in the electrical characteristics tables are in V/A x Kmcalculated for a maximum core temperature of 70˚C for PVC cables and 90˚C forXLPE cables.

The voltage drop between sending and receiving ends of line is :DU = U1 - U2 in VoltsDU = U1 - U2 x 100 in %

U1

In D.C.In Single phaseIn three phase

:::

DU = 2 l RIDU = 2 l I ( R cos ϕ + LW sin ϕ )DU = l I√3 ( R cos ϕ + LW sin ϕ )

7

Voltage drop in voltCable length in kmCurrent rating in AmperConductor resistance at the maximum operating temperature in Ohm/kmInductance in H/kmPulsation = 2 πF = 314 for F = 50 HzPower factor

0.1446424375458436351557538439

4.6 CONDUCTORS SHORT - CIRCUIT CURRENT

Current densities given in the table below are in (A / mm2 ), for different insulationmaterials and different overload time.

Temperatureof conductors

overload in secs0.2315300237324309248394380311

0.5199189150205195158249241196

Copper AluminiumConductor metal

Current density ( A / mm2 )

For an overload duration (t) different than those figured in the above table, thecorrespondant current density is given by the following formula :

Current density for a duration (t) = Current density for 1 sec

√ t

WhereDUlIRLWcos ϕ

=======

material

PE

PVC

XLPE

Initial˚C

Final˚C

203070203070203090

150

160

250

1141134106145138111176170139

999575

1029879

12412098

2 0.1294278221304284231367354288

0.2208197156215210163260254203

13112599

135127104164159129

0.5938870969073

11611291

1 2666349686452827965

4.7 MINIMUM BENDING RADIUS

Listed values represent the permanent bending radius the cables withstand in fixedinstallation and on dispatching reels. Other constraints may impose greater bendingradius.

Unarmoured single core cables

Unarmoured multi core cables

Armoured cables - steel tapes

- steel wires

Cable on drum Cable duringinstallation

Installed Cable

18 D

12 D

16 D

20 D

9 D

6 D

8 D

10 D

D = Overall diameter in mm

9 D

6 D

8 D

10 D

8

5 INDUSTRIAL AND DISTRIBUTION 0.6 / 1KV POWER CABLES

1. SCOPE

This specification covers single, two,three or four core cables, PVC or XLPEinsulated and PVC sheathed, rated at 0.6/1KV, unarmoured type to InternationalElectrotechnical Commission PublicationIEC 60502-1 for use in cable ducts andindoors and for underground burial, wherethey are not likely to suffer mechanicaldamage.

The cables have excellent thermalproperties, high dielectric strength andhigh resistance to ageing, abrasion,moisture, chemicals, acids and oils.

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper oraluminium conductors, solid, circularstranded, or sectoral stranded; conformingto the applicable requirements of IEC228.

2.2 Insulation

PVC based thermoplastic or XLPEthermosetting material, conforming tothe applicable requirements of IEC 60502-1.

2.3 Assembly

Insulated conductors are laid up, filledwhere necessary with non-hygroscopicmaterial and covered with an additionallayer of extruded thermoplasticmaterial or non-hygroscopic bindingtape.

2.4 Sheath

PVC based thermoplastic material,conforming to the applicablerequirements of IEC 60502-1.

2.5 TESTS

Conforming to the applicablerequirements of IEC 60502-1 either onraw materials or on finished products.

5.1 UNARMOURED, PVC OR XLPE INSULATED AND PVC SHEATHED CABLES

1

Stranded circular copper oraluminium conductor

*stranded sectoral copper oraluminium conductor

2 PVC or XLPE insulation

3 PVC Sheath

3 2 1

3 2 1

3 2 1*

10

DIMENSIONAL CHARACTERISTICS

UNARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

1 x 1.51 x 2.51 x 41 x 61 x 101 x 161 x 251 x 351 x 501 x 701 x 951 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.42.62.82.82.8

1.41.41.41.41.41.41.41.41.41.41.51.51.61.71.81.92.02.12.22.3

1.381.782.252.953.824.836.027.158.30

10.0011.8013.3014.8016.5519.4021.3024.1027.3 31.0 37.1

2.983.384.254.955.826.838.429.55

11.1012.8015.0016.5018.4020.5523.8026.1029.3032.9036.6042.70

5.96.37.27.98.79.8

1213141619202225283134384248

1322355389

141223309418604838

105912991630214326883439433555977203

496286

113160225332434565775

1060130015901990259032104070510064508250

...

...

...

...28436895

128185256324398499655822

1051132517102188

...

...

...

...99

127177220275356478565690860

110013401680209025603240

100010001000100010001000500500500500500500500500500500500500500250

SINGLE CORE

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35

0.80.81.01.01.01.01.21.2

1.81.81.81.81.81.81.81.8

1.381.782.252.953.824.836.027.15

2.983.384.254.955.826.838.429.55

1111131516192224

274470

107179284450624

131164233306425590870

1130

...

...

...

...5587

138191

...

...

...

...301393560695

100010001000100010001000500500

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Grater sections also available

11

DIMENSIONAL CHARACTERISTICS

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

1.81.81.81.81.81.81.81.81.81.92.12.22.32.52.72.9

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.983.384.254.955.826.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

11121415172023242730353844465259

4066

105160269426675945

12791848256232423978499065578226

152194279373530750

112013101730239032804060500062008050

10050

...

...

...

...82

130206289391565783990

1216152520042514

...

...

...

...343454650655840

1110150018102240274035004340

100010001000100010001000500500500500500250250250250250

THREE CORE

FOUR CORE

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

1.81.81.81.81.81.81.81.81.92.12.22.32.52.72.93.2

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.983.384.254.955.826.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

12131517192125273034394347535966

5388

140213358568900

12591705246434174323530566548743

10969

180232337456655940

14101730232032204400545066508350

1080013500

...

...

...

...110174275385521754

104413201621203326723352

...

...

...

...310545785855

11401510203024502970373047305900

100010001000100010001000500500500500500250250250250250

UNARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

12

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

Ph.1.21.21.41.41.61.61.82.02.22.4

1.81.81.92.02.22.32.42.62.83.0

24262932384144505662

817108615042163298938584595584576389552

132015302080285038904890580073509500

11800

249333460662914

11791404178623342919

750775

10401350182022102610329042005150

500500500500500250250250250250

FOUR CORE WITH REDUCED NEUTRAL

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.1.01.01.21.21.41.41.41.61.61.8

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.8.42shapedshaped

N.6.836.838.42

shapedshapedshapedshapedshapedshapedshaped

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Grater sections also available

UNARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

13

Where the thermal resistivity is different (not 100˚ C.cm/w) the current rating shouldbe multiplied by the correction factors shown in the following table.

Nature of the soil Soil thermal resistivity˚C.cm/w Correction factor

405070

1.251.211.13

Very wet soil

85100

1.051.00

Normal soil

120150

0.940.86

Dry soil

200250300

0.760.700.65

Very dry soil

05

10

1520253035404550

Soiltemperature

(˚C)

651.201.151.11

1.0510.940.880.820.750.670.58

701.181.141.10

1.0510.950.890.840.770.710.63

Carrying core temperature (˚C)

751.171.131.09

1.0410.950.900.850.800.740.67

801.151.121.08

1.0410.960.910.870.820.760.71

851.141.111.07

1.0410.960.920.880.830.780.73

901.131.101.07

1.0410.960.930.890.850.800.76

951.131.101.06

1.0310.970.930.890.860.820.77

1001.121.091.06

1.0310.970.940.900.870.830.79

1051.111.081.06

1.0310.970.940.910.870.840.80

Correction factor for different soil thermal resistivity

Correction factor for different soil temperatures

Where the temperature of the soil is different (not 20˚C) the current rating should bemultiplied by the following correction factors.

5

When several cables or ducts are laid underground with less than one meter spacing thecurrent rating values should be multiplied by the following correction factors :

Number ofcircuits

Touchingcables

One diameterspaced cables

a = D

2

3

4

5

6

0.76

0.64

0.57

0.52

0.49

0.79

0.67

0.61

0.56

0.53

0.84

0.74

0.69

0.65

0.60

0.88

0.79

0.75

0.71

0.69

0.92

0.85

0.82

0.80

0.78

a = 0.25m a = 0.5m a = 1.0m

4.4. 2. CABLES LAID “ IN AIR ” :

The stated values are for cables or ducts laid “ in air ” with an ambient temperature of30˚C and out of direct sunlight, spaced so that the temperature rise of individual cableshas no influence on others. The spacing between adjacent cables is at least twice thecable or duct diameter.When the ambient temperature is different ( not 30˚C ) the current rating values shouldbe multiplied by the following correction factors :

Ambienttemperature (˚C)

05

101520253035404550556065707580859095

100

Carrying core temperature (˚C)

1.361.311.251.201.131.0710.930.850.760.650.530.38

1.321.271.221.171.121.0610.940.870.790.710.610.500.35

1.291.251.201.151.111.0510.940.880.820.750.670.580.470.33

1.261.221.181.141.101.0510.950.890.840.770.710.630.550.450.32

1.241.211.171.131.091.0410.950.900.850.800.740.670.600.520.430.30

1.221.191.151.121.081.0410.960.910.870.820.760.710.650.580.500.410.29

1.211.181.141.111.071.0410.960.920.880.830.780.730.680.620.550.480.390.28

1.201.161.131.101.071.0410.960.930.890.850.800.760.710.650.600.530.460.380.27

1.181.151.131.101.061.0310.970.930.890.860.820.770.730.680.630.580.520.450.370.26

65 70 75 80 85 90 95 100 105

Correction factor of proximity effect for underground cables

D = overall outer sheath diameter a = Space between cables

Correction factor for different ambient temperatures

Single or multicore cables

6

When several cables are grouped, the current ratings values should be corrected asfollows :

ad

H

a & HNumber of layers

1234561

Number of cables

1

1.000.920.850.820.800.791.00

Distance

≥ 2d

1/4d to 2d

≤ 1/4d

No proximity effect2

0.940.870.810.780.760.750.80

3

0.910.840.780.740.720.710.70

4

0.880.810.760.730.710.700.65

5

0.870.800.750.720.700.690.60

6

0.860.790.740.720.700.680.57

Correction of proximity effect for Cables in air

4.5 VOLTAGE DROP

In addition to the current rating, the determination of the cross sectional area shouldensure that the selected cable size is capable to carry the required current betweensending and receiving ends of line with a maximum of 3 % in voltage drop for lightingpurpose circuits and 5 % for others.

The voltage drop values shown in the electrical characteristics tables are in V/A x Kmcalculated for a maximum core temperature of 70˚C for PVC cables and 90˚C forXLPE cables.

The voltage drop between sending and receiving ends of line is :DU = U1 - U2 in VoltsDU = U1 - U2 x 100 in %

U1

In D.C.In Single phaseIn three phase

:::

DU = 2 l RIDU = 2 l I ( R cos ϕ + LW sin ϕ )DU = l I√3 ( R cos ϕ + LW sin ϕ )

7

Voltage drop in voltCable length in kmCurrent rating in AmperConductor resistance at the maximum operating temperature in Ohm/kmInductance in H/kmPulsation = 2 πF = 314 for F = 50 HzPower factor

0.1446424375458436351557538439

4.6 CONDUCTORS SHORT - CIRCUIT CURRENT

Current densities given in the table below are in (A / mm2 ), for different insulationmaterials and different overload time.

Temperatureof conductors

overload in secs0.2315300237324309248394380311

0.5199189150205195158249241196

Copper AluminiumConductor metal

Current density ( A / mm2 )

For an overload duration (t) different than those figured in the above table, thecorrespondant current density is given by the following formula :

Current density for a duration (t) = Current density for 1 sec

√ t

WhereDUlIRLWcos ϕ

=======

material

PE

PVC

XLPE

Initial˚C

Final˚C

203070203070203090

150

160

250

1141134106145138111176170139

999575

1029879

12412098

2 0.1294278221304284231367354288

0.2208197156215210163260254203

13112599

135127104164159129

0.5938870969073

11611291

1 2666349686452827965

4.7 MINIMUM BENDING RADIUS

Listed values represent the permanent bending radius the cables withstand in fixedinstallation and on dispatching reels. Other constraints may impose greater bendingradius.

Unarmoured single core cables

Unarmoured multi core cables

Armoured cables - steel tapes

- steel wires

Cable on drum Cable duringinstallation

Installed Cable

18 D

12 D

16 D

20 D

9 D

6 D

8 D

10 D

D = Overall diameter in mm

9 D

6 D

8 D

10 D

8

5 INDUSTRIAL AND DISTRIBUTION 0.6 / 1KV POWER CABLES

1. SCOPE

This specification covers single, two,three or four core cables, PVC or XLPEinsulated and PVC sheathed, rated at 0.6/1KV, unarmoured type to InternationalElectrotechnical Commission PublicationIEC 60502-1 for use in cable ducts andindoors and for underground burial, wherethey are not likely to suffer mechanicaldamage.

The cables have excellent thermalproperties, high dielectric strength andhigh resistance to ageing, abrasion,moisture, chemicals, acids and oils.

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper oraluminium conductors, solid, circularstranded, or sectoral stranded; conformingto the applicable requirements of IEC228.

2.2 Insulation

PVC based thermoplastic or XLPEthermosetting material, conforming tothe applicable requirements of IEC 60502-1.

2.3 Assembly

Insulated conductors are laid up, filledwhere necessary with non-hygroscopicmaterial and covered with an additionallayer of extruded thermoplasticmaterial or non-hygroscopic bindingtape.

2.4 Sheath

PVC based thermoplastic material,conforming to the applicablerequirements of IEC 60502-1.

2.5 TESTS

Conforming to the applicablerequirements of IEC 60502-1 either onraw materials or on finished products.

5.1 UNARMOURED, PVC OR XLPE INSULATED AND PVC SHEATHED CABLES

1

Stranded circular copper oraluminium conductor

*stranded sectoral copper oraluminium conductor

2 PVC or XLPE insulation

3 PVC Sheath

3 2 1

3 2 1

3 2 1*

10

DIMENSIONAL CHARACTERISTICS

UNARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

1 x 1.51 x 2.51 x 41 x 61 x 101 x 161 x 251 x 351 x 501 x 701 x 951 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.42.62.82.82.8

1.41.41.41.41.41.41.41.41.41.41.51.51.61.71.81.92.02.12.22.3

1.381.782.252.953.824.836.027.158.30

10.0011.8013.3014.8016.5519.4021.3024.1027.3 31.0 37.1

2.983.384.254.955.826.838.429.55

11.1012.8015.0016.5018.4020.5523.8026.1029.3032.9036.6042.70

5.96.37.27.98.79.8

1213141619202225283134384248

1322355389

141223309418604838

105912991630214326883439433555977203

496286

113160225332434565775

1060130015901990259032104070510064508250

...

...

...

...28436895

128185256324398499655822

1051132517102188

...

...

...

...99

127177220275356478565690860

110013401680209025603240

100010001000100010001000500500500500500500500500500500500500500250

SINGLE CORE

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35

0.80.81.01.01.01.01.21.2

1.81.81.81.81.81.81.81.8

1.381.782.252.953.824.836.027.15

2.983.384.254.955.826.838.429.55

1111131516192224

274470

107179284450624

131164233306425590870

1130

...

...

...

...5587

138191

...

...

...

...301393560695

100010001000100010001000500500

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Grater sections also available

11

DIMENSIONAL CHARACTERISTICS

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

1.81.81.81.81.81.81.81.81.81.92.12.22.32.52.72.9

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.983.384.254.955.826.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

11121415172023242730353844465259

4066

105160269426675945

12791848256232423978499065578226

152194279373530750

112013101730239032804060500062008050

10050

...

...

...

...82

130206289391565783990

1216152520042514

...

...

...

...343454650655840

1110150018102240274035004340

100010001000100010001000500500500500500250250250250250

THREE CORE

FOUR CORE

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

1.81.81.81.81.81.81.81.81.92.12.22.32.52.72.93.2

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.983.384.254.955.826.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

12131517192125273034394347535966

5388

140213358568900

12591705246434174323530566548743

10969

180232337456655940

14101730232032204400545066508350

1080013500

...

...

...

...110174275385521754

104413201621203326723352

...

...

...

...310545785855

11401510203024502970373047305900

100010001000100010001000500500500500500250250250250250

UNARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

12

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

Ph.1.21.21.41.41.61.61.82.02.22.4

1.81.81.92.02.22.32.42.62.83.0

24262932384144505662

817108615042163298938584595584576389552

132015302080285038904890580073509500

11800

249333460662914

11791404178623342919

750775

10401350182022102610329042005150

500500500500500250250250250250

FOUR CORE WITH REDUCED NEUTRAL

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.1.01.01.21.21.41.41.41.61.61.8

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.8.42shapedshaped

N.6.836.838.42

shapedshapedshapedshapedshapedshapedshaped

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Grater sections also available

UNARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

13

DIMENSIONAL CHARACTERISTICS

CONCENTRIC CONDUCTOR PVC INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to VDE 271 / 3.69

TYPE : NYCY

Radial Thickness of Lengthon

drum

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable

mm2 mm mmmm mm Kg/Km Kg/Km m

OuterSheath

Nominalcross

section* Insulation

TWO CORE

0.91.01.01.01.01.2

1.81.81.81.81.81.8

1.782.252.953.824.836.02

3.584.254.955.826.838.42

9.39.09.9121315

4369

101175283443

112147197287413580

100010001000100010001000

mm

0.91.01.01.01.01.2

1.81.81.81.81.82.0

1.782.252.953.824.836.02

3.584.254.955.826.838.42

151718212429

87130207353567902

315380505710

10301530

10001000100010001000500

FOUR CORE

0.80.80.80.81.22.2

* - Solid conductor for sizes up to and including 4 mm2.- Stranded circular conductor for sizes of 6 mm2 and above.- Greater sections also available

1x 2.5 +2.51 x 4 + 41 x 6 + 61 x 10 +101 x 16 + 161 x 25 + 25

3x 2.5 + 2.53 x 4 + 43 x 6 + 63 x 10 + 103 x 16 + 163 x 25 + 25

41

Current carrying capacity**

mm2 Ω/Km Amp Amp Amp

ELECTRICAL CHARACTERISTICS

DC Resistance at 20˚C* Underground CableTwo Core Three core Two Core Three core

Cables in air

Nominalcross

section

Amp

Voltage DropCos ϕ = 0.8

Two Core Three core

V/A x Km V/A x Km

2.546101625

7.414.613.081.831.15

0.727

41536791

115146

36465879

100132

14.29.06.13.72.31.5

12.37.85.33.22.01.3

2635466385

112

2432415776

100

* At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

** Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w- In air : Ambient temperature 30˚C

1. SCOPE

This specification covers PVC or XLPEinsulated, multicore, self supportingcables rated 0.6/1KV; for use outdoorsin overhead and surface mountingapplications on walls, in street lightingand other overhead electricalapplications. These cables have highdielectric strength, excellent aging,thermal, chemical and mechanicalproperties which make them highlyresistant to the most strenuous weatherconditions.

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper or al-uminium conductors, solid, circularstranded conforming to the applicable re-quirements of IEC 60228.

2.2 Insulation

PVC based thermoplastic or XLPE ther-mosetting material conforming to the ap-plicable requirements of VDE 0209.

2.3 Assembly

Insulated conductors are laid up, filledwith non-hygroscopic material and cov-ered with an extruded thermoplastic ma-terial or a PVC binding tape.

2.4 Suspension strand

Torsion free strand of galvanized steelwires, laid up together parallel to the as-sembly of cores under a common PVCsheath.

2.5 Sheath

PVC based thermoplastic material si-multaneously covering steel supporter andassembly of cores and conforming to theapplicable requirements of VDE 0209.

2.6 TESTS

Conforming to the applicable re-quirements of relative specifications.

4 PVC sheath

5 Stranded galvanized steel wires

3 Bedding

2 PVC or XLPE insulation

1Stranded circular copperor aluinium conductor

5.4 SELF SUPPORTED, AERIAL, PVC OR XLPE INSULATED,0.6 / 1 KV POWER CABLES

42

4

2

1

3

5

43

DIMENSIONAL CHARACTERISTICS

SELF SUPPORTED AERIAL PVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to VDE 0271 / 3.69

Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableSheathNominal

crosssection*

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 25

0.80.81.01.01.01.01.2

1.81.81.81.81.81.81.8

1.381.782.252.953.824.836.02

2.983.384.254.955.826.838.42

274470

107179284450

252285352427545710990

...

...

...

...5587

138

...

...

...

...421515680

100010001000100010001000500

mm

7/1.27/1.27/1.27/1.27/1.27/1.27/1.2

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 25

0.80.81.01.01.01.01.2

1.81.81.81.81.81.81.8

1.381.782.252.953.824.836.02

2.983.384.254.955.826.838.42

4066

105160269426675

273315400494650870

1240

...

...

...

...82

130206

...

...

...

...463575770

100010001000100010001000500

THREE CORE

7/1.27/1.27/1.27/1.27/1.27/1.27/1.2

RadialThickness

ofInsulation

FOUR CORE

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 25

0.80.81.01.01.01.01.2

1.81.81.81.81.81.81.8

1.381.782.252.953.824.836.02

2.983.384.254.955.826.838.42

5388

140213358568900

301353458575775

10601530

...

...

...

...110174275

...

...

...

...525665905

100010001000100010001000500

7/1.27/1.27/1.27/1.27/1.27/1.27/1.2

* - Solid conductor for sizes up to and including 4 mm2.- Stranded circular conductor for remaining sizes.- Different sections also available.

Sizeof thesteel

messenger

nbr./dia

7.27.27.27.27.27.27.2

11121415171922

21222425272932

7.27.27.27.27.27.27.2

12131416182023

22232426283033

7.27.27.27.27.27.27.2

12141517192226

22242527293236

Current carrying capacity (3)

mm2 Ω/Km Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C (1)

AluCopper

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.546101625

...

...

...

...3.081.911.20

12.17.414.613.081.831.150.727

223040527196

127

23.314.29.06.13.72.31.5

...

...

...

...6.13.82.4

...

...

...

...557599

Copper

44

SELF SUPPORTED AERIAL PVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to VDE 0271 / 3.69

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) Ambient temperature 30˚C

45

DIMENSIONAL CHARACTERISTICS

SELF SUPPORTED AERIAL XLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to VDE 0271 / 3.69

Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableSheathNominal

crosssection*

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 25

0.70.70.70.70.70.70.9

1.81.81.81.81.81.81.8

1.381.782.252.953.824.836.02

2.783.183.654.355.226.237.82

274470

107179284450

241272316383496650915

...

...

...

...5587

138

100010001000100010001000500

mm

7/1.27/1.27/1.27/1.27/1.27/1.27/1.2

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 25

0.70.70.70.70.70.70.9

1.81.81.81.81.81.81.8

1.381.782.252.953.824.836.02

2.783.183.654.355.226.237.82

4066

105160269426675

258299356441590795

1140

...

...

...

...82

130206

...

...

...

...403500670

100010001000100010001000500

THREE CORE

7/1.27/1.27/1.27/1.27/1.27/1.27/1.2

RadialThickness

ofInsulation

Sizeof thesteel

messenger

FOUR CORE

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 25

0.70.70.70.70.70.70.9

1.81.81.81.81.81.81.8

1.381.782.252.953.824.836.02

2.783.183.654.355.226.237.82

5388

140213358568900

282333405510700970

1410

...

...

...

...110174275

...

...

...

...452575785

100010001000100010001000500

7/1.27/1.27/1.27/1.27/1.27/1.27/1.2

* - Solid conductor for sizes up to and including 4 mm2.- Stranded circular conductor for remaining sizes.- Different sections also available.

nbr./dia

...

...

...

...372

14561605

7.27.27.27.27.27.27.2

10111213151721

20212223252731

7.27.27.27.27.27.27.2

11121314161822

21222324262832

7.27.27.27.27.27.27.2

11121415172024

21222425273034

Current carrying capacity (3)

mm2 Ω/Km Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C (1)

AluCopper

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.546101625

...

...

...

...3.081.911.20

12.17.414.613.081.831.150.727

2737506488

119157

24.814.89.26.23.72.41.6

...

...

...

...6.13.92.5

...

...

...

...6993122

Copper

46

SELF SUPPORTED AERIAL XLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to VDE 0271 / 3.69

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) Ambient temperature 30˚C

47

1. SCOPEThis specification covers multicorecables for signalisation and control pur-poses, PVC insulated and sheathed rat-ed 0.6 / 1 KV; to International Electro-technical Commission IEC 60502-1,for use in cable ducts and indoors andfor underground burial. High re-sistance to deformations under hightemperature and pressure, and high re-sistance to ageing, abrasion, moisture,chemicals, acids and oils.

2. CONSTRUCTION

2.1 ConductorPlain, annealed electrolytic copper con-ductors, solid or circular stranded con-forming to the applicable requirementsof IEC 60228.

2.2 InsulationPVC based thermoplastic or XLPEthermosetting material conforming tothe applicable requirements of IEC 60502-1.

2.3 AssemblyInsulated conductors are laid up, filledwhere necessary with non-hygroscopicmaterial or covered with a layer of non-hygroscopic tape.The assembly is covered with an extrudedlayer of PVC in armoured cables.

2.4 Armour ( in armoured cables )Galvanized steel wires or double steeltapes, covering the assembly of cores,complying to the applicable re-quirements of IEC 60502-1.

2.5 SheathPVC based thermoplastic material con-forming to the applicable requirementsof IEC 60502-1.

2.6 TESTSConforming to the applicable re-quirements of IEC 60502-1 either onraw materials or on finished products.

5.5 CONTROL, PVC OR XLPE INSULATED AND PVC SHEATHEDMULTICORE CABLES.

3

2

1

4

2

1

5

3

4 Bedding

5Round galvanized steelwire armour

3 PVC sheath

2 PVC or XLPE insulation

1Solid circular copperconductor

DIMENSIONAL CHARACTERISTICS

UNARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV CONTROLE CABLES

Conforming to IEC 60502-1

Radial Thickness of Lengthon

drum

Nominal Diameters Approximative net weight

Conductor Insulation Overall Copper Cable

mm mmmm mm Kg/Km Kg/Km m

OuterSheathInsulation

CONDUCTOR 1.5 mm2

mm

Number*

ofConductors

1.81.81.81.81.81.81.81.81.81.81.81.9

1.381.381.381.381.381.381.381.381.381.381.381.38

2.982.982.982.982.982.982.982.982.982.982.982.98

0.80.80.80.80.80.80.80.80.80.80.80.8

131415171718202324262729

6692

105131157184249314393484524628

1000100010001000100010001000100010001000500500

CONDUCTOR 2.5 mm2

578

101214192430374048

1.81.81.81.81.81.81.81.81.81.91.92.0

1.781.781.781.781.781.781.781.781.781.781.781.78

3.383.383.383.383.383.383.383.383.383.383.383.38

0.80.80.80.80.80.80.80.80.80.80.80.8

141516181920222526293033

1091531752182623054145236538068711045

277325375448515585755940

1140139015001790

1000100010001000100010001000100010001000500500

48

* Greater number of conductors also available.

578

101214192430374048

212244281332378428545680815975

10501250

49

DIMENSIONAL CHARACTERISTICS

ARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV CONTROLE CABLES

Conforming to IEC 60502-1

Radial Thickness of Lengthon

drum

Nominal Diameters Approximative net weight

Conductor Insulation Overall Copper Cable

mm mmmm mm Kg/Km Kg/Km m

OuterSheathInsulation

CONDUCTOR 1.5 mm2

mm mm

InnerSheath

Number*

ofConductors

578

101214192430374048

1.81.81.81.81.81.81.81.81.91.92.02.1

1.381.381.381.381.381.381.381.381.381.381.381.38

2.982.982.982.982.982.982.982.982.982.982.982.98

0.80.80.80.80.80.80.80.80.80.80.80.8

1.01.01.01.01.01.01.01.01.01.01.01.0

171819212324252830323336

6692

105131147184249314393484524628

455520575670

10301080126015001700192020202560

10001000100010001000100010001000500500500500

CONDUCTOR 2.5 mm2

578

101214192430374048

1.81.81.81.81.81.81.81.92.02.12.12.2

1.781.781.781.781.781.781.781.781.781.781.781.78

3.383.383.383.383.383.383.383.383.383.383.383.38

0.80.80.80.80.80.80.80.80.80.80.80.8

1.01.01.01.01.01.01.01.01.01.01.21.2

181920242525273133363740

109153175218262305414523653806871

1045

535625700

111012001310155018702130269028903310

1000100010001000100010001000500500500500500

* Greater number of conductors also available.

Current carrying capacity (3)

mm2 Ω/Km Amp Amp Amp

Alu

Ω/Km

DC Resistance at 20˚C(1)

Underground CableCopper Alu Copper Alu

CopperCables in air

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.54610162535507095120150185240300400500630800

...

...

...

...3.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.07780.06050.04690.0367

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.0221

3041536791

115146176212261313358400451522590680769870979

...

...

...

...6790

114137165204244279312352407460530599678763

23.314.2

9.06.13.72.31.51.10.90.60.50.40.40.30.30.20.20.20.20.2

...

...

...

...6.13.82.41.71.41.00.70.60.50.40.30.30.20.20.20.2

223040527196

127157190242293339390444522595695780885990

...

...

...

...557599

125151192232269309353415472552618705790

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) a) Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w

- In air : Ambient temperature 30˚Cb) In three phase system decrease above listed current ratings by 10%

UNARMOURED, PVC INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

14

ELECTRICAL CHARACTERISTICS

DIMENSIONAL CHARACTERISTICS

UNARMOURED, XLPE INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

1 x 1.51 x 2.51 x 41 x 61 x 101 x 161 x 251 x 351 x 501 x 701 x 951 x 1201 x 1501 x 1851 x 2401 x 3001 x 4001 x 5001 x 6301 x 800

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.81.92.22.42.6

1.41.41.41.41.41.41.41.41.41.41.51.51.61.61.71.81.92.02.22.3

1.381.782.252.953.824.836.027.158.3010.0011.8013.3014.8016.5519.4021.3024.1027.0031.0037.10

2.783.183.654.355.226.237.828.9510.312.2014.0015.7017.6019.7522.8024.9028.1031.7035.8042.30

5.76.16.67.38.19.2

1112141618192124272933364148

1322355389

141223309418604838

105912991630214326883439433555977203

45577499

144206307406525735

1000124015201890246030603890487062508050

...

...

...

...28436895

128185256324398499655822

1051132517102188

...

...

...

...83

108152192235316418505620760970

11901500186023703040

100010001000100010001000500500500500500500500500500500500500500250

SINGLE CORE

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35

0.70.70.70.70.70.70.90.9

1.81.81.81.81.81.81.81.8

1.381.782.252.953.824.836.027.15

2.783.183.654.355.226.237.828.95

1011121315172123

274470

107179284450624

120151195262375530795

1040

...

...

...

...5587

138191

...

...

...

...251333483605

100010001000100010001000500500

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Grater sections also available

15

DIMENSIONAL CHARACTERISTICS

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.81.92.02.12.32.42.62.8

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.783.183.654.355.226.237.82

shapedshapedshapedshapedshapedshapedshapedshapedshaped

11121314161822222529323642445054

4066

105160269426675945

12781848256232423978499065578325

137178235320470675

1020122016102270306038404760590076509550

...

...

...

...82

130206289391565783990

1216152520042514

...

...

...

...283379550565725985

128015902000244031003740

100010001000100010001000500500500500500250250250250250

THREE CORE

FOUR CORE

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.81.92.02.12.32.42.62.83.0

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.783.183.654.355.226.237.82

shapedshapedshapedshapedshapedshapedshapedshapedshaped

11121415172024252833374145505662

5388

140213358568900

12591705246434174323530566548743

10969

161212284391580850

12901620215030304100515063507950

1030012850

...

...

...

...110174275385521754

104413201621202326723352

...

...

...

...332456665745965

1320173021502670333042305250

100010001000100010001000500500500500500250250250250250

UNARMOURED, XLPE INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

16

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section * Insulation

Ph.0.90.91.01.11.11.21.41.61.71.8

1.81.81.81.92.12.22.32.52.72.9

23242631353942475359

817108615042163298938584594584576389552

120014201910267036204630550070009000

11200

249333460662914

11791404178623342919

630665865

1170150019502310294037004570

500500500500500250250250250250

FOUR CORE WITH REDUCED NEUTRAL

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.0.70.70.90.91.01.11.11.11.21.4

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.7.82shapedshaped

N.6.236.237.82

shapedshapedshapedshapedshapedshapedshaped

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Grater sections also available

UNARMOURED, XLPE INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

17

Current carrying capacity (3)

mm2 Ω/Km Amp Amp Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C(1)

Underground CableCopper Alu Copper Alu

CopperCables in air

Nominalcross

section

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) a) Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w

- In air : Ambient temperature 30˚Cb) In three phase system decrease above listed current ratings by 10%

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.54610162535507095120150185240300400500630800

...

...

...

...3.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.07780.06050.04690.0367

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.04700.03660.02830.0221

34465974

101128162195235290347397444500578655754852961

1081

...

...

...

...79

100126152183226271310346390452512588665750844

24.814.8

9.26.23.72.41.61.20.870.640.480.400.350.290.240.230.220.220.210.21

...

...

...

...6.13.92.51.91.41.00.750.600.500.420.330.300.280.270.260.26

2737506488

119157194235299362419481549645735859960

10961235

...

...

...

...6993

122151183234282327375428503575670750855955

UNARMOURED, XLPE INSULATED, PVC SHEATHED0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

18

20

5.2 ARMOURED, PVC OR XLPE INSULATED AND PVC SHEATHED CABLES

1. SCOPE

This specification covers PVC or XLPE insulated, circular, twin, three or fourconductors armoured cables, rated at 0.6/1 KV to international Electrotechnicalcommission Publication IEC 60502-1 for use indoors, outdoors, in cable ducts, inwater and for direct burial underground, where severe mechanical stresses arepresent. These cables have high dielectric strength, an excellent resistance todeformations under high temperature and pressure, and high resistance to ageing,abrasion, moisture, chemicals, acids and oils.

2. CONSTRUCTION

2.1 Conductor

Plain, annealed electrolytic copper or Aluminium conductors, solid, circularstranded, or sectoral stranded, conforming to the applicable requirements of IEC60228.

2.2 Insulation

PVC based thermoplastic or XLPE thermosetting material, conforming to theapplicable requirements of IEC 60502-1.

2.3 Assembly

Insulated conductors are laid up, filled where necessary with non-hygroscopicmaterial and covered with an extruded thickness of thermoplastic material.

2.4 Armour

Galvanized round wires, or flat strips, completely covering the assembly of coresand a counter helix of galvanized steel tape on top; or two layers of steel tape,complying to the applicable requirements of IEC 60502-1.

2.5 Sheath

PVC based thermoplastic material, conforming to the applicable requirements ofIEC 60502-1.

2.6 TESTS

Conforming to the applicable requirements of IEC 60502-1 either on Raw materialsor on finished products.

1

Stranded circular copper oraluminium conductor

*stranded sectoral copper oraluminium conductor

2 PVC or XLPE insulation

3 Bedding

4Galvanized flat steel striparmour with flat steel tapeapplied in helical form

6 Double steel tape armoured

7 Galvanized round steelwire armour

5 PVC or PE sheath

12345

12365

12375

1*2365

1*2345

1*2375

21

5.2 ARMOURED, PVC OR XLPE INSULATED AND PVC SHEATHED CABLES

DIMENSIONAL CHARACTERISTICS

GALVANIZED STEEL WIRE ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35

0.80.81.01.01.01.01.21.2

1.81.81.81.81.81.81.81.8

1.381.782.252.953.824.836.027.15

2.983.384.254.955.826.838.429.55

1516171921242830

274470

107179284450624

345394496605760

127016602000

...

...

...

...5587

138191

...

...

...

...635

107013501570

100010001000100010001000500500

mm mm

InnerSheath

1.01.01.01.01.01.01.01.0

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

1.81.81.81.81.81.81.81.92.12.22.32.52.62.83.03.2

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.983.384.254.955.826.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

15161820232529293437424652556166

4066

105160269426675945

12791848256232423978499065578226

374434560685

1170147019602140292037504800610073508700

1080013100

...

...

...

...82

130206289391565783990

1216152520042514

...

...

...

...985

11701490148020302470302038504590520062507400

100010001000100010001000500500500500500250250250250250

THREE CORE

1.01.01.01.01.01.01.01.01.01.21.21.21.41.41.41.6

22

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

FOUR CORE

mm mm

InnerSheath

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

0.80.81.01.01.01.01.21.21.41.41.61.61.82.02.22.4

1.81.81.81.81.81.81.92.02.22.32.52.62.83.03.23.4

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.983.384.254.955.826.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

5388

140213358568900

12591705246434174323530566548743

10969

417490640795

135017202350264036504670645077009100

111001385017600

...

...

...

...110174275385521754

104413201621202326723352

...

...

...

...11001330173017702470296040804700540065007800

10000

100010001000100010001000500500500500500250250250250250

1.01.01.01.01.01.01.01.01.21.21.21.41.41.61.61.6

16171921252731323741475156616875

Ph.1.21.21.41.41.61.61.82.02.22.4

1.91.92.12.22.42.52.72.83.03.2

30313539444953586470

817108615042163298938584594584576389552

22202400329042405450705081509850

1230014850

249333460662914

11791404178623342919

1650165022502740338043704960580070008200

500500500500500250250250250250

FOUR CORE WITH REDUCED NEUTRAL

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.1.01.01.21.21.41.41.41.61.61.8

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.8.42shapedshaped

N.6.836.838.42

shapedshapedshapedshapedshapedshapedshaped

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available

1.01.01.01.21.21.41.41.41.61.6

23

GALVANIZED STEEL WIRE ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Current carrying capacity (3)

mm2 Ω/Km Amp Amp Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C(1)

Underground CableCopper Alu Copper Alu

CopperCables in air

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.54610162535507095120150185240300400

...

...

...

...3.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

3041536791

115146176212261313358400451522590680

...

...

...

...6790

114137165204244279312352407460530

23.314.2

9.06.13.72.31.51.10.90.60.50.40.40.30.30.20.2

...

...

...

...6.13.82.41.71.41.00.70.60.50.40.30.30.2

223040527196

127157190242293339390444522595695

...

...

...

...557599

125151192232269309353415472552

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) a) Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w

- In air : Ambient temperature 30˚Cb) In three phase system decrease above listed current ratings by 10%

24

GALVANIZED STEEL WIRE ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

DIMENSIONAL CHARACTERISTICS

GALVANIZED STEEL WIRE ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

TWO CORE

2 x 1.52 x 2.52 x 42 x 62 x 102 x 162 x 252 x 35

0.70.70.70.70.70.70.90.9

1.81.81.81.81.81.81.81.8

1.381.782.252.953.824.836.027.15

2.783.183.654.355.226.237.828.95

1415161819212629

274470

107179284450624

327372434535685880

15501880

...

...

...

...5587

138191

...

...

...

...560685

12401450

100010001000100010001000500500

mm mm

InnerSheath

1.01.01.01.01.01.01.01.0

3 x 1.53 x 2.53 x 43 x 63 x 103 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.82.02.12.22.42.62.72.93.1

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.783.183.654.355.226.237.82

shapedshapedshapedshapedshapedshapedshapedshapedshaped

15161718202428283135394350535863

4066

105160269426675945

12791848256232423978499065578226

354419490610795

135018201990249035004480540071508300

1035012450

...

...

...

...82

130206289391565783990

1216152520042514

...

...

...

...610

10501350133016002220270031504390484058006650

100010001000100010001000500500500500500250250250250250

THREE CORE

1.01.01.01.01.01.01.01.01.01.01.21.21.41.41.61.6

25

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

FOUR CORE

mm mm

InnerSheath

4 x 1.54 x 2.54 x 44 x 64 x 104 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

0.70.70.70.70.70.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.81.81.81.81.92.12.22.42.52.72.93.13.3

1.381.782.252.953.824.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2.783.183.654.355.226.237.82

shapedshapedshapedshapedshapedshapedshapedshapedshaped

5388

140213358568900

12591705246434174323530566548743

10969

388459560705935

15702160247033404430565072508700

105001320015950

...

...

...

...110174275385521754

104413201621202326723352

...

...

...

...685

11801540160021602720328042505000590071508350

100010001000100010001000500500500500500250250250250250

1.01.01.01.01.01.01.01.01.01.21.21.21.41.41.61.6

15161819222530313540444953596571

Ph.0.90.91.01.11.11.21.41.61.71.8

1.81.92.02.22.32.42.62.83.03.1

29303338424651566267

817108615042163298938584594584576389552

20502240305040805100625077509400

1175014150

249333460662914

11791404178623342919

1480149020102580303035704560535064507500

500500500500500250250250250250

FOUR CORE WITH REDUCED NEUTRAL

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.0.70.70.90.91.01.11.11.11.21.4

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.7.82shapedshaped

N.6.236.237.82

shapedshapedshapedshapedshapedshapedshaped

1.01.01.01.21.21.21.41.41.61.6

26

GALVANIZED STEEL WIRE ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available

Current carrying capacity (3)

mm2 Ω/Km Amp Amp Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C(1)

Underground CableCopper Alu Copper Alu

CopperCables in air

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.54610162535507095120150185240300400

...

...

...

...3.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

34465974

101128162195235290347397444500578655754

...

...

...

...79

100126152183226271310346390452512588

24.814.8

9.26.23.72.41.61.20.870.640.480.400.350.290.240.230.22

...

...

...

...6.13.92.51.91.41.00.750.600.500.420.330.300.28

2737506488

119157194235299362419481549645735859

...

...

...

...6993

122151183234282327375428503575670

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) a) Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w

- In air : Ambient temperature 30˚Cb) In three phase system decrease above listed current ratings by 10%

27

GALVANIZED STEEL WIRE ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

DIMENSIONAL CHARACTERISTICS

GALVANIZED STEEL STRIP ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

TWO CORE

2 x 162 x 252 x 35

1.01.21.2

1.81.81.8

4.836.027.15

6.838.429.55

232628

284450624

108014401760

87138191

88511301330

1000500500

mm mm

InnerSheath

1.01.01.0

3 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

1.01.21.21.41.41.61.61.82.02.22.4

1.81.81.82.02.12.22.32.52.62.83.0

4.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

6.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2427283135394249515763

426675945

12791848256232423978499065578226

1260173018902420319041605000615073509300

11600

130206289391565783990

1216152520042514

9651260123015301910238027503390389047505900

1000500500500500500250250250250250

THREE CORE

1.01.01.01.01.21.21.21.41.41.41.6

FOUR CORE

4 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

1.01.21.21.41.41.61.61.82.02.22.4

1.81.81.92.12.22.42.52.72.83.13.3

4.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

6.838.42

shapedshapedshapedshapedshapedshapedshapedshapedshaped

568900

12591705246434174323530566548743

10969

150020802370308040405350650078009700

1230015100

174275385521754

104413201621202326723352

11001460150019002330298035004120510062507500

1000500500500500500250250250250250

1.01.01.01.21.21.21.41.41.61.61.6

2630313539444852586571

28

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

FOUR CORE WITH REDUCED NEUTRAL

mm mm

InnerSheath

Ph.1.21.21.41.41.61.61.82.02.22.4

1.81.92.02.12.32.42.52.72.93.1

29303337424649546167

817108615042163298938584594584576389552

19602140276036304770590068508500

1090013300

249333460662914

11791404178623342919

1390139017202130270032203660444056006650

500500500500500250250250250250

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.1.01.01.21.21.41.41.41.61.61.8

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.8.42shapedshaped

N.6.836.838.42

shapedshapedshapedshapedshapedshapedshaped

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available.

1.01.01.01.21.21.41.41.41.61.6

29

GALVANIZED STEEL STRIP ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Current carrying capacity (3)

mm2 Ω/Km Amp Amp Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C(1)

Underground CableCopper Alu Copper Alu

CopperCables in air

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.54610162535507095120150185240300400

...

...

...

...3.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

3041536791

115146176212261313358400451522590680

...

...

...

...6790

114137165204244279312352407460530

23.314.2

9.06.13.72.31.51.10.90.60.50.40.40.30.30.20.2

...

...

...

...6.13.82.41.71.41.00.70.60.50.40.30.30.2

223040527196

127157190242293339390444522595695

...

...

...

...557599

125151192232269309353415472552

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) a) Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w

- In air : Ambient temperature 30˚Cb) In three phase system decrease above listed current ratings by 10%

GALVANIZED STEEL STRIP ARMOUREDPVC INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

30

31

DIMENSIONAL CHARACTERISTICS

GALVANIZED STEEL STRIP ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

TWO CORE

2 x 162 x 252 x 35

0.70.90.9

1.81.81.8

4.836.027.15

6.237.828.95

222527

284450624

98513401650

87138191

79010301220

1000500500

mm mm

InnerSheath

1.01.01.0

3 x 163 x 253 x 353 x 503 x 703 x 953 x 1203 x 1503 x 1853 x 2403 x 300

0.70.90.91.01.11.11.21.41.61.71.8

1.81.81.81.92.02.22.32.42.62.82.9

4.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

6.237.82

shapedshapedshapedshapedshapedshapedshapedshapedshaped

2326262933374047495559

426675945

12781848256232423978499065578325

1160160017702230297039004760585070508950

11000

130206289391565783990

1216152520042514

8651130115013401690212025103090359044005200

1000500500500500500250250250250250

THREE CORE

1.01.01.01.01.01.21.21.41.41.61.6

FOUR CORE

4 x 164 x 254 x 354 x 504 x 704 x 954 x 1204 x 1504 x 1854 x 2404 x 300

0.70.90.91.01.11.11.21.41.61.71.8

1.81.81.92.02.12.32.42.62.83.03.2

4.836.02

shapedshapedshapedshapedshapedshapedshapedshapedshaped

6.237.82

shapedshapedshapedshapedshapedshapedshapedshapedshaped

568900

12591705246434174323530566548743

10969

138019302220282038305000610074009150

1180014400

174275385521754

104413201621203326723352

9851310135016402120263031003720453057506800

1000500500500500500250250250250250

1.01.01.01.01.21.21.21.41.41.61.6

2428293237414550556268

GALVANIZED STEEL STRIP ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

Radial Thickness of Lengthon

drumCable

Nominal Diameters Approximative net weight

Conductor Insulation Overall Conductor Cable Conductor

mm2 mm mmmm mm Kg/Km Kg/Km Kg/Km Kg/Km m

Copper cable Aluminium cableOuterSheath

Nominalcross

section* Insulation

FOUR CORE WITH REDUCED NEUTRAL

mm mm

InnerSheath

Ph.0.90.91.01.11.11.21.41.61.71.8

1.81.81.92.12.22.32.52.62.83.0

27283135394347525864

817108615042163298938584594584576389552

18101990256034504470555065508100

1040012700

249333460662914

11791404178623342919

1240124015201950240028703360404051006050

500500500500500250250250250250

3 x Ph. +N.3 x 25+163 x 35 + 163 x 50 + 253 x 70 + 353 x 95 + 503 x 120+703 x 150+703 x 185+953x240+1203x300+150

N.0.70.70.90.91.01.11.11.11.21.4

Ph.6.02shapedshaped

N.4.834.836.02

shapedshapedshapedshapedshapedshapedshaped

Ph.7.82shapedshaped

N.6.236.237.82

shapedshapedshapedshapedshapedshapedshaped

1.01.01.01.21.21.21.41.41.61.6

32

* - Solid conductor for sizes up to and including 4 mm2.- Stranded sectoral conductor for sizes of 35 mm2 and above in three and four core cables.- Stranded circular conductor for remaining sizes.- Greater sections also available.

Current carrying capacity (3)

mm2 Ω/Km Amp Amp Amp

ELECTRICAL CHARACTERISTICS

Alu

Ω/Km

DC Resistance at 20˚C(1)

Underground CableCopper Alu Copper Alu

CopperCables in air

Nominalcross

section

Amp

Voltage Drop (2)

Cos ϕ = 0.8

Copper Alu

V/A x Km V/A x Km

1.52.54610162535507095120150185240300400

...

...

...

...3.081.911.200.8680.6410.4430.3200.2530.2060.1640.1250.1000.0778

12.17.414.613.081.831.150.7270.5240.3870.2680.1930.1530.1240.09910.07540.06010.0470

34465974

101128162195235290347397444500578655754

...

...

...

...79

100126152183226271310346390452512588

24.814.8

9.26.23.72.41.61.20.870.640.480.400.350.290.240.230.22

...

...

...

...6.13.92.51.91.41.00.750.600.500.420.330.300.28

2737506488

119157194235299362419481549645735859

...

...

...

...6993

122151183234282327375428503575670

(1) At different operating T(˚C) : R = R20˚C 1+ α (T˚C - 20)α : Temperature coefficient at 20˚C = 0.00393 for copper & 0.00403 for aluminium

(2) In three phase system decrease above listed voltage drop by 15%(3) a) Laying conditions : - Underground : Temperature of the soil 20˚C - Thermal resistivity 100˚C cm/w

- In air : Ambient temperature 30˚Cb) In three phase system decrease above listed current ratings by 10%

33

GALVANIZED STEEL STRIP ARMOUREDXLPE INSULATED, PVC SHEATHED

0.6 / 1 KV POWER CABLESConforming to IEC 60502-1

DIMENSIONAL CHARACTERISTICS

UNARMOURED, XLPE INSULATED, PVC SHEATHED0.6 / 1 KV CONTROLE CABLES

Conforming to IEC 60502-1

Radial Thickness of Lengthon

drum

Nominal Diameters Approximative net weight

Conductor Insulation Overall Copper Cable

mm mmmm mm Kg/Km Kg/Km m

OuterSheathInsulation

CONDUCTOR 1.5 mm2

mm

Number*

ofConductors

578

101214192430374048

1.81.81.81.81.81.81.81.81.81.81.81.8

1.381.381.381.381.381.381.381.381.381.381.381.38

2.782.782.782.782.782.782.782.782.782.782.782.78

0.70.70.70.70.70.70.70.70.70.70.70.7

121314161617192123242527

6692

105131157184249314393484524628

189216246293355375515635710845910

1070

1000100010001000100010001000100010001000500500

CONDUCTOR 2.5 mm2

578

101214192430374048

1.81.81.81.81.81.81.81.81.81.81.81.9

1.781.781.781.781.781.781.781.781.781.781.781.78

3.183.183.183.183.183.183.183.183.183.183.183.18

0.70.70.70.70.70.70.70.70.70.70.70.7

131415171819212425272830

1091531752182623054145236538068711045

251293336403462525675840

1020123013201570

1000100010001000100010001000100010001000500500

50

* Greater number of conductors also available.

51

DIMENSIONAL CHARACTERISTICS

ARMOURED, XLPE INSULATED, PVC SHEATHED0.6 / 1 KV CONTROLE CABLES

Conforming to IEC 60502-1

Radial Thickness of Lengthon

drum

Nominal Diameters Approximative net weight

Conductor Insulation Overall Copper Cable

mm mmmm mm Kg/Km Kg/Km m

OuterSheathInsulation

CONDUCTOR 1.5 mm2

mm mm

InnerSheath

Number*

ofConductors

578

101214192430374048

1.81.81.81.81.81.81.81.81.81.81.92.0

1.381.381.381.381.381.381.381.381.381.381.381.38

2.782.782.782.782.782.782.782.782.782.782.782.78

0.70.70.70.70.70.70.70.70.70.70.70.7

1.01.01.01.01.01.01.01.01.01.01.01.0

161718202023242728303134

6692

105131157184249314393484524628

433493530615685

1000116013701530174018402320

10001000100010001000100010001000500500500500

CONDUCTOR 2.5 mm2

578

101214192430374048

1.81.81.81.81.81.81.81.81.81.82.02.2

1.781.781.781.781.781.781.781.781.781.781.781.78

3.183.183.183.183.183.183.183.183.183.183.183.18

0.70.70.70.70.70.70.70.70.70.70.70.7

1.01.01.01.01.01.01.01.01.01.01.01.2

171819232425263031343538

109153175218262305414523653806871

1045

505580645

104011201210143017201950246025703040

1000100010001000100010001000500500500500500

* Greater number of conductors also available.

Phase and street lighting conductors :

Round stranded and compactedaluminium conforming to the applicablerequirements of IEC 60228.

Neutral / Messenger Conductor :

Round stranded and compactedaluminium alloy conforming to theapplicable requirements of IEC 60208.

Insulation :

Extruded black XLPE.

Design :

The cable consist of three phaseconductors and one or two optionalstreet lighting conductors strandedarround the messenger.

Core identification :

Either by longitunal ridges or bynumbering.

Marking :

Embossed on the phase insulation.

5.6 AERIAL BUNDLED CONDUCTORS (TORSADES)

5.6.1 - 3 PHASES + NEUTRAL / MESSENGER + STREET LIGHTING CONDUCTOR

1 23

MA

RK

ING

2

1

3

4

5

CHARACTERISTICS OF THE NEUTRAL / MESSENGER CONDUCTOR

Nominal cross sectional area

Diameter of the Conductor

Diameter over the insulation

Breaking load

Elasticity Modulus

Linear dilatation factor

( mm2 )

( mm )

( mm )

( daN )

( MPA )

min.

max.

min.

54.6

9.2

12.3

13.0

1660

62000

23 x 10-6

(7/3.15)70

10

13.1

13.6

2000

62000

23 x 10-6

(7/3.45)

1 Stranded Aluminium alloyconductor (Neutral / Messenger)

2 XLPE Insulation

3 Stranded Aluminium conductor(Phase or street lighting conductor)

5 Marking

4 XLPE Insulation

52

53

TECHNICAL CHARACTERISTICS

AERIAL BUNDLED CONDUCTORS (TORSADES03 PHASES + NEUTRAL / MESSENGER + STREET LIGHTING CONDUCTOR

Conforming to NFC 33 - 209

Conductors Insulation

mm2 mm

Nominalcross

section phase

mm mm

streetlighting

weight

Kg/Km

DC Resistance at20˚C

Current carryingcapacity

phase streetlighting phase street

lighting

Ω/Km Ω/Km Amp

phase

mm mm

Overall

Nominal Diameters

Amp

3 x 25+54.63 x 25+54.6+163 x 25+54.6+2x16

3 x 35+54.63 x 35+54.6+163 x 35+54.6+2x16

3 x 50+54.63 x 50+54.6+163 x 50+54.6+2x16

3 x 70+54.63 x 70+54.6+163 x 70+54.6+2x16

3 x 70 + 703 x 70 + 70+163 x 70 + 70+2x16

3 x 150 + 703 x 150+70+163 x 150+70+2x16

5.85.85.8

6.86.86.8

7.97.97.9

9.79.79.7

9.79.79.7

13.913.913.9

-4.64.6

-4.64.6

-4.64.6

-4.64.6

-4.64.6

-4.64.6

8.68.68.6

10.210.210.2

11.211.211.2

13.313.313.3

13.313.313.3

17.317.317.3

-7.17.1

-7.17.1

-7.17.1

-7.17.1

-7.17.1

-7.17.1

242526.5

24.625.527.5

2728.530

3032.233

323334

404142

531600670

644713781

773841990

994106311431

103411031172

168417531822

1.2001.2001.200

0.8680.8680.868

0.6410.6410.641

0.4430.4430.443

0.4430.4430.443

0.2060.2060.206

-1.9101.910

-1.9101.910

-1.9101.910

-1.9101.910

-1.9101.910

-1.9101.910

979797

118118118

141141141

180180180

213213213

335335335

-7474

-7474

-7474

-7474

-7474

-7474

streetlighting

5.6.2 - 2 and 4 ALUMINIUM CONDUCTORS + PILOT COPPER CONDUCTORCONFORMING TO NFC 33 - 209

1 Stranded Aluminium conductor

2 XLPE Insulation

3 Marking

Phase Conductor

Pilot Conductor

4

5 XLPE Insulation

Solid Copper Conductor

TECHNICAL CHARACTERISTICS

Nominal Diameters

Overall

mm

Conductormin.

InsulationNominal

CrossSection

2x162x254x164x252x16+2x1.54x16+2x1.52x25+2x1.54x25+2x1.5

mm2

max.Weight

DCResistance

at 20˚C

CurrentCarryingCapacity

VoltageDrop

Breaking load of eachConductor

min. max.min.

mm

7.08.77.08.77.07.08.68.6

4.76.04.76.04.64.55.85.8

mm

7.99.67.99.67.87.89.49.4

14.818.217.821.816.017.419.521.6

mm

140213280426191328270486

Kg/Km

1.911.201.911.201.911.911.201.20

Ω/Km

831087497837410897

Amp

3.982.543.282.183.983.283.542.18

V/A Km

190300190300190190300300

daN

290450290450290290450450

daN

1 2

MA

RK

ING

2

3

4

5

3

1

54

x S U x ∆u U

2 L Ix S

6.1 Formulae

U = RI

2Lx S

P(w) = U I

P(w) = U I cos ϕ

P (w)

UP(VA) P (W)

U cos ϕU

P(VA) P (W)

U 3 cos ϕU 3

W = RI2 t

P(w) = √3 U I cos ϕ

Ohms law

Joules law

Resistance of a line(feed and return)

DC Power

Single phase Power

Three phase Power

AC Single core current

DC Current

AC Three phase current

Efficiency P outputP input

Voltage drop

Three phasesystem

Voltage drop Size ∆u (v) mm2

If current known

2 L Ix ∆u

If power known2 L P(w) 2L P(w)x S U x ∆u U

If current known

1.73 L I cos ϕ 1.73 L I cos ϕx S x ∆u

If power known

L P(w) L P(w)

Nature of the current

Single phaseAC/DC systems

U

IRW

tL1x11S1P1Cosϕe∆u

=11

===1==1=11=1=1===

Rated Voltage in V(volts)(between phase in threephase system).

Current in A (Amperes).

Resistance in (ohms).

Energy in Ws (Wattsecond).

Time in s (second)

Length of cable in m(meter).

Conductivity (56 forcopper and 34 forAluminium).

Cross sectional area inmm2.

Power in W (Watt) orVA (Volt Ampere).

Power factor.

Efficiency.

Voltage drop sending toreceiving end of line inV(Volts).

R =

I =

I = =

I = =

e =

∆u =

∆u =

∆u =

∆u =

S =

S =

S =

S =

6 TECHNICAL INFORMATION

56

6.2 Conversion factors and units

The SI unit for power is the W1W = 0.102 Kgm / s = 1.359 x 10-3 HP = 3.412 BTU / h1 Kgm / s = 9.81 W = 0.0133 HP = 33.47 BTU / h1HP = 735.5 W = 75 Kgm / s = 2510 Btu /h1 BTu /h = 0.2931 W = 0.0298 Kgm / s = 0.393 x 10-3 HP

w = watt, Kgm / s = Kilogramme meter per second,HP = metric Horse power, BTU /h = British thermal unit per hour

The SI unit for force is the N1N = 0.10197 Kgf = 0.2248 Lbf1Kgf = 9.80665 N = 2.2046 Lbf1Lbf = 4.4482 N = 0.4536 Kgf

N = Newton, Kgf = Kilogram force, Lbf = pound force

The SI unit for length is the m1m = 102 cm = 103 mm = 10-3 Km1m = 39.37 in = 3.28 ft = 1.0936 Yd = 0.6214 x 10-3 miles1 in = 0.0254 m = 0.0833 ft = 0.0277 Yd = 0.0158 x 10-3 miles1 ft = 0.3048 m = 12 in = 0.333 Yd = 0.189 x 10-3 miles1 Yd = 0.9144 m = 36 in = 3 ft = 0.568 x 10-3 miles1 mile = 1609 m = 63360 in = 5280 ft = 1760 Yd

m = meters, in = inches, ft = feet, Yd = Yards

The SI unit for volume is the m3

1m3 = 10 dm3 = 106 cm3 = 109 mm3

1m3 = 1000 L = 35.315 ft3 = 219.97 I.gal = 264.17 U.S. gal1L = 0.001 m3 = 0.0353 ft3 = 0.21997 I.gal = 0.26417 U.S. gal1 ft3 = 28.317x10-3 m3 = 28.317 L = 6.2288 I.gal = 7.479 U.S. gal1 I.gal = 4.546 x 10-3 m3 = 4.546 L = 0.1605 ft3 = 1.2009 U.S. gal1 U.S. gal = 3.7854 x 10-3 m3 = 3.785 L = 0.1366 ft3 = 0.8327 I. gal

l = liters, ft = feet, I.gal = Imperial gallon, U.S.gal = United States gallon

Length :

Weight :

Volume :

Force :

Power :

The SI unit for weight is the Kg1 Kg = 103 g = 10-3 T (metric ton)1 Kg = 2.20462 lb = 35.27 oz1 oz = 28.349 x 10-3 Kg = 0.0625 lb

Kg = Kilogrammes, lb = pounds, oz = ounces

57

The SI unit for pressure is the Pa = 1 N/m2

1 N /m2 = 10-5 Kgf / cm2 = 10-5 bar1Kgf / cm2 = 105 N / m2 = 1 bar

Pa = Pascal, N/m2 = Newton per square meterKgf / cm2 = Kilogramme force per square centimeter

Pressure :

Work : The SI unit for work is the J1J = 1Ws (Wattsecond) = 1Nm (Newton meter)1J = 0.2778 x 10-6 Kwh = 0.239 x 10-3 Kcal1Kwh = 3.6 x 106 J = 859.8 Kcal1Kcal = 4186.8 J = 1.163 x 10-3 Kwh

J = Joules, Kwh = Kilowatt hour, Kcal = Kilocalories

Temperature : The SI unit for Temperature is the Kelvin (K)Temperature in o C = Temperature in o K - 273 = 5/9 (Temperature in o F - 32)

Temperature in o K = Temperature in o C + 273o C = degree celcius, o K = degree Kelvin, o F = degree Fahrenheit

58