2 transmission schemes 2010

Upload: apichartj

Post on 05-Apr-2018

232 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/2/2019 2 Transmission Schemes 2010

    1/29

    Transmission Schemes Part 12 Limited

    Introduction

    Some Terminology's in Power system Protection

    Protection system

    Complete arrangements of Protection equipments & protectionSystem based on a protection principal (IEC 60255-20)

    Protection Equipment

    A collection of protection devices (relays, fuses, etc.). Excludedare devices such as CTs, CBs, Contactors, etc.

    Protection Scheme

    Collection of protection equipment providing a defined functionand including all equipment required to make the scheme work(i.e. relays, CTs, CBs, batteries, etc.)

    LEGENDS-

    CT- Current transformer

    VT- Voltage transformer

    TE- Telecommunication equipment/Teleprotection

    DC- Direct current

    CB Circuit breaker

  • 8/2/2019 2 Transmission Schemes 2010

    2/29

    Transmission Schemes Part 13 Limited

    Introduction

    Topics covered

    Overview of different types of schemes

    Different principles & philosophies of Protection schemes

    Different elements of Protection Schemes

    Engineering practices used by different utilities

    Factors to consider for engineering

    Simple & reliable

    Ease of Maintenance

    Economical

    Integration of protection equipments and correctoperation of the Protection relays depend upon thescheme design

  • 8/2/2019 2 Transmission Schemes 2010

    3/29

    Transmission Schemes Part 14 Limited

    Different types of Protection

    Feeder ProtectionCurrent Differential

    Distance Protection

    Phase Comparison

    Directional Earth Fault

    Over Current & Earth Fault

    Circuit Breaker Failure

    Thermal Over Load Protection

    Voltage Protection

    Transformer Protection

    Biased Differential Transformer Protection

    Over Current & Earth FaultRestricted Earth Fault Protection

    Standby Earth Fault Protection

    Over Flux (V/F Protection)

    Transformer Mechanical Protection

    Circuit Breaker Failure

    Busbar Protection

    High Impedance Busbar Protection

    Low Impedance Busbar Protection

    Reactor Protection

    Differential Protection

    Over Current Protection

    Restricted Earth Fault Protection

    CB Fail Protection

    Voltage Protection

  • 8/2/2019 2 Transmission Schemes 2010

    4/29

    Transmission Schemes Part 15 Limited

    Current Transformer arrangements

    Feeder two Main & Back up protections

    Generally above 132 kV Levels

    Main Protection Relays with the same Principles or different (Distanceor Current differential)

    Backup Protection providing coverage for uncovered faults by the MainProtection and delayed trip for unclear remote faults

    Current transformer connections to Main 1 & Main 2 from independent

    cores

    Voltage transformer connections are to be supervised by fuse failuresupervision relays

    Built in functions for Main &Back up protection will have the risk that acommon relay element failure (e.g. the power supply) will resultin loss of both the protections

    Bus BAR arrangements can be

    Double Bus Bar

    Double Main &Transfer

    Double Main cum Transfer

    One & A Half Breaker Scheme

    Mesh Corner layout

  • 8/2/2019 2 Transmission Schemes 2010

    5/29

    Transmission Schemes Part 16 Limited

    Current Transformer arrangements

    Feeder single Main & Back up protections

    Generally up to 132 kV levels

    Bus BAR arrangements can be

    Single Main & Transfer

    Double Bus Bar

  • 8/2/2019 2 Transmission Schemes 2010

    6/29

    Transmission Schemes Part 17 Limited

    Current Transformer arrangements

    One & A Half Breaker System (4 CT Arrangements)

    The main protection will be connected by the currenttransformers on Main CB & Tie CB in parallel

    Separate Stub bus connection is not required LineIsolator interlocked over current will be used to protectthe Stub Bus area if the feeder is not on live

    Four sets of CTs are sufficient to cater for the complete

    protection

    Economical

  • 8/2/2019 2 Transmission Schemes 2010

    7/29Transmission Schemes Part 18 Limited

    Current Transformer arrangements

    One & A Half Breaker System (5 CT Arrangements)

    Ratio of CT can be selected to circuitrating

    No problem of matching parallelconnected CTs

    Separate Stub bus Protection is available

    For a Fault between the Tie CB & Bus 2side Tie CB Isolator bus 2 CB will havedelayed tripping

  • 8/2/2019 2 Transmission Schemes 2010

    8/29Transmission Schemes Part 19 Limited

    Current transformer arrangements

    One & A Half Breaker System (6 CT Arrangements)

    CTs will be there on both side of the Tie CB ,

    except the connection to the Stub Bus protection

    all other protection remains same as five CTarrangements

    Over lapping Stub bus protection CT on the BusTie CB

  • 8/2/2019 2 Transmission Schemes 2010

    9/29Transmission Schemes Part 110 Limited

    Current transformer arrangements

    Bus Coupler & Bus Section CT arrangements

  • 8/2/2019 2 Transmission Schemes 2010

    10/29Transmission Schemes Part 111 Limited

    Tripping Overview Example of two Main & transfer feeder schemes

    MTR Main Trip relay

  • 8/2/2019 2 Transmission Schemes 2010

    11/29Transmission Schemes Part 112 Limited

    Tripping Arrangements

    Protection Systems will be grouped in two different

    systems Group A & B Both systems will be connected with different DC supplies

    for redundancy & to enable protection system

    maintenance with the equipment live

    Group A & B will be electrically separated & physicallysegregated except relays associated with the CBs

    Direct Inter trip receive contacts are duplicated in both theGroups A & B

    Main 1 & Main 2 Protections give trip impulses to Single

    Phase trip units of respective CB Poles & All otherprotections give trip impulses to three phase trip units ofrespective Breakers

  • 8/2/2019 2 Transmission Schemes 2010

    12/29Transmission Schemes Part 113 Limited

    DC Supply Arrangements

    Each bay will have dual DC supplies for protection &

    control purposes with individual DC supervision systems DC Supply one is for Main 1 protection relays &

    respective trip circuits and control schemes,

    DC Supply two is for Main 2 & respective trip circuits,Backup, Bay control system and CB auxiliary supplies

    In addition to this one separate DC circuit may be providedfor alarm & signalling purposes

    Separate DC circuit will be provided for Busbar protectionscheme

    Dual DC supply arrangements can be feed from the sameBus or different bus

    Different Battery arrangements

    Single Battery with Single Float ,Float & Boost charger

    Double Battery with Two independent chargers

  • 8/2/2019 2 Transmission Schemes 2010

    13/29Transmission Schemes Part 114 Limited

    Supervision

    Continuous Supervision of the protection devices /

    important elements required

    Trip Circuit

    Master Trip Relay

    DC Supply & Main Protection Relay

    MTR MAIN TRIPRELAY

  • 8/2/2019 2 Transmission Schemes 2010

    14/29Transmission Schemes Part 115 Limited

    Supervision Trip Circuit Supervision

    1. Lamp Method

    2. TCS using Relay

    PR- Protective relay

    TC- CB Trip coil

    52 a & 52 b CB Auxiliary contacts

    A, B, C - Trip Circuit supervision relays

  • 8/2/2019 2 Transmission Schemes 2010

    15/29Transmission Schemes Part 116 Limited

    Supervision

    Trip Circuit Supervision

    3.Implementation using numerical relays

    The Connection of relay A should be made in such a way that it detects the discontinuity of Tripcircuit. It is desired to have the trip circuit supervision relay to be as a last equipment in the circuit)

    The Trip circuit healthy contact is wired on circuit breaker closing circuit to make sure the CB tripcircuit is health/available to trip

    The alarm supply should be independent of tripping supply so that the indication is obtained in theevent of a failure in the tripping supply

  • 8/2/2019 2 Transmission Schemes 2010

    16/29Transmission Schemes Part 117 Limited

    Supervision Master Trip Relay Supervision

    The Tripping relays are important components of thetrip systems

    DC Supply will be supervised by a No Volt relay for eachtrip relay

    DC Supply & Main Protection Relay Supervision Both the DC supplies will be supervised

    For Static & Numerical multifunction relays it is veryimportant to monitor the self supervision watch dogcontacts, to indicate any failures occurring in the relaysinternal circuits

    Normally closed watchdog contact are used for remotealarms

    MVAX11 or MVAX12 relays are generally used for triprelay supervision & DC supply supervision relays areconnected at end of wiring run

  • 8/2/2019 2 Transmission Schemes 2010

    17/29Transmission Schemes Part 118 Limited

    Inter tripping Types of Inter tripping

    Direct tripping

    Permissive tripping

    Blocking scheme

    Direct Inter tripping

    To ensure that protection at both the ends of faulted circuitsoperate to isolate the equipment

    Some instance of Direct Inter tripping

    CB Fail protection operations or faults between CB & CTs

    Operational Inter tripping for system stability conditions

    Over voltage Direct trips on EHV Networks

  • 8/2/2019 2 Transmission Schemes 2010

    18/29Transmission Schemes Part 119 Limited

    Inter tripping

  • 8/2/2019 2 Transmission Schemes 2010

    19/29Transmission Schemes Part 120 Limited

    Inter tripping Points to consider

    The system protection interface shall provide the DTT send initiationinputs from external trip contacts

    DTT signaling equipment should have switching and test facilities.

    Operation of the tripping outputs shall be conditioned by the lineDisconnector auxiliary switch on banked and teed circuits.

    The trip output contacts will have sufficient rating to activate thefollowing

    Master Trip relays

    CB Direct trip coils if required

    Alarm & CB fail initiation Circuits

    Alarm outputs from the equipments

    Signal Receive Signal Receive Trip relays operated

    Signaling channel Equipment / Communication channel Faulty

    Signal Send

  • 8/2/2019 2 Transmission Schemes 2010

    20/29Transmission Schemes Part 121 Limited

    Switches & LinksSwitches

    Used to perform various control/Protection operations in the scheme

    Broadly it can be classified in to standard & Special PurposeStandard switches examples

    Protection In/OUT or Test Normal switch

    Bus bar Protection In/Out

    Auto Re closure In/Out

    Intertrip In/Out

    CB Trip/Close

    AC or DC Supply Selector

    Special Purpose switches examples

    Trip transfer switch

    Bus VT Selector switches for Distance protection schemes

    Synchronizing selection functions

  • 8/2/2019 2 Transmission Schemes 2010

    21/29Transmission Schemes Part 122 Limited

    Switches & Links Links

    To isolate certain functions/circuits without removing

    any wiring & to carry out Maintenance activities

    Examples

    Alarm Isolation

    Trip relay Isolation

    CB Fail initiation blocking

    Test terminal Blocks

    To isolate the relays from the Primary Plant circuits(Current, Voltage, DC & Trip circuits)

    It facilitates the short circuiting of CT secondary circuitsto allow the secondary injection testing of the relays

  • 8/2/2019 2 Transmission Schemes 2010

    22/29Transmission Schemes Part 123 Limited

    ON Load By Pass arrangements CTs Out side the By Pass Zone

    Transfer buses are designed for on load bypassing of circuitbreakers

    CB Maintenance can be done without Load interruption

    The protection needs to be transferred to Transfer Bus Coupler &is done through Trip transfer switch

    The following also needs to be selected

    LBB of TBC is to be initiated.Auto Reclose initiation and lockout of TBC.

    The line voltage has to be taken to TBC for synchronising

  • 8/2/2019 2 Transmission Schemes 2010

    23/29

    Transmission Schemes Part 124 Limited

    ON Load By Pass arrangements CTs in the By Pass Zone

    Transfer buses are designed for on load bypassing of circuitbreakers for maintenance from the Main Bus to transfer Bus

    CB & CT Maintenance can be done without Load interruption

    Protection is not affected , so no trip transfer switch required

    Inter tripping needs to be re routed to TBC

  • 8/2/2019 2 Transmission Schemes 2010

    24/29

    Transmission Schemes Part 125 Limited

    Voltage selection scheme

    Required in double busbar Substations when Bus voltage transformers are used

    Achieved using set of Voltage selection relaysVTs are not to be paralleled due to the fact that the difference in secondary voltagecan cause circulating current between the VTs cause the winding to over heat.

    However for distance protection schemes momentary paralleling of VTs is essentialfor the protection stability

    The schemes can be built using self reset or using electrical reset relays

    In some cases the selection can be done manually through Selector Switches

  • 8/2/2019 2 Transmission Schemes 2010

    25/29

    Transmission Schemes Part 126 Limited

    Output Relays

    Variety of electrical outputs provided in relays fortripping, interlocking and remote indication purposes

    Majority of the applications employ self reset type contacts

    Hand reset types are required when it is necessary tomaintain a signal or lockout condition.

    Some of the protection relays having high speed trippingcontacts for direct tripping of Circuit breakers

    Relay contacts are not designed to break the Circuitbreaker trip coil currents

  • 8/2/2019 2 Transmission Schemes 2010

    26/29

    Transmission Schemes Part 127 Limited

    National Grid Protection philosophy in UK Standard Solutions

    The standard bay solution shall support the specified functionsappropriate to a Specific Plant type ( Feeder, transformer etc..)

    Standard bay solutions shall be engineered in a way thatminimises the number of design variants

    Each tier will have Plug & Socket arrangements with externalmounted in 19 rack system connected via pre-manufacturedcables to a marshalling wall box.

    All inter panel wirings done through cables, The purpose ofthis is to minimise the amount of site work & Easy replacementof faulty unit

    Each Main Protection tiers may have

    Separate DC supply MCB

    Test terminal blocks

    Alarm & Trip Isolation links

    Protection Test /Normal switch

    Main Protection Initiation Test facilities

    Auxiliary & Control Relays

  • 8/2/2019 2 Transmission Schemes 2010

    27/29

    Transmission Schemes Part 128 Limited

    National Grid Protection philosophy in UK

    STANDARD NICAPTIER

    Typical Protection Panel

    NICAP- Numerical IntegratedControl & Protection

    E i i d d

  • 8/2/2019 2 Transmission Schemes 2010

    28/29

    Transmission Schemes Part 129 Limited

    Engineering standards

    General guidelines followed in Protection cubicaldesigns

    Various standards followed by different utilities

    Type of terminal blocks

    Equipments symbols & Protection Device codes

    Standard wire numbering for panels

    Colour codes to represent the Mimic

    C l i

  • 8/2/2019 2 Transmission Schemes 2010

    29/29

    Conclusion

    Factors Driving the Engineering

    Utilities Standards

    System Requirements

    Functions Vs Cost

    User Preferences

    The acceptability of various engineering practices must beevaluated on a case-by-case basis