Number K86644/02 Issued July 9 th , 2015 Valid until July 10 th , 2016 Declaration of Conformity, based on parts of CEN/TR 15276-1, regarding DSPA Non-Pressurized Condensed Aerosol Generators and Components Kiwa Nederland B.V. Groningenweg 10 Postbus 256 2800 AG Gouda Tel. +31-182-820460 Fax +31-182-820465 Internet www.kiwafss.nl Company DSPA B.V. Hulzenseweg 10-20 6534 AN NIJMEGEN P.O. Box 6572 6503 GB NIJMEGEN The Netherlands Tel. +31 24 352 25 73 Fax +31 24 37 87 583 www.dspa.nl This declaration consists of 12 pages. Publication of this declaration is allowed. Note: Publication of only this front page or parts of the declaration is considered as “not valid”. STATEMENT BY KIWA With this declaration, Kiwa declares that legitimate confidence exists that the products supplied by DSPA B.V. comply with the technical specifications as laid down in this product declaration and marked with the Kiwa ® -mark in the manner as indicated in this product declaration. Bouke Meekma Kiwa

Upload: vuthu

Post on 05-Jun-2018

217 views

Category:

Documents


0 download

TRANSCRIPT

Number K86644/02

Issued July 9th, 2015

Valid until July 10th, 2016

Declaration of Conformity, based on parts of CEN/TR 15276-1, regarding

DSPA

Non-Pressurized Condensed Aerosol Generators and

Components

Kiwa Nederland B.V.

Groningenweg 10

Postbus 256

2800 AG Gouda

Tel. +31-182-820460

Fax +31-182-820465

Internet www.kiwafss.nl

Company

DSPA B.V.

Hulzenseweg 10-20

6534 AN NIJMEGEN

P.O. Box 6572

6503 GB NIJMEGEN

The Netherlands

Tel. +31 24 352 25 73

Fax +31 24 37 87 583

www.dspa.nl

This declaration consists of 12 pages.

Publication of this declaration is allowed.

Note: Publication of only this front page or parts of the declaration is considered as “not valid”.

STATEMENT BY KIWA

With this declaration, Kiwa declares that legitimate confidence exists that the

products supplied by

DSPA B.V.

comply with the technical specifications as laid down in this product

declaration and marked with the Kiwa®-mark in the manner as indicated in this

product declaration.

Bouke Meekma

Kiwa

Kiwa®

product declaration K86644/02 Page 2 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

Declaration

This product declaration is based on test protocol PRO10-001-AFG-nk rev 06 and parts of CEN/TR 15276-1.

Generator specifications

The products mentioned below belong to this product declaration.

DSPA 11-1, DSPA 11-2, DSPA 11-3, DSPA 11-4, DSPA 11-5, DSPA 11-6, DSPA 11-7 and DSPA 8-1.

Type Housing Red coated steel

Activation

DSPA 11-1 Disk, radial, double shaped plate Electrical

DSPA 11-2 Disk, radial, double shaped plate Electrical

DSPA 11-3 Disk, radial, double shaped plate Electrical

DSPA 11-4 Disk, radial, double shaped plate Electrical

DSPA 11-5 Disk, radial, double shaped plate Electrical

DSPA 11-6 Disk, radial, double shaped plate Electrical

DSPA 11-7 Disk, axial, double shaped plate Electrical

DSPA 8-1 Cylindrical, axial Electrical

Non-pressurized generator.

Application and use

Condensed aerosol extinguishing systems for total flooding applications in normally unoccupied and unoccupiable areas, primarily related

to buildings, plant and other specific applications, utilising electrically non-conducting aerosol fire extinguishants.

The following are typical of such hazards, but the list is not exhaustive:

a) Electrical and electronic hazards;

b) Telecommunications facilities;

c) Flammable and combustible liquids and gases;

Where aerosol generators are used in a potentially explosive application, the suitability of the generator to the atmosphere for the

determined life shall be assessed.

The fire extinguishing components shall be suitable for extinguishing fires of the following classes:

• Class A according EN2

• Class B according EN2

Conditions for application

• The numbers and types of the extinguishing components have to be determined in conformity with the guidelines and calculation

methods of the supplier.

• Distribution is to be done by supplier or companies authorised by the supplier.

• Before usage an instruction is to be given by a trainer or instructor for this product authorized by the supplier.

• The installation and maintenance of the fire extinguishing components have to take place according to the specifications of the

supplier, CEN/TR 15276-2 or evaluation guideline BRL-K23003

Point of interest during use or limitation of use

The condensed aerosol extinguishing components should not be used on fires involving the following unless relevant testing by accredited testing laboratories has been carried out to the satisfaction of the Authority:

• Chemicals containing their own supply of oxygen, such as cellulose nitrate;

• Mixtures containing oxidizing materials, such as sodium chlorate or sodium nitrate;

• Chemicals capable of undergoing auto thermal decomposition, such as some organic peroxides;

• Reactive metals (such as sodium, potassium, magnesium, titanium and zirconium), reactive hydrides, or metal amides, some of

which may react violently with the extinguishants;

• Oxidizing agents such as nitric oxides and fluorine;

• Pyrophoric materials such as white phosphorous or metallo-organic compounds.

The above list may not be exhaustive.

Kiwa®

product declaration K86644/02 Page 3 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

• The design, installation, service and maintenance of aerosol generators should be performed by those competent persons in fire

extinguishing system technology.

• The hazards, against which these aerosol generators offer protection, and any limitations on their use, should be included in the

system supplier’s design manual.

• Effects of agent particulate residue on sensitive equipment and other objects should be considered when using condensed aerosol

extinguishing agents in spaces containing that type of equipment.

• Under certain conditions the potential for explosive atmospheres may exist. Areas where such potential may exist are classified as

hazardous. Condensed aerosols may be used in hazardous areas subject to the supplier obtaining the specific listings and

approvals for such areas from the appropriate authorities.

• Where aerosol generators are used in potentially explosive atmosphere, the compatibility of the generator to the atmosphere for the

determined lifetime should be assessed. The EU Directive 94/9/EC (ATEX Directive) should be taken into consideration.

• Local applications 1) of condensed aerosol extinguishing systems are not covered by this product declaration.

• Local applications require a pre-engineered and pre-designed system which has been tested and approved for a specific application

by a authority such as Kiwa or by an accredited testing laboratory.

1)

a local application is used for the extinguishment of surface fires in flammable liquids, gasses, and shallow solids, where the

enclosure does not conform to the requirements for total flooding.

Manual

At delivery the product should be accompanied by an operation manual in the English language, known and authorized by Kiwa.

The supplier shall prepare and maintain documentation. The supplier shall prepare installation and user documentation. This

documentation shall compromise at least the following:

a) A general description of the components;

b) A technical specification including:

1. Information mentioned in drawings, parts list, description of function, operating instructions, the minimum distance from the

generator outlet to the first obstacle, the minimum and maximum mass of aerosol compound discharged from the generator and

actuation inside an explosive atmosphere;

2. Sufficient information to permit an assessment of the compatibility with other components of the system (if applicable e.g.

mechanical, electric or software compatibility);

c) Installation instructions including mounting instructions;

d) Operating instructions;

e) Maintenance instructions.

Marking

The products should be marked with the Kiwa®-mark.

Place of the mark Required specifications Method of marking

• On the generator

• Name of the product and supplier

• Supplier’s type designation

• Production date and serial number

• Mass of aerosol-forming compound

• Temperature range

• Storage humidity range

• Service life

• Distances as specified in table 5

• Reference to the application

instructions

• Certification mark

• Fire Class A according EN2

• Fire Class B according EN2

• Non-erasable and non-detachable;

• Non-flammable;

• Permanent an legible

Kiwa®

product declaration K86644/02 Page 4 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

Recommendations for Customers

Check at the time of delivery whether:

• The supplier has delivered in accordance with the agreement;

• The mark and the marking method are correct;

• The products show no visible defects as a result of transport etc.

If you should reject a product on the basis of the above, please contact:

• DSPA B.V.

and, if necessary,

• Kiwa Nederland B.V.

Consult the suppliers processing guidelines for the proper storage and transport methods.

Kiwa®

product declaration K86644/02 Page 5 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components Cross reference CEN/TR 15276-1, Fixed fire fighting systems - Condensed aerosol extinguishing systems - Part 1: Requirements and test methods for components, February 2009

Chapter Description Demand 1) Result Remarks

1. Scope Implemented

2. Normative references Implemented

3 Terms and definitions Implemented

4 Component requirements

4.1 Condensed aerosol generator A See DSPA Manual

V7.3 2015

4.2 Solid aerosol-forming compound A See DSPA Manual

V7.3 2015

4.3 Cooling mechanism A See DSPA Manual

V7.3 2015

See table 5

4.4 Ignition device

4.4.1 General Implemented

4.4.2 Electrical ignition device Implemented

4.4.3 Thermal ignition device N/A

4.4.4 Other methods of ignition device N/A

4.5 End plate and housing Implemented

See DSPA Manual

V7.3 2015

4.6 Extinguishants Implemented

See DSPA Manual

V7.3 2015

5. Condensed aerosol generator requirements

5.1 General A Implemented

See 5.16 and 7.3

See table 2

See table 5

5.2 Extinguishing factor A Implemented

See 7.4

See table 1

5.3 Agent distribution A Implemented

See 7.5

See table 3

5.4 Discharge time A Implemented

See 7.6

See table 4

Kiwa®

product declaration K86644/02 Page 6 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

Chapter Description Demand 1) Result Remarks

5.5 Ambient temperature and humidity operation ranges A Temperature

limitations from -40

°C to +75°C and ambient humidity up

to 95 %.

See 7.7

5.6 Service life A See 7.8

5.7 Shelf life and storage conditions Not relevant in

relationship to

this product

declaration

See DSPA Manual

V7.3 2015

5.8 Corrosion A Implemented

See 7.9 and 7.10

5.9 Vibration A Implemented

See 7.11

5.10 Mechanical shock A Implemented

See 7.12 and 7.13

5.11 Discharge temperature

5.11.1 General Implemented

5.11.2 Casing temperature Not tested See 7.14

5.11.3 Aerosol flow temperature A Implemented

See DSPA Manual

V7.3 2015

See 7.14

See table 5

5.12 Ignition device

5.12.1 General Implemented

5.12.2 Electrical ignition device A Implemented

See 7.15

5.12.3 Thermal ignition device N/A

5.13 Function reliability A Implemented

See 7.16

5.14 Open fire conditions Not tested

5.15 Accessories A Implemented

See 7.9, 7.11, 7.12

and 7.13.

5.16 Documentation A Pass See DSPA Manual

V7.3 2015

Kiwa®

product declaration K86644/02 Page 7 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

Chapter Description Demand 1) Result Remarks

6 Marking A Pass See DSPA Manual

V7.3 2015

7. Test methods

7.1 Conditions A Implemented

7.2 Samples A Implemented

7.3 Conformity A Implemented

See DSPA Manual

V7.3 2015

7.4 Extinguishing factor determination A Implemented

See DSPA Manual

V7.3 2015

See specific test in

Annex A.

See table 1

7.5 Coverage determination A Implemented

See DSPA Manual

V7.3 2015

See specific test in

Annex A.

See table 3

7.6 Discharge time test A Implemented

See DSPA Manual

V7.3 2015

See 7.16.1

See table 4

7.7 Temperature and humidity operation range tests

7.7.1 Object of the test

7.7.2 Test procedure

7.7.3 Low temperature Test

A Pass Implemented

DSPA 11-3, DSPA

11-6, DSPA 11-7 and

DSPA 8-1 were

tested.

DSPA 11-1, DSPA

11-2, DSPA 11-4 and

DSPA 11-5 are

members of the

same generator

family as DSPA 11-3

and DSPA 11-6.

7.8 Accelerated ageing test

7.8.1 Test time

7.8.2 Test procedure

A Pass All types

116 test days at 90

ºC = 15 years based

on UL 2775

See DSPA Manual

V7.3 2015

7.9 Corrosion test A Pass Implemented

DSPA 11-3, DSPA

Kiwa®

product declaration K86644/02 Page 8 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

Chapter Description Demand 1) Result Remarks

11-6, DSPA 11-7 and

DSPA 8-1 were

tested.

DSPA 11-1, DSPA

11-2, DSPA 11-4 and

DSPA 11-5 are

members of the

same generator

family as DSPA 11-3

and DSPA 11-6.

7.10 Stress corrosion test A Pass Materials used in the

construction are not

susceptible to

ammonia stress

corrosion

7.11 Vibration test A Pass Implemented

DSPA 11-3, DSPA

11-6, DSPA 11-7 and

DSPA 8-1 were

tested.

DSPA 11-1, DSPA

11-2, DSPA 11-4 and

DSPA 11-5 are

members of the

same generator

family as DSPA 11-3

and DSPA 11-6.

Type 8.1 only at 0,5G

7.12 Impact test A Pass

7.13 Drop test A Pass Implemented

DSPA 11-3, DSPA

11-6, DSPA 11-7 and

DSPA 8-1 were

tested.

DSPA 11-1, DSPA

11-2, DSPA 11-4 and

DSPA 11-5 are

members of the

same generator

family as DSPA 11-3

and DSPA 11-6.

7.14 Casing and aerosol flow temperatures test

7.14.1 Casing temperatures test Not tested

7.14.2 Aerosol flow temperature test A Implemented

See DSPA Manual

V7.3 2015

See 7.16

See table 5

7.15 Ignition performance test A Pass 500 ignition devices

are tested

Kiwa®

product declaration K86644/02 Page 9 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

Chapter Description Demand 1) Result Remarks

7.16 Function test

7.16.1 Discharge time A Pass See table 4

7.16.2 Aerosol flow temperatures A Pass See table 5

7.16.3 Test procedure A Pass

7.16.4 Casing temperature test Not tested

7.16.5 Discharged mass A Pass See DSPA Manual

V7.3 2015

See table 2

7.16.6 Explosive atmosphere actuation test Not tested

7.16.7 Requirements Implemented

7.17 Heat exposure test Not tested

7.18 Explosive atmosphere test Not tested

Annex A (normative) Extinguishing factor/coverage test procedure

A1 General Implemented

A2 Principle Implemented

A3 Extinguishing system Implemented

A4 Extinguishing factor Implemented

A5 Aerosol generator distribution verification tests

A5.1 Minimum height/maximum coverage test A Pass See table 3

A5.2 Maximum height test A Pass See table 3

A6 Extinguishing factor tests

A6.1 Wood crib test A Not tested

A6.2 n-Heptane pan test A Pass See table 1

A6.3 Polymeric sheet fire test

A6.3.2.2 Polymethyl methacrylate (PMMA);

A6.3.2.2 Polypropylene,

A6.3.2.2 Acrylonitrile-butadiene-styrene polymer (ABS)

A Pass See table 1

A6.4 Composite wood fire test

A6.4.2.2 Reformed wood (chops) both sides plastic lined

A6.4.2.2 MDF (Medium Density Fibreboards) according to

EN 622 and EN 316 not lined

A6.4.2.2 Multilayers plywood ( kiln spruce or fir) not lined

A Pass See table 1

A7 Aerosol generator explosive atmosphere test

A7.1 Actuation test inside an explosive atmosphere

environment.

Not tested

1) A = Applicable N/A = Not Applicable Not tested

Kiwa®

product declaration K86644/02 Page 10 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

Tests not performed (with requirements):

• 5.11.2 Casing temperature

• 5.14 Open fire conditions

• 7.16.6 Explosive atmosphere actuation test

• 7.17 Heat exposure test

• A6.1 Wood crib test

Kiwa®

product declaration K86644/02 Page 11 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components

Product specifications

Table 1

Fire

Class

Listing According

CEN/TR 15276-1

Pre burn

time

Soak

period

Test room Density

EN2 Material / fuel in

seconds

in

seconds

in m3 in grams per m3

A Polymethylmethacrylate A.6.3 210 600 112.12 97

A Polypropylene A.6.3 210 600 112.12 58

A ABS A.6.3 210 600 112.12 87

A Reformed wood (chops) A.6.4 360 600 112.12 29

A MDF A.6.4 360 600 112.12 59

A Multilayers plywood A.6.4 360 600 112.12 87

B Heptane A.6.2 30 30 112.12 34

Table 2

Type Efficiency in %

DSPA 11-1 100

DSPA 11-2 88 - 100

DSPA 11-3 90 - 100

DSPA 11-4 100

DSPA 11-5 94 - 100

DSPA 11-6 100

DSPA 11-7 100

DSPA 8-1 100

Table 3

Type Housing

Type and

Discharge

method

Agent distribution according CEN/TR 15276-1 and ISO 15779

Minimum height /

Maximum area coverage (in m)

Maximum height /

Maximum area coverage (in m)

DSPA 11-1 Disk, radial 0.5 3.66 x 1.22 1.83 1.22 x 1.22

DSPA 11-2 Disk, radial 0.5 3.66 x 2.44 2.44 1.22 x 1.22

DSPA 11-3 Disk, radial 0.5 3.66 x 2.44 2.44 1.22 x 1.22

DSPA 11-4 Disk, radial 1.22 3.66 x 3.66 3.05 1.83 x 1.83

DSPA 11-5 Disk, radial 1.22 4.88 x 3.66 3.66 2.44 x 2.44

DSPA 11-6 Disk, radial 1.22 7.32 x 3.66 3.66 2.44 x 2.44

DSPA 11-7 Disk, axial 1.22 7.32 x 1.22 3.05 1.83 x 1.83

DSPA 8-1 Cylinder, axial 2.44 9.76 x 3.66 4.88 4.88 x 3.66

Kiwa®

product declaration K86644/02 Page 12 of 12

DSPA Non-Pressurized Condensed Aerosol Generators and Components Table 4

Type Discharge time

In Sec

DSPA 11-1 6 - 10

DSPA 11-2 9 - 15

DSPA 11-3 14 - 26

DSPA 11-4 19 - 31

DSPA 11-5 40 - 60

DSPA 11-6 30 - 50

DSPA 11-7 30 - 50

DSPA 8-1 67 - 89

Table 5

Type Distance in m

75°C 200°C 400°C

DSPA 11-1 0.5 0.15 0.05

DSPA 11-2 0.5 0.15 0.05

DSPA 11-3 0.5 0.15 0.05

DSPA 11-4 1.0 0.25 0.15

DSPA 11-5 1.0 0.25 0.15

DSPA 11-6 1.5 0.35 0.15

DSPA 11-7 1.5 0.50 0.10

DSPA 8-1 1.5 0.75 0.15