2016 Update to the California Building Standards Code Webinar Series
Webinar 3 — Structural Provisions
May 22, 2017
Welcome
Amber McEwenCalifornia Hospital Association
2
Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-AIA members are available upon request.
This course is registered with AIA CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner ofhandling, using, distributing or dealing in any material or product._______________________________________
Questions related to specific materials, methods, and services will be addressed at the conclusion of this presentation.
Overview and Introductions
Cheri HummelVice President, Emergency Management & FacilitiesCalifornia Hospital Association
3
5
Roy Lobo, PhD, is a registered licensed structural engineer with OSHPD and has more than 23 years of experience in the field. Dr. Lobo’s expertise is in non-linear analysis and he is the prime author of the IDARC-3D computer program. In addition to his analytical background in computer modeling and software development, Dr. Lobo has vast design experience in the evaluation and retrofitting of existing buildings.
Faculty
6
Joseph L. La Brie, SE, is a registered civil and structural engineer, and founder of MakeItRight, Inc., a progressive multidiscipline hospital design firm. Mr. La Brie founded thestate-of-the-art Dynamic Certification Laboratory, which has been used extensively for the certification of a broad range of equipment for critical occupancy buildings.
From 2005 to 2013, he served as a member of the Hospital Building Safety Board and was chair for four of those years. He currently serves as a consulting member to the board’s Education and Technology committees.
Faculty
4
Hospital Building Safety Board May 22, 2017
Structural Provisions
Joseph L. La Brie, SEHBSB Consulting Member
Roy Lobo, PhDPrincipal Structural Engineer, OSHPD
Outline
INTRODUCTION
DESIGN
SPECIAL INSPECTIONS, TESTS AND OBSERVATIONS
STRUCTURAL ELEMENTS
EXISTING BUILDINGS
QUESTIONS
8
5
§ 129680. Legislative intent(a) it is the intent of the Legislature that hospital
buildings that house patients who have less than the capacity of normally healthy persons to protect themselves, and must be reasonably capable of providing services to the public after a disaster, shall be designed and constructed to resist, insofar as practical, the forces generated by earthquakes, gravity and winds. In order to accomplish this purpose, the office shall propose proper building standards for earthquake resistance based upon current knowledge, and provide independent review of the design and construction of hospital buildings.
9
State Law Regarding Hospital Building Safety
10
Proposed Building Standards for Code AdoptionBUILDING STANDARDS RULEMAKING PROCESS
6
1. Do not conflict, overlap or duplicate other building standards
2. Remain within the parameters established by enabling legislation
3. Adoption required by public interest
4. Not unreasonable, arbitrary, unfair or capricious
5. Cost to the public is reasonable, based on overall benefit
6. Not unnecessarily ambiguous or vague
7. National standards and model codes are incorporated
8. Consistent format with that adopted by the Commission
9. If promoting fire and panic safety, approved by the State Fire Marshal
11
Nine-Point Criteria —Health and Safety Code (H&SC) §18930
Adopt national codes/standards unless amendments are required for (consistent with H&SC Sections 129680 & 17958.7.a):
1. Statutory requirements
2. Geological conditions
3. Climatological conditions
4. Topographical conditions
OSHPD Policy on Code Adoption
6
7
Amendments for the CBC 2016
Amendments for the CAC 2016 13
Adoption of International Building Code 2015 (IBC 2015) and Referenced Standards
Retain Chapter 34A for OSHPD 1 buildings
Adopt Chapter 4 of the International Existing Building Code (IEBC) for OSHPD 2 buildings
New Structural Performance Category SPC-4D for existing nonconforming buildings
14
Big-Picture Amendments in 2016 — StructuralOSHPD’S STRUCTURAL AMENDMENTS FOR THE CBSC 2016
8
15
2016 California Building Code (CBC 2016)
Structural Design
9
Demand/Forces for design in the CBC 2013 & CBC 2016 are mostly the same
American Society of Civil Engineers (ASCE) 7-10 is the basis for ground motions in both the CBC 2013 & CBC 2016
No changes in seismic hazard maps
17
Demand Forces
Design criteria requirement for wind tunnel test is deletedsince the CBC 2016 adopted ASCE 49-12 for wind tunnel tests (Section 1616A.1.1).
18
Design Criteria
10
For Rp greater than 1.5, overstrength factor (Ω0) shall be 2.0 (Instead of 2.5)
Vibration isolators along with associated snubbers/connections shall be designed for overstrength factor of 2.0
Overstrength factor (Ω0) for exterior nonstructural wall elements and connections shall be 1.0
19
Overstrength Factor for Nonstructural Components CONCRETE ANCHORAGE 1616A.1.23
National Fire Protection Association (NFPA) 13-16 demand and capacities will be accepted without recalculations because they are consistent with ASCE 7-10/ACI 318-14.
20
NFPA 13-16 for Sprinkler Pipe Supports, Attachments & Seismic Bracings
11
Transverse diagonal ceiling brace can be omitted for exit ways up to 8’ wide when: Perimeter support satisfy ASTM 580;
and Perimeter wall designed to carry lateral
loads
Brace spacing shall be justified by analysis or test, and shall not exceed 12’x12’
Ceiling support and bracing wires shall be spaced a minimum of 6” from pipes, ducts, conduits and equipment that are not braced for horizontal forces
21
Suspended Ceilings — 1616A.1.21
Linear procedure can be used for base-isolated buildings in Seismic Design Category (SDC) D (Section 1616A.1.36) as permitted by ASCE 7-10, §17.4.1.
22
Base-isolated buildings in non-red areas (SDC D) can use linear procedure
Base-Isolated Buildings in SDC D Can Be Designed by Linear Procedure
12
Buildings with welded steel moment frames constructed under a permit issued prior to Oct. 25, 1994, post-earthquake verification shall be performed in accordance with Section 1616A.1.39.
Joint evaluation report to be submitted within specified time frames; no building permits until joint evaluation work is completed.
Exception: Seismic compliance, maintenance and repair
23
Post-Earthquake Structural Verification 1616A.1.39
Special Inspections and Tests
13
1703A.1 Approved agency
1703A.1.1 Independence
1703A.1.2 Equipment
1703A.1.3 Personnel
1703A.2 Written approval
1703A.3 Record of approval
1703A.4 Performance
1703A.4.1 Research and investigation
1703A.4.2 Research reports
25
Special Inspections & Tests1703A APPROVALS
1703A.5 Labeling
1703A.5.1 Testing
1703A.5.2 Inspection and identification
1703A.5.3 Label information
1703A.5.4 Method of labeling
1703A.6 Evaluation and follow-up inspection services
1703A.6.1 Follow-up inspection
1703A.6.2 Test and inspection records
26
Special Inspections & Tests1703A APPROVALS (CONT.)
14
1704A.1 General
1704A.2 Special inspections and tests
1704A.2.1 Special inspector qualifications
1704A.2.2 Access for special inspection
1704A.2.3 Statement or special inspections
1704A.2.4 Report requirement
1704A.2.5 Special inspection of fabricated items
27
Special Inspections & Tests1704A
28
Special Inspections & Tests1704A (CONT.)
1704A.3 Statement of special inspections
1704A.3.1 Content of statement of special inspections
1704A.3.2 Seismic requirements in the statement of special inspections
1704A.3.3 Wind requirements in the statement of special inspections
1704A.4 Contractor responsibility
15
1704A.5 Submittals to the building official
1704A.6 Structural observations
29
Special Inspections & Tests1704A (CONT.)
1705A.1 Special cases (unusual)
1705.A.1.1 Construction materials
1705.A.1.2 Design application of materials
1705.A.1.3 Manufacturer requirements
1705A.2 Steel construction
1705A.2.1 Structural steel
1705A.2.2 Cold-formed steel deck
1705A.2.3 Open-web steel joists and joist girders
1705A.2.4 Cold-formed steel trusses >60 feet span
1705A.2.4.1 Light-framed steel truss inspection
30
Special Inspections & Tests1705A REQUIRED SPECIAL INSPECTIONS AND TESTS
16
1705A.2 Steel construction (cont.)
1705A.2.5 Inspection of structural welding
1705A.3 Concrete construction
1705A.3.1 Welding of reinforcing
1705A.3.2 Material tests
1705A.3.3 Batch plant inspection
1705A.3.4 Inspection of prestressed concrete
1705A.3.5 Concrete preplacement inspection
31
Special Inspections & Tests1705A REQUIRED SPECIAL INSPECTIONS AND TESTS (CONT.)
32
Special Inspections & Tests
1705A.4 Masonry construction
1705A.5 Wood construction
1705A.6 Soils
1705A.7 Driven deep foundations
1705A.8 Cast-in-place deep foundations
1705A.9 Helical pile foundations
1705A.10 Fabricated items
1705A.11 Special inspection for wind
1705A REQUIRED SPECIAL INSPECTIONS AND TESTS (CONT.)
17
1705A.12 Special inspection for seismic
1705A.12.1 Structural steel
1705A.12.2 Structural wood
1705A.12.3 Cold-formed steel light-frame construction
33
Special Inspections & Tests1705A REQUIRED SPECIAL INSPECTIONS AND TESTS (CONT.)
1705A.12 Special inspection for seismic (cont.)
1705A.12.4 Special inspection for special seismic certification
1705A.12.5 Architectural components
1705A.12.6 Plumbing, mechanical and electrical components
1705A.12.7 Storage racks
1705A.12.8 Seismic isolation and damping systems
34
Special Inspections & Tests1705A REQUIRED SPECIAL INSPECTIONS AND TESTS (CONT.)
18
1705A.13 Testing for seismic resistance
1705A.13.1 Structural steel
1705A.13.2 Nonstructural components
1705A.13.3 Special seismic certification
35
Special Inspections & Tests1705A REQUIRED SPECIAL INSPECTIONS AND TESTS (CONT.)
1705A.13 Testing for seismic resistance
1705A.13.3 Special seismic certification
36
Special Inspections & Tests1705A REQUIRED SPECIAL INSPECTIONS AND TESTS (CONT.)
19
1705A.13 Testing for seismic resistance
1705A.13.3 Special seismic certification
37
Special Inspections & Tests1705A REQUIRED SPECIAL INSPECTIONS AND TESTS (CONT.)
1705A.14 Sprayed fire-resistant materials
1705A.15 Mastic and intumescent fire-resistant coatings
1705A.16 Exterior insulation and finish systems (EIFS)
1705A.17 Fire-resistant penetrations and joints
1705A.18 Testing for smoke control
1705A.19 Shotcrete
38
Special Inspections & Tests1705A REQUIRED SPECIAL INSPECTIONS AND TESTS (CONT.)
20
1708A.1 General
1708A.3 In-situ load test
1708A.3.1 Load test procedure specified
1708A.3.2 Load test procedure not specified
39
Special Inspections & Tests1708A IN-SITU LOAD TESTS
1709A.1 General
1709A.5 Exterior window and door assemblies
1709A.6 Skylights and sloped glazing
40
Special Inspections & Tests1709A PRECONSTRUCTION LOAD TESTS
21
Soils and Foundations
Provisions for earth retaining shoring and vibro stone columns for ground improvement movedfrom Appendix J to Chapter 18A.
42
Shoring and Stone Column Requirements Moved to Chapter 18A
22
Appendix J was creating perception that entire site grading is in OSHPD jurisdiction
ONLY grading supporting OSHPD-regulated facilities are in OSHPD jurisdiction and NOT site grading
43
Appendix J is Not Adopted Anymore
Requirements of underpinning for protection of adjacent structures explicitly added (Sections 1804A.2 & 1808A.3.2)
Requires compliance with Chapter 33, Safeguard During Construction
No more underpinning design criteria/Alternate Method of Compliance (AMC)!
44
Underpinning
23
Provisions for steel sheet piles shoring are added (Sections 1810A.3.2.3, 1810A.3.5.3.2 & 1810A.3.5.3.3)
45
Steel Sheet Piles
Inspection, monitoring and observation requirements will be equivalent to those required for installation of shoring with soldier piles & lagging (Sections 1812A.6 and 1812A.7).
46
Testing provisions and acceptance criteria for
proprietary non-hammer driven piles are added to
Section 1810A.3.3.1.2.
Non-Hammer Driven Piles Testing
24
Concrete
Code is fully reorganized from an engineer’s perspective (NOT for contractor!)
Each building member (beam, column, slab, etc.) has its own chapter with complete design and detailing rules
Each member chapter includes provisions for cast-in-place and precast concrete, mildly reinforced and prestressed
48
American Concrete Institute (ACI) 318-14: Completely Reorganized
25
There are two new chapters:
Chapter 4: Structural System Requirements
Chapter 12: Diaphragms
49
ACI 318-14: Completely Reorganized (cont.)
50
ACI 318-14: Completely Reorganized (cont.)
26
Existing OSHPD amendments covered by ACI 318-14 are deleted.
Examples:
Specifications for tests and materials 26.4.2.1a (concrete mix design requirements)
Mechanical and welding splices of reinforcing bars (25.5.7)
Horizontal shear transfer requirements in composite concrete members (16.4.1)
51
Chapter 19A Amendments
Existing amendments that address subjects not covered by ACI 318-14 are retained.
Examples:
Post-installed anchor bolt testing
Field rebar testing
52
Chapter 19A Amendments (cont.)
27
CBC 1903A.8 (ACI 318 Sec. 26.6.4.1(b)) — Welding of Reinforcing Bars
Repealed amendment that required chemical analysis of reinforcing steel to be welded, since they duplicate requirements in American Welding Society (AWS) D1.4.
Revised amendment to permit shop fusion welding of reinforcing cages of low-alloy steel reinforcing stirrups/ties conforming to ASTM A706 and longitudinal holding wires conforming to ASTM A1064.
Tack welding of primary bars together or to stirrups/ties is not permitted.
Fusion welding of holding wires is not permitted where reinforcing bar is or will be bent (ACI 318 Section 25.3).
53
Welding of Reinforcing Bars
54
Column Ф-Factor Table Revised
28
55
Column Ф-Factor Table Revised (cont.)
56
TMS 402-13 — Reorganized changes are mostly in format rather than technical:
Chapter 1 is split into seven chapters
Chapter 5 (Empirical Design ofMasonry) moved to Appendix A
Amendments in Chapter 21A: Masonry
29
Exceptions added:
1. Core sampling and testing is not required for nonbearing non-shear masonry walls, not exceeding total wall height of 12 feet above wall base, built with single-wythe hollow unit concrete masonry that attaches opposite face shells using webs cast as single unit, when designed using an f' m not exceeding 2,000 psi (13.79 MPa).
57
Core Testing of MasonryCORE TESTING REQUIREMENTS SIMILAR TO 2013
Exceptions added:
2. An infrared thermographic survey or other nondestructive test procedures, shall be permitted to be approved as an alternative system to detect voids or delamination in grouted masonry in lieu of core sampling and testing.
58
Core Testing of MasonryCORE TESTING REQUIREMENTS SIMILAR TO 2013 (CONT.)
30
Steel
Few changes in steel design:
American Institute of Steel Construction (AISC) 360-10, AISC 341-10 & AISC 358-10 are the basis for capacity in both the CBC 2013 & CBC 2016
Side plate moment connections will be permitted in accordance with AISC 358-10, Supplement No. 2, with OSHPD amendments
Slenderness ratio limits added
Multi-tiered braced frame amendments added
ASTM 1085 HSS steel permitted
60
2016 CBC: Steel DesignAN OVERVIEW
31
Supplement No. 2 for AISC 358-10 adopted with new amendments for the side plate moment connection in Chapter 11.
61
Amendments in Chapter 22ASIDE PLATE MOMENT CONNECTION
Tension slenderness ratio (L/r) shall not exceed 300 (except for rod hangers & NFPA 13)
Compression slenderness ratio (KL/r) shall not exceed 200 (except for NFPA 13)
62
Amendments in Chapter 22ASTEEL SLENDERNESS RATIO LIMITS
32
63
NDS-15 & SDPWS-15 are updated
Technical changes are minor
Only one new OSHPD amendment:
Cross Laminated Timber (CLT) for seismic design will be considered to be alternative system.
Amendments in Chapter 23: Wood
Existing Structures
33
IBC 2015 removed Chapter 34, Existing Structures, from scope.
OSHPD kept CBC Chapter 34A for OSHPD 1 buildings.
65
2016 CBC: Existing StructuresAN OVERVIEW
IEBC 2015, Chapter 4, is adopted for OSHPD 2 & 4 buildings
Requirements are similar to those in IBC 2012, Chapter 34
66
2016 CBC: Existing StructuresAN OVERVIEW (CONT.)
34
Incidental alterations (additions & repairs) are alterations that would not:
67
Incidental Alterations DEFINITION
Reduce the story lateral shear force-resisting capacity by more than 5 percent; or
Increase the story shear by more than 5 percent in any existing story; or
A combination thereof with equivalent effect (not exceeding 5 percent total)
Minor structural alterations (additions & repairs) are alterations that would not:
68
Reduce the story lateral shear force-resisting capacity by more than 10 percent; or
Increase the story shear by more than 10 percent in any existing story (base shear by 10%); or
A combination thereof with equivalent effect (not exceeding 10 percent total)
Minor Alterations DEFINITION
35
1. New building provisions in Sections 3403A (additions), 3404A (alterations) and 3405A (repairs); or
These are based on IEBC 2015, Chapter 4 (similar to IBC 2012, Chapter 34)
2. Nonconforming building provisions in Section 3411; or
3. Performance-based (ASCE 41-13) provisions in Section 3412A.
CANNOT mix and match items #1 through #3
69
Addition, Alteration & Repair Options
1. Major structural alterations shall satisfy the new building code provisions.
Analysis shall use demand based on Chapter 16A;
Capacity shall be based on material chapters of the CBC 2016; and
Drift shall be based on Chapter 16A
70
New Building Code ProvisionsMAJOR STRUCTURAL ALTERATIONS
36
Analysis shall use demand based on Chapter 16A
Triggers for structural element upgrade, which is based on demand/capacity (D/C) ratio, is unchanged:
• 5% increase in D/C ratio for gravity loads
• 10% increase in D/C ratio for lateral forces
Drift can be based on original design code
71
New Building Code ProvisionsINCIDENTAL OR MINOR STRUCTURAL ALTERATIONS
2. Incidental or minor provisions for nonconforming buildings:
Section 3411A (permits use of new building code provisions with Ie = Ip = 1.0, instead of 1.5)
Exception: Nonstructural components for life-safety after an earthquake shall have Ip = 1.5
H&SC Section 129875 mandates flexibility and simplified approval procedures
72
Nonconforming Building Provisions
37
3. ASCE 41-13-based provisions: Section 3412A through Section 3419A.
Include provisions mandated by HSSA 83 and SB 1953
Performance-based provisions based on IEBC, Chapter 4
73
Performance-Based Provisions (ASCE 41-13)
New structural elements are designed, detailed and connected to the existing structural elements as required by Chapter 16A. Alterations of existing structural elements shall be based on design demand required by Chapter 16A. Demands for new or altered existing structural elements need not exceed the maximum load effect that can be transferred to the elements by the system.
74
Voluntary Seismic Improvements
38
For additions, alterations and repairs
For buildings and structures in flood hazard areas established in Section 1612A.3, any additions, alterations or repairs that do not constitute substantial improvement of the existing structure, as defined in Section 202, are not required to comply with the flood design requirements for new construction.
75
Acampo Flooding Feb. 11, 2017SOURCE: Jami Spagnola
Flood Hazard Areas
1.0 Scope
1.1 Application
1.2 DefinitionsCONFORMING BUILDING
DAMAGE CONTROL STRUCTURAL PERFORMANCE CATEGORY
STRUCTURAL PERFORMANCE CATEGORY SPC-4D
76
Structural Performance Category SPC-4DARTICLE 1 DEFINITIONS AND REQUIREMENTS
39
1.4 Compliance plans
1.4.5.1 Change in seismic performance category
77
Structural Performance Category SPC-4DARTICLE 1 DEFINITIONS AND REQUIREMENTS (CONT.)
1.4 Compliance plans
1.4.5.1.3 Reclassify to SPC-4D
78
Structural Performance Category SPC-4DARTICLE 1 DEFINITIONS AND REQUIREMENTS (CONT.)
40
3401A.1 Additions, alterations and repairs
3401A.4 Building materials, equipment and systems
3401A.4.1 Existing materials and equipment
3401A.4.2 New and replacement materials and equipment
79
Structural Performance Category SPC-4DSECTION 3401A
80
Structural Performance Category SPC-4DSECTION 3402A
1. Where the lateral seismic forces are resisted by under-reinforced masonry walls (reinforcing not meeting TMS 402 Section 7.3.2.6), the determination of whether the retrofit meets objective of SPC-4D shall be made on a case-by-case basis via an Alternate Method of Compliance.
2. Walls that are retrofitted to be equivalent to walls having minimum reinforcement per TMS 402 shall resist a substantial majority of the lateral seismic forces.
41
3412A.1 Adoption of ASCE 41
3412A.2 Seismic evaluation and retrofit of general acute care hospitals for compliance with the California Administrative Code, Chapter 6
81
Structural Performance Category SPC-4DSECTION 3412A
82
Structural Performance Category SPC-4DSECTION 3412A (CONT.)
3412A.2.3 SPC-4D (cont.)
3412A.2.3.1 Prescriptive compliance provisions for SPC-4D using the California Building Code, 1980 (CBC 1980)
42
Structural Performance Category SPC-4DSECTION 3412A (CONT.)
3412A.2.3 SPC-4D (cont.)
3412A.2.3.1 Prescriptive compliance with CBC 1980
Structural Performance Category SPC-4DSECTION 3412A (CONT.)
3412A.2.3 SPC-4D (cont.)
3412A.2.3.1 Prescriptive compliance with CBC 1980
84
43
3412A.2.3 SPC-4D (cont.)
3412A.2.3.2 SPC-4D using ASCE 41.
85
Structural Performance Category SPC-4DSECTION 3412A (CONT.)
3412A.2.3 SPC-4D (cont.)
3412A.2.3.3 Prescriptive compliance provisions for SPC-4D using the new building design requirements of this code
86
Structural Performance Category SPC-4DSECTION 3412A (CONT.)
44
Thank You
Roy Lobo, PhDStructural Engineer, [email protected]
Joseph L. La Brie, SECivil and Structural Engineer, MakeItRight, Inc. Former HBSB [email protected]
87
Questions