YATES TANK INSPECTION SERVICES P.O. Box 505
PRINCETON, KY. 42445
(270) 625-4898 CELL
2016 UNDERWATER INSPECTION REPORT
THE 300,000 GALLON FIRE PROTECTION TANK
LOCATED AT HURRICANE, UT. DC #6029
WAS INSPECTED FOR
WAL-MART, INC.
ON SATURDAY APRIL 30, 2016
2
YATES TANK INSPECTION
P.O. Box 505 Princeton, KY. 42445 PH. (270)625-4898 FX. (270)365-2123
INTRODUCTION:
WE ARE AN EVALUATION FIRM THAT SPECIALIZES IN PROFESSIONAL
UNDERWATER TANK INSPECTIONS.
WE USED A REMOTE OPERATED VEHICLE (ROV) TO COMPLETE THE
INSPECTION IN A CLEAN AND SANITARY MANNER WITHOUT INTERRUPTING
THE SYSTEM.
WE HAVE PROVIDED A COMPLETE AND DETAILED REPORT OF THE
FOLLOWING SANITARY CONDITIONS, STRUCTURAL INTEGRITY,
FOUNDATION, COATING AND SURFACE CONDITIONS, SAFETY AND SECURITY
REQUIREMENTS ACCORDING TO THE FOLLOWING AGENCIES.
(AWWA) AMERICAN WATER WORKS ASSOCIATION
(ANSI) AMERICAN NATIONAL STANDARDS INSTITUTE
(OSHA) OCCUPATIONAL SAFETY AND HEALTH ADMINISTRATION
(EPA) ENVIRO PROTECTION AGENCIES
(NSF) NATIONAL SANITATION FOUNDATION
(NFPA) NATIONAL FIRE PROTECTION ASSOCIATION
(NACE) NATIONAL ASSOCIATION OF CORROSION ENGINEERS
(SSPC) STEEL STRUCTURES PAINTING COUNCIL
FACTORY MUTUAL
STATE AND FEDERAL STANDARDS
THE REPORT REPRESENTS THE OPINIONS OF YATES TANK INSPECTION.
BECAUSE WE REMAIN INDEPENDENT OF PAINTING AND FABRICATION YOU
CAN BE ASSURED OF AN UNBIASED INSPECTION. WHILE EVERY PRECAUTION
WAS TAKEN TO INSURE THAT ALL INFORMATION GATHERED AND
PRESENTED IS ACCURATE, COMPLETE AND TECHNICALLY CORRECT, IT IS
BASED ON THE INFORMATION, DATA, TIME, MATERIAL, ETC. SUPPLIED TO US
DURING THE INSPECTION.
3
YATES TANK INSPECTION
TECHNICAL SPECIFICATIONS:
DATE OF INSPECTION: 04-30-2016
LAST INSPECTION: 04-02-2011
INSPECTOR’S NAME: DARRIN YATES
FIRM: WAL*MART STORES, INC.
OWNER’S REPRESENTATIVE:
LARRY REDDING
TITLE: FIELD SUPPORT MANAGER
MAILING ADDRESS: 3900 INTERSTATE 35 N.
NEW BRAUNFELS, TX.
TELEPHONE: (830) 620-3385
FAX: (830) 620-3392
PHYSICAL ADDRESS OF TANK: 150 N. HIGHWAY 91 HURRICANE, UT.
MAINTENANCE MGR: PAUL PARMENTER
PURCHASE #: 6029988047
SEISMIC ZONE TANK IS IN: ZONE 1
IS TANK BELOW THE NORMAL DAILY MINIMUM 30 DEGREE ISOTHERMAL
LINE: NO
WERE ALL INLET PIPES AND SUCTION LINES PROTECTED FROM FREEZING
TEMPERATURES? YES
IS THE TANK INSULATED OR INSIDE A HEATED BUILDING TO PROTECT IT
FROM FREEZING? YES
4
TANK SPECIFICATIONS:
TYPE OF TANK:
X GROUND __STANDPIPE __MULTI-LEGGED __SINGLE PEDESTAL SPHERE
__SINGLE PEDESTAL COMPOSITE __ PRE-STRESSED CONCRETE GROUND
SHELL RINGS HIGH: 4
TYPE OF MATERIAL:
X STEEL __CONCRETE __GLASS COATING __STAINLESS __OTHER
X WELDED __BOLTED __RIVETED
TANK MEASUREMENTS:
TANK MEASURES APPROXIMATELY 32’ IN HEIGHT ON SHELL AND 34’ OVERALL
HEIGHT OF THE AREA ABOVE OVERFLOW TO VENT IS 3’-0”
TANK CAPACITY IS 300,000 GALLONS DIAMETER: 40’-6”
TANK HIGH WATER LEVEL IS 30’-10 ¼” IN HEIGHT
TANK LOW WATER LEVEL IS 28’-0” IN HEIGHT
TANK IS USED FOR:
X FIRE PROTECTION __POTABLE __WASTE __PROCESSING __WAX __FLOUR
__GRAIN __PLASTIC __CHEMICAL __FUEL __GAS __OIL
ORIGINAL MANUFACTURER: PITTSBURGH TANK & TOWER COMPANY
YEAR BUILT: 1992
TYPE OF FOUNDATION:
X CONCRETE __CONCRETE SLAB BUILT WITHIN RING WALL ON STONE
__SUPPORTED ON GRAVEL BERMS ON GRAVEL WITH STEEL RINGS
__CONCRETE PIERS __CONCRETE CRADLES __STEEL CRADLES
TYPE OF ROOF:
__SELF SUPPORTED X SUPPORTED ROOF
DOME __ELLIPSOIDAL CONE X FLAT __KNUCKLE __CONE
IF ELEVATED WHAT TYPE OF COLUMNS: N/A
__ROUND PIPE __LATTICE I BEAM __VERTICAL __ANGLED
NUMBER OF COLUMNS: ____ __WELDED __RIVETS __BOLTED
5
SECURITY AND SAFETY:
DOES TANK SITE HAVE “NO TRESPASSING” SIGNS POSTED? YES
TANK IS LOCATED AT FRONT GATE OF DISTRIBUTION CENTER
DOES TANK SITE HAVE A FENCE COMPLETELY AROUND IT? YES
IF YES, DOES IT APPEAR TO BE IN GOOD CONDITION? YES
DOES EXTERIOR LADDER HAVE A GUARD TO PREVENT ENTRY? NO
WERE ALL GATES, GUARDS, AND HATCHES LOCKED AT THIS TIME? YES
WAS THERE EVIDENCE OF VANDALISM AT TANK SITE? NO
ELECTRICAL:
DOES TANK HAVE LIGHTNING PROTECTION? NO
DOES TANK SITE HAVE ELECTRICAL OUTLETS? YES
DOES TANK HAVE ANTENNAS, WIRING OR OTHER OBSTRUCTIONS IN THE PATH
OF THE LADDER? NO
IF IN CLOSE PROXIMITY TO AN AIRPORT, DOES TANK HAVE WARNING LIGHTS?
NOT IN CLOSE PROXIMITY.
6
CONDITION OF FOUNDATION: THE FOLLOWING ARE AWWA 12.6.1 AND 12.9 REQUIREMENTS
DOES AREA SURROUNDING FOUNDATION HAVE POSITIVE DRAINAGE? YES
DOES FOUNDATION HAVE ANY INDICATIONS OF SETTLING? NO
IS THERE INDICATION OF EROSION AROUND FOUNDATION DUE TO OVERFLOW
NOT HAVING AN APPROVED SPLASH-PAD? NO
DOES FOUNDATION EXTEND A MINIMUM OF SIX INCHES ABOVE EXISTING
GRADE AS REQUIRED BY AWWA? YES
DOES FOUNDATION APPEAR TO BE IN GOOD CONDITION? YES
7
FOUNDATION CONTINUED:
IS THERE EVIDENCE OF CHIPPING, CRACKING, OR DETERIORATION IN
FOUNDATION THAT NEEDS TO BE REPAIRED? NO IF YES EXPLAIN: N/A
IS THE VOID BETWEEN BASE OF TANK AND FOUNDATION SEALED? YES
WHAT TYPE OF MATERIAL WAS USED TO SEAL VOID? CAULK
EXPLAIN THE CONDITION OF SEAL: FAIR
DOES FOUNDATION HAVE ANCHOR BOLTS? NO
IS THERE ANY EVIDENCE OF METAL LOSS ON ANCHOR BOLTS? N/A
DOES TANK HAVE A WEED BARRIER AROUND THE FOUNDATION AREA TO
PREVENT STEEL DETERIORATION DUE TO MOISTURE FROM VEGETATION? YES
IS THERE ANY EVIDENCE OF LEAKS IN THE UNDERGROUND PIPING AROUND THE
FOUNDATION THAT MAY LEAD TO STRUCTURAL DAMAGE? NO
IS THERE ANY EVIDENCE OF LEAKS IN THE TANK THAT COULD POSSIBLY WASH
OUT THE SAND CUSHION THAT SUPPORTS THE CENTER OF FLOOR? NO
IF YES EXPLAIN: N/A
8
SHELL MAN-WAYS:
DOES TANK HAVE TWO SHELL MAN-WAYS, 180 DEGREES APART, TO MINIMIZE
ANY POSSIBILITY THAT A MAN-WAY BE BLOCKED DURING EMERGENCY
CONDITIONS? YES REQUIRED BY OSHA 1910.36, 1910.37, NFPA-22 SECTION 11.6.2 AND AWWA.
IS EACH MAN-WAY EQUIPPED WITH BOLTS THAT ARE NON-CORROSIVE OR
PAINTED TO PREVENT METAL LOSS? YES, (HAS 3 MAN-WAYS)
DO THE THREADS PROTRUDE THROUGH NUTS? YES
DO ALL BOLTS APPEAR TO BE TIGHT? YES
DOES THE FLANGE APPEAR TO BE STRAIGHT? YES
DOES EACH MAN-WAY HAVE A REINFORCING PLATE DESIGNED TO WITHSTAND
THE WEIGHT AND PRESSURE OF TANKS’ CONTENTS? YES
9
SHELL MAN-WAYS CONTINUED:
IS MAN-WAY DOOR COVER DESIGNED TO WITHSTAND THE WEIGHT AND
PRESSURE OF TANKS CONTENTS? YES
DOES EACH MAN-WAY COVER WEIGH OVER 50 LBS? YES
IS EACH COVER SUPPORTED WITH HINGES OR DAVIT ARM? YES
ARE MAN-WAYS CIRCULAR OR RECTANGLE DESIGN? CIRCULAR
IS THE MINIMUM DIAMETER 24 INCHES? YES
STATE THE DIAMETER: 24 X 24
DOES ANY MAN-WAY SHOW EVIDENCE OF PAST OR PRESENT LEAKS? NO
IS A “CONFINED SPACE” SIGN POSTED AT EACH ENTRY POINT? YES REQUIRED BY OSHA 1910.146 (C) (2)
10
EXTERIOR LADDERS: THE FOLLOWING ARE AWWA, NFPA & OSHA 29 CFR 1910 REQUIREMENTS.
DOES TANK HAVE A LADDER TO GAIN ACCESS BEGINNING AT 8 FEET (OR AS
SPECIFIED) FROM GROUND THAT EXTENDS TO THE ROOF TO BE ABLE TO
MAINTAIN TANK? YES
IS LADDER SECURED TO STRUCTURE EVERY 10 FEET? YES
DOES LADDER HAVE A FALL PREVENTION DEVICE THAT ATTACHES HARNESSES
ONTO THE LADDER? YES
WHAT TYPE OF FALL PREVENTION DEVICE DOES LADDER HAVE? SAFETY CAGE
DOES IT APPEAR TO BE IN GOOD CONDITION? YES
DOES TANK HAVE A STEEP ROOF? NO
11
OVERFLOW PIPE:
THE FOLLOWING ARE AWWA, NFPA, AND STATE DIVISION OF WATER REQUIREMENTS.
STATE DIAMETER OF OVERFLOW PIPE: 10”
IS OVERFLOW SECURED TO EXTERIOR EVERY 10 FEET? YES
IS PIPE SIZED TO CARRY MORE THAN THE LARGEST FILLING RATE? YES
IS THE TOP OF OVERFLOW DESIGNED TO PREVENT WHIRL POOLING? YES
IS THERE ANY EVIDENCE OF LEAKS IN THE OVERFLOW? NO
IF OVERFLOW IS LOCATED ON INTERIOR IS IT CONSTRUCTED OF NON-
CORROSIVE MATERIAL OR PAINTED TO PREVENT METAL LOSS? YES
IF NO, HAS SEVERE METAL LOSS OCCURRED? NO
IF EQUIPPED WITH FLANGES ON THE INTERIOR IS THE HARDWARE
CONSTRUCTED OF NON-CORROSIVE MATERIAL? N/A
ARE THE STAND OFF BRACKETS THAT SECURE OVERFLOW TO SHELL
CONSTRUCTED OF NON-CORROSIVE MATERIAL OR PAINTED? PAINTED
12
OVERFLOW PIPE CONTINUED:
DOES TANK HAVE AN OVERFLOW PIPE THAT DISCHARGES AT AN ELEVATION NO
HIGHER THAN 24 INCHES ABOVE THE GRADE? YES
IS OVERFLOW EQUIPPED WITH AN EPA APPROVED FLAPPER VALVE? NO
DOES THE FLAPPER MOVE FREELY TO PREVENT A BLOCKAGE? N/A
IS THE FLAPPER DESIGNED TO CLOSE WHEN NOT IN USE? N/A
IS OVERFLOW EQUIPPED WITH A NON-CORRODING MESH SCREEN? YES
WHAT IS THE CONDITION OF SCREEN? GOOD
DOES OVERFLOW HAVE A CONCRETE OR ROCK SPLASH-PAD? YES
IS THERE ANY EVIDENCE OF EROSION AROUND OVERFLOW? NO
13
WATER LEVEL GAUGE: THE FOLLOWING ARE NFPA 22, SECTION 11-1. 11 REQUIREMENTS
TANK HAS A WATER LEVEL GAUGE THAT READS IN FEET
DOES GAUGE APPEAR TO BE ACCURATE? YES
DOES GAUGE APPEAR TO BE IN GOOD CONDITION? YES
TANK HAS A 4” ALTITUDE CONTROL VALVE TO KEEP TANK FULL.
14
WATER LEVEL GAUGE CONTINUED:
WAS THE FLOAT BUILT WITH NON CORROSIVE MATERIAL TO PREVENT METAL
LOSS? YES
ARE THE CABLES ATTACHED TO THE FLOAT NON CORROSIVE? YES
ARE ALL HARDWARE AND CABLE CLAMPS USED ON INTERIOR MADE OF NON
CORROSIVE MATERIAL? YES
IF EQUIPPED WITH PULLEYS DO THEY MOVE FREELY TO ALLOW GAUGE TO
READ ACCURATELY? YES
15
HANDRAIL AND BALCONIES: THE FOLLOWING ARE OSHA 1926.501, 1910.23, AWWA AND NFPA 22 SECTION 10-7 REQUIREMENTS.
DOES ROOF HAVE HANDRAIL? YES
IS HANDRAIL EQUIPPED WITH A MID RAIL? YES
DOES IT HAVE A 4” TOE PLATE TO PREVENT OBJECTS FROM FALLING? YES
MATERIAL HANDRAIL IS CONSTRUCTED OF: STEEL
STATE THE OVERALL HEIGHT OF HANDRAIL: 42”
HOW IS HANDRAIL INSTALLED TO THE ROOF OF TANK? WELDED
DOES HANDRAIL APPEAR TO BE IN GOOD CONDITION? YES
IF NOT EXPLAIN? N/A
16
HANDRAIL CONTINUED:
IS HANDRAIL INSTALLED AT THE LADDER JUNCTION TO ALLOW SAFE PASSAGE
ONTO THE ROOF OF TANK? YES
IS THE HANDRAIL SECURED TO STRUCTURE EVERY 10 FEET AROUND
CIRCUMFERENCE? YES
IS THE ROOF REQUIRED TO HAVE AN OSHA APPROVED SAFETY CLIMB DEVICE
INSTALLED AT ITS HIGHEST POINT DUE TO THE DOME OF THE ROOF NOT
ALLOWING SAFE PASSAGE TO GAIN ACCESS TO BOTH MAN WAYS AND VENTS?
N/A
IS LADDER OPENING GUARDED BY A SAFETY CHAIN OR GATE? YES
IS SAFETY CHAIN OR GATE AN OSHA APPROVED DESIGN? CHAIN NEEDS TO BE
RAISED FROM MID RAIL TO TOP RAIL OF HANDRAIL.
WE RECOMMEND USING AN OSHA APPROVED GATE THAT CLOSES IN BEHIND
CLIMBER RATHER THAN A CHAIN DUE TO MOST CHAINS NOT GETTING
REATTACHED LEAVING PATHWAY OPEN.
17
EXTERIOR ROOF SURFACE:
IS ROOF COVERED WITH INSULATION? NO
IS A PROTECTIVE COVER INSTALLED OVER THE INSULATION? N/A
IS ROOF SLOPED TO WHERE THERE IS NO DRAINAGE PROBLEM? YES
DOES ROOF HAVE BULGES OR DENTS THAT MAY HAVE BEEN CAUSED BY VENT
OR OVERFLOW PIPE BEING BLOCKED DURING DAILY OPERATION? NO
IS ROOF SEALED TO PREVENT ENTRY OF DUST, INSECTS, ETC.? YES
DOES EXTERIOR ROOF SHOW SIGNS OF METAL LOSS? NO
IF ROOF IS WELDED ARE SEAMS IN GOOD CONDITION? YES
18
SANITARY CONDITIONS:
STORAGE RESERVOIRS, BOTH POTABLE AND FIRE PROTECTION, ARE DESIGNED TO BE WATER TIGHT TO
PREVENT LEAKAGE AND THE ENTRY OF DUST, SAND, INSECTS, BIRDS, BATS AND ANIMALS THAT MAY
CAUSE WATER BORN DISEASE OR CAN CAUSE BLOCKAGES IN FIRE PROTECTION SYSTEMS. REQUIRED BY
AWWA, NFPA, STATE DIVISION OF WATER AND DEPT. OF NATURAL RESOURCES.
ROOF VENT:
DOES TANK APPEAR TO HAVE ADEQUATE VENTILATION? YES
DOES VENT HAVE A SHIELD OVER ITS’ TOP AND SIDES TO PROTECT AGAINST
BIRD DROPPINGS, DUST, RAIN, ICE, ETC.? YES
IS VENT EQUIPPED WITH A #24 NON-CORRODING MESH SCREEN? YES
IS ROOF VENT WATER-TIGHT TO PREVENT CONTAMINATES SUCH AS BIRD
DROPPINGS AND DIRT FROM WASHING INTO THE FACILITY BY RAIN? YES
DOES TANK HAVE A SECONDARY CENTER ROOF OPENING USED AS A MAN-WAY
AND TO SECURE VENTILATION FANS DURING PAINTING PROJECTS? NO
19
ROOF VENT CONTINUED:
DUE TO GEOGRAPHIC LOCATION IS VENT REQUIRED TO BE SHIELDED TO
PREVENT FREEZING RAIN FROM STOPPING VENTILATION? YES
DUE TO GEOGRAPHIC LOCATION DOES IT APPEAR THAT THE VENT EXTENDS
ABOVE NORMAL SNOW LEVEL WHICH COULD BLOCK VENTILATION? YES
DOES IT APPEAR THAT THE ROOF IS SLOPED ENOUGH TO PREVENT MELTING
SNOW FROM ENTERING THROUGH THE VENT? YES
IF VENT IS ALSO USED AS A MAN-WAY WAS ANY HARDWARE MISSING? NO
DOES IT APPEAR THAT ALL HARDWARE IS TIGHT? YES
WERE THERE ANY VOIDS IN OR AROUND VENT SCREEN THAT MAY ALLOW
BIRDS TO ROOST? NO
IF VENT IS BOLTED TO THE ROOF WAS A GASKET USED BETWEEN THE FLANGES
TO COMPLETELY SEAL THE CONNECTION? NO
20
ROOF HATCHES AND MAN-WAYS:
THE FOLLOWING ARE AWWA, NFPA-22 SECTION 3-7 AND OSHA 1910.36 AND 37 REQUIREMENTS.
HOW MANY ROOF MAN-WAYS DOES TANK HAVE? ONE
ARE THE ROOF OPENING FRAMES CURBED 4 INCHES UPWARD AND DO THEY
HAVE 2 INCH OVERLAPPING COVERS TO PREVENT PRECIPITATION ON THE
ROOF’S SURFACE FROM DRAINING INTO THE FACILITY? YES
ARE ROOF OPENINGS A MINIMUM OF 24 INCHES IN DIAMETER? YES
DOES EACH ROOF OPENING HAVE A LOCK TO PREVENT ENTRY? NA
DOES EACH ROOF OPENING HAVE A “CONFINED SPACE” SIGN POSTED AT EACH
MAN-WAY AS REQUIRED BY OSHA 1910.146 (C) (2)? YES
21
ROOF MAN-WAYS CONTINUED:
IS VENT MAN-WAY EQUIPPED WITH BOLTS THAT ARE NON-CORROSIVE OR
PAINTED TO PREVENT METAL LOSS? YES
IS EACH MAN-WAY EQUIPPED WITH HINGES TO SUPPORT COVER? YES
DO ALL BOLTS APPEAR TO BE TIGHT? YES
DOES THE COVER APPEAR TO BE STRAIGHT? YES
ARE MAN-WAYS CIRCULAR OR RECTANGLE DESIGN? SQUARE
STATE THE DIAMETER OF MAN-WAY OPENING: 24” X 24”
IS THE ROOF HATCH EQUIPPED WITH A HANDLE? YES
22
INTERIOR LADDER: THE FOLLOWING ARE AWWA, NFPA & OSHA REQUIREMENTS
DOES TANK HAVE AN INTERIOR LADDER FOR PAINT CONTRACTORS TO
MAINTAIN INTERIOR COATING? YES
STATE ITS’ CONDITION: CAGE HAS SUFFERED METAL LOSS
HOW IS LADDER SECURED TO INTERIOR? WELDED
DOES LADDER HAVE A FALL PREVENTION DEVICE? YES
DOES IT APPEAR TO BE IN GOOD CONDITION? NO
WHAT TYPE OF FALL PREVENTION DEVICE IS ON LADDER? CAGE
IS FALL PREVENTION DEVICE STAINLESS STEEL? NO
23
INTERIOR COATING:
INTERIOR WAS LAST PAINTED IN: UNKNOWN
COLOR IS: WHITE
DRY FILM THICKNESS OF COATING IS: 8 TO 15 MILS
INTERIOR COATING CONDITIONS OF STRUCTURE:
ROOF: VERY LITTLE RUST IN LAP JOINTS AND SHARP EDGES
SHELL ABOVE WATER: POOR, COATING HAS FLAKED OFF
SHELL BELOW WATER: FAIR, RUSTING ALONG SHARP EDGES
FLOOR: FAIR, COVERED IN IN SEDIMENT
INTERIOR COATING HAS ANOTHER 1 TO 4 YEARS LIFE REMAINING
24
INTERIOR SURFACE:
IS THERE EVIDENCE OF METAL LOSS SUCH AS PITS OR RUST TUBERCLES BELOW
WATER? YES
TANK IS CONSTRUCTED OF: STEEL
IS TANK SEALED TO PREVENT ENTRY OF DUST, INSECTS, ETC.? YES
DOES INTERIOR SHELL SURFACE SHOW SIGNS OF DETERIORATION? YES
DOES ROOF HAVE ANY EVIDENCE OF METAL LOSS? NO
IS INTERIOR ROOF WELDED? NO
IS UNDERSIDE OF ROOF SEAM SEALED? NO
25
INTERIOR SURFACE CONTINUED:
DOES SHELL BELOW WATER HAVE SIGNS OF CORROSION? RUSTING ALONG
SHARP EDGES
DOES INTERIOR FLOOR HAVE SIGNS OF CORROSION? COVERED IN SEDIMENT
ARE THERE SIGNS THAT THE FLOOR MAY BE SAGGING? NO
IS THERE EVIDENCE THAT THE FLOOR MAY BE LEAKING? NO
WHAT IS THE CONDITION OF COATING ON VERTICAL WELD SEAMS? GOOD
DOES SHELL HAVE SIGNS OF LEAKS? NO
26
SURFACE PREPARATION AND COATING: ALL PAINT USED ON WATER TANKS MUST BE (ANSI/NSF) CERTIFIED FOR POTABLE WATER. ALL
SURFACES TO BE REFINISHED SHALL BE PREPARED IN ACCORDANCE WITH THE REQUIREMENTS
OF THE STEEL STRUCTURE PAINTING COUNCIL (SSPC). ALL PAINTS SHALL COMPLY WITH (ASTM)
SPECIFICATIONS AND BE DELIVERED IN SEALED CONTAINERS & LABELED BY MANUFACTURER.
EXTERIOR ROOF COATING:
ROOF WAS LAST PAINTED IN: UNKNOWN
COLOR IS: LIGHT GRAY
COATING APPEARS TO BE: FACTORY APPLIED
DRY FILM THICKNESS OF EXTERIOR COATING IS: 4 TO 6 MILS
EXPLAIN COATING CONDITIONS: FAIR, BUT COVERED IN DUST
27
EXTERIOR SHELL COATING:
SHELL WAS LAST PAINTED IN: UNKNOWN
COLOR IS: LIGHT GRAY
COATING APPEARS TO BE: FACTORY APPLIED
DRY FILM THICKNESS OF EXTERIOR COATING IS: 4 TO 12 MILS
STATE COATING CONDITIONS: GOOD
28
EXTERIOR SHELL SURFACE:
SHELL IS CONSTRUCTED OF: STEEL
IS SHELL SEALED TO PREVENT ENTRY OF DUST, INSECTS, ETC.? YES
DOES SHELL SHOW SIGNS OF LEAKS? NO
EXPLAIN: N/A
DOES SHELL SHOW EVIDENCE OF BULGES OR DENTS? NO
29
TANK HEATING: THE FOLLOWING MAY BE REQUIRED BY NFPA
DOES TANK HAVE A FM APPROVED THERMOMETER? NO
IS TANK INSULATED? INSIDE HEATED BUILDING
IF THE TANK HAS FOAM INSULATION IS INSULATION PROTECTED WITH A METAL
COVER TO PREVENT IT FROM BEING DAMAGED? N/A
DUE TO GEOGRAPHIC LOCATION IS TANK REQUIRED BY NFPA TO PROTECT
AGAINST BELOW FREEZING TEMPERATURES? YES
MISCELLANEOUS:
IS THERE SEDIMENT ON FLOOR OF TANK? YES
STATE APPROXIMATE AMOUNT OF SEDIMENT: 1 TO 2 INCHES
DO INLET AND OUTLET PIPES EXTEND ABOVE SEDIMENT? YES
DOES TANK HAVE BIRDS ROOSTING ON IT? NO
WERE ANY FOREIGN OBJECTS DETECTED WITHIN TANK? NO
STATE WATER LEVEL AT TIME OF INSPECTION: 27’-0”
ROAD LEADING TO TANK IS CONCRETE
DOES TANK HAVE A PUMP HOUSE? YES
IF YES, DOES IT APPEAR TO BE IN GOOD CONDITION? YES
DOES TANK HAVE A LOGO ON EXTERIOR? NO
DOES EXTERIOR SHELL HAVE EVIDENCE OF LEAKS? NO
DOES FLOOR HAVE EVIDENCE OF LEAKS? NO
DOES TANK HAVE ANY BOLTS, RIVETS OR PINS MISSING? NO
IF YES, STATE LOCATION: N/A
DOES TANK HAVE CATHODIC PROTECTION? NO
IF YES, IS CATHODIC PROTECTION IN GOOD CONDITION? N/A
DOES TANK HAVE GRAFFITI? NO
30
YATES TANK INSPECTION SERVICES
P.O. BOX 505 - PRINCETON, KY 42445 (270) 625-4898 PHONE (270) 365-2123 FAX
ELECTRIC AND DIESEL PUMP-HOUSE REPORT
YEAR PUMP HOUSE BUILT: 1992
WAS PUMP HOUSE DOOR LOCKED? YES
WAS LIGHTING IN PUMP HOUSE IN GOOD WORKING ORDER? YES
DO FLOOR DRAINS WORK PROPERLY? YES
IS THERE ANY EVIDENCE OF LEAKS IN THE ROOF OF PUMP ROOM? NO
DO PUMP HOUSE HEATERS WORK PROPERLY? YES
DO PUMP HOUSE VENTILATION LOUVERS WORK PROPERLY? YES
31
DOES IT APPEAR THAT PUMP, PIPING, AND VALVES NEED TO BE CLEANED AND
PAINTED TO PREVENT METAL LOSS? NO
IS THERE ANY VISIBLE EVIDENCE OF LEAKS IN THE PIPING? NO
DOES THE PIPING HAVE SUPPORT BRACKETS? YES
IF SUCTION AND INLET PIPES ARE ON THE EXTERIOR OF TANK OR PUMP HOUSE
ARE THEY INSULATED? YES
HOW MANY HEATERS ARE IN PUMP HOUSE? ONE
STATE HEATERS CONDITION: FAIR
DOES IT HAVE A THERMOSTAT? YES
WHAT IS THE SETTING? 70 DEGREES HEATER MANUFACTURER: TRAIN
HEATER TYPE: RADIATE MODEL: UHC-07288CA
VOLTS: 208 PHASE: 03 KW: 7.5
32
FILL VALVE AND TANK DRAIN:
WHAT TYPE OF CONTROL VALVE IS IN THE SYSTEM? ALTITUDE CONTROL
MANUFACTURER: CLA-VAL PIPE SIZE: 4” INSTALLED: 1992
MODEL #: 1- 210-01AB STOCK#: 210-01-172B CODE#: KX
SOLENOID MANUFACTURER: N/A S/N#: N/A CAT#: N/A
SOLENOID PIPE SIZE#: N/A SOLENOID REBUILD KIT#: N/A
IS THERE ANY EVIDENCE OF LEAKS IN THE PIPING? NO
DOES THE PIPING HAVE SUPPORT BRACKETS? YES
IS CONTROL VALVE EQUIPPED WITH SHUT OFF VALVES ON BOTH SIDES SO IT
CAN BE SERVICED WITHOUT DRAINING TANK? YES
IS STORAGE TANK EQUIPPED WITH A VALVE ON THE DRAIN PIPE? YES
STATE THE DIAMETER: 8” PIPE
CAN THE DRAIN PIPE BE USED TO TEST THE FILL VALVE? YES
WHERE IS THE DRAIN VALVE LOCATED? NEXT TO OVERFLOW
33
PRIMARY FIRE PUMP:
WHAT TYPE OF FIRE PUMP IS USED AS PRIMARY? ELECTRIC CENTRIFUGAL
PUMP MANUFACTURER: PENTAIR
MODEL #: 8-2824AF SPEED: 1,770
MFG SERIAL #: 15-2466666 NUMBER OF STAGES: 01
MAX SUCTION: 201.7 MAX BHP: 172.5
IMPELLER DIAMETER: 14.315
MAX NET PSI: 98.3
PRESSURE AT 150 PERCENT 56.5
IS THERE ANY EVIDENCE OF LEAKS IN THE CASING OF PUMP? NO
IS THE SHAFT TO MOTOR PROTECTED WITH A GUARD? YES
34
PRIMARY FIRE PUMP CONTINUED:
MOTOR BUILT BY: US MOTOR RATED: 150 HP RPM#: 1,775
FRAME #: 445TS S/N OR ID#: HO2W04WO48P139M CAT#: NOT ON TAG
MANUFACTURER OF CONTROLLER: METRON
SERIAL #: JE-9310494-01 CAT#: M300P-150-460-C
MAX PRESSURE#: 300 VOLTS: 480 PHASE: 03 HERTZ: 60
ENCLOSURE TYPE: 12 MADE IN: USA INSTALLED: 1995
WERE ALL MODE SELECTORS IN AUTO POSITION ON PANEL? YES
DOES IT APPEAR THAT POWER IS ON FOR FIRE PUMP CONTROLLER? YES
WHAT IS THE PRESSURE ON CONTROLLER GAUGE? 150 PSI
35
SECONDARY FIRE PUMP:
MANUFACTURER OF SECONDARY MOTOR IN THE SYSTEM: JOHN DEERE
YEAR BUILT: 2012 MADE IN: USA ENGINE TYPE: 6 CYLINDER
ENGINE SERIAL #: RG6081H170793 MODEL#: JW6H-UF60
TYPE.9.0 HOURS: 91.9 RPM: 2,100 BHP: 399 KW: NA
BATTERY METER: 24.0 VOLTS COLD CRANKING AMPS: 1,400 AMPS
MANUFACTURER OF DRIVE LINE BETWEEN PUMP AND ENGINE: CLARK
MANUFACTURER OF CONTROL PANEL: CLARK
WERE ALL MODE SELECTORS IN AUTO POSITION ON PANEL? YES
WERE ANY LEAKS VISIBLE IN OR AROUND ENGINE? NO
ARE ENGINE SUPPORT BRACKETS TIGHT AND FREE OF CORROSION? YES
36
SECONDARY FIRE PUMP CONTINUED:
MANUFACTURER OF DIESEL FIRE PUMP: PENTAIR
PUMP TYPE: CENTRIFUGAL FIRE PUMP/SPLIT CASE
MADE IN: USA YEAR BUILT: 2012
SERIAL #: 15-246665 SIZE MODEL#: 8”-2824AF
IMPELLER DIAMETER: 15.406 RATED PSI: 140 MAX SUCTION: 16.6
GPM: 2,500 RPM: 2,100 MAX B.H.P: 333.5 @ 150%: 122
MANUFACTURER OF FIRE PUMP CONTROLLER: METRON
SERIAL #: FF-11N48699-11 CAT#: FD4-JW
ARE ALL SWITCHES IN AUTO? YES CONTROLLER INSTALLED: 2012
PHASE: 1 HERTZ: 60 INPUT VOLTS: 120 MAX WORKING PRESSURE: 300
RESET PRESSURE: N/A SHUT OFF PRESSURE: N/A MADE IN: USA
ARE ALL VALVES IN NORMAL OPEN POSITION? YES ENCLOSURE TYPE: 04
37
PUMP ROOM CONTINUED:
WERE ANY ALARMS GOING OFF ON FIRE PUMP CONTROLLER? NO
WERE ALL PUMPS IN THE AUTO POSITION? YES
WERE BATTERY TERMINALS FREE OF CORROSION? YES
WAS THE BLOCK HEATER ON DIESEL PUMP WORKING? YES
IS THE OIL LEVEL ON DIESEL PUMP AT THE DESIRED HEIGHT ON
STICK? YES
DID BATTERY TERMINALS APPEAR TO BE TIGHT? YES
IS WATER DRIPPING AROUND THE SEALS ON THE PUMP TO KEEP THE
PUMP SHAFT LUBRICATED? YES
IS EXCESS WATER FROM PUMP SEALS DRAINING OFF OF THE PUMP
AND MOTOR BASE TO PREVENT METAL LOSS? YES
WHERE DOES SYSTEM RECEIVE ITS WATER FROM? LOCAL UTILITY
IF FILL LINE FROM LOCAL UTILITY IS EQUIPPED WITH A PRESSURE
GAUGE WHAT IS THE CURRENT PRESSURE? N/A
WHAT IS THE PRESSURE ON JOCKEY PUMP GAUGE? 155
IS THE PUMP ROOM INSULATED TO REDUCE COST OF HEATING AND
ADD PROTECTION AGAINST FREEZING? YES
IS THERE ANY EVIDENCE OF LEAKS IN THE BUILDINGS ROOF? NO
IS THERE ANY EVIDENCE OF VANDALISM? NO
ARE VALVES LOCKED AND EQUIPPED WITH TAMPER SWITCHES? YES
38
YATES TANK INSPECTION SERVICES
P.O. BOX 505 - PRINCETON, KY 42445 (270) 625-4898 PHONE (270) 365-2123 FAX
DIESEL FUEL TANK REPORT
YEAR FUEL TANK WAS BUILT: 1995
MFG SERIAL: 65616
WHO IS THE MANUFACTURER OF TANK? WE-MAC
WHAT IS THE TOTAL CAPACITY? 440 GALLONS
FUEL LEVEL DURING INSPECTION: ¾ FULL
OVERALL DIAMETER: 48”
OVERALL LENGTH: 73”
39
FUEL TANK CONTINUED:
IS TANK DESIGNED WITH SECONDARY CONTAINMENT AROUND IT
SUCH AS A DOUBLE WALL? NO, HAS AN UNDER CONTAINMENT
IS CONTAINMENT AROUND TANK EQUIPPED WITH A DRAIN PIPE
INSTALLED AT THE LOWEST POINT? NA
IS THERE A LEAK DETECTOR ATTACHED TO THE DRAIN PIPE? NO
IF YES WERE ANY ALARMS ACTIVATED? N/A
DOES THE TOP OF OUTER WALL OF TANK HAVE AN INSPECTION PLUG
TO VISUALLY CHECK FOR LEAKS? N/A
IS THERE ANY EVIDENCE OF FUEL IN THIS AREA? NO
IS THE AREA UNDER AND AROUND FUEL TANK DRY? YES
IS THE OUTER WALL OF TANK EQUIPPED WITH A VENT? YES
DOES VENT EXTEND OUT OF PUMP ROOM TO REMOVE ANY FUMES?
YES
40
FUEL TANK CONTINUED:
WHAT IS THE COLOR OF EXTERIOR FUEL TANK? YELLOW
WHAT IS THE CONDITION OF COATING ON TANK? GOOD
WHAT TYPE OF COATING WAS USED? ENAMEL
WHAT IS THE DRY FILM THICKNESS OF COATING? 2 TO 3 MILS
IS THE TANK SUPPORTED AND SECURED TO THE FLOOR? YES
TOTAL OF COLUMNS USED TO SUPPORT TANK: FOUR
WHAT TYPE OF MATERIAL USED? 4 INCH STEEL PIPE
HOW IS IT SECURED? CONNECTED BY THREADED PIPE STANDS
41
FUEL TANK CONTINUED:
IS TANK EQUIPPED WITH A FUEL LEVEL GAUGE? YES
DOES GAUGE APPEAR TO BE IN GOOD WORKING ORDER? YES
IS TANK EQUIPPED WITH A LOW FUEL ALARM? NO IF YES, WERE
ANY ALARMS GOING OFF DURING SITE VISIT? N/A
IS TANK EQUIPPED WITH AN EXCESS RETURN FUEL LINE THAT RUNS
FROM DIESEL FIRE PUMP TO TOP OF TANK? YES
IS THERE ANY EVIDENCE OF LEAKS IN THE PIPING? NO
ARE THERE ANY SIGNS OF KINKS IN THE LINES THAT COULD STOP
THE FLOW OF FUEL? NO
ARE ALL VALVES SUPPLYING FUEL TO THE DIESEL FIRE PUMP
LOCKED INTO THE OPEN POSITION? YES
IS THE PRIMARY SIDE OF FUEL TANK EQUIPPED WITH A VENT? YES
DOES VENT EXTEND OUT OF PUMP ROOM TO REMOVE ANY FUMES?
YES
42
FUEL TANK CONTINUED:
IS THE FILL LINE ATTACHED TO THE TOP OF TANK TO ALLOW FOR
POSITIVE FLOW WHEN FILLING? YES
IS FUEL TANK FILLED FROM THE EXTERIOR OF BUILDING TO
PREVENT FUMES FROM ENTERING BUILDING? YES
IS THE FILL LINE EQUIPPED WITH A GRAVITY FLOW TANK TO ALLOW
FOR PROPER FLOW WHEN FILLING? NO
IS THE GRAVITY FLOW TANK SECURED TO BUILDING? N/A
IS THE LID ON FUEL PIPING EQUIPPED WITH A LOCK TO PREVENT
THEFT OR VANDALISM? YES, CAP OVER END OF NOZZLE.
IS THIS LID SEALED TO KEEP WATER OUT OF SYSTEM? YES
43
RECOMMENDATIONS:
1) THE ROOF NEEDS A 30” SECONDARY ROOF HATCH INSTALLED 180
DEGREES FROM EXISTING.
2) THE INTERIOR COATING HAS POOR ADHESION AND NEEDS TO BE
COMPLETELY REMOVED. USE COATING OPTION ON FOLLOWING PAGE.
3) THE EXISTING SAFETY CAGE ON INTERIOR LADDER HAS SUFFERED METAL
LOSS AND NEEDS TO BE REMOVED. I RECOMMEND INSTALLING A
STAINLESS STEEL CABLE TYPE SAFETY CLIMB FOR FALL PROTECTION.
4) THE TANKS INTERIOR FLOOR SHOULD BE FLAT WITH THE WEIGHT OF
WATER ON IT YET IT HAS SOME UPWARD BULGES IN IT. WHEN TANK IS
DRAINED FOR REPAIRS CONDITION OF FLOOR WILL NEED TO BE
INSPECTED.
44
INTERIOR COATING OPTIONS
Interior Wet –Epoxy Coating System:
Field Surface Preparation:
All of interior surface needs to be blasted in accordance with the recommended methods outlined
in The Society for Protective Coatings Specification SSPC-SP10 (NACE No. 2). Also remove all
weld spatters, rough or sharp edges on weld seams by grinding them smooth allowing paint to be
applied evenly preventing pin holes.
Clean Surfaces:
All surfaces needs to be cleaned of blast media and dust by vacuuming.
Field Prime Coat:
Immediately after abrasive blasting and before any rusting occurs, apply one complete coat of
Sherwin Williams Dura plate 235 (color beige) resulting in a dry film thickness of 4.0 to 6.0 mils
Pit Filling:
Fill all pitted areas with an owner’s pre-approved epoxy filler and weld any pits over half the
thickness of shell.
Finish Coat:
Apply 2ND coat of Sherwin Williams Dura plate 235 (Color white to insure coating was applied
evenly preventing pin holes and holidays) Resulting in a finish dry film thickness of 8.0 to 12.0
mils.
Sealing Voids In Roof:
After all interior painting seam seal all non-immersed areas such as lap joints and voids between
rafters under 3/8 of an inch from roof with A flexible caulk that will bond to a steel surface such
as Silkaflex 1A .
Note: @ 77 degrees a 7 day cure time before tank can be filled.
All paints being used must be preapproved and (ANS/NSF) certified for potable water.
All surfaces to be refinished shall be prepared in accordance with the requirements of the Steel Structure
Painting Council (SSPC). All paints shall comply with (ASTM) specifications and delivered in sealed
containers & labeled by manufacturer. All coating being used should be within its shelf life and
stored at a minimum of 20 degrees and a maximum of 110 degrees. Do not paint over any
surfaces where moisture content exceeds 15 percent or more of water. The moisture content can
be determined by using a moisture meter.