· 2020-04-15 · contents and general instructions festo p.be−cpx−ax−en en 0811d i original...

278
Manual Electronics CPX analogue I/O modules I/O modules ɣ CPX−2AE−U−I ɣ CPX−4AE−I ɣ CPX−4AE−T ɣ CPX−4AE−TC ɣ CPX−2AA−U−I Sub−bases ɣ CPX−AB−... ɣ CPX−M−... CPX Terminal Manual 526 416 en 0811d [740 896]

Upload: others

Post on 05-Jul-2020

2 views

Category:

Documents


0 download

TRANSCRIPT

Page 1:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Manual Electronics

CPX analogue I/O modules

I/O modules� CPX−2AE−U−I� CPX−4AE−I� CPX−4AE−T� CPX−4AE−TC� CPX−2AA−U−I

Sub−bases� CPX−AB−...� CPX−M−...

CPX Terminal

Manual526 416en 0811d[740 896]

Page 2:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de
Page 3:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

IFesto P.BE−CPX−AX−EN en 0811d

Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Edition en 0811d. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Designation P.BE−CPX−AX−EN. . . . . . . . . . . . . . . . . . . . . . . . .

Order no. 526 416. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

© (Festo AG�&�Co. KG, D�73726 Esslingen, Germany, 2008)Internet: http://www.festo.comE−Mail: [email protected]

The reproduction, distribution and utilization of this docu−ment as well as the comunication of its contents to otherswithout express authorization is prohibited. Offenders willbe held liable for the payment of damages. All rights re−served in the event of the grant of a patent, utility moduleor design.

Page 4:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

II Festo P.BE−CPX−AX−EN en 0811d

TORX�® is a registered trade mark of CAMCAR TEXTRON INC.,Rockford, Ill., USA

HARAX�® is a registered trade mark of HARTING Deutschland GmbH,32381 Minden, Germany

SPEEDCON�® is a registered trade mark of PHOENIX CONTACTGmbH�&�Co.�KG, 32825 Blomberg, Germany

Page 5:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

IIIFesto P.BE−CPX−AX−EN en 0811d

Contents

Designated use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Target group VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Important user instructions IX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CPX analogue I/O modules XI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Diagnosis via the field bus XIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Structure of a CPX terminal XIV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1. Overview and connection technology I/O modules 1−1 . . . . . . . . . . . . . . . . . . .

1.1 Components of an I/O module 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Connection technology 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.1 Display and connecting elements 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.2 Combinations of analogue I/O modules and sub−bases 1−8 . . . . . . . . .

1.2.3 Connecting the cables and plugs to the sub−bases 1−9 . . . . . . . . . . . . .

1.3 Assembly 1−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.1 Fitting the sub−bases 1−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.2 Fitting the screening/shield plates 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . .

2. Analogue input module CPX−2AE−U−I 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 Function of the analogue input modules 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2 Fitting 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Installation 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.1 DIL switch settings 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.2 Pin assignment 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.3 Connecting the analogue intputs 2−11 . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Instructions on commissioning 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.1 Processing analogue input signals 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.2 General information on parametrizing 2−16 . . . . . . . . . . . . . . . . . . . . . . .

2.4.3 Parameters of the analogue input module type CPX−2AE−U−I 2−18 . . . . .

2.4.4 Module parameter �Input analogue−value data format" 2−26 . . . . . . . .

2.4.5 Channel−specific module parameters � Limits 2−28 . . . . . . . . . . . . . . . . .

2.4.6 Channel−specific module parameters � Filter measured value 2−31 . . . .

2.4.7 Channel−specific module parameters � Monitor of wire fracture 2−31 . .

Page 6:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

IV Festo P.BE−CPX−AX−EN en 0811d

2.5 Diagnosis 2−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.1 Fault messages of the analogue input modules 2−33 . . . . . . . . . . . . . . .

2.5.2 LED display 2−35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.3 Fault treatment and parametrizing 2−37 . . . . . . . . . . . . . . . . . . . . . . . . . .

3. Analogue input module CPX−4AE−I 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Function of the analogue input modules 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2 Fitting 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Installation 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 DIL switch settings 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.2 Pin assignment 3−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.3 Connecting the analogue intputs 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Instructions on commissioning 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.1 Processing analogue input signals 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.2 General information on parametrizing 3−16 . . . . . . . . . . . . . . . . . . . . . . .

3.4.3 Parameters of the analogue input module type CPX−4AE−I 3−18 . . . . . . .

3.4.4 Module parameter �Input analogue−value data format" 3−27 . . . . . . . .

3.4.5 Channel−specific module parameters � Limits 3−29 . . . . . . . . . . . . . . . . .

3.4.6 Channel−specific module parameters � Filter measured value 3−32 . . . .

3.4.7 Channel−specific module parameters � Monitor of wire fracture 3−32 . .

3.5 Diagnosis 3−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.1 Fault messages of the analogue input modules 3−34 . . . . . . . . . . . . . . .

3.5.2 LED display 3−36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.3 Fault treatment and parametrizing 3−38 . . . . . . . . . . . . . . . . . . . . . . . . . .

4. Analogue input module CPX−4AE−T 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 Function of analogue input module CPX−4AE−T 4−4 . . . . . . . . . . . . . . . . . . . . . . .

4.2 Fitting 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3 Installation 4−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3.1 DIL switch settings 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3.2 Pin assignment 4−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3.3 Connecting temperature sensors to the analogue inputs 4−11 . . . . . . . .

Page 7:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

VFesto P.BE−CPX−AX−EN en 0811d

4.4 Instructions on commissioning 4−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.1 Processing the input signals of temperature sensors 4−14 . . . . . . . . . . .

4.4.2 General information on parametrizing 4−17 . . . . . . . . . . . . . . . . . . . . . . .

4.4.3 Parameters of the analogue input module type CPX−4AE−T 4−18 . . . . . .

4.4.4 Monitoring wire fracture/short circuit 4−26 . . . . . . . . . . . . . . . . . . . . . . .

4.4.5 Limit value monitoring by parametrizing 4−26 . . . . . . . . . . . . . . . . . . . . .

4.4.6 Measured value smoothing by parametrizing 4−27 . . . . . . . . . . . . . . . . .

4.5 Diagnosis 4−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5.1 Error messages of the analogue input modules 4−29 . . . . . . . . . . . . . . .

4.5.2 LED display 4−31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5.3 Error treatment and parametrizing 4−33 . . . . . . . . . . . . . . . . . . . . . . . . . .

5. Analogue input module CPX−4AE−TC 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.1 Function of the analogue input module CPX−4AE−TC 5−4 . . . . . . . . . . . . . . . . . . .

5.2 Assembly 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3 Installation 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.1 Pin allocation 5−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.2 Introduction to temperature measurement by means of thermocouples 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.3 Cold junction compensation 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.4 Connecting temperature sensors to the analogue inputs 5−14 . . . . . . . .

5.4 Instructions on commissioning 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4.1 Processing the input signals of temperature sensors 5−15 . . . . . . . . . . .

5.4.2 General information on parametrizing 5−18 . . . . . . . . . . . . . . . . . . . . . . .

5.4.3 Parameters of analogue input module type CPX−4AE−TC 5−19 . . . . . . . .

5.5 Diagnostics 5−31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.5.1 Fault messages of the analogue input modules 5−32 . . . . . . . . . . . . . . .

5.5.2 LED displays 5−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.5.3 Fault treatment and parametrizing 5−35 . . . . . . . . . . . . . . . . . . . . . . . . . .

6. Analogue output module CPX−2AA−U−I 6−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.1 Function of the analogue output modules 6−4 . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.2 Fitting 6−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 8:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

VI Festo P.BE−CPX−AX−EN en 0811d

6.3 Installation 6−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.3.1 DIL switch settings 6−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.3.2 Pin assignment 6−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.3.3 Connecting the analogue outputs 6−11 . . . . . . . . . . . . . . . . . . . . . . . . . .

6.4 Instructions on commissioning 6−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.4.1 Processing analogue output signals 6−12 . . . . . . . . . . . . . . . . . . . . . . . .

6.4.2 General information on parametrizing 6−15 . . . . . . . . . . . . . . . . . . . . . . .

6.4.3 Parameter with analogue output module type CPX−2AA−U−I 6−17 . . . . .

6.4.4 Module parameter �Output analogue−value data format" 6−27 . . . . . . .

6.4.5 Channel−specific module parameters � Limits 6−29 . . . . . . . . . . . . . . . . .

6.4.6 Channel−specific module parameters � Monitor wire fracture 6−31 . . . .

6.5 Diagnosis 6−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.5.1 Fault messages of the anaolgue output modules 6−33 . . . . . . . . . . . . . .

6.5.2 LED display 6−37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.5.3 Fault treatment and parametrizing 6−39 . . . . . . . . . . . . . . . . . . . . . . . . . .

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical specifications of analogue input module CPX−2AE−U−I A−3 . . . . . . . . .

A.2 Technical specifications of analogue input module CPX−AE−U−I A−5 . . . . . . . . . . .

A.3 Technical specifications of analogue input module CPX−4AE−T (temperature module) A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.4 Technical specifications of analogue input module CPX−4AE−TC (temperature module) A−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.5 Technical specifications of analogue output module CPX−2AA−U−I A−11 . . . . . . . .

A.6 Technical specifications of the sub−bases A−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.7 Internal structure of the CPX modules A−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.8 Connection examples A−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.8.1 Analogue input and output modules A−18 . . . . . . . . . . . . . . . . . . . . . . . .

A.8.2 Connecting temperature sensors to the module CPX−4AE−T A−22 . . . . . .

A.8.3 Connecting temperature sensors to the module CPX−4AE−TC A−24 . . . . .

A.9 Accessories A−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B. Index B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 9:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

VIIFesto P.BE−CPX−AX−EN en 0811d

Designated use

The CPX analogue I/O modules described in this manual havebeen designed exclusively for use in conjunction with CPXterminals from Festo. The analogue I/O modules are only tobe used as follows:

� as designated

� in faultless technical condition

� without any modifications by the user.

If additional commercially available components such assensors and actuators are connected, the specified limits forpressures, temperatures, electrical data, torques, etc. mustnot be exceeded.

Please observe the standards specified in the relevantchapters and comply with technical regulations, as well aswith national and local regulations.

Warning· In order to provide the electric power supply, use onlyPELV circuits as per IEC/DIN EN 60204−1 (ProtectiveExtra−Low Voltage, PELV).Also take into account the general requirements for PELVcircuits according to IEC/DIN EN 60204−1.

· Only use power packs which guarantee reliableelectrical isolation of the operating voltage according toIEC/DIN EN 60204−1.

By the use of PELV power units, protection against electricshock (protection against direct and indirect contact) isguaranteed in accordance with IEC/DIN EN 60204−1(electrical equipment of machines, general requirements).

Page 10:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

VIII Festo P.BE−CPX−AX−EN en 0811d

Target group

This manual is intended exclusively for technicians trained incontrol and automation technology, who have experience ininstalling, commissioning, programming and diagnosingprogrammable logic controllers (PLC) and field bus systems.

Service

Please consult your local Festo Service agent if you have anytechnical problems.

Page 11:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

IXFesto P.BE−CPX−AX−EN en 0811d

Important user instructions

Danger categories

This manual contains instructions on the possible dangerswhich may occur if the product is not used correctly. Theseinstructions are marked (Warning, Caution, etc.), printed on ashaded background and marked additionally with a picto�gram. A distinction is made between the following dangerwarnings:

WarningThis means that failure to observe this instruction mayresult in serious personal injury or damage to property.

CautionThis means that failure to observe this instruction mayresult in personal injury or damage to property.

NoteThis means that failure to observe this instruction mayresult in damage to property.

The following pictogram marks passages in the text whichdescribe activities with electrostatically sensitive compo�nents.

Electrostatically sensitive components may be damaged ifthey are not handled correctly.

Page 12:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

X Festo P.BE−CPX−AX−EN en 0811d

Marking special information

The following pictograms mark passages in the textcontaining special information.

Pictograms

Information:Recommendations, tips and references to other sources ofinformation.

Accessories:Information on necessary or sensible accessories for theFesto product.

Environment:Information on environment−friendly use of Festo products.

Text markings

· The bullet indicates activities which may be carried out inany order.

1. Figures denote activities which must be carried out in thenumerical order specified.

� Hyphens indicate general activities.

Page 13:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

XIFesto P.BE−CPX−AX−EN en 0811d

CPX analogue I/O modules

Analogue I/O modules for CPX terminals are available asinput or output modules. This manual contains informationon the method of operation, the fitting and installation of thefollowing modules:

Analogue I/O modules Typedesignation

Description Sub−bases andmanifold sub−bases

� CPX−2AE−U−I Input module with2�analogue inputs,signal range can beselected per inputchannel:� 0 � 10 V� 0 � 20 mA� 4 � 20 mA

The I/O modules eachconsist of the electronicmodule as well as asub−base and a manifoldsub−base.

Sub−bases (note thepossible combinations insection 1 2 2)

� CPX−4AE−I Input module with4�analogue inputs,signal range can beselected per inputchannel:� 0 � 20 mA� 4 � 20 mA

section 1.2.2).� CPX−M−4−M12x2−5POL� CPX−AB−4−M12x2−5POL� CPX−AB−4−M12x2−5POL−R� CPX−AB−8−KL−4POL� CPX−AB−1−SUB−BU−25POL� CPX−AB−4−HAR−4POL

� CPX−4AE−T Input module with upto �4 analogue inputsfor registering thetemperature. Numberof inputs can beselected with DILswitch (2 or 4).

Manifold sub−bases:� CPX−GE−EV−S...� CPX−GE−EV−Z...� CPX−M−GE−EV−S...� CPX−M−GE−EV−Z...� CPX−GE−EV−V...

Tab.�0/1: Overview of analogue I/O modules (part 1)

Page 14:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

XII Festo P.BE−CPX−AX−EN en 0811d

Analogue I/O modules Typedesignation

Description Sub−bases andmanifold sub−bases

� CPX−4AE−TC Input module with4�analogue inputsfor temperatureregistering

The I/O modules eachconsist of the electronicmodule as well as asub−base and a manifoldsub−base.

Sub−bases (note thepossible combinations insection 1.2.2).� CPX−M−4−M12x2−5POL

� CPX−2AA−U−I Output module with2�analogue outputs,signal range can beselected per outputchannel:� 0 � 10 V� 0 � 20 mA� 4 � 20 mA

� CPX−M−4−M12x2−5POL� CPX−AB−4−M12x2−5POL� CPX−AB−4−M12x2−5POL−R� CPX−AB−8−KL−4POL� CPX−AB−1−SUB−BU−25POL� CPX−AB−4−HAR−4POL

Manifold sub−bases:� CPX−GE−EV−S...� CPX−GE−EV−Z...� CPX−M−GE−EV−S...� CPX−M−GE−EV−Z...� CPX−GE−EV−V...

Tab.�0/2: Overview of analogue I/O modules (part 2)

Page 15:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

XIIIFesto P.BE−CPX−AX−EN en 0811d

Diagnosis via the field bus

Depending on the parametrizing, CPX I/O modules registerthe specific faults via the field bus.

These can be evaluated via the:

� status bits (system status)

� I/O diagnostic interface (system diagnosis)

� module diagnosis

� fault numbers.

Further information on diagnosis can be found in the CPXsystem manual or in the manual for the field bus node.

Page 16:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

XIV Festo P.BE−CPX−AX−EN en 0811d

Structure of a CPX terminal

CPX terminals consist of electric function modules, individualmodules and components (see example in Fig.�0/1).

ÖÖÖÖÖÖ

ÖÖÖÖÖÖ

ÖÖÖÖÖÖÖÖ

ÖÖÖÖÖÖÖÖÖÖ

ÖÖ

ÖÖÖÖ

ÖÖÖÖÖÖÖÖÖÖÖÖ

1 2 3 4

5

6

7

8

1 Field bus node

2 I/O modules

3 Pneumatic interface

4 Pneumatic modules (example CPA � type 12)

5 Manifold sub−base with additional powersupply

6 Manifold sub−base without supply

7 Manifold sub−base with system supply

8 End plate

Fig.�0/1: Example of CPX terminal

Page 17:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

XVFesto P.BE−CPX−AX−EN en 0811d

Type Title Description

ManualElectronics

�System manual"type P.BE−CPX−SYS−...

Overview of structure, components andmethod of operation of CPX terminals;installation and commissioning instructions aswell as basic principles of parameterising

�CPX field bus node"type P.BE−CPX−FB...

Instructions for the assembly, installation,commissioning and diagnosis of the relevantfield bus nodes

�CPX I/O modules"type P.BE−CPX−EA−...

Notes about connection types and instruc�tions on fitting, installing and commissioninginput and output modules of type CPX−... , theMPA pneumatic modules, as well as MPA, CPAand Midi/Maxi pneumatic interfaces

�CPX analogue I/Omodules"type P.BE−CPX−AX−...

Notes about connection types and instruc�tions for fitting, installing and commissioningCPX analogue I/O modules

�CPX−CP interface"type P.BE−CPX−CP−...

Instructions on commissioning and diagnosingCPX terminals with the CP interface typeCPX−CP−4−FB

�Handheld"type P.BE−CPX−MMI−1...

Instructions on commissioning and diagnosingCPX terminals with the handheld typeCPX−MMI−1

�CPX−FEC"type P.BE−CPX−FEC−...

Instructions for fitting, installing,commissioning and diagnosing the CPX FrontEnd Controller

Softwarepackage

�FST" Programming in Statement List and LadderDiagram for the FEC

ManualPneumatics

�Valve terminals withMPA pneumatics"type P.BE−MPA−...

Instructions on fitting, installing andcommissioning MPA pneumatics (type 32)

�Valve terminals withCPA�pneumatics"type P.BE−CPA−...

Instructions on fitting, installing andcommissioning CPA pneumatics (type 12)

�Valve terminals withMidi/Maxi pneumatics"type P.BE−Midi/Maxi−03−...

Instructions on fitting, installing andcommissioning Midi/Maxi pneumatics(type�03)

Tab.�0/3: Manuals on the CPX terminal

Page 18:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

XVI Festo P.BE−CPX−AX−EN en 0811d

The following product−specific terms and abbreviations areused in this manual:

Term/abbreviation Meaning

Analogue I/Os Analogue inputs and outputs

Analogue output module CPX output module with analogue outputs

Analogue input module CPX input module with analogue inputs

AI Analogue input (input channel, 16 bits)

AO Analogue output (output channel, 16 bits)

CPX modules Common term for the various modules which can be incorporated in aCPX terminal

CPX terminal Modular, electric terminal type 50

Data The CPX terminal provides settings and diagnostic information in the formof data; the data can be read but not changed

DIL switches Dual−in−line switches consist of several switch elements with whichsettings can be made

I/O diagnostic interface The I/O diagnostic interface is a bus−independent diagnostic interface atI/O level, permitting access to internal data of the CPX terminal

I/O modules Common term for the CPX modules which provide inputs and outputs(CPX input modules and CPX output modules)

IU / II Analogue voltage input / analogue current input

OU / OI Analogue voltage output / analogue current output

Sub−base Replaceable upper part of housing of modules with connections

Tab.�0/4: Product−specific abbreviations � part 1

Page 19:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

XVIIFesto P.BE−CPX−AX−EN en 0811d

Term/abbreviation Meaning

Fieldbus node Provides the connection to specific field buses. They transmit controlsignals to the connected modules and monitor their functioning

Manifold base Lower part of the housing of a module or block for linking the moduleelectrically with the terminal

Parameters With the aid of parametrizing, the reaction of the CPX terminal or thereaction of the individual modules and I/O channels can be adapted toeach particular application; parameters can be read and changed

PLC / IPC Programmable Logic Controller / Industrial PC

RTD Resistance Temperature Device

Status bits Internal inputs which supply coded common diagnostic messages

TC Thermocouple

Tab.�0/5: Product−specific abbreviations � part 2

Page 20:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Contents and general instructions

XVIII Festo P.BE−CPX−AX−EN en 0811d

Page 21:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Overview and connection technology I/O modules

1−1Festo P.BE−CPX−AX−EN en 0811d

Chapter 1

Page 22:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−2 Festo P.BE−CPX−AX−EN en 0811d

Contents

1. Overview and connection technology I/O modules 1−1 . . . . . . . . . . . . . . . . . . .

1.1 Components of an I/O module 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2 Connection technology 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.1 Display and connecting elements 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.2.2 Combinations of analogue I/O modules and sub−bases 1−8 . . . . . . . . .

1.2.3 Connecting the cables and plugs to the sub−bases 1−9 . . . . . . . . . . . . .

1.3 Assembly 1−20 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.1 Fitting the sub−bases 1−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

1.3.2 Fitting the screening/shield plates 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 23:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−3Festo P.BE−CPX−AX−EN en 0811d

Contents of this chapter This chapter provides an overview of the structure andcomponents of CPX I/O modules.

The concept of variable connection technology with modularsub−bases is also described.

You will also find a description of how to fit and removeelectronic modules and sub−bases on the manifold sub−basesof the CPX terminal.

Further information Special information on the analogue input modules can befound in chapters 2 to 4. Special information on the analogueoutput modules can be found in chapter 5.

Information on fitting the complete CPX terminal, connectingthe power supply as well as general instructions on configur�ation and parametrizing can be found in the CPX systemmanual.

Information on the address assignment as well as on com�missioning can be found in the appropriate field bus nodemanual or function module manual.

Page 24:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−4 Festo P.BE−CPX−AX−EN en 0811d

1.1 Components of an I/O module

All I/O modules consist of three parts:

� The sub−base provides the electrical connections in theform of different sockets or terminal strips.

� The electronic module contains the printed circuit boardwith the electronics and the LED display of the I/O module.The electronic module is fitted into the sub−base and isconnected to this and to the manifold sub−base by meansof electric plug connectors.

� The manifold sub−base as the lower part of the housingprovides the mechanical and electrical link between themodule and the CPX terminal.

1 Sub−base withspecificconnections

2 Electronicsmodule

3 Manifold base

1

2

3

Fig.�1/1: Components of an I/O module

Page 25:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−5Festo P.BE−CPX−AX−EN en 0811d

1.2 Connection technology

Individual connection requirements can be fulfilled withdifferent sub−bases. These sub−bases provide the requiredsockets or terminal strips for connecting the sensors andactuators, irrespective of the I/O module used.

Sub−base Type Description

CPX−M−4−M12x2−5POL 4 M12 sockets with metal thread, 5−pin, 4 A loadcapacity� Protection class IP65/IP67 1)

� One functional earth connection per socket� Screening/shielding possibility via metal thread� Sub−base housing in metal design

CPX−AB−4−M12x2−5POL 4 M12 sockets, 5−pin, 3 A load capacity� Protection class IP65/IP67 1)

� One functional earth connection per socket� Screening/shielding possibility via screening/

shield plate (see �Accessories", appendix�A.9)

CPX−AB−4−M12x2−5POL−R 4 M12 sockets with metal thread, 5−pin, 4 A load capacity� Protection class IP65/IP67 2)

� One functional earth connection per socket� Screening/shielding possibility via metal thread� Enables M12 connectors and SPEEDCON quick

connectors to be used

1) With plug connector inserted or with protective cap ISK−M122) With plug connector inserted or with protective cap ISK−M12; when using quick connectors,

follow the manufacturer’s instructions

Tab.�1/1: Connection technology � part 1

Page 26:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−6 Festo P.BE−CPX−AX−EN en 0811d

Sub−base Type Description

CPX−AB−8−KL−4POL 2 terminal strips, 16−pin (4 x 4−pin), 4 A load capacity� Protection class IP20 3)

� Protection class IP65/IP67 with cover AK−8KLand screw connector set VG−K−M9

� All cores can be laid individually in spring−clipterminals

� Connections are in groups of 4, one functionalearth connection per group

CPX−AB−1−SUB−BU−25POL 1 Sub−D socket, 25−pin, 4 A load capacity� Protection class IP20 4)

� Protection class IP65 with plugSD−SUB−D−ST25 (see �Accessories",appendix�A.9)

CPX−AB−4−HAR−4POL(in the case of CPX analoguemodules can only be usedfor module 4AE−T)

4 HARAX sockets, 4−pin, 3 A load capacity� Protection class IP65/IP67 1) with the

intended plugs� Connection of the cable cores in the plug using

insulation displacement technology

1) With plug connector inserted or with protective cap ISK−M122) With plug connector inserted or with protective cap ISK−M12; when using quick connectors,

follow the manufacturer’s instructions3) With cover AK−8KL and screw connector set VG−K−M9: IP65 / IP674) With plug SD−SUB−D−ST25: IP65

Tab.�1/2: Connection technology � part 2

Page 27:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−7Festo P.BE−CPX−AX−EN en 0811d

1.2.1 Display and connecting elements

On all input and output modules the status LEDs can be seenthrough the transparent cover of the sub−base.

The analogue I/O modules have the following display andconnecting elements:

1 Type plate ofsub−base

2 Identification ofmodule (e.g. 2AO =2�analogue outputs � module typeCPX−2AA−U−I)

3 Electrical connections(example)

4 Inscription fields foraddresses

5 Fault LED (red) Module fault

6 Channel−relatederror LEDs(only�CPX−4AE−T andCPX−4AE−TC)

2AO

1

2

3

4

5

6

Fig.�1/2: Display and connecting elements

Use identity labels type IBS 6x10 for marking the addresses.

Page 28:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−8 Festo P.BE−CPX−AX−EN en 0811d

1.2.2 Combinations of analogue I/O modules and sub−bases

The following table shows the permitted combinations ofmodules and sub−bases.

Sub−base CPX...

Input module CPX−...

Outputmodule CPX−...

2AE−U−I(2 analogueinputs)

4AE−I(4 analogueinputs)

4AE−T(temperat.registering)

4AE−TC(temperat.registering)

2AA−U−I(2 analogueoutputs)

−M−4−M12x2−5POL(4 M12 sockets, 5−pin,metal housing)

· · · · ·

−AB−4−M12x2−5POL(4 M12 sockets, 5−pin)

· · · · ·

−AB−4−M12x2−5POL−R(4 M12 sockets, 5−pin,metal thread)

· · · · ·

−AB−8−M8−3POL(8 M8 sockets, 3−pin)

� � � � �

−AB−8−M8−4POL(8 M8 sockets, 4−pin)

� � � � �

−AB−8−KL−4POL(2 terminal strips, 16−pin)

· · · · ·

−AB−1−SUB−BU−25POL(1 SUB−D socket, 25−pin)

· · � � ·

−AB−4−HAR−4POL(4 M12 sockets, 4−pin)

� � · � �

−AB−4−M12−8POL(4 M12 sockets, 8−pin)

� � � � �

· Can be combined� Cannot be combined

Tab.�1/3: Combinations of I/O modules and sub−bases

Page 29:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−9Festo P.BE−CPX−AX−EN en 0811d

1.2.3 Connecting the cables and plugs to the sub−bases

Sensors and actuators must be connected to the CPX I/Omodules only at the sub−bases. In this way, e.g. when anelectronic module is replaced, the plugs and cables remainfitted in the sub−base.

WarningSudden unexpected movement of the connected actuatorsand�uncontrolled movements of loose tubing can causeinjury to human beings or damage to property.

Switch off the following equipment before undertakinginstallation and/or maintenance work:

� Compressed air supply

� Operating and load voltage supplies

The protection class of the I/O modules depends on the sub−base, as well as on the plugs and protective caps used.Instructions can be found on the following pages and in theappendix A.6.

Use plugs and cables from the Festo range for connectingsensors and actuators (see appendix A.9).

If you wish to use your own cables, use only screened/shielded cables for transmitting analogue signals.

CautionLong signal cables reduce the immunity to interference. Do not exceed the maximum permitted I/O signal cablelength:

� CPX−2AE−U−I, 2AA−U−I, 4AE−I: 30 m

� CPX−4AE−T: 10 m (with measuring error max. 200 m)

� CPX−4AE−TC: 10 m (with measuring error max. 50 m)

The measuring accuracy of modules CPX−4AE−T and 4AE−TCdiminishes at cable lengths over 10 m; the�measuring errorcannot be compensated for.

Page 30:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−10 Festo P.BE−CPX−AX−EN en 0811d

Screening

NoteFor transmitting analogue signals:

· Connect the cable screening/shield to FE. Use only screened/shielded cables and plugs withmetallic housing.

· Observe the instructions on the following pages forconnecting the cable screening/shield depending on theconnections.

In this way, you will avoid interference caused by electromag�netic influences.

The following variants are permitted for connecting the cablescreening/shield:

� screening/shield connection on the FE pin of the I/O plugwithout connection to further potentials

� screening/shield connection to an external FE connectionwithout connection to the FE pin of the I/O plug.

Recommendation:

· Connect the cable screening/shield to both sides of theFE with sufficient potential equalization.

· If the cable screening/shield is connected only to oneside of the FE, it should be connected to the �signalreceiver side:"

� analogue inputs (CPX−2AE−U−I): connect the cable screening/shield on the CPX side

� analogue outputs (CPX−2AA−U−I): connect the cable screening/shield on the actuatorside.

Page 31:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−11Festo P.BE−CPX−AX−EN en 0811d

Sub−base CPX−M−4−M12x2−5POL...

NoteIn order that the completely fitted modules with sub−baseCPX−M−4−M12x2−5POL... comply with protection classIP65/IP67:

· Use plugs and cables specified from the Festo range forconnecting sensors and actuators (see appendix A.9)

· Tighten the union nuts of the plugs at first by hand.

· Seal unused sockets with protective caps type ISK−M12(Accessories).

Screening

� On plugs without metal housing:

· Connect the cable screening/shield to pin 5 (functional earth FE).

� On plugs with metal housing:

· Connect the cable screening via the plug housing withFE. If necessary, additionally connect the cablescreening/shield to pin�5.

Page 32:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−12 Festo P.BE−CPX−AX−EN en 0811d

Sub−base CPX−AB−4−M12x2−5POL (−R)

NoteIn order that the completely fitted modules with sub−baseCPX−AB−4−M12x2−5POL (−R) comply with protection classIP65/IP67:

· Use plugs and cables specified from the Festo range forconnecting sensors and actuators (see appendix A.9)

· Tighten the union nuts of the plugs at first by hand.

· Seal unused sockets with protective caps type ISK−M12(Accessories).

The connector sockets of sub−base CPX−AB−4−M12x2−5POL−R(with metal thread) enable fast locking systems to be used,e.g. SPEEDCON from Phoenix Contact.

· When using fast locking systems follow the manufac�turer’s instructions in order to comply with protectionclass IP65/IP67.

Screening

� On plugs without metal housing:

· Connect the cable screening/shield to pin 5 (functional earth FE).

� On plugs with metal housing:

· Use sub−base CPX−AB−4−M12x2−5POL−R. The metal thread of the connector sockets isconnected internally to pin 5 (FE).

or

· Connect the cable screening/shield via the plughousing and the screening plate (see below) to FE. If necessary, additionally connect the cablescreening/shield to pin�5.

Page 33:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−13Festo P.BE−CPX−AX−EN en 0811d

Screening plate type CPX−AB−S−4−12

Sub−base CPX−AB−4−M12x2−5POL (sockets without metalthread) can be combined with a screening/shield plate.Depending on what you have ordered, this may already befitted on the sub−base.

Instructions on subsequent fitting of the screening/shieldplate can be found in section 1.3.2.

The electromagnetic compatibility can be improved withscreening/shield plates, e.g. in environments heavily sub�jected to interference or for analogue signals. For this pur�pose the screening/shield plates must be earthed at the flatcontact intended for this purpose as per DIN 46�244 B2,�8−1(2.8 x 1 mm).

· Connect the earth cable of the screening/shield platewith low impedance to the functional earth connection(FE) as per Fig.�1/3.

Screening/shield plates lying next to each other areconnected together by spring clips and must not beconnected individually to FE.

If the intended plugs are used (see �Accessories", appen�dix�A.9), the plug housing will be connected to functionalearth via the screening/shield plate by means of the springcontacts.

· Before fitting the plugs screw the spring contacts as far aspossible onto the thread of the plug.

Page 34:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−14 Festo P.BE−CPX−AX−EN en 0811d

1 Plug

2 Spring contact

3 Screening plate

4 Functional earthconnection (FE)with bladeconnector asper DIN�46�245B2,�8−1

1

2

3

4

Fig.�1/3: Connecting the screening/shield plate

NoteTo comply with protection class IP65/IP67:

· Do not use the spring contacts if you have sealedunused sockets with protective caps.

Sub−base CPX−AB−8−KL−4POL

The completely fitted sub−base CPX−AB−8−KL−4POL complieswith protection class IP20.

Screening

· Use a cable as short as possible to connect the cablescreening/shield to the FE terminal of the sub−base. Use suitable core end sleeves for the connection.

Page 35:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−15Festo P.BE−CPX−AX−EN en 0811d

Specification of the cable terminals

� Cable cross−sectional area: 0.08 � 1.5 mm2

� Max. current: 1.5 A

� Insulation removed: 5 � 6 mm

Permitted copper conductors

� Single wire, multi−wire, fine wire, also with tin−platedindividual cores

� Fine wire strands compressed

� Fine wire with core end sleeves (sealed against gas, crimped on) *)

� Fine wire with pin cable socket (sealed against gas, crimped on) *)

*) If necessary, use next smaller cross−sectional area

Fitting and removing the cables

Note· To ensure reliable contact, connect only one conductorper spring terminal.

· Insert only cables into the terminal opening. Theterminal will be damaged if a screwdriver is inserted intothe opening.

When connecting and disconnecting the cables:

1. Press the screwdriver with a light rotary movement to�wards the centre of the�unlocking opening (see Fig.�1/4).The cable terminal will then be unlocked.

Page 36:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−16 Festo P.BE−CPX−AX−EN en 0811d

1 Screwdriver, blade2.5 x 0.4 mm

2 Unlocking opening(inside)

3 Cable

4 Terminal opening forinserting the conduc�tors (outside)

5 Terminal strips

1

23

4

5

1

2

3

4 5

Fig.�1/4: Connecting the terminal strips

2. When the terminal is unlocked you can insert or pull outthe ends of the cable through the opening.

3. Remove the screwdriver from the unlocking opening. The cable will then be securely locked.

You will then comply with protection class IP65/IP67

In order that sub−base CPX−AB−8−KL−4POL complies withprotection class IP65/IP67, use cover type AK−8KL and thescrew connector set type VG−K−M9 from Festo. Note therelevant fitting instructions.

Page 37:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−17Festo P.BE−CPX−AX−EN en 0811d

1 Cover AK−8KL

2 Screw connectorset VG−K−M9

12

Fig.�1/5: Cover and screw connector set for sub−base CPX−AB−8−KL−4POL (for complying with protection class IP65/67)

Sub−base CPX−AB−1−SUB−BU−25POL

The completely fitted sub−base CPX−AB−1−SUB−BU−25POLcomplies with protection class IP20.

In order that sub−base CPX−AB−1−SUB−BU−25POL complies with protection class IP65/IP67, use plug type SD−SUB−D−ST25 from Festo.When fitting the plug onto the sub−base, observe themaximum tightening torque of 0.5 Nm.

Screening

· Use a cable as short as possible to connect the cablescreening/shield to the FE pin of the Festo sub−D plug.

If other screened plugs are used, the metal flange(housing) of the sub−D plug can also be used forconnecting the cable screening/shield.

Page 38:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−18 Festo P.BE−CPX−AX−EN en 0811d

Sub−base CPX−AB−4−HAR−4POL

NoteIn order that the completely fitted modules with sub−baseCPX−AB−4−HAR−4POL comply with protection classIP65/IP67:

· Use plugs type SEA−GS−HAR−4POL from the Festo range(consisting of union nut, strain relief and splicing ring)for connecting sensors and actuators.

· Tighten the union nuts of the plugs at first by hand.

· Seal the unused connecting sockets with protectivecaps from Harting (see Accessories, appendix A.9).

Specifications of the cables for the sub−base CPX−AB−4−HAR−4POL

� Cable cross−sectional area: 0.25 � 0.5 mm2

� Strand cross−section: up to 0.1 mm

� Insulation material: PVC/PUR/PE

� Insulation thickness: max. 1.6 mm

� Core diameter: 1.2 � 1.6 mm

� Cable outer diameter: 4.0 � 5.1 mm

Page 39:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−19Festo P.BE−CPX−AX−EN en 0811d

Assembly

1 Cut the cable tolength, remove thecoating. Push theunion nut and theseal insert onto theend of the cable.

2 Insert the ends of thecore into the ap�propriate slots of thesplicing ring.

3 Place the seal andthe splicing ring to�gether and cut off theprojecting core endsflush with the splicingring.

4 Insert the pre−fittedsplicing seal elementinto the contact sup�port in the sub−base.Screw in the unionnut as far as possible.

1

2

4

3

1

2

4

3

Fig.�1/6: Connect the cable to sub−base CPX−AB−4−HAR−4POL

Dismantling

· Loosen the screw connector and remove the cores bypulling them out of the contacts.

The cores can be connected up to 10 times if the contactends are cut away each time (if the same core diameter isused). Cut off the used cable ends and repeat steps 2 to 4.

Page 40:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−20 Festo P.BE−CPX−AX−EN en 0811d

1.3 Assembly

WarningSudden unexpected movement of the connected actuatorsand�uncontrolled movements of loose tubing can causeinjury to human beings or damage to property.

Switch off the following equipment before undertakinginstallation and/or maintenance work:

� Compressed air supply

� Operating and load voltage supplies

CautionInappropriate handling can result in damage to themodules.

· Do not touch the electrical contacts of the modules.

· Observe the handling instructions for electrostaticallysensitive components.

· Discharge yourself before installing or removingsub−assemblies to protect the sub−assemblies fromstatic discharges.

Before the CPX terminal can be extended or converted, itmust first be unscrewed and dismantled. Instructions on thiscan be found in the CPX system manual.

The CPX terminal does not need to be dismantled when sub−bases or electronic modules are fitted or removed. This alsoapplies to the plugs and cables on the sub−base.

Page 41:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−21Festo P.BE−CPX−AX−EN en 0811d

1.3.1 Fitting the sub−bases

NoteHandle all modules and components of the CPX terminalwith great care. Please note especially the followingpoints:

· Screws must be fitted accurately (otherwise threads willbe damaged).Screws must be fastened at first only by hand. Screwsmust be placed so that the self−cutting threads can beused.

· The specified torques must be observed.

· Screw connections must be fitted free of offset andmechanical tension.

· Check the seals for damage (IP65/IP67).

· Connecting surfaces must be clean (to ensure sealingeffect, avoid leakage and contact faults).

The screw connection between the sub−base and the mani�fold sub−base is designed to withstand at least 10 fitting/removal cycles under observance of the instructions.

Observe also the installation instructions supplied withmodules and components ordered at a later stage.

CPX terminals are supplied from the factory completely fitted.It may be necessary to fit or remove the sub−bases for thefollowing reasons:

� for replacing the connections

� to simplify fitting the sensor plugs or cables.

It may be necessary to fit or remove the electronic modulesfor the following reasons:

� for modifying the function of the I/O module (e.g. CPX−2AE−U−I instead of CPX−2AA−U−I).

� for replacing defective electronic modules.

Page 42:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−22 Festo P.BE−CPX−AX−EN en 0811d

Dismantling Dismantle the sub−base as follows (see Fig.�1/7):

1. Loosen the 4 screws in the relevant sub−base with a TORXscrewdriver size T10.

2. Pull the sub−base carefully and without tilting away fromthe electrical plug connection of the electronic module.

Only in cases where the electronic module is to be removed:

· Pull the electronic module carefully and without tiltingaway from the contact rails of the manifold sub−base.

1 Sub−base

2 Screws

3 Electrical plugconnector

4 Electronicsmodule

5 Contact rails

6 Manifold base

1

2

3

4

5

6

Fig.�1/7: Fitting/removing the I/O module

Page 43:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−23Festo P.BE−CPX−AX−EN en 0811d

Fitting Fit the modules as follows (see Fig.�1/7):

Note· Please observe the instructions on combining I/Omodules and sub−bases in section 1.2.2.

· Please observe the instructions on combining andarranging modules on the CPX terminal in the CPXsystem manual.

Only in cases where the electronic module has beenremoved:

· Place the electronic module in the manifold sub−base.Make sure that the grooves with the contact terminals onthe bottom of the electronic module lie above the contactrails. Then push the electronic module carefully and with�out tilting as far as possible into the manifold sub−base.

Fitting the sub−base:

1. Align the sub−base over the manifold sub−base with theelectronic module. Make sure that the plug connectors ofthe sub−base are aligned exactly with the connectors ofthe electronic module. Then push the sub−base carefullyand without tilting onto the manifold sub−base.

2. Tighten the screws at first only by hand. Place the screwsso that the self−cutting threads can be used.Tighten the screws with a TORX screwdriver size T10 withtorque 0.9 � 1.1 Nm.

Page 44:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−24 Festo P.BE−CPX−AX−EN en 0811d

1.3.2 Fitting the screening/shield plates

A screening/shield plate type CPX−AB−S−4−12 can be fitted on sub−base CPX−AB−4−M12x5−5POL. The sub−base must beremoved before the screening/shield plate is fitted ordismantled.

Fitting Fit the screening plate as follows (see Fig.�1/8):

1. Dismantle the sub−base (see section 1.3.1).

2. Snap the spring clips of the screening/shield plate fromabove into the appropriate recesses on the dismantledsub−base.

3. Fit the sub−base.

Instructions on earthing the screening/shield plate can befound in section 1.2.3.

Dismantling The screening/shield plate must be removed in the oppositesequence to the fitting procedure.

Page 45:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−25Festo P.BE−CPX−AX−EN en 0811d

1 Spring contact

2 Screening plate

3 Spring clip

4 Sub−base typeCPX−AB−4−M12x2−5POL

5 CPX Terminal

1

2

3

4

5

Fig.�1/8: Fitting screening/shield plate type CPX−AB−S−4−12

Page 46:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

1. Overview and connection technology I/O modules

1−26 Festo P.BE−CPX−AX−EN en 0811d

Page 47:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Analogue input module CPX−2AE−U−I

2−1Festo P.BE−CPX−AX−EN en 0811d

Chapter 2

Page 48:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−2 Festo P.BE−CPX−AX−EN en 0811d

Contents

2. Analogue input module CPX−2AE−U−I 2−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.1 Function of the analogue input modules 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.2 Fitting 2−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3 Installation 2−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.1 DIL switch settings 2−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.2 Pin assignment 2−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.3.3 Connecting the analogue intputs 2−11 . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4 Instructions on commissioning 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.1 Processing analogue input signals 2−12 . . . . . . . . . . . . . . . . . . . . . . . . . .

2.4.2 General information on parametrizing 2−16 . . . . . . . . . . . . . . . . . . . . . . .

2.4.3 Parameters of the analogue input module type CPX−2AE−U−I 2−18 . . . . .

2.4.4 Module parameter �Input analogue−value data format" 2−26 . . . . . . . .

2.4.5 Channel−specific module parameters � Limits 2−28 . . . . . . . . . . . . . . . . .

2.4.6 Channel−specific module parameters � Filter measured value 2−31 . . . .

2.4.7 Channel−specific module parameters � Monitor of wire fracture 2−31 . .

2.5 Diagnosis 2−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.1 Fault messages of the analogue input modules 2−33 . . . . . . . . . . . . . . .

2.5.2 LED display 2−35 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

2.5.3 Fault treatment and parametrizing 2−37 . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 49:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−3Festo P.BE−CPX−AX−EN en 0811d

Contents of this chapter This chapter describes the analogue input module CPX−2AE−U−I.

Analogue input modules provide analogue voltage inputs orcurrent inputs in a CPX terminal and can be adapted to spe�cific applications by means of different sub−bases.

Further information An overview of the modular structure of a CPX terminal, themodular connections as well as the display and connectingelements can be found in chapter 1.

Information on mounting the complete CPX terminal,connecting the power supply as well as general instructionson configuration and parametrizing can be found in the CPXsystem manual.

Information on the address assignment as well as on com�missioning can be found in the appropriate field bus nodemanual or function module manual.

Page 50:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−4 Festo P.BE−CPX−AX−EN en 0811d

2.1 Function of the analogue input modules

Analogue input modules provide analogue voltage inputs orcurrent inputs for connecting sensors and enable the regis�tering and processing of analogue current and voltage sig�nals. At present the following type is available:

Type Description

CPX−2AE−U−I This type provides 2 analogueinputs (input channels) withscalable value ranges. The inputsignal range can be configuredchannel by channel, eitherelectrically isolated or non−floating:� 0 � 10 V� 0 � 20 mA� 4 � 20 mASensor supply 24 V / 0.7 A permodule.

Tab.�2/1: Overview of analogue input modules 2AE−U−I

2.2 Fitting

See section 1.3.

Page 51:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−5Festo P.BE−CPX−AX−EN en 0811d

2.3 Installation

WarningUndesired movement of the connected actuators anduncontrolled movements of loose tubing can cause injuryto human beings or damage to property.

Before carrying out installation and maintenance work,switch off the following:

� the compressed air supply

� the operating and load voltage supplies.

In the following sections you will find the pin assignments of

the analogue input modules for the different sub−bases.

Instructions on connecting the cables and plugs to the sub−bases can be found in section 1.2.3.Note in particular the instructions on connecting the cablescreening to functional earth (FE).

Power supply

The 24 V sensor supply for the inputs as well as the powersupply for the electronics of the input modules is providedvia the operating voltage supply for the electronics/sensors(VEL/SEN).

The sensors can also be supplied externally (electrical isola�tion, see section 2.3.3, Fig.�2/2).

Page 52:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−6 Festo P.BE−CPX−AX−EN en 0811d

2.3.1 DIL switch settings

2 DIL switches are available for configuring the analogueinput modules. These are located on the top of the electronicmodule.

1 DIL switch 0: Signal range ofanalogue input 0

2 DIL switch 1: Signal range ofanalogue input 1

2AI

1 2

ON 1

21 2

ON

Fig.�2/1: DIL switches in the electronic module (further information on 1 and 2 see following pages)

Proceed as follows:

1. Switch off the power supply.

2. Remove if necessary the fitted sub−base (see �Fitting"section 1.3).

3. Set the DIL switch elements in accordance with theinstructions on the following pages.

4. Refit if necessary the sub−base (see �Fitting" section 1.3,tightening torque 0.9 � 1.1�Nm).

Page 53:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−7Festo P.BE−CPX−AX−EN en 0811d

Setting the input signal range

You can set the signal range of the relevant analogue inputwith the 2−element DIL switches 0 and 1.

Signal Setting the DIL switches 1)

range Setting DIL switch 0 DIL switch 1

0 � 10 V 0.1: OFF 2)

0.2: OFF 2)1.1: OFF 2)

1.2: OFF 2)

0.1: ON0.2: OFF

1.1: ON1.2: OFF

0 � 20 mA 0.1: OFF0.2: ON

1.1: OFF1.2: ON

4 � 20 mA 0.1: ON0.2: ON

1.1: ON1.2: ON

1) DIL switch 0 for input channel 0DIL switch 1 for input channel 1

2) Default (factory setting)

Tab.�2/2: DIL switches of the analogue input module2AE−U−I

Please noteThe setting of the signal range with the DIL switches canbe modified by parametrizing (see section 2.4). Parame�trizing has precedence over the DIL switch setting.

Page 54:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−8 Festo P.BE−CPX−AX−EN en 0811d

2.3.2 Pin assignment

Pin assignment of CPX−2AE−U−I with sub−baseCPX−AB−4−M12x2−5POL(−R)

Analogue input module type CPX−2AE−U−I with sub−base CPX−AB−4−M12x2−5POL(−R)

Sub−base Pin assignment X1, X2 (input I...0) Pin assignment X3, X4 (input I...1)

Voltage inputs 1)

2AI

2

3

1

5

4

X1

Socket X1:1: 24 VSEN2: IU0+3: 0 VSEN4: IU0−5: FE (screening) 2)

2

3

1

5

4

X3

Socket X3:1: 24 VSEN2: IU1+3: 0 VSEN4: IU1−5: FE (screening) 2)

Current inputs 1)

2

3

1

5

4

X2Socket X2:1: 24 VSEN2: II0+3: 0 VSEN4: II0−5: FE (screening) 2)

2

3

1

5

4

X4Socket X4:1: 24 VSEN2: II1+3: 0 VSEN4: II1−5: FE (screening) 2)

IUx+ = Positive voltage input signalIUx− = Negative voltage input signalIIx+ = Positive current input signalIIx− = Negative current input signalFE = Functional earth

1) Assignment depends on the DIL switch setting and on parametrizing (see section 2.3.1), a total of 2 input channels are available per module (I...0 and I...1, connection X1 or X2 as well as connection X3 or X4).

2) With CPX−AB−4−M12x2−5POL−R the metal thread is connected to FE

Tab.�2/3: Pin assignment of analogue input module type CPX−2AE−U−I with sub−baseCPX−AB−4−M12x2−5POL(−R)

CPX−AB−4−M12x2−5POL−R The metal thread (�...−R") of this sub−base is connectedinternally with pin 5 (Functional earth FE).

Page 55:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−9Festo P.BE−CPX−AX−EN en 0811d

Pin assignment of CPX−2AE−U−I with sub−baseCPX−AB−8−KL−4POL

Analogue input module type CPX−2AE−U−I with sub−base CPX−AB−8−KL−4POL

Sub−base Pin assignment X1 � X4 (input I...0)

Pin assignment X5 � X8 (input I...1)

Voltage inputs 1)

2AI

X1

X2

X3

X5

X6

X7

.0

.1

.2

.3

.0

.1

.2

.3

.0

.1

.2

.3

X1

X2

.0

.1

.2

.3

.0

.1

.2

.3

X1.0: 24 VSENX1.1: 0 VSENX1.2: IU0−X1.3: FE (screening)

X2.0: n.c.X2.1: n.c.X2.2: IU0+X2.3: FE (screening)

X5

X6

.0

.1

.2

.3

.0

.1

.2

.3

X5.0: 24 VSENX5.1: 0 VSENX5.2: IU1−X5.3: FE (screening)

X6.0: n.c.X6.1: n.c.X6.2: IU1+X6.3: FE (screening)

X4 X8

.3

.0

.1

.23

Current inputs 1)

X4 X8.2.3

X3

X4

.0

.1

.2

.3

.0

.1

.2

.3

X3.0: 24 VSENX3.1: 0 VSENX3.2: II0−X3.3: FE (screening)

X4.0: n.c.X4.1: n.c.X4.2: II0+X4.3: FE (screening)

X7

X8

.0

.1

.2

.3

.0

.1

.2

.3

X7.0: 24 VSENX7.1: 0 VSENX7.2: II1−X7.3: FE (screening)

X8.0: n.c.X8.1: n.c.X8.2: II1+X8.3: FE (screening)

IUx+ = Positive voltage input signalIUx− = Negative voltage input signalIIx+ = Positive current input signalIIx− = Negative current input signaln.c. = Not connectedFE = Functional earth

1) Assignment depends on the DIL switch setting and on parametrizing (see section 2.3.1), a total of 2 input channels are available per module (I...0 and I...1, connection X1/X2 or X3/X4 as well as connection X5/X6 or X7/X8).

Tab.�2/4: Pin assignment of analogue input module type CPX−2AE−U−I with sub−baseCPX−AB−8−KL−4POL

Page 56:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−10 Festo P.BE−CPX−AX−EN en 0811d

Pin assignment of CPX−2AE−U−I with sub−baseCPX−AB−1−SUB−BU−25POL

Analogue input module type CPX−2AE−U−I with sub−base CPX−AB−1−SUB−BU−25POL

Sub−base Pin assignment 1)

2AI

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

1: IU0−2: IU0+3: II0−4: II0+5: n.c.6: n.c.7: n.c.8: n.c.9: 24 VSEN10: 24 VSEN11: 0 VSEN12: 0 VSEN13: FE

14: IU1−15: IU1+16: II1−17: II1+18: 24 VSEN19: n.c.20: 24 VSEN21: n.c.22: 0 VSEN23: 0 VSEN24: 0 VSEN25: FEHousing: FE (screening)

Pin 1/2, 14/15 = Voltage inputsPin 3/4, 16/17 = Current inputsIUx+ = Positive voltage input signalIUx− = Negative voltage input signalIIx+ = Positive current input signalIIx− = Negative current input signaln.c. = Not connectedFE = Functional earth

1) Assignment depends on the DIL switch setting and on parametrizing (see section 2.3.1), a total of 2 input channels are available per module (I...0 and I...1)

Tab.�2/5: Pin assignment of analogue input module type CPX−2AE−U−I with sub−baseCPX−AB−1−SUB−BU−25POL

Page 57:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−11Festo P.BE−CPX−AX−EN en 0811d

2.3.3 Connecting the analogue intputs

Only screened cables are usually permitted for the trans�mission of analogue signals (see section 1.2.3).

1 Without electricalisolation: The sensors are supplied via the CPX module

2 With electrical isolation: If an external sensorsupply is used

0...20

mA

0...10

V

0...10

V

0/�4...20

mA

External

sensor

supply

4...20

mA

24�VIUx+ IUx− FE0�V 24�VIIx+ IIx− FE0�V

24�VIUx+ IUx− FE0��V 24�VIIx+ IIx− FE0�V

24�VIIx+ IIx− FE0�V

1

2

Fig.�2/2: Examples of analogue input connections (screening connection on FE pin)

Please noteMake sure that cables which are not used, but which areconnected to the sub−base, are short−circuited by voltageinputs at the unused end of the cable.

Further connection examples can be found in appendix A.8.1.

Page 58:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−12 Festo P.BE−CPX−AX−EN en 0811d

2.4 Instructions on commissioning

2.4.1 Processing analogue input signals

The analogue values are transmitted from the CPX terminal tothe control system as input words (2 bytes, 16 bits). Eachanalogue input module occupies 2 input words for this pro�cedure in the address range.

The position of the input words in the address range dependson the field bus used (see manual for the field bus node).

Parametrizing The data format as well as the limit values and, where appli�cable, also the scaling of the analogue input signals can beadapted by parametrizing. Instructions on this can be foundin the sections 2.4.2 and 2.4.3.

The reaction with the default settings is described below.

Page 59:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−13Festo P.BE−CPX−AX−EN en 0811d

Reaction with the default settings

The module parameter �Input analogue−value data format"possesses the default setting �VZ + 12 bits right−justified"(compatible with valve terminal type 03). With this setting theanalogue values will be saved in the input word as follows:

Data format �VZ + 12 bits right−justified" (compatible with valve terminal type 03)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ 0 0 0 B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

Abbreviations used:VZ: Sign (with data format �VZ + 12 bits right−justified" always = 0, i.e. a positive value)B0 � B11: Input valueD0 � D15: 16 bits input data field MSB/LSB: Most significant bit / least significant bit

Tab.�2/6: Data format �VZ + 12 bits right−justified"

The channel−specific parameters �Lower limit" and �Upperlimit" possess the following default settings:

� Lower limit = 0

� Upper limit = 4095

These correspond to the scaling end values (data range) ofthe default data format.

Page 60:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−14 Festo P.BE−CPX−AX−EN en 0811d

The following diagram shows the processing of the analogueinput signals with the default data format �VZ + 12 bitsright−justified". The example shows a sensor which convertsthe range of the physical measuring variables from 0 � 6 barlinear into the analogue signals 0 � 10 V, 0 � 20 mA or4���20�mA.

1 Lower limit of ratedrange

2 Measured value(example)

3 Upper limit of ratedrange

4 Physical measuringvariables

5 Assigned analoguesignal

6 Digital value rangeafter A−D conversion(linear scaling)

7 Digital input value(example)

1 3

0 V0 mA4 mA

0 4095

10 V20 mA20 mA

0 6 bar3.5 bar

2

4

5

6

5.833 V11.66 mA9.33 mA

7

2389

Fig.�2/3: Example of default data format �VZ + 12 bits right−justified"

Page 61:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−15Festo P.BE−CPX−AX−EN en 0811d

The assignment of analogue input signal ranges to the digitalvalue range is shown in the table below.

Analogue input signal range Digital data preparation

0 � 10 V 0 � 20 mA 4 � 20 mA Ranges Digital values

�> 9.9975 V > 19.995 mA > 19.995 mA Rated range exceeded

Limiting to the upperscaling end value

4095

9.9975 V 19.995 mA 19.995 mA Upper limit 4095

... ... ... Rated range

i l

1 � 4094

0 V 0 mA 4 mA Lower limit ofrated range

Linear value range0

< 0 V < 0 mA < 4 mA Less than ratedrange

Limiting to the lowerscaling end value

0

Tab.�2/7: Scaling end values of the analogue input modules with default settings

Page 62:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−16 Festo P.BE−CPX−AX−EN en 0811d

2.4.2 General information on parametrizing

The reaction of the analogue input modules can beparametrized.

Further information on parametrizing can be found in thesystem manual or in the manual for the field bus node.

Due in some cases to necessary calculations, modified para�meters are not valid until they have been thoroughly checkedand saved. Until then, as in the case of invalid parameters,the previous settings apply.

Depending on the parameter, no valid analogue values areavailable for up to max. 30 ms after a value modification.

Special instructions on avoiding parametrizingfaults

In order to avoid parametrizing faults, note the sequencedescribed below when modifying the following parameters:

� Input analogue−value data format

� Lower limit channel x

� Upper limit channel x

Page 63:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−17Festo P.BE−CPX−AX−EN en 0811d

Sequence for first or startup parametrizing (CPX terminal indelivery status, monitoring of parametrizing faults active):

1. First set the desired data format (parameter �Inputanalogue−value data format").

2. Then set the upper and lower limits for both channels:

� If the new upper limit value is positive, set first theupper limit; then the lower limit.

� If the new upper limit is negative (only in the case ofdata format �VZ + 15 bits linear scaled"), set first thelower limit, then the upper limit.

Sequence for modifying the parametrizing:

1. Activate, if applicable, the monitoring of parametrizingfaults (module parameter �Monitoring CPX module �monitoring parametrizing faults" and channel−specificmodule parameter �Monitoring channel x � monitoringparametrizing faults").

2. Set the lower limit to 0 and the upper limit to 4095 forboth channels.

3. Then set the desired data format (parameter �Inputanalogue−value data format").

4. If required, then set the upper and lower limits for bothchannels:

� If the new upper limit value is positive, set first theupper limit; then the lower limit.

� If the new upper limit is negative (only in the case ofdata format �VZ + 15 bits linear scaled"), set first thelower limit, then the upper limit.

Page 64:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−18 Festo P.BE−CPX−AX−EN en 0811d

2.4.3 Parameters of the analogue input module type CPX−2AE−U−I

The tables below give an overview of the module parametersof the analogue input modules.

Function number 1) Module parameters

4828 + m * 64 + 0 Monitoring the CPX module

4828 + m * 64 + 1 Behaviour after short circuit/overload

4828 + m * 64 + 2 Reserved

4828 + m * 64 + 3 Input analogue−value data format

1) m = module number (counting from left to right, beginning with 0)

Tab.�2/8: Overview � module parameters

Function number 1) Channel−specific module parameters

4828 + m * 64 + 6/7 Monitoring channel 0, 1

4828 + m * 64 + 8 Signal range channel 0, 1

4828 + m * 64 + 9 Filter measured value channel 0, 1

4828 + m * 64 + 10/11 Lower limit channel 0

4828 + m * 64 + 12/13 Lower limit channel 1

4828 + m * 64 + 14/15 Upper limit channel 0

4828 + m * 64 + 16/17 Upper limit channel 1

� 2) Force channel x (see also CPX system manual)

1) m = module number (counting from left to right, beginning with 0)2) Access is protocol−specific (see manual for field bus node)

Tab.�2/9: Overview � channel−specific module parameters

Page 65:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−19Festo P.BE−CPX−AX−EN en 0811d

Description of the parameters

Module parameters: Monitoring the CPX module

Function no. 4828 + m * 64 + 0 m = module number (0 � 47)

Description With the analogue input modules, monitoring of individual faults can be acti�vated or deactivated (suppressed) independently of each other. Active monitor�ing causes the following: The fault is:� sent to the CPX field bus node� displayed by the module common error LED.

Bit Bit 0: monitoring short circuit/overload in the sensor supplyBit 1 � 6: reservedBit 7: monitoring parametrizing faults

Values 1 = active (presetting); 0 = inactive

Remark � Monitoring short circuit at sensors:Monitoring can also be set for the complete CPX terminal (see CPX systemmanual, system parameter �Monitoring").

� Monitoring parametrizing faults:Some parameters are checked for non−permitted values during parametrizing:� Data format� Filter measured value� Lower limit� Upper limitThe setting of the module parameter �Monitoring parametrizing faults" is onlyeffective for channel−specific parametrizings if the corresponding channelparameter �Monitoring parametrizing faults" is set to �active".

Tab.�2/10: Monitoring the CPX module

Page 66:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−20 Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Behaviour after short circuit/overload

Function no. 4828 + m * 64 + 1 m = module number (0 � 47)

Description Determines after a short circuit in the sensor supply whether the power is toremain switched off or whether it is to be switched on again automatically.

Bit Bit 0: behaviour after short circuit/overload in the sensor supply

Values 0 = leave voltage/current switched off1 = switch voltage on again (presetting)Bit 2 � 7: reserved

Remark With the setting �Leave voltage switched off", Power off/on is necessary forswitching the power on again. Ascertain the setting which is necessary for reliable operation of your machine or system. Further information can be foundin section 2.5.1.

Tab.�2/11: Behaviour after short circuit/overload

Module parameters: Input analogue−value data format

Function no. 4828 + m * 64 + 3 m = module number (0 � 47)

Description Determines the format in which the analogue input signals are provided by theCPX terminal.

Bit Bit 0, 1: input analogue−value data formatBit 2 � 7: reserved (= 0)

Values Bit 1 Bit 00 0 VZ + 15 bits linear scaled0 1 VZ + 12 bits right−justified (compatible with valve terminal

type 03, presetting)1 0 VZ + 15 bits left−justified (Simatic S7)1 1 VZ + 12 bits left−justified + diagnosis (Simatic S5)

(VZ = sign)

Remark The reserved bits 2 � 7 must always be 0. If one or several bits are set to �1"during parametrizing, the parametrizing carried out is invalid and therefore noteffective. If the module parameter �Monitoring parametrizing faults" is set to�active", the relevant fault will be displayed.Further information on this parameter can be found in section 2.4.4.

Tab.�2/12: Input analogue−value data format

Page 67:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−21Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Monitoring channel x

Function no. 4828 + m * 64 + 6 (channel 0) m = module number (0 � 47)4828 + m * 64 + 7 (channel 1)

Description For the individual channels of the analogue input modules, monitoring of indi�vidual faults can be activated or deactivated (suppressed) independently of eachother. Active monitoring causes the following: The fault is:� sent to the CPX field bus node� displayed by the module common error LED.Further infomation on these monitorings can be found under the description ofthe relevant fault in section 2.5.1.

Bit Bit 0: monitoring lower limit (or less than rated range)Bit 1: monitoring upper limit (or rated range exceeded)Bit 2: monitoring wire fractureBit 3 � 6: reservedBit 7: monitoring parametrizing faults

Values 1 = active; 0 = inactivePresetting bit 0 � 2: 0 (inactive)Presetting bit 7: 1 (active)

Remark � Monitoring the upper/lower limit:Monitoring the input signals for less than or exceeding the rated range ormonitoring the range limits defined with the parameters �Lower limit ..." aswell as �Upper limit ..." (depending on the data format used, see sections2.4.4 and 2.4.5).

� Monitoring wire fracture:Only effective for the signal range 4 � 20 mA. A drop below the minimuminput current (IIN�< 2.0�mA) counts as a wire fracture.

� Monitoring parametrizing faults:Some channel−specific parameters are checked for non−permitted values during parametrizing: � Filter measured value� Lower limit� Upper limitThe setting of the channel parameter �Monitoring parametrizing faults" is onlyeffective if the module parameter �Monitoring parametrizing faults" is set to�active".

Tab.�2/13: Monitoring channel x

Page 68:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−22 Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Signal range channel x

Function no. 4828 + m * 64 + 8 m = module number (0 � 47)

Description For the individual channels of the analogue input modules, the signal ranges ofthe analogue inputs can be set independently of each other.

Bit Bit 0/1: setting of DIL switch 0 for channel 0 (read only)switch 0.1 = bit 0switch 0.2 = bit 1

Bit 2/3: signal range channel 0 (AI0)Bit 4/5: setting of DIL switch 1 for channel 1 (read only)

switch 1.1 = bit 4switch 1.2 = bit 5

Bit 6/7: signal range channel 1 (AI1)

Values Channel 0 Channel 1Bit 3 Bit 2 Bit 7 Bit 60 0 0 0 Using the setting of the DIL switches (presetting)0 1 0 1 0 � 10 V1 0 1 0 0 � 20 mA1 1 1 1 4 � 20 mA

Remark Bits 0/1 as well as 4/5 represent the status of the DIL switches for setting thesignal range.With bits 2/3 and 6/7 other signal ranges can be parametrized irrespective ofthe DIL switch setting.Modified parameter settings have precedence over the DIL switch settings. The setting of the DIL switches is carried out with the presetting (bit 2/3 = 0; bit 6/7 = 0).

Tab.�2/14: Signal range channel x

Page 69:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−23Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Filter measured value channel x

Function no. 4828 + m * 64 + 9 m = module number (0 � 47)

Description For the individual channels of the analogue input modules, the filter formeasured values can be set independently of each other.

Bit Bit 0, 1: filter measured value channel 0Bit 2, 3: reserved (= 0)Bit 4, 5: filter measured value channel 1Bit 6, 7: reserved (= 0)

Values Channel 0 Channel 1Bit 1 Bit 0 Bit 5 Bit 40 0 0 0 No filter measured value (presetting)0 1 0 1 Filter measured value over 2 values1 0 1 0 Filter measured value over 4 values1 1 1 1 Filter measured value over 8 values

Remark Faults can be suppressed with the Filter measured value (see section 2.5.1).The reserved bits 2, 3 and 6, 7 must always be 0. If these bits are set to �1" during parametrizing, the parametrizing carried out is invalid and therefore noteffective.If the module parameter �Monitoring parametrizing faults" as well as the relevant channel parameter �Monitoring parametrizing faults" is set to �active",the relevant fault will be displayed.

Tab.�2/15: Filter measured value channel x

Page 70:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−24 Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Lower limit channel x / Upper limit channel x

Function no. Lower limit: m = module number (0 � 47)4828 + m * 64 + 10 (channel 0, low byte)4828 + m * 64 + 11 (channel 0, high byte)4828 + m * 64 + 12 (channel 1, low byte)4828 + m * 64 + 13 (channel 1, high byte)

Upper limit:4828 + m * 64 + 14 (channel 0, low byte)4828 + m * 64 + 15 (channel 0, high byte)4828 + m * 64 + 16 (channel 1, low byte)4828 + m * 64 + 17 (channel 1, high byte)

Description A lower as well as an upper limit value can be set for the individual channels ofthe analogue input modules (see section 2.4.5).With data format �VZ + 15 bits linear scaled", the limits have the function ofscaling end values.

Bit Bit 0 � 7: high byte or low byte of the limit value

Values Presettings:� Lower limit = 0 (low byte = 0; high byte: 0)� Upper limit = 4095 (low byte = 255; high byte: 15)Low byte: 0 � 255High byte: 0 � 15

Remark If the input value is less than the parametrized lower limit or exceeds theparametrized upper limit, an appropriate fault is displayed (providing the relevant channel parameter �Monitoring channel x � monitoring lower limit" or�Monitoring channel x � monitoring upper limit" is active).The upper limit must always be more than the lower limit.Modifications to the limits must be made in steps of 16 bits.

Permitted limits:The limits are checked for validity during parametrizing. Invalid parametrizingsare not accepted � the module uses the previous (last valid) parametrizings. The permitted values depend on the parametrized data format (see section2.4.5). If the module parameter �Monitoring parametrizing faults" as well as therelevant channel parameter �Monitoring parametrizing faults" is set to �active", the relevant fault will be displayed.

Tab.�2/16: Lower and upper limits channel x

Page 71:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−25Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Force channel x

Function no. Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).

Description The Force function permits the manipulation of analogue values irrespective ofthe actual input value (see also CPX system manual). This can be accomplishedwith the following parameters:� Force mode inputs channel x� Force state inputs channel x

Values � Force mode inputs channel x 0 = blocked (presetting)1 = Force state

� Force state inputs channel x 0 = reset value (presetting)1 = set value

Remark The enabling of the Force function with the parameter �Force mode outputschannel x" depends on the field bus protocol and is accomplished:� by an individual parameter setting or bit (e.g. CPX−FB11),� by setting all parameter bits of the relevant word (e.g. CPX−FB6) to �blocked"

or �Force state".For parametrizing the Force state, the desired input word must be correspon�dingly mapped in the parameter bits �Force state inputs channel x".The enabling of the Force function for the complete CPX terminal is made bymeans of the system parameter �Force mode" (see CPX system manual).

Tab.�2/17: Force channel x (channel−specific)

Page 72:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−26 Festo P.BE−CPX−AX−EN en 0811d

2.4.4 Module parameter �Input analogue−value data format"

The parametrized data format determines how the analoguevalues are transferred by the CPX terminal to the control sys�tem. The setting applies to all analogue input channels. Irre�spective of the data format the data width is always 16�bits(2�bytes, 1�word).

Supported data formats of the analogue input modules

VZ + 15 bits linear scaled

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B14MSB

B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

VZ + 12 bits right−justified (compatible with valve terminal type 03, presetting)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ 0 0 0 B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

VZ + 15 bits left−justified (compatible with Simatic S7)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

x x x

VZ + 12 bits left−justified + diagnosis (compatible with Simatic S5)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

0 F 0

Abbreviations used:VZ: Sign (0 = positive value, 1 = negative value)B0 � B14: Input valueD0 � D15: 16 bits input data fieldMSB/LSB: Most significant bit / least significant bitF: Wire fracture monitoring with signal range 4 � 20 mA: F = 1 wire fracture exists

F = 0 no wire fracture existsx: Not relevant

Tab.�2/18: Supported data formats of the analogue input modules

Page 73:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−27Festo P.BE−CPX−AX−EN en 0811d

Data format �VZ + 15 bits linear scaled"

The 12−bit digital values, which exist after the A−D conversionof the analogue input signals, are linearly scaled to the datarange defined by the scaling end values (limit values) andoutput in the input word (see section 2.4.5, Fig.�2/5).

Data format �VZ + 12 bits right−justified"

The 12−bit digital values, which exist after the A−D conversionof the analogue input signals, are output unmodified in theinput word (see also example in section 2.4.1, Fig.�2/3).

Data format �VZ + 15 bits left−justified" anddata format �VZ + 12 bits left−justified + diagnosis"

The 12−bit digital values, which exist after the A−D conversionof the analogue input signals, plus the preceding sign bit arearranged left−justified in the data format. The three zeros atthe end cause the output data word to correspond to the12−bit digital value after A−D conversion multiplied by 8(providing there is no wire fracture diagnosis).

The following diagram shows an example of the data format�VZ + 15 bits left−justified":

1 Analogue inputvalues

2 Digital signals afterA−D conversion

3 Available digitalsignals scaled to theend value of the datarange

1

2

332760

0 4095

0

0 V0 mA4 mA

10 V20 mA20 mA

Fig.�2/4: Example of data format �VZ + 15 bits left−justified"

Page 74:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−28 Festo P.BE−CPX−AX−EN en 0811d

2.4.5 Channel−specific module parameters � Limits

You can determine limits with the channel−specific para�meters �Lower limit" and �Upper limit". The meaning of thelimit parameters depends on the parametrized data format ofthe module.

With data format �VZ + 15 bits linear scaled", the limits havethe function of defining the scaling end values of the datarange. This results in an additional scaling of the analoguevalues. If the input data lie outside this data range, a diagnosticmessage can be generated with appropriate parametrizing.

With other data formats the data range is already defined bythe scaling end values. In this case, the limits permit datamonitoring even within the data range.

Data format 1) Data range Limits/scaling end values 2)

VZ + 15 bits linear scaled

−30000 � +30000 Lower scaling end value:−30000 � +29999

Upper scaling end value:−29999 � +30000

VZ + 12 bits right−justified

0 � 4095 Lower limit:0 � 4094

Upper limit:1 � 4095

VZ + 15 bits left−justified

0 � 32760 Lower limit:0 � 32759

Upper limit:1 � 32760

VZ + 12 bits left−justified + diagnosis 3)

0 � 32760 Lower limit:0 � 32752

Upper limit:1 � 32760

1) VZ = SignAs the analogue inputs with the �Fixed value" data formats �VZ + 12 bits right−justified", �VZ + 15 bits left−justified" and �VZ + 12 bits left−justified + diagnosis" generate only positive signals, the sign bit with these formats is always 0.

2) The lower limit/scaling end value must always be less than the upper limit/scaling end value.3) If the max. voltage or current values are exceeded, values greater than 4095 will also be output.

Tab.�2/19: Limits or scaling end values of the analogue input modules

Page 75:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−29Festo P.BE−CPX−AX−EN en 0811d

Scaling end values with data format �VZ + 15 bitslinear scaled"

The following diagram shows an example of the data format�VZ + 15 bits linear scaled" with the scaling end values:

� Lower limit = 0

� Upper limit = 6000

The example shows a sensor which converts the range of thephysical measuring variables from 0 � 6 bar linear into theanalogue signals 0 � 10 V or 0 � 20 mA.

1 Physical measuringvariables

2 Digital signals afterA−D conversion (resolution: 12 bits)

3 Available digitalsignals after scalingby the scaling endvalues

1

2

3

0

6000

0 4095

0

6 bar

Fig.�2/5: Example scaling data format �VZ + 15 bits linear scaled"

The scaling end values in this data format are identical withthe limits for less than or exceeding the rated range:

1 Digital input signalafter scaling

2 Limits

3 Less than orexceeding the limits

12

3

0 6.000

2

Fig.�2/6: Limit monitoring with data format �VZ + 15 bits linear scaled"

Page 76:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−30 Festo P.BE−CPX−AX−EN en 0811d

Limits with the �Fixed value" data formats

The following diagram shows an example of the data format�VZ + 12 bits right−justified" with the scaling end values:

� Lower limit = 500

� Upper limit = 3500

The principle of the limits also applies to the data formats�VZ + 15 bits left−justified" and �VZ + 12 bits left−justified +diagnosis".

1 End values of thedata range

2 Lower limit

3 Upper limit

4 Less than orexceeding the limits

1 2 3

40950 500 3500

4

1

Fig.�2/7: Monitoring of limits with the �Fixed value" data formats

Page 77:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−31Festo P.BE−CPX−AX−EN en 0811d

2.4.6 Channel−specific module parameters � Filter measured value

In order to suppress faults, the input data can be filtered digi�tally, whereby the degree of filtering can be set by means ofparametrizing.

Filtering is carried out as follows:

� by forming the sum of n values,

� by subtracting an average value,

� by adding the current input value.

The following applies here: the greater n, the more the signalwill be filtered.

2.4.7 Channel−specific module parameters � Monitor of wire fracture

A wire fracture monitoring (open load) can be activated withappropriate parametrizing for the signal range 4 � 20 mA.

The criterion for a wire fracture is software monitoring toensure that the value does not drop below the lower limit(IIN�� 2.0 mA). If the value drops below the lower limit, themodule will send an appropriate fault message to the fieldbus node.

Page 78:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−32 Festo P.BE−CPX−AX−EN en 0811d

2.5 Diagnosis

Specific faults of the analogue input modules are registeredor suppressed depending on the module parametrizing.

The faults are shown on−the−spot by means of the Error LEDand, if necessary, can be evaluated with the handheld.

Depending on the module parametrizing the faults areregistered by the field bus node, where they can be evaluatedaccording to the field bus protocol used.

Representation of the faults in the various field bus nodesdepends on the field bus protocol (see manual for the fieldbus node).

Page 79:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−33Festo P.BE−CPX−AX−EN en 0811d

2.5.1 Fault messages of the analogue input modules

An analogue input module can register the following faults:

Faultnumber

Description Fault treatment

2 Fault short circuit/overload 1)

Short circuit/overload in sensor supply(VEL/SEN).(See �Parameters" �Monitoring the CPX module � monitoring short circuit/overload at sensor")

1. Eliminate short circuit/overload orcheck connected sensors

2. Depending on parametrization (Para�meters �Behaviour after short circuit/overload"):· Setting �Switch on voltage again":

Power supply for sensors will beswitched on again automaticallywhen short circuit is eliminated.

· Setting �Leave voltage switched off":� Power off/on necessaryor� Modify parameter �Behaviour after short circuit/overload" to �Leave voltage switched off".

3 Wire fracture at current input 1)

Only with voltage inputs with signal range4 � 20 mA:The input currennt IIN is less than 2.0 mA.(See parameter �Monitoring channel x �monitoring of wire fracture")

· Check and, if necessary, replace thecable and connected sensors.

9 Less than the rated range 1)

Lower limit exceeded.(See parameter �Lower limit channel x �low byte/high byte" or �Monitoringchannel x � monitoring below ratedrange")

· Check signal range of input.· Check input signal present.· Check parametrized limit.· If necessary, deactivate monitoring.

1) The module displays the relevant fault depending on the parametrizing. The analogue input signals, however, will be processed further.

Tab.�2/20: Fault messages of the input modules � part 1

Page 80:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−34 Festo P.BE−CPX−AX−EN en 0811d

Faultnumber

Description Fault treatment

10 Rated range exceeded 1)

Upper limit exceeded.(See parameter �Upper limit channel x �low byte/high byte" or �Monitoring channel x � monitoring rated range exceeded")

· Check signal range of input.· Check input signal present.· Check parametrized limit.· If necessary, deactivate monitoring.

15 Module/channel failed 2)

General fault, module faulty.· Power off/on necessary· If this fault occurs again: check and, if

necessary, replace the analogue inputmodule.

Evaluation of the analogue input signalshas stopped.

21232425

Fault in parametrizing 1) 3)

A fault has occurred in the setting of therelevant parameter.� Parameter data format� Parameter measured value smoothing� Parameter lower limit� Parameter upper limit(See parameter �Monitoring the CPXmodule � monitoring parametrizing fault"or �Monitoring channel x � monitoringparametrizing fault")

· Check the parametrizing undertakenand, if necessary, undertake theparametrizing again with the correctparameters (valid parameters seesection 2.4.3).

The analogue input module will beoperated further with the last validparametrizing.

1) The module displays the relevant fault depending on the parametrizing. The analogue input signals, however, will be processed further.

2) Processing of the analogue input signals will be stopped.3) The parameters entered will be ignored, the module operates with the last valid parameters.

Tab.�2/21: Fault messages of the input modules � part 2

Please notePlease note the following when using the input modules:

� If there is a short circuit, all sensor supplies of themodule will be switched off together.

� If not parametrized otherwise, the sensor supply voltagewill be switched on again automatically when the shortcircuit is eliminated.

Page 81:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−35Festo P.BE−CPX−AX−EN en 0811d

2.5.2 LED display

There is an LED under the transparent cover of the module fordiagnosing the input modules.

1 Error LED (red)

2AI

1

CPX−2AE−U−I

Fig.�2/8: LED display of the analogue input modules

Page 82:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−36 Festo P.BE−CPX−AX−EN en 0811d

Error LED

The red error LED indicates a module fault depending on theparametrizing (short circuit or overload of the sensor supply,wire fracture or parametrizing fault).

Error LED(red)

Sequence Status Faultnumber

Faulttreatment

LED is out

ON

OFF

Faultless operation � None

LED lights up

ON

OFF

Fault short circuit/overloadShort circuit/overload in sensorsupply (VEL/SEN).orModule defective

2

15

See section2.5.1, Tab.�2/21

Check and, ifnecessary, replace compo�nent

LED flashes

ON

OFF

1 flash 1)

Wire fracture at current inputIIN < 2.0 mAorLower limit exceededInput signal is less than theparametrized limitorUpper limit exceeded

3

9

10

See section2.5.1, Tab.�2/21

ON

OFF

2 flashes 1)

Upper limit exceededInput signal is greater than theparametrized limitorFault in parametrizing� Parameter data format� Parameter filter measured value� Parameter lower limit� Parameter upper limit

10

21232425

1) The number of flash pulses indicates the input channel concerned.1 flash = channel 0 (or both channels)2 flashes = channel 1

Tab.�2/22: Error LED of analogue input modules

Page 83:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−37Festo P.BE−CPX−AX−EN en 0811d

2.5.3 Fault treatment and parametrizing

The following diagrams show the fault treatment in the ana�logue input modules. Further registering and display of thefault can be suppressed as desired with the appropriate module parameter, represented in the diagram as a switch. A description of the parameter can be found in section 2.4.3.

2

Fault messageto field bus node

Fault no. 3

Wire fracture atcurrent inputchannel 0

MonitoringWire fracturechannel 0

Moduleerror LED

3 1

0 1

Fault no. 15

Moduledefective

MonitoringShort circuitat sensors

0 1

Fault messageto field bus node

Moduleerror LED

Fault no. 2

Short circuit/overload insensor supply

Fault no. 3

Wire fracture atcurrent inputchannel 1

MonitoringWire fracturechannel 1

0 1

1 Module parameters (switch position represented = default setting)

2 Module−specific faults

3 Channel−specific faults

Fig.�2/9: Principle of fault treatment and parametrizing of the analogue input modules �part 1

Page 84:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

2. Analogue input module CPX−2AE−U−I

2−38 Festo P.BE−CPX−AX−EN en 0811d

2

Fault no. 9

Lower limit exceededchannel 1

1

MonitoringUpper limitchannel 1

Fault no. 21 � 25

Parametrizingfault channel 1

Fault messageto field bus node

Moduleerror LED

MonitoringParametrizingfault

Fault no. 9

Lower limit exceededchannel 0

Fault no. 10

Upper limit exceededchannel 1

Fault no. 10

Upper limit exceededchannel 0

Fault no. 21 � 25

Parametrizingfault channel 0

MonitoringParametrizingfault channel 1

0 1

MonitoringParametrizingfault channel 0

0 1

0 1 0 1

MonitoringUpper limitchannel 0

0 1

MonitoringLower limitchannel 1

0 1

MonitoringLower limitchannel 0

0 1

1 Module parameters (switch position represented = default setting)

2 Channel−specific faults

Fig.�2/10: Principle of fault treatment and parametrizing of the analogue input modules �part 2

Page 85:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Analogue input module CPX−4AE−I

3−1Festo P.BE−CPX−AX−EN en 0811d

Chapter 3

Page 86:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−2 Festo P.BE−CPX−AX−EN en 0811d

Contents

3. Analogue input module CPX−4AE−I 3−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.1 Function of the analogue input modules 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.2 Fitting 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3 Installation 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.1 DIL switch settings 3−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.2 Pin assignment 3−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.3.3 Connecting the analogue intputs 3−11 . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4 Instructions on commissioning 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.1 Processing analogue input signals 3−12 . . . . . . . . . . . . . . . . . . . . . . . . . .

3.4.2 General information on parametrizing 3−16 . . . . . . . . . . . . . . . . . . . . . . .

3.4.3 Parameters of the analogue input module type CPX−4AE−I 3−18 . . . . . . .

3.4.4 Module parameter �Input analogue−value data format" 3−27 . . . . . . . .

3.4.5 Channel−specific module parameters � Limits 3−29 . . . . . . . . . . . . . . . . .

3.4.6 Channel−specific module parameters � Filter measured value 3−32 . . . .

3.4.7 Channel−specific module parameters � Monitor of wire fracture 3−32 . .

3.5 Diagnosis 3−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.1 Fault messages of the analogue input modules 3−34 . . . . . . . . . . . . . . .

3.5.2 LED display 3−36 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

3.5.3 Fault treatment and parametrizing 3−38 . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 87:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−3Festo P.BE−CPX−AX−EN en 0811d

Contents of this chapter This chapter describes the analogue input module CPX−4AE−I.

Analogue input modules provide analogue voltage inputs orcurrent inputs in a CPX terminal and can be adapted to spe�cific applications by means of different sub−bases.

Further information An overview of the modular structure of a CPX terminal, themodular connections as well as the display and connectingelements can be found in chapter 1.

Information on mounting the complete CPX terminal, connect�ing the power supply as well as general instructions on con�figuration and parametrizing can be found in the CPX systemmanual.

Information on the address assignment as well as on commis�sioning can be found in the appropriate field bus node man�ual or function module manual.

Page 88:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−4 Festo P.BE−CPX−AX−EN en 0811d

3.1 Function of the analogue input modules

Analogue input modules provide analogue voltage inputs orcurrent inputs for connecting sensors and enable the register�ing and processing of analogue current and voltage signals.At present the following type is available:

Type Description

CPX−4AE−I This type provides 4 analogueinputs (input channels) withscalable value ranges. The inputsignal range can be configuredchannel by channel, eitherelectrically isolated or non−floating:� 0 � 20 mA� 4 � 20 mASensor supply 24 V / 0.7 A permodule.

Tab.�3/1: Overview of analogue input modules CPX−4AE−I

3.2 Fitting

See section 1.3.

Page 89:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−5Festo P.BE−CPX−AX−EN en 0811d

3.3 Installation

WarningUndesired movement of the connected actuators anduncontrolled movements of loose tubing can cause injuryto human beings or damage to property.

Before carrying out installation and maintenance work,switch off the following:

� the compressed air supply

� the operating and load voltage supplies.

In the following sections you will find the pin assignments ofthe analogue input modules for the different sub−bases.

Instructions on connecting the cables and plugs to the sub−bases can be found in section 1.2.3.Note in particular the instructions on connecting the cablescreening to functional earth (FE).

Power supply

The 24 V sensor supply for the inputs as well as the powersupply for the electronics of the input modules is provided viathe operating voltage supply for the electronics/sensors(VEL/SEN).

The sensors can also be supplied externally (electrical isola�tion, see section 3.3.3, Fig.�3/2).

Page 90:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−6 Festo P.BE−CPX−AX−EN en 0811d

3.3.1 DIL switch settings

2 DIL switches are available for configuring the analogueinput modules. These are located on the top of the electronicmodule.

1 DIL switch 0: Signal range ofanalogue input0,�1

2 DIL switch 1: Signal range ofanalogue input2,�3

4AI–I

1 2

ON 1

21 2

ON

Fig.�3/1: DIL switches in the electronic module (further information on 1 and 2 see following pages)

Proceed as follows:

1. Switch off the power supply.

2. Remove if necessary the fitted sub−base (see �Fitting"section 1.3).

3. Set the DIL switch elements in accordance with theinstructions on the following pages.

4. Refit if necessary the sub−base (see �Fitting" section 1.3,tightening torque 0.9 � 1.1�Nm).

Page 91:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−7Festo P.BE−CPX−AX−EN en 0811d

Setting the input signal range

On the 4AE−I module each channel has a DIL switch elementfor setting the signal range.

� DIL switch 0: channels 0 and 1

� DIL switch 1: channels 2 and 3

Channel Signal range

0 � 20 mA 4 � 20 mA

0 DIL0.1: OFF 1)

DIL0.1: ON

1 DIL0.2: OFF 1)

DIL0.2: ON

2 DIL1.1: OFF 1)

DIL1.1: ON

3 DIL1.2: OFF 1)

DIL1.2: ON

1) Default (factory setting)

Tab.�3/2: DIL switches of the analogue input module 4AE−I

Please noteThe setting of the signal range with the DIL switches can bemodified by parametrizing (see section 3.4). Parametrizinghas precedence over the DIL switch setting.

Page 92:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−8 Festo P.BE−CPX−AX−EN en 0811d

3.3.2 Pin assignment

Pin assignment of CPX−4AE−I with sub−baseCPX−AB−4−M12x2−5POL(−R)

Analogue input module type CPX−4AE−I with sub−base CPX−AB−4−M12x2−5POL(−R)

Sub−base Pin assignment X1, X2 (input II0, II1)

Pin assignment X3, X4 (input II2, II3)

4AI−I

2

3

1

5

4X1 Socket X1:

1: 24 VSEN2: II0+3: 0 VSEN4: II0−5: FE (screening) 1)

2

3

1

5

4X3 Socket X3:

1: 24 VSEN2: II2+3: 0 VSEN4: II2−5: FE (screening) 1)

2

3

1

5

4

X2Socket X2:1: 24 VSEN2: II1+3: 0 VSEN4: II1−5: FE (screening) 1)

2

3

1

5

4

X4Socket X4:1: 24 VSEN2: II3+3: 0 VSEN4: II3−5: FE (screening) 1)

IIx+ = Positive current input signalIIx− = Negative current input signalFE = Functional earth1) With CPX−AB−4−M12x2−5POL−R the metal thread is connected to FE

Tab.�3/3: Pin assignment of analogue input module type CPX−4AE−I with sub−baseCPX−AB−4−M12x2−5POL(−R)

CPX−AB−4−M12x2−5POL−R The metal thread (�...−R") of this sub−base is connectedinternally with pin 5 (Functional earth FE).

Page 93:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−9Festo P.BE−CPX−AX−EN en 0811d

Pin assignment of CPX−4AE−I with sub−baseCPX−AB−8−KL−4POL

Analogue input module type CPX−4AE−I with sub−base CPX−AB−8−KL−4POL

Sub−base Pin assignment X1 � X4 (input II0, II1)

Pin assignment X5 � X8 (input II2, II3)

4AI−I

X1

X2

X5

X6

.0

.1

.2

.3

.0

.1

.2

.30

X1

X2

.0

.1

.2

.3

.0

.1

.2

.3

X1.0: 24 VSENX1.1: 0 VSENX1.2: II0−X1.3: FE (screening)

X2.0: n.c.X2.1: n.c.X2.2: II0+X2.3: FE (screening)

X5

X6

.0

.1

.2

.3

.0

.1

.2

.3

X5.0: 24 VSENX5.1: 0 VSENX5.2: II2−X5.3: FE (screening)

X6.0: n.c.X6.1: n.c.X6.2: II2+X6.3: FE (screening)

X3

X4

X7

X8

.3

.0

.1

.2

.3

.0

.1

.2

.3X3

X4

.0

.1

.2

.3

.0

.1

.2

.3

X3.0: 24 VSENX3.1: 0 VSENX3.2: II1−X3.3: FE (screening)

X4.0: n.c.X4.1: n.c.X4.2: II1+X4.3: FE (screening)

X7

X8

.0

.1

.2

.3

.0

.1

.2

.3

X7.0: 24 VSENX7.1: 0 VSENX7.2: II3−X7.3: FE (screening)

X8.0: n.c.X8.1: n.c.X8.2: II3+X8.3: FE (screening)

IIx+ = Positive current input signalIIx− = Negative current input signaln.c. = Not connectedFE = Functional earth

Tab.�3/4: Pin assignment of analogue input module type CPX−4AE−I with sub−baseCPX−AB−8−KL−4POL

Page 94:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−10 Festo P.BE−CPX−AX−EN en 0811d

Pin assignment of CPX−4AE−I with sub−baseCPX−AB−1−SUB−BU−25POL

Analogue input module type CPX−4AE−I with sub−base CPX−AB−1−SUB−BU−25POL

Sub−base Pin assignment

4AI−I

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

1: II0−2: II0+3: II1−4: II1+5: n.c.6: n.c.7: n.c.8: n.c.9: 24 VSEN10: 24 VSEN11: 0 VSEN12: 0 VSEN13: FE

14: II2−15: II2+16: II3−17: II3+18: 24 VSEN19: n.c.20: 24 VSEN21: n.c.22: 0 VSEN23: 0 VSEN24: 0 VSEN25: FEHousing: FE (screening)

IIx+ = Positive current input signalIIx− = Negative current input signaln.c. = Not connectedFE = Functional earth

Tab.�3/5: Pin assignment of analogue input module type CPX−4AE−I with sub−baseCPX−AB−1−SUB−BU−25POL

Page 95:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−11Festo P.BE−CPX−AX−EN en 0811d

3.3.3 Connecting the analogue intputs

Only screened cables are usually permitted for thetransmission of analogue signals (see section 1.2.3).

1 Without electricalisolation: The sensors are supplied via the CPX module

2 With electrical isolation: If an external sensorsupply is used

0/�4...20

mA

0/�4...20

mA

External

sensor

supply

0/�4...20

mA

24�VIIx+ IIx− FE0�V

24�VIIx+ IIx− FE0�V

24�VIIx+ IIx− FE0�V

1

2

Fig.�3/2: Examples of analogue input connections (screening connection on FE pin)

Further connection examples can be found in appendix A.7.1.

Page 96:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−12 Festo P.BE−CPX−AX−EN en 0811d

3.4 Instructions on commissioning

3.4.1 Processing analogue input signals

The analogue values are transmitted from the CPX terminal tothe control system as input words (2 bytes, 16 bits). Eachanalogue 4−input module occupies 4 input words for this pro�cedure in the address range (4 inputs, 64 bits).

The position of the input words in the address range dependson the field bus used (see manual for the field bus node).

Parametrizing The data format as well as the limit values and, where appli�cable, also the scaling of the analogue input signals can beadapted by parametrizing. Instructions on this can be foundin the sections 3.4.2 and 3.4.3.

The reaction with the default settings is described below.

Page 97:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−13Festo P.BE−CPX−AX−EN en 0811d

Reaction with the default settings

The module parameter �Input analogue−value data format"possesses the default setting �VZ + 12 bits right−justified"(compatible with valve terminal type 03). With this setting theanalogue values will be saved in the input word as follows:

Data format �VZ + 12 bits right−justified" (compatible with valve terminal type 03)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ 0 0 0 B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

Abbreviations used:VZ: Sign (with data format �VZ + 12 bits right−justified" always = 0, i.e. a positive value)B0 � B11: Input valueD0 � D15: 16 bits input data field MSB/LSB: Most significant bit / least significant bit

Tab.�3/6: Data format �VZ + 12 bits right−justified"

The channel−specific parameters �Lower limit" and �Upperlimit" possess the following default settings:

� Lower limit = 0

� Upper limit = 4095

These correspond to the scaling end values (data range) ofthe default data format.

Page 98:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−14 Festo P.BE−CPX−AX−EN en 0811d

The following diagram shows the processing of the analogueinput signals with the default data format �VZ + 12 bits right−justified". The example shows a sensor which converts therange of the physical measuring variables from 0 � 6 bar lin�ear into the analogue signals 0 � 20 mA or 4 � 20 mA.

1 Lower limit of ratedrange

2 Measured value(example)

3 Upper limit of ratedrange

4 Physical measuringvariables

5 Assigned analoguesignal

6 Digital value rangeafter A−D conversion(linear scaling)

7 Digital input value(example)

1 3

0 mA4 mA

0 4095

20 mA20 mA

0 6 bar3.5 bar

2

4

5

6

11.66 mA9.33 mA

7

2389

Fig.�3/3: Example of default data format �VZ + 12 bits right−justified"

Page 99:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−15Festo P.BE−CPX−AX−EN en 0811d

The assignment of analogue input signal ranges to the digitalvalue range is shown in the table below.

Analogue input signal range Digital data preparation

0 � 20 mA 4 � 20 mA Ranges Digital values

> 19.995 mA > 19.995 mA Rated rangeexceeded

Limiting to the upperscaling end value

4095

19.995 mA 19.995 mA Upper limit 4095

... ... Rated range

i l

1 � 4094

0 mA 4 mA Lower limit ofrated range

Linear value range0

< 0 mA < 4 mA Less than ratedrange

Limiting to the lowerscaling end value

0

Tab.�3/7: Scaling end values of the analogue input modules with default settings

Page 100:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−16 Festo P.BE−CPX−AX−EN en 0811d

3.4.2 General information on parametrizing

The reaction of the analogue input modules can beparametrized.

Further information on parametrizing can be found in thesystem manual or in the manual for the field bus node.

Due in some cases to necessary calculations, modified para�meters are not valid until they have been thoroughly checkedand saved. Until then, as in the case of invalid parameters,the previous settings apply.

Depending on the parameter, no valid analogue values areavailable for up to max. 30 ms after a value modification.

Special instructions on avoiding parametrizingfaults

In order to avoid parametrizing faults, note the sequencedescribed below when modifying the following parameters:

� Input analogue−value data format

� Lower limit channel x

� Upper limit channel x

Page 101:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−17Festo P.BE−CPX−AX−EN en 0811d

Sequence for first or startup parametrizing (CPX terminal indelivery status, monitoring of parametrizing faults active):

1. First set the desired data format (parameter �Inputanalogue−value data format").

2. Then set the upper and lower limits for both channels:

� If the new upper limit value is positive, set first theupper limit; then the lower limit.

� If the new upper limit is negative (only in the case ofdata format �VZ + 15 bits linear scaled"), set first thelower limit, then the upper limit.

Sequence for modifying the parametrizing:

1. Activate, if applicable, the monitoring of parametrizingfaults (module parameter �Monitoring CPX module �monitoring parametrizing faults" and channel−specificmodule parameter �Monitoring channel x � monitoringparametrizing faults").

2. Set the lower limit to 0 and the upper limit to 4095 forboth channels.

3. Then set the desired data format (parameter �Inputanalogue−value data format").

4. If required, then set the upper and lower limits for bothchannels:

� If the new upper limit value is positive, set first theupper limit; then the lower limit.

� If the new upper limit is negative (only in the case ofdata format �VZ + 15 bits linear scaled"), set first thelower limit, then the upper limit.

Page 102:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−18 Festo P.BE−CPX−AX−EN en 0811d

3.4.3 Parameters of the analogue input module type CPX−4AE−I

The tables below give an overview of the module parametersof the analogue input modules.

Function number 1) Module parameters

4828 + m * 64 + 0 Monitoring the CPX module

4828 + m * 64 + 1 Behaviour after short circuit/overload

4828 + m * 64 + 2 Reserved

4828 + m * 64 + 3 Input analogue−value data format

1) m = module number (counting from left to right, beginning with 0)

Tab.�3/8: Overview � module parameters

Function number 1) Channel−specific module parameters

4828 + m * 64 + 6 � 9 Monitoring channel 0 � 3

4828 + m * 64 + 10 Signal range channel 0 � 3

4828 + m * 64 + 11 Filter measured value channel 0 � 3

4828 + m * 64 + 12/13 Lower limit channel 0

4828 + m * 64 + 14/15 Lower limit channel 1

4828 + m * 64 + 16/17 Lower limit channel 2

4828 + m * 64 + 18/19 Lower limit channel 3

4828 + m * 64 + 20/21 Upper limit channel 0

4828 + m * 64 + 22/23 Upper limit channel 1

4828 + m * 64 + 24/25 Upper limit channel 2

4828 + m * 64 + 26/27 Upper limit channel 3

� 2) Force channel x (see also CPX system manual)

1) m = module number (counting from left to right, beginning with 0)2) Access is protocol−specific (see manual for field bus node)

Tab.�3/9: Overview � channel−specific module parameters

Page 103:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−19Festo P.BE−CPX−AX−EN en 0811d

Description of the parameters

Module parameters: Monitoring the CPX module

Function no. 4828 + m * 64 + 0 m = module number (0 � 47)

Description With the analogue input modules, monitoring of individual faults can be activatedor deactivated (suppressed) independently of each other. Active monitoringcauses the following: The fault is:� sent to the CPX field bus node� displayed by the module common error LED.

Bit Bit 0: monitoring short circuit/overload in the sensor supplyBit 1 � 6: reservedBit 7: monitoring parametrizing faults

Values 1 = active (presetting); 0 = inactive

Remark � Monitoring short circuit at sensors:Monitoring can also be set for the complete CPX terminal (see CPX systemmanual, system parameter �Monitoring").

� Monitoring parametrizing faults:Some parameters are checked for non−permitted values during parametrizing:� Data format� Lower limit� Upper limitThe setting of the module parameter �Monitoring parametrizing faults" is onlyeffective for channel−specific parametrizings if the corresponding channelparameter �Monitoring parametrizing faults" is set to �active".

Tab.�3/10: Monitoring the CPX module

Page 104:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−20 Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Behaviour after short circuit/overload

Function no. 4828 + m * 64 + 1 m = module number (0 � 47)

Description Determines after a short circuit in the sensor supply whether the power is toremain switched off or whether it is to be switched on again automatically.

Bit Bit 0: behaviour after short circuit/overload in the sensor supply

Values 0 = leave voltage/current switched off1 = switch voltage on again (presetting)Bit 2 � 7: reserved

Remark With the setting �Leave voltage switched off", Power off/on is necessary forswitching the power on again. Ascertain the setting which is necessary for reliable operation of your machine or system. Further information can be found insection 3.5.1.

Tab.�3/11: Behaviour after short circuit/overload

Module parameters: Input analogue−value data format

Function no. 4828 + m * 64 + 3 m = module number (0 � 47)

Description Determines the format in which the analogue input signals are provided by theCPX terminal.

Bit Bit 0, 1: input analogue−value data formatBit 2 � 7: reserved (= 0)

Values Bit 1 Bit 00 0 VZ + 15 bits linear scaled0 1 VZ + 12 bits right−justified (compatible with valve terminal

type 03, presetting)1 0 VZ + 15 bits left−justified (Simatic S7)1 1 VZ + 12 bits left−justified + diagnosis (Simatic S5)

(VZ = sign)

Remark The reserved bits 2 � 7 must always be 0. If one or several bits are set to �1"during parametrizing, the parametrizing carried out is invalid and therefore noteffective. If the module parameter �Monitoring parametrizing faults" is set to�active", the relevant fault will be displayed.Further information on this parameter can be found in section 3.4.4.

Tab.�3/12: Input analogue−value data format

Page 105:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−21Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Monitoring channel x

Function no. 4828 + m * 64 + 6 (channel 0) m = module number (0 � 47)4828 + m * 64 + 7 (channel 1)4828 + m * 64 + 8 (channel 2)4828 + m * 64 + 9 (channel 3)

Description For the individual channels of the analogue input modules, monitoring of individ�ual faults can be activated or deactivated (suppressed) independently of eachother. Active monitoring causes the following: The fault is:� sent to the CPX field bus node� displayed by the module common error LED.Further infomation on these monitorings can be found under the description ofthe relevant fault in section 3.5.1.

Bit Bit 0: monitoring lower limit (or less than rated range)Bit 1: monitoring upper limit (or rated range exceeded)Bit 2: monitoring wire fractureBit 3 � 6: reservedBit 7: monitoring parametrizing faults

Values 1 = active; 0 = inactivePresetting bit 0 � 2: 0 (inactive)Presetting bit 7: 1 (active)

Remark � Monitoring the upper/lower limit:Monitoring the input signals for less than or exceeding the rated range ormonitoring the range limits defined with the parameters �Lower limit ..." aswell as �Upper limit ..." (depending on the data format used, see sections3.4.4 and 3.4.5).

� Monitoring wire fracture:Only effective for the signal range 4 � 20 mA. A drop below the minimum inputcurrent (IIN�< 2.0�mA) counts as a wire fracture.

� Monitoring parametrizing faults:Some channel−specific parameters are checked for non−permitted values during parametrizing:� Lower limit� Upper limitThe setting of the channel parameter �Monitoring parametrizing faults" is onlyeffective if the module parameter �Monitoring parametrizing faults" is set to�active".

Tab.�3/13: Monitoring channel x

Page 106:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−22 Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Signal range channel x

Function no. 4828 + m * 64 + 10 m = module number (0 � 47)

Description For the individual channels of the analogue input modules, the signal ranges ofthe analogue inputs can be set independently of each other.

Bit Bit 0/2: Setting of DIL switch 0 for channel 0 or 1 (read only)bit 0 = switch 0.1 (channel 0)bit 2 = switch 0.2 (channel 1)

Bit 4/6: Setting of DIL switch 1 for channel 2 or 3 (read only)bit 4 = switch 1.0 (channel 2)bit 6 = switch 1.1 (channel 3)

Bit 1, 3, 5, 7: Signal range for channel 0, 1, 2, 3 can be set independently of each other.

Values Channel 3 Channel 2 Channel 1 Channel 0Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 Use the setting of the DIL

switches (presetting)(see Tab.�3/2)

0 1 0 1 0 1 0 1 0 � 20 mA1 0 1 0 1 0 1 0 4 � 20 mA1 1 1 1 1 1 1 1 Reserved

Remark Modified parameter settings have precedence over the DIL switch settings. The setting of the DIL switches (bit 0 � 7 = 0) is carried out with the presetting.

Tab.�3/14: Signal range channel x

Page 107:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−23Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Filter measured value channel x

Function no. 4828 + m * 64 + 11 m = module number (0 � 47)

Description For the individual channels of the analogue input modules, the filter formeasured values can be set independently of each other.

Bit Bit 0/1: filter measured value channel 0Bit 2/3: filter measured value channel 1Bit 4/5: filter measured value channel 2Bit 6/7: filter measured value channel 3

Values Channel 3 Channel 2 Channel 1 Channel 0Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 No filter measured value

(presetting)0 1 0 1 0 1 0 1 Filter measured value over

2 values1 0 1 0 1 0 1 0 Filter measured value over

4 values1 1 1 1 1 1 1 1 Filter measured value over

8 values

Remark Faults can be suppressed with the Filter measured value (see section 3.5.1).If the module parameter �Monitoring parametrizing faults" as well as the relevant channel parameter �Monitoring parametrizing faults" is set to �active",the relevant fault will be displayed.

Tab.�3/15: Filter measured value channel x

Page 108:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−24 Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Lower limit channel x / Upper limit channel x

Function no. Lower limit: m = module number (0 � 47)4828 + m * 64 + 12 (channel 0, low byte)4828 + m * 64 + 13 (channel 0, high byte)4828 + m * 64 + 14 (channel 1, low byte)4828 + m * 64 + 15 (channel 1, high byte)4828 + m * 64 + 16 (channel 2, low byte)4828 + m * 64 + 17 (channel 2, high byte)4828 + m * 64 + 18 (channel 3, low byte)4828 + m * 64 + 19 (channel 3, high byte)

Upper limit:4828 + m * 64 + 20 (channel 0, low byte)4828 + m * 64 + 21 (channel 0, high byte)4828 + m * 64 + 22 (channel 1, low byte)4828 + m * 64 + 23 (channel 1, high byte)4828 + m * 64 + 24 (channel 2, low byte)4828 + m * 64 + 25 (channel 2, high byte)4828 + m * 64 + 26 (channel 3, low byte)4828 + m * 64 + 27 (channel 3, high byte)

Description A lower as well as an upper limit value can be set for the individual channels ofthe analogue input modules (see section 3.4.5).With data format �VZ + 15 bits linear scaled", the limits have the function ofscaling end values.

Bit Bit 0 � 7: high byte or low byte of the limit value

Values Presettings:� Lower limit = 0 (low byte = 0; high byte: 0)� Upper limit = 4095 (low byte = 255; high byte: 15)Low byte: 0 � 255High byte: 0 � 15

Page 109:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−25Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Lower limit channel x / Upper limit channel x

Remark If the input value is less than the parametrized lower limit or exceeds the parame�trized upper limit, an appropriate fault is displayed (providing the relevant channel parameter �Monitoring channel x � monitoring lower limit" or�Monitoring channel x � monitoring upper limit" is active).The upper limit must always be more than the lower limit.Modifications to the limits must be made in steps of 16 bits.

Permitted limits:The limits are checked for validity during parametrizing. Invalid parametrizingsare not accepted � the module uses the previous (last valid) parametrizings. The permitted values depend on the parametrized data format (see section3.4.5). If the module parameter �Monitoring parametrizing faults" as well as therelevant channel parameter �Monitoring parametrizing faults" is set to �active", the relevant fault will be displayed.

Tab.�3/16: Lower and upper limits channel x

Page 110:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−26 Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Force channel x

Function no. Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).

Description The Force function permits the manipulation of analogue values irrespective ofthe actual input value (see also CPX system manual). This can be accomplishedwith the following parameters:� Force mode inputs channel x� Force state inputs channel x

Values � Force mode inputs channel x 0 = blocked (presetting)1 = Force state

� Force state inputs channel x 0 = reset value (presetting)1 = set value

Remark The enabling of the Force function with the parameter �Force mode outputschannel x" depends on the field bus protocol and is accomplished:� by an individual parameter setting or bit (e.g. CPX−FB11),� by setting all parameter bits of the relevant word (e.g. CPX−FB6) to �blocked"

or �Force state".For parametrizing the Force state, the desired input word must be correspon�dingly mapped in the parameter bits �Force state inputs channel x".The enabling of the Force function for the complete CPX terminal is made bymeans of the system parameter �Force mode" (see CPX system manual).

Tab.�3/17: Force channel x (channel−specific)

Page 111:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−27Festo P.BE−CPX−AX−EN en 0811d

3.4.4 Module parameter �Input analogue−value data format"

The parametrized data format determines how the analoguevalues are transferred by the CPX terminal to the control sys�tem. The setting applies to all analogue input channels. Irre�spective of the data format the data width is always 16�bits(2�bytes, 1�word).

Supported data formats of the analogue input modules

VZ + 15 bits linear scaled

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B14MSB

B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

VZ + 12 bits right−justified (compatible with valve terminal type 03, presetting)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ 0 0 0 B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

VZ + 15 bits left−justified (compatible with Simatic S7)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

x x x

VZ + 12 bits left−justified + diagnosis (compatible with Simatic S5)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

0 F 0

Abbreviations used:VZ: Sign (0 = positive value, 1 = negative value)B0 � B14: Input valueD0 � D15: 16 bits input data fieldMSB/LSB: Most significant bit / least significant bitF: Wire fracture monitoring with signal range 4 � 20 mA: F = 1 wire fracture exists

F = 0 no wire fracture existsx: Not relevant

Tab.�3/18: Supported data formats of the analogue input modules

Page 112:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−28 Festo P.BE−CPX−AX−EN en 0811d

Data format �VZ + 15 bits linear scaled"

The 12−bit digital values, which exist after the A−D conversionof the analogue input signals, are linearly scaled to the datarange defined by the scaling end values (limit values) andoutput in the input word (see section 3.4.5, Fig.�3/5).

Data format �VZ + 12 bits right−justified"

The 12−bit digital values, which exist after the A−D conversionof the analogue input signals, are output unmodified in theinput word (see also example in section 3.4.1, Fig.�3/3).

Data format �VZ + 15 bits left−justified" anddata format �VZ + 12 bits left−justified + diagnosis"

The 12−bit digital values, which exist after the A−D conversionof the analogue input signals, plus the preceding sign bit arearranged left−justified in the data format. The three zeros atthe end cause the output data word to correspond to the12−bit digital value after A−D conversion multiplied by 8(providing there is no wire fracture diagnosis).

The following diagram shows an example of the data format�VZ + 15 bits left−justified":

1 Analogue inputvalues

2 Digital signals afterA−D conversion

3 Available digitalsignals scaled to theend value of the datarange

1

2

332760

0 4095

0

0 mA4 mA

20 mA20 mA

Fig.�3/4: Example of data format �VZ + 15 bits left−justified"

Page 113:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−29Festo P.BE−CPX−AX−EN en 0811d

3.4.5 Channel−specific module parameters � Limits

You can determine limits with the channel−specific para�meters �Lower limit" and �Upper limit". The meaning of thelimit parameters depends on the parametrized data format ofthe module.

With data format �VZ + 15 bits linear scaled", the limits havethe function of defining the scaling end values of the datarange. This results in an additional scaling of the analoguevalues. If the input data lie outside this data range, a diagnosticmessage can be generated with appropriate parametrizing.

With other data formats the data range is already defined bythe scaling end values. In this case, the limits permit datamonitoring even within the data range.

Data format 1) Data range Limits/scaling end values 2)

VZ + 15 bits linear scaled

−30000 � +30000 Lower scaling end value:−30000 � +29999

Upper scaling end value:−29999 � +30000

VZ + 12 bits right−justified

0 � 4095 Lower limit:0 � 4094

Upper limit:1 � 4095

VZ + 15 bits left−justified

0 � 32760 Lower limit:0 � 32759

Upper limit:1 � 32760

VZ + 12 bits left−justified + diagnosis 3)

0 � 32760 Lower limit:0 � 32752

Upper limit:1 � 32760

1) VZ = SignAs the analogue inputs with the �Fixed value" data formats �VZ + 12 bits right−justified", �VZ + 15 bits left−justified" and �VZ + 12 bits left−justified + diagnosis" generate only positive signals, the sign bit with these formats is always 0.

2) The lower limit/scaling end value must always be less than the upper limit/scaling end value.3) If the max. current values are exceeded, values greater than 4095 will also be output.

Tab.�3/19: Limits or scaling end values of the analogue input modules

Page 114:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−30 Festo P.BE−CPX−AX−EN en 0811d

Scaling end values with data format �VZ + 15 bitslinear scaled"

The following diagram shows an example of the data format�VZ + 15 bits linear scaled" with the scaling end values:

� Lower limit = 0

� Upper limit = 6000

The example shows a sensor which converts the range of thephysical measuring variables from 0 � 6 bar linear into theanalogue signals 0 � 20 mA.

1 Physical measuringvariables

2 Digital signals afterA−D conversion (resolution: 12 bits)

3 Available digitalsignals after scalingby the scaling endvalues

1

2

3

0

6000

0 4095

0

6 bar

Fig.�3/5: Example scaling data format �VZ + 15 bits linear scaled"

The scaling end values in this data format are identical withthe limits for less than or exceeding the rated range:

1 Digital input signalafter scaling

2 Limits

3 Less than orexceeding the limits

12

3

0 6.000

2

Fig.�3/6: Limit monitoring with data format �VZ + 15 bits linear scaled"

Page 115:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−31Festo P.BE−CPX−AX−EN en 0811d

Limits with the �Fixed value" data formats

The following diagram shows an example of the data format�VZ + 12 bits right−justified" with the scaling end values:

� Lower limit = 500

� Upper limit = 3500

The principle of the limits also applies to the data formats �VZ + 15 bits left−justified" and �VZ + 12 bits left−justified +diagnosis".

1 End values of thedata range

2 Lower limit

3 Upper limit

4 Less than orexceeding the limits

1 2 3

40950 500 3500

4

1

Fig.�3/7: Monitoring of limits with the �Fixed value" data formats

Page 116:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−32 Festo P.BE−CPX−AX−EN en 0811d

3.4.6 Channel−specific module parameters � Filter measured value

In order to suppress faults, the input data can be filtered digi�tally, whereby the degree of filtering can be set by means ofparametrizing.

Filtering is carried out as follows:

� by forming the sum of n values,

� by subtracting an average value,

� by adding the current input value.

The following applies here: the greater n, the more the signalwill be filtered.

3.4.7 Channel−specific module parameters � Monitor of wire fracture

A wire fracture monitoring (open load) can be activated withappropriate parametrizing for the signal range 4 � 20 mA.

The criterion for a wire fracture is software monitoring toensure that the value does not drop below the lower limit(IIN�� 2.0 mA). If the value drops below the lower limit, the

module will send an appropriate fault message to the field busnode.

Page 117:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−33Festo P.BE−CPX−AX−EN en 0811d

3.5 Diagnosis

Specific faults of the analogue input modules are registeredor suppressed depending on the module parametrizing.

The faults are shown on−the−spot by means of the Error LEDand, if necessary, can be evaluated with the handheld.

Depending on the module parametrizing the faults areregistered by the field bus node, where they can be evaluatedaccording to the field bus protocol used.

Representation of the faults in the various field bus nodesdepends on the field bus protocol (see manual for the fieldbus node).

Page 118:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−34 Festo P.BE−CPX−AX−EN en 0811d

3.5.1 Fault messages of the analogue input modules

An analogue input module can register the following faults:

Faultnumber

Description Fault treatment

2 Fault short circuit/overload 1)

Short circuit/overload in sensor supply(VEL/SEN).(See �Parameters" �Monitoring the CPX module � monitoring short circuit/overload at sensor")

1. Eliminate short circuit/overload orcheck connected sensors

2. Depending on parametrization (Para�meters �Behaviour after short circuit/overload"):· Setting �Switch on voltage again":

Power supply for sensors will beswitched on again automaticallywhen short circuit is eliminated.

· Setting �Leave voltage switched off":� Power off/on necessaryor� Modify parameter �Behaviour after short circuit/overload" to �Leave voltage switched off".

3 Wire fracture at current input 1)

Only with voltage inputs with signal range4 � 20 mA:The input currennt IIN is less than 2.0 mA.(See parameter �Monitoring channel x �monitoring of wire fracture")

· Check and, if necessary, replace thecable and connected sensors.

9 Less than the rated range 1)

Lower limit exceeded.(See parameter �Lower limit channel x �low byte/high byte" or �Monitoringchannel x � monitoring below ratedrange")

· Check signal range of input.· Check input signal present.· Check parametrized limit.· If necessary, deactivate monitoring.

1) The module displays the relevant fault depending on the parametrizing. The analogue input signals, however, will be processed further.

Tab.�3/20: Fault messages of the input modules � part 1

Page 119:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−35Festo P.BE−CPX−AX−EN en 0811d

Faultnumber

Description Fault treatment

10 Rated range exceeded 1)

Upper limit exceeded.(See parameter �Upper limit channel x �low byte/high byte" or �Monitoring channel x � monitoring rated range exceeded")

· Check signal range of input.· Check input signal present.· Check parametrized limit.· If necessary, deactivate monitoring.

15 Module/channel failed 2)

General fault, module faulty.· Power off/on necessary· If this fault occurs again: check and, if

necessary, replace the analogue inputmodule.

Evaluation of the analogue input signalshas stopped.

212425

Fault in parametrizing 1) 3)

A fault has occurred in the setting of therelevant parameter.� Parameter data format� Parameter lower limit� Parameter upper limit(See parameter �Monitoring the CPXmodule � monitoring parametrizing fault"or �Monitoring channel x � monitoringparametrizing fault")

· Check the parametrizing undertakenand, if necessary, undertake theparametrizing again with the correctparameters (valid parameters seesection 3.4.3).

The analogue input module will beoperated further with the last validparametrizing.

1) The module displays the relevant fault depending on the parametrizing. The analogue input signals, however, will be processed further.

2) Processing of the analogue input signals will be stopped.3) The parameters entered will be ignored, the module operates with the last valid parameters.

Tab.�3/21: Fault messages of the input modules � part 2

Please notePlease note the following when using the input modules:

� If there is a short circuit, all sensor supplies of themodule will be switched off together.

� If not parametrized otherwise, the sensor supply voltagewill be switched on again automatically when the shortcircuit is eliminated.

Page 120:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−36 Festo P.BE−CPX−AX−EN en 0811d

3.5.2 LED display

There is an LED under the transparent cover of the module fordiagnosing the input modules.

1 Error LED (red)

4AI−I

1

CPX−4AE−I

Fig.�3/8: LED display of the analogue input modules

Page 121:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−37Festo P.BE−CPX−AX−EN en 0811d

Error LED

The red error LED indicates a module fault depending on theparametrizing (short circuit or overload of the sensor supply,wire fracture or parametrizing fault).

Error LED(red)

Sequence Status Faultnumber

Faulttreatment

LED is out

ON

OFF

Faultless operation � None

LED lights up

ON

OFF

Fault short circuit/overloadShort circuit/overload in sensorsupply (VEL/SEN).orModule defective

2

15

See section3.5.1, Tab.�3/21

Check and, ifnecessary, replace compo�nent

LED flashes

ON

OFF

1 flash 1)

Wire fracture at current inputIIN < 2.0 mAorLower limit exceededInput signal is less than theparametrized limitor

3

9

See section3.5.1, Tab.�3/21

ON

OFF

2 flashes 1)

3 flashes 1)

4 flashes 1)

orUpper limit exceededInput signal is greater than theparametrized limitorFault in parametrizing� Parameter data format� Parameter lower limit� Parameter upper limit

10

212425

1) The number of flash pulses indicates the input channel concerned (1 flash = channel 0, 2 flashes = channel 1 ...). In the case of several channels with error messages, the channel which first had the fault will be shown.

Tab.�3/22: Error LED of analogue input modules

Page 122:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−38 Festo P.BE−CPX−AX−EN en 0811d

3.5.3 Fault treatment and parametrizing

The following diagrams show the fault treatment in the ana�logue input modules. Further registering and display of thefault can be suppressed as desired with the appropriate module parameter, represented in the diagram as a switch. A description of the parameter can be found in section 3.4.3.

2

Fault message tofield bus node

Fault no. 3

Wire fracture atcurrent inputchannel 0 ...

MonitoringWire fracturechannel 0 ...

Moduleerror LED

3 1

0 1

Fault no. 15

Moduledefective

MonitoringShort circuitat sensors

0 1

Fault message tofield bus node

Moduleerror LED

Fault no. 2

Short circuit/overload insensor supply

Fault no. 3

Wire fracture atcurrent input ... channel 3

MonitoringWire fracture... channel 3

0 1

1 Module parameters (switch position represented = default setting)

2 Module−specific faults

3 Channel−specific faults

Fig.�3/9: Principle of fault treatment and parametrizing of the analogue input modules �part 1

Page 123:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−39Festo P.BE−CPX−AX−EN en 0811d

2

Fault no. 9

Lower limit exceeded... channel 3

1

MonitoringUpper limitchannel 3

Fault no.21���25

Parametrizingfault ... channel 3

Fault message tofield bus node

Moduleerror LED

MonitoringParametrizingfault

Fault no. 9

Lower limit exceededchannel 0 ...

Fault no. 10

Upper limit exceeded... channel 3

Fault no. 10

Upper limit exceededchannel 0 ...

Fault no.21���25

Parametrizingfault channel 0 ...

MonitoringParametrizingfault ... channel 3

0 1MonitoringParametrizingfault channel 0 ...

0 1

0 1 0 1

MonitoringUpper limitchannel 0 ...

0 1

MonitoringLower limitchannel 3

0 1

MonitoringLower limitchannel 0 ...

0 1

1 Module parameters (switch position represented = default setting)

2 Channel−specific faults

Fig.�3/10: Principle of fault treatment and parametrizing of the analogue input modules �part 2

Page 124:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

3. Analogue input module CPX−4AE−I

3−40 Festo P.BE−CPX−AX−EN en 0811d

Page 125:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Analogue input module CPX−4AE−T

4−1Festo P.BE−CPX−AX−EN en 0811d

Chapter 4

Page 126:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−2 Festo P.BE−CPX−AX−EN en 0811d

Contents

4. Analogue input module CPX−4AE−T 4−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.1 Function of analogue input module CPX−4AE−T 4−4 . . . . . . . . . . . . . . . . . . . . . . .

4.2 Fitting 4−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3 Installation 4−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3.1 DIL switch settings 4−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3.2 Pin assignment 4−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.3.3 Connecting temperature sensors to the analogue inputs 4−11 . . . . . . . .

4.4 Instructions on commissioning 4−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.4.1 Processing the input signals of temperature sensors 4−14 . . . . . . . . . . .

4.4.2 General information on parametrizing 4−17 . . . . . . . . . . . . . . . . . . . . . . .

4.4.3 Parameters of the analogue input module type CPX−4AE−T 4−18 . . . . . .

4.4.4 Monitoring wire fracture/short circuit 4−26 . . . . . . . . . . . . . . . . . . . . . . .

4.4.5 Limit value monitoring by parametrizing 4−26 . . . . . . . . . . . . . . . . . . . . .

4.4.6 Measured value smoothing by parametrizing 4−27 . . . . . . . . . . . . . . . . .

4.5 Diagnosis 4−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5.1 Error messages of the analogue input modules 4−29 . . . . . . . . . . . . . . .

4.5.2 LED display 4−31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

4.5.3 Error treatment and parametrizing 4−33 . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 127:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−3Festo P.BE−CPX−AX−EN en 0811d

Contents of this chapter This chapter describes the analogue input module CPX−4AE−T.

This module provides the CPX terminal with analogue inputsfor registering the temperature. By means of different sub−bases, this module can be adapted to the specific application.

Further information An overview of the modular structure of a CPX terminal, themodular connections as well as the display and connectingelements can be found in chapter 1.

Information on mounting the complete CPX terminal, connect�ing the power supply as well as general instructions on con�figuration and parametrizing can be found in the CPX systemmanual.

Information on the address assignment as well as on commis�sioning can be found in the appropriate field bus node man�ual or function module manual.

Page 128:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−4 Festo P.BE−CPX−AX−EN en 0811d

4.1 Function of analogue input module CPX−4AE−T

Module CPX− 4AE−T provides 4 inputs for connecting tempera�ture sensors.

Type Description

CPX−4AE−T Provides 2 or 4 analogue inputs(input channels) for registering thetemperature.

� The sensors can be connected in2−cable, 3−cable or 4−cabledesign

� Conversion time: 250 ms foreach channel

Supported platinum sensors:� Pt 100, Pt 200, Pt 500, Pt�1000� Temperature coefficients TK =

0.00385 or 0.00391

Supported nickel sensors:� Ni 100, Ni 120, Ni 500, Ni�1000

Tab.�4/1: Overview of analogue input module CPX−4AE−T

4.2 Fitting

See section 1.3.

Page 129:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−5Festo P.BE−CPX−AX−EN en 0811d

4.3 Installation

WarningSudden unexpected movement of the connected actuatorsand uncontrolled movements of loose tubing can causeinjury to human beings or damage to property.

Before carrying out installation and maintenance work,switch off the following:

� the compressed air supply

� the operating and load voltage supplies.

In the following sections you will find the pin assignments ofthe analogue input modules for the different sub−bases.

Instructions on connecting the cables and plugs to the sub−bases can be found in section 1.2.3.Note in particular the instructions on connecting the cablescreening to functional earth (FE).

Page 130:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−6 Festo P.BE−CPX−AX−EN en 0811d

4.3.1 DIL switch settings

A DIL switch is available for configuring the analogue inputmodule. This is located on the top of the electronic module.

1 DIL switch: Setting thenumber of inputs

4AI–T

1 2

ON 1

Fig.�4/1: DIL switches in the electronic module

Proceed as follows:

1. Switch off the power supply.

2. Remove if necessary the fitted sub−base (see �Fitting"section 1.3).

3. Set the DIL switch in accordance with the instructions onthe following pages.

4. Refit if necessary the sub−base (see �Fitting" section 1.3),tightening torque 0.9 � 1.1�Nm).

Page 131:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−7Festo P.BE−CPX−AX−EN en 0811d

Setting the number of inputs

In the case of module 4AE−T, the number of inputs can beselected with a DIL switch:

� 4 inputs (standard)

� 2 inputs.

Number of inputs Setting the DIL switch

4 DIL 1.1: OFFDIL 1.2: OFF(factory setting)

2 DIL 1.1: ONDIL 1.2: OFF

Tab.�4/2: DIL switch for analogue input module 4AE−T

Please noteIn the case of input module 4AE−T, the setting of the DILswitch cannot be modified by parametrizing.

Page 132:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−8 Festo P.BE−CPX−AX−EN en 0811d

4.3.2 Pin assignment

Pin assignment of CPX−4AE−T with sub−baseCPX−AB−4−M12x2−5POL(−R)

Analogue input module type CPX−4AE−T with sub−base CPX−AB−4−M12x2−5POL(−R)

Sub−base Pin assignment X1, X2 (inputs 0, 1)

Pin assignment X3, X4 (inputs 2, 3)

4AI−T

2

3

1

5

4X1 Socket X1:

1: II0+2: IU0+3: II0−4: IU0−5: FE (screening/

shield) 1)

2

3

1

5

4X3 Socket X3:

1: II2+2: IU2+3: II2−4: IU2−5: FE (screening/

shield) 1)

2

3

1

5

4

X2Socket X2:1: II1+2: IU1+3: II1−4: IU1−5: FE (screening/

shield) 1)

2

3

1

5

4

X4Socket X4:1: II3+2: IU3+3: II3−4: IU3−5: FE (screening/

shield) 1)

IIx+ = Positive current input signalIIx− = Negative current input signalIUx+ = Positive voltage input signalIUx− = Negative voltage input signalFE = Functional earth1) With CPX−AB−4−M12x2−5POL−R the metal thread is connected to FE

Tab.�4/3: Pin assignment of analogue input module type CPX−4AE−T with sub−baseCPX−AB−4−M12x2−5POL(−R)

CPX−AB−4−M12x2−5POL−R The metal thread (�...−R") of this sub−base is connectedinternally with pin 5 (Functional earth FE).

Page 133:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−9Festo P.BE−CPX−AX−EN en 0811d

Pin assignment CPX−4AE−T with sub−baseCPX−AB−4−HAR−4POL

Analogue input module type CPX−4AE−T with sub−base CPX−AB−4−HAR−4POL

Sub−base Pin assignment X1, X2 (inputs 0, 1)

Pin assignment X3, X4 (inputs 2, 3)

0

1

2

3

4AE−T

23

14

X1

Socket X1:1: II0+2: IU0+3: II0−4: IU0− 23

14

X3

Socket X3:1: II2+2: IU2+3: II2−4: IU2−

X22 3

1 4

Socket X2:1: II1+2: IU1+3: II1−4: IU1−

X42 3

1 4

Socket X4:1: II3+2: IU3+3: II3−4: IU3−

IIx+ = Positive current input signalIIx− = Negative current input signalIUx+ = Positive voltage input signalIUx− = Negative voltage input signal

Tab.�4/4: Pin assignment of analogue input module type CPX−4AE−T with sub−baseCPX−AB−4−HAR−4POL

Page 134:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−10 Festo P.BE−CPX−AX−EN en 0811d

Pin assignment CPX−4AE−T with sub−baseCPX−AB−8−KL−4POL

Analogue input module type CPX−4AE−T with sub−base CPX−AB−8−KL−4POL

Sub−base Pin assignment X1 � X4 (inputs 0, 1)

Pin assignment X5 � X8 (inputs 2, 3)

4AI−T

X1

X2

X3

X5

X6

X7

.0

.1

.2

.3

.0

.1

.2

.3

.0

.12

X1

X2

.0

.1

.2

.3

.0

.1

.2

.3

X1.0: II0+X1.1: II0−X1.2: IU0−X1.3: FE (screening/

shield)

X2.0: n.c.X2.1: n.c.X2.2: IU0+X2.3: FE (screening/

shield)

X5

X6

.0

.1

.2

.3

.0

.1

.2

.3

X5.0: II2+X5.1: II2−X5.2: IU2−X5.3: FE (screening/

shield)

X6.0: n.c.X6.1: n.c.X6.2: IU2+X6.3: FE (screening/

shield)X3

X4

X7

X8

.1

.2

.3

.0

.1

.2

.3

X3

X4

.0

.1

.2

.3

.0

.1

.2

.3

X3.0: II1+X3.1: II1−X3.2: IU1−X3.3: FE (screening/

shield)

X4.0: n.c.X4.1: n.c.X4.2: IU1+X4.3: FE (screening/

shield)

X7

X8

.0

.1

.2

.3

.0

.1

.2

.3

X7.0: II3+X7.1: II3−X7.2: IU3−X7.3: FE (screening/

shield)

X8.0: n.c.X8.1: n.c.X8.2: IU3+X8.3: FE (screening/

shield)

IIx+ = Positive current input signalIIx− = Negative current input signalIUx+ = Positive voltage input signalIUx− = Negative voltage input signalFE = Functional earth

Tab.�4/5: Pin assignment of analogue input module type CPX−4AE−T with sub−baseCPX−AB−8KL−4POL

Page 135:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−11Festo P.BE−CPX−AX−EN en 0811d

4.3.3 Connecting temperature sensors to the analogue inputs

Each input provides a constant source of current and twoconnections for measuring the voltage drop at the sensor. Thevoltage drop can be measured at various points, dependngon the degree of accuracy desired. A distinction is thereforemade between various connecting methods:

4−cable design The highest degree of accuracy is achieved with the 4−cabledesign:

� 2 cables transmit the current from the constant source ofcurrent (connections lx+, Ix−) through the sensor,

� 2 cables serve for measuring the voltage drop directly onthe sensor. Connections Ux+ and Ux− are highly−resistive,so that the cable resistance does not lead to incorrectmeasurement.

1 Constant sourceof current in themodule

2 Connecting pin ofthe CPX module

3 Current supplyfor sensor

4 Separate voltagecable

5 Temperaturesensor

Ix+

Ix−

Ux+

Ux−

1 2

3

4

5

3

Fig.�4/2: Connection in 4−cable design

Page 136:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−12 Festo P.BE−CPX−AX−EN en 0811d

3−cable design Alternatively, connections Ix+ and Ux+ can be linkedtogether in the plug, whereby only 3 cables must beconnected to the sensor.

1 Constant sourceof current in themodule

2 Connecting pin ofthe CPX module

3 Linked current/voltageconnection l

4 Combinedcurrent/voltagecable

5 Temperaturesensor

6 Separate voltagecable

Ix+

Ix−

Ux+

Ux−

1 2 3

4

5

6

Fig.�4/3: Connection in 3−cable design

Page 137:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−13Festo P.BE−CPX−AX−EN en 0811d

2−cable design If Ix+ is linked to Ux+ and if Ix− is linked to Ux− in the plug,there remain only 2 cables which must be connected to thesensor. With this most simple connection method, accuracyis less because the voltage drop is no longer measured atthe sensor.

1 Constant sourceof current in themodule

2 Connecting pin ofCPX module

3 Linked current/voltageconnection

4 Combinedcurrent/voltagecable

5 Temperaturesensor

Ix+

Ix−

Ux+

Ux−

1 2 3

4

3

5

4

Fig.�4/4: Connection in 2−cable design

Usually only screened/shielded cables are permitted for thetransmission of analogue signals (see section 1.2.3).

Page 138:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−14 Festo P.BE−CPX−AX−EN en 0811d

4.4 Instructions on commissioning

4.4.1 Processing the input signals of temperature sensors

The analogue values are transmitted to the control system bythe CPX terminal as input words (4 inputs, 64 bits or 2 inputs,32 bits). Each temperature module occupies 2 or 4 inputwords in the address range for this procedure.

The position of the input words in the address range dependson the field bus used (see manual for the field bus node).

Temperature sensors Pt temperature sensors can be operated in two temperatureranges:

� Standard (−200 � +850 °C)

� Climate (−120 � +130 °C)

Ni temperature sensors always operate in the temperaturerange −60 � +180 °C.

Parametrizing By means of parametrizing, the CPX temperature modulecan be set to different temperature sensors and sensor con�nection methods.

In addition, the unit of measurement, the diagnostic reaction,limit value monitoring, etc. can be adapted by means ofparametrizing. Instructions on this can be found in the sec�tions 4.4.2 and 4.4.3.

Page 139:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−15Festo P.BE−CPX−AX−EN en 0811d

Reaction with default settings

The module parameters are set as standard to these values:

� Unit of measurement: °C

� Interference frequency suppression: 50 Hz

The channel−specific parameters are set as standard to thesevalues:

� Sensor type: Pt 100 with temperature coefficient 0.00385

� Temperature range: Standard (−200 � +850 °C)

� Connection design: 2−cable

The temperature values are stored in the input word with thedata format �VZ + 15 bits binary complement of two":

Data format �VZ +15 bits complement of two binary numbers"

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B14MSB

B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

Abbreviations used:VZ: Mathematical sign (0 = positive value, 1 = negative value)B0 � B14: Input valueD0 � D15: 16 bits input data fieldMSB/LSB: Most significant bit / least significant bit

Tab.�4/6: Data format of temperature module CPX−4AE−T

The complete parameter settings can be found insection�4.4.3.

Page 140:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−16 Festo P.BE−CPX−AX−EN en 0811d

The diagram below shows the processing of the input signalsof a temperature sensor. A Pt�100 sensor in the standard tem�perature range is used as an example. (temperature coeffi�cient TK = 0.00385 /°C).

1 Lower limit of ratedrange

2 Measured value(example)

3 Upper limit of ratedrange

4 Physical measuringvariables

5 Resistance of thesensor

6 Digital value rangeafter A−D conversion

7 Digital input value(example)

1 3

18.52

− 2000 + 8500

390.481

− 200 °C + 850 °C+ 42 °C

2

4

5

6

116.313

7

420

Fig.�4/5: Example: Representing the temperaturesfor a Pt�100 sensor

Page 141:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−17Festo P.BE−CPX−AX−EN en 0811d

4.4.2 General information on parametrizing

If necessary, use parametrizing to set other temperaturesensors, connection designs, diagnostic reactions, etc.

Due in some cases to necessary calculations, modified para�meters are not valid until they have been thoroughly checkedand saved. Until then, as in the case of invalid parameters,the previous settings apply.

Depending on the parameter, no valid analogue values areavailable for up to max. 30 ms after a value modification.

Special instructions on avoiding parametrizingfaults

Parametrize in this sequence:

1. set the temperature sensor and the temperaturecoefficients

2. set limit values

3. activate limit value monitoring.

Page 142:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−18 Festo P.BE−CPX−AX−EN en 0811d

4.4.3 Parameters of the analogue input module type CPX−4AE−T

The tables below give an overview of the module parametersof the analogue input module.

Function number 1) Module parameters

4828 + m * 64 + 0 � 5 Reserved

4828 + m * 64 + 6 � Measuring unit (°C, °Fahrenheit)� Interference frequency suppression (50�Hz, 60�Hz)

1) m = module number (counting from left to right, beginning with 0)

Tab.�4/7: Overview � module parameters

Function number 1) Channel−specific module parameters

4828 + m * 64 + 7 Diagnostic message in the event of wire fracture or short circuit inchannel 0 � 3

4828 + m * 64 + 8 Limit value monitoring channel 0 � 3

4828 + m * 64 + 9 Measured value smoothing channel 0 � 3

4828 + m * 64 + 10 Connection designs of temperature sensors channel 0 � 3

4828 + m * 64 + 11 Sensor type/temperature coefficient, temperature range channel 0

4828 + m * 64 + 12 Sensor type/temperature coefficient, temperature range channel 1

4828 + m * 64 + 13 Sensor type/temperature coefficient, temperature range channel 2

4828 + m * 64 + 14 Sensor type/temperature coefficient, temperature range channel 3

4828 + m * 64 + 15 � 16 Limit values channel 0

4828 + m * 64 + 17 � 18 Limit values channel 1

4828 + m * 64 + 19 � 20 Limit values channel 2

4828 + m * 64 + 21 � 22 Limit values channel 3

� 2) Force channel x (see also CPX system manual)

1) m = module number (counting from left to right, beginning with 0)2) Access is protocol−specific (see manual for the field bus node)

Tab.�4/8: Overview � channel−specific module parameters

Page 143:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−19Festo P.BE−CPX−AX−EN en 0811d

Description of the parameters

Module parameters: Measuring unit and interference frequency suppression

Function no. 4828 + m * 64 + 6 m = module number (0 � 47)

Description The measuring unit for the temperature can be switched to either:� °Centigrade or °Fahrenheit

The interference frequency suppression specifies the frequency at which powerunits etc. are to be operated in order that interference resulting therefrom can besuppressed.� 50 Hz or 60 Hz

Bit Bit 3: Measuring unit for temperatureBit 4: Interference frequency suppression

Values Bit 3: 0 = °C (presetting); 1 = °FahrenheitBit 4: 0 = 50 Hz (presetting); 1 = 60 Hz

Remark � Converting temperature units:°F = (°C * 9/5) + 32°C = (°F − 32) * 5/9

Tab.�4/9: Module parameters

Page 144:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−20 Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Diagnostic message in the event of wire fracture or short circuit channel x

Function no. 4828 + m * 64 + 7 (channel 0 � 3) m = module number (0 � 47)

Description Sets whether or not a diagnostic message is to be displayed after wire fracture orshort circuit. The parameter can be set for the individual channels independentlyof each other.

Bit Bit 0/1: channel 0Bit 2/3: channel 1Bit 4/5: channel 2Bit 6/7: channel 3

Values Channel 3 Channel 2 Channel 1 Channel 0Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 No diagnostic message

(presetting)0 1 0 1 0 1 0 1 Diagnostic message in the

event of wire fracture or short circuit

Remark �

Tab.�4/10: Diagnostic message channel x

Page 145:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−21Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Limit value monitoring channel x

Function no. 4828 + m * 64 + 8 (channel 0 � 3) m = module number (0 � 47)

Description Sets whether or not a diagnostic message is to be displayed after� a limit value set with parameters 15 � 22 is exceeded or not reached� value falls below the minimum sensor temperature range� value exceeds the maximum sensor temperature range.The limit value monitoring can be set for the individual channels independently ofeach other.

Bit Bit 0/1: channel 0Bit 2/3: channel 1Bit 4/5: channel 2Bit 6/7: channel 3

Values Channel 3 Channel 2 Channel 1 Channel 0Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 No limit value

monitoring (presetting)0 1 0 1 0 1 0 1 Diagnostic message in

value falls below the set limit value

1 0 1 0 1 0 1 0 Diagnostic message if value exceeds the the set limit value

Remark Only the falling below or exceeding the limit value can be monitored. The limitvalue is set separately for each channel with parameters 15 � 22 (see Tab.�4/15).The limit value monitoring of the sensor temperature range is activated as soonas the diagnosis for the set limit value becomes active.

Tab.�4/11: Activating the limit value monitoring channel x

Page 146:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−22 Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Measured value smoothing channel x

Function no. 4828 + m * 64 + 9 (channel 0 � 3) m = module number (0 � 47)

Description Sets whether or not the measured values of the individual channels are to besmoothed. The parameter can be set for the individual channels independently ofeach other.

Bit Bit 0/1: channel 0Bit 2/3: channel 1Bit 4/5: channel 2Bit 6/7: channel 3

Values Channel 3 Channel 2 Channel 1 Channel 0Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 No measured value

smoothing (presetting)0 1 0 1 0 1 0 1 Smoothing 2 values1 0 1 0 1 0 1 0 Smoothing 4 values1 1 1 1 1 1 1 1 Smoothing 8 values

Remark Interference can be suppressed with the measured value smoothing.

Tab.�4/12: Measured value smoothing channel x

Channel parameters: Sensor connection designs channel x

Function no. 4828 + m * 64 + 10 m = module number (0 � 47)

Description Set the connection design of the temperature sensor for the channels. The para�meter can be set for the individual channels independently of each other.

Bit Bit 0/1: sensor connection design channel 0Bit 2/3: sensor connection design channel 1Bit 4/5: sensor connection design channel 2Bit 6/7: sensor connection design channel 3

Values Channel 3 Channel 2 Channel 1 Channel 0Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 2−cable (presetting)0 1 0 1 0 1 0 1 3−cable1 0 1 0 1 0 1 0 4−cable

Remark For sensor connection designs see section 4.3.3

Tab.�4/13: Sensor connection designs channel x

Page 147:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−23Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Sensor type/temperature coefficient, temperature range channel x

Function no. 4828 + m * 64 + 11 (channel 0) m = module number (0 � 47)4828 + m * 64 + 12 (channel 1)4828 + m * 64 + 13 (channel 2)4828 + m * 64 + 14 (channel 3)

Description Sets the temperature sensor used for the channels. If necessary, set the tempe�rature range for Pt sensors. The parameters can be set for the individual channelsindependently of each other.

Bit Bit 0 � 3: sensor type with temperature coefficient (TK)Bit 4 � 6: reservedBit 7: temperature range (only for Pt sensors)

Values Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 Channel is deactivatedSensor type Pt sensors:� 0 0 0 0 0 0 1 Pt 100 with TK = 0.00385

(presetting)� 0 0 0 0 0 1 0 Pt 200 TK = 0.00385� 0 0 0 0 0 1 1 Pt 500 TK = 0.00385� 0 0 0 0 1 0 0 Pt 1000 TK = 0.00385� 0 0 0 0 1 0 1 Pt 100 TK = 0.00391� 0 0 0 0 1 1 0 Pt 200 TK = 0.00391� 0 0 0 0 1 1 1 Pt 500 TK = 0.00391� 0 0 0 1 0 0 0 Pt 1000 TK = 0.00391Sensor type Ni sensors:� 0 0 0 1 0 0 1 Ni 100 TK = 0.00617� 0 0 0 1 0 1 0 Ni 120 TK = 0.00617� 0 0 0 1 0 1 1 Ni 500 TK = 0.00617� 0 0 0 1 1 0 0 Ni 1000 TK = 0.00617Temperature range for Pt sensors:0 0 0 0 � � � � Standard (presetting)1 0 0 0 � � � � Climate

� = not relevant here

Remark The temperature range can only be set for Pt sensors:Temperature range standard: −200 � +850 °C (−328 � 1562 °Fahrenheit)Temperature range climate: −120 � +130 °C (−184 � 266 °Fahrenheit)

Tab.�4/14: Sensor type/temperature coefficient, temperature range channel x

Page 148:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−24 Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Definition Limit value for channel x

Function no. Limit values: m = module number (0 � 47)4828 + m * 64 + 15 (channel 0, low byte)4828 + m * 64 + 16 (channel 0, high byte)4828 + m * 64 + 17 (channel 1, low byte)4828 + m * 64 + 18 (channel 1, high byte)4828 + m * 64 + 19 (channel 2, low byte)4828 + m * 64 + 20 (channel 2, high byte)4828 + m * 64 + 21 (channel 3, low byte)4828 + m * 64 + 22 (channel 3, high byte)

Description One limit value can be set for each of the individual channels.

Bit Bit 0 � 7: high byte or low byte of the limit value

Values Complement of two binary format in 1/10 °C or °Fahrenheit.Presetting: Limit value = 0 (low byte = 0; high byte: 0)

Remark With parameter 8 you can set whether a diagnostic message is to be displayedwhen the limit value is exceeded or not reached (see Tab.�4/11 and section 4.4.5).

Tab.�4/15: Definition limit value for channel x

Page 149:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−25Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Force channel x

Function no. Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).

Description The Force function permits the manipulation of analogue values irrespective ofthe actual input signal (see also CPX system manual). This can be accomplishedwith the following parameters:� Force mode inputs channel x� Force state inputs channel x

Values � Force mode inputs channel x: 0 = blocked (presetting)1 = Force state

� Force state inputs channel x: 0 = reset value (presetting)1 = set value

Remark The enabling of the Force function with the parameter �Force mode outputschannel x" depends on the field bus protocol and is accomplished:� by an individual parameter setting or bit (e.g. CPX−FB11),� by setting all parameter bits of the relevant word (e.g. CPX−FB6) to �blocked"

or �Force state".For parametrizing the Force state, the desired input word must be correspondin�gly mapped in the parameter bits �Force state inputs channel x".The enabling of the Force function for the complete CPX terminal is carried outwith the system parameter �Force mode" (see CPX system manual).

Tab.�4/16: Force channel x (channel−specific)

Page 150:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−26 Festo P.BE−CPX−AX−EN en 0811d

4.4.4 Monitoring wire fracture/short circuit

With appropriate parametrizing, a wire fracture (open load)and short−circuit monitoring can be activated (see Tab.�4/10).

4.4.5 Limit value monitoring by parametrizing

With the channel−specific parameters �Definition limit value"(parameters 15 � 22) you can define a limit value for eachchannel. With the parameter �Limit value monitoring" (para�meter 8), you can define whether a diagnostic message is tobe displayed when the limit value is exceeded or not reached.

NoteIf you are using a different temperature sensor from thePt�100: Set the sensor used with the parametrizing.Monitoring of the sensor temperature range functionscorrectly as follows:

Parametrizing the limitvalue monitoring 1)

Set limit value 2)

is not reachedSet limit value 2)

is exceededSensortemperature range

�No diagnosis" No message No message No message

�Message if limit value isnot reached"

Diagnostic messagefault no. 9

No message Diagnostic messageIf limit value is notreached 9

�Message if limit value isexceeded"

No message Diagnostic messagefault no. 10

reached 9If limit value isexceeded 10

1) See Tab.�4/112) See Tab.�4/15

Tab.�4/17: Effect of limit value monitoring on the diagnostic messages

Page 151:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−27Festo P.BE−CPX−AX−EN en 0811d

The following table shows examples for setting limit valueswith parameters. The limit values are specified in 1/10 °C or°Fahrenheit.

Setting of limit value = 42° = 42 * 10 = 420

D7 D6 D5 D4 D3 D2 D1 D0

1 0 1 0 0 1 0 0 Channel x, low byte

0 0 0 0 0 0 0 1 Channel x, high byte

Setting of limit value = −30° = −30 * 10 = −300

D7 D6 D5 D4 D3 D2 D1 D0

1 1 0 1 0 1 0 0 Channel x, low byte

1 1 1 1 1 1 1 0 Channel x, high byte

Tab.�4/18: Example: Parametrizing of limit values for channel x

4.4.6 Measured value smoothing by parametrizing

In order to suppress interference, there is the possibility ofdigitally smoothing the input data, whereby the degree ofsmoothing can be set by parametrizing (see Tab.�4/12).

Smoothing is carried out as follows:

� by forming the sum of n values,

� by subtracting an average value,

� by adding the current input value.

The following applies here: the greater n, the more the signalwill be smoothed.

Page 152:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−28 Festo P.BE−CPX−AX−EN en 0811d

4.5 Diagnosis

Specific faults of the analogue input modules are registeredor suppressed depending on the module parametrizing.

The faults are shown on−the−spot with the Module Error LEDand the relevant Channel Error LED (see Fig.�4/6) and can be

evaluated with the handheld.

Depending on the module parametrizing, the faults are sentto the field bus node, where they can be evaluated accordingto the field bus protocol used.

Representation of the faults in the various field bus nodesdepends on the field bus protocol (see manual for the fieldbus node).

Page 153:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−29Festo P.BE−CPX−AX−EN en 0811d

4.5.1 Error messages of the analogue input modules

An analogue input module can register the following faults:

Fault number Description Fault treatment

2 Short circuit/overload 1)

Short circuit in sensor supply (VEL/SEN).(see parameter �Diagnostic message inthe event of wire fracture or shortcircuit")

· Eliminate short circuit or check con�nected sensorsThe sensor power supply will beswitched on again automaticallywhen the short circuit is eliminated.

3 Wire fracture 1) · Check and, if necessary, replace thecable and connected sensors

9 Limit value not reached 1)

Set limit value not reached or sensortemperature range not reached(see parameter �Limit value monitoringchannel x" or �Definition limit valuechannel x")

· Check parametrizing of sensor typeand connection design

· Check input signal present· Check parametrized limit value· If necessary, deactivate monitoring

10 Limit value exceeded 1)

Set limit value exceeded or sensortemperature range exceeded(see parameter �Limit value monitoringchannel x" or �Definition limit valuechannel x")

· Check parametrizing of sensor typeand connection design

· Check input signal present· Check parametrized limit value· If necessary, deactivate monitoring

1) The module will register the appropriate fault depending on the parametrizing. The analogue input signals will, however, be processed further.

Tab.�4/19: Error messages of the input modules � part 1

Page 154:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−30 Festo P.BE−CPX−AX−EN en 0811d

Fault number Description Fault treatment

15 Module/channel failed 2)

General fault, module faulty.· Power off/on necessary· If this fault occurs again: check

and, if necessary, replace theanalogue input module.

Evaluation of the analogue inputsignals has stopped.

29 Fault in parametrizing 1) 3)

A fault has occurred in the setting of aparameter:� wire fracture� connection design of the sensor� sensor type and temperature range.

· Check the parametrizingundertaken and, if necessary,undertake the parametrizing againwith the correct parameters (validparameters see section 4.4.3).

The analogue input module will beoperated further with the last validparametrizing.

1) The analogue input signals will, however, be processed further.2) Processing of the analogue input signals will be stopped. This error message will be triggered by

the field bus node.3) The parameters entered will be ignored, the module operates with the last valid parameters.

Tab.�4/20: Error messages of the input modules � part 2

NotePlease note the following when using the input modules:

� If there is a short circuit, all sensor supplies of themodule will be switched off together.

� The sensor power supply will be switched on againautomatically when the short circuit is eliminated.

Page 155:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−31Festo P.BE−CPX−AX−EN en 0811d

4.5.2 LED display

LEDs are situated under the transparent cover of the modulefor diagnosing the input modules.

1 Channel fault LEDs(red)

2 Module fault LED(red)

4AE−T

1

CPX−4AE−T

2

Fig.�4/6: LED displays of the temperature module

Page 156:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−32 Festo P.BE−CPX−AX−EN en 0811d

Error LEDs

The red error LEDs indicate channel or module faults depend�ing on the parametrizing.

Error LEDchannel x 1)

Modulefault LED

Installation Faultnumber

Fault treatment

LED is out LED is out

Faultless operation � None

LED lights up LED lights up

Fault short circuit channel x

orFault wire fracture channel x

2

3

Eliminate shortcircuit or checkconnected sensors

Check and, ifnecessary, replacethe cable andconnected sensors.

LED flashes LED lights up

Limit value not reachedSet limit value not reached orsensor temperature range notreached

orLimit value exceededSet limit value exceeded orsensor temperature rangeexceeded

9

10

See section 4.5.1,Tab.�4/19

LED lights up LED flashes

Parametrizing faults 29 See section 4.5.1,Tab.�4/20

LED flashes LED is out

Servicing required 255 Replace module

1) One LED per channel

Tab.�4/21: Error LEDs of the temperature module CPX−4AE−T

Page 157:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−33Festo P.BE−CPX−AX−EN en 0811d

4.5.3 Error treatment and parametrizing

The following diagrams show the fault treatment in the ana�logue input modules. With the appropriate module para�meter, represented in the diagram as a switch, further regis�tering and display of the fault can be suppressed as desired.The parameters are described in section 4.4.3.

2

Fault message tofield bus node

Fault no. 3

Wire fracturechannel x

Monitoring wirefracture/shortcircuit channel x

Moduleerror LED

10 1Monitoring wirefracture/shortcircuit channel x

0 1

Fault no. 2

Short circuitchannel x

Error LEDchannel x

2

1 Channel−specific parameter (switch position represented = default setting)

2 Channel−specific faults

Fig.�4/7: Principle of fault treatment and parametrizing CPX−4AE−T � part 1

Page 158:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

4. Analogue input module CPX−4AE−T

4−34 Festo P.BE−CPX−AX−EN en 0811d

2

Fault no. 10

Limit valueexceededchannel x

1

Fault message tofield bus node

Moduleerror LED

Fault no. 9

Limit value not reachedchannel x

Fault no. 29

Parametrizingfaults channel x

Limit valuemonitoringchannel x

0 1Limit valuemonitoringchannel x

0 1

Error LEDchannel x

Error LEDchannel x

Moduleerror LED

3

0 1Monitoringparametri−zing faults

4

1 Channel−specific parameter(switch position represented = default setting)

2 Module−specific parameter

3 Channel−specific faults

4 Module fault

Fig.�4/8: Principle of fault treatment and parametrizing CPX−4AE−T � part 2

Page 159:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Analogue input module CPX−4AE−TC

5−1Festo P.BE−CPX−AX−EN en 0811d

Chapter 5

Page 160:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−2 Festo P.BE−CPX−AX−EN en 0811d

Contents

5. Analogue input module CPX−4AE−TC 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.1 Function of the analogue input module CPX−4AE−TC 5−4 . . . . . . . . . . . . . . . . . . .

5.2 Assembly 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3 Installation 5−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.1 Pin allocation 5−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.2 Introduction to temperature measurement by means of thermocouples 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.3 Cold junction compensation 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.3.4 Connecting temperature sensors to the analogue inputs 5−14 . . . . . . . .

5.4 Instructions on commissioning 5−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.4.1 Processing the input signals of temperature sensors 5−15 . . . . . . . . . . .

5.4.2 General information on parametrizing 5−18 . . . . . . . . . . . . . . . . . . . . . . .

5.4.3 Parameters of analogue input module type CPX−4AE−TC 5−19 . . . . . . . .

5.5 Diagnostics 5−31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.5.1 Fault messages of the analogue input modules 5−32 . . . . . . . . . . . . . . .

5.5.2 LED displays 5−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

5.5.3 Fault treatment and parametrizing 5−35 . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 161:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−3Festo P.BE−CPX−AX−EN en 0811d

Contents of this chapter This chapter describes the analogue input moduleCPX−4AE−TC.

This module makes analogue inputs available to the CPXterminal for registering the temperature. It can be adapted forthe specific application by means of various sub−bases.

Further information An overview of the modular structure of a CPX terminal, themodular connection technology as well as the displays andconnecting elements can be found in chapter 1.

Information on mounting the complete CPX terminal, connect�ing the power supply as well as general instructions on con�figuration and parametrizing can be found in the CPX systemmanual.

Information on the address assignment as well as on commis�sioning can be found in the appropriate field bus node man�ual or function module manual.

Page 162:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−4 Festo P.BE−CPX−AX−EN en 0811d

5.1 Function of the analogue input module CPX−4AE−TC

The module CPX−4AE−TC makes available 4 inputs forconnecting thermocouple temperature sensors.

Type Description

CPX−4AE−TC Provides 4 analogue inputs(input channels) for registeringthe temperature.

� Connecting thermocouples (TC) in 2−cable design

� Module cycle time: 250 ms

TC sensors supported:� E, J, T, K, N, S, B, R

Signal ranges of the individualsensor types:

EJTKNSBR

−200 � 900 °C−200 �1200 °C−200 � 400 °C−200 �1370 °C

0 � 1300 °C0 �1760 °C

400 �1820 °C0 �1760 °C

60 V/°C51 V/°C40 V/°C40 V/°C38 V/°C11 V/°C8 V/°C

12 V/°C

Tab.�5/1: Overview of analogue input module CPX−4AE−TC

5.2 Assembly

See section 1.3.

Page 163:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−5Festo P.BE−CPX−AX−EN en 0811d

5.3 Installation

WarningSudden unexpected movement of the connected actuatorsand uncontrolled movements of loose tubing can causeinjury to human beings or damage to property.

Switch off the following equipment before undertakinginstallation and/or maintenance work:

� Compressed air supply

� Operating and load voltage supplies

In the following sections you will find the pin assignments ofthe analogue input modules for the different sub−bases.

Instructions on connecting the cables and plugs to the sub−bases can be found in section 1.2.3.Note in particular the instructions on connecting the cablescreening to functional earth (FE).

Page 164:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−6 Festo P.BE−CPX−AX−EN en 0811d

5.3.1 Pin allocation

Pin assignment CPX−4AE−TC with sub−baseCPX−M−4−M12x2−5POL or CPX−AB−4−M12x2−5POL (−R)

Analogue I−module type CPX−4AE−TC with sub−base CPX−AB−4−M12x2−5POL (−R)

Sub−base Pin assignment X1, X2 (inputs 0, 1)

Pin assignment X3, X4 (inputs 2, 3)

2

3

1

5

4

X1

Socket X1:1: CJC02: U0+3: CJC0’4: U0−5: FE (screening) 1)

2

3

1

5

4

X3

Socket X3:1: CJC22: U2+3: CJC2’4: U2−5: FE (screening) 1)

2

3

1

5

4

X2Socket X2:1: CJC12: U1+3: CJC1’4: U1−5: FE (screening) 1)

2

3

1

5

4

X4Socket X4:1: CJC32: U3+3: CJC3’4: U3−5: FE (screening) 1)

CJC = cold junction compensation (CJC), by means of RTD temperature sensor Pt�1000)

Ux+ = input signal (TC sensor, cable 1)Ux− = input signal (TC sensor, cable 2)FE = functional Earth1) With CPX−AB−4−M12x2−5POL−R the metal thread is connected to FE

Tab.�5/2: Pin assignment for analogue input module type CPX−4AE−TC with sub−baseCPX−AB−4−M12x2−5POL�(−R)

CPX−AB−4−M12x2−5POL−R The metal thread (�...−R") of this sub−base is connectedinternally with pin 5 (Functional earth FE).

Page 165:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−7Festo P.BE−CPX−AX−EN en 0811d

Pin assignment CPX−4AE−TC with sub−baseCPX−AB−8−KL−4POL

Analogue input module type CPX−4AE−TC with sub−base CPX−AB−8−KL−4POL

Sub−base Pin assignment X1 � X4 (inputs 0, 1)

Pin assignment X5 � X8 (inputs 2, 3)

X1

X2

.0

.1

.2

.3

.0

.1

.2

.3

X1.0: CJC0X1.1: CJC0’X1.2: U0−X1.3: FE (screening)

X2.0: n.c.X2.1: n.c.X2.2: U0+X2.3: FE (screening)

X5

X6

.0

.1

.2

.3

.0

.1

.2

.3

X5.0: CJC2X5.1: CJC2’X5.2: U2−X5.3: FE (screening)

X6.0: n.c.X6.1: n.c.X6.2: U2+X6.3: FE (screening)

X3

X4

.0

.1

.2

.3

.0

.1

.2

.3

X3.0: CJC1X3.1: CJC1’X3.2: U1−X3.3: FE (screening)

X4.0: n.c.X4.1: n.c.X4.2: U1+X4.3: FE (screening)

X7

X8

.0

.1

.2

.3

.0

.1

.2

.3

X7.0: CJC3X7.1: CJC3’X7.2: U3−X7.3: FE (screening)

X8.0: n.c.X8.1: n.c.X8.2: U3+X8.3: FE (screening)

CJC = cold junction compensation (CJC),by means of RTD temperature sensor Pt�1000)

Ux+ = input signal (TC sensor, cable 1)Ux− = input signal (TC sensor, cable 2)FE = functional Earth

Tab.�5/3: Pin assignment for analogue input module type CPX−4AE−TC with sub−baseCPX−AB−8−KL−4POL

Page 166:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−8 Festo P.BE−CPX−AX−EN en 0811d

5.3.2 Introduction to temperature measurement by means ofthermocouples

Thermocouples (TCs) consist of two different metal conduc�tors that are connected (e.g. soldered or welded) at one end(���1 and 2 in Fig.�5/1). At the connection point 3 a touchvoltage is created that depends on the conductor materialsand the ambient temperature, the so−called thermoelectricvoltage.

If one connects the free ends of the two conductors (���4 inFig.�5/1), a temperature−dependent touch voltage/thermo�electric voltage is also created at this connection point.

If there is a temperature difference between the two TC con�nection points (���3 and 4���), then the result is a thermoelectriccurrent.

This thermoelectric effect, which is also called the �Seebeckeffect" for its discoverer, Thomas Johann Seebeck, can be usedfor measuring purposes, e.g. for registering temperatures.

1 Thermocouplecable 1 of material1, e.g. iron

2 Thermocouplecable 2 ofmaterial 2, e.g.copper/nickel

Together cables 1and 2 form athermocouple (TC)

3 �Measuringjunction"(sensor�tip)

4 Referencejunction(�Cold�junction")

Ux+

Uxz

2

34

1

Fig.�5/1: Fundamental principle of a thermocouple (TC)

Page 167:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−9Festo P.BE−CPX−AX−EN en 0811d

The thermoelectric effect(�Seebeck effect") intechnical applications

Two different metal conductors are connected to each otherat one end. At the other end, the so−called reference junc�tion or connection point to a measurement device (see 4 inFig.�5/2) a thermoelectric voltage can be created if there is atemperature difference between the connection point, i.e.the measuring junction or sensor tip, and the connectionpoint of the measurement device.

This thermoelectric voltage is temperature−dependent, andfor metals (pure metals or alloys) has a value of a few micro�volts per kelvin. The relationship between voltage and tem�perature (U−T characteristic) is nearly linear for most puremetals.

1 Thermocouplecable 1 (of metal 1)

2 Thermocouplecable 2 (of metal 2)

3 Measuringjunction (sensor tip)

4 Referencejunction (connectionpoint)

5 Measurementdevice (e.g.voltmeter orCPX−4AE−TC)

6 Standardconnecting cable

2

3

4 1

Ux+

Uxz

5

6

6

4

Fig.�5/2: Fundamental principle of temperature measurement by means of thermocouples

Page 168:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−10 Festo P.BE−CPX−AX−EN en 0811d

When selecting a pair of materials for measuring purposes,the goals are a high thermoelectric voltage, high linearity andhigh corrosion resistance/low oxidation at high temperatures.These goals cannot be achieves with any one thermocoupleor combination of materials. Therefore different combinationsof materials are used depending on the intended application.

Typical TC sensors Widely used thermocouple combinations (sensor types):

� nickel−chrome/nickel−aluminium (−200 to 1370 °C)or nickel−chrome/nickel: Type K, frequently used sensor type with a broad rangeof application temperatures

� iron/copper−nickel (−200 to 1200 °C):Type J, one of the most commonly used thermocouples forindustrial applications due to relatively high Seebeckcoefficients and low costs

� platinum−rhodium/platinum (0 to 1760 °C):Type S, for high temperatures.

Because of the different characteristics of the thermocouplepairings, the sensor type must be selected very carefully. For points of reference and general conditions, please see therelevant standards and specifications, e.g. in IEC standard(DIN) EN 60584 and DIN�43722.

Advantages ofthermocouple sensors Thermocouple sensors are notable for their:

� Extensive temperature measuring ranges

� Quick registering of temperature changes (response time)

� Simple mechanical installation

� Ability to be used at high temperatures and in harshenvironments (if necessary in a sheathed thermocoupledesign or with the use of protective tubes).

Page 169:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−11Festo P.BE−CPX−AX−EN en 0811d

Avoid extending TC sensor cables. If necessary, extendthermocouple sensor cables exclusively with thermocouplecables (of original materials) or compensating cables(substitute materials) corresponding to the type of thethermocouple sensor, i.e. that have identical or compatiblecharacteristics, in order to keep the measuring errorsresulting from the extension small. For further informationsee e.g. the above−mentioned IEC standard or thecorresponding national version.

The temperature at the connection point of the TC sensor, i.e.at the reference junction or �cold junction" (���4 in Fig.�5/3/Fig.�5/1) must either be kept constant or recorded, and inboth cases is included in the evaluation of the measurementresults. The temperature module CPX−4AE−TC has the �coldjunction compensation" required for this (see section 5.3.3).

1 TC sensor cbl. 1 (of metal 1)

2 TC sensor cbl. 2 (of metal 2)

3 Measuringjunction (sensor tip)

4 Connection point(connecting pinsof CPX module)

5 Temperaturesensor (RTD,Pt�1000, Class�A)for cold junctioncompensation(CJC)

5

Ux+

Uxz

CJCx

CJCx’

2

3

4

1

Fig.�5/3: Connecting a thermocouple (TC) with cold junction compensation (CJC) totemperature module CPX−4AE−TC

Page 170:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−12 Festo P.BE−CPX−AX−EN en 0811d

5.3.3 Cold junction compensation

Cold junction compensation (CJC) is � besides selection of thea suitable sensor � one of the essential requirements for pre�cise measurements using thermocouples (TC). It eliminatesthe influence of the ambient temperature in the area sur�rounding the connection point on the module, i.e. in the areaaround the plug connectors or the terminal strip of the sub−base.

The cold junction compensation is necessary in order to pre�cisely measure the absolute temperature at the measuringjunction, i.e. at the sensor tip. Without�cold junction com�pensation the thermocouple measurement provides only�relative" measurement results: The measured value corre�sponds to the difference between the temperature/thermo�electric voltage at the sensor tip (���3 in Fig.�5/3) and the tem�perature (thermoelectric voltage) at the sensor connectionpoint (���4���).

The ambient temperature at the connection point, the refer�ence junction or the so−called �cold junction" (���4 in Fig.�5/3/Fig.�5/1) thus has a considerable effect on the measurementresult.

The temperature model of the CPX−4EA−TC has an internalcold junction compensation which may provide sufficientmeasuring accuracy for certain applications, such as wherethere are low requirements for measuring accuracy and anapproximately constant ambient temperature of about�25�°C(at the connection point of the module).

To do this, the internal cold junction compensation uses theinternally stored reference value of 25�°C. If the actual ambi�ent temperature deviates from this reference value, then theinternal cold junction compensation has a negative effect onthe accuracy of the measured values.

Please note that any deviation from this reference value isreflected 1:1 in the measurement results. 1�°C (or 1 °F) ofdifference leads to a 1�°C (or�1�°F) shift in the measuredtemperature values!

Page 171:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−13Festo P.BE−CPX−AX−EN en 0811d

If the temperature at the connection point significantly devi�ates from the internal reference value, or if high accuracy, i.e.exact temperature indications, are required, then a�Pt�1000temperature sensor of Class A must be used for cold junctioncompensation at each input. The Pt�1000 determines theactual temperature at the connection point.

The so−called external cold junction compensation of moduleCPX−4AE−TC takes into account the actual ambient tempera�ture as part of the evaluation of the measured results, andmakes the appropriately corrected measured temperaturevalues (measurement data) available at the module output.

For external cold junction compensation, all inputs must beprovided with their own Pt�1000.

Pt 1000 resistance temperature devices (RTDs) can beobtained from Festo as an individual sales item (seeappendix�A.9).

Fit the Pt 1000 temperature sensors in the immediate vicinityof the connection point of the thermocoupler (in the plug oron the terminal; see appendix A.8.3).

You can use parameter settings to choose between internaland external cold junction compensation.

Make sure that the value of the parameter �Cold junctioncompensation" has been set appropriately: for external coldjunction compensation to �0" or �external (PT1000)"(see�Tab.�5/12).

Further information on cold junction compensation, e.g.accessories, installation instructions and connectionexamples can be found in the following sections:

� Accessories: appendix A.9

� Installation instructions and connection examples: appendix A.8.3

� Introduction to temperature measurement by means ofthermocouples: section 5.3.2.

Page 172:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−14 Festo P.BE−CPX−AX−EN en 0811d

5.3.4 Connecting temperature sensors to the analogue inputs

Detailed information on connecting temperature sensors(thermocouples) to module CPX−4AE−TC can be found inappendix A.8.3.

The signal of a thermocouple is very vulnerable to interfer�ence. Therefore only screened/shielded cables are permittedfor transmission of the sensor signals (see section 1.2.3).

5.4 Instructions on commissioning

Basic setting (parametrizing)

By means of parametrizing it is possible to set the CPXtemperature module for the temperature sensors beingused (see Tab.�5/16).

The individual channels can be set separately; it is thuspossible to use up to four different thermocouples permodule.

The signal ranges of the individual temperature sensors areshown in Tab.�5/1.

In addition, the unit of measurement, limit value monitoring,the diagnostic reaction, and other functions can be adaptedby means of parametrizing. Instructions on this can be foundin the sections 5.4.2 and 5.4.3.

Tab.�5/7 and Tab.�5/8 provide an overview of the availableparameters.

Monitoring open load/short circuit

If desired, parametrizing can be used to activate the openload (OL) monitoring and short circuit (SC) monitoring foreach channel (see Tab.�5/13).

Page 173:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−15Festo P.BE−CPX−AX−EN en 0811d

Measured valuesmoothing

In order to suppress interference, there is the possibility ofdigitally smoothing the input data, whereby the degree ofsmoothing can be set by parametrizing (see Tab.�5/15).

Limit value monitoring The channel−specific �Limit value" parameters can be usedto define a limit value for each channel (see Tab.�5/17).

With the parameter �Limit value monitoring", you can definewhether a diagnostic message is to be displayed when thelimit value is overrun or underrun (see Tab.�5/14).

Monitoring 1) Limit value 2)

underrun overrun

Inactive (disabled) No diagnostic message

Limit value overrun Diagnostic message fault no. 9 No diagnostic message

Limit value overrun No diagnostic message Diagnostic message fault no. 10

1) see Tab.�5/142) see Tab.�5/17

Tab.�5/4: Effect of limit value monitoring on the diagnostic messages

5.4.1 Processing the input signals of temperature sensors

The analogue values are transmitted from the CPX terminalto the control system as input words (4 inputs, 64 bits). Eachtemperature module occupies 4 input words for this pro�cedure in the address range.

The position of the input words in the address range dependson the field bus used (see manual for the field bus node,P.BE−CPX−SYS−...).

Page 174:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−16 Festo P.BE−CPX−AX−EN en 0811d

Reaction with default settings

The module parameters are set as standard to these values:

� Unit of measurement: °C

� Interference frequency suppression: 50 Hz

� Cold junction compensation, abbreviated CJC: external CJC by means of Pt 1000 resistance temperaturedevice, RTD).

The channel−specific parameters are set as standard to thesevalues:

� Sensor type K � with the following specification:

� Cable 1 (Ux+): Ni−Cr sensor cable

� Cable 2 (Ux−): Ni−Al sensor cable

Further information can be found in IEC standardEN�60584.

� Temperature range −200 � +1370 °C

The complete parameter settings can be found insection�5.4.3.

The temperature values are transferred in the input word inthe data format �mathematical sign (VZ) + 15 bits, comple�ment of two, binary notation in tenths of a degree"(see�Tab.�5/5).

This means that measured data from −32767 to +32767 andmeasured values from −3276.7 °C/°F to +3276.7 °C/°F can bedepicted (possible range of values, see Tab.�5/6). The per�mitted range of values depends on the sensor being used(see Tab.�5/1).

Page 175:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−17Festo P.BE−CPX−AX−EN en 0811d

Data format �VZ + 15 bits compliment of two, binary notation in tenths of a degree"

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

Sign B14MSB

B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

Abbreviations used:VZ: mathematical sign (0 = positive value, 1 = negative value)B0 � B14: input valueD0 � D15: 16 bits input data fieldMSB/LSB: most significant bit / least significant bit

Tab.�5/5: Data format of temperature module CPX−4AE−TC

Type of measurement Possible value range Permitted value range

Temperature measurement withthermocouple (TC)

±3276.7 °C Depending on the sensortype (see Tab.�5/1)

Tab.�5/6: Value ranges

Fig.�5/4 shows the processing of the input signals of a type Kthermocouple in the nominal temperature range (example).

1 End values of thenominal temperaturerange

2 Temperature at themeasuring junction(example)

3 Signal representationafter the A−D con�verter and measuredvalue acquisition

4 Digital input word(in�decimal notation,example)

1

3−2000 +13700

−200 °C +1370 °C+42 °C

2

+420

4

1

Fig.�5/4: Representation of measured values (example)

Page 176:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−18 Festo P.BE−CPX−AX−EN en 0811d

5.4.2 General information on parametrizing

If desired, you can use parametrizing to set the sensor type,the unit of measurement, the diagnostic reaction, a limitvalue monitoring function and if necessary additionalfunctions.

Due in some cases to necessary calculations, modified para�meters are not valid until they have been thoroughly checkedand saved. Until then, as in the case of invalid parameters,the previous settings apply.

Depending on the parameter, no valid analogue values areavailable a max. of 30 ms after a value modification.

Special instructions on avoiding parametrizingfaults

Parametrize in this sequence:

1. Set temperature sensor.

2. Set limit value.

3. Activate limit value monitoring.

Page 177:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−19Festo P.BE−CPX−AX−EN en 0811d

5.4.3 Parameters of analogue input module type CPX−4AE−TC

An overview of all parameters

The following tables (Tab.�5/7 and Tab.�5/8) contain an over�view of the module parameters of the analogue input moduleCPX−4AE−TC.

Module parameters of CPX−4AE−TC � overview

Function number 1) Bit Module parameters Presetting Value

4828 + m * 64 + 0 0 � 67

Reserved

Monitoring the CPX module, here parametrizing faults

active

1

4828 + m * 64 + 1 ... 5 0 � 7 Reserved � �

4828 + m * 64 + 6 0 � 23

4

5 � 67

Reserved

Unit of measurement for temperature(°�Celsius or °�Fahrenheit)

Interference frequency suppression(50�Hz or 60�Hz)

Reserved

Cold junction compensation (external,

by means of Pt 1000−RTD, or internal,fixed to reference temperature 25 °C)

°C

50 Hz

external(Pt�1000)

0

0

0

1) m = module number (counting mode: from left to right, beginning with 0)

Tab.�5/7: Module parameters � overview

Page 178:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−20 Festo P.BE−CPX−AX−EN en 0811d

Channel−specific module parameters of CPX−4AE−TC � overview

Function number 1) Bit Module parameters Presetting Value

4828 + m * 64 + 7 0 � 7 Monitoring open load/short circuit,each separately for channels 0 � 3

disabled 0

4828 + m * 64 + 8 0 � 7 Monitoring of limit values each separately for channels 0 � 3

disabled 0

4828 + m * 64 + 9 0 � 7 Measured value smoothing, each separately for channels 0 � 3

None 0

4828 + m * 64 + 10 � 13 0 � 7 Setting the sensor type, each separately for channels 0 � 3

Type K 4

4828 + m * 64 + 14 � 21 0 � 7 Limit values, each separately for channels 0 � 3

0 0

� 2) � 2) Forcing, channel x 2) � �

1) m = module number (counting mode: from left to right, beginning with 0)2) Access is protocol−specific (see manual for the field bus node, P.BE−CPX−FB..., and CPX system

manual, P.BE−CPX−SYS...)

Tab.�5/8: Channel−specific module parameters � overview

Page 179:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−21Festo P.BE−CPX−AX−EN en 0811d

Detailed description of the individual parameters

Module parameter: Monitoring the CPX module, here parametrizing faults

Handheld display

Function no. 4828 + m * 64 + 0; m = module number (0 � 47)

Description For this input module the monitoring of parametrizing faults can be activated ordeactivated (suppressed). When monitoring is active, parametrizing faults:� are indicated by the module fault LED� sent to the CPX field bus node

Bit MonitoringBit 0 � 6: ReservedBit 7: Monitoring parametrizing faults

[Monitor]

[Monitor parameters]

Values 0 = inactive1 = active (presetting)

[Inactive][Active]

Note The following parameters are checked for invalid values when the parametersettings are made:� Sensor type channel x� Unit of measurement for temperature� Interference frequency suppression� Cold junction compensation

Tab.�5/9: Monitoring the CPX module, here parametrizing faults

Page 180:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−22 Festo P.BE−CPX−AX−EN en 0811d

Module parameter: Unit of measurement for temperature Handheld display

Function no. 4828 + m * 64 + 6; m = module number (0 � 47)

Description The the unit of measurement for temperature values can be switched to either:� °�Celsius� °�Fahrenheit

Bit Bit 3: Measuring unit for temperature [Temp. scale]

Values 0 = °Celsius (presetting)1 = °Fahrenheit

[°C][°F]

Note The setting for the unit of measurement refers to all temperature specifications,e.g. to the recorded measured values, and also to limit values (see Tab.�5/17).Limit values already saved are not automatically converted. After conversion ofthe unit of measurement it is therefore necessary to convert the limit values andre−enter them.Converting temperature units:� (x °C * 9/5) + 32 Z y °F� (m °F − 32) * 5/9 Z n °C

Tab.�5/10: Unit of measurement for temperature

Module parameter: Interference frequency suppression Handheld display

Function no. 4828 + m * 64 + 6; m = module number (0 � 47)

Description The module−internal interference frequency suppression has to be set to themains frequency of the power supply. Select the appropriate value:� 50 Hz� 60 Hz

Bit Bit 4: Interference frequency suppression [Noise rejection]

Values 0 = 50 Hz (presetting)1 = 60 Hz

[50 Hz][60 Hz]

Tab.�5/11: Interference frequency suppression

Page 181:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−23Festo P.BE−CPX−AX−EN en 0811d

Module parameter: Cold junction compensation Handheld display

Function no. 4828 + m * 64 + 6; m = module number (0 � 47)

Description Defines whether the following is used for cold junction compensation (CJC):� external Pt 1000 resistance temperature devices (RTDs),� or the internal reference value (25 °C) is used

Bit Bit 7: cold junction compensation [Cold junction compensation]

Values 0 = external cold junction compensation(Pt 1000 resistors connected; pre−setting)

1 = internal cold junction compensation (fixed to 25 °C)

[external (PT1000)]

[internal (25 °C)]

Note Cold junction compensation (CJC) is necessary for precise measurements usingthermocouples (TC). Cold junction compensation eliminates the effect of theambient temperature in the area surrounding the connection point on themodule.With the setting �internal (25 °C)", the module uses the internally storedreference value of 25�°C from cold junction compensation.If the temperature at the connection point significantly deviates from the internalreference value, or if high accuracy, i.e. exact temperature indications, arerequired, then a�Pt 1000 temperature sensor of Class A must be used for coldjunction compensation at each input.Make sure that the value of the parameter �Cold junction compensation" is set to�0" or �external (PT1000)"

Further information on cold junction compensation and a brief introduction to themeasuring method can be found in the following sections:� Accessories: appendix A.9� Installation instructions and connection examples: appendix A.8.3� Explanation of cold junction compensation: section 5.3.3� Introduction to temperature measurement by means of thermocouples:

section 5.3.2

Tab.�5/12: Cold junction compensation

Page 182:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−24 Festo P.BE−CPX−AX−EN en 0811d

Module parameter: Monitoring�open load/short circuit Handheld display

Function no. 4828 + m * 64 + 7 (channel 0 � 3); m = module number (0 � 47)

Description Defines whether or not a diagnostic message is to be displayed after wire openload or short circuit. The parameter can be set for the individual channelsindependently of each other.

Bit Diagnosis of open load/short circuit sensorBits 0/1: channel 0Bits 2/3: channel 1Bits 4/5: channel 2Bits 6/7: channel 3

[Monitoring OL/SC Sensor]

Values Channel 3 Channel 2 Channel 1 Channel 0

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0 0 0 0 0 0 0 0 No diagnostic message(presetting)

0 1 0 1 0 1 0 1 Diagnostic message in theevent of open load or short circuit

00 = disabled (presetting)01 = enabled

[Disabled][Enabled]

Tab.�5/13: Monitoring open load/short circuit (channel−specific)

Page 183:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−25Festo P.BE−CPX−AX−EN en 0811d

Module parameter: Monitoring of limit values Handheld display

Function no. 4828 + m * 64 + 8 (channel 0 � 3); m = module number (0 � 47)

Description Defines whether or not a diagnostic message is to be displayed after� Underrunning a limit value set with parameter 15 � 22 and leaving the sensor

temperature range� Overrunning a limit value set with parameter 15 � 22 and leaving the sensor

temperature rangeThe limit value monitoring can be set for the individual channels independently ofeach other.

Bit Limit value monitoringBits 0/1: channel 0Bits 2/3: channel 1Bits 4/5: channel 2Bits 6/7: channel 3

[Monitoring limit value]

Values Channel 3 Channel 2 Channel 1 Channel 0

Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0

0 0 0 0 0 0 0 0 No limit value monitoring (presetting)

0 1 0 1 0 1 0 1 Diagnostic message if value underruns the set limit value and leaving the sensor temperature range

1 1 1 1 1 1 1 1 Diagnostic message if value overruns the set limit value and leaving the sensor temperature range

00 = disabled (presetting)01 = diagnostic message if underrun10 = diagnostic message if overrun

[disabled] :[Diag at limit underrun][Diag at limit overrun]

Note Only the underrunning or overrunning of the limit value can be monitored. The limit value is set separately for each channel with parameters 14 � 21 (see Tab.�5/17).The limit value monitoring of the sensor temperature range is activated as soonas the diagnosis for the set limit value becomes active.

Tab.�5/14: Monitoring limit values (channel−specific)

Page 184:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−26 Festo P.BE−CPX−AX−EN en 0811d

Module parameter: Measured value smoothing Handheld display

Function no. 4828 + m * 64 + 9 (channel 0 � 3); m = module number (0 � 47)

Description To suppress faults, the input data can be smoothed digitally. You can activate andset this function and the necessary degree of smoothing separated for eachchannel.The smoothing is performed using the averaging method over a certain numberof measured values (so−called moving average method, here over two, four oreight values, see �Values" line in the table).

Bit Measured value smoothingBits 0/1: channel 0Bits 2/3: channel 1Bits 4/5: channel 2Bits 6/7: channel 3

[Filter measured values]

Values Channel 3 Channel 2 Channel 1 Channel 0Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 no measur. value smoothing

(presetting)0 1 0 1 0 1 0 1 Smoothing 2 values1 0 1 0 1 0 1 0 Smoothing 4 values1 1 1 1 1 1 1 1 Smoothing 8 values

Note The following applies here: the greater the number of measured values, the morethe signal will be smoothed.The measured value smoothing has no effect on the continuous transmission ofthe measured data or the module cycle time.

Tab.�5/15: Measured value smoothing (channel−specific)

Page 185:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−27Festo P.BE−CPX−AX−EN en 0811d

Module parameter: Sensor type Handheld display

Function no. 4828 + m * 64 + 10 (channel 0); m = module number (0 � 47)4828 + m * 64 + 11 (channel 1)4828 + m * 64 + 12 (channel 2)4828 + m * 64 + 13 (channel 3)

Description The sensor type can be set separately for each channel.

Bit Setting the sensor typeBits 0 � 4: sensor typeBits 5 � 7: reserved

[Sensor setup]

Values Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 00 0 0 0 0 0 0 0 no sensor

(channel deactivated)Sensor type thermocouples [Type ...] *)�:

0 0 0 0 0 0 0 1 Type E0 0 0 0 0 0 1 0 Type J0 0 0 0 0 0 1 1 Type T0 0 0 0 0 1 0 0 Type K0 0 0 0 0 1 0 1 Type N0 0 0 0 0 1 1 0 Type S0 0 0 0 0 1 1 1 Type B0 0 0 0 1 0 0 0 Type R

Note *) Type indication on handheld

Further information on the individual sensor types can be found in Tab.�5/1.

Tab.�5/16: Sensor type (channel−specific)

Page 186:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−28 Festo P.BE−CPX−AX−EN en 0811d

Module parameter: Limit value Handheld display

Function no. Limit value channels 0 � 3; m = module number (0 � 47)4828 + m * 64 + 14 (channel 0, low byte)4828 + m * 64 + 15 (channel 0, high byte)4828 + m * 64 + 16 (channel 1, low byte)4828 + m * 64 + 17 (channel 1, high byte)4828 + m * 64 + 18 (channel 2, low byte)4828 + m * 64 + 19 (channel 2, high byte)4828 + m * 64 + 20 (channel 3, low byte)4828 + m * 64 + 21 (channel 3, high byte)

Description One limit value can be set for each of the individual channels.

Bit Limit valueBits 0 � 7: high byte or low byte of the limit value

[Limit value]

Values Complement of two binary format in 1/10 °Celsius or °Fahrenheit.Presetting: Limit value = 0 (low byte: 0; high byte: 0).

Note With parameter 8 you can set whether a diagnostic message is to be displayedwhen the limit value is underrun or overrun (see Tab.�5/14).

Tab.�5/17: Limit value (channel−specific)

The temperature unit (°�Celsius or °�Fahrenheit) is dependenton the setting for the parameter �Unit of measure fortemperature" (see Tab.�5/10). Make sure that the necessarysetting has been saved in the module.

Page 187:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−29Festo P.BE−CPX−AX−EN en 0811d

The following table shows examples for setting limit valueswith parameters. The limit values are specified in tenths of adegree (1/10�°).

Example: �420" = 42.0�°

Setting of limit value = 42° = 42 * 10 = 420

D7 D6 D5 D4 D3 D2 D1 D0

1 0 1 0 0 1 0 0 Channel x, low byte

0 0 0 0 0 0 0 1 Channel x, high byte

Tab.�5/18: Example 1: Parametrizing of limit values for channel x

Setting of limit value = −30° = −30 * 10 = −300

D7 D6 D5 D4 D3 D2 D1 D0

1 1 0 1 0 1 0 0 Channel x, low byte

1 1 1 1 1 1 1 0 Channel x, high byte

Tab.�5/19: Example 2: Parametrizing of limit values for channel x

Page 188:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−30 Festo P.BE−CPX−AX−EN en 0811d

Module parameter: Forcing channel x

Function no. Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node, P.BE−CPX−FB...).

Description The Force function permits the manipulation of analogue values irrespective of theactual input signal (see also CPX system manual, P.BE−CPX−SYS−...).This can be accomplished with the following parameters:� Force mode inputs channel x� Force state inputs channel x

Values � Force mode inputs channel x: 0 = blocked (presetting)1 = Force state

� Force state inputs channel x: 0 = reset value (presetting)1 = set value

Note The enabling of the Force function for the complete CPX terminal is carried out withthe system parameter �Force mode" (see CPX system manual P.BE−CPX−SYS−...).Channel−specific enabling (for forcing) is performed with the parameter �Forcemode inputs channel x" (in accordance with the field bus protocol � see descriptionfor field bus node P.BE−CPX−FB...).For parametrizing the Force state, the desired input word must be mapped in theparameter bits �Force state inputs channel x."

Tab.�5/20: Force channel x (channel−specific)

Page 189:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−31Festo P.BE−CPX−AX−EN en 0811d

5.5 Diagnostics

Specific faults of the analogue input modules are registeredor suppressed depending on the module parametrizing.

The faults are shown on−the−spot with the Module Fault LEDand the relevant Channel Fault LED (see Fig.�5/5) and can beevaluated with the handheld.

Depending on the module parametrizing, the faults are sentto the field bus node, where they can be evaluated accordingto the field bus protocol used.

Representation of the faults in the various field bus nodesdepends on the field bus protocol (see manual for the fieldbus node).

Page 190:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−32 Festo P.BE−CPX−AX−EN en 0811d

5.5.1 Fault messages of the analogue input modules

An analogue input module can register the following faults:

Fault no. Description Fault treatment

2 Short circuit/overload 1)

Short circuit of a sensor for cold junctioncompensation (CJC; see parameter�Diagnostic message after open load or shortcircuit")

· Eliminate short circuit or checkconnected CJC sensors

3 Open load 2)

Open load of a thermocouple (TC) or of asensor for cold junction compensation (CJC; see parameter �Diagnostic messageafter open load or short circuit")

· Check and, if necessary, replace thecable and connected sensors

9 Limit value underrun 1)

Set limit value underrun or sensortemperature range underrun(see parameter �Limit value monitoringchannel x" or �Definition limit valuechannel�x")

· Check parametrizing of sensor typeand connection design

· Check input signal present· Check parametrized limit value· If necessary, deactivate monitoring

10 Limit value overrun 1)

Set limit value overrun or sensor temperaturerange overrun(see parameter �Limit value monitoringchannel x" or �Definition limit valuechannel�x")

· Check parametrizing of sensor typeand connection design

· Check input signal present· Check parametrized limit value· If necessary, deactivate monitoring

1) The module will register the appropriate fault depending on the parametrizing.The analogue input signals will, however, be processed further.

2) The analogue input signals is set to the value 32767 (�Overflow").

Tab.�5/21: Fault messages of the input modules � part 1

Page 191:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−33Festo P.BE−CPX−AX−EN en 0811d

Fault no. Description Fault treatment

15 Module/channel failed 3)

General fault, module faulty· Power Off/On is necessary· If this fault occurs again: check and, if necess�

ary, replace the analogue input module

29 Fault in parametrizing 1) 4)

A fault has occurred in the setting ofa parameter (monitored parameters:see Tab.�5/9)

· Check the parametrizing undertaken and, ifnecessary, undertake the parametrizing againwith the correct parameters (valid parameters:see section 5.4.3.

1) The module will register the appropriate fault depending on the parametrizing.The analogue input signals will, however, be processed further.

3) This fault message is triggered by the field bus node. Processing of the analogue input signals will be stopped.

4) The (faulty) param. entered will be ignored, the module operates with the last valid parameters.

Tab.�5/22: Fault messages of the input modules � part 2

5.5.2 LED displays

Various LEDs are situated under the transparent cover of thedevice for diagnosing the input modules.

1 Channel fault LEDs(red)

2 Module fault LED(red)

1

CPX−4AE−TC

2

Fig.�5/5: LED displays of the temperature module

Page 192:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−34 Festo P.BE−CPX−AX−EN en 0811d

Fault LEDs

The red fault LEDs indicate channel or module faultsdepending on the parametrizing.

Fault LEDchannel x 1)

Modulefault LED

Status Faultnumber

Fault treatment

LED is off LED is off

Faultless operation � None

LED lights LED lights

Fault short circuit channel x

orFault open load channel x

2

3

Check cables andsensors, eliminateshort circuit

Check and, if necess�ary, replace the cableand sensors

LED flashes LED lights

Limit value overrunSet limit value underrun orsensor temperature rangeunderrun

orLimit value overrunSet limit value overrun orsensor temperature rangeoverrun

9

10

See section 5.5.1,Tab.�5/21

LED lights LED flashes

Parametrizing faults 29 See section 5.5.1,Tab.�5/22

LED is off LED flashes

Servicing required 255 Replace module

1) One LED per channel

Tab.�5/23: Fault LEDs of the temperature module CPX−4AE−TC

Page 193:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−35Festo P.BE−CPX−AX−EN en 0811d

5.5.3 Fault treatment and parametrizing

The following diagrams show the fault treatment in theanalogue input modules. With the appropriate moduleparameter, represented in the diagram as a switch, furtherregistering and display of the fault can be suppressed asdesired. The parameters are described in section 5.4.3.

2

Fault message to field bus node

Fault no. 3

Open load channel x

Monitoring openload/short circuitchannel x

Modulefault LED

10 1Monitoring openload/short circuitchannel x

0 1

Fault no. 2

Short circuitchannel x

Fault LEDchannel x

2

1 Channel−specific module parameters (switch position represented = default setting)

2 Channel−specific module faults

Fig.�5/6: Principle of fault treatment and parametrizing CPX−4AE−TC � part 1

Page 194:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

5. Analogue input module CPX−4AE−TC

5−36 Festo P.BE−CPX−AX−EN en 0811d

3 4

2

Fault no. 10

Limit valueoverrunchannel x

1

Fault message to field bus node

Modulefault LED

Fault no. 9

Limit valueunderrunchannel x

Fault no. 29

Parametrizingfaultschannel x

Monitoringof limitvalueschannel x

0 1Limit valuemonitoringchannel x

0 1

Fault LEDchannel x

Fault LEDchannel x

Modulefault LED

0 1Monitoringparametriz−ing faults

1 Channel−specific module parameters (switch position represented = default setting)

2 Module−specific parameter

3 Channel−specific module faults

4 Module fault

Fig.�5/7: Principle of fault treatment and parametrizing CPX−4AE−TC � part 2

Page 195:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Analogue output module CPX−2AA−U−I

6−1Festo P.BE−CPX−AX−EN en 0811d

Chapter 6

Page 196:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−2 Festo P.BE−CPX−AX−EN en 0811d

Contents

6. Analogue output module CPX−2AA−U−I 6−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.1 Function of the analogue output modules 6−4 . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.2 Fitting 6−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.3 Installation 6−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.3.1 DIL switch settings 6−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.3.2 Pin assignment 6−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.3.3 Connecting the analogue outputs 6−11 . . . . . . . . . . . . . . . . . . . . . . . . . .

6.4 Instructions on commissioning 6−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.4.1 Processing analogue output signals 6−12 . . . . . . . . . . . . . . . . . . . . . . . .

6.4.2 General information on parametrizing 6−15 . . . . . . . . . . . . . . . . . . . . . . .

6.4.3 Parameter with analogue output module type CPX−2AA−U−I 6−17 . . . . .

6.4.4 Module parameter �Output analogue−value data format" 6−27 . . . . . . .

6.4.5 Channel−specific module parameters � Limits 6−29 . . . . . . . . . . . . . . . . .

6.4.6 Channel−specific module parameters � Monitor wire fracture 6−31 . . . .

6.5 Diagnosis 6−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.5.1 Fault messages of the anaolgue output modules 6−33 . . . . . . . . . . . . . .

6.5.2 LED display 6−37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

6.5.3 Fault treatment and parametrizing 6−39 . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 197:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−3Festo P.BE−CPX−AX−EN en 0811d

Contents of this chapter This chapter describes the analogue output moduleCPX−2AA−U−I.

Analogue output modules provide analogue voltage outputsor current outputs in a CPX terminal and can be adapted tospecific applications by means of different sub−bases.

Further information An overview of the modular structure of a CPX terminal, themodular connections as well as the display and connectingelements can be found in chapter 1.

Information on mounting the complete CPX terminal, con�necting the power supply as well as general instructions onconfiguration and parametrizing can be found in the CPXsystem manual.

Information on the address assignment as well as on com�missioning can be found in the appropriate field bus nodemanual or function module manual.

Page 198:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−4 Festo P.BE−CPX−AX−EN en 0811d

6.1 Function of the analogue output modules

Analogue output modules provide analogue voltage outputsor current outputs in the valve terminal for connecting actua�tors and other current−consuming devices (e.g. proportionaldirectional control valves). At present the following type isavailable:

Type Description

CPX−2AA−U−I This type provides 2 analogueoutputs (output channels) withscalable value ranges. The outputsignal range can be configuredchannel by channel, eitherelectrically isolated or non−floating:� 0 � 10 V� 0 � 20 mA� 4 � 20 mAActuator supply 24 V / 2.8 A permodule.

Tab.�6/1: Overview of analogue output modulesCPX−2AA−U−I

6.2 Fitting

See section 1.3.

Page 199:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−5Festo P.BE−CPX−AX−EN en 0811d

6.3 Installation

WarningUndesired movement of the connected actuators and uncontrolled movements of loose tubing can cause injuryto human beings or damage to property.

Before carrying out installation and maintenance work,switch off the following:

� the compressed air supply

� the operating and load voltage supplies.

In the following sections you will find the pin assignments of

the analogue output modules for the different sub−bases.

Instructions on connecting the cables and plugs to the sub−bases can be found in section 1.2.3.Note in particular the instructions on connecting the cablescreening to functional earth (FE).

Power supply

The supply for the output channels as well as the 24 V supplyfor the electronics of the output modules is provided via theoperating voltage supply for the electronics/sensors(VEL/SEN).

The 24 V supply for the actuators is provided via the loadvoltage supply for the outputs of the CPX terminal (VOUT).

The actuators can also be supplied externally (electricalisolation, see section 6.3.3, Fig.�6/2).

Page 200:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−6 Festo P.BE−CPX−AX−EN en 0811d

6.3.1 DIL switch settings

2 DIL switches are available for configuring the analogueoutput modules. These are located on the top of the elec�tronic module.

1 DIL switch 0: Signal range ofanalogue output 0

2 DIL switch 1: Signal range ofanalogue output 1

2AO

1 2

ON 1

21 2

ON

Fig.�6/1: DIL switches in the electronic module (further information on 1 and 2 see following pages)

Proceed as follows:

1. Switch off the power supply.

2. Remove if necessary the fitted sub−base (see �Fitting"section 1.3).

3. Set the DIL switch elements in accordance with theinstructions on the following pages.

4. Refit the sub−base if necessary (see �Fitting" section 1.3,tightening torque 0.9 � 1.1�Nm).

Page 201:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−7Festo P.BE−CPX−AX−EN en 0811d

Setting the output signal range

You can set the signal range of the relevant analogue outputwith the 2−element DIL switches 0 and 1.

Signal Setting the DIL switches 1)

range Setting DIL switch 0 DIL switch 1

0 � 10 V 0.1: OFF 2)

0.2: OFF 2)1.1: OFF 2)

1.2: OFF 2)

0.1: ON0.2: OFF

1.1: ON1.2: OFF

0 � 20 mA 0.1: OFF0.2: ON

1.1: OFF1.2: ON

4 � 20 mA 0.1: ON0.2: ON

1.1: ON1.2: ON

1) DIL switch 0 for output channel 0DIL switch 1 for output channel 1

2) Default (factory setting)

Tab.�6/2: DIL switches of the analogue output module

Please noteThe setting of the signal range with the DIL switches canbe modified by parametrizing (see section 6.4). Parame�trizing has precedence over the DIL switch setting.

Page 202:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−8 Festo P.BE−CPX−AX−EN en 0811d

6.3.2 Pin assignment

Pin assignment of CPX−2AA−U−I with sub−baseCPX−AB−4−M12x2−5POL(−R)

Analogue output module type CPX−2AA−U−I with sub−base CPX−AB−4−M12x2−5POL(−R)

Sub−base Pin assignment X1, X2 (output O...0)

Pin assignment X3, X4 (output O...1)

Voltage outputs 1)

2AO

2

3

1

5

4

X1

Socket X1:1: 24 VOUT2: OU0+3: 0 VOUT4: OGND5: Screening (FE) 2)

2

3

1

5

4

X3

Socket X3:1: 24 VOUT2: OU1+3: 0 VOUT4: OGND5: Screening (FE) 2)

Current outputs 1)

2

3

1

5

4

X2Socket X2:1: 24 VOUT2: OI0+3: 0 VOUT4: OGND5: Screening (FE) 2)

2

3

1

5

4

X4Socket X4:1: 24 VOUT2: OI1+3: 0 VOUT4: OGND5: Screening (FE) 2)

OUx+ = Positive voltage output signalOIx+ = Positive current output signalOGND = Reference potential for the analogue output signalsFE = Functional earth

1) Assignment depends on the DIL switch setting and on parametrizing (see section 6.3.1), a total of 2 output channels are available per module (O...0 and O...1, connection X1 or X2 as well as connec−tion X3 or X4).

2) With CPX−AB−4−M12x2−5POL−R the metal thread is connected to FE

Tab.�6/3: Pin assignment of analogue output module type CPX−2AA−U−I with sub−baseCPX−AB−4−M12x2−5POL(−R)

CPX−AB−4−M12x2−5POL−R The metal thread (�...−R") of this sub−base is connectedinternally with pin 5 (Functional earth FE).

Page 203:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−9Festo P.BE−CPX−AX−EN en 0811d

Pin assignment of CPX−2AA−U−I with sub−baseCPX−AB−8−KL−4POL

Analogue output module type CPX−2AA−U−I with sub−base CPX−AB−8−KL−4POL

Sub−base Pin assignment X1 � X4 (output O...0)

Pin assignment X5 � X8 (output O...1)

Voltage outputs 1)

2AO

X1

X2

X3

X5

X6

X7

.0

.1

.2

.3

.0

.1

.2

.3

.0

.1

.2

.3

X1

X2

.0

.1

.2

.3

.0

.1

.2

.3

X1.0: 24 VOUTX1.1: 0 VOUTX1.2: OGNDX1.3: Screening (FE)

X2.0: n.c.X2.1: n.c.X2.2: OU0+X2.3: Screening (FE)

X5

X6

.0

.1

.2

.3

.0

.1

.2

.3

X5.0: 24 VOUTX5.1: 0 VOUTX5.2: OGNDX5.3: Screening (FE)

X6.0: n.c.X6.1: n.c.X6.2: OU1+X6.3: Screening (FE)

X4 X8

.3

.0

.1

.23

Current outputs 1)

X4 X8.2.3

X3

X4

.0

.1

.2

.3

.0

.1

.2

.3

X3.0: 24 VOUTX3.1: 0 VOUTX3.2: OGNDX3.3: Screening (FE)

X4.0: n.c.X4.1: n.c.X4.2: OI0+X4.3: Screening (FE)

X7

X8

.0

.1

.2

.3

.0

.1

.2

.3

X7.0: 24 VOUTX7.1: 0 VOUTX7.2: OGNDX7.3: Screening (FE)

X8.0: n.c.X8.1: n.c.X8.2: OI1+X8.3: Screening (FE)

OUx+ = Positive voltage output signalOIx+ = Positive current output signalOGND = Reference potential for the analogue output signalsn.c. = Not connectedFE = Functional earth

1) Assignment depends on the DIL switch setting and on parametrizing (see section 6.3.1), a total of 2 output channels are available per module (O...0 and O...1, connection X1/X2 or X3/X4 as well as connection X5/X6 or X7/X8).

Tab.�6/4: Pin assignment of analogue output module type CPX−2AA−U−I with sub−baseCPX−AB−8−KL−4POL

Page 204:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−10 Festo P.BE−CPX−AX−EN en 0811d

Pin assignment of CPX−2AA−U−I with sub−baseCPX−AB−1−SUB−BU−25POL

Analogue output module type CPX−2AA−U−I with sub−base CPX−AB−1−SUB−BU−25POL

Sub−base Pin assignment 1)

2AO

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

1: OGND2: OU0+3: OGND4: OI0+5: n. c.6: n. c.7: n. c.8: n. c.9: 24 VOUT10: 24 VOUT11: 0 VOUT12: 0 VOUT13: FE

14: OGND15: OU1+16: OGND17: OI1+18: 24 VOUT19: n. c.20: 24 VOUT21: n. c.22: 0 VOUT23: 0 VOUT24: 0 VOUT25: FEHousing: FE (screening)

Pins 1/2, 14/15 = Voltage outputsPins 3/4, 16/17 = Current outputsOUx+ = Positive voltage output signalOIx+ = Positive current output signalOGND = Reference potential for the analogue output signalsn.c. = Not connectedFE = Functional earth

1) Assignment depends on the DIL switch setting and on parametrizing (see section 6.3.1), a total of 2 output channels are available per module (O...0 and O...1).

Tab.�6/5: Pin assignment of analogue output module type CPX−2AA−U−I with sub−baseCPX−AB−1−SUB−BU−25POL

Page 205:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−11Festo P.BE−CPX−AX−EN en 0811d

6.3.3 Connecting the analogue outputs

Only screened cables are usually permitted for the trans�mission of analogue signals (see section 1.2.3).

1 Without electricalisolation: The actuators aresupplied via the CPXmodule

2 With electricalisolation: Without actuatorsupply or if anexternal actuatorsupply is used

0/4...20

mA

0...10

V

External

actuator

supply

24�VOUx+ OGND FE0�V 24�VOIx+ OGND FE0�V

1

2

0...10

V

0/4...20

mA

0...10

V

0/4...20

mA

OUx+ OGND OIx+ OGND

OUx+ OGND OIx+ OGND

Fig.�6/2: Examples of analogue output connections (screening connection on FE pin)

Further connection examples can be found in appendix A.7.1.

Page 206:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−12 Festo P.BE−CPX−AX−EN en 0811d

6.4 Instructions on commissioning

6.4.1 Processing analogue output signals

The analogue values are transmitted from the control systemto the CPX terminal as output words (2 bytes, 16 bits). Eachanalogue output module occupies 2 output words for this inthe address range.

The position of the output words in the address range de�pends on the field bus used (see manual for the field busnode).

Parametrizing The data format as well as the limit values and, where appli�cable, also the scaling of the analogue output signals canbe adapted by parametrizing. Instructions on this can befound in the sections 6.4.2 and 6.4.3.

The reaction with the default settings is described below.

Page 207:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−13Festo P.BE−CPX−AX−EN en 0811d

Reaction with the default settings

The module parameter �Output analogue−value data format"possesses the default setting �VZ + 12 bits right−justified"(compatible with valve terminal type 03). With this setting theoutput words will be output as analogue values as follows:

Data format �VZ + 12 bits right−justified" (compatible with valve terminal type 03)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ 0 0 0 B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

Abbreviations used:VZ: Sign (with data format �VZ + 12 bits right−justified" always = 0, i.e. a positive value)B0 � B11: Output valueD0 � D15: 16 bits output data field MSB/LSB: Most significant bit / least significant bit

Tab.�6/6: Data format �VZ + 12 bits right−justified"

The channel−specific parameters �Lower limit" and �Upperlimit" possess the following default settings:

� Lower limit = 0

� Upper limit = 4095

These correspond to the scaling end values (data range) ofthe default data format.

Page 208:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−14 Festo P.BE−CPX−AX−EN en 0811d

The following diagram shows the processing of the outputwords with the default data format �VZ + 12 bits right−justi�fied".

1 Lower limit of ratedrange

2 Digital output value(example)

3 Upper limit of ratedrange

4 Digital output values

5 Assigned analoguesignals

6 Output voltage orcurrent

1 3

0 V0 mA4 mA

0 4095

10 V20 mA20 mA

2

4

5

6

5.833 V11.66 mA9.33 mA

2389

Fig.�6/3: Example of default data format �VZ + 12 bits right−justified"

The assignment of the digital value range and the analogueoutput signal ranges is shown in the table below.

Digital data preparation Analogue output signal range

Output data Output values 0 � 10 V 0 � 20 mA 4 � 20 mA

Output value > 4095 Rated range exceeded Output of last valid value

Output value 4095 9.9975 V 19.995 mA 19.995 mA

Output value 1 � 4094 Linear value range ... ... ...

Output value 0

g

0 V 0 mA 4 mA

Output value < 0 Value less than rated range Output of last valid value

Tab.�6/7: Output signals of the analogue output modules with default settings

Page 209:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−15Festo P.BE−CPX−AX−EN en 0811d

6.4.2 General information on parametrizing

The reaction of the analogue output modules can be parame�trized.

Further information on parametrizing can be found in thesystem manual or in the manual for the field bus node.

Due in some cases to necessary calculations, modified para�meters are not valid until they have been thoroughly checkedand saved. Until then, as in the case of invalid parameters,the previous settings apply.

Depending on the parameter, no valid analogue values areavailable for up to max. 30 ms after a value modification.

Special instructions on avoiding parametrizingfaults

In order to avoid parametrizing faults, note the sequencedescribed below for modifying the following parameters:

� Output analogue−value data format

� Lower limit channel x

� Upper limit channel x

Page 210:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−16 Festo P.BE−CPX−AX−EN en 0811d

Sequence for first or startup parametrizing (CPX terminal indelivery status, monitoring of parametrizing faults active):

1. First set the desired data format (parameter �Outputanalogue−value data format").

2. Then set the upper and lower limits for both channels:

� If the new upper limit value is positive, set first theupper limit; then the lower limit.

� If the new upper limit is negative (only in the case ofdata format �VZ + 15 bits linear scaled"), set first thelower limit, then the upper limit.

Sequence for modifying the parametrizing:

1. Activate, if applicable, the monitoring of parametrizingfaults (module parameter �Monitoring CPX modules �monitoring parametrizing faults" and channel−specificmodule parameter �Monitoring channel x � monitoringparametrizing faults").

2. Set the lower limit to 0 and the upper limit to 4095 forboth channels.

3. Then set the desired data format (parameter �Outputanalogue−value data format").

4. If required, then set the upper and lower limits for bothchannels:

� If the new upper limit value is positive, set first theupper limit; then the lower limit.

� If the new upper limit is negative (only in the case ofdata format �VZ + 15 bits linear scaled"), set first thelower limit, then the upper limit.

Page 211:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−17Festo P.BE−CPX−AX−EN en 0811d

6.4.3 Parameter with analogue output module type CPX−2AA−U−I

The tables below give an overview of the module parametersof the analogue output modules.

Function number 1) Module parameters

4828 + m * 64 + 0 Monitoring the CPX module

4828 + m * 64 + 1 Reaction after short circuit/overload

4828 + m * 64 + 2 Reserved

4828 + m * 64 + 3 Output analogue−value data format

1) m = module number (counting from left to right, beginning with 0)

Tab.�6/8: Overview � Module parameters

Function number 1) Channel−specific module parameters

4828 + m * 64 + 6 Monitoring channel 0

4828 + m * 64 + 7 Monitoring channel 1

4828 + m * 64 + 8 Signal range channel 0/1

4828 + m * 64 + 9/10 Lower limit channel 0

4828 + m * 64 + 11/12 Lower limit channel 1

4828 + m * 64 + 13/14 Upper limit channel 0

4828 + m * 64 + 15/16 Upper limit channel 1

� 2) Fail safe channel x (see also CPX system manual)

� 2) Idle mode channel x (see also CPX system manual)

� 2) Force channel x (see also CPX system manual)

1) m = module number (counting from left to right, beginning with 0)2) Access is protocol−specific (see manual for field bus node)

Tab.�6/9: Overview � Channel−specific module parameters

Page 212:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−18 Festo P.BE−CPX−AX−EN en 0811d

Description of the parameters

Module parameters: Monitoring the CPX module

Function no. 4828 + m * 64 + 0 m = module number (0 � 47)

Description With the analogue output modules, monitoring of individual faults can be activated or deactivated (suppressed) independently of each other. Active monitoring causes the following: The fault is:� sent to the CPX field bus node� displayed by the module common error LED.

Bit Bit 0: reservedBit 1: monitoring actuator supply (short circuit/overload or undervoltage)Bit 2 � 6: reservedBit 7: monitoring parametrizing faults

Values 1 = active (presetting); 0 = inactive

Remark � Monitoring short circuit at outputs:Monitoring can also be set for the complete CPX terminal (see CPX systemmanual, system parameter �Monitoring").

� Monitoring parametrizing faults:Some parameters are checked for non−permitted values during parametrizing:� Data format� Lower limit� Upper limitWith the exception of the parameter �Data format", the setting of the moduleparameter �Monitoring parametrizing faults" is only effective if the appropri�ate channel parameter �Monitoring parametrizing faults" is set to �active".

Tab.�6/10: Monitoring the CPX module

Page 213:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−19Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Behaviour after short circuit/overload

Function no. 4828 + m * 64 + 1 m = module number (0 � 47)

Description Determines after a short circuit at an output or in the actuator supply whetherthe power is to remain switched off or whether it is to be switched on againautomatically.

Bit Bit 0: reservedBit 1: behaviour after short circuit at an output

(short circuit/overload in actuator supply)Bit 2: reservedBit 3: behaviour after short circuit/overload at analogue outputBit 4 � 7: reserved

Values 0 = Leave voltage/current switched off1 = Switch voltage/current on againPresetting bit 1: 1 (switch voltage on again)Presetting bit 3: 0 (leave voltage/current switched off )

Remark With the setting �Leave voltage/current switched off", Power off/on is necessaryfor switching the power on again. Ascertain which setting is necessary for reli�able operation of your machine or system. Further information can be found insection 6.5.1.

Tab.�6/11: Behaviour after short circuit/overload

Page 214:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−20 Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Output analogue−value data format

Function no. 4828 + m * 64 + 3 m = module number (0 � 47)

Description Determines the format in which the digital output words from the output moduleare interpreted for the analogue output signals.

Bit Bit 0 � 3: reserved (= 0)Bit 4, 5: output analogue−value data formatBit 6, 7: reserved (= 0)

Values Bit 5 Bit 40 0 VZ + 15 bits linear scaled0 1 VZ + 12 bits right−justified (compatible with valve terminal

type 03, presetting)1 0 VZ + 15 bits left−justified, linear scaled (Simatic S7)1 1 VZ + 12 bits left−justified + diagnosis (Simatic S5)

(VZ = sign)

Remark The reserved bits 0 � 3 and 6, 7 must always be 0. If one or several bits are setto �1" during parametrizing, the parametrizing carried out is invalid and there�fore not effective. If the module parameter �Monitoring parametrizing faults" isset to �active", the relevant fault will be displayed.Further information on this parameter can be found in section 6.4.4.

Tab.�6/12: Output analogue−value data format

Page 215:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−21Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Monitoring channel x

Function no. 4828 + m * 64 + 6 (channel 0) m = module number (0 � 47)4828 + m * 64 + 7 (channel 1)

Description For the individual channels of the analogue output modules, monitoring of indi�vidual faults can be activated or deactivated (suppressed) independently of eachother. Active monitoring causes the following: The fault is:� sent to the CPX field bus node� displayed by the module common error LED.Further infomation on these monitorings can be found under the description ofthe relevant fault in section 6.5.1.

Bit Bit 0: monitoring lower limitBit 1: monitoring upper limitBit 2: behaviour after short circuit/overload at analogue outputBit 3: monitoring wire fracture/idlingBit 4 � 6: reservedBit 7: monitoring parametrizing faults

Values 1 = active; 0 = inactivePresetting bit 0 � 2: 1 (active)Presetting bit 3: 0 (inactive)Presetting bit 7: 1 (active)

Remark � Monitoring the upper/lower limit:Monitoring the output values on the range limits defined with the parameters�Lower limit ..." as well as �Upper limit ..." (depending on the data formatused, see sections 6.4.4 and 6.4.5).

� Monitoring short circuit/overload at output:Only effective for the signal range 0 � 10 V.

� Monitoring wire fracture (idling):Only effective for the signal range 0/4 � 20 mA.The wire fracture monitoring is only effective if more than approx. 1 mA output current is output.

� Monitoring parametrizing faults:The channel specific parameters �Lower limit" and �Upper limit" are checkedfor non−permitted values during parametrizing. The setting of the channel parameter �Monitoring parametrizing faults" is onlyeffective if the module parameter �Monitoring parametrizing faults" is set to�active".

Tab.�6/13: Monitoring channel x

Page 216:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−22 Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Signal range channel x

Function no. 4828 + m * 64 + 8 m = module number (0 � 47)

Description For the individual channels of the analogue output modules, the signal ranges ofthe analogue outputs can be set independently of each other.

Bit Bit 0/1: setting of DIL switch 0 for channel 0 (read only)switch 0.1 = bit 0switch 0.2 = bit 1

Bit 2/3: signal range channel 0 (AO0)Bit 4/5: setting of DIL switch 1 for channel 1 (read only)

switch 1.1 = bit 4switch 1.2 = bit 5

Bit 6/7: signal range channel 1 (AO1)

Values Channel 0 Channel 1Bit 3 Bit 2 Bit 7 Bit 60 0 0 0 Using the setting of the DIL switches (presetting)0 1 0 1 0 � 10 V1 0 1 0 0 � 20 mA1 1 1 1 4 � 20 mA

Remark Bits 0/1 as well as 4/5 represent the status of the DIL switches for setting thesignal ranges.With bits 2/3 and 6/7 other signal ranges can be parametrized irrespective ofthe DIL switch setting.Modified parameter settings have precedence over the DIL switch settings. The setting of the DIL switches is carried out with the presetting (bit 2/3 = 0; bit 6/7 = 0).

Tab.�6/14: Signal range channel x

Page 217:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−23Festo P.BE−CPX−AX−EN en 0811d

Channel parameters: Lower limit channel x / Upper limit channel x

Function no. Lower limits: m = module number (0 � 47)4828 + m * 64 + 9 (channel 0, low byte)4828 + m * 64 + 10 (channel 0, high byte)4828 + m * 64 + 11 (channel 1, low byte)4828 + m * 64 + 12 (channel 1, high byte)

Upper limits:4828 + m * 64 + 13 (channel 0, low byte)4828 + m * 64 + 14 (channel 0, high byte)4828 + m * 64 + 15 (channel 1, low byte)4828 + m * 64 + 16 (channel 1, high byte)

Description A lower limit can be set for the individual channels of the analogue outputmodules (see section 6.4.5).

Bit Bit 0 � 7: high byte or low byte of the limit value

Values Presettings:� Lower limit = 0 (low byte = 0; high byte: 0)� Upper limit = 4095 (low byte = 255; high byte: 15)Low byte: 0 � 255High byte: 0 � 15

Remark The output signals which are output are always limited to the parametrizedvalues.If the output value is less than the parametrized lower limit or exceeds theparametrized upper limit, an appropriate fault is displayed (providing therelevant channel parameter �Monitoring channel x � monitoring lower limit" or�Monitoring channel x � monitoring upper limit" is active).The upper limit must always be greater than the lower limit.Modifications to the limits must be made in steps of 16 bits.

Permitted limits:The limits are checked for validity during parametrizing. Invalid parametrizingsare not accepted � the module uses the previous (last valid) parametrizings. The permitted values depend on the parametrized data format (see section6.4.5). If the module parameter �Monitoring parametrizing faults" as well as therelevant channel parameter �Monitoring parametrizing faults" is set to �active",the relevant fault will be displayed.

Tab.�6/15: Lower and upper limits channel x

Page 218:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−24 Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Fail safe channel x

Function no. Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).

Description With the aid of the so−called Fail safe parametrizing, you can specify the signalstatus which the outputs are to assume in the event of field bus communicationfaults (see also CPX system manual). This can be accomplished with the follow�ing parameters:� Fault mode channel x� Fault state channel x

Values � Fault mode channel x: 0 = Hold last state1 = Fault state (presetting)

� Fault state channel x: 0 = Reset value (presetting)1 = Set value

Remark The parametrizing of the fault mode for an analogue output channel depends onthe field bus protocol and is carried out:� by an individual parameter setting or bit (e.g. CPX−FB11),� by setting all parameter bits of the relevant word (e.g. CPX−FB6) to �Hold last

state" or �Fault state".For parametrizing the Fault state, the desired output word must be correspon�dingly mapped in the parameter bits �Fault state channel x".The Fail safe reaction is determined for the complete CPX terminal by means ofthe system parameter �Fail safe" (see CPX system manual).

Tab.�6/16: Fail safe channel x (channel−specific)

Page 219:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−25Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Idle mode channel x

Function no. Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).

Description The Idle mode parametrizing is only relevant with certain field bus protocols.With the aid of the so−called Idle mode, you can determine the signal statuswhich the outputs are to assume when the Idle function is accessed (see alsoCPX system manual). This can be accomplished with the following parameters:� Idle mode channel x� Idle state channel x

Values � Idle mode channel x: 0 = Hold last state1 = Idle state (presetting)

� Idle state channel x: 0 = Reset value (presetting)1 = Set value

Remark The parametrizing of the Idle mode for an analogue output channel is accom�plished in the case of the field bus node CPX−FB11 by means of an individualparameter setting or bit.For parametrizing the Idle state, the desired output word must be correspon�dingly mapped in the parameter bits �Idle state channel x".The Idle mode reaction is determined for the complete CPX terminal by means ofthe system parameter �System Idle mode" (see CPX system manual).

Tab.�6/17: Idle mode channel x (channel specific)

Page 220:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−26 Festo P.BE−CPX−AX−EN en 0811d

Module parameters: Force channel x

Function no. Access to these module parameters is made via protocol−specific functions (see the manual for the field bus node).

Description The Force function permits the manipulation of analogue values irrespective ofthe actual output value (see also CPX system manual). This can be accomplishedwith the following parameters:� Force mode outputs channel x� Force state outputs channel x

Values � Force mode outputs channel x: 0 = Blocked (presetting)1 = Force state

� Force state outputs channel x: 0 = Reset value (presetting)1 = Set value

Remark The enabling of the Force function with the parameter �Force mode outputschannel x" depends on the field bus protocol and is carried out:� by an individual parameter setting or bit (e.g. CPX−FB11),� by setting all parameter bits of the relevant word (e.g. CPX−FB6) to �blocked"

or �Force state".For parametrizing the Force state, the desired output word must be correspon�dingly mapped in the parameter bits �Force state outputs channel x".The enabling of the Force function for the complete CPX terminal is made bymeans of the system parameter �Force mode" (see CPX system manual).

Tab.�6/18: Force channel x (channel−specific)

Page 221:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−27Festo P.BE−CPX−AX−EN en 0811d

6.4.4 Module parameter �Output analogue−value data format"

The parametrized data format determines how the valuestransferred by the control system are to be processed by theCPX analogue module. The setting applies to all analogueoutput channels. Irrespective of the data format the datawidth is always 16�bits (2 bytes, 1�word).

Supported data formats of the analogue output modules

VZ + 15 bits linear scaled

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B14MSB

B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

VZ + 12 bits right−justified (compatible with valve terminal type 03, presetting)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ 0 0 0 B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

VZ + 15 bits left−justified (compatible with Simatic S7)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

x x x

VZ + 12 bits left−justified (compatible with Simatic S5)

D15 D14 D13 D12 D11 D10 D9 D8 D7 D6 D5 D4 D3 D2 D1 D0

VZ B11MSB

B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0LSB

0 0 0

Abbreviations used:VZ: Sign (0 = positive value, 1 = negative value)B0 � B14: Output valueD0 � D15: 16 bits output data fieldMSB/LSB: Most significant bit / least significant bit x: Not relevant

Tab.�6/19: Data format analogue output modules

Page 222:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−28 Festo P.BE−CPX−AX−EN en 0811d

Data format �VZ + 15 bits linear scaled"

The data range defined by the scaling end values (limits) ofthe 15−bit digital value in the output word is scaled linearly to12 bits. The resulting value is available after D−A conversionas an analogue output signal (see section 6.4.5, Fig.�6/5).

Data format �VZ + 12 bits right−justified"

The 12−bit digital value in the output word is available afterD−A conversion as an analogue output signal (see also sec�tion 6.4.1, Fig.�6/3).

Data format �VZ +15 bits left−justified" anddata format �VZ + 12 bits left−justified"

The 12−bit digital values in the output word plus the preced�ing sign bit are arranged left−justified in the data format (withthe three zeros at the end this results in a 15−bit data wordwhich, divided by 8, corresponds to the 12−bit digital value).The 12−bit digital value is available after D−A conversion as ananalogue output signal.

The following diagram shows an example of the data format�VZ + 15 bits left−justified":

1 Digital output values15−bit

2 Digital output values12−bit (without threezeros at the end)

3 Analogue outputsignals

1

2

3

32760

0 4095

0

0 V0 mA4 mA

10 V20 mA20 mA

Fig.�6/4: Example of data format �VZ + 15 bits left−justified"

Page 223:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−29Festo P.BE−CPX−AX−EN en 0811d

6.4.5 Channel−specific module parameters � Limits

You can determine limits with the channel−specific para�meters �Lower limit" and �Upper limit". The meaning of thelimit parameters depends on the parametrized data format ofthe module.

With data format �VZ + 15 bits linear scaled", the limits havethe function of defining the scaling end values of the datarange. This results in an additional scaling of the analoguevalues.If the output data lie outside this data range, a diagnosticmessage can be generated with appropriate parametrizing.

With other data formats the data range is already defined bythe scaling end values. In this case, the limits permit datamonitoring even within the data range.

Data format 1) Data range Limits/scaling end values 2)

VZ + 15 bits linear scaled

−30000 � +30000 Lower scaling end value:−30000 � +29999

Upper scaling end value:−29999 � +30000

VZ + 12 bits right−justified

0 � 4095 Lower limit:0 � 4094

Upper limit:1 � 4095

VZ + 15 bits left−justified

0 � 32760 Lower limit:0 � 32759

Upper limit:1 � 32760

VZ + 12 bits left−justified

0 � 32760 Lower limit:0 � 32752

Upper limit:1 � 32760

1) (VZ = sign)As the analogue outputs can only output positive signals and as there is no scaling on the data range with the �Fixed value" data formats �VZ + 12 bits right−justified", �VZ + 15 bits left−justified"and �VZ + 12 bits left−justified", the sign bit with these formats is always 0.

2) The lower limit/scaling end value must always be less than the upper limit/scaling end value.

Tab.�6/20: Limits or scaling end values of the analogue output modules

Page 224:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−30 Festo P.BE−CPX−AX−EN en 0811d

Scaling end values with data format �VZ + 15 bitslinear scaled"

The following diagram shows an example of the data format�VZ + 15 bits linear scaled" with the scaling end values:

� Lower limit = 400

� Upper limit = 2000

With these values the output signal corresponds to e.g. forthe signal range 4 � 20 mA the digital output value multipliedby 0.01 mA.

1 Digital output value

2 Digital signals afterA−D conversion(resolution: 12 bits)

3 Analogue outputsignal after scaling

1

2

3

0

0 4095

2000400

0 20 mA4 mA

Fig.�6/5: Example scaling data format �VZ + 15 bits linear scaled"

The scaling end values in this data format are identical withthe limits for less than or exceeding the rated range:

1 Digital output signalafter scaling

2 Limits

3 Less than orexceeding the limits

12

3

400 2000

2

Fig.�6/6: Limit monitoring with data format �VZ + 15 bits linear scaled"

Page 225:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−31Festo P.BE−CPX−AX−EN en 0811d

Limits with the �Fixed value" data formats

The following diagram shows an example of the data format�VZ + 12 bits right−justified" with the scaling end values:

� Lower limit = 500

� Upper limit = 3500

The principle of the limits also applies to the data formats�VZ + 15 bits left−justified" and �VZ + 12 bits left−justified".

1 End value of the data range

2 Lower limit

3 Upper limit

4 Less than orexceeding the limits

1 2 3

40950 500 3500

4

1

Fig.�6/7: Monitoring of limits with the �Fixed value" data formats

6.4.6 Channel−specific module parameters � Monitor wire fracture

A wire fracture/open load monitoring can be activated withappropriate parametrizing for the signal range 0/ 4 � 20 mA.The messages are made available as diagnostic information(see section 6.5.1).

Page 226:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−32 Festo P.BE−CPX−AX−EN en 0811d

6.5 Diagnosis

Specific faults of the analogue output modules are registeredor suppressed depending on the module parametrizing.

The faults are shown on−the−spot by means of the Error LEDand, if necessary, can be evaluated with the handheld.

Depending on the module parametrizing the faults are regis�tered by the field bus node, where they can be evaluatedaccording to the field bus protocol used.

Representation of the faults in the various field bus nodesdepends on the field bus protocol (see manual for the fieldbus node).

Page 227:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−33Festo P.BE−CPX−AX−EN en 0811d

6.5.1 Fault messages of the anaolgue output modules

An analogue output module can register the following faults:

Fault number Description Fault treatment

2 Short circuit/overload in voltagesupply 1)

Only with voltage outputs with signalrange 0 � 10 V:Short circuit/overload at an output(see �Parameters� �Monitoring theCPX module � monitoring short cir�cuit/overload at output").The reaction depends on the parame�trizing, parameter �Behaviour aftershort circuit/overload at output":

� Setting �Leave voltage/currentswitched off": The output is switched off.

� Setting �Switch on voltage/currentagain": The output current is limited to approx. 15�mA.

1. Check actuators, eliminate shortcircuit/overload (number of faultychannel: see LED display or modulediagnostic data).

2. Depending on parametrizing:(Parameter �Behaviour after shortcircuit/overload at output")

· Power off/on necessary (operating voltage supply forelectronics/sensors VEL/SEN), orchange parameter �Behaviourafter short circuit/overload atoutput" to �Switch voltage onagain".

· The voltage will be switched onagain automatically when theshort circuit is eliminated.

1) The module displays the relevant fault depending on the parametrizing. The analogue output signals, however, will be processed further.

Tab.�6/21: Fault messages of the output modules � part 1

Page 228:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−34 Festo P.BE−CPX−AX−EN en 0811d

Fault number Description Fault treatment

3 Wire fracture/idling Current output 1)

Only with current outputs with signalrange 0/4 � 20 mA:The wire−fracture monitoring is onlyeffective if more than approx. 1 mAoutput current is output.(See parameter �Monitoring channel x� monitoring wire fracture/idling")

· Check and, if necessary, replace thecable and connected actuators.

9 Less than the rated range 1)

Lower limit exceeded.(See parameter �Lower limit channel x� low byte/high byte" or �Monitoring

channel x � monitoring below rated range")

· Check signal range of output.· Check parametrized limit.· If necessary, deactivate monitoring.

10 Rated range exceeded 1)

Upper limit exceeded.(See parameter �Upper limit channel x� low byte/high byte" or �Monitoring

channel x � monitoring rated range exceeded")

· Check signal range of output.· Check parametrized limit.· If necessary, deactivate monitoring.

15 Module/channel failed 2)

General fault, module faulty.· Power off/on necessary· If this fault occurs again: check

and, if necessary, replace theanalogue output module.

Evaluation of the analogue outputsignals has stopped.

1) The module displays the relevant fault depending on the parametrizing. The analogue output signals, however, will be processed further.

2) Processing of the analogue output signals will be stopped.

Tab.�6/22: Fault messages of the output modules � part 2

Page 229:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−35Festo P.BE−CPX−AX−EN en 0811d

Fault number Description Fault treatment

212425

Fault in parametrizing 1) 2)

A fault has occurred in the setting ofthe relevant parameter.� Parameter data format� Parameter lower limit� Parameter upper limit

· Check the parametrizing undertakenand, if necessary, undertake theparametrizing again with the correctparameters.

The analogue output module will beoperated further with the last validparametrizing.

26 Fault in actuator supply 1)

Short circuit/overload or undervoltagein actuator supply (VOUT). (See parameter �Monitoring the CPXmodule � monitoring short circuit/overload at output")

� Setting �Leave voltage switched off":

The actuator supply is switched off.

� Setting �Switch on voltage again": The output current is limited to approx. 250�mA.

1. Eliminate short circuit/overload orcheck actuator supply, if necessary,check connected actuators

2. Depending on parametrizing (parameter �Behaviour after shortcircuit/overload at output"):

· Power off/on necessary (load volt�age supply for outputs VOUT), orchange parameter �Behaviour after short circuit/overload at output" to �Switchvoltage on again".

· If the actuator current supply isless than 400�mA: The voltage will be switched onagain automatically when theshort circuit is eliminated.If the actuator current supply ismore than 400�mA: Power off/on is necessary (VOUT).

1) The module displays the relevant fault depending on the parametrizing. The analogue output signals, however, will be processed further.

2) The parameters entered will be ignored, the module operates with the last valid parameters.

Tab.�6/23: Fault messages of the output modules � part 3

Page 230:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−36 Festo P.BE−CPX−AX−EN en 0811d

Please notePlease note the following when using the output modules:

� If there is a short circuit, all actuator supplies of themodule will be switched off together.

� If not parametrized otherwise, the actuator supplyvoltage will be switched on again automatically whenthe short circuit is eliminated.

Page 231:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−37Festo P.BE−CPX−AX−EN en 0811d

6.5.2 LED display

There is an LED under the transparent cover of the module fordiagnosing the output modules.

1 Error LED (red)

2AO

1

CPX−2AA−U−I

Fig.�6/8: LED display of the analogue output modules

Error LED

The red error LED indicates a module fault due to short circuitor overload of the actuator supply or an output, by a wirefracture or a parametrizing fault, depending on the parame�trizing.

Error LED(red)

Sequence Status Faultnumber

Faulttreatment

LED is out

ON

OFF

Faultless operation � None

LED lights up

ON

OFF

Fault in actuator supplyShort circuit/overload or under−voltage in actuator supply (VOUT).orComponent defective

26

15

See section6.5.1, Tab.�6/23

Check and, ifnecessary,replacecomponent

Tab.�6/24: Error LED analogue output modules � part 1

Page 232:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−38 Festo P.BE−CPX−AX−EN en 0811d

Error LED(red)

Sequence Status Faultnumber

Faulttreatment

LED flashes

ON

OFF

1 flash 1)

Overload/short circuit Voltage outputShort circuit/overload at the outputorWire fracture/idling Current outputOutput current below nominal valueorLower limit exceededOutput value is less than the

2

3

9

See�section6.5.1,Tab.�6/21,Tab.�6/22�andTab.�6/23

ON

OFF

2 flashes 1)

Output value is less than theparametrized limitorUpper limit exceededOutput value is greater than theparametrized limitorFault in parametrizing� Parameter data format� Parameter lower limit� Parameter upper limit

10

212425

1) The number of flash pulses indicates the output channel concerned.1 flash = channel 0 (or both channels)2 flashes = channel 1

Tab.�6/25: Error LED analogue output modules � part 2

Page 233:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−39Festo P.BE−CPX−AX−EN en 0811d

6.5.3 Fault treatment and parametrizing

The following diagrams show the fault treatment in the ana�logue output modules. Further registering and display of thefault can be suppressed as desired with the appropriate mod�ule parameter, represented in the diagram as a switch. A de�scription of the parameter can be found in section 6.4.3.

2

Fault message tofield bus node

Module error LED

1

Fault no. 15

Module defective

MonitoringShort circuitat outputs

0 1

Fault no. 26

Fault in actuator supply

1 Module parameters(switch position represented = default setting)

2 Module−specific faults

3 Channel−specific faults

Fig.�6/9: Principle of fault treatment and parametrizing ofthe analogue output modules � part 1

Page 234:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−40 Festo P.BE−CPX−AX−EN en 0811d

2

Fault messageto field bus node

Fault no. 3

Wire fracture/idlingCurrent outputchannel 0

MonitoringWire fracture/idlingchannel 0

1

0 1

Module error LED

Fault no. 3

Wire fracture/idlingCurrent outputchannel 1

MonitoringWire fracture/idlingchannel 1

0 1

Fault no. 2

Short circuit/overload atvoltage outputchannel 0

MonitoringShort circuit/overloadchannel 0

0 1 MonitoringShort circuit/overloadchannel 1

0 1

Fault no. 2

Short circuit/overload atvoltage outputchannel 1

1 Module parameters (switch position represented = default setting)

2 Channel−specific faults

Fig.�6/10: Principle of fault treatment and parametrizing of the analogue output modules � part 2

Page 235:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−41Festo P.BE−CPX−AX−EN en 0811d

2

Fault no. 9

Lower limitexceededchannel 1

1

MonitoringUpper limitchannel 1

Fault no.21���25

Parametrizingfault channel 1

Fault messageto field bus node

Module error LED

MonitoringParametrizingfault

Fault no. 9

Lower limitexceededchannel 0

Fault no. 10

Upper limitexceededchannel 1

Fault no. 10

Upper limitexceededchannel 0

Fault no.21���25

Parametrizingfault channel 0

MonitoringParametrizingfault channel 1

0 1

MonitoringParametrizingfault channel 0

0 1

0 1 0 1

MonitoringUpper limitchannel 0

0 1

MonitoringLower limitchannel 1

0 1

MonitoringLower limitchannel 0

0 1

1 Module parameters (switch position represented = default setting)

2 Channel−specific faults

Fig.�6/11: Principle of fault treatment and parametrizing of the analogue output modules � part 3

Page 236:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

6. Analogue output module CPX−2AA−U−I

6−42 Festo P.BE−CPX−AX−EN en 0811d

Page 237:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Technical appendix

A−1Festo P.BE−CPX−AX−EN en 0811d

Appendix A

Page 238:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−2 Festo P.BE−CPX−AX−EN en 0811d

Contents

A. Technical appendix A−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.1 Technical specifications of analogue input module CPX−2AE−U−I A−3 . . . . . . . . .

A.2 Technical specifications of analogue input module CPX−AE−U−I A−5 . . . . . . . . . . .

A.3 Technical specifications of analogue input module CPX−4AE−T (temperature module) A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.4 Technical specifications of analogue input module CPX−4AE−TC (temperature module) A−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.5 Technical specifications of analogue output module CPX−2AA−U−I A−11 . . . . . . . .

A.6 Technical specifications of the sub−bases A−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.7 Internal structure of the CPX modules A−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.8 Connection examples A−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

A.8.1 Analogue input and output modules A−18 . . . . . . . . . . . . . . . . . . . . . . . .

A.8.2 Connecting temperature sensors to the module CPX−4AE−T A−22 . . . . . .

A.8.3 Connecting temperature sensors to the module CPX−4AE−TC A−24 . . . . .

A.9 Accessories A−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 239:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−3Festo P.BE−CPX−AX−EN en 0811d

A.1 Technical specifications of analogue input module CPX−2AE−U−I

Technical specifications CPX−2AE−U−I

Voltage inputs Current inputs

General technical specifications of theCPX�terminal

See CPX system manual

Protection class to EN 60529 See technical specifications of the fitted sub−base(section A.6)

Operating voltage supply forelectronics/sensors (VEL/SEN)� Nominal voltage� Internal current consumption at 24 V

(internal electronics)

DC 24 V ±25 %Typ. 50 mA

Analogue inputs Total of 2 input channels per module

� Channels� Signal ranges

Max. 2 channels0 � 10 V

Max. 2 channels0 � 20 mA / 4 � 20 mA

� Signal range selection

� Cable length� Resolution (A−D converter, internal)� Insulation voltage� Potential connection� Analogue value formation

� Measuring principle� Conversion time per channel� Module cycle time

� Interference suppression� Common−mode interference (Vpp)� Crosstalk between inputs

Can be selected channel by channel with DIL switch orsoftwareMax. 30 m, screened/shielded12 bitDC 500 VHighly resistive + capacitive connection to FE

Suc. approximationTyp. 150 s� 4 ms

Min. 70 dBMin. −50 dB

� Permitted potential differences� between input channels� between inputs and FE

AC 1 VppDC 30 V

AC 0 VDC 30 V

Page 240:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−4 Festo P.BE−CPX−AX−EN en 0811d

Technical specifications CPX−2AE−U−ITechnical specifications

Current inputsVoltage inputs

Analogue inputs (cont.)� Fault limits

� Operating fault limit (Tmin..Tmax)� Basic fault limit (25 °C)� Temperature fault� Linearity fault (without scaling)� Repetition accuracy at 25 °C

� Specifications on sensor selection� Input resistance� Permitted input voltage or input

current (destruction limit)

±0.5 %±0.3 %±0.015 % / K±0.05 %0.15 %

� 100 k30 V lasting

±0.6 %±0.4 %±0.015 % / K±0.05 %0.15 %

� 100 (50 )40 mA

Sensor supply

� Load capacity� Output voltage� Fuses

� Response current� Response time

� Reaction after end of overload� Protection against incorrect polarity at

24 V load input� Protection against reverse voltage

One connection per analogue input, the same supplypotential at all inputs, sensor supply generated from24�VEL/SENMax. sum continuous current per module: 0.7 A24 V ±25 %Electronic, thermal0.7 � 2.4 AMax. 20 msCan be parametrized (see parameters)Yes

Max. 30 V

� Electrical isolation

� between channel and 24 VSEN

� between the channels

The logic supply of the electrically isolated analoguepart is branched from the analogue voltage which isgenerated by a DC−DC converter from the 24 VEL/SEN.Yes (no potential isolation if internal sensor supplyis�used)No

Module code (internal identifier in CPX terminal)

1282AI

Page 241:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−5Festo P.BE−CPX−AX−EN en 0811d

A.2 Technical specifications of analogue input module CPX−AE−U−I

Technical specifications CPX−4AE−I

Current inputs

General technical specifications of theCPX�terminal

See CPX system manual

Protection class to EN 60529 See technical specifications of the fitted sub−base(section A.6)

Operating voltage supply for electronics/sensors (VEL/SEN)� Nominal voltage� Internal current consumption at 24 V

(internal electronics)

DC 24 V ±25 %Typ. 50 mA

Analogue inputs

� Channels� Signal ranges� Signal range selection

� Cable length� Resolution (A−D converter, internal)� Insulation voltage� Potential connection� Analogue value formation

� Measuring principle� Conversion time per channel� Module cycle time

� Interference suppression� Common−mode interference (Vpp)� Crosstalk between inputs

Total of 4 input channels per module0 � 20 mA / 4 � 20 mACan be selected channel by channel with DIL switch orsoftwareMax. 30 m, screened/shielded12 bitDC 500 VHighly resistive + capacitive connection to FE

Suc. approximationTyp. 150 s� 10 ms

Min. 70 dBMin. −50 dB

� Permitted potential differences� between input channels� between inputs and FE

AC 0 VDC 30 V

Page 242:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−6 Festo P.BE−CPX−AX−EN en 0811d

Technical specifications CPX−4AE−ITechnical specifications

Current inputs

Analogue inputs (cont.)� Fault limits

� Operating fault limit (Tmin � Tmax)� Basic fault limit (25 °C)� Temperature fault� Linearity fault (without scaling)� Repetition accuracy at 25 °C

� Specifications on sensor selection� Input resistance� Permitted input voltage or input

current (destruction limit)

±0.6 %±0.5 %±0.015 % / K±0.05 %0.15 %

� 100 (50 )40 mA

Sensor supply

� Load capacity� Output voltage� Fuses

� Response current� Response time

� Reaction after end of overload� Protection against incorrect polarity at

24 V load input� Protection against reverse voltage

One connection per analogue input, the same supplypotential at all inputs, sensor supply generated from24�VEL/SENMax. sum continuous current per module: 0.7 A24 V ±25 %Electronic, thermal0.7 � 2.4 AMax. 20 msCan be parametrized (see parameters)Yes

Max. 30 V

� Electrical isolation

� between channel and 24 VSEN

� between the channels

The logic supply of the electrically isolated analoguepart is branched from the analogue voltage which isgenerated by a DC−DC converter from the 24 VEL/SEN.Yes (no potential isolation if internal sensor supplyis�used)No

Module code (CPX−specific)Module identification (Handheld)

1304AI−I

Page 243:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−7Festo P.BE−CPX−AX−EN en 0811d

A.3 Technical specifications of analogue input module CPX−4AE−T (temperature module)

Technical specifications CPX−4AE−T

Pt sensors Ni sensors

General technical specifications of theCPX�terminal

See CPX system manual

Protection class to EN 60529 See technical specifications of the fitted sub−base(section A.6)

Operating voltage supply for electronics/sensors (VEL/SEN)� Nominal voltage� Internal current consumption at 24 V

(internal electronics)

DC 24 V ±25 %Typ. 50 mA

Analogue inputs

� Channels Selectable: 2 or 4 input channels per module

� Signal ranges Pt 100, 200, 500, 1000 Ni 100, 120, 500, 1000

� Signal range selection

� Cable length

� Sensor connection technology� Resolution (A−D converter, internal)� Insulation voltage� Potential connection� Analogue value formation

� Module cycle time� Interference suppression

� Common−mode interference (Vpp)� Crosstalk between inputs

Can be selected channel−by−channel by software(parametrizing)Max. 200 m, screened/shielded (accuracy diminishesat cable length over 10 m)2, 3 or 4−cable designs (to be set by parametrizing)15 bits + signDC 500 VHigh resistive, capacitive connection to FE

� 250 ms

Min. 70 dBMin. −50 dB

� Permitted potential differences� between input channels� between inputs and FE

AC 0 VDC 30 V

Page 244:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−8 Festo P.BE−CPX−AX−EN en 0811d

Technical specifications CPX−4AE−TTechnical specifications

Ni sensorsPt sensors

Analogue inputs (cont.)� Fault limits

� Operating error limit (Tmin � Tmax)relative to input range

� Basic fault limit (25 °C)

±0.06 %

Pt standard ± 0.6 KPt climate ± 0.2 K

±0.06 %

±0.2 K

� Temp. errors relative to input range� Linearity fault (without scaling)� Repetition accuracy at 25 °C

±0.001 %±0.02 %±0.05 %

Module code (CPX−specific)Module identification (Handheld)

1324AI−T

Page 245:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−9Festo P.BE−CPX−AX−EN en 0811d

A.4 Technical specifications of analogue input module CPX−4AE−TC(temperature module)

Technical specifications CPX−4AE−TC

TC sensors

General technical specifications of theCPX�terminal

See CPX system manual

Protection class to EN 60529 See technical specifications of the fitted sub−base(section A.6)

Operating voltage supply for electronics/sensors (VEL/SEN)� Nominal voltage� Internal current consumption at 24 V

(internal electronics)

DC 24 V ±25 %Typ. 25 mA

Analogue inputs

� Channels 4

� Signal rangesof the individual sensor types

EJTKNSBR

−200 � 900 °C−200 �1200 °C−200 � 400 °C−200 �1370 °C

0 �1300 °C0 �1760 °C

400 �1820 °C0 �1760 °C

60 V/°C51 V/°C40 V/°C40 V/°C38 V/°C11 V/°C8 V/°C

12 V/°C

� Sensor selection� Cable length

Can be selected channel−by−channel per parameterMax. 50 m, screened/shielded (accuracy diminishes atcable length over 10 m; measurement error cannot becompensated for)

� Resolution (A−D converter)� Data format

� Analogue value formation� Measuring principle� Module cycle time

16 bits (internal)15 bits + prefix, complement of two, binary notation intenths of a degree

Register. of the thermoelectric voltage (Seebeck effect)� 250 ms

� Interference suppression� Common mode attenuation� Crosstalk attenuation

Min.�−70 dBMin.�−50 dB (between inputs)

Page 246:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−10 Festo P.BE−CPX−AX−EN en 0811d

Technical specifications CPX−4AE−TCTechnical specifications

TC sensors

� Permitted potential difference� between input channels� between inputs and FE

0 V (no potential isolation)AC 60 V / DC 75 V

� Insulation voltage� Potential connection to FE� Internal current consumption at 24�V

(internal electronics)� Permitted voltage on measurement and

power supply line� Resolution� Operating error limit� Basic fault limit� Temperature fault

� Compensation fault� Linearity fault� Repeatability

DC 500 VHigh resistive, capacitive connectionTyp. 25 mA

Max. 30 V

0.1 °C / 0.1 °F< ±0.6 % (relative to ambient temperature range)< ±0.4 % (at 25 °C, without sensor fault)±0.005 %/K (relative to ambient temperature range,when an RTD auxiliary sensor Pt�1000 Class�A is usedfor cold junction compensation)< ±0.5 K±0.02 % (without scaling)< ±0.05 % (at 25 °C, relative to input range)

Module code (CPX−specific)Module identification (Handheld)

1344AI−TC

Page 247:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−11Festo P.BE−CPX−AX−EN en 0811d

A.5 Technical specifications of analogue output module CPX−2AA−U−I

Technical specifications CPX−2AA−U−I

Voltage outputs Current outputs

General technical specifications of theCPX�terminal

See CPX system manual

Protection class to EN 60529 See technical specifications of the fitted sub−base(section A.6)

Operating voltage supply for electronics/sensors (VEL/SEN)� Nominal voltage� Internal current consumption at 24 V

(internal electronics, no current supplyat outputs)

� Maximum current consumption at 24 V(maximum current supply at outputs)

DC 24 V ±25 %Typ. 50 mA

Typ. 100 mA

Load voltage supply at outputs (VOUT)� Nominal voltage� Maximum current consumption at 24 V� Diagnostic message undervoltage VOUT

(monitoring VOUT, load voltage outsidefunction range)

DC 24 V ±25 %4 � 10 A (response current of fuse)17 � 14 V

Analogue outputs Total of 2 output channels per module

� Channels

� Output ranges

Max. 2 channels (single−ended outputs)0 � 10 V

Max. 2 channels (single−ended outputs)0 � 20 mA / 4 � 20 mA

� Output range selection

� Cable length� Resolution (D−A converter, internal)� Insulation voltage� Analogue value formation

� Cycle time

Can be selected channel by channel with DIL switch orsoftwareMax. 30 m, screened/shielded12 bitDC 500 V

� 4 ms

� Response time� for ohmic load� for capacitive load� for inductive load

0.1 ms (min. 1 k)0.7 ms (max. 1 F)�

0.1 ms (max. 600 )�0.5 ms (max. 1 mH)

Page 248:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−12 Festo P.BE−CPX−AX−EN en 0811d

Technical specifications CPX−2AA−U−ITechnical specifications

Current outputsVoltage outputs

Analogue outputs (cont.)� Interference suppression

� Crosstalk between outputs� Permitted potential differences

� between the output channels� between OGND and FE

Min. −40 dB

AC 0 VDC 30 V

� Fault limits� Operating fault limit (Tmin � Tmax)� Basic fault limit (25 °C)� Temperature fault� Linearity fault (without scaling)� Repetition accuracy at 25 °C

� Specifications on sensor selection� Load resistance

� for ohmic load� for capacitive load� for inductive load� short−circuit protection� short circuit current� idling voltage

� Destructive limit against voltagesapplied externally

� Connecting the actuators

±0.6 %±0.5 %±0.015 % / K±0.1 %0.05 %

Min. 1 kMax. 1 F�YesApprox. 20 mA�Max. 30 V lasting

2 conductor connections

±0.6 %±0.5 %±0.015 % / K±0.1 %0.05 %

Max. 600 �Max. 1 mH��18 VMax. 30 V lasting

2 conductor connections

Actuator supply

� Load capacity� Fuses

� Response current� Reaction after end of overload� Protection against incorrect polarity

24�V actuator supply� Protection against reverse voltage

24 VOUT, one connection per analogue output, the same supply potential at all outputsMax. sum continuous current per module: 2.8 AElectronic, thermal4 � 10 ACan be parametrized (see parameters)Yes

Max. 30 V

� Electrical isolation

� between channel and 24 VOUT

� between the channels

The logic supply of the electrically isolated analoguepart is branched from the analogue voltage which isgenerated by a DC−DC converter from the 24 VEL/SEN.Yes (no potential isolation if internal actuator supply isused)No

Module code (CPX−specific)Module identification (Handheld)

1292AA

Page 249:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−13Festo P.BE−CPX−AX−EN en 0811d

A.6 Technical specifications of the sub−bases

Sub−base typeCPX

Technical specifications *)

CPX...ProtectionclassEN 60529

Connections, contact loading

−M−4−M12x2−5POL IP65/67 1) 4 M12 sockets, metal thread, 5−pin, 4 A, sub−base housing inmetal design

−AB−4−M12x2−5POL IP65/67 1) 4 M12 sockets, 5−pin, 3 A

−AB−4−M12x2−5POL−R IP65/67 2) 4 M12 sockets, metal thread, 5−pin, 4 A

−AB−8−KL−4POL IP20 3) 2 terminal strips (spring clip terminals), 16−pin (4�x�4−pin), 4�A, for cable cross section 0.08 � 1.5 mm2, conductor specification:see section 1.2.3

−AB−1−SUB−BU−25POL IP20 4) 1 Sub−D socket, 25−pin, 4 A

−AB−4−HAR−4POL IP65/67 1) 4 HARAX sockets, 4−pin, 3�A, connection using insulationdisplacement technology, for cable cross section 0.5 � 1.0 mm2,conductor specification: see section 1.2.3

*) General technical specifications of the CPX terminal see CPX system manual P.BE−CPX−SYS−...1) With plug connector inserted or with protective cap ISK−M122) With plug connector inserted or with protective cap ISK−M12; when using quick connectors,

follow the manufacturer’s instructions3) With cover AK−8KL and screw connector set VG−K−M9: IP65/IP674) With plug SD−SUB−D−ST25: IP65

Page 250:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−14 Festo P.BE−CPX−AX−EN en 0811d

A.7 Internal structure of the CPX modules

Internal structure of CPX−2AE−U−I and CPX−4AE−I

1 Diagnosticinformation

2 Input values(measured data for the inputs)

I...x =�Input x

*) only CPX−2AE−U−I

(data transferbetween module andPLC/IPC via field bus)

3 Logic

4 Power supply unit

5 A−D converter

6 Module fault LED

7 Connections on thesub−base

1

2

4

5

24 VSEN

0 VSEN

FE

24 V ±25 % (VEL/SEN�)

0 V (VEL/SEN�)

67

3

IIxz

IIx+IUx+ *)

IUxz *)

Fig.�A/1: Internal structure of CPX−2AE−U−I and CPX−4AE−I

Page 251:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−15Festo P.BE−CPX−AX−EN en 0811d

Internal structure of CPX−4AE−T

1 Diagnosticinformation

2 Input values(measured datafor the inputs)

I...x =�Input x

*) Depending on the sensor connection,certain inputs mustbe bridged (see section A.8.2).

(data transferbetween module andPLC/IPC via field bus)

3 Logic

4 Power supply unit

5 A−D converter

6 Channel and moduleerror LEDs

7 Connections on thesub−base

1

2

4

5IIxz *)

FE

24 V ±25 % (VEL/SEN�)

0 V (VEL/SEN�)

67

3 IIx+ *)

IUx+ *)

IUxz *)

Fig.�A/2: Internal structure of CPX−4AE−T

Page 252:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−16 Festo P.BE−CPX−AX−EN en 0811d

Internal structure of CPX−4AE−TC

1 Diagnosticinformation

2 Input values(measured datafor the inputs)

Ix =�Input x

*) Connections for the cold junction compensation (CJC, CJC’) by means of RTD (Pt�1000; see section A.8.3)

(data transfer between module andPLC/IPC via field bus)

3 Logic

4 Power supply unit

5 A−D converter

6 Channel and moduleerror LEDs

7 Connections on thesub−base

1

2

4

5CJC’ *)

FE

24 V ±25 % (VEL/SEN�)

0 V (VEL/SEN�)

67

3 Ix+CJC *)

Ixz

Fig.�A/3: Internal structure of CPX−4AE−TC

Page 253:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−17Festo P.BE−CPX−AX−EN en 0811d

Internal structure of CPX−2AA−U−I

1 Initial values(signal�data)

O...�x =�Output x

*) OIx+ or OUx+

(data transferbetween module and PLC/IPC via field bus)

2 Diagnosticinformation (statusdata) regarding� Actuator supply� Output status� Overload� Idling (open load)

3 Logic, D−A conversion

4 Power supply unit,monitoring actuatorsupply

5 Output driver

6 Monitoring output

7 Limiting inductivevoltage peaks

8 Module fault LED

9 Connections on thesub−base

1

2

5O...x+ *)

0 VOUT

FE

76

0 V (VEL/SEN�)

24 V ±25 % (VOUT�)

4

9

8

24 VOUT

24 V ±25 % (VEL/SEN�)

0 V (VOUT�)

OGND

3

Fig.�A/4: Internal structure of CPX−2AA−U−I

Page 254:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−18 Festo P.BE−CPX−AX−EN en 0811d

A.8 Connection examples

A.8.1 Analogue input and output modules

Connection variants of current sensors

1 Sensor 4 � 20 mA

2 Connections toanalogue CPX module

1

2

24 VSEN

IIxzIIx+

+

0 VSEN

Fig.�A/5: Connecting 4 � 20 mA sensors with internal 24 V power supply (CPX−2AE−U−I, CPX−4AE−I)

1 24 V power unit

2 Sensor 4 � 20 mA

3 Voltage differencemax. 30 V

4 Connections toanalogue CPX module

1

2

IIx+

3

IIxz

+

0 VSEN

0 V

24 V

4

Fig.�A/6: Connecting 4 � 20 mA sensors with external 24 V power supply (CPX−2AE−U−I, CPX−4AE−I)

NoteInterference on the 24 VSEN cable can influence theanalogue signal of the sensor.

Page 255:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−19Festo P.BE−CPX−AX−EN en 0811d

Connecting the sensor for bipolar voltage signals

NoteWith this connection variant, the following measuringfaults occur when the analogue value is registered:

� overlapping of the value range in the vicinity of 0 V(offset fault of the input amplifier)

� symmetry fault in respect of the zero point (0 V).

1 Sensor 4 � 20 mA

2 Positive sensorvoltage

3 Negative sensorvoltage

4 Connections toanalogue CPX module

12IUxz

3

IUx++

4

IU(x+1)zIU(x+1)

Fig.�A/7: Connecting 4 � 20 mA sensors for registering of bipolar voltage signals with2�inputs (CPX−2AE−UI, CPX−4AE−I)

Page 256:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−20 Festo P.BE−CPX−AX−EN en 0811d

Connecting pressure sensors

1 Pressure sensor typeSDE, voltage output

2 Pressure sensor typeSDE, current output

3 Pressure sensor typeSDE1−...−PU−... orSDE1−...−NU−...

4 Connections to analogue CPX module

1

2

4

3

24 VSEN

0 VSEN / IUxz

IUx+1

2

3

4

24 VSEN

0 VSEN / IIxz

IIx+

1

2

3

4

1

2 3

4

24 VSEN

0 VSEN

IUx+

Fig.�A/8: Connecting pressure sensors (CPX−2AE−U−I, CPX−4AE−I)

Page 257:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−21Festo P.BE−CPX−AX−EN en 0811d

Connecting proportional valves

1 Proportional 5/3−waydirectional controlvalve type MPYE

2 Proportional pressureregulator type MPPEor type MPPES

3 Connections toanalogue CPX module

1

2

24 VOUT

OUx+ / OIx+

3

OGND

0 VOUT

1

2 3

4

1

2

354

86 7

24 VOUT

OUx+ / OIx+

OGND

0 VOUT

Fig.�A/9: Connection proportional valves (CPX−2AA−U−I)

Page 258:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−22 Festo P.BE−CPX−AX−EN en 0811d

A.8.2 Connecting temperature sensors to the module CPX−4AE−T

The following illustrations show the connection of tempera�ture sensors to the module CPX−4AE−T in 2−, 3− and 4−cabledesigns.

Explanations of the various connection designs and the pinassignments can be found in sections 4.3.2 and 4.3.3.

Only screened/shielded cables are permitted for the trans�mission of analogue signals (see section 1.2.3).

1 Constant sourceof current in themodule

2 Connecting pin ofCPX module

3 Sensor powersupply

4 Separate voltagecable

5 Temperaturesensor

Ix+

Ixz

Ux+

Uxz

1 2

3

4

5

3

Fig.�A/10: Connecting temperature sensors in 4−cable design (CPX−4AE−T)

Page 259:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−23Festo P.BE−CPX−AX−EN en 0811d

1 Constant sourceof current in themodule

2 Connecting pin ofCPX module

3 Linkedcurrent/voltageconnection

4 Combinedcurrent/voltagecable

5 Temperaturesensor

6 Separate voltagecable

Ix+

Ixz

Ux+

Uxz

1 2 3

4

5

6

Fig.�A/11: Connecting temperature sensors in 3−cable design (CPX−4AE−T)

1 Constant sourceof current in themodule

2 Connecting pin ofCPX module

3 Linkedcurrent/voltageconnection

4 Combinedcurrent/voltagecable

5 Temperaturesensor

Ix+

Ixz

Ux+

Uxz

1 2 3

4

5

4

3

Fig.�A/12: Connecting temperature sensors in 2−cable design (CPX−4AE−T)

Page 260:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−24 Festo P.BE−CPX−AX−EN en 0811d

A.8.3 Connecting temperature sensors to the module CPX−4AE−TC

The following illustrations show the connection of tempera�ture sensors (thermocouples with cold junction compensa�tion) to the module CPX−4AE−TC.

Explanations of the pin assignments can be found insection�5.3.1.

Further information on temperature measurement by meansof thermocouples can be found in the following sections:

� Introduction to the measuring method: section 5.3.2

� Explanation of cold junction compensation: section 5.3.3

� Accessories: appendix A.9

Only screened/shielded cables are permitted for the trans�mission of analogue signals (see section 1.2.3).

1 Connecting pin ofCPX module

2 Sensor cable 1(of metal 1)

3 Sensor cable 2(of metal 2)

4 Temperaturesensor (RTD,Pt�1000, Class�A)for cold junctioncompensation(CJC)

5 Measuring point(sensor tip)

5

Ux+

Uxz

CJCx

CJCx’

2

3

4

1

Fig.�A/13: Connecting a thermocouple (TC) with cold junction compensation (CJC);CPX−4AE−TC)

Page 261:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−25Festo P.BE−CPX−AX−EN en 0811d

The Pt 1000 temperature sensor for cold junction compensa�tion must be fitted in the immediate vicinity of the connectionpoint for the thermocouple (in the plug or on the terminal)(connecting pins CJCx, CJCx’).

For each input you will need a Pt�1000 in the design Class A,which you can obtain as an individual sales item via Festo(part number 553��596).

For external cold junction compensation, all inputs must beprovided with their own Pt�1000.

The following schematic diagrams (Fig.�A/14 and Fig.�A/15)show the connection of the Pt�1000:

� in an M12 plug (Fig.�A/14)

� directly to a sub−base with terminal strips (spring clip terminals; Fig.�A/15).

1 Measuring point(sensor tip)

2 Measuring cable(sensor cable)

3 M12 plug

4 Resistor (RTD)for�cold junctioncompensation(Pt�1000, Class�A)

2 3 4

2

1

Fig.�A/14: Connecting a thermocouple and Pt−1000−RTDs for cold junction compensationby means of an M12 plug to the module CPX−4AE−TC (with sub−base CPX−M−4−M12x2−5POL or CPX−AB−4−M12x2−5POL(−R))

Page 262:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−26 Festo P.BE−CPX−AX−EN en 0811d

1 Measuring point(sensor tip)

2 Measuring cable(sensor cable)

3 Terminal strip(spring clipterminals) ofconnection blockCPX−AB−8−KL−4POL

4 Resistor (RTD)for�cold junctioncompensation(Pt�1000, Class�A)

2

3

4

1

2

Fig.�A/15: Connecting thermocouples and Pt−1000−RTDs for cold junction compensationby means of a terminal strip (spring clip terminals) to the module CPX−4AE−TC(with sub−base CPX−AB−8−KL−4POL)

Page 263:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−27Festo P.BE−CPX−AX−EN en 0811d

A.9 Accessories

General accessories

General accessories

Accessories Type Designation Description

IBS 6x10 Identification signs 64 identification signs 6 x 10

Accessories for module CPX−4AE−TC

Accessories Type Designation Description

CPX−W−PT1000(Festo part number553 596)

Resistor Temperature sensor (RTD) for coldjunction compensation (CJC),Pt�1000, Class�A

You will nee a Pt 1000 resistance temperature device (RTD)for each module input.

The Pt 1000 resistor must be fitted in the immediate vicinityof the input (in the plug or on the terminal).

Page 264:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−28 Festo P.BE−CPX−AX−EN en 0811d

Accessories for sub−base CPX−AB−4−M12x2−5POL�(−R)

Accessories Type Designation Description

SEA−G−S−7

SEA−4GS−7−2,5

SEA−GS−9SEA−GS−11−DUO

Sensor plug

Sensor plug

Sensor plugSensor plug

Sensor plug, straight, M12, 4−pin� PG7 screw connector, for cable

diameter 4 � 6 mm� PG7 screw connector, for cable

diameter 2.5 � 2.9 mm� PG9 screw connector� PG11 screw connector, 2 cable exits

(DUO)

SEA−M12−5GS−PG7SEA−5GS−11−DUO

PlugSensor plug

Sensor plug, straight, M12, 5−pin� PG7 screw connector� PG11 screw connector

ISK−M12 Protective cap Protective cap for sealing unusedconnector sockets

CPX−AB−S−4−M12 Screening plate Screening plate for improving EMCcompatibilityA blade connector as per DIN�46245 orDIN 46247 B2, 8−1 (2.8 x 1 mm) is alsorequired for connecting the functionalearth (FE).

NEBU−... Modular kit forconnecting cables

Connecting cables of various lengthsand designs for M8 and M12connections (as�from 2005)

Page 265:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−29Festo P.BE−CPX−AX−EN en 0811d

Accessory for sub−base CPX−AB−8−KL−4POL

Accessories Type Designation Description

SIM−M12−8GD−2−PUSIM−M12−8GD−5−PU

Socket cableSocket with cable

Connecting cable with free cableend and M12 socket, 8−pin, forconnecting cylinder−valvecombination type DNCV� 2 m long� 5 m long

AK−8KLVG−K−M9

CoverScrew connector

Terminal cover and screwconnector set for complying withprotection class IP65/IP67.

If screened plugs are required for your application, werecommend the following plugs from Binder:

Description Cable diameter Binder ordernumber

Cable plug, can bescreened (5 pin)

4 � 6 mm 99−1437−814−05screened (5−pin)

6 � 8 mm 99−1437−812−05

Order address:Franz Binder GmbH & Co.Elektrische Bauelemente KGRötelstraße 27D � 74172 Neckarsulm, GermanyE−mail: vk@binder−connector.deInternet: www.binder−connector.de

Page 266:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

A. Technical appendix

A−30 Festo P.BE−CPX−AX−EN en 0811d

Accessories for sub−base CPX−AB−1−SUB−BU−25POL

Accessories Accessories type Designation Description

SD−SUB−D−ST25 Plug Plugs with hood for IP65, straight,Sub−D, 25−pin, crimp contacts, PG11 screw connector

Accessory for sub−base CPX−AB−4−HAR−4POL

Accessories Type Designation Description

SEA−GS−HAR−4POL Sensor plug Sensor plug, straight, HARAX, 4−pin,for cable diameter 4.0���5.1�mm, for connecting sensors/actuators

If not all connector sockets are used, the unused ones mustbe sealed with the following sealing caps from Harting: Youwill then comply with protection class IP65.

Description Harting order number

Sealing caps SAB passive, M12 21010000003

Order address:HARTING Vertrieb für Steckverbinder und Systemtechnik GmbH & Co. KGPostfach 2451D � 32381 Minden, GermanyE−mail: [email protected]: http://www.HARTING.com

Page 267:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

Index

B−1Festo P.BE−CPX−AX−EN en 0811d

Appendix B

Page 268:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−2 Festo P.BE−CPX−AX−EN en 0811d

Contents

B. Index B−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 269:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−3Festo P.BE−CPX−AX−EN en 0811d

A

Abbreviations, product−specific XVI . . . . . . . . . . . . . . . . . . . .

Analogue input modulesCPX−4AE−T 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−4AE−TC 5−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Diagnosis 2−32, 3−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault messages 2−33, 3−34 . . . . . . . . . . . . . . . . . . . . . . . . . . . Function 2−4, 3−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation 2−5, 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instructions on commissioning 2−12, 3−12 . . . . . . . . . . . . . . Power supply 2−5, 3−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Analogue output modulesDiagnosis 6−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault messages 6−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function 6−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Installation 6−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Instructions on commissioning 6−12 . . . . . . . . . . . . . . . . . . Power supply 6−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

B

Behaviour after short circuit/overload 2−20, 3−20, 6−19 . . . . .

C

Channel parametersFilter measured value channel x 2−23, 3−23 . . . . . . . . . . . . . Limit value channel x 4−24 . . . . . . . . . . . . . . . . . . . . . . . . . . Lower limit channel x 2−24, 3−24, 6−23 . . . . . . . . . . . . . . . . . Measured value smoothing channel x 4−22, 4−23 . . . . . . . . . Monitoring channel x 2−21, 3−21, 4−20, 4−21, 6−21 . . . . . . . Signal range channel x 2−22, 3−22, 6−22 . . . . . . . . . . . . . . . . Upper limit channel x 2−24, 3−24, 6−23 . . . . . . . . . . . . . . . . .

Page 270:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−4 Festo P.BE−CPX−AX−EN en 0811d

Channel−specific parameters 5−20 . . . . . . . . . . . . . . . . . . . . . . Force channel x 5−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Lower limit value 5−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measured value smoothing 5−26 . . . . . . . . . . . . . . . . . . . . . Monitoring of limit values 5−25 . . . . . . . . . . . . . . . . . . . . . . Monitoring open load/short circuit 5−24 . . . . . . . . . . . . . . . Sensor type 5−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Upper limit value 5−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cold junction compensationCPX−4AE−TC 5−21, 5−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Introduction 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parameters 5−13, 5−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Pt 1000 5−13, 5−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Cold junction compensation (CJC)Introduction 5−12 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Connection examples A−18 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Connection technology 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature sensors 4−11, 5−14 . . . . . . . . . . . . . . . . . . . . . .

CPX I/O modules XI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CPX TerminalStructure XIV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

CPX−2AA−U−IInternal structure A−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical specifications A−11 . . . . . . . . . . . . . . . . . . . . . . . . With sub−base CPX−AB−1−SUB−BU−25POL 6−10 . . . . . . . . . . With sub−base CPX−AB−4−M12x2−5POL(−R) 6−8 . . . . . . . . . . . With sub−base CPX−AB−8−KL−4POL 6−9 . . . . . . . . . . . . . . . . . .

CPX−2AE−U−IInternal structure A−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical specifications A−3 . . . . . . . . . . . . . . . . . . . . . . . . . With sub−base CPX−AB−1−SUB−BU−25POL 2−10 . . . . . . . . . . With sub−base CPX−AB−4−M12x2−5POL(−R) 2−8 . . . . . . . . . . . With sub−base CPX−AB−8−KL−4POL 2−9 . . . . . . . . . . . . . . . . . .

CPX−4AE−IInternal structure A−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical specifications A−5 . . . . . . . . . . . . . . . . . . . . . . . . . With sub−base CPX−AB−1−SUB−BU−25POL 3−10 . . . . . . . . . . With sub−base CPX−AB−4−M12x2−5POL(−R) 3−8 . . . . . . . . . . . With sub−base CPX−AB−8−KL−4POL 3−9 . . . . . . . . . . . . . . . . . .

Page 271:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−5Festo P.BE−CPX−AX−EN en 0811d

CPX−4AE−T 4−3 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Internal structure A−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical specifications A−7 . . . . . . . . . . . . . . . . . . . . . . . . .

CPX−4AE−TC 5−3, 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cold junction compensation 5−23 . . . . . . . . . . . . . . . . . . . . Diagnostics 5−31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault message 5−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Forcing channel x 5−30 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Interference frequency suppression 5−22 . . . . . . . . . . . . . . Internal structure A−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LED display 5−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Limit value 5−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Limit values 5−22, 5−25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Measured value smoothing 5−26 . . . . . . . . . . . . . . . . . . . . . Monitoring of limit values 5−25 . . . . . . . . . . . . . . . . . . . . . . Monitoring open load/short circuit 5−24 . . . . . . . . . . . . . . . Open load 5−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Parametrizing faults 5−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . Sensor type 5−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Short circuit 5−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Technical specifications A−9 . . . . . . . . . . . . . . . . . . . . . . . . . Unit of measurement for temperature 5−22 . . . . . . . . . . . .

CPX−AB−1−SUB−BU−25POLConnecting the cables and plugs 1−17 . . . . . . . . . . . . . . . .

CPX−AB−4−HAR−4POLConnecting the cables and plugs 1−18 . . . . . . . . . . . . . . . .

CPX−AB−4−M12x2−5POL�(−R)Connecting the cables and plugs 1−12 . . . . . . . . . . . . . . . .

CPX−AB−4−M12x2−5POL...Connecting the cables and plugs 1−11 . . . . . . . . . . . . . . . .

CPX−AB−8−KL−4POLConnecting the cables and plugs 1−14 . . . . . . . . . . . . . . . .

Page 272:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−6 Festo P.BE−CPX−AX−EN en 0811d

D

Default settingCPX−4AE−TC 5−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Designated use VII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DiagnosisCPX−2AA−U−I 6−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−2AE−U−I 2−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−4AE−I 3−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−4AE−T 4−28 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DiagnosticsCPX−4AE−TC 5−31 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Via the field bus XIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

DIL switches 2−6, 3−6, 4−6, 6−6 . . . . . . . . . . . . . . . . . . . . . . . . .

Display and connecting elementsI/O modules 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

E

Electronics module 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Error messagesAnalogue input modules 4−29 . . . . . . . . . . . . . . . . . . . . . . .

F

Fail safe 6−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fail safe parametrizing 6−24 . . . . . . . . . . . . . . . . . . . . . . . . . . .

Fault messagesAnalogue input modules 2−33, 3−34, 5−32 . . . . . . . . . . . . . . Analogue output modules 6−33 . . . . . . . . . . . . . . . . . . . . . .

Filter measured value channel x 2−23, 3−23 . . . . . . . . . . . . . . .

Force 2−25, 3−26, 4−25, 5−30, 6−26 . . . . . . . . . . . . . . . . . . . . . .

Page 273:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−7Festo P.BE−CPX−AX−EN en 0811d

I

I/O modulesAssembly 1−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Combinations with sub−bases 1−8 . . . . . . . . . . . . . . . . . . . . . Components 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Idle mode 6−25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Idle mode parametrizing 6−25 . . . . . . . . . . . . . . . . . . . . . . . . .

Important user instructions IX . . . . . . . . . . . . . . . . . . . . . . . . . .

Input analogue−value data format 2−20, 3−20 . . . . . . . . . . . . .

Input moduleCPX−4AE−TC 5−3, 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fault message 5−32 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . LED display 5−33 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Input modulesLED display 2−35, 3−36, 4−31 . . . . . . . . . . . . . . . . . . . . . . . . . Short circuit/overload 2−36, 3−37 . . . . . . . . . . . . . . . . . . . . .

Input signal range 2−7, 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Instructions on commissioningAnalogue input modules 2−12, 3−12, 4−14, 5−14 . . . . . . . . . Analogue output modules 6−12 . . . . . . . . . . . . . . . . . . . . . .

Interference frequency suppressionCPX−4AE−TC 5−21, 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Internal structureCPX−2AA−U−I A−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−2AE−U−I A−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−4AE−I A−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−4AE−T A−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−4AE−TC A−16 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 274:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−8 Festo P.BE−CPX−AX−EN en 0811d

L

LED displayInput modules 2−35, 3−36, 4−31, 5−33 . . . . . . . . . . . . . . . . . On the sub−bases 1−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output modules 6−37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Limit value channel x 4−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Limit values, CPX−4AE−TC 5−22, 5−25, 5−28 . . . . . . . . . . . . . . . .

Lower limit channel x 2−24, 3−24, 6−23 . . . . . . . . . . . . . . . . . . .

M

Manifold base 1−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Manuals on the CPX terminal XV . . . . . . . . . . . . . . . . . . . . . . .

Measured value smoothing channel x 4−22, 4−23, 5−26 . . . . .

Module parameters 2−18, 3−18, 4−18, 5−19, 6−17 . . . . . . . . . . Behaviour after short circuit 6−19 . . . . . . . . . . . . . . . . . . . . Behaviour after short circuit/overload 2−20, 3−20 . . . . . . . . Channel−specific module parameters 2−25, 3−26, 4−25, . . .

5−20, 6−24, 6−25, 6−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . Cold junction compensation, CPX−4AE−TC 5−23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Forcing channel x, CPX−4AE−TC 5−30 . . . . . . . . . . . . . . . . . . Input analogue−value data format 2−20, 3−20 . . . . . . . . . . . . Interference frequency suppression, CPX−4AE−TC 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Limit values, CPX−4AE−TC 5−28 . . . . . . . . . . . . . . . . . . . . . . . Measured value smoothing, CPX−4AE−TC 5−26 . . . . . . . . . . Monitoring of limit values, CPX−4AE−TC 5−25 . . . . . . . . . . . . Monitoring open loop/short circuit, CPX−4AE−TC 5−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Monitoring the CPX module 2−19, 3−19, 4−19, 6−18 . . . . . . . CPX−4AE−TC 5−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Output analogue−value data format 6−20 . . . . . . . . . . . . . . Sensor type, CPX−4AE−TC 5−27 . . . . . . . . . . . . . . . . . . . . . . . Unit of measurement for temperature, CPX−4AE−TC 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 275:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−9Festo P.BE−CPX−AX−EN en 0811d

Monitoring channel x 2−21, 3−21, 4−20, 6−21 . . . . . . . . . . . . . .

Monitoring of limit valuesCPX−4AE−TC 5−25 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Monitoring open load/short circuitCPX−4AE−TC 5−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Monitoring the CPX module 2−19, 3−19, 4−19, 5−21, 6−18 . . . . CPX−4AE−TC 5−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

O

Open load, CPX−4AE−TC 5−24 . . . . . . . . . . . . . . . . . . . . . . . . . .

Output analogue−value data format 6−20 . . . . . . . . . . . . . . . .

Output modulesLED display 6−37 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Short circuit/overload 6−37 . . . . . . . . . . . . . . . . . . . . . . . . .

Output signal range 6−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

P

ParametersCold junction compensation 5−13, 5−19 . . . . . . . . . . . . . . . . CPX−4AE−TC 5−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Overview 5−19 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Parametrizing faultsCPX−4AE−TC 5−21 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pictograms X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pin assignmentCPX−2AA−U−Iwith sub−base CPX−AB−1−SUB−BU−25POL 6−10 . . . . . . . . with sub−base CPX−AB−4−M12x2−5POL(−R) 6−8 . . . . . . . . . with sub−base CPX−AB−8−KL−4POL 6−9 . . . . . . . . . . . . . . . .

CPX−2AE−U−I 2−8, 2−9, 2−10 . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−4AE−Iwith sub−base CPX−AB−1−SUB−BU−25POL 3−10 . . . . . . . . with sub−base CPX−AB−4−M12x2−5POL 3−8 . . . . . . . . . . . . with sub−base CPX−AB−8−KL−4POL 3−9 . . . . . . . . . . . . . . . .

CPX−4AE−T 4−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . CPX−4AE−TC 5−6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 276:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−10 Festo P.BE−CPX−AX−EN en 0811d

Power supply 2−5, 3−5, 6−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Protection class 1−9, 1−17 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Pt 1000Cold junction compensation 5−13, 5−23 . . . . . . . . . . . . . . . .

R

Reaction after short circuit 4−20 . . . . . . . . . . . . . . . . . . . . . . .

S

Screening plateConnect 1−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Fitting 1−24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Sensor connection designs channel x 4−22 . . . . . . . . . . . . . . .

Sensor typeCPX−4AE−TC 5−21, 5−27 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Thermocouples 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Service VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

SettingInput signal range 2−7, 3−7 . . . . . . . . . . . . . . . . . . . . . . . . . . Output signal range 6−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Short circuit, CPX−4AE−TC 5−24 . . . . . . . . . . . . . . . . . . . . . . . .

Short circuit/overload 2−36, 3−37, 4−20, 6−37 . . . . . . . . . . . . .

Signal range channel x 2−22, 3−22, 6−22 . . . . . . . . . . . . . . . . . .

Signal rangesThermocouples 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Standard settings, CPX−4AE−TC 5−16 . . . . . . . . . . . . . . . . . . . .

Sub−base CPX−AB−1−SUB−BU−25POLWith analogue input module CPX−2AE−U−I 2−10 . . . . . . . . . With analogue input module CPX−4AE−I 3−10 . . . . . . . . . . . With analogue output module CPX−2AA−U−I 6−10 . . . . . . . .

Sub−base CPX−AB−4−M12x2−5POL(−R)With analogue input module CPX−2AE−U−I 2−8 . . . . . . . . . . . With analogue input module CPX−4AE−I 3−8 . . . . . . . . . . . . . With analogue output module CPX−2AA−U−I 6−8 . . . . . . . . . .

Page 277:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−11Festo P.BE−CPX−AX−EN en 0811d

Sub−base CPX−AB−8−KL−4POLWith analogue input module CPX−2AE−U−I 2−9 . . . . . . . . . . . With analogue input module CPX−4AE−I 3−9 . . . . . . . . . . . . . With analogue output module CPX−2AA−U−I 6−9 . . . . . . . . . .

Sub−basesCombinations with I/O modules 1−8 . . . . . . . . . . . . . . . . . . . Connecting the cables and plugs 1−9 . . . . . . . . . . . . . . . . . . Overview 1−4, 1−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

T

Target group VIII . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

TC 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Technical specificationsInput modules A−3, A−5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Output modules A−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Sub−bases A−13 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Temperature module A−7 . . . . . . . . . . . . . . . . . . . . . . . . . . . Thermocouple A−9 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature measurement by means of thermocouplesIntroduction 5−8 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature module 4−4, 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature sensorConnection technology 5−14 . . . . . . . . . . . . . . . . . . . . . . . . Input signals 5−15 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . TC 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Thermocouple (TC) 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Temperature sensorsConnection technology 4−11 . . . . . . . . . . . . . . . . . . . . . . . . Input signals 4−14 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Text markings X . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Thermocouple (TC) 5−4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 278:  · 2020-04-15 · Contents and general instructions Festo P.BE−CPX−AX−EN en 0811d I Original de

B. Index

B−12 Festo P.BE−CPX−AX−EN en 0811d

U

Unit of measurement for temperatureCPX−4AE−TC 5−21, 5−22 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Upper limit channel x 2−24, 3−24, 6−23 . . . . . . . . . . . . . . . . . . .