ADDENDUM LEVIN PORTER ASSOCIATES, INC. 3011 NEWMARK DRIVE MIAMISBURG, OHIO 45342 O: 937.224.1931 F:937.224.3091 www.levin-porter.com ADDENDUM NO. 02 November 13, 2020 Welding Lab Renovation Upper Valley Career Center LPA Project No. 203405.00 LEVIN PORTER ASSOCIATES, INC 3011 NEWMARK DRIVE MIAMISBURG, OHIO 45342 LPA PROJECT NO. 203405.00 TO ALL BIDDERS: This addendum including all items listed hereinafter, shall become a part of the documents, shall be taken into account in preparing the Proposal, and shall become a part of the Contract. The work under each branch shall be in accordance with the original specifications unless accepted in this Addendum. This Addendum consists of 2 pages plus 3 attachments totaling 5 pages. ITEM NO. 1: THE DRAWINGS SHALL BE REVISED AS FOLLOWS: 1.1 Sheet E.01 In ‘Fire Alarm System Specifications’ clarify vendor and delete reference of R.P Biedermann Company. 1.2 Sheet E2.1 On ‘Power New Work Plan’ add Added ‘Partial Plan’ – add 480 volt welder services to five locations in the open shop areas as shown on the plan Plan note additions and revisions. 1.3 Sheet M0.1 Added valve schedule Added Pipe identification Section to Gas Systems Schedule.

Upload: others

Post on 28-Mar-2021

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: ADDENDUMrlfender.com/files/UVCC_Welding_Lab_2020.11.13_Addendum... · 2020. 11. 13. · accordance with the original specifications unless accepted in this Addendum. This Addendum

ADDENDUM

LEVIN PORTER ASSOCIATES, INC.

3011 NEWMARK DRIVE MIAMISBURG, OHIO 45342

O: 937.224.1931 F:937.224.3091

www.levin-porter.com

ADDENDUM NO. 02 November 13, 2020 Welding Lab Renovation Upper Valley Career Center LPA Project No. 203405.00 LEVIN PORTER ASSOCIATES, INC 3011 NEWMARK DRIVE MIAMISBURG, OHIO 45342 LPA PROJECT NO. 203405.00 TO ALL BIDDERS: This addendum including all items listed hereinafter, shall become a part of the documents, shall be taken into account in preparing the Proposal, and shall become a part of the Contract. The work under each branch shall be in accordance with the original specifications unless accepted in this Addendum. This Addendum consists of 2 pages plus 3 attachments totaling 5 pages. ITEM NO. 1: THE DRAWINGS SHALL BE REVISED AS FOLLOWS: 1.1 Sheet E.01

• In ‘Fire Alarm System Specifications’ clarify vendor and delete reference of R.P Biedermann Company.

1.2 Sheet E2.1

• On ‘Power New Work Plan’ add Added ‘Partial Plan’ – add 480 volt welder services to five locations in the open shop areas as shown on the plan

• Plan note additions and revisions.

1.3 Sheet M0.1

• Added valve schedule

• Added Pipe identification Section to Gas Systems Schedule.

Page 2: ADDENDUMrlfender.com/files/UVCC_Welding_Lab_2020.11.13_Addendum... · 2020. 11. 13. · accordance with the original specifications unless accepted in this Addendum. This Addendum

LEVIN PORTER ASSOCIATES, INC.

3011 NEWMARK DRIVE MIAMISBURG, OHIO 45342 2

O: 937.224.1931 F:937.224.3091

www.levin-porter.com

ITEM NO. 2: THE SPECIFICATIONS SHALL BE REVISED AS FOLLOWS: 2.1 None

ITEM NO. 3: CLARIFICATIONS AS FOLLOWS: 3.1 QUESTION: Preferred or UVCC Controls Contractor used for DDC? ANSWER: Point to point, however there is no controls scope needed other than

demolition of one dual duct box. 3.2 QUESTION: Is the Existing Exhaust Duct for Demo Welded or Slip & Drive? ANSWER: Slip Drive 3.3 QUESTION: New Exhaust Duct for Fume Hoods? ANSWER: No new exhaust duct needed, hoods are filtered an self-contained. 3.4 The Bid Opening will remain as noted in the bid solicitation; IN PERSON and

NOT a virtual meeting. END OF ADDENDUM NO. 02

Page 3: ADDENDUMrlfender.com/files/UVCC_Welding_Lab_2020.11.13_Addendum... · 2020. 11. 13. · accordance with the original specifications unless accepted in this Addendum. This Addendum
Page 4: ADDENDUMrlfender.com/files/UVCC_Welding_Lab_2020.11.13_Addendum... · 2020. 11. 13. · accordance with the original specifications unless accepted in this Addendum. This Addendum
Page 5: ADDENDUMrlfender.com/files/UVCC_Welding_Lab_2020.11.13_Addendum... · 2020. 11. 13. · accordance with the original specifications unless accepted in this Addendum. This Addendum

WEL

DIN

G L

AB

REN

OV

ATI

ON

UPP

ER V

ALL

EY C

AR

EER

CEN

TER

8811

CA

REE

R D

RIV

EPI

QU

A, O

HIO

453

56

NAUMAN ELINSKIZ& LLC.

E FO

STA

OHTOI

GENERAL LEGENDDUCTWORK LEGEND

PIPING LEGEND

DUCT CONSTRUCTION AND SEALING 3113

DUCT SYSTEMSMACNA CLASS.

NOTESS.P.CONSTR.

SEALCLASS

AIR DEVICE SCHEDULE 3713

TAG DESCRIPTION MODEL NO. MATERIAL ACCESSORIES NOTES

DUCT INSULATION SCHEDULE 0713

SYSTEM INSULATION THICKNESS TYPE LOCATION NOTES

TYPE BASIS OF DESIGN APPROVED EQUALS DESCRIPTION

INDEX OF DRAWINGS

GAS SYSTEMS SCHEDULE

PIPING SYSTEM TYPE

TYPE DESCRIPTION TYPE DESCRIPTION

MC1 BRAZED COPPER FOR GASES S1 THREADED GALVANIZED STEEL

PLUMBING FIXTURE SCHEDULE

ITEM FIXTURE DESCRIPTION FIXTURESERVICES MTG.

HGT .TRIM REQUIREMENTS

NOTESH.W. C.W. SAN. VENT SUPPLY STOPS WASTE TRAP CARRIERS ACCESSORIES

VALVE SCHEDULE

PIPING SYSTEMVALVE TYPE

BUTTERFLY BALL CHECK GATE BALANCING LUB. PLUG

TYPE DESCRIPTION TYPE DESCRIPTION TYPE DESCRIPTION

B15

AutoCAD SHX Text
REVISIONS:
AutoCAD SHX Text
PROJECT NO:
AutoCAD SHX Text
CHECKED BY:
AutoCAD SHX Text
DRAWN BY:
AutoCAD SHX Text
DATE:
AutoCAD SHX Text
PRINTING:
AutoCAD SHX Text
DRAWING NUMBER
AutoCAD SHX Text
Phone: (937) 223-3821 ~ Fax: (937) 223-3849
AutoCAD SHX Text
204 S. Ludlow Street Dayton, Ohio 45402
AutoCAD SHX Text
203405.00
AutoCAD SHX Text
10/22/2020
AutoCAD SHX Text
BID / PERMIT SET - 10/22/2020
AutoCAD SHX Text
R
AutoCAD SHX Text
P
AutoCAD SHX Text
D
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
I
AutoCAD SHX Text
E
AutoCAD SHX Text
G
AutoCAD SHX Text
N
AutoCAD SHX Text
A
AutoCAD SHX Text
N
AutoCAD SHX Text
O
AutoCAD SHX Text
I
AutoCAD SHX Text
S
AutoCAD SHX Text
S
AutoCAD SHX Text
L
AutoCAD SHX Text
F
AutoCAD SHX Text
O
AutoCAD SHX Text
E
AutoCAD SHX Text
R
AutoCAD SHX Text
E
AutoCAD SHX Text
S
AutoCAD SHX Text
I
AutoCAD SHX Text
G
AutoCAD SHX Text
T
AutoCAD SHX Text
R
AutoCAD SHX Text
N
AutoCAD SHX Text
E
AutoCAD SHX Text
E
AutoCAD SHX Text
JEFFREY D.
AutoCAD SHX Text
ZELINSKI
AutoCAD SHX Text
63822
AutoCAD SHX Text
M0.1
AutoCAD SHX Text
DZ
AutoCAD SHX Text
JZ
AutoCAD SHX Text
EC
AutoCAD SHX Text
ELECTRICAL CONTRACTOR.
AutoCAD SHX Text
FC
AutoCAD SHX Text
FIRE PROTECTION CONTRACTOR.
AutoCAD SHX Text
GC
AutoCAD SHX Text
GENERAL CONTRACTOR.
AutoCAD SHX Text
HC
AutoCAD SHX Text
HVAC CONTRACTOR.
AutoCAD SHX Text
PC
AutoCAD SHX Text
PLUMBING CONTRACTOR.
AutoCAD SHX Text
TC
AutoCAD SHX Text
TEMPERATURE CONTROLS CONTRACTOR.
AutoCAD SHX Text
NIC
AutoCAD SHX Text
NOT IN CONTRACT.
AutoCAD SHX Text
AFF
AutoCAD SHX Text
ABOVE FINISHED FLOOR - TO BOTTOM OF ITEM UNLESS INDICATED OTHERWISE IN DRAWING.
AutoCAD SHX Text
(E)
AutoCAD SHX Text
EXISTING.
AutoCAD SHX Text
ES
AutoCAD SHX Text
EQUIPMENT SUPPLIER.
AutoCAD SHX Text
EM
AutoCAD SHX Text
EMERGENCY.
AutoCAD SHX Text
MH
AutoCAD SHX Text
MOUNTING HEIGHT.
AutoCAD SHX Text
S
AutoCAD SHX Text
SURFACE MOUNTED.
AutoCAD SHX Text
WP
AutoCAD SHX Text
WEATHER PROOF.
AutoCAD SHX Text
NOTE SYMBOL - APPLIES ONLY TO SHEET ON WHICH IS SHOWN.
AutoCAD SHX Text
DETAIL NOTE SYMBOL - APPLIES ONLY TO DETAIL ON WHICH IS SHOWN.
AutoCAD SHX Text
EQUIPMENT REFERENCE SYMBOL. ELECTRICAL CONNECTION REQUIRED.
AutoCAD SHX Text
EQUIPMENT REFERENCE SYMBOL. NO ELECTRICAL CONNECTION REQUIRED.
AutoCAD SHX Text
ROOM NUMBER.
AutoCAD SHX Text
DETAIL SYMBOL DETAIL "B" SHOWN ON SHEET H2.
AutoCAD SHX Text
SECTION SYMBOL SECTION "A" DESIGNATION, SHOWN ON SHEET H1.
AutoCAD SHX Text
CONNECTION, NEW TO EXISTING.
AutoCAD SHX Text
"UP TO" SYMBOL - INDICATES ITEM SERVED ON FLOOR ABOVE.
AutoCAD SHX Text
1 HOUR FIRE PROTECTION SEE SPECIFICATION FOR PENETRATION DETAILS.
AutoCAD SHX Text
2 HOUR FIRE PROTECTION SEE SPECIFICATION FOR PENETRATION DETAILS.
AutoCAD SHX Text
3 HOUR FIRE PROTECTION SEE SPECIFICATION FOR PENETRATION DETAILS.
AutoCAD SHX Text
ITEM TO BE REMOVED.
AutoCAD SHX Text
EXISTING ITEM TO REMAIN.
AutoCAD SHX Text
NEW ITEM.
AutoCAD SHX Text
3
AutoCAD SHX Text
2
AutoCAD SHX Text
H-1
AutoCAD SHX Text
H-1
AutoCAD SHX Text
123
AutoCAD SHX Text
B
AutoCAD SHX Text
H2
AutoCAD SHX Text
A
AutoCAD SHX Text
H1
AutoCAD SHX Text
FD1
AutoCAD SHX Text
RECTANGULAR DUCT FIRST FIGURE IS SIDE SHOWN
AutoCAD SHX Text
ROUND DUCT DIAMETER INDICATED
AutoCAD SHX Text
FLAT OVAL DUCT FIRST FIGURE IS SIDE SHOWN
AutoCAD SHX Text
INSULATED FLEXIBLE DUCT
AutoCAD SHX Text
CHANGE OF ELEVATION R = RISE, D = DROP
AutoCAD SHX Text
ELBOW WITH TURNING VANES
AutoCAD SHX Text
ROUND RUNOUT DUCT TAP TO RECTANGULAR DUCT WITH SPIN-IN FITTING, SEE DETAIL
AutoCAD SHX Text
ROUND RUNOUT DUCT FITTING IN ROUND DUCT MAIN
AutoCAD SHX Text
VOLUME DAMPER
AutoCAD SHX Text
SUPPLY DUCT SECTION - RISE, DROP
AutoCAD SHX Text
RETURN DUCT SECTION - RISE, DROP
AutoCAD SHX Text
VARIABLE AIR VOLUME UNIT WITH REHEAT COIL
AutoCAD SHX Text
VARIABLE AIR VOLUME UNIT WITHOUT REHEAT COIL
AutoCAD SHX Text
SUPPLY AIR DEVICE S1 SEE SCHEDULE AND DETAIL 8" = NECK SIZE 300 = REQUIRED AIR FLOW (CFM)
AutoCAD SHX Text
TRANSFER AIR DEVICE 24"X24" WITH PLENUM R1 DEVICE TAG, SEE SCHEDULE AND DETAIL
AutoCAD SHX Text
TRANSFER AIR DEVICE 24"X12" WITH PLENUM R1 DEVICE TAG, SEE SCHEDULE AND DETAIL
AutoCAD SHX Text
RETURN/EXHAUST/TRANSFER GRILLE R1 R1 = DEVICE TAG, SEE SCHEDULE AND DETAIL 300 = REQUIRED AIR FLOW (CFM) DEVICE SIZE AS DEPICTED ON DRAWINGS OR AS INDICATED IN AIR DEVICE SCHEDULE
AutoCAD SHX Text
SIDEWALL AIR DEVICE SEE AIR DEVICE SCHEDULE 24/12 = DEVICE SIZE 300 = AIR FLOW (CFM) 8'6" = MOUNTING HEIGHT (AFF)
AutoCAD SHX Text
EXISTING AIR DEVICE REBALANCE TO AIR FLOW INDICATED
AutoCAD SHX Text
ROOM TEMPERATURE SENSOR
AutoCAD SHX Text
20/12
AutoCAD SHX Text
20/12
AutoCAD SHX Text
10"%%c
AutoCAD SHX Text
10"%%c
AutoCAD SHX Text
24/14%%c
AutoCAD SHX Text
24/14%%c
AutoCAD SHX Text
R
AutoCAD SHX Text
20/12
AutoCAD SHX Text
10"%%c
AutoCAD SHX Text
%%US1-8"
AutoCAD SHX Text
300
AutoCAD SHX Text
%%UR1
AutoCAD SHX Text
%%UR1
AutoCAD SHX Text
%%UR1
AutoCAD SHX Text
300
AutoCAD SHX Text
%%US2-24/12
AutoCAD SHX Text
300-8'6"
AutoCAD SHX Text
%%U(E)
AutoCAD SHX Text
120
AutoCAD SHX Text
T
AutoCAD SHX Text
SHUT-OFF VALVE, SEE SCHEDULE FOR TYPE
AutoCAD SHX Text
CHECK VALVE
AutoCAD SHX Text
BALANCING VALVE
AutoCAD SHX Text
VALVE ON RISER
AutoCAD SHX Text
PRESSURE REDUCING VALVE
AutoCAD SHX Text
REGULATOR
AutoCAD SHX Text
PRESSURE GAUGE
AutoCAD SHX Text
TEMPERATURE GAUGE
AutoCAD SHX Text
CONNECTION, BOTTOM
AutoCAD SHX Text
CONNECTION, TOP
AutoCAD SHX Text
INDICATES DIRECTION OF FLOW
AutoCAD SHX Text
CAP
AutoCAD SHX Text
ARGON GAS
AutoCAD SHX Text
ARGON/CO GAS 2 GAS
AutoCAD SHX Text
COMPRESSED AIR
AutoCAD SHX Text
R
AutoCAD SHX Text
P
AutoCAD SHX Text
T
AutoCAD SHX Text
AR
AutoCAD SHX Text
FOLLOW SMACNA HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE - THIRD EDITION.
AutoCAD SHX Text
DUCT TO BE HOT DIPPED, GALVANIZED BOTH SIDES, G90 PER ASTM A653 EXCEPT WHERE NOTED OTHERWISE.
AutoCAD SHX Text
EXPOSED DUCTWORK IN FINISHED AREAS TO BE PAINTED SHALL BE HOT DIPPED, HEAT TREATED GALVANEALED BOTH SIDES, UNIFORM GRAY MATTE APPEARANCE, A40 PER ASTM A653.
AutoCAD SHX Text
ROUND OR FLAT OVAL DUCTWORK (2" S.P. AND HIGHER)
AutoCAD SHX Text
CONTINUOUS HELICAL (SPIRAL) LOCK SEAM CONSTRUCTION WITH SLIP CONNECTIONS. GASKETED FLANGES ARE NOT ACCEPTABLE.
AutoCAD SHX Text
USE 45 DEG. LATERAL TEE WHEREVER POSSIBLE.
AutoCAD SHX Text
90 DEG. TEES SHALL BE CONICAL.
AutoCAD SHX Text
DIE STAMPED ELBOWS, r/D = 1.5 (MIN.)
AutoCAD SHX Text
RADIUSED, ANGLED (15 DEG. MAX.) OR MITERED (15 DEG. MAX.) OFFSETS
AutoCAD SHX Text
CONCENTRIC TRANSITIONS, 0 = 45 DEG. MAX.
AutoCAD SHX Text
ECCENTRIC TRANSITIONS, 0 = 30 DEG. MAX.
AutoCAD SHX Text
ROUND DUCTWORK (1" S.P. OR LESS) SAME AS ABOVE EXCEPT:
AutoCAD SHX Text
LONGITUDINAL SEALED SEAM ACCEPTABLE AT FINAL AIR DEVICE ONLY.
AutoCAD SHX Text
STANDARD TEES ALLOWED.
AutoCAD SHX Text
SEGMENTED ELBOWS ALLOWED.
AutoCAD SHX Text
RECTANGULAR DUCTW0RK (2" S.P. AND HIGHER)
AutoCAD SHX Text
FLAT SLIP, STANDING DRIVE OR GASKETED DUCT SYSTEM JOINTS.
AutoCAD SHX Text
RADIUS OR SQUARE THROAT WITH DOUBLE WALL TURNING VANES ELBOW.
AutoCAD SHX Text
45 DEG. ENTRY OR CONICAL SPIN IN BRANCH CONNECTIONS.
AutoCAD SHX Text
RADIUSED, ANGLED (15 DEG. MAX.) OR MITERED (15 DEG. MAX.) OFFSETS.
AutoCAD SHX Text
CONCENTRIC TRANSITIONS, 0 = 45 DEG. MAX.
AutoCAD SHX Text
ECCENTRIC TRANSITIONS, 0 = 30 DEG. MAX.
AutoCAD SHX Text
BRANCH DUCTS SHALL BE CONICAL TEE FITTINGS.
AutoCAD SHX Text
SQUARE THROAT, RADIUS HEEL 90 DEG. ELBOWS ARE NOT PERMITTED WITHOUT THE USE OF TURNING VANES.
AutoCAD SHX Text
RECTANGULAR DUCTWORK (1" S.P. OR LESS) SAME AS ABOVE EXCEPT:
AutoCAD SHX Text
TURNING VANES IN ELBOWS NOT REQUIRED FOR AIR VELOCITIES LESS THAN 800 FPM.
AutoCAD SHX Text
STRAIGHT TAP AND STANDARD SPIN IN BRANCH CONNECTIONS PERMITTED.
AutoCAD SHX Text
DUCT HANGER SUPPORTS SHALL DIRECTLY ATTACH TO DUCTWORK. EXTERIOR DUCT INSULATION WRAP SHALL BE APPLIED OVER DUCT AND HANGER SUPPORTS. ANGLE OR UNISTRUT SUPPORTS SHALL BE INSULATED A MINIMUM OF 4" BEYOND DUCT BEARING POINT TO PREVENT CONDENSATION.
AutoCAD SHX Text
FLEXIBLE DUCTWORK (SUPPLY/RETURN/TRANSFER/EXHAUST)
AutoCAD SHX Text
CHLORINATED POLYETHYLENE INNER FABRIC - BLACK COLOR
AutoCAD SHX Text
R = 4.2 (MIN.) FIBERGLASS INSULATION.
AutoCAD SHX Text
REINFORCED METALIZED VAPOR BARRIER, 0.05 PERM.
AutoCAD SHX Text
UL 181, CLASS 1 DUCT, MEET NFPA 90A & 90B.
AutoCAD SHX Text
PROVIDE MANUFACTURERED DUCT SUPPORTS AT 90 DEGREE ELBOWS TO CEILING AIR DEVICES.
AutoCAD SHX Text
FLAME SPREAD LESS THAN 25, SMOKE DEVELOPMENT LESS THAN 50.
AutoCAD SHX Text
RETURN AIR
AutoCAD SHX Text
-2"
AutoCAD SHX Text
A
AutoCAD SHX Text
EXHAUST AIR
AutoCAD SHX Text
-2"
AutoCAD SHX Text
A
AutoCAD SHX Text
AIR TRANSFER
AutoCAD SHX Text
-1"
AutoCAD SHX Text
NOT REQ'D
AutoCAD SHX Text
SUPPLY AIR VAV UPSTREAM
AutoCAD SHX Text
+4"
AutoCAD SHX Text
A
AutoCAD SHX Text
SUPPLY AIR VAV DOWNSTREAM
AutoCAD SHX Text
+1"
AutoCAD SHX Text
A
AutoCAD SHX Text
SUPPLY AIR CONSTANT VOLUME
AutoCAD SHX Text
+3"
AutoCAD SHX Text
A
AutoCAD SHX Text
FLEXIBLE DUCT - SUPPLY
AutoCAD SHX Text
+10" -5"
AutoCAD SHX Text
N.A.
AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text
AIR DEVICES BASED ON PRICE, LOUVERS BASED ON GREENHECK. REFER TO SPECIFICATIONS FOR OTHER MANUFACTURERS. MAXIMUM SOUND LEVEL OF NC-25 AT INDICATED AIR FLOW. BALANCING DAMPER GENERALLY PROVIDED IN DUCT, NOT AT DEVICE.
AutoCAD SHX Text
STANDARD WHITE BAKED ACRYLIC FINISH UNLESS NOTED OTHERWISE. DIFFUSERS SHALL BE 4-WAY THROW UNLESS OTHERWISE NOTED OR INDICATED ON DRAWINGS. VERIFY CEILING TYPE AND PROVIDE APPROPRIATE MOUNTING FRAME WHERE REQUIRED FOR OTHER THAN LAY-IN APPLICATION OR IN LINE "T" BAR.
AutoCAD SHX Text
S1
AutoCAD SHX Text
2'X2' SQUARE PLAQUE DIFFUSER LAY-IN FRAME ROUND DUCT CONNECTION
AutoCAD SHX Text
SPD
AutoCAD SHX Text
STEEL
AutoCAD SHX Text
INSULATED BACKPAN (STYLE 31)
AutoCAD SHX Text
R1
AutoCAD SHX Text
RETURN/EXHAUST/TRANSFER GRILLE DEVICE SIZE - 24" X 12" 45° HORIZONTAL BLADES 1/2" SPACING
AutoCAD SHX Text
635
AutoCAD SHX Text
ALUMIN.
AutoCAD SHX Text
LAY-IN FRAME
AutoCAD SHX Text
QUALITY ASSURANCE INSULATION SHALL MEET NFPA 255, 25 FLAME SPREAD & 50 SMOKE DEVELOPMENT, UL 181, NFPA 90A/90B, ASTM 1136, AND ASTM E84. MINIMUM INSULATION THICKNESS SHALL COMPLY WITH ASHRAE 90.1-2010.
AutoCAD SHX Text
PRODUCTS - PROTECTIVE METAL JACKET COVERS - 0.016" ALUMINUM.
AutoCAD SHX Text
EXECUTION - INSULATION SHALL BE INSTALLED IN STRICT ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. - DUCTWORK SHALL BE SEALED PRIOR TO INSTALLATION OF INSULATION. - ALL EXTERIOR DUCT INSULATION SHALL BE SEALED WATERTIGHT. - REINSULATE DUCTWORK WHERE EXISTING INSULATION IS DAMAGED IN CONNECTION OF NEW DUCTWORK. - ALL INSULATION VAPOR BARRIERS SHALL BE MAINTAINED. - ADHESIVE SHALL BE APPLIED TO AID INSTALLATION. - REQUIRED INTERNAL DUCT LINING IS INDICATED ON DRAWINGS. LINED DUCTWORK NEED NOT BE FURTHER INSULATED. - DUCT COILS, REHEAT BOX COILS, CONTROL DAMPER, FIRE DAMPERS & SMOKE DAMPERS SHALL BE INSULATED IF SYSTEM INSULATION IS INDICATED. - ALL INSULATION SHALL BE MARKED WITH MANUFACTURER, "R" VALUE, FLAME SPREAD & SMOKE DEVELOPMENT.
AutoCAD SHX Text
SUPPLY AIR DUCT
AutoCAD SHX Text
1.5"
AutoCAD SHX Text
1
AutoCAD SHX Text
CONCEALED
AutoCAD SHX Text
SUPPLY AIR DUCT
AutoCAD SHX Text
2"
AutoCAD SHX Text
2
AutoCAD SHX Text
EXPOSED
AutoCAD SHX Text
RETURN AIR DUCT
AutoCAD SHX Text
-
AutoCAD SHX Text
-
AutoCAD SHX Text
CONCEALED
AutoCAD SHX Text
1
AutoCAD SHX Text
OWENS-CORNING SOFTR TYPE 75
AutoCAD SHX Text
KNAUF JM CERTAIN TEED
AutoCAD SHX Text
MATERIAL FIBERGLASS DUCT WRAP ON DUCT K = 0.30 @ 75 DEG. F. DENSITY - 0.75 PCF JACKET - FOIL REINFORCED JOINTS - OVERLAPPING STAPLE ALL JOINTS AT 6" CENTERS. FASTENERS - MECHANICAL ON 24" & WIDER DUCT. ADHESIVE - NONE TAPE - 3" WIDE
AutoCAD SHX Text
2
AutoCAD SHX Text
OWENS-CORNING TYPE 703
AutoCAD SHX Text
KNAUF JM CERTAIN TEED
AutoCAD SHX Text
MATERIAL FIBERGLASS BOARD ON DUCT K = 0.23 @ 75 DEG. F. DENSITY - 3.0 PCF JACKET - ASJ JOINTS - BUTT FASTENERS - METAL PINS & CLIPS ON 12" CENTERS ADHESIVE - NONE TAPE - 3" WIDE VAPOR PATCHED
AutoCAD SHX Text
SHEET
AutoCAD SHX Text
DRAWING TITLE
AutoCAD SHX Text
M0.1
AutoCAD SHX Text
LEGENDS & SCHEDULES
AutoCAD SHX Text
M1.1
AutoCAD SHX Text
WORK PLANS
AutoCAD SHX Text
M2.1
AutoCAD SHX Text
DETAILS
AutoCAD SHX Text
AR/C0 2
AutoCAD SHX Text
GENERAL NOTES:
AutoCAD SHX Text
QUALITY ASSURANCE PIPING SHALL CONFORM TO OBC REQUIREMENTS. PIPING SHALL COMPLY WITH ASME B31.9 "BUILDING SERVICES PIPING". ALL COMPONENTS OF DOMESTIC WATER SYSTEMS (CW, HW, & HWR) SHALL BE "LEAD FREE" IN ACCORDANCE WITH THE FEDERAL SAFE WATER ACT (S3874) DEFINITION AND CONFORM TO NSF 61. PRODUCTS DIELECTRIC CONNECTORS SHALL BE PROVIDED AT CONNECTIONS BETWEEN FERROUS & COPPER PIPING. UNIONS COPPER TUBING - WROUGHT OR CAST COPPER, CLASS 150, SOLDERED ENDS THREADED STEEL PIPE - MALLEABLE IRON W/GROUND SEAT, 300 LB SCREWED ENDS. MECHANICALLY FORMED TEES AND COUPLINGS (T-DRILL) ARE NOT PERMITTED. EXECUTION PIPE AND TUBING SHALL BE CUT AND FABRICATED TO FIELD MEASUREMENTS AND RUN PARALLEL TO NORMAL BUILDING LINES. PIPE INTERIOR SHALL BE CLEANED OF FOREIGN MATTER AND BURRS BEFORE ERECTION OF PIPE. ANNULAR SPACE AROUND PIPING THRU ALL WALLS SHALL BE SEALED OFF WITH PERMANENT PLIABLE CAULKING OR APPROVED PATCHING SEALANT. PROVIDE PIPING SLEEVES AT FLOORS, WALLS & ROOFS IN NEW CONSTRUCTION. EXISTING WALLS TO BE SAW CUT TO PASS NEW PIPING. PIPING SHALL NOT BE RUN ABOVE ELECTRICAL SWITCHGEAR OR PANELBOARDS, NOR ABOVE THE ACCESS SPACE OF SUCH EQUIPMENT - NEC ARTICLE 384. PIPING SHALL BE PITCHED FOR DRAINAGE. CLOSE OPEN ENDS OF PIPING DURING CONSTRUCTION. MECHANICAL JOINT PIPING SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S RECOMMENDATIONS. SUPPORT PIPING FROM BUILDING STRUCTURE WITH RODS, ANGLES & CLAMPS ATTACHED TO STRUCTURE. HANG PIPING WITH CLEVIS HANGER OR ROLLER SUPPORTS. HANGERS SHALL BE INSTALLED ON CENTERS AS RECOMMENDED BY MANUFACTURER. TESTING WELD GAS PIPING - 200 PSI FOR 6 HOURS. COMPRESSED AIR PIPING - 200 PSI FOR 6 HOURS. IDENTIFICATION & MARKING PLASTIC SNAP-ON PIPE MARKERS SHALL BE INSTALLED ON PIPING INDICATING SERVICE AND DIRECTION OF FLOW.
AutoCAD SHX Text
WELDING GASES ARGON & ARGON/CO 2
AutoCAD SHX Text
MC1
AutoCAD SHX Text
COMPRESSED AIR
AutoCAD SHX Text
S1
AutoCAD SHX Text
SEAMLESS ASTM B819 TYPE "L" HARD COPPER COPPER FITTINGS ASME B16.22 OR MSS SP-73 PIPE AND FITTINGS SHALL BE MANUFACTURER CLEANED, PURGED, AND BAGGED ACCORDING TO CGA G-4-1
AutoCAD SHX Text
SCHEDULE 40, ASTM A53 TYPE E OR F CLASS 300 FITTINGS W/ PTFE TAPE ASME B16.3
AutoCAD SHX Text
F1
AutoCAD SHX Text
DRINKING FOUNTAIN/ STAINLESS STEEL/ WALL HUNG/ SINGLE COOLER/ HANDS FREE/ BOTTLE FILLER/ ACCESSIBLE
AutoCAD SHX Text
ELKAY # EZO8WSSK
AutoCAD SHX Text
-
AutoCAD SHX Text
0.5"
AutoCAD SHX Text
1.5"
AutoCAD SHX Text
1.25"
AutoCAD SHX Text
34" TO BBLR.
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
MCGUIRE # LFBV170
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
MCGUIRE # 8902
AutoCAD SHX Text
UNIT
AutoCAD SHX Text
1
AutoCAD SHX Text
EQUALS ELKAY - JUST, ADVANCED TABCO,
AutoCAD SHX Text
NOTES 1. COORDINATION INSTALLATION WITH EXISTING PLUMBING ROUGH-IN.
AutoCAD SHX Text
A
AutoCAD SHX Text
2
AutoCAD SHX Text
ADDENDUM 2 - 11/13/2020
AutoCAD SHX Text
GENERAL NOTES FOR VALVES:
AutoCAD SHX Text
QUALITY ASSURANCE CE VALVES SHALL COMPLY WITH ANSI, ASTM AND ASME. VALVES ON DOMESTIC WATER SYSTEMS SHALL BE "LEAD FREE" IN ACCORDANCE WITH THE FEDERAL SAFE WATER ACT (S3874) DEFINITION AND CONFORM TO NSF 61. GROOVED END VALVES SHALL CONFORM TO ANSI/AWWA C-606. PRODUCTS WORKING PRESSURES SHALL EXCEED THOSE IMPOSED BY THE SERVICE APPLIED. VALVES WHICH ARE INSULATED SHALL HAVE EXTENDED SHAFTS. PROVIDE FLOW MEASURING GAUGES WITH COCKS, HOSES & CONNECTORS FOR BALANCING VALVES. PROVIDE METERING TOOL. PROVIDE HOSE ADAPTORS ON DRAIN VALVES. SWEAT END VALVES OF EQUAL CONSTRUCTION ARE ACCEPTABLE IN LIEU OF SCREWED ENDS. IN MECHANICALLY JOINED SYSTEMS, VALVES OF EQUAL CONSTRUCTION WITH COMPATIBLE ENDS ARE ACCEPTABLE AND MAY BE MANUFACTURED BY THE COUPLING MANUFACTURER. VALVE MANUFACTURERS: BALL VALVES - NIBCO, WATTS, MILWAUKEE, APOLLO, CONBRACO, CRANE. BALANCING VALVES - BELL & GOSSETT, ARMSTRONG, WATTS. CHECK VALVES - NIBCO, STOCKHAM, WATTS. EXECUTION VALVES SHALL BE INSTALLED WITH STEM ABOVE CENTERLINE OF PIPE.
AutoCAD SHX Text
COMPRESSED AIR (150 PSI AND LESS) 2" AND SMALLER
AutoCAD SHX Text
B15
AutoCAD SHX Text
WELDING GASES
AutoCAD SHX Text
B17
AutoCAD SHX Text
NIBCO T-580-CS-R-66 1500 W.O.G., TWO-PIECE CARBON STEEL BODY, SCREWED ENDS, STAINLESS STEEL BALL AND STEM, TFE SEAT AND SEAL, HANDLE.
AutoCAD SHX Text
B17
AutoCAD SHX Text
NIBCO T-FP-600A, 600 PSI NON-SHOCK COLD., 2 PIECE, BRASS BODY, SCREWED ENDS, FULL PORT, BRASS BALL, TFE SEAT, HANDLE. UL LISTED FOR GAS. ASME B16.44
AutoCAD SHX Text
2