2100-269(g) (2002 10) - bardhvac.com
TRANSCRIPT
SPLIT AIR CONDITIONEROUTDOOR SECTION50HZ Models
HAC181-DHAC241-DHAC301-DHAC361-GHAC421-GHAC421-EHAC421-FHAC481-GHAC481-EHAC481-FHAC601-GHAC601-EHAC601-F
For Use With:Matching IndoorBlower Coil Unitsand Matching AddOn Coil Units Only
INSTALLATION INSTRUCTIONS
Manual No.: 2100-269GSupersedes: 2100-269FFile: Tab 4Date: 10-01-02
Bard Manufacturing CompanyBryan, Ohio 43506
Since 1914...Moving ahead, just as planned.
© Copyright 2002
CONTENTS
i
Split Air Conditioner General Information ......... 1Split Air Conditioner Model Nomenclature ............... 1
Application and Location .................................... 5General .................................................................... 5Shipping Damage .................................................... 5Application ............................................................... 5Location ................................................................... 5Mounting Unit Outside on Slab ................................. 5Important Installer Note ............................................ 5Installing Refrigerant Tubing ..................................... 5Sweat Style Tubin Connections: SweatIndoor Unit and Sweat Outdoor Unit ........................ 6Field Fabricated Tubing Connections:Quick Connect Indoor Unit and SweatOutdoor Unit Using CTO Kit ..................................... 7
Wiring Instructions ............................................ 10General .................................................................. 10Control Circuit Wiring ............................................. 10Wall Thermostats ................................................... 10Optional Controls ................................................... 13Installation Instructions – CMA-5 ............................ 13Installation Instructions – CMA-6 ............................ 13Installation Instructions – CMA-10A........................ 14Installation Instructions – CMA-13A........................ 15
Charging Instructions........................................ 16Pressure Service Ports .......................................... 16System Start-Up (Indoor Unitswithout Expansion Valves ....................................... 16
Service ................................................................ 18Service Hints .......................................................... 18Fan Blade Setting Dimensions ............................... 18Pressure Tables ................................................ 22-25
FIGURESFigure 1 .................................................................... 1Figure 2 .................................................................... 5Figure 3 .................................................................... 6Figure 4 .................................................................... 6Figure 5 .................................................................. 13Figure 6 .................................................................. 13Figure 7 .................................................................. 13Figure 8 .................................................................. 14Figure 9 .................................................................. 15
TABLESTable 1 ..................................................................... 1Table 2 ..................................................................... 2Table 3 ............................................................... 3 & 4Table 4 ..................................................................... 7Table 5 ..................................................................... 9Table 6 ................................................................... 10Table 7 ................................................................... 10Table 8 ................................................................... 10Table 9 ................................................................... 16Table 10 ................................................................. 16Table 11 ................................................................. 17Table 12 ................................................................. 18Table 13 ................................................................. 22Table 14 ................................................................. 22Table 15 ................................................................. 23Table 16 ................................................................. 23Table 17 ................................................................. 24Table 18 ................................................................. 24Table 19 ................................................................. 25
Manual 2100-269Page 1
SPLIT AIR CONDITIONER MODEL NOMENCLATURE
TABLE 1UNIT DIMENSIONS (INCHES)
.oNledoM"W"htdiW
"D"htpeD
"H"thgieH A B C E F
181CAH142CAH 00.04 00.51 00.62 521.5 881.02 00.4 521.7 881.42
103CAH163CAH 00.54 00.51 00.62 521.5 881.52 00.4 521.7 881.92
124CAH184CAH106CAH
00.05 00.51 00.23 526.6 886.82 00.4 526.8 886.23
W
H
C
BF
E
A
D
HIGH VOLTAGEENTRANCE
LOW VOLTAGEENTRANCE
ALTERNATEELECTRICALENTRANCES
ON BACK
REFRIGERANTSHUTOFFVALVES
MIS-1789
Customized Unit Code
Electrical CharacteristicsD - 240-220-50-1E - 220-200-50-3F - 415-380-50-3G - 220-200-50-1
Modification Code
Capacity – 3 Ton or approx. 36,000 BTU
Basic Model Number
HAC 36 1 – G DXXX
FIGURE 1
DIMENSIONAL DRAWING
Manual 2100-269Page 2
� Measured across the evaporator coil assembly, including drain pan.� External static pressure available for the duct system -- supply and return. All blower coils have
multispeed motors, and value shown is at the recommended rated speed. Consult specificationair flow charts with the blower coil units for complete information at other speeds.
* IMPORTANT INFORMATIONProper sized orifice is not factory installed in indoor section. Proper orifice size is shipped withindoor coil packaged with its installation instructions for indoor sections listed on this page. Theorifice must be replaced with the proper system orifice shown above in Table 2.
For other evaporator coil models not listed, see indoor coil installation instructions for proper orificeinformation.
TABLE 2
RATED CFM AND AIR FLOW DATA(WET COIL – COOLING)
wolfriAdetaR
gnisnednoCtinU
.oNledoM
rotaropavElioC
.oNledoMMFC
erusserPHporD 2O
dednemmoceRwolFriAegnaR
metsySecifirO
deriuqeR
181CAH A-SA03A 056 51. 517-055 250. *
142CAH A-SA03A 008 81. 019-007 550.
103CAH A-SA63A 000,1 02. 571,1-058 360.
163CAH A-SA73A 001,1 81. 022,1-029 960.
124CAHA-SA24AA-SA84A
004,1 03.055,1-072,1526,1-052,1
870.870.
184CAH B-SA16A 007,1 82. 578,1-054,1 180. *
106CAH B-SA16A 067,1 03. 059,1-005,1 290.
Manual 2100-269
Page 3
SLEDOM D-181CAH D-142CAH D-103CAH G-163CAH G-124CAH E-124CAH F-124CAH
)HP/V/ZH06(gnitaRlacirtcelE 1-022/042 1-022/042 1-022/042 1-002/022 1-002/022 3-002/022 3-083/514
egnaRegatloVgnitarepO 452-891 452-891 452-891 242-081 242-081 242-081 654-243
yticapmAtiucriCmuminiM 21 61 71 82 23 02 11
� eziSeriWdleiF 41 41 21 01 8 21 41
� rekaerBtiucriCromumixaMesuFyaleD 51 52 03 54 05 03 51
802/032spmAtinUlatoT 6.9 8.21 9.41 2.12 0.32 8.41 1.8
ROSSERPMOC
802/032stloV 022/042 022/42 022/042 002/022 002/022 002/022 083-514
spmAdaoLdetaR 1.8 3.11 4.31 7.91 5.12 3.31 6.6
tnerruCnoitceleStiucriChcnarB 1.8 3.11 7.31 1.12 7.32 7.41 0.7
802/032spmArotoRkcoL 0.54 0.56 7.08 0.801 0.611 0.29 0.64
taeHesacknarC epyTnoisremmI
RESNEDNOCdnaROTOMNAF
MPR/PHrotoMnaF 528-4/1 528-4/1 528-4/1 528-4/1 528-4/1 528-4/1 528-4/1
spmArotoMnaF 5.1 5.1 5.1 5.1 5.1 5.1 5.1
retemaiDnaF 000,2-"02 000,2-"02 000,2-"02 000,2-"02 006,2-"42 006,2-"42 006,2-"42
METSYSTCENNOCTAEWS
DIeziSeniLnoitcuS "8/5 "4/3 "4/3 "4/3 "8/7 "8/7 "8/7
DIeziSeniLdiuqiL "4/1 "8/3 "8/3 "8/3 "8/3 "8/3 "8/3
.zO22-RegnahCyrotcaF .zo37 .zo97 .zo48 .zo69 .zo201 .zo201 .zo201
.SBLTHGIEWGNIPPIHS 551 551 081 081 052 052 052
TABLE 3
SPECIFICATIONS
Manual 2100-269
Page 4
TABLE 3
SPECIFICATIONS (CONTINUED)
SLEDOM G-184CAH E-184CAH F-184CAH G-184CAH E-106CAH F-106CAH
)HP/V/ZH06(gnitaRlacirtcelE 1-002/022 3-002/022 3-083/514 1-002-022 3-002/022 3-083/514
egnaRegatloVgnitarepO 022-081 242-081 654-243 022-081 242-081 654-243
yticapmAtiucriCmuminiM 83 32 31 04 72 51
� eziSeriWdleiF 8 01 41 8 8 41
� rekaerBtiucriCromumixaMesuFyaleD 06 04 02 06 54 02
802/032spmAtinUlatoT 9.52 0.61 0.9 7.92 5.81 3.01
ROSSERPMOC
802/032stloV 002/022 002/022 083-514 002/022 002/022 083-514
spmAdaoLdetaR 4.42 5.41 5.7 2.82 0.71 8.8
tnerruCnoitceleStiucriChcnarB 8.82 3.71 0.9 1.03 5.02 2.01
802/032spmArotoRkcoL 831 601 35 871 421 26
taeHesacknarC epyTnoisremmI
RESNEDNOCdnaROTOMNAF
MPR/PHrotoMnaF 528-4/1 528-4/1 528-4/1 528-4/1 528-4/1 528-4/1
spmArotoMnaF 5.1 5.1 5.1 5.1 5.1 5.1
retemaiDnaF 006,2-"42 006,2-"42 006,2-"42 006,2-"42 006,2-"42 006,2-"42
METSYSTCENNOCTAEWS
DIeziSeniLnoitcuS "8/7 "8/7 "8/7 "8/7 "8/7 "8/7
DIeziSeniLdiuqiL "8/3 "8/3 "8/3 "8/3 "8/3 "8/3
.zO22-RegnahCyrotcaF .zo551 .zo551 .zo551 .zo351 .zo351 .zo351
.SBLTHGIEWGNIPPIHS 052 052 052 552 552 552
Manual 2100-269Page 5
APPLICATION and LOCATION
GENERAL
These instructions explain the recommended method toinstall the air cooled remote type condensing unit, theinterconnecting refrigerant tubing and the electrical wiringconnections to the unit.
The condensing units are to be used in conjunction with thematching evaporator coils or evaporator blower units forcomfort cooling applications as shown in the specificationsheet.
These instructions and any instructions packaged with anyseparate equipment required to make up the entire airconditioning system should be carefully read beforebeginning the installation. Note particularly “StartingProcedure” and any tags and/or labels attached to theequipment.
SHIPPING DAMAGE
Upon receipt of equipment, the carton should be checked forexternal signs of shipping damage. If damage is found, thereceiving part must contact the last carrier immediately,preferably in writing, requesting inspection by the carrier’sagent.
APPLICATION
Size of unit for a proposed installation should be based onheat loss calculation and air duct sizing made according tomethods of Air Conditioning Contractors of America. Theair duct should be installed in accordance with the Standardsof the National Fire Protection Association for theInstallation of Air Conditioning and Ventilating Systems ofOther Than Residence Type, NFPA 90A, and ResidenceType Warm Air Heating and Air Conditioning Systems,NFPA 90B. Where local regulations are at a variance withinstructions, installer should adhere to local codes.
LOCATION
The condensing unit is designed to be located outside withfree and unobstructed condenser air inlet and discharge. Itmust also permit access for service and installation.Condenser air enters the coil and discharges. Refrigerantand electrical connections are made from the rear of the unitas shown in Figure 2 with electrical service access.
MOUNTING UNIT OUTSIDE ON SLAB
A solid level base or platform, capable to support the unit’sweight, must be set at the outdoor unit predeterminedlocation. The base should be at least two inches larger thanthe base dimensions of the unit and at least two incheshigher than surrounding grade level. The required unitminimum installed clearances must be maintained as calledout in Figure 2 when locating and setting the base.
Remove the unit from its shipping carton and position theunit on the prepared base or platform.
NOTE: These units employ internally sprungcompressors; therefore, it is not necessary toremove or loosen the base mounting bolts on thecompressor prior to operation.
Consideration should be given to the electrical and tubingconnections when placing the unit to avoid unnecessarybends or length of material.
IMPORTANT INSTALLER NOTE
For improved start up performance, wash the indoor coilwith a dishwashing detergent.
INSTALLATION REFRIGERANT TUBING
The information that follows on installing refrigerant tubingand for changing the system orifice (if required) coversapplications listed in the front of this installation instructiononly. Although other indoor units may be of similarconstruction, the installation instructions for these unitsshould be consulted for proper installation of those unitsprior to installation.
This information is provided for the field service personnelto install refrigerant tubing in compliance with Section 608of Title VI National Recycling and Emission ReductionProgram for the U.S. Clean Air Act effective July 1, 1992.
Consult manual 2100-002 on procedure for leak test –evacuation – charging before installation refrigerant tubingthat requires any refrigerant recovery or system evacuation.Manual 2100-002 is included with the unit installationinstruction package when shipped from the factory.
FIGURE 2
INSTALLATION CLEARANCE
MIS-589
Manual 2100-269Page 6
SWEAT STYLE TUBING CONNECTIONS: SWEATINDOOR UNIT and SWEAT OUTDOOR UNIT
Use only refrigeration grade (dehydrated and sealed) coppertubing. Care must be taken to insure that the tubing is keptclean and dry before and during installation. Do not removethe plugs from the tubing ends, coil connections or basevalves until the connection is ready to be brazed.
The suction line must be insulated with a minimum of 3/8”Armaflex or equivalent before cutting and makingconnections.
1. Being careful not to kink, route both the suction lineand liquid line between the indoor unit and outdoorunit. Use a tubing bender to make any necessary bendsin tubing. When necessary to bend the insulated tubesuction line, cut the insulation around its circumferenceat a distance far enough beyond the point of the bend soas to clear the tubing bender. Slip the insulation backtogether and vapor seal the joint with tape. Coil anyexcess tubing in a horizontal place with the slope of thetubing toward the condensing unit. See Figure 3.
NOTE: Do not braze line to units! If orifice needs to bechanged, change out orifice first.
If the orifice does not have to be changed, skip theinstructions outlined further in Step 3 and proceed to Step 8.
3. Disassemble Flow Control Assembly by turning bodyhex.
4. If existing orifice has not dropped out of the body whendisassembled, remove by using a pin or paper clip.Discard this original orifice.
5. Insert proper sized orifice fully into the flow controlbody with rounded “bullet” nose towards the unit asshown in Figure 4. Insure the orifice stays inserted inbody before connecting mating half. See chart in theoutdoor unit installation instructions for proper size.
6. Thread assembly halves together by hand to insureproper mating of threads and tighten until bodies“bottom” or a definite resistance is felt.
7. Using a marker pen or ink pen, mark a line lengthwisefrom the union nut to the bulkhead. Then tighten anadditional 1/6 turn (or 1 hex flat). The misalignment ofthe line will show the amount the assembly has beentightened. This final 1/6 turn is necessary to insure theformation of the leakproof joint.
8. Wrap a wet rag around the copper stub before brazing.
9. Flux the copper tube and insert into the stub. Braze thejoint using an alloy of silver or copper and phosphoruswith a melting temperature above 1,100° F for copperto copper joints. The phosphorus will act as a flux,therefore, no flux will be required.
FIGURE 3
INSTALLING REFRIGERANT TUBING
FIGURE 4
FLOW CONTROL ASSEMBLYFIELD ORIFICE REPLACEMENT INSTRUCTIONS
PP5
CAUTION1. Be careful not to tear the insulation whenpushing it through hole in masonry or framewalls. 2. When sealing the tube opening inhouse wall, use a soft material to prevent tubedamage and vibration transmission. 3. Avoidexcessive bending in any one place to avoidkinking.
CAUTIONBe sure there is no dirt introduced into the flowcontrol - orifice assembly. Be sure to install theorifice with the bullet nose pointing in the properdirection as shown in Figure 4. Failure to do sowill result in improper operation.
2. The tubing ends should be cut square. Make sure it isround and free of burrs at the connecting ends. Cleanthe tubing to prevent contaminants from entering thesystem.
PP5
Manual 2100-269Page 7
A copper-silver alloy with a high silver content shouldbe used when iron or steel material is involved in thejoint. These alloys require the use of silver solder flux.Alloys containing phosphorus should not be used withiron or steel. Phosphorus reacts with the iron formingiron phosphate which is extremely brittle.
CAUTION1. Brazing alloys with a melting temperaturebelow 700° F should not be used. 2. Lead-tinor tin-antimony solders should not be used dueto their low melting point and necessity forcorrosive fluxes.
To further prevent the formation of copper oxide insidethe tubing, dry nitrogen may be purged through therefrigerant system during brazing.
WARNINGNever purge or pressurize a system withoxygen. An explosion and fire will result.
10. After brazing, quench with wet rag to cool the joint andremove any flux residue.
11. Leak test all connections using an electronic leakdetector or a halide torch.
12. Evacuate suction line, liquid line and indoor unitthrough outdoor unit base valves.
13. Open both the suction and liquid base valves to thefully open position. Refer to section later in installationinstructions for details on setting proper system charge.
FIELD FABRICATED TUBING CONNECTIONS:QUICK CONNECT INDOOR UNIT and SWEATOUTDOOR UNIT USING CTO KIT
Use only refrigeration grade (dehydrated and sealed) coppertubing. Care must be taken to insure that the tubing is keptclean and dry before and during installation. Do not removethe plugs from the tubing ends, coil connections or basevalves until the connection is ready to be brazed.
The suction line must be insulated with a minimum of 3/8”Armaflex or equivalent before cutting and makingconnections.
1. Being careful not to kink, route both the suction lineand liquid line between the indoor unit and outdoorunit. Use a tubing bender to make any necessary bendsin tubing. When necessary to bend the insulated tubesuction line, cut the insulation around its circumferenceat a distance far enough beyond the point of the bend soas to clear the tubing bender. Slip the insulation backtogether and vapor seal the joint with tape. Coil anyexcess tubing in a horizontal place with the slope of thetubing toward the condensing unit. See Figure 3.
TABLE 4
TUBING CHART
cisaBgnisnednoCledoMtinU
).tF(htgneLeniLtnaregirfeR
02-0 06-12 001-16
diuqiL noitcuS diuqiL noitcuS diuqiL noitcuS
181CAH "4/1 "8/5 "4/1 "8/5 "8/3 "4/3
142CAH "8/3 "8/5 "8/3 "4/3 "8/3 "4/3
103CAH "8/3 "8/5 "8/3 "4/3 "8/3 "4/3
163CAH "8/3 "8/5 "8/3 "4/3 "2/1 "8/7
124CAH "8/3 "4/3 "8/3 "8/7 "2/1 "8/7
184CAH "8/3 "8/7 "8/3 "8/7 "2/1 "8/1-1
106CAH "8/3 "8/7 "8/3 "8/7 "2/1 "8/1-1
CAUTION1. Be careful not to tear the insulation whenpushing it through hole in masonry or framewalls. 2. When sealing the tube opening inhouse wall, use a soft material to prevent tubedamage and vibration transmission. 3. Avoidexcessive bending in any one place to avoidkinking.
Manual 2100-269Page 8
NOTE: Do not make any tubing connection at indoor unitat this time. Make all brazing of joints andevacuate both suction and liquid line first.
3. Wrap a wet rag around the copper stub before brazing.
4. Flux the copper tube and insert into the stub. Braze thejoint using an alloy of silver or copper and phosphoruswith a melting temperature above 1,100° F for copperto copper joints. The phosphorus will act as a flux,therefore, no flux will be required.
A copper-silver alloy with a high silver content shouldbe used when iron or steel material is involved in thejoint. These alloys require the use of silver solder flux.Alloys containing phosphorus should not be used withiron or steel. Phosphorus reacts with the iron formingiron phosphate which is extremely brittle.
To further prevent the formation of copper oxide insidethe tubing, dry nitrogen may be purged through therefrigerant system during brazing.
2. The tubing ends should be cut square. Make sure it isround and free of burrs at the connecting ends. Cleanthe tubing to prevent contaminants from entering thesystem.
CAUTION1. Brazing alloys with a melting temperaturebelow 700° F should not be used. 2. Lead-tinor tin-antimony solders should not be used dueto their low melting point and necessity forcorrosive fluxes.
WARNINGNever purge or pressurize a system withoxygen. An explosion and fire will result.
5. After brazing, quench with wet rag to cool the joint andremove any flux residue.
6. Leak test all connections using an electronic leakdetector or a halide torch.
7. Evacuate suction line and liquid line through outdoorunit base valves.
If orifice does not have to be changed, skip the instructionsoutlined further in Step 8 and proceed to Step 15.
8. Recover charge from the indoor unit.
A. Connect the suction line only to the indoor unit asoutlined in Steps 15, 16, and 17.
B. Recover indoor unit and suction line unit chargethrough service port located on outdoor unit basevalve.
9. Disassemble Flow Control Assembly by turning bodyhex.
10. If existing orifice has not dropped out of the body whendisassembled, remove by using a pin or paper clip.Discard this original orifice.
11. Insert proper sized orifice fully into the flow controlbody with rounded “bullet” nose towards the unit asshown in Figure 4. Insure the orifice stays inserted inbody before connecting mating half. See chart in theoutdoor unit installation instructions for proper size.
CAUTIONBe sure there is no dirt introduced into the flowcontrol – orifice assembly. Be sure to install theorifice with the bullet nose pointing in the properdirection as shown in Figure 4. Failure to do sowill result in improper operation.
14. Evacuate the suction line and indoor unit through theoutdoor unit base valve before connecting all othertubing. Refer to section later in installation instructionsfor details on setting the proper refrigerant charge.
15. Remove (remaining) protector caps and plugs (if orificewas changed). Inspect fittings and if necessarycarefully wipe coupling seats and threaded surfaceswith a clean cloth to prevent the inclusion of dirt or anyforeign material in the system.
12. Thread assembly halves together by hand to insureproper mating of threads and tighten until bodies“bottom” or a definite resistance is felt.
13. Using a marker pen or ink pen, mark a line lengthwisefrom the union nut to the bulkhead. Then tighten anadditional 1/6 turn (or 1 hex flat). The misalignment ofthe line will show the amount the assembly has beentightened. This final 1/6 turn is necessary to insure theformation of the leakproof joint.
Manual 2100-269Page 9
16. Lubricate male half diaphragm and synthetic rubberseal with refrigerant oil. Thread coupling halvestogether by hand to insure proper mating of threads. Besure to hold the coupling firmly to prevent movement ofthe coupling and tubing. Failure to do so could tear outthe diaphragm causing a blockage of the system. Useproper size wrenches (on coupling body hex and onunion nut) and tighten until coupling bodies ”bottom”or a definite resistance is felt.
18. Leak test all connections using an electronic leakdetector or a halide torch.
19. When tubing is installed in attics or drop ceilings,insulate the couplings on the larger tube thoroughlywith 3/8” wall thickness, closed cell sponge tubeinsulation or equivalent. Failure to insulate will resultin water damage to ceiling since the fitting will “sweat”and drop water on the ceiling.
20. Open both the suction and liquid base valves to thefully open position. Refer to section later in installationinstructions for details on setting proper system charge.
17. Using a marker or ink pen, mark a line lengthwise fromthe coupling union nut to the bulkhead. Then tightenan additional 1/4 turn. The misalignment of the linewill show the amount the coupling has been tightened.This final 1/4 turn is necessary to insure the formationof leakproof joint. If a torque wrench is used, thetorque values shown in Table 5 are recommended.
CAUTIONAfter starting to tighten up the fitting, never try toback it off or take it apart.
TABLE 5
COUPLINGS
eziSgnilpuoC sdnuoPteeF
6- 21-01
01- 54-53
11- 54-53
21- 56-05
Manual 2100-269Page 10
WIRING INSTRUCTIONS
GENERAL
All wiring must be installed in accordance with the NationalElectrical Code and local codes. In Canada, all wiring mustbe installed in accordance with the Canadian ElectricalCode and in accordance with the regulations of theauthorities having jurisdiction. Power supply voltage mustconform to the voltage shown on the unit serial plate. Awiring diagram of the unit is attached to the inside of theelectrical cover. The power supply shall be sized and fusedaccording to the specification supplied. A ground lug issupplied in the control compartment for equipment ground.
The unit rating plate lists a “Maximum Time Delay Fuse” orHACR type” circuit breaker that is to be used with theequipment. The correct size must be used for proper circuitprotection and also to assure that there will be no nuisancetripping due to the momentary high starting current of thecompressor motor.
CONTROL CIRCUIT WIRING
For split systems, the minimum control circuit wiring gaugeneeded to insure proper operation of all controls in bothindoor and outdoor units will depend on two factors:
1. The rated VA of the control circuit transformer.
2. The maximum total distance of the control circuitwiring. (This is the distance between the wallthermostat to the indoor unit plus the distancebetween the indoor unit to the outdoor unit.)
The following table should be used to determine propergauge of control circuit wiring required.
Example: 1. Control circuit transformer rated at 40 VA2. Maximum total distance of control circuit
wiring 85 feet.
From Table 6, minimum of 18 gauge wire should be used inthe control circuit wiring.
For control circuit transformers rated other than those listed,use the next lower rated transformer listed.
Example: 1. Control circuit transformer rated at 55 VA
From table use 50VA transformer.
There are two (2) separate control diagrams for fossil fuelfurnaces with air conditioners.
Control diagrams for the various circuit which could beencountered with blower coils can be found in theinstallation instructions of the blower coil.
WALL THERMOSTATS
The following wall thermostats and subbases should beused as indicated, depending on the application.
TABLE 6
CONTROL CIRCUIT WIRING
foAVdetaRtiucriClortnoC
remrofsnarT
remrofsnarTyradnoceS
ALF @ V42
latoTmumixMfoecnatsiD
tiucriClortnoCteeFnigniriW
04 6.1
56eguag0209eguag81541eguag61032eguag41
05 1.2
54eguag0206eguag81001eguag61061eguag41052eguag21
56 7.2
04eguag0255eguag8158eguag61531eguag41012eguag21
TABLE 7
CONTROL DIAGRAMS
metsySecanruFsaGmargaiDlortnoC
ecanruFliOmargaiDlortnoC
sledoMllA 001-1904 101-1904
TABLE 8
WALL THERMOSTAT AND SUBBASECOMBINATIONS
tatsomrehT esabbuS serutaeFetanimoderP
200-3048113F78T
300-40480221A925Q
yrucreM;loocegats1,taehegats1otua-no:naFlooc-ffo-taeh:metsyS
140-3048C-4308T
---yrucreM;loocegats1,taehegats1otua-no:naFlooc-ffo-taeh:metsyS
530-304808-59F1
---loocegats2,taehegats2
elbammargorPcinortcelE
240-3048G1158T
---loocegats1,taehegats2looc-otua-ffo-taeh:metsyS
cinortcelEotua-no:naF
340-3048002MC
---loocegats1,taehegats1
otua-no:naFlooc-ffo-taeh:metsySnoitcApanS
720-304817-29F1
---loocegats2,taehegats3
elbammargorPcinortcelE
Manual 2100-269Page 11
Manual 2100-269Page 12
Manual 2100-269Page 13
FIGURE 5
COMPONENT MOUNTING LOCATION
OPTIONAL CONTROLS
MIS-1302
INSTALLATION INSTRUCTIONS — CMA-5
Disconnect all power to the unit. Remove control panelcover.
1. Mount compressor TDR in position shown in Figure 5with screw provided.
2. Disconnect yellow low voltage (Y) wire at thecompressor contactor coil and reconnect to the Y1 or #3terminal of the TDR.
3. Connect yellow wire from terminal (Y) of the TDR tothe (Y) terminal of the compressor contactor coil. Thisis the terminal that the wire was removed from inStep 2.
4. Recheck wiring. Refer to Figure 9. Energize unit.Compressor should start. Remove power and reapply.Compressor should not start until the 5 minute timedelay has expired.
5. Apply “This unit equipped with CMA-5 controlmodule” label to inside of the inner control panel coverabove wiring diagram.
6. Replace all panels and covers. This completesinstallation.
INSTALLATION INSTRUCTIONS — CMA-6
Disconnect all power to unit. Remove control panel innerand outer cover.
1. Mount terminal block in position shown in Figure 5.
2. Disconnect black high voltage outdoor motor lead fromcompressor contactor and reconnect to terminal block.
3. Route low ambient control wires up through thebushing in the bottom of the control panel. Connect thelow ambient control wires between the terminal blockand T2 of the compressor contactor.
4. Remove service port cap on discharge line. Install thelow ambient control on the discharge line with the flaretee adapter that is brazed to the low ambient control.Check for pressure at the flare tee dill valve afterinstallation to insure that the dill valve in the unitservice port was depressed by the flare tee connector.Check for leaks at the flare tee connectors. Replaceservice port cap on the flare tee service port and tighten.
5. Recheck wiring. See Figure 10. Check for properoperation of the unit by energizing in cooling mode.The condenser fan motor should not run until thedischarge pressure has exceeded 300 PSI. Should thedischarge pressure fall below 200 PSI while running,the condenser fan motor will de-energize until the headpressure builds to 300 PSI.
6. Apply “This unit equipped with CMA-6 controlmodule” label to the inside of the control panel coverabove the wiring diagrams.
7. Replace all panels and covers. This completesinstallation.
FIGURE 6
INSTALLATION INSTRUCTIONSFOR CMA-5 COMPRESSOR TIME DELAY RELAY
MIS-598
FIGURE 7
INSTALLATION INSTRUCTIONS FORCMA-6 LOW AMBIENT FAN CYCLING CONTROL
MIS-594
CMA-5 & CMA-13A LOWAMBIENT FAN CYCLINGCONTROL TERMINAL BLOCK
CMA-5 COMPRESSORTIME DELAY RELAY
SK109 LOW VOLTAGESTART KIT
CMA-10A & CMA-13ACOMPRESSORCONTROL
Manual 2100-269Page 14
INSTALLATION INSTRUCTIONS – CMA-10A
Disconnect all power to unit. Remove control panel cover.
1. Screw compressor control module and terminal blockinto control panel as shown in Figure 5.
2. Disconnect yellow low voltage wire form compressorcontactor and reconnect to terminal “Y” of thecompressor control module.
3. Connect the yellow wire from the compressor controlmodule to “Y” side of the compressors contactor coil.This is the same terminal from which the wire wasremoved in Step 2.
4. Connect the black wire form the compressor controlmodule to common “C” side of the compressorcontactor coil.
5. Connect a field supplied wire from “R” of the indoorunit to “R” on the compressor control module.
6. Route the high (red) and low (blue) pressure switchwires through the bushing in the bottom of the controlpanel. Connect the low pressure switch wire toterminals LPC of the compressor control module.
7. Remove service port caps on both the suction anddischarge lines. Install the high pressure switch on thedischarge line to the flare tee adapter that is brazed tothe controls. Install the low pressure switch on thesuction line. Check for pressure at the flare tee dillvalves after installation to insure that the dill valve inthe unit service port was depressed by the flare teeconnector. Check for leaks at the flare tee connectors.Replace service port caps on the flare tee service portsand tighten.
8. Adjust the compressor time delay relay to the desireddelay on break. Two minutes are recommended. ThisTDR is variable form 30 seconds to 5 minutes.
9. Recheck wiring. Energize unit is first stage cooling.Compressor should not start until the time delay hasexpired. This will be 10% of the delay on break period.Run the unit for at least 5 minutes. The unit should notgo into lockout.
10. Apply “This unit equipped with CMA-10A controlmodule.” label to the inside of the inner control panelcover above the wiring diagram.
11. Replace all panels and covers. This completesinstallation.
FIGURE 8
INSTALLATION INSTRUCTIONS FORCMA-10A DUAL PRESSURE CONTROL AND
COMPRESSOR TIME DELAY RELAY
MIS-1303
Manual 2100-269Page 15
INSTALLATION INSTRUCTIONS – CMA-13A
Disconnect all power to unit. Remove control panel cover.
1. Screw compressor control module and terminal blockinto control panel as shown in Figure 5.
2. Disconnect yellow low voltage wire from compressorcontactor and reconnect to terminal “Y” of thecompressor control module.
3. Connect the yellow wire from the compressor controlmodule to “Y” side of the compressor’s contactor coil.This is the same terminal from which the wire wasremoved in Step 2.
4. Connect the black wire from the compressor controlmodule to common “C” side of the compressorcontactor coil.
5. Connect a field supplied wire from “R” of the indoorunit to “R” on the compressor control module.
6. Route the high (red) and low (blue) pressure switchwires through the bushing in the bottom of the controlpanel. Connect the low pressure switch wire toterminals LPC of the compressor control module.Connect the high pressure switch wires to terminalsHPC of the compressor control module.
7. Disconnect the high voltage outdoor motor lead andreconnect to the terminal block installed in Step 1.
8. Route the LAC (black) wires up through the busing inthe bottom of the control panel. Connect one wire tothe terminal block and the other to “T2” of thecontactor. This will be the same terminal from which
the high voltage outdoor motor lead was removed inStep 7.
9. Remove service port caps on both the suction anddischarge lines. Install the high pressure switch andthe low ambient control on the discharge line with theflare tee adapter that is brazed to the controls. Installthe low pressure switch on the suction line. Check forpressure at the flare tee dill valves after installation toinsure that the dill valve in the unit service port wasdepressed by the flare tee connector. Check for leaks atthe flare tee connectors. Replace service port caps onthe flare tee service ports and tighten.
10. Adjust the compressor time delay relay to the desireddelay on break. Two minutes are recommended. ThisTDR is variable from 30 seconds to 5 minutes.
11. Recheck wiring. Energize unit in first stage cooling.Compressor should not start until the time delay hasexpired. This will be 10% of the delay on break period.Run the unit for at least 5 minutes. The unit should notgo into lockout. The condenser fan motor should notrun until the discharge pressure has exceeded 300 PSI.Should the discharge pressure fall below 200 PSI whilerunning the condenser fan motor will de-energize untilthe head pressure builds to 300 PSI.
12. Apply “This unit equipped with CMA-13A controlmodule.” label to the inside of the inner control panelcover above the wiring diagram.
13. Replace all panels and covers. This completesinstallation.
FIGURE 9
INSTALLATION INSTRUCTIONS FORCMA-13A DUAL PRESSURE CONTROL, LOW AMBIENT FAN CYCLING CONTROL
AND COMPRESSOR TIME DELAY RELAY
MIS-1304
Manual 2100-269Page 16
PRESSURE SERVICE PORTS
High and low pressure service ports are installed on all unitsso that the system operating pressures can be observed.Pressure tables can be found later in the manual covering allmodels. It is imperative to match the correct pressure tableto the unit by model number.
SYSTEM START-UP (INDOOR UNITSWITHOUT EXPANSION VALVES)
1. Close disconnect switch(es) and set the thermostat tocool and the temperature to the highest setting.
2. Check for proper airflow across the indoor coil byreferring to indoor unit installation.
3. Connect the service gauges and allow the unit to run forat least 10 minutes or until pressures are stable. Checkpressures to the system pressure table attached to theoutdoor unit service panel. For optimum systemperformance, go to Step 4.
4. Install a thermometer on the suction line approximately6" to 10" from the compressor. Optimum systemperformance will occur with a refrigerant chargeresulting in a suction line superheat as determined fromthe following calculations.
A. Measure outdoor air dry bulb temperature________ ºF
B. Measure indoor air wet bulb temperature________ ºF
C. Measure suction pressure ______ PSIG
D. Measure suction line temperature ________ ºF
E. Determine optimum system superheatfrom Table 9 using outdoor air dry bulb(Step B) and indoor air wet bulb (Step A)
________ ºF
F. Determine saturated suction temperaturefrom suction pressure using Table 10 ________ ºF
G. Determine system superheat:Suction line temperature (Step D) ________ ºF- Saturated suction temperature (Step F)
- ________ ºF= System superheat
= ________ ºF
H. Adjust the system superheat (Step G) to theoptimum system superheat (Step E) by addingcharge to lower the superheat or removingcharge to raise the superheat.
I. Check final system operating pressures to thesystem pressure tables as was done in Step 3.
CHARGING INSTRUCTIONS
TABLE 9SYSTEM SUPERHEAT
tneibmAroodtuOerutarepmeT)bluByrDF(
erutarepmeTriAnruteRbluBteWF
95 36 76 17
5015909580857
1113801
13794102
5)8(41915203
0262339324
TABLE 10
SATURATED SUCTION TEMPERATURE R-22
GISPerusserPnoitcuSnoitcuSdetarutaS)F(erutarepmeT
053555
628203
851636
234363
567607
839314
376797
345474
2868
9415
Manual 2100-269Page 17
TABLE 11
TOTAL SYSTEM OPERATING CHARGE(INCLUDES CHARGE FOR THE BASIC OUTDOOR
UNIT,INDOOR COIL AND 25’ OF INTERCONNECTING
TUBING.)noitceSroodtuO noitceSroodnI
22-RlatoT).zO(egrahC
A-181CAHA-SA03AA-SA42S
C42CB
.zo37
.zo37
.zo87
A-142CAHA-SA03AA-SA42S
C42CB
.zo08
.zo08
.zo97
A-103CAHA-SA63A
C63CB.zo48.zo59
A-163CAHA-SA73A
C63CB.zo89.zo69
A-124CAH
A-SA24AA-SA84A
C63CBC06CB
.zo201
.zo711
.zo501
.zo241
B-,A-184CAHB-SA16A
C06CB.zo551.zo571
B-,A-106CAHB-SA16A
C06CB.zo351.zo561
�
�
Includes 25’ of 1/4” diameter liquid line. For other than 25’ andother tube sizes, adjust the total charge according to thefollowing schedule.
Includes 25’ of 3/8” diameter liquid line. For other than 25’ andother tube sizes, adjust the total charge according to thefollowing schedule.
�
�
�
�
�
�
�
Installer Note: Stamp or mark the final system chargedetermined above on the outdoor unit serial plate.
SCHEDULE FOR TABLE 11
retemaiDeniLdiuqiL .tFreP22-R.zO
"4/1"8/3"2/1
52.006.002.1
Manual 2100-269Page 18
SERVICE
SERVICE HINTS
1. Caution homeowner to maintain clean air filters at alltimes. Also, not to needlessly close off supply andreturn air registers. This reduces air flow through thesystem, which shortens equipment service life, as wellas, increasing operating costs.
2. Check all power fuses or circuit breakers to be sure thatthey are the correct rating.
3. Periodic cleaning of the outdoor coil to permit full andunrestricted air flow circulation is essential.
FAN BLADE SETTING DIMENSIONS
Shown in Figure 10 are the correct fan blade settingdimensions for proper air delivery across the outdoor coil.
Any service work requiring removal or adjustment in the fanand/or motor area will require that the dimensions below bechecked and blade adjusted in or out on the motor shaftaccordingly.
FIGURE 10
FAN BLADE
MIS-1309
TABLE 12
FAN BLADE SETTING
ledoM AnoisnemiD
181CAH142CAH103CAH163CAH124CAH184CAH106CAH
"4/1-3
Manual 2100-269Page 19
Manual 2100-269Page 20
Manual 2100-269Page 21
Manual 2100-269Page 22
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being inthe system. The charge should be removed, system evacuated and recharged to serial plate instructions.
TABLE 13
PRESSURE TABLEHAC181-A
roodnInoitceS
riAnruteR.pmeT erusserP
lioCroodtuOgniretnEerutarepmeTriA
56 07 57 08 58 09 59 001 501 011 511
A-SA03SAA-SA42S
BD57BW26
ediSwoLediShgiH
86051
07071
27781
47302
67622
87442
08452
28852
48552
58642
78023
BD08BW76
ediSwoLediShgiH
07961
37381
67891
97312
18822
48442
68062
88672
09392
29013
39823
BD58BW27
ediSwoLediShgiH
67771
97191
28602
58122
78632
09252
29962
49682
69403
89223
99043
42CB C
BD57BW26
ediSwoLediShgiH
55261
26871
86391
37902
87422
18042
48652
68272
78882
78403
78023
BD08BW76
ediSwoLediShgiH
77461
87081
87891
08312
18032
28642
48362
68082
88692
09313
39923
BD58BW27
ediSwoLediShgiH
67771
97191
28602
58122
78632
09252
29962
49682
69403
89223
99043
TABLE 14
PRESSURE TABLEHAC241-A
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being inthe system. The charge should be removed, system evacuated and recharged to serial plate instructions.
roodnInoitceS
riAnruteR.pmeT erusserP
lioCroodtuOgniretnEerutarepmeTriA
56 07 57 08 58 09 59 001 501 011 511
A-SA03SAA-SA42S
BD57BW26
ediSwoLediShgiH
06271
46091
86702
17422
47142
67852
87572
08292
18803
28523
28143
BD08BW76
ediSwoLediShgiH
66771
07591
37312
67032
97742
18562
38282
58992
68613
78333
88053
BD58BW27
ediSwoLediShgiH
37581
67302
97022
28832
58752
78372
98192
19903
29623
49443
59263
42CB C
BD57BW26
ediSwoLediShgiH
56971
96491
37902
77522
08142
28752
38372
48092
58603
68423
78143
BD08BW76
ediSwoLediShgiH
07401
37251
57291
77522
97152
18962
38082
58482
68182
88072
98252
BD58BW27
ediSwoLediShgiH
37581
67302
97022
28832
58652
78372
98192
19903
29623
49443
59263
Manual 2100-269Page 23
TABLE 15
PRESSURE TABLEHAC301-A
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being inthe system. The charge should be removed, system evacuated and recharged to serial plate instructions.
roodnInoitceS
riAnruteR.pmeT erusserP
lioCroodtuOgniretnEerutarepmeTriA
56 07 57 08 58 09 59 001 501 011 511
A-SA63A
BD57BW26
ediSwoLediShgiH
26261
56381
76402
96422
17442
37262
57082
77792
87313
08923
18443
BD08BW76
ediSwoLediShgiH
86761
07881
27012
47032
67052
87962
08782
28503
48123
58833
78353
BD58BW27
ediSwoLediShgiH
57171
77491
87612
08832
28852
48872
68792
88513
09333
29943
49563
C63CB
BD57BW26
ediSwoLediShgiH
16581
56102
96712
27432
57052
77662
97282
18892
28413
38133
48743
BD08BW76
ediSwoLediShgiH
76091
17702
47322
77932
08652
28272
48982
68603
78223
88933
98653
BD58BW27
ediSwoLediShgiH
47891
77512
08232
38842
68562
88282
09992
29613
39333
59153
69863
TABLE 16
PRESSURE TABLEHAC361-A
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating change being inthe system. The charge should be removed, system evacuated and recharged to serial plate instructions.
roodnInoitceS
riAnruteR.pmeT erusserP
lioCroodtuOgniretnEerutarepmeTriA
56 07 57 08 58 09 59 001 501 011 511
A-SA73A
BD57BW26
ediSwoLediShgiH
66181
86791
07312
27032
47642
67262
87872
08492
28013
48623
68343
BD08BW76
ediSwoLediShgiH
17681
37202
57912
77532
97252
18862
38582
58203
78813
98533
19153
BD58BW27
ediSwoLediShgiH
77191
97802
18622
38342
58062
78872
98592
19213
39033
59743
79463
C63CB
BD57BW26
ediSwoLediShgiH
36871
66591
86212
07822
27542
47262
67972
87692
97313
18133
28843
BD08BW76
ediSwoLediShgiH
66481
96002
27712
57432
87152
08962
28682
48403
58123
78933
88753
BD58BW27
ediSwoLediShgiH
27881
57602
87422
18242
38062
68872
88692
09413
29233
49153
59963
Manual 2100-269Page 24
TABLE 17
PRESSURE TABLEHAC 421-A
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating changebeing in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
roodnInoitceS
riAnruteR.pmeT erusserP
lioCroodtuOgniretnEerutarepmeTriA
57 08 58 09 59 001 501 011 511
A-SA24A63CB C
BD57BW26
ediSwoLediShgiH
46302
76812
07332
27052
47662
67382
77003
87813
97633
BD08BW76
ediSwoLediShgiH
96802
27422
57042
77652
97372
28092
28803
48623
58543
BD58BW27
ediSwoLediShgiH
37612
77232
08842
38562
58282
78003
98813
09733
19953
A-SA84A06CB C
BD57BW26
ediSwoLediShgiH
37212
47822
67442
77062
97772
18492
28213
48033
68943
BD08BW76
ediSwoLediShgiH
77812
97432
18052
38762
58482
78203
98023
09933
29853
BD58BW27
ediSwoLediShgiH
38422
58142
78852
98672
19492
39492
59133
79053
99073
TABLE 18
PRESSURE TABLEHAC481-A, HAC481-B
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating changebeing in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
roodnInoitceS
riAnruteR.pmeT erusserP
lioCroodtuOgniretnEerutarepmeTriA
57 08 58 09 59 001 501 011 511
B-SA16A
BD57BW26
ediSwoLediShgiH
47802
57322
77832
87452
08172
28882
38603
58423
78343
BD08BW76
ediSwoLediShgiH
87412
08922
28542
48162
68872
88692
09413
19333
39253
BD58BW27
ediSwoLediShgiH
48022
68632
88352
09072
29882
49603
69523
79443
99463
06CB C
BD57BW26
ediSwoLediShgiH
86242
07052
27062
47272
67582
87003
97713
08633
18653
BD08BW76
ediSwoLediShgiH
67842
77652
87662
08872
18292
28803
48523
58443
78563
BD58BW27
ediSwoLediShgiH
28752
38562
48672
68882
78203
88813
09633
19653
39873
Manual 2100-269Page 25
TABLE 19
PRESSURE TABLEHAC601-A, HAC601-B
Low side pressure ± 2 PSIG (suction line 8 inches from compressor)High side pressure ± 5 PSIG (discharge line 8 inches from compressor, liquid at base valve approximately -20 PSIG from
values listed)
Tests are based upon rated CFM (airflow) across the evaporator coil. If there is any doubt as to correct operating changebeing in the system. The charge should be removed, system evacuated and recharged to serial plate instructions.
roodnInoitceS
riAnruteR.pmeT erusserP
lioCroodtuOgniretnEerutarepmeTriA
57 08 58 09 59 001 501 011 511
B-SA16A
BD57BW26
ediSwoLediShgiH
76722
96342
17062
37672
57392
67013
87623
97343
97953
BD08BW76
ediSwoLediShgiH
27232
47942
67662
87482
08103
28813
48633
68353
88073
BD58BW27
ediSwoLediShgiH
87042
08852
28672
48392
68113
88923
09643
29463
49283
C06CB
BD57BW26
ediSwoLediShgiH
46322
76932
07752
27572
47592
67613
77933
87363
87883
BD08BW76
ediSwoLediShgiH
96032
27642
57462
77382
97303
18523
28843
38273
48893
BD58BW27
ediSwoLediShgiH
67732
87552
08372
28392
58413
58633
78063
98583
09114