Packaged Control ProductsMilwaukee, WI 53204 U.S.A.Publication 2100-WD1 - July, 1994Supersedes NoneCopyright 1994 Allen-Bradley Company, Inc.Printed in USA
WIRING DIAGRAMSWIRING DIAGRAMS
A Reference Resource forCENTERLINE Motor Control Centers
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 1
CONTENT GUIDEWiring Class
Class I 2. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Class II, Class I-S and II-S 3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring TypeType A Wiring 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type B Wiring 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Type C Wiring 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Photos - Type A, Type B-T, Type B-D, and Type C Wiring 6 and 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Customer Wiring 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control Circuit Wiring and DevicesControl Circuit Wiring, Terminal Blocks, Pilot Devices 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Schematic Symbols 10 through 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring DiagramsGeneral Information 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Allen-Bradley Wiring Diagram Example 20 and 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2102L-Full Voltage Lighting Contactor 22. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2103L-Full Voltage Lighting Contactor 23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2106-Full Voltage Reversing Starter 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2107-Full Voltage Reversing Starter 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2112-Full Voltage Non-Reversing Starter With Fusible Disconnect 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2112-Full Voltage Non-Reversing Starter with Fusible Disconnect 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2113-Full Voltage Non-Reversing Starter with Circuit Breaker 28. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2113-Full Voltage Non-Reversing Starter with Circuit Breaker 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2122E-Two Speed 2-Winding Starter with Fusible Disconnect 30. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2122F-Two Speed 1-Winding Starter with Fusible Disconnect 31. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2123E-Two Speed 2-Winding Starter with Circuit Breaker 32. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2123F-Two Speed 1-Winding Starter with Circuit Breaker 33. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2126E-Two Speed Reversing 2-Winding Starter with Fusible Disconnect 34. . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2126F-Two Speed Reversing 1-Winding Starter with Fusible Disconnect 35. . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2127J-Two Speed Reversing in Low Speed Only 2-Winding with Circuit Breaker 36. . . . . . . . . . . . . . . . . . Bulletin 2127-Two Speed Reversing in Low Speed Only 1-Winding with Circuit Breaker 37. . . . . . . . . . . . . . . . . . Bulletin 2154E-Comb. Solid State Motor Controller with Fusible Disconnect (SMC-2) 38. . . . . . . . . . . . . . . . . . . . . Bulletin 2154F-Comb. Solid State Motor Controller with Fusible Disconnect (SMC PLUS) 39. . . . . . . . . . . . . . . . . . Bulletin 2155F-Comb. Solid State Motor Controller with Circuit Breaker (SMC PLUS) 40. . . . . . . . . . . . . . . . . . . . . Bulletin 2162J-Bulletin 1333 Variable Freuency AC Drive with Fusible Disconnect 41. . . . . . . . . . . . . . . . . . . . . . . Bulletin 2163-Bulletin 1336 Variable Freuency AC Drive with Circuit Breaker-75p 42. . . . . . . . . . . . . . . . . . . . . Bulletin 2172-Closed Transition Reduced Voltage Autotransformer Type Starter with Fusible Disconnect 43. . . . . . . Bulletin 2173-Closed Transition Reduced Voltage Autotransformer Starter with Circuit Breaker 44. . . . . . . . . . . . . . Bulletin 2182E-Bulletin 1771 PLC I/O Rack with Fusible Disconnect and Transformer 45. . . . . . . . . . . . . . . . . . . . . Bulletin 2182J-Bulletin 1746 SLC 500 PLC with Fusible Disconnect and Transformer 46. . . . . . . . . . . . . . . . . . . . Bulletin 2183E-Bulletin 1771 PLC I/O Rack with Circuit Breaker and Transformer 47. . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2190-Metering Compartment 48. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2191F-Outgoing Feeder Lug Compartment 49. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2191M-Incoming Line Lug Compartment 50. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2192F-Fusible Disconnect-Feeder - Dual 51. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2192M-Fusible Disconnect-Main 52. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2193F-3-Pole Circuit Breaker - Feeder 53. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2193M-3-Pole Circuit Breaker - Main 54. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2193LE-Bolt-On Lighting Panel 55. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2196-Control and Lighting Transformer with Fusible Disconnect 56. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2197-Control and Lighting Transformer with Circuit Breaker 57. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2402-Full Voltage Contactor with Fusible Disconnect 58. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2403-Full Voltage Contactor with Circuit Breaker 59. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2406-Combination Full Voltage Reversing Starter with Fusible Disconnect 60. . . . . . . . . . . . . . . . . . . . . . . Bulletin 2407-Combination Full Voltage Reversing Starter with Circuit Breaker 61. . . . . . . . . . . . . . . . . . . . . . . . . . Bulletin 2412-Combination Full Voltage Non-Reversing Starter with Fusible Disconnect 62. . . . . . . . . . . . . . . . . . . Bulletin 2413-Combination Full Voltage Non-Reversing Starter with Circuit Breaker 63. . . . . . . . . . . . . . . . . . . . . . Bulletin 2492F-Fusible Disconnect Switch - Feeder 64. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers2
Wiring Class
Class I Independent UnitsClass I motor control centers (MCC) consistof mechanical groupings of combinationstarter units, feeder and other units, andelectrical devices arranged in a convenientpackage.
Allen–Bradley furnishes drawings thatinclude:• Overall dimensions of the MCC, identifi-
cation of units and their locations in theMCC, locations of incoming line termi-nals, mounting dimensions, and availableconduit entrances.
• Standard diagrams for individual unitsconsisting of drawings that identify elec-trical devices, indicate electrical connec-tions, and indicate terminal numberingdesignations.
When a combination schematic and / orwiring diagram for a unit is suppliedshowing optional devices, Allen–Bradleyprovides information to indicate whichdevices are actually furnished.
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 3
Class II Interconnected Units
Class II motor control centersare the same as Class I but withthe addition of fact furnishedelectrical interlocking andwiring between units, aspecifically described in
overall controlsystem diagrams supplied bythe purchaser. In addition tothe drawings furnished forClass I MCCs, Allen–Bradleyfurnishes drawings that showfactory interconnections withinthe MCC.
Class I-S & Class II -S Motor Control Centers
Requiring Custom Drawings
Class I–S and Class II–S motorcontrol centers are the same asClass I and Class II MCCsexcept that custom drawingsare provided as specified by thecustomer rather than standarddrawings. Examples are:
• special identifications forelectrical devices
• special terminal numberingdesignations
• special drawing sizes.
These drawings give the sameinformation as those for Class Iand Class II motor controlcenters, plus show customermodifications.
91C-111
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers4
WiringType
Type A Wiring - No Terminal Blocks
Type A wiring is available for Class I motorcontrol centers. When Type A wiring is specified,components within the unit are wired directly toeach other, and no terminal blocks are supplied forcustomer wiring. The customer must connectexternal control and load wiring directly to theelectrical devices within the unit. See Photo 1 onpage 6.
Type B Wiring - Terminal Blocks
Type B wiring is available for Class I and Class IImotor control centers. NEMA/EEMAC definesType B wiring as follows:
ICS 2-322.10 TYPES OF WIRING.02 Type B
a. Type B user field load wiring for combination motor controlunits size 3 or smaller shall be designated as B-D or B-T,according to the following
B-D connects directly to the device terminals, which arelocated immediately adacent, and readily accessible, to thevertical wireway
B-T connects directly to a load terminal block in, or adacentto, the unit.NEMA Standard 3-6-1985
b. Type B user field load wiring for combination motor controlunits larger than size 3, and for feeder tap units, shall connectdirectly to unit device terminals.NEMA Standard 3-6-1985
c. Type B user field control wiring shall connect directly tounit terminal block(s) located in or adacent to each combinationmotor control unit.NEMA Standard 3-6-1985
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 5
CENTERLINE Motor Control Centers provide thefollowing:
Type B-T
Power wired to
terminal blocks
(See Photo 2 on page 6)
Type B-D
Power wired to
device terminals
(see Photo 3 on page 7)
Type B
Size 1, 2 (except 0.5 space fac�tor)
Pull apart controlPull apart power
Pull apart controlNo power terminalblocks
N/A
Size 3Pull apart controlNon-pull apart power
Pull apart controlNo power terminalblocks
N/A
Size 4 and larger N/A N/APull apart controlNo power terminalblocks
0.5 space factor unitsand Bul. 2400 units.
Pull apart control terminal blocksNo power terminal blocks
N/A = Not applicable, undefined by NEMA/EEMAC
Type C Wiring - Master Terminal Compartment
Type C wiring is available for Class II motorcontrol centers. See Photo 4 on page 7.
Control wiring from each unit within an MCCsection is wired from the unit’s terminal blocks tomaster terminal blocks contained in a separate unitmounted at the top or bottom of that section.
The customer connects the external control wiresto the master terminal blocks. The customerconnects the load wiring for size 3 or smaller tothe master terminal blocks. The customer connectthe load wiring for size 4 or larger to unit deviceterminals.
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers6
Photo 1. Type A Wiring
Photo 2. Type B-T Wiring
93C-491-3
93C-491-2
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 7
Photo 3. Type B-D Wiring
Photo 4. Type C Wiring
93C-491-1
87C-143-13
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers8
Customer Wiring
The method that a customer uses to connect theirexternal wiring differs depending upon whether ornot terminal blocks are supplied:
When control and/or power
terminal blocksare supplied:
When noterminal blocksare supplied:
The customer’s external
control and/or load wires
are connected to those
blocks that are located
adjacent to the vertical
wireway and are readily
accessible.
The customer must
connect the external
control and load wires
directly to the applicable
electrical devices
internal to the unit.
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 9
Control Circuit Wiring and Devices
Control Circuit WiringFor Bulletin 2100 units, the standard control circuit wiring is 16 AWG copper wirewith Type MTW (TEW) insulation. 14 AWG (tinned) copper wire with TypeMTW (TEW) insulation and 14 AWG (tinned) copper wire with Type SISinsulation are other available options (when specifications do not allow PVCinsulation).
For Bulletin 2400 units, the standard control circuit wiring is 18 AWG copperwire with Type MTW (TEW) insulation. 16 AWG copper wire with Type MTW(TEW) insulation is also available as an option.
Terminal BlocksDifferent terminal blocks will accept different wire quantities and sizes. Themaximum wire sizes accepted are as follows:
Pull-apart Terminal Blocks Maximum Wires Per Pole
5–pole controlTwo (2) 14 AWG wiresorOne (1) 12 AWG wire
3–pole power One (1) 4 AWG wire
10–pole control(used on all 0.5 space factor units)
Two (2) 18 AWG wiresorOne (1) 16 AWG wire
Pilot DevicesThere are several types of pilot devices supplied on our Bulletin 2100 and 2400units. The maximum wire sizes accepted are as follows:
Pilot Device Maximum Wires Per Pole
Bulletin 800T Two (2) 14 AWG wires
Bulletin 800M(w/small terminals)
One (1) 14 AWG wire
Bulletin 800M(w/large terminals)
Two (2) 12 AWG wires
Bulletin 800ETwo (2) 14 AWG wiresorOne (1) 12 AWG wire
For further information on types of pilot devices supplied with each unit, see Publication 2100–3.0.
Wiring Diagram Reference Resource
for CENTERLINE Motor Control Centers10 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
Schematic Symbols
US/Canadian International / British German
An automatic device that under abnormal conditions will open acurrent–carrying circuit without damaging itself (unlike a fuse that must bereplaced when it blows).––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Generally, an air–break switch, however, containing no fuses. A powercircuit employing this type of switch must have some kind of circuitprotection elsewhere.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Generally, an air–break switch with a fusing unit in the blade. Used foropening and closing power circuits.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
An application–rated version of an air–break switch with a fusing unit in theblade.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
CB
DS
FDS
FDS
Three-Pole Circuit Breaker
Three-PoleDisconnect Switch
Three-PoleFusible DisconnectSwitch
IEC Fusible Disconnect Switch
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 11
US/Canadian International / British German
Dark black nodes on a circuit schematic indicate that an electrical connectionis made. It is a point of connection for two or more conductors in anelectrical circuit.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A device attached to the end of a wire or cable for convenience in makingelectrical connections.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A coupling device that provides an electrical and/or mechanical junctionbetween two cables.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Part of a contactor, motor starter, or relay consisting of a number of turns ofwire wound around an iron core. When voltage is applied, anelectromagnetic field is set up in the coil causing the contacts of thecontactor, starter, or relay to change state.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
This device is mounted directly across the coil terminals of contactors andstarters with 120V or 240V AC coils. The purpose of the supressor is tolimit voltage transients for applications requiring interface with solid statecomponents.
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
M
SUP
Node
Terminal Block (TB)
Connector
Coil
Surge Suppressor
Wiring Diagram Reference Resource
for CENTERLINE Motor Control Centers12 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
US/Canadian International / British German
Symbolized by N.O. designation applied to the contacts of a relay or starterwhen they are connected so that the circuitry will be broken when the relayor starter coil is not energized.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Symbolized by N.C. designation applied to the contacts of a starter or relaywhen they are connected so that the circuit will be completed when the relayor starter coil is not energized.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A device that automatically disconnects the circuit whenever the current ortemperature becomes excessive.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
OL
Relay contacts designed to open when its coil current rises above apredetermined value.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
I I
Contact - Normally Open (N.O.)
Contact -Normally Closed(N.C.)
Overload Relay
Overload Relay Contact(OL)
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 13
US/Canadian International / British German
A device that stores electrical energy, blocks the flow of DC, and permits theflow of AC to a degree dependent upon the capacitance and the frequency.Used in an inductive (motor) circuit in order to increase the power factor bymaking the total current more nearly in phase with the applied voltage.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
L1/1
L2/3
L3/5
T1/2
T2/4
T3/6
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
TM
CONTACTSAUXILIARY
SMC PLUS CONTROL TERMINALS
10 20 30 40 50 60 70 80 90
––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A protective device that melts and breaks the circuit when the currentexceeds the rated value.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
An electrical device that by electromagnetic induction transforms electricenergy from the power circuit to the control circuit at the same frequency butat a lower voltage.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
FU
H4
H3H2
H1
X2X1TRANS.
Power FactorCorrectionCapacitor
SMC Reduced VoltageMotor Starter
SMC PLUSInterface Module
Fuse
Control CircuitTransformer
Wiring Diagram Reference Resource
for CENTERLINE Motor Control Centers14 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
US/Canadian International / British German
A conductor that carries no current but serves to connect exposed metalsurfaces to an earth ground to prevent hazards in case of breakdown betweencurrent–carrying parts and the exposed surfaces.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Switch where button must be depressed each time contacts are to be opened.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Switch where button must be depressed each time contacts are to be closed.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A two position switch that permits one conductor to be connected to anotherconductor.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A multiposition switch that permits one or more conductors to be connectedto any of several other conductors.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
GRD
OFF ON1 2
1 2
B B
B A
HAND AUTO
OFF
1 2 31 0 2
Ground
Push Button - Normally Closed
Push Button - Normally Open
Selector Switch - 2-Position
Selector Switch - 3-Position
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 15
US/Canadian International / British German
A two–position snap switch operated by a projecting lever to open or closecircuits, contact is normally in the open position.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A two–position snap switch operated by a projecting lever to open or closecircuits, contact is normally in the closed position.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
The contact of a timer relay with an appreciable time interval between thede–energizing of the coil and the opening of its contact.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
The contact of a timer relay with an appreciable time interval between thede–energizing of the coil and the closing of its contact. ––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
The contact of a timer relay with an appreciable time interval between theenergizing of the coil and the closing of its contact.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
The contact of a timer relay with an appreciable time interval between theenergizing of the coil and the opening of its contact.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
T.C.
T.O.
T.C.
T.O.
Toggle Switch - Normally Open
Toggle Switch - Normally Closed
Timed Contact - Normally Open,Timed Open
Timed Contact - Normally Closed,Timed Closed
Timed Contact - Normally Open,Timed Closed
Timed Contact - Normally Closed,Timed Open
Wiring Diagram Reference Resource
for CENTERLINE Motor Control Centers16 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
US/Canadian International / British German
An electromechanical device having a terminal on each end of the resistiveelement, and a third terminal connected to the wiper contact. The electricalinput is divided as the contact moves over the element, thus making itpossible to mechanically change the resistance.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A light that indicates the state of a circuit.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Similar to a regular pilot light but can be depressed to test if the bulb isfunctional.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
GRD
1PT
2PT
H1
H2
X1
X2
H1
H2
X1
X2
Three–phase configuration of instrument transformers, the primary windingsof which are connected in parallel with the circuit whose voltage is to bemeasured or controlled.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A transformer intended for measuring or control purposes and designed tohave its primary winding connected in series with a circuit carrying thecurrent to be measured or controlled.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Insert color code next to symbolInsert color codeinside symbol
Insert color code next to symbol
Potentiometer
Pilot Light
Pilot Light - Push-To-Test
Two Potential Transformers-Schematic Diagram
Current Transformer
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 17
US/Canadian International / British German
GRD
3CT
2CT
1CT
(H1)
(X1)
(H1)
(X1)
(H1)
(X1)
Three–phase current transformer configuration used for inputs to digitalmetering system.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
An electrical instrument used to measure electrical parameters, such asvoltage, current, and power.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
A machine that converts electric energy into mechanical energy to do work.––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––––
Insert function codeinside symbol.
Insert function codeinside symbol.
Insert function codeinside symbol.
MTRM
3M
3
3-PhaseCurrent Transformer-Schematic Diagram
Meter
Motor
Wiring Diagram Reference Resource
for CENTERLINE Motor Control Centers18 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
Notes
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 19
Wiring Diagrams
Connection diagramsAllen–Bradley connection diagrams are that portion of the wiring diagramthat shows an approximate physical layout of the components that make upthe unit. This diagram gives the relative locations of the electrical devicesand includes wire numbers for easy identification of how the components arewired together.
Schematic diagramsAllen–Bradley schematic diagrams are the portion of the wiring diagram thatshows an electrical representation of how the circuits operate. Both thepower and control circuits are represented. The schematic diagram is oftenused by assemblers to wire the units and by maintenance electricians forinstallation and troubleshooting purposes.
Wiring diagramsA schematic diagram together with a connection diagram make up anAllen–Bradley ‘‘customer specific’’ wiring diagram. See the following twopages for an example of a full wiring diagram (CS70024150 – Bul. 2113).
Catalog number specific diagramsBeginning on page 22, you will find diagrams that are specific toAllen–Bradley catalog numbers. These diagrams are the schematic portionstaken from the full wiring diagrams.
Wiring Diagram Reference Resource
for CENTERLINE Motor Control Centers20 Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers
NOTES
54321
D
C
B
A
H
G
F
E
CONNECT BETWEEN SIMILARLY MARED TERMINALS
CB
22
21
TO BUSL2L1
STST
1L21L1
2
2
1
1
2
1 FU
GRD.2
TRANS.
1L21L1
24 A
OFF
23 A
ON
1L3
1L2
15A3
6 4
22 TB
1L1
1L1
3A1
M2
2112 A 4321 65
A2
2
1L2
24
DOOR
1A
STOP
(REAR VIEW)
23
START
24
1
T3T2T1
A3A2A1
OL
L3
1L3
1A1A11A3A3 1A2A2
BLOWN FUSELIGTS FOR
P.F. CAP. BAN
FLANGE(REAR VIEW)
1A1
1A2
VAR
1A3
P.F. CAPACITOR
FUA3
FUA2
FUA1
A3
1A3
A2
1A2
A1
1A1
Wiring Diagram Reference Resource for CENTERLINE Motor Control Centers 21
8765
ReferencesRevision
Release
BookRefer.
Angles ± 1°
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in InchesSurface Treatment
Dimensions Apply Before
±.023 Place Decimal
±.005 N/AN/A
PPEN577B 10/02/93
N/AN/A DateDateDate
Appd.Chkd.Dr.
D
OfSheetDwgSize
11
ACAD
Packaged Control Cadds9–17–93
G
F
E
D
C
B
A
HA 10/18/93
T1
1T2MTR
T3
1A1
OLSA1M
A2
A3
P.F.1A2 CAPACITOR
GRD
1A3
FUA2
2M
ONA
OFF
FUA1
FUA3
1L2
1L1
1L3
CB
L2
L1
BUSTO
480V
L360 3 P
2 21
21TRANS.
START
FU
3
M
2
4M
J
1ASTOP
24OL1
22OL216M5
A
TYPE BBUL. 2113 SIE 4 (2.5SF)
CS70024150
22
8765
1
LOAD
T1
T2
C
T3
GRD
X2C
ON
R
OFF
1L1
1L2
1L3
L2
L1TOBUS
480V
FDSL360 HZ
3 PH
2
X1H4
H3H2H1
X2X1
TRANS.CB
OFF ON
2C
3
4C
BA1
8C7C
10C
61A
(SPARE)
5
9
G
TYPE A
04/15/93
BUL. 2102L 30-60AMP
A
CS70006974
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface TreatmentDimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
NOTES:1
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
2
REMOTE DEVICE
TBTT32
108 9 T
15 6 71 2 3 4X2 1 A(TYPE "B" WIRING ONLY)
G
F
E
D
C
B
A
H
23
H4
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
1 REMOTE DEVICE
INTERNAL CB AUXILIARIES
SUPPLIED WITH UNMOUNTED
CONNECTION BLOCKS.
2
1
LOAD
1
1T1
1T2
1C
1T3
2T1
2T2
2C
GRD
2T3
1
1X21C
3
LOAD
1L1
1L2
1L3
2L1
2L2
1CB
L2
L1TOBUS
3 PH480V
L360 HZ
2L3
3FU
1X1
1H1
1FU
1C
21
2CB
H4
H3H2
H1
X2X1
TRANS.
5FU
1H4
GRD
2X22C
33
4FU
2H1
2L1
2L2
2FU
32
2C
2X1
31
H3H2H1
X2X1TRANS.
2
2H4
6FU
A 10/18/93
Dual Bul. 2103L 30-60 Amp Type A
CS70024114
24
2
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
1
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
2
REMOTE DEVICE
TT1 T1 11111
321653 4210TB
1X
A
"J1"
21 2 3 4 5
ON TYPE "A" WIRING, JUMPER "J1" WILL
BE ON DOOR MOUNTED PUSH BUTTONS.
9
(TYPE "B" WIRING ONLY)
1
T1
T2
MTRT3
OL'SF
R
GRD
X2OL8F
6
R
FORWARD
R7
R
REVERSE
2L1
2L2
2L3
MFU
L2
L1TO
BUS
480V
DSL360 HZ
3 PH
1L1
1L2
1L3
R3FORWARD
H4H3H2
H1
X2X1
TRANS.FU
21A
F
REVERSE
R
5 F
"J1"
"J2"
4
1STOP
A
OVERLOADOL
A 10/18/93
BUL. 2106 SIZE 1-2 (2SF) Type A
CS70024115
14F10F9 13
16RR 1211 15
25
H3H2
1L3
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
1REMOTE DEVICE
SECONDARY CONNECTIONS OF
POLARITY MARKINGS.
BE SURE TO CONNECT PER
CURRENT TRANSFORMER MUST
BE CONNECTED TO A LOAD OR
SHORTED TOGETHER TO AVOID
A HIGH VOLTAGE ACROSS
SECONDARY LEADS.
AMPS EFFECTIVE RATIO WITHAMPS NAMEPLATE RATIO
PRIMARY TURNSSECONDARY TURNS
1
T1
T2MTR
T3
OL'S1A1F
1A2
1A3
R
GRD
X2OL8F
6
SUP
R7
SUP
1L1
1L2
2L33CT
(H2)
BLK(X2)
(H1)
WHT(X1)
C2C1AMMETER
L2
L1TOBUS
480V
L360 HZ3 PH
CB
H4
2FU
H1
1FU
R3
H4H1
X2X1
TRANS.
AM
CB
21A
GRD
F
R
5 F
"J1"
"J2"
4
1
TTT
321TB
1X
A
"J1"
21 2 3 4 5
A 10/18/93
Bul. 2107 Size 1-2 (1.5SF) Type B
CS70024116
3
26
8765
G
E
D
C
B
A
4321
X2(96)
(2/T1)
(4/T2)
(6/T3)
1A1
1A3
1A2
(5/L3)
(3/L2)
(1/L1)
OLM
1L2
1L1
1L3
2FU
H2H1
1FU
(95)
3AM
3
START
M
2
X1H2H1
X2X1
TRANS.
1
MTR
OL
T3
T2
T1
FDS
L1
L3
L2
TO
60 HZ3 PH480V
BUS
FU
1ASTOP
1
"J"
"J"
1X2
1A
32
CS70020770
1
NOTES
REMOTE DEVICE
NEC.
UNIT INSTALLATION
THE GROUND FOR COMPLIANCE WITH
ARE HIGHER THAN 6-1/2 FEET OFF
TOP UNIT OPERATING HANDLES THAT
NE1, MAY BE NECESSARY FOR ANY
THE HANDLE EXTENDER KIT, 2100-
F
H
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
A 09/08/93
BUL. 2112 SIZE 1 (0.5 SF) Type B
GRD
27
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
1
THIS UNIT IS SUPPLIED
WITH AN INTERNALLY
PROTECTED TRANSFORMER.
REQUIRED.
PRIMARY FUSING NOT
2
REMOTE DEVICE
T1
1T2
T3
MTR
OL
M
OL
OL
GRD
X23A
CR(A1) (A2)
OL
GRD
1L1
1L3
1L2
L1
TOBUS
L2
FDSL3
3 PH480V
60 HZ
2 H2H1
X2X1TRANS.
2M
3
FU
OFF
1
BA
BB 1A
1 HAND AUTO
ETM TIME METER
MCR
(14)
7
(13)
M6M 5
23
4
ELAPSED
TB1XA2 321 7654
BUL. 2112 SIZE 5 Type B
A 10/18/93
CS70024134
28
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
1
CONDUCTORS EXTEND
BEYOND THE ENCLOSURE.
REFER TO NATIONAL
ELECTRICAL CODE.
ADDITIONAL CONTROL
CIRCUIT OVERCURRENT
PROTECTION MAY BE
CONTROL CIRCUIT
REQUIRED WHEN THE
2
REMOTE DEVICE
T1
1T2MTR
T3
OL'SM
X2
ON
R1
M
SUP
4M
OFF5M
1L2
1L1
1L3
CB
L2
L1
BUSTO
480V
L360 HZ3 PH
2
HAND STARTOFF
120V SEPARATE CONTROL
3
M
2
LB
1C
1LA 1A
HAND STOP24OL
1HAND AUTO
1
OVERLOAD
A
OL
1
22
7M6
G
TBTT321
T7651 32 4X2 1 A
A 10/18/93
BUL. 2113 SIZE 1-2 Type B
CS70024135
29
621
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
22 TB21X
1
"J"
2 A 43 5
1
THIS UNIT IS SUPPLIED
WITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
2
REMOTE DEVICE
THIS IS AN EXTERNAL CIRCUIT
BREAKER AUXILIARY ANDSHOULD NOT BE USED FOR
BREAKER TRIP INDICATION.
A 10/18/93
Bul. 2113 Size 4 (2.5SF) Type B
T1
1T2MTR
T3
1A1
OL'SA1M
A2
A3
P.F.1A2CAPACITOR
GRD
1A3
FUA2
X2M
ON
A
OFF
FUA1
FUA3
1L2
1L1
1L3CB
L2
L1
BUSTO
480V
L360 HZ3 PH
2 H2H1
X2X1TRANS.
START
FU
3
M
2
4M
"J"
1ASTOP24
OL1
22OL216M5
A
CS70024150
30
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
T2
MOTOR
WINDINGS
T12
LINES
T3
NEMA STANDARD
MOTOR CONNECTIONS
T11 T1
1
2
T13
REMOTE DEVICE
T13
T3
T12T11
T2T1
L3
T3
T13
L1
T1
T11
L2
T2
T12
LOW
HIGH
SPEED OPEN
T1
T2
1T3
T11
T12
MTR2
LOL'SL
HOL'SH
T13
X2H
6
RHIGH
L7
G
LOW
1L1
1L2
1L3
L2
L1TO
BUS
480V
FDSL360 HZ
3 PH
2FU1FU
L3HIGH
21A
H
LOW
L
5 H
"J1"
"J2"
4
HOL 24
L81 OL
STOP
AOVERLOAD22
HOL
LOL
TB1X2
"J1"
A1 2 3 4 5
A 10/18/93
Bul. 2122E Size 1-2 Type B
CS70024136
31
3
2
1
3
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
MOTOR
T6T2
T1
TORQUEVARIABLE
T1
T2T6
LINES
T3
T5
NEMA STANDARDMOTOR CONNECTIONS
T4 T4WINDINGS
T5
T3
CONSTANTTORQUE
REMOTE DEVICE
T2 T3
T6
T1
NONET4T3
L3
T5
T2
L2
T1
L1
T6 T4
T5
NONE
CONDUCTORS EXTENDBEYOND THE ENCLOSURE.REFER TO NATIONALELECTRICAL CODE.
ADDITIONAL CONTROLCIRCUIT OVERCURRENTPROTECTION MAY BE
CONTROL CIRCUITREQUIRED WHEN THE
LOW
HIGH
SPEED OPEN TOGETHER
T1
T2
1T3
T6
T4
2
MTR
L
H
L OL'S
HH OL'S
H
T5
H6
H
X28OL
RES
9L
7
LOL
1L1
1L2
1L3
L2
L1TO
BUS
480V
FDSL360 HZ
3 PH
L321A
120V SEPARATE CONTROL
H
L
H5
"J1"
"J2"
4
1
TB53A1 212
X
"J1"
4
Bul. 2122F Size 4 Type B
CS70006989
32
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
T2
WINDINGSMOTOR
T12
LINES
MOTOR CONNECTIONSNEMA STANDARD
T3
T1T11
1
2
T13
REMOTE DEVICE
T13
T3
T12T11
T2T1
T3
L3
T13
T1
L1
T11 T12
T2
L2
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
3
FAST
SLOW
OPENSPEED
T1
T2
1
T3
T11
T12
2MTR
SOL'SS
FOL'SF
T13
X2F
OL89
F
SOL
RFAST
SUP
S
RSLOW
1L1
1L2
1L3
L2
L1TO
BUS
480V
L360 HZ3 PH
CB
6
3
S
H2H1
X2X1TRANS.
CB
3
OFF
2F
7
4S
F
BA
BB 5
1
FAST SLOW
BUL 2123E SIZE 3 TYPE A
GRD
11S
13F
10
12(SPARE)
1A
CS70024137
SUP
33
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
MOTOR
T6T2
T1
TORQUEVARIABLE
T1
T2T6
LINES
T3
T5
NEMA STANDARDMOTOR CONNECTIONS
T4 T4WINDINGS
1
2
T5
T3
CONSTANTTORQUE
REMOTE DEVICE
T2 T3
T6
T1
NONET4T3
L3
T5
T2
L2
T1
L1
T6 T4
T5
NONE
LOW
HIGH
SPEED OPEN TOGETHER
T1
T2
1
T3
T6
T4
2
MTR
L
H
L OL'S
HH OL'S
H
T5
H6
H
X28OL
RHIGH
9L7
R
LOW
OLL
1L1
1L2
1L3
L2
L1TOBUS
480V
L360 HZ3 PH
CB
L3
HIGH
21A
X1120V SEPARATE CONTROL
H
LOW
L
H5
"J1"
"J2"
4
FU
1
STOP
TB432 51A2
X 1
"J1"
BUL. 2123F SIZE 3 TYPE B
CS70024139
RES
34
1
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
T1
T2
21
MTR
T3
T11
T12
OL'SL
L
HOL'SH
T13
GRD
X2OLOL3AH
L
L H
F
R
1L1
1L2
1L3
L2
L1TO
BUS
480V
FDSL360 HZ
3 PH
1FU
H4H1
H4H3H2
H1
X2X1
TRANS.
2FU
L3
H5
2
H
4
L
1A1
FU
1A1
1A2
1A3
F
R
R7
F9
6
8
F
R
T1
T3
TB
T2
9876432 5A1
2X TB(TYPE "B" WIRING ONLY)
(TYPE "B" WIRING ONLY)
T13T12T11
T1T11
T2
OPEN
T12
WINDINGS
L3L1
LINES
L2
T3
SYNOPSIS OF
MOTOR CONNECTIONS
MOTOR
1
T13
REMOTE DEVICE
SPEED
T13
T3
T12T11
T2T1
T13
T3
T12T11
T2T1
T3
T13
T1
T11
T2
T12
T1
T11
T3
T13
T2
T12
LOW
FOR.
HIGH
FOR.
LOW
REV.
HIGH
REV.
BUL. 2126E SIZE 1-2 TYPE A
CS70043575
2
35
L
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles ± 1°
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in InchesSurface Treatment
Dimensions Apply Before
±.023 Place Decimal
±.005 N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheetDwgSize
11
ACAD
Packaged Control Cadds9–17–93
G
F
E
D
C
B
A
H
A 10/18/93
T1
T2H
21MTR
T3
T6
T4
H
OL'SL
HOL'SH
T5
X2OLOL3AH
A
HIGH
L
LOW
L H
F
R
1L1
1L2
1L3
L2
L1TO
BUS
480V
FDSL360 HZ
3 PH
3
120V SEPARATE CONTROL
L3
H5
2
H
"J"
4
L
1A1
1A1
1A2
1A3
F
C
R
FORWARD
G
REVERSE
R7
F9
6
8
F
R
B
H16
18 L
17
19
13F
15R
12
14
T1
T3
T5T4
T6
TB
T2
TB19
18
164 5
1 1319 2
1876432 51A
X2 1
"J"
17
T4T1
MOTORT4 WINDINGS
T6
TORQUE
T2
VARIABLE
TOGETHER
T2T6
L3L2L1
LINES
T3
T5
OPEN
SYNOPSIS OF
MOTOR CONNECTIONS
T1
1
2
T5
T3
CONSTANTTORQUE
SPEED
REMOTE DEVICE
T2 T3
T6
T1
NONE
T2 T3
T6
T1
NONE
T4T3
T5
T2T1
T6 T4
T4T1
T6
T2T3
T5 T4
T5
NONE
T5
NONE
CONDUCTORS EXTENDBEYOND THE ENCLOSURE.REFER TO NATIONALELECTRICAL CODE.
ADDITIONAL CONTROLCIRCUIT OVERCURRENTPROTECTION MAY BE
CONTROL CIRCUITREQUIRED WHEN THE
3
HIGH
FOR.
LOW
FOR.
LOW
REV.
HIGH
REV.
BUL. 2126F SIZE 1-2 TYPE B
CS70043572
36
TRANS.
2MTR
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles ± 1°
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in InchesSurface Treatment
Dimensions Apply Before
±.023 Place Decimal
±.005 N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheetDwgSize
11
ACAD
Packaged Control Cadds9–17–93
G
F
E
D
C
B
A
H
A 10/18/93
T1
T2
1
T3
OL'SL
L1A1
1A2
1A3
T11
T12
GRD
T13
HOL'SH
X2OLOL3AH
L
L H
F
R
1L1
1L2
1L3
L2
L1BUSTO
480V
L360 HZ3 PH
CB
1FU
H4H1
H4H3H2
X2X1
2FU
2
4
L3
H
H5
L
1
WB
LOW OFF
WA
HIGH REV
FU
F
R
6
R7
F9
F
8R
BA
WB1
BA2
T1
T3
TB
T2
T11T12T13
1A
(SPARE)
97 8642 3 51A
X2 1 TB
T1 T11
T2
OPEN
T12
WINDINGS
L3L1
LINES
L2
T3
SYNOPSIS OFMOTOR CONNECTIONS
MOTOR
1
T13
REMOTE DEVICE
SPEED
T13
T3
T12T11
T2T1
T13T12T11
T3
T13
T1
T11
T2
T12
T1T3 T2
LOWFOR.
HIGHFOR.
LOWREV.
2
H1
BUL. 2127J SIZE 1-2 Type B
CS70043573
37
A
H
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles ± 1°
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in InchesSurface Treatment
Dimensions Apply Before
±.023 Place Decimal
±.005 N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheetDwgSize
11
ACAD
Packaged Control Cadds9–17–93
G
F
E
D
C
B
A
H
A 06/16/94
T1
T2H
21
T3H
OL'SL
L1A1
1A2
1A3
T6
T4
T5
HOL'SH
X2OLOL3AH
G
HIGH
L
LOW
L
F
R
1L1
1L2
1L3
L2
L1BUSTO
480V
L360 HZ3 PH
CB
3 H4
H3H2H1
X2X1
TRANS.
2
4
L3
H
H5
L
1
WB
LOW OFF
WA
HIGH REV
FU
F
G
R
FORWARD
G
REVERSE
R
OFF
OVERLOAD
6
R7
F9
F
11L
8
10
22
R
H
H
L
OL
OL
BA
WB1
BA2G
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
3
1REMOTE DEVICE
2
TOGETHERL3L2L1
LINES
MOTOR CONNECTIONS
SYNOPSIS OF
OPENSPEED
T2 T3
T6
T1
NONE
T6 NONE
T4T3
T5
T2T1
T6 T4
T4T1T2T3 T5
NONE
T5
REV.
LOW
FOR.
LOW
FOR.
HIGH
T4
T1
MOTORT4 WINDINGS
T6
TORQUE
T2
VARIABLE
T2T6 T5
T3T1
T5
TORQUE
CONSTANT
T3
13F
15R
121A
14(SPARE)
T1
T3
T5T4
T6
TB
T2
(TYPE "B" WIRING ONLY)
TB5411
319 2
1876432 51A
X2 1
(TYPE "B" WIRING ONLY)
MTR
BUL. 2127K SIZE 1-2 TYPE A
CS70043574
38
3
2
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
1
FOR APPLICATION DATA.TO PUBLICATION 150-804MOTOR CONTROLLER. REFERBULLETIN 150 SOLID STATE
REMOTE DEVICE
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
3
T1
1T2
OL4L1
4L2
T34L3
T2/4
T1/2
L2/3
L1/1
T3/6
2
L3/5
SMC-2
GRD
X2OL
OFF
G
3A(A2)
IC
3L1IC
3L2
2L1
2L2(T2/4)(L2/3)
(T1/2)(L1/1)
3L32L3(T3/6)(L3/5)
1L1
1L2
MFU
1L3
SCRFUSESL1A
L2AL2BUSTO
480V
L1
L3ADS
L360 HZ
3 PH
1
5
4START
IC
H4H3H2
H1
X2X1TRANS.FU
(A1)
ON
R
40
2
1
3IC
(14)
2(13)
"J"
6050
CONTACTAUXILIARY
3020
TMSMC-2 CONTROL TERMINALS
1A1 STOP
10
(TO BE SET FORINSTANTANEOUSCONTACT)
7IC6
3T
2T
1T75 643212
XA1
TB"J"
Bul . 2154E 4-5 Amp Type B
CS70006994
MTR
39
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles ± 1°
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in InchesSurface Treatment
Dimensions Apply Before
±.023 Place Decimal
±.005 N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheetDwgSize
11
ACAD
Packaged Control Cadds9–17–93
G
F
E
D
C
B
A
H
A 10/18/93
T1
1MTR
T2
OL
T3
2SMC PLUS
L1/1
L2/3
L3/5
T1/2
T2/4
T3/6
3L1
3L2
3L3
GRD
X2(A2)
IC3A OL
2L1
2L2
IC(T1/2)(L1/1)
(T2/4)(L2/3)
2L3(T3/6)(L3/5)
1L1
1L2
1L3
L2
L1BUSTO
480V
FDSL360 HZ
3 PH
3FU
H2H1
X2X1
TRANS.
FAN
4
SUP
(A1)
AON
BOFF5
60
24
5070
3START
2
9080
CONTACTSAUXILIARY
4030
TMSMC PLUS CONTROL TERMINALS
1
1ASOFT STOP
10
STOP
20
(TO BE SET FORINSTANTANEOUSCONTACT)
1
2
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANS-FORMER PRIMARYFUSING NOT REQUIRED.
3
REMOTE DEVICE
BULLETIN 150 SOLIDSTATE MOTOR CONT-ROLLER. REFER TOPUB. 150-811 FOR APP-LICATION DATA.
FOR SET-UP OF SOFTSTOP FEATURE, REFERTO PUB. 150-805.
4
5
TB
42 3A121X
T2T3
TB
T1
BUL. 2154F 45-54 AMP TYPE B
WITH SOFT STOP FEATURE
CS70043576
40
H2
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles ± 1°
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in InchesSurface Treatment
Dimensions Apply Before
±.023 Place Decimal
±.005 N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheetDwgSize
11
ACAD
Packaged Control Cadds9–17–93
G
F
E
D
C
B
A
H
A 10/18/93
T1
1MTR
T2
OL
T34L3
4L1
2
BC
(L1/1) (T1/2)
SMC PLUS
L1/1
L2/3
L3/5
T1/2
T2/4
T3/6
4L2
GRD
(L2/3)
(L3/5) (T3/6)
(T2/4)
RON
X2
OFFG
(A2)CR
3A OL
3L1
3L2
IC2L1
2L2(T1/2)(L1/1)
(T2/4)(L2/3)
3L32L3(T3/6)(L3/5)
SCR1L1
1L2
1L3
FUSES
L2
L1BUSTO
480V
CBL360 HZ
3 PH
3
5
H4
H3H1
X2X1
TRANS.
1
1SLOW SPEED4 7
START
6
BRAKE
CR
(13)
"J"
2 3
(14)
FU
IC
IC
STOP 1A1
SUP
(A1)
(K2)TDR
(A2)BC
IC (A2)
60
25
5070
14IC
(14)
15
13(13)
17
CR
(33)
4TDR
(D1X)
16CR
(43) (44)
T.C.
(D1Y)
(34)
9080
CONTACTSAUXILIARY
4030
TMSMC PLUS CONTROL TERMINALS
2
8
10 20
SUP
SUP
SUP
CONTACT)INSTANTANEOUS(TO BE SET FOR
(A1)
(K1)
(A1)
1
2
4
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
3
REMOTE DEVICE
BULLETIN 150 SOLID STATEMOTOR CONTROLLER. REFERTO PUBLICATION 150-811FOR APPLICATION DATA.
5
TDR TIME DELAY SETTING MUSTEXCEED SMC PLUS STARTINGTIME & MOTOR ACCELERATIONTIME BY 2 TO 5 SECONDS.
FOR SET-UP OF SLOW SPEEDWITH BRAKING FEATURE,REFER TO PUB. 150-810.
321TTT87665
TB
32A
"J"
12 4X 1
BUL. 2155F 30-35 AMP TYPE BWITH SLOW SPEED WITH BRAKING FEATURE
CS70043577
41
(2)
MOD-G4
3
2
1
DRIVE LEGEND
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
REMOTE DEVICE
FOR INTERNAL WIRING.REFER TO BUL. 1333-5.2
DRIVE TERMINAL BLOCKS
SPEED POT WIRING MUST BETWISTED THREE CONDUCTORSHIELDED WIRE, HAVING (2)
OF ELECTRICAL NOISE.THE SHIELD MUST BE GROUNDEDAT THE CONTROLLER END ONLY.
TO (3) TWISTS PER INCH. IFTHE POT IS REMOTELY MOUNTEDTHE WIRING MUST BE RUN INSEPARATE STEEL CONDUIT TOELIMINATE THE POSSIBILITY
T1
T2
OL
T3
1
MTR
M1
M2T2
T1
M3T3
(1)
GRDTB3
MOD-G43
(2)0-10V
4-20 mA
(3)
(4)
1SPEED
3A
4A
3
4 4
55
3
L2
L1
L3
H2
2FU1FU
H1
1L3
1L2
1L1
L2
L1BUSTO
3 PH600V
L3FDS
60 HZ
X2 GRD
FAN
(1)
TB4 MOD-G4
(3)
1919AT SPEED
B
RUN21
2020
R21
20FU
H2H1
X2X1TRANS.
(5)
(6)GRD
5A
FOR REV
6BA
(7)
(8)
6A
10
(LA)
10
OL16 16
11 11 (9)
17 17
77
88
9 9DRIVE STOP
11 11
JOG1212
DRIVE START
AC DRIVE
2 BUL. 1333 VARIABLE FREQUENCY
TB2
BA2
(LA)
2A
AUTO MANUAL
CUSTOMER'S120V, 1PH, 60HZ
SUPPLY1 (1)
BUL. 2162J 15HP AC DRIVE-NEMA 1
CS70024152
42
1
8765
NOTES:
References
Revision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.02
3 Place Decimal
+.005 N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
DRIVE LEGEND
TB3 TERMINAL BLOCKS
TB2 TERMINAL BLOCKS
TB1 TERMINAL BLOCKS
1
2REFER TO BUL. 1336-5.0
FOR INTERNAL WIRING.
REMOTE DEVICE
T1
T2
T3
M2
M1
M3
0-10V
4-20 mA
5
4
(1)8
TB2 MOD-G1
(2)7
6
7
8
2L2
2L1
2L3
MFU
1L1
1L2
1FU
2FU
H1
1L3
H2
L2
L1TOBUS
3 PH600V
L360 HZ
CB
X2 GRD
FAN2
X2
(3)(2)
FU
11
FAN3
FAN1
TB1 MOD-G1
(1)
TB2 MOD-G1
(3)
H2H1
X2X1TRANS.
L3
L2
L1
21
(4)2323
PANELPROGRAMMINGDISPLAY AND
COMMUN-CATION
SERIAL
AC MOTOR DRIVE
19
19A
FOR REV
23
11
(LA)BA
OFF
(LB)BA
HAND AUTO
(LA)BB
2
20
19
23
W/ 115VAC LOGIC INTERFACE BOARD
30
28
BUL. 1336 ADJUSTABLE FREQUENCY
MTR
11
BUL. 2163K 75HP AC DRIVE-NEMA 12
CS70024154
11
PORTS
43
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
T1OL
1
MTRT2
T3
1S0%
56
53R
65%80% 50%
1S0%
57
54
65%80%
65%
55R
50%
R
1S0%
58ST
80% 50%
50
2S
1L1
2S
51
1L2
1L3
L1
BUSTO
L2
FDSL3
480V
60 HZ3 PH
52
2S100%
100%
100%
X218
THERMALCUT-OUT
(ST)13
(A2)(A1) ISTR
1S12
OL
2
3
R11
(34)(33)
2S
(56)
T.O.
(55)
ISTR
2
(56)
ISTR
T.O.
3A
1
1BISTR
(13) (14) (55)
120V SEPARATE CONTROL120V SEPARATE CONTROL
2S15
R17
(A2)
TIME METERELAPSED
(A1)
ETM
CR
R
(L.B.)
1S162S
(68) (67)
T.C.
1S
2S
R
R
14
5
(44)(43)
ISTR
4
TB21
T T T354
2220 1
2 2 232
95 6
1A1
2 32X
1
(TYPE "B" WIRING ONLY)(TYPE "B" WIRING ONLY)
1
CONDUCTORS EXTENDBEYOND THE ENCLOSURE.REFER TO NATIONALELECTRICAL CODE.
ADDITIONAL CONTROLCIRCUIT OVERCURRENTPROTECTION MAY BE
CONTROL CIRCUIT
REQUIRED WHEN THE
2REMOTE DEVICE
CS70024144
Bul. 2172 Size 2 Type A
23CR
25CR(43) (44)
(13) (14)6CR19
21CR(32)
20(31)
(22)(21)
24
22
44
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 04/15/93
1
REMOTE DEVICE
T1OL
1MTR
T2
T3
1S0%
56
53R
65%80% 50%
1S0%
57
54
65%80%
65%
55R
50%
R
1S0%
58ST
80% 50%
50
2S
1L1
2S
51
1L2
1L3
CB
L1
BUSTO
L2
L3
480V
60 HZ3 PH
52
2S
2FU
H4
1FU
H1
X2X1
TRANS.
100%
100%
100%
GRD
X218
THERMALCUT-OUT
(ST)13(A2)(A1) ISTR
1S12
OL3
R11
(34)(33)
2S
(56)
T.O.
(55)
ISTR
2
"J"
1A
(56)
ISTR
T.O.
3A
1
1BISTR
(13) (14) (55)
2S15
R17
R
(L.B.)
1S162S
(68) (67)
T.C.
1S
2S
R
14
5(44)(43)
ISTR
CS70006998
BUL. 2173 SIZE 3 TYPE B
H4
H3H2
H1
45
H1
8765
References
Revision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.02
3 Place Decimal
+.005 N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/21/93
216 CA TB'S
G
S
GRD
GS
X21
BLOCKS
POWER
2X1
X1
1 1X1
DISTRIBUTION
TO BUS
1L21L1
L3L2L1
DS
1771-CP2
1X1X2
H41L2
H11L1
2FU
1FU
FU
TRANS.
H1 H3 H2 H4
GRD. X2 X1
X1
X2
H4
1771-P7
P/SACTIVE
L1L2/NGND
ONPOWEROFF
FUSE3A 250VNORM BLOW
12 3 4 5 6 7 8ON
OFF
CONNECT BETWEEN SIMILARLY MARKED TERMINALS
CS70024646
BUL. 2182E
46
8765
G
F
E
D
C
B
A
4321
CONNECT BETWEEN SIMILARLY MARKED TERMINALS
AC COM
IN 15
IN 7
IN 8
IN 0
IN 3
IN 5
IN 11
IN 13
AC COM
SLC5001746-IA16
IN 12
IN 10
IN 4
IN 2
IN 1
IN 6
IN 9
IN 14
X21
PWR OUT +24VDC
PWR OUT COM
120/240VAC
VAC NEUT
EARTH GND
200/240V
100/120V
SLC5001746-P1/P2
FUSE
POWER
SLC5/011747-L511
PC RUN
CPU FAULT
FORCED I/O
BATTERY LOW
BATTERY1747-BA
LINE 1SHIELDLINE 2
SLC5001747-DCM
FAULT
COMM
VAC-VDC 2
VAC-VDC 1
OUT 14
OUT 13
OUT 6
OUT 7
OUT 2
OUT 4
OUT 9
OUT 11
OUT 15
SLC5001746-OW16
OUT 10
OUT 8
OUT 3
OUT 1
OUT 0
OUT 5
OUT 12
CS70024147
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
A 10/18/93
BUL. 2182J
H
47
1
8765
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
BUS ORTO GRD
CUST'SGRD SYS
1
X2
L
N
DNG
120VAC
POWER
SLOW BLOW1.5A 250V
ON
ACTIVEP/S
OFF
P/SPARALLEL
1771-P4S
12 3 4 5 6 7 8ON
OFF
Bul. 2183E
CS70024148
48
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
DIGITAL METERING SYSTEM
(H1A)
(H1B)
1
2
(H1C)
3
4
(H2A)
(H2B)
IQ(H2C)
DATA PLUS
CUSTOMER'S
VOLTS, 3 PH., HZINCOMING LINE CABLES
(X1)
GRD
LUGS
(X1)
(X1)
1
(H1)
(H1)
3CT1
2CT
1CT
(H1)
0L20L1 0L3
MODULE
(A)
(C)
(NEU)
(B)
1L2
1L1
1L3
DS
L2
L1
HORIZONTAL BUS
L1
L2
L3
L3
POWER
SECONDARY CONNECTIONS OF
POLARITY MARKINGS.BE SURE TO CONNECT PER
CURRENT TRANSFORMER MUSTBE CONNECTED TO A LOAD ORSHORTED TOGETHER TO AVOIDA HIGH VOLTAGE ACROSSSECONDARY LEADS.
AMPS EFFECTIVE RATIO WITHAMPS NAMEPLATE RATIO
PRIMARY TURNSSECONDARY TURNS
1
CUSTOMER IS TO MOUNT ANDWIRE CURRENT TRANSFORMERS.
CS70002602
BUL.2190 METERING PANEL
1
/ / /
49
0L3
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
1211
1314 VM
VOLTMETER
(7)
(5)
(3)
(1)
(8)
(6)
(4)
(2)
AMMETER
AM
AMMETER SWITCH
321OFF
OUTGOING LOAD CABLES VOLTS, 3 PH., HZ
CUSTOMER'S
2
8
11
(X1)
GRD
LUGS
(X1)
(H1)
2CT1
1
1CT
(H1)
0L20L1
L3-L1
(2)
(6)
(8)
(4)
(1)
O
(5)
1
(7)
4
7
(3)
VOLTMETER SWITCH
1PT
X1
X2
1L1
1L2
H1
H2
2PTX1
X21L3
H1
H2
1FU
2FU
3FU
L2
L1
HORIZONTAL BUS
L1
L2
L3
L3
GRD
L1-L2 L2-L3
SECONDARY CONNECTIONS OF
POLARITY MARKINGS.BE SURE TO CONNECT PER
CURRENT TRANSFORMER MUSTBE CONNECTED TO A LOAD ORSHORTED TOGETHER TO AVOIDA HIGH VOLTAGE ACROSSSECONDARY LEADS.
AMPS EFFECTIVE RATIO WITHAMPS NAMEPLATE RATIO
PRIMARY TURNSSECONDARY TURNS
1
CUSTOMER IS TO MOUNT ANDWIRE CURRENT TRANSFORMERS.
IN VERTICAL POSITION.SCREWS WITH DRUM SWITCHVIEW FACING TERMINAL
- TOP TERMINAL
- BOTTOM TERMINAL
2
ON 6 S.F. INCOMING LINE LUGCOMPARTMENTS, THE CURRENTTRANSFORMERS ARE FACTORYMOUNTED AND WIRED.
CS70024643
Bul. 2191F Outgoing Feeder Lug Compartment
/ / /
50
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
SECONDARY CONNECTIONS OF
POLARITY MARKINGS.BE SURE TO CONNECT PER
CURRENT TRANSFORMER MUSTBE CONNECTED TO A LOAD ORSHORTED TOGETHER TO AVOIDA HIGH VOLTAGE ACROSSSECONDARY LEADS.
AMPS EFFECTIVE RATIO WITHAMPS NAMEPLATE RATIO
PRIMARY TURNSSECONDARY TURNS
1
CUSTOMER IS TO MOUNT ANDWIRE CURRENT TRANSFORMERS.
ON 6 S.F. INCOMING LINE LUGCOMPARTMENTS, THE CURRENTTRANSFORMERS ARE FACTORYMOUNTED AND WIRED.
INCOMING LINE CABLES VOLTS, 3 PH., HZ
CUSTOMER'S
2
11
GRD
LUGS
(X1)1
1CT
(H1)
0L20L1 0L3
AM
AMMETER
HORIZONTAL BUS
L1
L2
L3
CS70024642
Bul. 2191M Incoming Line Lug Compartment
/ / /
51
8765
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 07/16/93
CS70015974
BUL. 2192F DUAL
L3L2L1
TO HORIZONTAL BUS
USER'S OUTGOING LOAD CABLES
FDS
2T32T22T1
USER'S OUTGOING LOAD CABLES
FDS
1T1 1T31T2
52
8765
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/21/93
OL3OL2OL1
BPS
USER'S INCOMING LINE CABLES
L3
L2
L1
L1
L2
L3
HORIZONTAL BUS
CS70024644
BUL. 2192M
1L3 C
L3
1L2 C
L2
1L1 C
L1
GRD
(REAR VIEW)
DOOR
53
8765
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70002993
BUL. 2193F
L3L2L1
TO HORIZONTAL BUS
T3T2T1
USER'S OUTGOING LOAD CABLES
54
1
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70003259
Bul. 2193M
1
HORIZONTAL BUS
GRD
GRN
YEL
WHT
GRYSENSOR
CURRENT
BLK
BLU
RED
NOL2OL1
L1
L2
L3
OL3
USER'S INCOMING LINE CABLES
AVOID A HIGH VOLTAGE ACROSS SECONDARY LEADS.BE CONNECTED TO A LOAD OR SHORTED TOGETHER TOSECONDARY CONNECTIONS OF CURRENT SENSOR MUST
BE SURE TO CONNECT PER POLARITY MARKINGS.
SENSOR IS NOT NECESSARY.TO NEUTRAL LOADS ARE USED, THE NEUTRAL CURRENTIF THE SYSTEM NEUTRAL IS GROUNDED, BUT NO PHASE
SENSOR MUST BE USED.NEUTRAL LOADS ARE USED, THEN THE NEUTRAL CURRENTIF THE SYSTEM NEUTRAL IS GROUNDED AND PHASE TO
CONNECTION BLOCKS.INTERNAL CB AUXILIARIES SUPPLIED WITH UNMOUNTED
ATTENTION__________________________________
Line side power connected tobottom of switch.
De-energize power to switchbefore servicing.
Failure to de-energize powercan result in severe injury or
death.
!
55
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70024145
BUL. 2193LE 3-PHASE LIGHTING PANEL
2
4
6
8
1NEUTRAL
12
14
16
18
X3
10
PANEL
1
3
5
7
X2X1
13
15
11
17
9
WHITE WIRE
PANEL
BUS
N
PANEL
BRANCH
CIRCUIT
GFI
CIRCUIT BREAKER
NEUTRAL
GFI CIRCUIT BREAKER
CONNECTIONS
(WHERE SPECIFIED)
REFER TO MANUFACTURERS
INSTRUCTIONS FOR
INSTALLATION AND TESTING.
1
5 - 20A. - 1 POLE BREAKER(S)
6 - 30A. - 1 POLE BREAKER(S)
7 - 15A. - 1 POLE BREAKER(S)
LIGHTING PANEL SUPPLIED WITH:
ALSO CONNECTED TO PANEL NEUTRAL.
OTHER SIDE OF EACH CIRCUIT IS
56
8765
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
TO BUS
L3L2L1
FDS
1L2
1L1
H2
X1
TRANS.
H4H3
X2
H1
X2
GRD.
120V
480 VOLTS
FU
Bul. 2196 2kVA
A 10/18/.93
CS70024146
57
8765
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70024151
CB
L3
TO
LOAD
1L3
1L2
1L1
BLK
BLU
RED
L1
BLK
BLU
RED
FUSES
INTERNAL CB AUXILIARIESSUPPLIED WITH UNMOUNTEDCONNECTION BLOCKS.
TO
GRD BUS
OR CUST.
GRD SYS. SECONDARY
PRIMARY TAP CONNECTIONS PRIMARY
H1 H2 H3
X0 X0 X1 X2 X3
5 3 1 2 4 6 5 3 1 2 4 6 5 3 1 2 4 6
1 2 3 4 5 6 1 2 3 4 5 6 1 2 3 4 5 6X0 X0 X1 X2 X3 H1 H2 H3
TRANS.
TO BUSL2
SECONDARY600
615
630
VOLTS
600
570
585
3 - 4
2 - 3
1 - 2
TAP
CONNECTION
5 - 6
4 - 5
456
480
468
492
504
VOLTS
480
Bul. 2197 37.5 kVA
58
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70024106
BUL. 2402 30 AMP (0.5 SF) TYPE A
1
LOAD
GRD
X2
T1
T2
T3
(1/L1)
(6/T3)
(4/T2)
(2/T1)
C
1L3
1L2
1L1
(5/L3)
(3/L2)
C(A2)
ON
C
(A1)
3
(4)(3)
ON
(13)(14)
C
X1
2
"J"
(62)
C7
H2H1
X2X1
TRANS.2
FDS
TO
L3
L2
L1
60 HZ3 PH480V
BUS
1AOFF
(2)(1)
65
(53)
C4
(54)
1
FU
(61)
1
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
2
REMOTE DEVICE "J"
LOCATED ON DOORJUMPER "J" WILL BEON TYPE "A" WIRING,
MOUNTED PUSH BUTTONS.
11A
X2
45
3
7
TB
6
2
(TYPE "B" WIRING ONLY)
59
1
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70024107
BUL. 2403 100 AMP TYPE B
LOAD
GRD
X2
T1
T2
T3
(1/L1)
(6/T3)
(4/T2)
(2/T1)
C
1L3
1L2
1L1
H2
1FU
H1
2FU
(5/L3)
(3/L2)
C(A2)(A1)
2
(14)(13)
C
X1
3
H2H1
X2X1
TRANS.
CB
TO
L3
L2
L1
60 HZ3 PH600V
BUS
(4)(3)
OFF ON
1
(SPARE)
1A
FU
1
REMOTE DEVICE
TB31A
1X2
2
60
3
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70024108
BUL. 2406 18-24 AMP TYPE B
CAUSE INJURY TO PERSONS OR
DAMAGE TO EQUIPMENT.
DO NOT USE AUTOMATIC RESET
MODE IN APPLICATIONS WHERE
UNEXPECTED AUTOMATIC
RESTART OF THE MOTOR CAN
3
REMOTE DEVICE
1
MTR
T1
T2(4/T2)
(2/T1)
T3(6/T3)
F
(4/T2)
(2/T1)(1/L1)
(6/T3)
R(2/T1)
(4/T2)
(1/L1)
OL'S
GRD
X2OL
(6/T3)
8F
6
(X2)R
(X1)
FORWARD
(A2)
(X2)
R7
(A1)
R(X1)
REVERSE
(A1) (A2) (96)(95)
1L1
1L2
1L3
L2
L1BUSTO
600V
FDSL360 HZ
3 PH
H2
2FU
H1
1FU
R3
H2H1
X2X1TRANS.FU
21A
X1
F
(13) (14)
(21)
R
(13) (14)
5 F
"J1"
"J2"
4
(21)
1(22)
(22)
(5/L3)
(3/L2)
(5/L3)
(3/L2)
(X2)A(X1)
OVERLOAD22
(97)
OL
(98)
14F
(63) (64)
10F
(54)
9(53)
13
16R
(63) (64)
R
(54)
12(53)
11 15
TB15
113
14 6
12
10
11
94 52A1
1
"J1"
2X
"J2"
3
1
! ATTENTION
61
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70024640
Bul. 2407 304 Amp Type A
1
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
2
REMOTE DEVICE
CAUSE INJURY TO PERSONS OR
DAMAGE TO EQUIPMENT.
DO NOT USE AUTOMATIC RESET
MODE IN APPLICATIONS WHERE
UNEXPECTED AUTOMATIC
RESTART OF THE MOTOR CAN
3TB4 531
AX2 1 2
(TYPE "B" WIRING ONLY)
T1
1MTR
T2
T3
1CT1A1
OL(B)
(1L1)
F(2/T1)
(3L2)
OL
3CT
(5L3)
(D)
1A2(4/T2)
1A3(6/T3)
2CT
3
(2T1)
(A)
(4T2)
(6T3)
(C)
OL(F)
R(2/T1)
(6/T3)
(4/T2)
(E)
GRD
X2F(A2)(A1)
G (X2)(X1)
FORWARD
GRD
1L1
1L2
1L3
CB
L1
TOBUS
L2
L3
480V
60 HZ3 PH
6R
(22)(21)
2
7
F
F
(14) (13)
X1FU
3
OFF
(3)(4)
5
H2H1
X2X1TRANS.
2
24OL
(96)
1(95)
FOR REV
(5/L3)
(1/L1)
(3/L2)
(1/L1)
(3/L2)
(5/L3)
(A2)
(X2)G
(A1)
(X1)
REVERSE
B (X2)(X1)
OFF
4
(22)
R
(21)
(13)(14)
10R9F
(SPARE)
1A
(4)(3)R
! ATTENTION
62
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70024110
Bul. 2412 38 - 45 Amp Type B
1
REMOTE DEVICE
CAUSE INJURY TO PERSONS OR
DAMAGE TO EQUIPMENT.
DO NOT USE AUTOMATIC RESET
MODE IN APPLICATIONS WHERE
UNEXPECTED AUTOMATIC
RESTART OF THE MOTOR CAN
3
1
MTR
T1
T2
T3
GRD
R
ON
(X2)
X2
OFF
G(X2)
3
(1/L1) (2/T1)
(4/T2)
(6/T3)
M OL'S1L1
1L2
1L3
H4
1FU
H1
2FU
(3/L2)
(5/L3)
M(A2)
4
(A1)
3
M
5M
(4)(3)
HAND START
(13)(14)
M
X1
2
1
H4
H3
H2
H1
X2X1
TRANS.
(6/T3)
(4/T2)
(2/T1)
(X1)
(X1)
TO
L3
L2
L1
FDS60 HZ3 PH240V
BUS
1C
1A
OFF
24(3)(4)
HAND AUTO
(4)(3)
OL
(96)
1(95) (2)(1)
FU
HAND STOP
4 5 TB31A
21X2! ATTENTION
63
2
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/18/93
CS70024111
Bul. 2413 180 Amp (2.5 SF) Type B
1
THIS UNIT IS SUPPLIEDWITH AN INTERNALLYPROTECTED TRANSFORMER.
REQUIRED.PRIMARY FUSING NOT
2
REMOTE DEVICE
CAUSE INJURY TO PERSONS OR
DAMAGE TO EQUIPMENT.
DO NOT USE AUTOMATIC RESET
MODE IN APPLICATIONS WHERE
UNEXPECTED AUTOMATIC
RESTART OF THE MOTOR CAN
3
TB31A1 2X
2
"J"
1MTR
T13
(A)
(2T1)
2L1
(B)
(1L1)
1CT
OL
T2(4T2)
T3(6T3)
(C)
2L2(3L2)
2L3(5L3)
(D)OL
3CT
2CT
GRD
(E)(F)OL
X2OL
(95)
3AM(A1)
ON
A
(A2) (96)
GRD
M
(1/L1)
1L1
(3/L2)
(5/L3)
1L2
1L3
CB
L1
TOBUS
L2
L3
480V
60 HZ3 PH
H2H1
X2X1TRANS.X1FU
3
1
M
(13)
2
(14)
"J"(2)(1)
1ASTOP
1
(2/T1)
(4/T2)
(6/T3)
OVERLOAD
AOL
1(98)
22(97)
! ATTENTION
64
8765
NOTES:
ReferencesRevision
Release
BookRefer.
Angles + 15
2 Place DecimalOtherwise SpecifiedTolerances Unless
Dimensions in Inches
Surface Treatment
Dimensions Apply Before
+.023 Place Decimal
+.005N/AN/A
PPEN577B 10/02/93
N/AN/A Date
Date
Date
Appd.
Chkd.
Dr.
D
OfSheet
DwgSize
11
ACAD
Packaged Control Cadds9-17-93
G
F
E
D
C
B
A
H
A 10/21/93
CS70024626
Bul. 2492F
NE1, MAY BE NECESSARY FOR ANY
UNIT INSTALLATION
THE HANDLE EXTENDER KIT, 2100-
TOP UNIT OPERATING HANDLES THAT
ARE HIGHER THAN 6-1/2 FEET OFF
THE GROUND FOR COMPLIANCE WITH NEC
T2
T3
LOAD CABLES
USER'S OUTGOING
T1
L2
L3
TO
BUS
HORIZONTAL
L1
FDS
Publication 2100-WD1 - April, 1995
AllenBradley , a Rockwell Automation Business, has been helping its customers improve productivity and uality for more than 90 years. W e design, manufacture and support a broad rangeof automation products worldwide. They include logic processors, power and motion controldevices, operator interfaces, sensors and a variety of software. Rockwell is one of the worldsleading technology companies.
Worldwide representation.
Argentina • Australia • Austria • Bahrain • Belgium • Brazil • Bulgaria • Canada • Chile • China, PRC • Colombia • Costa Rica • Croatia • Cyprus • Czech Republic •Denmark • Ecuador • Egypt • El Salvador • Finland • France • Germany • Greece • Guatemala • onduras • ong ong • ungary • Iceland • India • Indonesia •
Ireland • Israel • Italy • Jamaica • Japan • Jordan • orea • uwait • Lebanon • Malaysia • Mexico • Netherlands • New ealand • Norway • Pakistan • Peru •Philippines • Poland • Portugal • Puerto Rico • atar • Romania • RussiaCIS • Saudi Arabia • Singapore • Slovakia • Slovenia • South Africa, Republic • Spain •Sweden • Switzerland • Taiwan • Thailand • Turkey • United Arab Emirates • United ingdom • United States • Uruguay • Venezuela • Yugoslavia
AllenBradley eaduarters, 1201 South Second Street, Milwaukee, WI 53204 USA, T el (1) 414 3822000 Fax (1) 414 3824444
Publication 2100-WD1 - April, 1995Copyright 1985 AllenBradley Company , Inc. Printed in USA