220 kv gss heerapura report

59
CHAPTER 1 INTRODUCTION Electrical power is generated, transmitted in the form of alternating current. The electric power produced at the power stations is delivered to the consumers through a large network of transmission & distribution. The transmission network is inevitable long and high power lines are necessary to maintain a huge block of power source of generation to the load centers to inter connected. Power house for increased reliability of supply greater. The assembly of apparatus used to change some characteristics (e.g. voltage, ac to dc, frequency, power factor etc.) of electric supply keeping the power constant is called a substation. An electrical substation is a subsidiary station of an electricity generation, transmission and distribution system where voltage is transformed from high to low or the reverse using transformers. Electric power may flow through several substations between generating plant and consumer, and may be changed in voltage in several steps. 1

Upload: mohit-bhavsar

Post on 26-Oct-2014

124 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: 220 Kv GSS Heerapura Report

CHAPTER 1

INTRODUCTION

Electrical power is generated, transmitted in the form of alternating current. The electric power

produced at the power stations is delivered to the consumers through a large network of transmission

& distribution. The transmission network is inevitable long and high power lines are necessary to

maintain a huge block of power source of generation to the load centers to inter connected. Power

house for increased reliability of supply greater.

The assembly of apparatus used to change some characteristics (e.g. voltage, ac to dc, frequency,

power factor etc.) of electric supply keeping the power constant is called a substation.

An electrical substation is a subsidiary station of an electricity generation, transmission and

distribution system where voltage is transformed from high to low or the reverse using transformers.

Electric power may flow through several substations between generating plant and consumer, and

may be changed in voltage in several steps.

Fig.1 - 220 KV GSS IG Nagar

1

Page 2: 220 Kv GSS Heerapura Report

Substations have switching, protection and control equipment and one or more transformers. In a

large substation, circuit breaker are used to interrupt any short-circuits or overload currents that may

occur on the network.

Depending on the constructional feature, the high voltage substations may be further

subdivided:

(a) Outdoor substation

(b) Indoor substation

(c) Base or Underground substation

1.1) 220KV Grid Substation, IG Nagar:

Its part of RRVPNL. It is situated 13.4km away from Jaipur. The power mainly comes from three

incoming feeders of 220 KV(Heerapura). The substation is equipped with various equipments and

there are various arrangements for the protection purpose. The equipments in the GSS are listed

previously. At this substation following feeders are established.

1. TIE FEEDERS

2. RADIAL FEEDERS

220KV GSS IG Nagar is an outdoor type primary substation and distribution as well it has not only

step down but the distribution work

The electrical work in a substation comprises to:

1. Choice of bus bar arrangement layout.

2. Selection of rating of isolator.

3. Selection of rating of instrument transformer.

4. Selection of rating of C.B.

5. Selection of lighting arrester [LA]

6. Selection of rating of power transformer

7. Selection of protective relaying scheme, control and relay boards.

8. Selection of voltage regulator equipment.

9. Design a layout of earthing grids and protection against lightening stockes.

2

Page 3: 220 Kv GSS Heerapura Report

1.2 INCOMING FEEDERS:

220 KV(Heerapura)

220 KV Bassi(PGCIL)

Puranaghat(Currently Dead)

1.3 OUTGOING FEEDERS:

The outgoing feeders are:

1. Puranaghat 220 KV

2. Jagatpura 33 KV

3. Mahel 33 KV

4. IG Nagar 33 KV

5. Bisalpur 33 KV

6. Pradhan Marg 33 KV

Rajasthan Rajya Vidyut Prasaran Nigam Limited (RRVPNL) a company under the Companies Act,

1956 and registered with Registrar of Companies as "RAJASTHAN RAJYA VIDYUT PRASARAN

NIGAM LIMITED" vide No. 17-016485 of 2000-2001 with its Registered Office at VIDYUT

BHAWAN, JYOTI NAGAR, JAIPUR-302005 has been established on 19 July, 2000 by Govt. of

Rajasthan under the provisions of the Rajasthan Power Sector Reform act 1999 as the successor

company of RSEB. The RERC has granted RRVPNL a license for transmission and bulk supply vide

RERC/Transmission and Bulk Supply License 4/2001 dated 30.

Our aim is to provide reliable electric transmission service to these customers. As a public utility

whose infrastructure serves as the link in transporting electricity to millions of electricity users,

RRVPNL has following duties and responsibilities:

• Intra state transmission of electricity through Intra-State Transmission System.

• Ensuring development of an efficient, co-ordinated and economical system of intra-state

transmission of electricity from generating stations to Load Centers.

• Non-discriminatory Open Access to its transmission system on payment of transmission charges

• Complying with the directions of RLDC and SLDC, operating SLDC until any other authority is

3

Page 4: 220 Kv GSS Heerapura Report

established by the State Govt.

• Now RRVPNL is "An ISO 9001:2000 Certified Company".

4

Page 5: 220 Kv GSS Heerapura Report

5

Page 6: 220 Kv GSS Heerapura Report

Fig. 2: Single Line Diagram of 220KV GSS Heerapura(Jaipur)

CHAPTER 2

LIGHTNING ARRESTER

Fig. 3- Lightning arrester

A lightning arrester (also known as surge diverter) is a device connected between line and earth i.e. in

parallel with the over headline, HV equipments and substation to be protected. It is a safety valve

which limits the magnitude of lightning and switching over voltages at the substations, over headlines 6

Page 7: 220 Kv GSS Heerapura Report

and HV equipments and provides a low resistance path for the surge current to flow to the ground.

The practice is also to install lightning arresters at the incoming terminals of the line.

All the electrical equipments must be protected from the severe damages of lightning strokes. The

techniques can be studied under:-

Protection of transmission line from direct stroke.

Protection of power station and sub-station from direct stroke.

Protection of electrical equipments from travelling waves.

2.1) Types of Arrestors:-

2.1.1) Rod/sphere gap:- It is a very simple protective device i.e. gap is provided across the

stack of Insulators to permit flash-over when undesirable voltages are impressed of the

system.

2.1.2) Expulsion type LA:- It have two electrodes at each end and consists of a fiber tube

capable of producing a gas when is produced. The gas so evolved blows the arc

through the bottom electrode.

2.1.3) Valve type LA:- It consists of a divided spark-gap in series will a non linear resistor.

The divided spark gap consists of a no. of similar elements, each of it two electrode

across which are connected high resistor.

7

Page 8: 220 Kv GSS Heerapura Report

CHAPTER 3

BUS BARS

Bus Bars are the common electrical component through which a large no of feeders operating at same

voltage have to be connected. If the bus bars are of rigid type (Aluminum types) the structure height

are low and minimum clearance is required. While in case of strain type of bus bars suitable ACSR

conductor are strung/tensioned by tension insulators discs according to system voltages. In the widely

used strain type bus bars stringing tension is about 500-900 Kg depending upon the size of conductor

used.

Here proper clearance would be achieved only if require tension is achieved. Loose bus bars would

effect the clearances when it swings while over tensioning may damage insulators. Clamps or even

effect the supporting structures in low temperature conditions.

The clamping should be proper, as loose clamp would spark under in full load condition damaging

the bus bars itself.

3.1) BUS BAR ARRENGEMENT MAY BE OF FOLLOWING TYPE

WHICH IS BEING ADOPTED BY R.R.V.P.N.L.:-

3.1.1) Single bus bar arrangement

3.1.2) Double bus bar arrangement

a) Main bus with transformer bus

b) Main bus-I with main bus-II

3.1.3) Double bus bar arrangement with auxiliary bus.

8

Page 9: 220 Kv GSS Heerapura Report

3.1.1) SINGLE BUS BAR ARRANGEMENT :

This arrangement is simplest and cheapest. It suffers, however, from major defects.

1. Maintenance without interruption is not possible.

2. Extension of the sub station without a shut down is not possible

3.1.2) DOUBLE BUS BAR ARRANGEMENT :

1. Each load may be fed from either bus.

2. The load circuit may be divided in to two separate groups if needed from

operational consideration. Two supplies from different sources can be put on each

bus separately.

3. Either bus bar may be taken out from maintenance of insulators.

The normal bus selection insulators can not be used for breaking load currents. The

arrangement does not permit breaker maintenance without causing stoppage of supply.

3.1.3) DOUBLE BUS BAR ARRANGEMENTS CONTAINS MAIN BUS WITH

AUXILARY BUS :

The double bus bar arrangement provides facility to change over to either bus to carry out maintenance on the other but provide no facility to carry over breaker maintenance. The main and transfer bus works the other way round. It provides facility for carrying out breaker maintenance but does not permit bus maintenance. Whenever maintenance is required on any breaker the circuit is changed over to the transfer bus and is controlled through bus coupler breaker.

9

Page 10: 220 Kv GSS Heerapura Report

CHAPTER 4

INSULATOR

The insulator for the overhead lines provides insulation to the power conductors from the ground so

that currents from conductors do not flow to earth through supports. The insulators are connected to

the cross arm of supporting structure and the power conductor passes through the clamp of the

insulator. The insulators provide necessary insulation between line conductors and supports and thus

prevent any leakage current from conductors to earth. In general, the insulator should have the

following desirable properties:

High mechanical strength in order to withstand conductor load, wind load etc.

High electrical resistance of insulator material in order to avoid leakage currents to

earth.

High relative permittivity of insulator material in order that dielectric strength is high.

High ratio of puncture strength to flash over.

These insulators are generally made of glazed porcelain or toughened glass. Poly come type insulator

[solid core] are also being supplied in place of hast insulators if available indigenously. The design of

the insulator is such that the stress due to contraction and expansion in any part of the insulator does

not lead to any defect. It is desirable not to allow porcelain to come in direct contact with a hard

metal screw thread.

4.1) TYPE OF INSULATORS:

4.1.1: Pin type

4.1.2: Suspension type

4.1.3: Strain insulator

4.1.1) PIN TYPE: Pin type insulator consist of a single or multiple shells adapted to be

mounted on a spindle to be fixed to the cross arm of the supporting structure. When

10

Page 11: 220 Kv GSS Heerapura Report

the upper most shell is wet due to rain the lower shells are dry and provide sufficient

leakage resistance these are used for transmission and distribution of electric power at

voltage up to voltage 33 KV. Beyond operating voltage of 33 KV the pin type

insulators thus become too bulky and hence uneconomical.

Fig. 4-Pin type insulator

4.1.2) SUSPENSION TYPE: Suspension type insulators consist of a number of porcelain

disc connected in series by metal links in the form of a string. Its working voltage is

66KV. Each disc is designed for low voltage for 11KV.

11

Page 12: 220 Kv GSS Heerapura Report

Fig. 5-Suspension type insulator

4.1.3) STRAIN INSULATOR: The strain insulators are exactly identical in shape with the

suspension insulators. These strings are placed in the horizontal plane rather than the

vertical plane. These insulators are used where line is subjected to greater tension. For

low voltage lines (< 11KV) shackle insulator are used as strain insulator.

Fig. 6-Strain type insulator

12

Page 13: 220 Kv GSS Heerapura Report

CHAPTER 5

ISOLATORS

“Isolator" is one, which can break and make an electric circuit in no load condition. These are

normally used in various circuits for the purposes of Isolation of a certain portion when required for

maintenance etc. Isolation of a certain portion when required for maintenance etc. "Switching

Isolators" are capable of

Interrupting transformer magnetized currents

Interrupting line charging current

Load transfer switching

13

Page 14: 220 Kv GSS Heerapura Report

Fig. 7- Isolators

Its main application is in connection with transformer feeder as this unit makes it possible to

switch out one transformer, while the other is still on load. The most common type of isolators is the

rotating centre pots type in which each phase has three insulator post, with the outer posts carrying

fixed contacts and connections while the centre post having contact arm which is arranged to move

through 90` on its axis.

The following interlocks are provided with isolator:

a) Bus 1 and2 isolators cannot be closed simultaneously.

b) Isolator cannot operate unless the breaker is open.

c) Only one bay can be taken on bypass bus.

d) No isolator can operate when corresponding earth switch is on breaker.

14

Page 15: 220 Kv GSS Heerapura Report

CHAPTER 6

CIRCUIT BREAKER

The function of relays and circuit breakers in the operation of a power system is to prevent or limit

damage during faults or overloads, and to minimize their effect on the remainder of the system. This

is accomplished by dividing the system into protective zones separated by circuit breakers. During a

fault, the zone which includes the faulted apparatus is de-energized and disconnected from the

system. In addition to its protective function, a circuit breaker is also used for circuit switching under

normal conditions.

Each having its protective relays for determining the existence of a fault in that zone and having

circuit breakers for disconnecting that zone from the system. It is desirable to restrict the amount of

system disconnected by a given fault; as for example to a single transformer, line section, machine, or

15

Page 16: 220 Kv GSS Heerapura Report

bus section. However, economic considerations frequently limit the number of circuit breakers to

those required for normal operation and some compromises result in the relay protection.

Some of the manufacturers are ABB, AREVA, Cutler-Hammer (Eaton), Mitsubishi Electric,

Pennsylvania Breaker, Schneider Electric, Siemens, Toshiba, Končar HVS and others.

Circuit breaker can be classified as "live tank", where the enclosure that contains the breaking

mechanism is at line potential, or dead tank with the enclosure at earth potential. High-voltage AC

circuit breakers are routinely available with ratings up to 765,000 volts.

6.1) Various types of circuit breakers:-

6.1.1) SF6 Circuit Breaker

6.1.2) Air Blast Circuit Breaker

6.1.3) Oil Circuit Breaker

6.1.4) Bulk Oil Circuit Breaker (MOCB)

6.1.5) Minimum Oil Circuit Breaker

6.1.1) SF6 CIRCUIT BREAKER:-

Sulphur hexafluoride has proved its-self as an excellent insulating and arc quenching medium. It has

been extensively used during the last 30 years in circuit breakers, gas-insulated switchgear (GIS), high

voltage capacitors, bushings, and gas insulated transmission lines. In SF6 breakers the contacts are

surrounded by low pressure SF6 gas. At the moment the contacts are opened, a small amount of gas is

compressed and forced through the arc to extinguish it.

16

Page 17: 220 Kv GSS Heerapura Report

Fig. 8-SF6 Circuit Breaker

6.1.2) AIR BLAST CIRCUIT BREAKER:

The principle of arc interruption in air blast circuit breakers is to direct a blast of air, at high

pressure and velocity, to the arc. Fresh and dry air of the air blast will replace the ionized hot

gases within the arc zone and the arc length is considerably increased. Consequently the arc

may be interrupted at the first natural current zero. In this type of breaker, the contacts are

surrounded by compressed air. When the contacts are opened the compressed air is released in

forced blast through the arc to the atmosphere extinguishing the arc in the process.

17

Page 18: 220 Kv GSS Heerapura Report

Fig. 9-Air Blast Circuit Breaker

Advantages:

An air blast circuit breaker has the following advantages over an oil circuit breaker:

The risk of fire is eliminated

The arcing products are completely removed by the blast whereas the oil deteriorates with

successive operations; the expense of regular oil is replacement is avoided

The growth of dielectric strength is so rapid that final contact gap needed for arc extinction is

very small. this reduces the size of device

The arcing time is very small due to the rapid build up of dielectric strength between contacts.

Therefore, the arc energy is only a fraction that in oil circuit breakers, thus resulting in less

burning of contacts

Due to lesser arc energy, air blast circuit breakers are very suitable for conditions where

frequent operation is required

18

Page 19: 220 Kv GSS Heerapura Report

The energy supplied for arc extinction is obtained from high pressure air and is independent

of the current to be interrupted.

Disadvantages:

Air has relatively inferior arc extinguishing properties.

Air blast circuit breakers are very sensitive to the variations in the rate of restriking voltage.

Considerable maintenance is required for the compressor plant which supplies the air blast

Air blast circuit breakers are finding wide applications in high voltage installations. Majority

of circuit breakers for voltages beyond 110 kV are of this type.

6.1.3) OIL CIRCUIT BREAKER:

Circuit breaking in oil has been adopted since the early stages of circuit breakers

manufacture. The oil in oil-filled breakers serves the purpose of insulating the live parts from the

earthed ones and provides an excellent medium for arc interruption. Oil circuit breakers of the

various types are used in almost all voltage ranges and ratings. However, they are commonly used at

voltages below 115KV leaving the higher voltages for air blast and SF6 breakers. The contacts of an

oil breaker are submerged in insulating oil, which helps to cool and extinguish the arc that forms

when the contacts are opened. Oil circuit breakers are classified into two main types namely: bulk oil

circuit breakers and minimum oil circuit breakers.

The advantages of using oil as an arc quenching medium are:

1. It absorbs the arc energy to decompose the oil into gases, which have excellent cooling

properties.

2. It acts as an insulator and permits smaller clearance between live conductors and earthed

components.

The disadvantages of oil as an arc quenching medium are:

1. Its inflammable and there is risk of fire

2. It may form an explosive mixture with air.

3. The arcing products remain in the oil and it reduces the quality of oil after several

operations.

4. This necessitates periodic checking and replacement of oil.

19

Page 20: 220 Kv GSS Heerapura Report

6.1.4) BULK OIL CIRCUIT BREAKER:

Bulk oil circuit breakers are widely used in power systems from the lowest voltages up to 115KV.

However, they are still used in the systems having voltages up to 230KV. The contacts of bulk oil

breakers may be of the plain-break type, where the arc is freely interrupted in the oil, or enclose

within the arc controllers.

Plain-break circuit breakers consist mainly of a large volume of oil contained in a metallic tank. Arc

interruption depends on the head of oil above the contacts and the speed of contact separation. The

head of oil above the arc should be sufficient to cool the gases, mainly hydrogen, produced by oil

decomposition. A small air cushion at the top of the oil together with the produced gases will increase

the pressure with a subsequent decrease of the arcing time.

6.1.5) MINIMUM OIL CIRCUIT BREAKER:

Bulk oil circuit breakers have the disadvantage of using large quantity of oil. With frequent breaking and

making heavy currents the oil will deteriorate and may lead to circuit breaker failure. This has led to the

design of minimum oil circuit breakers working on the same principles of arc control as those used in

bulk oil breakers. In this type of breakers the interrupter chamber is separated from the other parts and

arcing is confined to a small volume of oil. The lower chamber contains the operating mechanism and the

upper one contains the moving and fixed contacts together with the control device. Both chambers are

made of an insulating material such as porcelain. The oil in both chambers is completely separated from

each other. By this arrangement the amount of oil needed for arc interruption and the clearances to earth

are roused. However, conditioning or changing the oil in the interrupter chamber is more frequent than in

the bulk oil breakers. This is due to carbonization and slugging from arcs interrupted chamber is

equipped with a discharge vent and silica gel breather to permit a small gas cushion on top of the oil.

Single break minimum oil breakers are available in the voltage range 13.8 to 34.5 KV.

20

Page 21: 220 Kv GSS Heerapura Report

CHAPTER 7

PROTECTIVE RELAYS

Relays must be able to evaluate a wide variety of parameters to establish that corrective action is

required. Obviously, a relay cannot prevent the fault. Its primary purpose is to detect the fault and

take the necessary action to minimize the damage to the equipment or to the system. The most

common parameters which reflect the presence of a fault are the voltages and currents at the

terminals of the protected apparatus or at the appropriate zone boundaries. The fundamental problem

in power system protection is to define the quantities that can differentiate between normal and

abnormal conditions. This problem is compounded by the fact that “normal” in the present sense

means outside the zone of protection. This aspect, which is of the greatest significance in designing a

secure relaying system, dominates the design of all protection systems.

Fig. 10-Relays

21

Page 22: 220 Kv GSS Heerapura Report

7.1) Distance Relays:

Distance relays respond to the voltage and current, i.e., the impedance, at the relay location.

The impedance per mile is fairly constant so these relays respond to the distance between the relay

location and the fault location. As the power systems become more complex and the fault current

varies with changes in generation and system configuration, directional over current relays become

difficult to apply and to set for all contingencies, whereas the distance relay setting is constant for a

wide variety of changes external to the protected line.

7.2) Types of Distance relay:-

7.2.1) Impedance Relay:

The impedance relay has a circular characteristic centred. It is non directional and is used

primarily as a fault detector.

7.2.2) Admittance Relay:

The admittance relay is the most commonly used distance relay. It is the tripping relay in pilot

schemes and as the backup relay in step distance schemes. In the electromechanical design it

is circular, and in the solid state design, it can be shaped to correspond to the transmission line

impedance.

7.2.3) Reactance Relay:

The reactance relay is a straight-line characteristic that responds only to the reactance of the

protected line. It is non directional and is used to supplement the admittance relay as a

tripping relay to make the overall protection independent of resistance. It is particularly useful

on short lines where the fault arc resistance is the same order of magnitude as the line length.

22

Page 23: 220 Kv GSS Heerapura Report

CHAPTER 8

POWER TRANSFORMER

8.1) Windings:

Winding shall be of electrolytic grade copper free from scales & burrs. Windings shall be made in

dust proof and conditioned atmosphere. Coils shall be insulated that impulse and power frequency

voltage stresses are minimum. Coils assembly shall be suitably supported between adjacent sections

by insulating spacers and barriers. Bracing and other insulation used in assembly of the winding shall

be arranged to ensure a free circulation of the oil and to reduce the hot spot of the winding. All

windings of the transformers having voltage less than 66 kV shall be fully insulated. Tapping shall be

so arranged as to preserve the magnetic balance of the transformer at all voltage ratio. All leads from

the windings to the terminal board and bushing shall be rigidly supported to prevent injury from

vibration short circuit stresses.

Fig. 11-Power Transformer

23

Page 24: 220 Kv GSS Heerapura Report

8.2) Tanks and fittings:

Tank shall be of welded construction & fabricated from tested quality low carbon steel of adequate

thickness. After completion of welding, all joints shall be subjected to dye penetration testing.

At least two adequately sized inspection openings one at each end of the tank shall be provided for

easy access to bushing & earth connections. Turrets & other parts surrounding the conductor of

individual phase shall be non-magnetic. The main tank body including tap changing compartment,

radiators shall be capable of withstanding full vacuum.

8.3) Cooling Equipments:

Cooling equipment shall conform to the requirement stipulated below:

(a.) Each radiator bank shall have its own cooling fans, shut off valves at the top and bottom (80mm

size) lifting lugs, top and bottom oil filling valves, air release plug at the top, a drain and sampling

valve and thermometer pocket fitted with captive screw cap on the inlet and outlet.

(b.) Cooling fans shall not be directly mounted on radiator bank which may cause undue vibration.

These shall be located so as to prevent ingress of rain water. Each fan shall be suitably protected by

galvanized wire guard.

Fig. 12-Radiator with fan

24

Page 25: 220 Kv GSS Heerapura Report

8.4) Transformer Accessories:

8.4.1) Buchholz Relay:

This has two Floats, one of them with surge catching baffle and gas collecting space at top.

This is mounted in the connecting pipe line between conservator and main tank. This is the

most dependable protection for a given transformer.

Gas evolution at a slow rate that is associated with minor faults inside the transformers gives

rise to the operation or top float whose contacts are wired for alarm. There is a glass window

with marking to read the volume of gas collected in the relay. Any major fault in transformer

creates a surge and the surge element in the relay trips the transformer. Size of the relay varies

with oil volume in the transformer and the mounting angle also is specified for proper

operation of the relay.

Fig. 13-Buchholz Relay

8.4.2) Temperature Indicators:

Most of the transformer (small transformers have only OTI) are provided with indicators that

displace oil temperature and winding temperature. There are thermometers pockets provided in

the tank top cover which hold the sensing bulls in them. Oil temperature measured is that of the

top oil, where as the winding temperature measurement is indirect.

25

Page 26: 220 Kv GSS Heerapura Report

This is done by adding the temperature rise due to the heat produced in a heater coil (known as

image coil) when a current proportional to that flowing in windings is passed in it to that or top

oil. For proper functioning or OTI & WTI it is essential to keep the thermometers pocket clean

and filled with oil.

Fig. 14-Winding and oil temperature indicator

8.4.3) Silica Gel Breather:

Both transformer oil and cellulosic paper are highly hygroscopic. Paper being more

hygroscopic than the mineral oil The moisture, if not excluded from the oil surface in

conservator, thus will find its way finally into the paper insulation and causes reduction

insulation strength of transformer. To minimize this conservator is allowed to breathe only

through the silica gel column, which absorbs the moisture in air before it enters the

conservator air surface.

Fig. 15-Silica gel Breather

26

Page 27: 220 Kv GSS Heerapura Report

8.4.4) Conservator:

With the variation of temperature there is corresponding variation in the oil volume. To

account for this, an expansion vessel called conservator is added to the transformer with a

connecting pipe to the main tank. In smaller transformers this vessel is open to atmosphere

through dehydrating breathers (to keep the air dry). In larger transformers, an air bag is

mounted inside the conservator with the inside of bag open to atmosphere through the

breathers and the outside surface of the bag in contact with the oil surface.

Fig. 16-Conservator with Buchholz relay and tank [ref.-6]

Total No. of transformers = 6 No. of transformers

220/132 KV------------------------------------ 100MVA 2

132/33 KV--------------------------------------20/25MVA 2

132/33KV---------------------------------------40/50MVA 1

132/11 KV---------------------------------------10/12.5 MVA 1

27

Page 28: 220 Kv GSS Heerapura Report

CHAPTER 9

CURRENT TRANSFORMER

As you all know this is the device which provides the pre-decoded fraction of the primary current

passing through the line/bus main circuit. Such as primary current 60A, 75A, 150A, 240A, 300A,

400A, to the secondary output of 1A to 5A.

Now a day mostly separate current transformer units are used instead of bushing mounting CT’s on

leveled structure they should be for oil level indication and base should be earthed properly. Care

should be taken so that there should be no strain as the terminals.

When connecting the jumpers, mostly secondary connections is taken to three unction boxes where

star delta formation is connected for three phase and final leads taken to protection /metering scheme.

There should be no chance of secondary circuit remaining opens as it leads to extremely high voltage

which ultimately damages the CT itself

Fig. 17-Current Transformers

It can be used to supply information for measuring power flows and the electrical inputs for the

operation of protective relays associated with the transmission and distribution circuit or for power

transformer. These current transformers have the primary winding connected in series with the

28

Page 29: 220 Kv GSS Heerapura Report

conductor carrying the current to be measured or controlled. The secondary winding is thus insulated

from the high voltage and can then be connected to low voltage metering circuits.

Current transformers are also used for street lighting circuits. Street lighting requires a constant

current to prevent flickering lights and a current transformer is used to provide that constant current.

In this case the current transformer utilizes a moving secondary coil to vary the output so that a

constant current is obtained.

29

Page 30: 220 Kv GSS Heerapura Report

CHAPTER 10

POTENTIAL TRANSFORMER

A potential transformer (PT) is used to transform the high voltage of a power line to a lower value,

which is in the range of an ac voltmeter or the potential coil of an ac voltmeter.

Fig.18-Potential Transformer

The voltage transformers are classified as under:

Capacitive voltage transformer or capacitive type

Electromagnetic type.

Capacitive voltage transformer is being used more and more for voltage measurement in high voltage

transmission network, particularly for systems voltage of 132KV and above where it becomes

increasingly more economical. It enables measurement of the line to earth voltage to be made with

simultaneous provision for carrier frequency coupling, which has reached wide application in modern

high voltage network for tele-metering remote control and telephone communication purpose.

The capacitance type voltage transformers are of twp type:

Coupling Capacitor type

Pushing Type

30

Page 31: 220 Kv GSS Heerapura Report

The performance of CVT is affected by the supply frequency switching transient and magnitude of

connected Burdon. The CVT is more economical than an electromagnetic voltage transformer when

the nominal supply voltage increases above 66KV.

The carrier current equipment can be connected via the capacitor of the CVT. There by there is no

need of separate coupling capacitor. The capacitor connected in series act like potential dividers,

provided, the current taken by burden is negligible compared with current passing through the series

connected capacitor.

CVT as coupling capacitor for carrier current application:

The carrier current equipments is connected to the power line via coupling capacitor. The coupling

CVT combines the function of coupling and voltage transformer.

31

Page 32: 220 Kv GSS Heerapura Report

CHAPTER 11

CAPACITIVE VOLTAGE TRANSFORMER

A capacitor voltage transformer (CVT) is a transformer used in power systems to step-down extra

high voltage signals and provide low voltage signals either for measurement or to operate a protective

relay. In its most basic form the device consists of three parts: two capacitors across which the

voltage signal is split, an inductive element used to tune the device to the supply frequency and a

transformer used to isolate and further step-down the voltage for the instrumentation or protective

relay. The device has at least four terminals, a high-voltage terminal for connection to the high

voltage signal, a ground terminal and at least one set of secondary terminals for connection to the

instrumentation or protective relay. CVTs are typically single-phase devices used for measuring

voltages in excess of one hundred kilovolts where the use of voltage transformers would be

uneconomical. In practice the first capacitor, C1, is often replaced by a stack of capacitors connected

in series. This results in a large voltage drop across the stack of capacitors that replaced the first

capacitor and a comparatively small voltage drop across the second capacitor, C2, and hence the

secondary terminals.

The porcelain in multi unit stack, all the potentials points are electrically tied and suitably shielded to

overcome the effect of corona RIV etc. Capacitive voltage transformers are available for system

voltage.

CHAPTER 1232

Page 33: 220 Kv GSS Heerapura Report

CONTROL ROOM

Control panel contain meters, control switches and recorders located in the control building, also

called the dog house. These are used to control the substation equipment to send power from one

circuit to another or to open or to shut down circuits when needed.

Fig.19-Control Room in GSS Heerapura

12.1) MEASURING INSTRUMENT USED:

33

Page 34: 220 Kv GSS Heerapura Report

12.1.1) ENERGY METER: To measure the energy transmitted energy meters are fitted to the

panel to different feeders the energy transmitted is recorded after one hour regularly for it

MWHr, meter is provided.

12.1.2) WATTMETERS: It is attached to each feeder to record the power exported from GSS.

12.1.3) FREQUENCY METER: To measure the frequency at each feeder there is the provision of

analog or digital frequency meter.

12.1.4) VOLTMETER: It is provided to measure the phase to phase voltage .It is also available in

both the analog and digital frequency meter.

12.1.5) AMETER: It is provided to measure the line current. It is also available in both the forms

analog as well as digital.

12.1.6) MAXIMUM DEMAND INDICATOR: There are also mounted the control panel to record

the average power over successive predetermined period.

12.1.7) MVAR METER: It is to measure the reactive power of the circuit.

CHAPTER 1334

Page 35: 220 Kv GSS Heerapura Report

CAPACITOR BANK

The capacitor bank provides reactive power at grid substation. The voltage regulation problem

frequently reduces so of circulation of reactive power.

Unlike the active power, reactive power can be produced, transmitted and absorbed of course with in

the certain limit, which have always to be workout. At any point in the system shunt capacitor are

commonly used in all voltage and in all size.

Fig. 20-Capacitor Bank

Benefits of using the capacitor bank are many and the reason is that capacitor reduces the reactive

current flowing in the whole system from generator to the point of installation.

1 .Increased voltage level at the load

2. Reduced system losses

3. Increase power factor of loading current

CHAPTER 1435

Page 36: 220 Kv GSS Heerapura Report

POWER LINE CARRIER COMMUNICATION

As electronics plays a vital role in the industrial growth, communication is also a backbone of any

power stations. Communication between various generating and receiving station is very essential for

proper operation of power of power system. This is more in case of large interconnected system

where a control leads dispatch station has to co-ordinate the working of various unit to see that the

system is maintained in the optimum working condition, power line communication is most

economic and reliable method of communication for medium and long distance in power network.

14.1) Wave Trap:

Line trap also is known as Wave trap. What it does is trapping the high frequency

communication signals sent on the line from the remote substation and diverting them to the

telecom/teleprotection panel in the substation control room (through coupling capacitor and

LMU).

Fig. 21-Wave Trap

This is relevant in Power Line Carrier Communication (PLCC) systems for communication among

various substations without dependence on the telecom company network. The signals are primarily

teleprotection signals and in addition, voice and data communication signals.

36

Page 37: 220 Kv GSS Heerapura Report

The Line trap OFFERS HIGH IMPEDANCE TO THE HIGH FREQUENCY COMMUNICATION SIGNALS thus

obstructs the flow of these signals in to the substation bus bars. If there were not to be there, then

signal loss is more and communication will be ineffective/probably impossible.

CHAPTER 15

EARTHING OF THE SYSTEM

The provision of an earthing system for an electric system is necessary by the following reason.

37

Page 38: 220 Kv GSS Heerapura Report

In the event of over voltage on the system due to lightening discharge or other system fault.

These parts of equipment, which are normally dead, as for as voltage, are concerned do not

attain dangerously high potential.

In a three phase, circuit the neutral of the system is earthed in order to stabilize the potential

of circuit with respect to earth.

The resistance of earthing system is depending on:

Shape and material of earth electrode used.

Depth in the soil.

Specific resistance of soil surrounding in the neighbourhood of system electrodes.

15.1) PROCEDURE OF EARTHING:

Technical consideration the current carrying path should have enough capacity to deal with more

faults current. The resistance of earth and current path should be low enough to prevent voltage rise

between earth and neutral. The earth electrode must be driven in to the ground to a sufficient depth to

as to obtain lower value of earth resistance. To sufficient lowered earth resistance a number of

electrodes are inserted in the earth to a depth, they are connected together to form a mesh. The

resistance of earth should be for the mesh in generally inserted in the earth at 0.5m depth the several

point of mesh then connected to earth electrode or ground conduction. The earth electrode is metal

plate copper is used for earth plate.

15.2) NEUTRAL EARTHING:

Neutral earthing of power transformer all power system operates with grounded neutral. Grounding

of neutral offers several advantages the neutral point of generator transformer is connected to earth

directly or through a reactance in some cases the neutral point is earthed through an adjustable reactor

of reactance matched with the line.

The earth fault protection is based on the method of neutral earthing.

The neutral earthing is associated switchgear.

The neutral earthing is provided for the purpose of protection arcing grounds unbalanced

voltages with respect to protection from lightening and for improvement of the system.

38

Page 39: 220 Kv GSS Heerapura Report

CHAPTER 16

BATTERY ROOM

39

Page 40: 220 Kv GSS Heerapura Report

In a GSS, separate dc supply is maintained for signalling remote position control, alarm circuit etc.

Direct current can be obtained from 220volt 3 phase ac supply via rectifier and in event of ac failure,

from the fixed batteries, which are kept, charged in normal condition by rectifier supply.

Fig. 22-Battery Room

Battery System:

The batteries used are lead acid type having a solution of sulphuric acid and distilled water as

electrolytes. In charged state, it has a specific gravity of 1.2 at temperature of 30C.In the battery room

batteries are mounted on wooden stand. The cells are installed stand by porcelain.

Following precautions are taken in a battery room:

The conductor connecting the cells are greased and coated with electrolyte resisting varnish.

Proper care is taken so that acid vapours do not accumulate in the room to avoid risk of

explosion, smoking, winding etc.

The windows of battery are of forested glass to avoid the batteries from direct action of sun

light.

CHAPTER 17

RATINGS

40

Page 41: 220 Kv GSS Heerapura Report

17.1) TRANSFORMER:

Total No. of transformers = 6 No. of transformers

220/132 KV------------------------------------ 100MVA 2

132/33 KV--------------------------------------20/25MVA 2

132/33KV---------------------------------------40/50MVA 1

132/11 KV---------------------------------------10/12.5 MVA 1

MAKE Company

220/133 KV, 100MVA X-Mer 1----------------------------------- TELK

220/133KV, 100 MVA X-Mer 2---------------------------------- ALSTOM

132/33 KV, 20/25 MVA X-Mer 1---------------------------------- TELK

132/33 KV, 20/25 MVA X-Mer 2-----------------------------------BBL

132/33 KV, 40/50 MVA X-Mer 3-----------------------------------T&R

132/33 KV, 10/12.5 MVA X-Mer 1---------------------------------EMCO

17.2) CIRCUIT BREAKER:

No. of 220KV breaker - 6

No. of 132KV breaker - 13

No. of 33KV breaker - 12

No. of Capacitor Bank (33kv)- 4

No. of 11KV breaker - 7

SF6 CB

BREAKER SERIAL NO. 030228

RATED VOLTAGE 145KV

NORMAL CURRENT 1250A

41

Page 42: 220 Kv GSS Heerapura Report

FREQUENCY 5OHz

LIGHTNING IMPULSE WITHSTAND 650KV (Peak)

FIRST POLE TO CLEAR TO CLEAR FACTOR 1-2

SHORT TIME WITHSTAND CURRENT 31.5KA

DURATION OF SHORT CIRCUIT 3 Sec.

(SHORT CIRCUIT SYM. 31.5KA

BREAKING CURRENT) ASYM. 37.5KA

SHORT TIME MAKING CURRENT 8.0KA

OUT OF PHASE BREAKING CURRENT 7.9KA

OPERATING SEQUENCE 0-0.3-CO-3min-CO

SF6 GAS PRESSURE AT 20C 6.3 Bar

TOTAL MASS OF CB 1300Kg

MASS OF SF6 GAS 8.7Kg

17.3) BATTERY CHARGER:

Battery Charger – 220AH VDC HBL NIFE LTD.

440AH VDC HBL NIFE LTD.

Capacitor BankNo.-1 BHEL 38KV 6.6MVAR

Capacitor BankNo.-2 BHEL 38KV 7.2MVAR

Capacitor BankNo.-1 ABB 38KV 7.2MVAR

Capacitor BankNo.-1 WS 38KV 7.2MVAR

17.4) CURRENT TRANSFORMER:

FREQUENCY 50Hz

HIGHEST SYSTEM VOLTAGE 245KV

SHORT TIME CURRENT 40KA/15

RATED CURRENT 600A

CURRENT RATIO 600-300-150/1

MIN. KNEE POTENTIAL VOLTAGE 850V at 150/1

MAX. EXCITING CURRENT 100MA at 150/1

MAX. SEC. WINDING RESISTANCE 2.5OHM at 150/1

42

Page 43: 220 Kv GSS Heerapura Report

17.5) CAPACITIVE VOLTAGE TRANSFORMER:

SERIAL NO. 0173537

INSULATION LEVEL 460KV

RATED VOLTAGE FACTOR 1.2/cont

TIME 1.5/30sec.

HIGHEST SYSTEM VOLTAGE 245KV

PRIMARY VOLTAGE 22OKV/1.732

TYPE OUTDOOR Wgt. 850Kg

PHASE SINGLE TBONP.CAT 50C

SECONDARY VOLTAGE 110/1.732 110/1.732

RATED BURDON 220Va 110Va

FREQUENCY 49.5-50.5Hz

CONCLUSION

43

Page 44: 220 Kv GSS Heerapura Report

Training at 220KV GSS IG Nagar, Jagatpura, Jaipur gives the insight of the real instruments used.

There are many instruments like transformer, CT, PT, CVT, LA, relay, PLCC, bus bars, capacitor

bank, insulator, isolators, control room, Battery room etc.

What is the various problem seen in substation while handling this instruments.

There are various occasion when relay operate and circuit breaker open, load shedding, shut down,

which has been heard previously.

To get insight of the substation, how things operate, how things manage all is learned there. Practical

training as a whole proved to be extremely informative and experience building and the things learnt

at it would definitely help a lot in snapping the future ahead a better way.

BIBILIOGRAPHY

1. B.R.GUPTA (2005), “POWER SYSTEM ANALYSIS AND DESIGN”

44

Page 45: 220 Kv GSS Heerapura Report

P122, P123, S.Chand & Company Ltd.

2. ASHFAQ HUSSAIN (2005), “ELECTRICAL POWER SYSTEM” P79, P501, P516,

CBS publisher and distributors.

3. V.K.MEHTA (2002), “POWER SYSTEM” P447, P483, P507, P527, P555,

S.chand & company Ltd.

4. http://upload.wikimedia.org/wikipedia/en/6/63/cvt.png

5. http://images.google.co.in/(Equipment’s name)

6. www.browzen.com/relay

7. Manual of G.S.S.

45