2204development of a wide area measurement system for smart grid applications m. m. amin, student...
DESCRIPTION
Development of a Wide Area Measurement System for Smart Grid ApplicationsTRANSCRIPT
Development of a Wide Area Measurement System for Smart Grid Applications
M. M. Amin, Student Member, IEEE, H. B. Moussa, Student Member, IEEE
and O. A. Mohammed, Fellow, IEEE
Energy Systems Research Laboratory, Electrical & Computer Engineering Department, Florida international university,
Miami, FL 33174, USA (Tel: +1 305-348-3040; e-mail: mohammed@ fiu.edu).
Abstract:
In this paper, the modeling for a complete scenario of a proposed wide area measurement system (WAMS)
based on synchronized phasor measurement units (PMUs) technology with the access of a broadband
communication capability is presented. The purpose is to increase the overall system efficiency and
reliability for all power stages via significant dependence on WAMS as distributed intelligence agents with
improved monitoring, protection, and control capabilities of power networks. The developed system is
simulated using the Matlab/Simulink program. The power system layer consists of a 50 kW generation
station, 20 kW wind turbine, three transformers, four circuit breakers, four buses, two short transmission
lines, and two 30 kW loads. The communication layer consists of three PMUs, located at generation and
load buses, and one phasor data concentrator (PDC), that will collect the data received from remote PMUs
and send it to the control center for analysis and control actions. The proposed system is tested under two
possible cases; normal operation and fault state. It was found that power system status can be easily
monitored and controlled in real time by using the measured bus values online which improves the overall
system reliability and avoids cascaded blackout during fault occurrence. The simulation results confirm the
validity of the proposed WAMS technology for smart grid applications.
1. INTRODUCTION
WAMS became one of the most recent technologies that are
popular for upgrading the traditional electric grid. This
upgrade has become a necessity to modernize the electricity
delivery system following the occurrence of major blackouts
in power systems around the world. Although many
algorithms have been developed in the past for online
monitoring of transmission systems, distribution systems and
estimation of operating frequency, with a few examples
included as references (A. A. Girgis 1982, M. S. Sachdev
1985 and S. Paul et al. 1987), but still the required level of
details for online assessment is yet to be achieved. In early
1980s, synchronized phasor measurement units (PMUs) were
first introduced and since then have become the ultimate data
acquisition technology, which will be used in wide area
measurement systems with many applications that are
currently under development around the world (H. Hr. 2004).
Synchronized phasor measurements, or synchrophasors,
provide a method for comparing phase and sequence values
from anywhere on a power system which can be integrated
with phasor data concentrators (PDCs) at substations in a
hierarchical structure (A. R. Metke 2010 and M. Pipat. 2009).
The precise and accurate data that can be acquired from
PMUs in a WAMS built on the power system confirms the
need for a robust, reliable communication network with
secure and high speed capabilities for online data access.
As smart grid applications, utility power grid analysts can get
benefited from WAMS in validation of system models and
components which has been one of the first uses of
synchrophasors. This validation occurs through use of inter-
area communication or simultaneous data collection of
conditions at a single point in time (Z. Zhong 2005).
In addition, Real-Time System Monitoring (RTSM) for
stability assessment and state measurement is another
application where phasor measurements at nodes help system
operators to gain a dynamic view of the power system and
initiate the necessary measures in proper time, with the latest
IEEE standard (C37.118-2005) developed to standardize data
transmission format and sampling rates of PMUs. This can
significantly be supported by the stability assessment
algorithms, which are designed to take advantage of the
phasor measurement information (M. Venk. 2009).
In the past, post-event analysis was an application of
synchrophasors (PMUs) without wide-area communication
where data was archived locally. However, it was not a useful
tool for online (dynamic) control. Recently, Real-Time
Control (RTC) of WAMS became a powerful control and
analysis tool that provides a new view of power systems (J.
De La Ree 2010). This is achieved by improving
communication network capabilities while maintain PMUs as
a main component in the network. The use of PMUs for RTC
will increase the control accuracy since data are measured
online. Also, it will enhance the power system stability and
delivery automation capabilities after challenges of new data
communication requirements across the system are firstly
resolved (A. Bose 2010, Y. Zhang 2008 and A.G.Pha. 2007).
Depth of observability is another advantage for PMUs. It
means the ability of measuring bus voltage phasor directly or
calculating it using the PMU voltage and line current of the
Preprints of the 18th IFAC World CongressMilano (Italy) August 28 - September 2, 2011
Copyright by theInternational Federation of Automatic Control (IFAC)
1672
nearest connected bus. This is a cost effective part since it
reduces the number of data acquisition tools needed across
the network as measuring line currents can extend the voltage
measurements to buses where no PMU is installed. In Fig. 1,
a simple generalization of PMU block diagram is shown,
which serves as the basis of simulating such unit (R. F.2005).
This paper discusses a method to utilize this type of data
collection to check the health state of power system
networks. This is achieved through building WAMS
infrastructure communication network. The performance of
the overall proposed system is investigated through a Matlab
simulation of PMUs in a small scenario of a WAMS on a 4-
bus utility network with the associated communication
network. This paper is organized as follows. In section 1, an
introduction to the subject is presented. In Sections 2, 3
description and mathematical modeling of the system are
introduced. In Section 4, test results are presented and
discussed under different system conditions. Finally, Section
5 presents some conclusions.
2 . SYSTEM DESCRIPTION
The principle of a WAMS network based on synchrophasors
data with the aid of a broadband communication network is
described in this section. The system consists mainly of two
layers as shown in Fig. 2. First, the electrical power system
layer which consists of line-line 208V generation station with
50 kW output rated power, 208V wind turbine as a renewable
source of 20 kW rated power, 3-power transformers (T1, T2,
and T3) linking different parts of the electrical system, 2-
short transmission lines (T.L1, and T.L2), 4-buses (B1, B2,
B3, and B4), 4- circuit breakers (CB1, CB2, CB3, and CB4)
and 2-loads each of 30 kW (O. A. Mohammed 2005). Second,
the WAMS layer which consists of 3-PMUs, and 1-PDC that
will collect the data received from remote PMUs and send it
to the control center for analysis and control actions (Bei Xu
2005).
3. SYSTEM MODELING
A small size WAMS platform built on a 208V, 60 Hz test-
bed network was modeled as shown in Fig. 3. This proposed
communication network can be implemented in the lab by
locating one PMU at each generation or load bus where all
PMUs will send its measured voltage and current
measurements to the PDC in order to monitor the system
status and taking the proper control action if required.
Furthermore, depth of observability can be utilized here in
order to significantly reduce system costs through reducing
the number of PMUs since one can read voltage and current
measurements at its bus and other buses measurements
locating at same area can be calculated. However, this
algorithm has less accuracy than installing one PMU at each
bus. A simulation of the PMU units was done with using
sampling clock pulses to achieve synchronization between
synchrophasors which are phase locked to the signal provided
by the Global positioning system (GPS) receiver built inside
or outside the PMU. The GPS module is simulated as a clock
enabling pulses sent to all PMUs at the same time so that all
of them will have the same time tags and in accordance the
same reference wave can be used at all different PMU
locations through the WAMS.
Fig. 1. Block Diagram of PMU
Fig. 2. Schematic diagram of the proposed WAMS according
to the installed test-bed power system in the lab.
3.1 PMU network analysis
The PMU has to separate the fundamental frequency
component from other harmonics and find its phasor
representation. Discrete Fourier transform (DFT) is then
applied on the sampled input signal to compute its phasor.
Also, it has to compensate for the phase delay introduced to
the signal by the antialiasing filters present in the input to the
PMU. For x��k = 0,1, … , N� where N is the number of
samples taken over one period, then the phasor representation
will be given by;
= √2� � ��������
����
��� (1)
Since the components for real input signals at a frequency
appears in DFT and are complex conjugates of each other so
they can be combined giving the factor of 2 in front of the
summation in (1) and then the rms of the fundamental
frequency peak value can be obtained through dividing by
√2. Matlab Simulink model was built to evaluate the system
performance. Different cases were studied during normal
CB3
Control Station
B2
B3
T3
Rx
T1 T2
B4
Wind Turbine
B1
CB4 30 kW
Load
30 kW
Load
PMU1 PMU2
PMU3
T.L1
T.L2
Gen.
Station CB1 CB2
RPDC
S/H
A/D
PLL
Oscillator
Analog
Filter
Micro
Processor
GPS
Receiver Antenna
Analog
Input
Remote
Communication
Local
Communication
Preprints of the 18th IFAC World CongressMilano (Italy) August 28 - September 2, 2011
1673
Fig. 3. Simulink model for a scenario of the proposed PMUs communication network layer on a power system Smart Grid
Test-bed in our Laboratory.
mode of operation and fault occurrence mode. The simulated
system parameters are shown in Table 1.
In Steady State, all generators have the same frequency
( ��� Hz). In accordance, the voltage at all points of the power
system will have the same frequency ���which is measured
by PMU according to the following equation;
!"#$ = %!&'( "2) ���# + +!$ (2)
In case of frequency disturbance, the power system different
generators will run with different frequencies and each
generator may be considered as a voltage source with
different values of %! , ��� ,-. +! as slow time varying
functions. It can be assumed for a small interval of time
"∆t = n cycles$ that E8, f:: and δ8 constants. As a result, the
power system can be represented as a circuit with several
voltage sources of different frequencies. The actual voltage at
any bus i using superposition theorem becomes as in (3)
(Ning Jiaxin 2009);
>!?@A = >!,�"#$ + ⋯ + >!,�C"#$ = ∑ >!,�"#$�C��� =
∑ E!,�&'(F2)��C# + G!,�CH�C��� (3)
Where E!,� represents the voltage at bus i due to generator j.
which indicates that this bus have a multi frequency voltage
that are all close to 60 HZ. In dynamic power system studies
this can be estimated as in (4);
>!I�A"#$ = E!I�Acos "2)�!I�A# + G!I�A$ (4)
In equation (4), the frequency �!I�A represents the frequency
of the system at this location and equals to the frequency
measured by the PMU at that bus by assuming that >!I�A"#$ =>!?@A and having access to the sampled data of
>!?@A so �!I�Acan be easily evaluated (R. Malpani 2010).
3.2 Communication channel analysis
IEEE PC37.118 16 protocol format is usually used in PMUs
communication. This format standard includes frequency and
rate of change of frequency in each message. Once the
frequency and size of the messages are known, the following
equation can be used to determine the bit-per-second (bps)
rate at which the data can be sent (V.K. Sood 2009);
KL( = 1.2"-- . N . �$ (5) where:
nn = message size (bytes)
L = length of frame (1 start bit, 8 data bits, 2 stop bits, 1
parity = 12)
f = messages frequency
1.2 = factor to account for system delays (based on typical
experience)
The synchrophasor data can be sent at various rates,
depending on application requirements. The communications
link connecting the substations could be a fiber-optic
multiplexer. Relays communicate with the multiplexer via
EIA-232 asynchronous interface.
Enable
1To control center
Discrete,Ts = 5e-005 s.
powergui
[A]clk pulses
Wind TurbineInduction Generator
20 KW
v+ -
v+ -
v+ -
Vab3
Vab2
Vab1
A
B
C
a
b
c
Transformer 3
A
B
C
a
b
c
Transformer 2
A
B
C
a
b
c
Transformer 1
A B C
A B C
TL2
Va
Ia
Va-ph
Ia-ph
Rx
En
ab
le
C1
B1
A1 A B C
PMU3
En
ab
le
C1
B1
A1 A B C
PMU2
En
ab
le A B C
A1
B1
C1
PMU1
PDC
A
B
C
Main AC Grid50 KW
A B C
Load30 kW
[A]
From2
[A]
From1
[A]
From
A
B
C
A
B
C
Fault
Breaker
A
B
C
a
b
c
CB4
A B C
a b c
CB3
A
B
C
a
b
c
CB2
A
B
C
a
b
c
CB1
A
B
C
a
b
c
B4208 V
A
B
C
a
b
c
B3208 V
A
B
C
a
b
c
B2208 V
A
B
C
a
b
c
B1208 V
AC Load : 30 kW
A B C
1 Watt
ABC
ABC
TL1
Preprints of the 18th IFAC World CongressMilano (Italy) August 28 - September 2, 2011
1674
4. SIMULATION RESULTS
A Matlab Simulink model has been constructed in order to
investigate the performance of the proposed WAMS for
smart grid applications. The model was carried out according
to the operation that has been described in section 2. The
simulation parameters are shown in Table 1. In order to
estimate the PMUs characteristics, two types of tests are
carried out. The first is normal operation test without any
fault or unbalance in the network. The second is fault
operation test which used as an extreme condition to show
the behavior of the network under this condition.
Table 1. System simulation parameters
Symbol Parameter Value
vg, vt Generator and wind
turbine output voltage
208 Vrms
fg, ft Generator and wind
turbine frequency
60 Hz
R PMU message report
rate
60 msg/sec
Pg Generator power
rating
50 kW
Pg Wind turbine power
rating
20 kW
L Load rating 60 kW
4.1 Normal operation test
The electrical system under normal operation conditions is
observed. The 30 kW load on bus 2 is supplied from the wind
generator sharing with generation station and the other 30 kW
load on bus 3 supplied by the generation station, so all PMUs
shows stable readings within the references.
From Figs. 4-6, the three PMUs read accurate information
about line voltage >?O; a sampled data of about 296 V
average voltage amplitude starts from 0 sec for bus 1 and 2.
At bus 3, zero voltage amplitude for the first 0.1 sec at no
load then tracking the right average voltage amplitude level
as other buses with a phase difference of 2.65 degrees at
stable state for all readings. The exported data by the
simulated PMUs to the control center shows that the
developed WAMS succeeded to accurately reflect the system
status in real-time (online). However, for complete
verification of its performance another test with applying a
fault at bus 3 and observing their responses.
4.2 Fault operation test
In this case, a three line to ground short circuit (3-LG SC)
fault is applied at bus 3. Figs. 7-10 show the readings for all
PMUs at the 3-buses. According to Fig. 7, the whole system
shows normal operation for 0.2 sec while bus 3 is loaded
after 0.1 sec. the fault is occurred after 0.2 and it is cleared
after 0.05 sec. PMUs 1&2 reads larger phase differences
(7.54 degrees) than in normal mode (2.65 degrees) while the
voltage amplitude dropped with small value (10 V) which
means that the fault is not located on their buses area as
shown in Figs. 8, 9. On the other hand, PMU 3 has extremely
phase difference change (50 degrees) associated with a large
drop in the voltage amplitude as a result to the fault that
occurs in this area as shown in Fig. 10. Consequently, the
control center has to send control signal to the relay to release
the circuit breaker at that bus upon receiving these data in
real time from PMUs to protect the other generation stations
which are the most valuable part in the power network from
damage, preventing cascaded turnoff stations which may
result in major blackouts and maintaining a healthy power
system (S. H. Horowitz 2003). Furthermore, it helps analysts
to determine the type of fault that has been occurred using the
data transmitted from PMUs.
Fig. 4. PMU1 readings under normal operation condition.
Fig. 5. PMU2 readings under normal operation condition.
0 0.05 0.1 0.15 0.2 0.25 0.30
100
200
300
400Vab-S
am
ple
d0 0.05 0.1 0.15 0.2 0.25 0.3
-400
-200
0
200
400
Vab R
ef. &
Act.
PMU1PMU1PMU1PMU1
0 0.05 0.1 0.15 0.2 0.25 0.30
1
2
3
4
time sec
Phase A
ngle
Phase Diff. =2.65
0 0.05 0.1 0.15 0.2 0.25 0.30
100
200
300
400
Vab-S
am
ple
d
0 0.05 0.1 0.15 0.2 0.25 0.3-400
-200
0
200
400
Vab R
ef. &
Act.
PMU2
0 0.05 0.1 0.15 0.2 0.25 0.30
1
2
3
4
time sec
Phase A
ngle
Phase Diff. =2.65
Preprints of the 18th IFAC World CongressMilano (Italy) August 28 - September 2, 2011
1675
Fig. 6. PMU3 readings under normal operation condition.
Fig. 7. Line voltages of Buses 1, 2 and 3
Fig. 8. PMU1 readings during fault occurrence
Fig. 9. PMU2 readings during fault occurrence
0 0.05 0.1 0.15 0.2 0.25 0.30
100
200
300
400
Vab-S
am
ple
d
0 0.05 0.1 0.15 0.2 0.25 0.3-400
-200
0
200
400
Vab
Ref.
& A
ct.
PMU3
0 0.05 0.1 0.15 0.2 0.25 0.30
1
2
3
4
time sec
Ph
ase A
ngle
Phase Diff. =2.65
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35
-500
-300
-100
100
300
VL
ine-B
1
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35
-500
-300
-100
100
300
VL
ine-B
2
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35
-300
-100
100
300
time sec
VL
ine-B
3
0.18 0.2 0.22 0.24 0.26 0.28-400
-200
0
200
400
Va
b R
ef.
& A
ct.
PMU1
0.18 0.2 0.22 0.24 0.26 0.280
100
200
300
Va
b-A
mp
litu
de
0.18 0.2 0.22 0.24 0.26 0.280
1
2
3
4
time sec
Ph
as
e A
ng
le
Phase Diff.=7.54 degrees
0.18 0.2 0.22 0.24 0.26 0.28-400
-200
0
200
400
Vab
Ref.
& A
ct.
PMU2
0.18 0.2 0.22 0.24 0.26 0.280
100
200
300
Vab
-Am
plitu
de
0.18 0.2 0.22 0.24 0.26 0.280
1
2
3
4
time sec
Ph
ase A
ng
le
Phase Diff.=7.54 degrees
Normal
operation
with no
load at
B3
Normal
operation
with
connecting
load at B3
Fault
operation
Occurrence
at B3
Return to
normal
operation
with loading
at B3
Preprints of the 18th IFAC World CongressMilano (Italy) August 28 - September 2, 2011
1676
Fig. 10. PMU3 readings during fault occurrence
5. CONCLUSIONS
A performance analysis for a PMU based WAMS network
was presented. The developed system was tested under two
different possible conditions. The simulated PMUs shows
coincident data with the real values of a maximum phase
difference equal to 2.65 degrees and normal average
amplitude reading which shows the system stability. In this
case, no action has to be taken from the control center during
the dynamic system monitoring. On the other hand, during
the fault state the PMUs data shows that the system has
unstable part with about 50 degrees phase difference added to
a large drop in voltage amplitude in the area where the fault
was occurred which should be disconnected or cleared via
dynamic control signals before spreading to other parts
resulting in catastrophic failure in some parts of the power
system or blackouts. The developed simulated WAMS
network verified its effectiveness for smart grid applications.
REFERENCES
A. A. Girgis and F. M. Ham (1982). A NEW FFT-based
digital frequency relay for load shedding. IEEE Trans.
Power App. Syst., vol. PAS-101, pp.433–439.
A. Bose (2010). SMART transmission grid applications and
their supporting infrastructure. IEEE Transactions on
Smart Grid, vol. 1, Issue 1, pp. 11-19.
A. G. Phadke, D. Novosel, and S. H. Horowitz (2007). WIDE
area measurement applications in functionally integrated
power systems. In: the CIGRE B-5 Colloq., Spain.
A. R. Metke and R. L. Ekl (2010). SECURITY technology
for smart grid networks. IEEE Transactions on Smart
Grid, vol. 1, no. 1, pp. 99-107.
Bei Xu, Y. J. Yoon and A. Abur (2005). OPTIMAL
Placement and Utilization of Phasor Measurements for
State Estimation. In: Power Sys. Comp. Conf., Belgium.
Final Report on the August 14, 2003 Blackout in the United
States and Canada: Causes and Recommendations
(2004). U.S.–Canada Power System Outage Task Force.
H. Hrasnica, A. Haidine, and R. Lehnert (2004).
BROADBAND powerline communications networks:
Network Design.: Wiley Books, Germany.
IEEE Standard for Synchrophasors for Power Systems, IEEE
Standard C37.118-2005 (IEEE Std 1344-1995).
J. De La Ree, V. Centeno, J. S. Thorp, and A. G. Phadke,
(2010). SYNCHRONIZED phasor measurement
applications in power systems. IEEE Transactions on
Smart Grid, vol. 1, no. 1, pp. 20-27.
M. Pipattanasomporn, H. Feroze, and S. Rahman (2009).
MULTI-agent systems in a distributed smart grid: design
and implementation. In: IEEE PES 2009 Power Systems
Conference and Exposition (PSCE’09), Seattle, USA.
M. S. Sachdev and M. M. Giray (1985). A LEAST error
squares technique for determining power system
frequency. IEEE Trans. Power App. Syst., vol. PAS-104,
pp. 437–443.
M. Venkatasubramanian, X. Yue, G. Liu, M. Sherwood, and
Q. Zhang (2009). WIDE-area monitoring and control
algorithms for large power systems using
synchrophasors. In: the Power System Conf. Expos., WA.
Ning, Jiaxin; Gao, Wenzhong; Radman, Ghadir; Liu, Jane
(2009). THE application of the groebner basis technique
in power flow study. In: North American Power
Symposium (NAPS), vol., no., pp.1-7.
O. A. Mohammed, Z. Liu, and S. Liu (2005). PHYSICAL
machine models in integrated power system applications.
Middle East Power Systems Journal, vol. 2, pp. 37-41.
R. F. Nuqui and A. G. Phadke (2005). PHASOR
measurement placement techniques for complete and
incomplete observability. IEEE Trans, Power Del., vol.
20, no. 4, pp. 2381–2388.
R. Malpani, Z. Abbas, and K. S. Swarup (2010). HIGH
precision frequency estimation using internet-based
phasor measurement unit. IEEE Transactions On Power
Systems, vol. 25, no. 2, pp. 607-614.
S. H. Horowitz and A. G. Phadke (2003). BOOSTING
immunity to blackouts. IEEE Power Energy Mag., vol.
1, no. 5, pp. 47–53.
S. Paul et al. (1987). NOVEL frequency factor method for
power system frequency measurement and estimation of
load shedding. Proc. Inst. Elect. Eng., Gen., Transm.,
Distrib., vol. 134, no. 6, pp. 389–395.
V.K. Sood, D. Fischer, M. Eklund, and T. Brown (2009).
DEVELOPING a communication infrastructure for the
smart grid. In: Elect. Power & Energy Conf. (EPEC), pp.
1-7, Montreal.
Y. Zhang and A. Bose (2008). DESIGN of wide area
damping controllers for interarea oscillations. IEEE
Trans. Power Syst., vol. 23, no. 3, pp. 1136–1143.
Z. Zhong, C. Xu, B. Billian, L. Zhang, S. Tsai, R. Conners,
V. Centeno, and Y. Liu (2005). Power system frequency
monitoring network (FNET) implementation. IEEE
Trans. Power Syst., vol. 20, no. 4, pp. 1914–1921.
0.18 0.2 0.22 0.24 0.26 0.28-400
-200
0
200
400
Vab
Re
f. &
Act.
PMU3
0.18 0.2 0.22 0.24 0.26 0.280
100
200
300
Va
b-A
mp
litu
de
0.18 0.2 0.22 0.24 0.26 0.280
1
2
3
4
time sec
Ph
ase
An
gle
Phase Diff.=50 degrees
Preprints of the 18th IFAC World CongressMilano (Italy) August 28 - September 2, 2011
1677