242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
1 of 25
Tank Farm Plant Operating Procedure 242-A Evaporator
USQ # EV-18-1933-S Rev. 0
CHANGE HISTORY ( LAST 5 REV-MODS )
Rev-Mod Release Date Justification: Summary of Changes
J-65 12/13/2018 Operations request - Chiller off
in the winter.
Shaded out cells for Chiller rounds pages 3 & 4 and the last two
rows on page 10.
J-64 05/17/2018 Engineering request Updated Normal Range for PDI-K1-315 Ember Screen dP and
corrected the Basis.
J-63 04/05/2018 Operations request
Deleted the "C" from PDIC-K1-304A in page 7.
Deleted the "T" from PDIT-K2-358 in page 9.
Deleted the "C" from TIC-K2-451 in page 9.
J-62 02/01/2018 Engineering request Corrected typo in Basis range for PDI-K1-308 and PDI-K1-311.
Range is 0.1 - 2.5. Updated Records section.
J-61 12/21/2017 Operations request Page 6 removed the asterisk in table
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
2 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal
Range Limit D N D N D N D N D N D N D N
PI-SW-1
(Sanitary Water Pressure) 80 - 115 psig 120 psig
PI-SW-2
(Sanitary Water Pressure) 60 - 100 psig 110 psig
PI-SW-6
(Sanitary Water Pressure) 60 - 100 psig 110 psig
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
3 of 25
Starting Date:
Parameter Normal Range Limit Monday Tuesday Wednesday Thursday Friday Saturday Sunday
D N D N D N D N D N D N D N
242-A CHILLER CH-CHW-1
P-CHW-001, Chilled
Water Pump ON - OFF ON - OFF
P-CHW-002, Chilled
Water Pump ON - OFF ON - OFF
HS-CHW-P-1, Chilled
Water Pump Selector
Switch
HS-1 HAND/OFF
/AUTO
PI-CHW-325
Inlet for glycol pump #1 1 3 – 15 psig
PI-CHW-326
Outlet for glycol pump #1 1 20-45 psig
PI-CHW-327
Inlet for glycol pump #2 1 3 -15 psig
PI-CHW-328
Outlet for glycol pump #2 1 20-45 psig
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page. 1 Gauges are read locally on the chiller pad.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
4 of 25
Starting Date:
Parameter Normal Range Limit Monday Tuesday Wednesday Thursday Friday Saturday Sunday
D N D N D N D N D N D N D N
242-A CHILLER CH-CHW-1 (Cont.)
Evap Entering Water
Temp 2 40 – 60 °F
Evap Leaving Water
Temp 2 40 – 50 °F
Alarm light flashing 3 Y/N
Chiller Pad free of
debris () If condition is met
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
2Evap Entering Water Temp and Evap Leaving Water Temp are read on the chiller local display control panel. To access reading press “Custom Report” button then “Next” button till readings
appear.
3Alarm indicating light is found on the front of the chiller local display control panel. If alarm light is found to be flashing notify Shift Manager and reference the Installation, Operation, and
Maintenance manual RTAA-SVX01A-EN pages 127 thru 134 diagnostic descriptions to determine cause of alarm.
4If the HVAC Chiller Water Cooling System needs to be shut down, Press the “STOP” button on the chiller local display control panel. Press “STOP” button once for controlled shutdown
(called turn down cycle, compressors and pumps may continue to run up to several minutes to clear the systems). OR Press “STOP” button twice for immediate shut down.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
5 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Basis D N D N D N D N D N D N D N
ESR - IF any designated K1 Ventilation parameter in the shaded blocks exceed their normal range, IMMEDIATELY NOTIFY supervision.
A TRAIN FILTER BANK DPs
PDI-K1-306, K1-15-3
Pre-Filter dP < 1.3 in WG
RPP-114131
1.5 in. WG*
PDI-K1-307, K1-6-3,
1st HEPA Filter dP 0.3 to 3.8 in WG
RPP-114131
0.1-4.0 in WG*
PDI-K1-308, K1-6-6
2nd HEPA Filter dP 0.3 to 2.3 in WG
RPP-114131
0.1-2.5 in WG*
B TRAIN FILTER BANK DPs
PDI-K1-309, K1-15-2
Pre-Filter dP < 1.3 in WG
RPP-114131
1.5 in. WG*
PDI-K1-310, K1-6-2
1st HEPA Filter dP 0.3 to 3.8 in WG
RPP-114131
0.1-4.0 in WG*
PDI-K1-311, K1-6-5
2nd HEPA Filter dP 0.3 to 2.3 in WG
RPP-114131
0.1-2.5 in WG*
ENDNOTE: RPP-114131, 4.1 Differential Pressure Limits.
*Out of Spec readings require immediate 242-A Shift Manager notification.
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
6 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Basis D N D N D N D N D N D N D N
ESR - IF any designated K1 Ventilation parameter in the shaded blocks exceed their normal range, IMMEDIATELY NOTIFY supervision.
C TRAIN FILTER BANK DPs
PDI-K1-312, K1-15-1
Pre-Filter dP < 1.3 in WG
RPP-114131
1.5 in WG
PDI-K1-313, K1-6-1,
1st HEPA Filter dP 0.3 to 3.8 in WG
RPP-114131
0.1-4.0 in WG
PDI-K1-314, K1-6-4
2nd HEPA Filter dP 0.3 to 2.3 in WG
RPP-114131
0.1-2.5 in WG
PDI-K1-315 Ember
Screen dP 1.0 to 2.5 in WG (ES)
ENDNOTE: RPP-114131, 4.1 Differential Pressure Limits.
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
7 of 25
Starting Date:
Parameter Normal
Range Basis
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
D N D N D N D N D N D N D N
242-A HVAC HMI CONTROL ROOM (K1 SYSTEM)
TI-K1-401, K1 Inlet Temp 0 to 100 F
PDI-K1-301, K1-7- 1 Roll
Filter Delta Pressure
0.05 to 1.0 in
WG
1.0
in WG
PDI-K1-302, K1-11-1 Bag
Filter Delta Pressure 0.1 to 1.5 in WG
1. 5
in WG
FIC-K1-201, K1-5-1 Supply
Fan Flow > 15,000 cfm
TIC-K1-403, HTR-K1-4-2A
Outlet Temp 60 to 100 F
TIC-K1-405, Cooling Coil
K1-3-1 Out let Temp 50 to 140 F
PDIC-K1-303,
Room C Pressure
-0.49 to -0.12 in
WG
TIC-K1-4-1, Condenser Room
5th Floor Temp 40 to 100 F
TIC-K1-407, Loading Room
Temp 40 to 100 F
TI-K1-11, Pump Room Temp 40 to 100 F
PDI- K1-304A, Room B
Pressure High Range
-0.21 to -4.0 in
WG
SPECIAL INSTRUCTIONS: *Out of Spec readings require immediate 242-A Shift Manager notification.
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
8 of 25
Starting Date:
Parameter Normal Range Basis Monday Tuesday Wednesday Thursday Friday Saturday Sunday
D N D N D N D N D N D N D N
242-A HVAC HMI CONTROL ROOM (K1 SYSTEM) (Cont.)
PDIC- K1-304, Room B
Pressure
-0.49 to -0.12 in
WG & more
negative than
PDIC-K1-303
PDI-K1-305, Room A
Pressure
-0.49 to -0.12 in
WG & more
negative than
PDIC-K1-303
TI-K1-12A-1, Evap Room
Upper Temp 40 to 100 F <150 F*
TI-K1-12B-1, Evap Room
Lower Temp 40 to 100 F <150 F*
UIC-K1-1 Mode PDIC, PDIC/FIC,
FIC
K1-5-3, Electric Exhaust Fan
(Status) ON-OFF
K1-5-2, Electric Exhaust Fan
(Status) ON-OFF
K1-5-1, K1 Supply Fan
(Status) ON-OFF
FIC-K1-1, Exhaust Flow > 15,500 cfm
SPECIAL INSTRUCTIONS: *Out of Spec readings require immediate 242-A Shift Manager notification.
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
9 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Basis D N D N D N D N D N D N D N
242-A HVAC HMI CONTROL ROOM (K2 SYSTEM)
PDIC-K2-351, Room 7 Pressure 0 to 0.2 in WG
FIC-K2-251, K2-5-1 Supply Fan Flow < 13,000 cfm
TIC-K2-455, Supply Temp After Preheat Coil 50 to 100 F
PDI-K2-359, K2-1-1 Bag Filters Delta Pressure 0.1 to 2.0 in WG
PDI-K2-358, K2-7-1 Roll filter Delta Pressure 0.05 to 1.0 in WG
TI-K2-451, Outside Air Temperature 0 to 100 F
TIC-K2-454, HTR-K2-4-1 Outlet Temp. 50 to 100 F
PDIC-K2-354, Room E Pressure 0.15 to 0.25 in WG
TIC-K2-456, Lunch Room Temp 65 to 75 F
TIC-K2-460, Survey Room Temp 65 to 75 F
TIC-K2-457, Women’s RR Temp 65 to 75 F
TIC-K2-458 Men’s RR Temp 65 to 75 F
TIC-K2-459, HPT Office Temp 65 to 75 F
SPECIAL INSTRUCTIONS: *Out of Spec readings require immediate 242-A Shift Manager notification
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
10 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Limit D N D N D N D N D N D N D N
242-A HVAC HMI CONTROL ROOM
K2-5-1, K2 Supply Fan Status ON or OFF ON - OFF
K2-5-3, K2 Exhaust Fan Status ON or OFF ON - OFF
HS-CHW-1, Chiller
CH-CHW-1 Status ENABLE – STOP E, S
TIC-CHW-1, Chiller Water
Return Temp 42 to 50 °F
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
11 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Basis D N D N D N D N D N D N D N
242-A HVAC ROOM
**PDIT-K1-301
Filter K1-7-1 Diff. Pressure 0.1 to 2.0 in WG
**PDIT-K1-302
Filter K1-11-1 Diff. Pressure 0.1 to 1.0 in WG
**PDIT-K1-303
Condenser Room Pressure -0.49 to -0.12 in WG
**PDIT-K1-304/PDSL-K1-304
Pump Room Diff. Pressure
-0.49 to -0.12 in WG &
more negative than
PDIT-K1-305
**PDIT-K1-305
Evaporator Room Diff. Pressure
-0.49 to -0.12 in WG &
more negative than
PDIT-K1-303
**PDIT-K2-358,
Filter K2-7-1 Diff. Pressure 0.05 to 2.0 in WG
**PDIT-K2-359,
Filter K2-1-1 Diff. Pressure 0.1 to 1.0 in WG
**PDIT-K2-351/PDSL-K2-351
Survey Room Diff. Pressure 0 to 0.25 in WG
**PDIT-K2-354/PDSL-K2-354
AMU Room Diff. Pressure 0 to 0.25 in WG
**PDIT-K1-304A
Pump Room Diff. Pressure -4.0 to -0.21 in WG
**PDI-2-2
Pump Room Pressure Indicator -4.0 to 0 in WG
SPECIAL INSTRUCTIONS:
*Out of Spec readings require immediate 242-A Shift Manager notification.
**N/A if VCS HMI readings are obtained.
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
12 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal
Range Limit D N D N D N D N D N D N D N
K1-7-1 Roll Filter Light ON – OFF ON - OFF
K1-7-1 Roll Filter Condition1 Clean/Dirty C/D
K1-11-1 Bag Filter Condition Clean/Dirty C/D
K2-7-1 Roll Filter Light ON - OFF ON - OFF
K2-7-1 Roll Filter Condition1 Clean/Dirty C/D
K2-1-1 Bag Filter Condition Clean/Dirty C/D
SPECIAL INSTRUCTIONS: *Out-of-Spec readings require 242-A Evaporator Shift Manager notification. 1 If roll filter is dirty, CONTACT 242-A Evaporator Shift Manager for permission to advance the filter material.
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
13 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Limit D N D N D N D N D N D N D N
242-A VFD PANELS
K1-5-3, Exhaust Fan
(K1 Exhaust Pad) HS-K1-5-3
HAND/OFF/AUTO
H,O,A
K1-5-2, Exhaust Fan
(K1 Exhaust Pad)
HS-K1-5-2 HAND/OFF/
AUTO H,O,A
HS-K1-5-2C TEST/
NORMAL T/N
SS-K1-5-2 AFC/OFF/
BYP A,O,B
K1-5-1, Supply Fan
(HVAC Room) HS-1
HAND/OFF/
AUTO H,O,A
K2-5-1, Supply Fan
(HVAC Room)
HS-1 HAND/OFF/
AUTO H,O,A
HS-2 NORMAL/
TEST N/T
HS-3 AFC/OFF/
BYP A,O,B
K2-5-3, K2 Exhaust
Fan
(Men’s Rest Room) HS-1
HAND/OFF/AUTO
H,O,A
SPECIAL INSTRUCTIONS: IF at least one K1 Exhaust Fan is NOT running, THEN notify Supervision IMMEDIATELY.
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
14 of 25
Starting Date:
Parameter Normal Range Limit Monday Tuesday Wednesday Thursday Friday Saturday Sunday
D N D N D N D N D N D N D N
Fan Conditions
K1-5-3, Exhaust Fan
(K1 Exhaust Pad )
CHECK for
Abnormal
Condition
None
Observed
() If
condition
is met
K1-5-2, Exhaust Fan
(K1 Exhaust Pad )
CHECK for
Abnormal
Condition
None
Observed
() If
condition
is met
K1-5-1, Supply Fan
(HVAC Room)
CHECK for
Abnormal
Condition
None
Observed
() If
condition
is met
K2-5-1, Supply Fan
(HVAC Room)
CHECK for
Abnormal
Condition
None
Observed
() If
condition
is met
K2-5-3, K2 Exhaust
Fan
(Men’s Rest Room)
CHECK for
Abnormal
Condition
None
Observed
() If
condition
is met
SPECIAL INSTRUCTIONS: IF at least one K1 Exhaust Fan is NOT running, THEN notify Supervision IMMEDIATELY.
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
15 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal
Range Limit D N D N D N D N D N D N D N
242-A AIR DRYERS, FILTERS AND AIR RECEIVER (Continued)
FI-RE1-1, Process Air
Flow Indication
Document
Reading
PI-RE1-1, Air Receiver Pressure 95 to 120 psi
PI-RE1-2, Instrument Air Press 15 to 25 psi
TI-RE1-2, Air Receiver
Temperature F
Blow Down Receiver R-E-1
HV-RE1-3
() If Blow Down Complete
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
16 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Limit D N D N D N D N D N D N D N
Compressor CP-E-2 (Data from SIGMA Control Panel)
Compressor 2 Disch. Air
Pressure 95 to 120 psi
CPE-2 Discharge Air
Temp < 230 F
Compressor position
(lead/lag) **P1 or P2
Total run hours hours
Total load hours hours
Event Information since
last round
text
*Yes/No
Check for abnormal
conditions None Found
() If condition is met
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
* If yes record text in remarks section.
** P1- CP-E-1 is lead compressor and CP-E-2 is lag compressor.
P2- CP-E-2 is lead compressor and CP-E-1 is lag compressor.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
17 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Days D N D N D N D N D N D N
Compressor CP-E-2 Weekly Readings
Oil Filter 0 – 3000 hours
Oil Separator 0 – 6000 hours
Oil Change 0 – 6000 hours
Air Filter 0 – 6000 hours
Belt Coupling
Change 0 – 32000 hours
Belt Coupling
Inspection 0 – 6000 hours
Bearing Change 0 – 32000 hours
Bearing Maintenance 0 – 32000 hours
Electrical Equipment 0 – 9000 hours
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
18 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Limit D N D N D N D N D N D N D N
Compressor CP-E-1 (Data from SIGMA Control Panel)
Compressor 1
Disch. Air Pressure 95 to 120 psi
CPE-1 Discharge Air
Temp < 230 F
Compressor position
(lead/lag) **P1 or P2
Total run hours hours
Total load hours hours
Event Information since
last round
text
*Yes/No
Check for abnormal
conditions
None Found
() If condition is
met
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
* If yes record text in remarks section.
** P1- CP-E-1 is lead compressor and CP-E-2 is lag compressor.
P2- CP-E-2 is lead compressor and CP-E-1 is lag compressor.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
19 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range Days D N D N D N D N D N D N
Compressor CP-E-1 Weekly Readings
Oil Filter 0 – 3000 hours
Oil Separator 0 – 6000 hours
Oil Change 0 – 6000 hours
Air Filter 0 – 6000 hours
Belt Coupling
Change 0 – 32000 hours
Belt Coupling
Inspection 0 – 6000 hours
Bearing Change 0 – 32000 hours
Bearing Maintenance 0 – 32000 hours
Electrical Equipment 0 – 9000 hours
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
20 of 25
SPECIAL INSTRUCTIONS:
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
*N/A if the glycol cooling system is not in service.
RATL # REMARKS
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter Normal Range D N D N D N D N D N D N D N
Compressor Cooling System (Inside)
*FG-CW-2 CP-E-2 Coolant Flow Ball Suspended
() If condition is met
*TI-CW-4 CP-E-2 Coolant Out Temp 75 to 120 F
*TI-CW-3 CP-E-1 Coolant Out Temp 75 to 120 F
*FG-CW-1 CP-E-1 Coolant Flow Ball Suspended
() If condition is met
Compressor Cooling System (Outside)
TI-CW-2, Chiller Outlet < 120 F
PI-CW-1, Pump Outlet 30 to 50 psi
TI-CW-1, Chiller Inlet < 120 F
Check for abnormal
Coolant Pump Noise () If condition is met
Compressor Chiller Pad free of debris () If condition is met
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
21 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter
(Normal Range)
Normal
Range Limit D N D N D N D N D N D N D N
242-A EVAPORATOR FIRE PROTECTION DATA
Fire Protection System P.I.V.
(242-A 119R) Open()
BFP Upstream Isolation
(A-FP-1 Valve)
Open &
Locked ()
BFP Downstream Isolation
(A-FP-2 Valve)
Open &
Locked ()
System Water Pressure Upstream
of BFP (PI-FP-1) > 80 psi
System Water Pressure Upstream
of Check Valve
(PI-FP-2)
> 80psi
System Water Pressure
Downstream of Check Valve
(PI-FP-3)
> 80psi
Alarm Valve Position (A-FP-3) Open ()
SPECIAL INSTRUCTIONS:
Note: Perform Fire Protection checks on Friday Day shift only.
Readings may be performed out of sequence to facilitate work progress.
Note any missing or illegible labels on Comment Page.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
22 of 25
Starting Date: Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Parameter
(Basis) D N D N D N D N D N D N D N
242-A EVAPORATOR FIRE PROTECTION DATA (Cont.)
No buildup of transient material around K1 system
filters
Condition Met ()
(HNF-SD-WM-FHA-02A)
SPECIAL INSTRUCTIONS:
Note: Perform Fire Protection checks on Friday Day shift only.
RATL # REMARKS
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
23 of 25
COMMENT PAGE
RECORD ANY EXTRA COMMENTS BELOW:
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
24 of 25
Starting Date:
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
DAYS
Performed
By:
Print (First and Last)
Sign
Date/
Time
Reviewed
By:
Print (First and Last)
Sign
Date/
Time
NIGHTS
Performed
By:
Print (First and Last)
Sign
Date/
Time
Reviewed
By:
Print (First and Last)
Sign
Date/
Time
242-A Evaporator Stationary Operating Engineer Rounds
Type
CONTINUOUS Document No.
TF-OR-PWR-03 Rev/Mod
J-65 Release Date
12/13/2018 Page
25 of 25
Records
The following records are generated during the performance of this procedure:
Hard copy records are submitted to the File Custodian, located at 274-AW. Electronic
records are entered into IDMS.
Submit the entire round procedure as a record.
The record custodian identified in the company-level Records Inventory and Disposition
Schedule (RIDS) is responsible for record retention in accordance with
TFC-BSM-IRM_DC-C-02.