250edj 7bar local part 1
TRANSCRIPT
SAUDI FACTORY FOR FIRE EQUIPMENT. P.O. Box 4441, Riyadh 14334, K.S.A.
Tel. No. 966-1-265 0070, Fax No. 966-1-265 21 90, E-mail : [email protected], website : www.sffeco.com
FIRE PROTECTION ENGINEERS
EDJ 250/7
EXCEL SERIES
FIRE PUMP SUBMITTAL
SAUDI FACTORY FOR FIRE EQUIPMENT Co.
SECTION 1
DESCRIPTION
SFFECO FIRE PUMPS
PRODUCT : EDJ 250/7
DESCRIPTION :
DUTY PUMP DETAIL :
Brand : G-MAX PumpsModel : GHS 850/500/200Type : Horizontal-End SuctionRated Flow : 250 GPM Rated Head : 7 BAR Impeller Size : 200 mmSuction/Discharge : 65mm/50mm
MOTOR DETAIL :
Brand : HITEC,Series/Model : HM 180 M-3Rated Speed : 3500 RPMPerformance Rating : 30 Hp / 3 Ph / 60 Hz - 220 /380 Vac
STANDBY PUMP DETAIL:
Brand : G-MAX PumpsModel : GHR 650/500/260Type : Horizontal-End SuctionRated Flow : 250 GPM Rated Head : 7 BAR Impeller Size : 245 mmSuction/Discharge : 65mm/50mm
ENGINE DETAIL :
Brand : MEGAFORCE,Series/Model : MFS-25Power : 25 HPRated Speed : 2900 RPMCooling System : Radiator
Visit www.sffeco.com
Fire Pump Division
Saudi Factory for Fire Equipment Co. P .O. Box 4441, Riyadh 14334, K.S.A.; Tel. No. 966-1-265-0070; Fax No. 966-1-265-2190
The SFFECO EDJ 250/7 Excel Series is a package type fire pump consisting of an electric motor-driven duty pump, diesel engine-driven standby pump, jockey pump, combined controller , mounted in a common base plate. Nominal performance rating is 250 GPM @ 7 BAR. The package is complete with discharge valves, and accessories.
SFFECO FIRE PUMPS
PRODUCT : EDJ 250/7
JOCKEY PUMP DETAIL:
Brand : G -MAX Pumps Series/Model : GVS4-60Rated Flow : 15 GPMRated Head 7 BARHorsepower : 3HPMotor Detail : 220 / 380Vac / 3 Ph / 60 Hz / 3500 RpmSuction/Discharge : 32 mm
CONTROLLER DETAIL:
Make : SFFECO, K.S.A.Model : Type AOperation : Combined Automatic and ManualEnclosure : General PurposeMounting : Pump chassis mountedMethod of Start : DOL Means of Activation : Pressure Switch, Selector SwitchPower Supply Detail : 380 Vac, 60 Hz, 3 Ph, 12Vdc
SYSTEM VALVES & ACCESSORIES DETAIL:
Gate Valves : 2.5" dia., flanged, LIFECOCheck Valves : 2.5" dia., flanged, LIFECORubber Expansion Joints : 2.5" dia., flanged, LIFECOHeader Pipe : 4" dia., Black SteelPressure Switches : Range 1-20 Bar (15-290 Psig), ALCOPressure Gauge : 2" dial, range 0 - 400 Psi, LIFECO
Visit www.sffeco.com
Fire Pump Division
Saudi Factory for Fire Equipment Co. P.O. Box4441, Riyadh 14334, K.S.A.; Tel. No. 966-1-265-0070; Fax No. 966-1-265-2190
SAUDI FACTORY FOR FIRE EQUIPMENT Co.
SECTION 2
THE PUMP
FIRE PROTECTION CONTRACTOR ISO 9001 COMPANY
To avoid cavitation, make sure that there is aminimum pressure on the suction side of thepump. The maximum suction lift "H" inmeters head can be calculated as follows
H = Pb X 10.2 - NPSH - Hf - Hv - Hs
Pb = Barometric pressure in bar.(Barometric pressure can be set to 1 bar.) In closed systems, Pb indicatesthe system pressure in bar.
NPSH = Net Positive Suction Head in meters head.(To be read from the NPSH curve at the highest flow the pump will be delivering.)
Hf = Friction loss in suction pipe in metershead.(At the highest flow the pump will be delivering).
Hv = Vapor pressure in meters head.(To be read from the vapor pressurescale. “Hv” depends on the liquid temperature "Tm")
Hs = Safety margin = minimum 0.5 metershead.(To be read from the vapor pressurescale.“Hv” depends on the liquid temperature “Tm”)
If the "H" calculated is positive, the pump canoperate at a suction lift of maximum "H"meters head.
If the "H" calculated is negative, an inletpressure of minimum "H" meters head isrequired.
c. Motor
The motor is totally enclosed, fan-cooled, 2-pole with principal dimensions in accordancewith the EN standards
Electrical tolerances according to EN 60034
Electrical Data
Mounting Up to 4kW: V18Designation From 5.5 kW: V1
Insulation Class F
Efficiency class Eff.2Eff.1 - on request
Enclosure class IP 55IP 44 & IP 54 - on request
50Hz 3 x 200 - 220 / 346 - 380V,±10%standard voltages 3 x 220 - 240 / 380 - 415V.
3 x 380 - 415 ∆V1 x 220-230 / 240 V
60Hz 3 x 460 / 220 V.standard voltages
Motor protection
Single phase motors have a built in thermaloverload switchThree phase motors must be connected to amotor starter in accordance with localregulationsThree phase motors from 3 kW and upwardshave a built-in thermostat (PTC) according toDIN 44 082.
Ambient temperature
Maximum +40˚CIf the ambient temperature exceeds +40˚C orif the motor is located 1000 meters abovesea level, the motor output (P2) must bereduced due to the low density andconsequently low cooling effect of the air. Insuch cases, it may be necessary to use amotor with a higher output.
Stainless Steel Centrifugal Pumps
50
60
70
80
90
100
[%]
P2
20 25 30 35 40 45 50 55 60 65 70 75 80
1000 2250 3500 m
t[˚C]