2_chp and tri generation
TRANSCRIPT
-
8/3/2019 2_CHP and Tri Generation
1/2
KNOWLEDGE GUIDES
For Architects
XCO2 Energy 2009 www.xco2energy.com
CHP Engine
Grid
Input Process Output Eciency
60
80
96
30
50
30
Heat
Electricity
Boiler
Conventional
Energy Network
Combined
Heat and Power
(CHP)83%
ElectricityGeneration
HeatGeneration
57%
Losses 10 units
Losses 50 units
Losses 16 units
Coal Power Station
50
units ofelectricity
units ofelectricity
units ofprimary fuel
units ofprimary fuel
units ofprimary fuel
units ofheat
units ofheat
02: Combined Heat and Power/Trigeneration
Combined heat and power (CHP) is a system where heat, which is usually lost during the electricity
generation process, is recovered and used. This results in much greater overall eciencies than grid-supplied electricity and, thereore, carbon emissions are usually reduced. In addition, a trigeneration system
can convert the waste heat into chilled water or cooling uses with the inclusion o an absorption chiller.
Building Scale CHPCHP is generally suitable or the
ollowing types o building due to
their high constant heat demand:
Hotels
Hospitals
Leisure Centres (especially
with swimming pools)
Universities
In addition to these building types,
any mixed use development, such
as oces and retail, may also beeasible as, together, they provide
a constant heating demand.
The easibility o CHP or any
building relies on many actors
(see Building Evaluation); however,
a good heat baseload is usually
essential.
Micro CHPMicro CHP is a relatively new
technology that attempts to
service buildings with low heating
loads (
-
8/3/2019 2_CHP and Tri Generation
2/2
KNOWLEDGE GUIDES
For Architects
XCO2 Energy 2009 www.xco2energy.com
London PlanThe London Plan provides an approach or reducing the operational carbon
emissions o new developments.
This is commonly known under the mantra Lean, Clean, Green, which
denotes the order o improvements to be made.
Lean - passive design energy eciency measures
Clean - CHP, Trigeneration and/or district heating networks
Green - Renewable energy technologies (biomass, wind, solar thermal, etc.)
Incorporating CHP or Trigeneration into a new development reduces the
quantity o renewable technology needed to meet the 20% target.
Depending on the type o development, the post-eciency CO2
emissions
can be reduced by 5 - 15%.
Trigeneration Trigeneration makes use o the
waste heat or cooling purposes.
An absorption chiller converts the
heat rom the CHP engine intochilled water.
Heat can be used or heating
purposes during the winter and,
with the application o the chiller,
can provide cooling during the
summer.
Because o this, Trigeneration can
result in much larger installations
than CHP providing much greater
environmental and nancial
benets.
Single, double and triple-stage
absorption chillers require dierent
temperatures to operate.
Most building-size applications will
use single-stage absorption chillers
which typically have a coecient
o perormance (COP) o 0.6 - 0.7.
Absorption chillers can require
signicant heat rejection
inrastructure and is likely to be
expensive.
Building EvaluationHeat and electricity demand
- Ideally the hourly heat and
electricity demand o the
development is required. However,in the case o new developments,
assumptions have to be made as
to the likely energy consumption
patterns throughout the year.
Space implications - CHP plant is
larger than typical boilers and will
require more plant space.
Fuel type - Certain gas pressures
are required and oil/biomass CHP
will require large storage space.
Noise implications - noise
attenuation may be needed and
noise levels in adjacent areas, air
inlets, exhaust outlets and nearbybuildings should be considered.
Vibration - anti-vibration mounting
o engine and pipework may be
required.
Stack height - special consideration
must be taken when speciying
exhaust gases and fue heights.
Location - CHP engines can be
situated in plant rooms, on roos
and externally in weather-proo
enclosures.
GlossaryCogeneration - CHP is sometimes reerred to as cogeneration.
Coecient o Perormance (COP) - A ratio o the heat energy extracted or
each unit o heat energy inputed. e.g. a COP o 0.6 means that or every unit
o heat supplied, 0.6 units o cooling is provided.
Heat-to-power ratio - The ratio o heat output to power output. e.g. an
engine that produces 100kW o heat and 50kW o power would have a ratio
o 2:1 (100/50). Micro CHP engines (domestic) typically have ratios o 3:1 -
15:1, small-scale systems (large buildings) have ratios o 2:1 and large systems
(district energy power stations) have ratios o 1:1.
Baseload - The minimum amount o heat or power required or a CHP engine
to be easible.
Modulation - The ability o an engine to work below ull capacity. Most
CHP engines can only modulate to approximately 75% o ull power beore
shutting down.
Load Profle - a graph showing a particular building load (e.g. heat)
throughout the year enabling a visual representation o the CHP operation.
This is usually an hourly prole.
CHCP/CCHP - Trigeneration is sometimes reered to as either Combined
Heat, Cooling and Power or Combined Cooling, Heat and Power.
Spark Gap - The dierence in price between a kWh o electricity and gas. The
wider the gap, the greater are the economic benets that can be obtained
rom CHP.
Climate Change Levy (CCL) - A levy imposed on electricity (0.456p/kWh)
and gas (0.159p/kWh). Certain CHP installations can be exempt rom this levy
(see Good Quality CHP) providing an additional economic incentive.
Good Quality CHP - Through a process known as CHP Quality Assurance,a CHP engine can be certied as Good Quality. Any CHP installation that
meets these requirements is exempt rom paying the CCL.
Integration with Renewable Technology
Photovoltaics
Very compatible
Any excess electricity can be
exported to the grid
Wind
Very compatible
Any excess electricity can be
exported to the grid
GSHP
Partially compatible
Shares some heat load
Biomass
Partially compatible
Shares some heat load
Solar Thermal
Generally not compatible
Removes heat baseload
required or CHP operation
Compatibility
Less More
CHP
XCO2 Energy ServicesWhen specied correctly, CHP can produce good carbon savings and provideshort payback periods o only ve to ten years.
Our services include:
CHP Sizing - Feasibility study or installing CHP in either new developmentsor retro-tting into existing buildings.
Site-wide Energy Strategies - CHP integration into large-scaledevelopments, energy networks and district heating.
Multi-Utility Service Company (MUSCo) Feasibility Studies - Investigationinto economic viability in terms o return on capital investiment or site-
wide services strategies.
Energy Statements - Local Authority planning application reportsconsidering energy eciency, clean technologies and renewabletechnology easibility.