3. protection primer-1
TRANSCRIPT
-
8/12/2019 3. Protection Primer-1
1/72
O&M of Protection System and RelayCoordinationDr. Sasidharan Sreedharan
www.sasidharan.webs.com
Over View of Power System Protection
-
8/12/2019 3. Protection Primer-1
2/72
2
Detailed Schedule
-
8/12/2019 3. Protection Primer-1
3/72
Generation-typically at 4-20kV
Transmission-typically at 230-765kV
Subtransmission-typically at 69-161kV
Receives power from transmission system and
transforms into subtransmission level
Receives power from subtransmission system and
transforms into primary feeder voltage
Distribution network-typically 2.4-69kV
Low voltage (service)-typically 120-600V
Typical
Bulk
Power
System
3
-
8/12/2019 3. Protection Primer-1
4/72
Introduction
Sub Station Transformer Explosion 4
http://localhost/var/www/apps/conversion/tmp/scratch_7/Department%20of%20energy%20substation%20transformer%20explosion%20in%20Cheyenne%20Wyoming.mp4 -
8/12/2019 3. Protection Primer-1
5/72
Introduction
Equipment Failure
5
-
8/12/2019 3. Protection Primer-1
6/72
Winding Damage-1
6
-
8/12/2019 3. Protection Primer-1
7/72
Winding Damage-2
7
-
8/12/2019 3. Protection Primer-1
8/72
Generator Damage
Generator Damage
-
8/12/2019 3. Protection Primer-1
9/72
Transformer Winding Damage
9
-
8/12/2019 3. Protection Primer-1
10/72
Factors Affecting the Protection
System
Economics
Personality
Location of Disconnecting and Input Devices
Available Fault Indicators
10
-
8/12/2019 3. Protection Primer-1
11/72
Protective Relay
Relay: An electric device that is designed to respond toinput conditions in a prescribed manner and , afterspecified conditions are met, to cause contactoperation or similar abrupt change in associatedelectric control circuits. (IEEE)
Protective Relay: A relay whose function is to detect
defective lines or apparatus or other power systemconditions of an abnormal or dangerous nature and toinitiate appropriate control circuit action. (IEEE)
11
-
8/12/2019 3. Protection Primer-1
12/72
Typical Protective Relays
12
-
8/12/2019 3. Protection Primer-1
13/72
Classification of Relays
Protective Relays
Regulating Relays
Reclosing, Synchronism Check, and SynchronizingRelays
Monitoring Relays
Auxiliary Relays
Others
13
-
8/12/2019 3. Protection Primer-1
14/72
Protective Relay Performance
Since many relays near the trouble area may beginto operate for any given fault, it is difficult tocompletely evaluate an individual relays
performance. Performance can be categorized as follows:
Correct: (a) As planned or (b) Not as planned orexpected.
Incorrect: (a) Fail to trip or (b) False tripping No conclusion
14
-
8/12/2019 3. Protection Primer-1
15/72
Principles of Relay Application
The power system is divided into protection zonesdefined by the equipment and available circuit breakers.
Six possible protection zones are listed below:
1. Generators and generator-transformer units
2. Transformers
3. Buses
4. Lines (Transmission, sub transmission, anddistribution)
5. Utilization equipment
6. Capacitor or reactor banks
15
-
8/12/2019 3. Protection Primer-1
16/72
1. Generator or Generator-Transformer Units2. Transformers
3. Buses
4. Lines (transmission and distribution)
5. Utilization equipment (motors, static loads, etc.)
6. Capacitor or reactor (when separately protected)
Unit Generator-Tx zone
Bus zone
Line zone
Bus zone
Transformer zoneTransformer zone
Bus zone
Generator
~
XFMR Bus Line Bus XFMR Bus Motor
Motor zone
ProtectionZones
16
-
8/12/2019 3. Protection Primer-1
17/72
17
-
8/12/2019 3. Protection Primer-1
18/72
18
-
8/12/2019 3. Protection Primer-1
19/72
Desirable Protection Attributes1. Reliability: System operate properly
Security: Donttrip when you shouldnt Dependability: Trip when you should
2. Selectivity: Trip the minimal amount to
clear the fault or abnormal operatingcondition
3. Speed: Usually the faster the better in
terms of minimizing equipment damageand maintaining system integrity
4. Simplicity:
5. Economics: Dontbreak the bank 19
-
8/12/2019 3. Protection Primer-1
20/72
Selection of protective relays requires compromises:
Maximum and Reliable protection at minimum
equipment cost
High Sensitivity to faults and insensitivity tomaximum load currents
High-speed fault clearance with correct selectivity
Selectivity in isolating small faulty area.
Ability to operate correctly under all predictable
power system conditions
Art & Science of Protection
20
-
8/12/2019 3. Protection Primer-1
21/72
Cost of protective relays should be balanced
against risks involved if protection is not sufficient
and not enough redundancy.
Primary objectives is to have faulted zonesprimary protection operate first, but if there are
protective relays failures, some form of backup
protectionis provided.
Backup protection is local (if local primary
protection fails to clear fault) and remote (if remote
protection fails to operate to clear fault)
Art & Science of Protection
21
-
8/12/2019 3. Protection Primer-1
22/72
Primary Equipment & Components
Transformers- to step up or step down voltage level
Breakers- to energize equipment and interrupt fault current to
isolate faulted equipment
Insulators - to insulate equipment from ground and other
phases
Isolators (switches) - to create a visible and permanent
isolation of primary equipment for maintenance purposes and
route power flow over certain buses.
Bus - to allow multiple connections (feeders) to the same
source of power (transformer).
22
-
8/12/2019 3. Protection Primer-1
23/72
Primary Equipment & Components
Grounding- to operate and maintain equipment safely
Arrester- to protect primary equipment of sudden
overvoltage (lightning strike).
Switchgearintegrated components to switch, protect, meter
and control power flow
Reactors- to limit fault current (series) or compensate for
charge current (shunt)
VT and CT - to measure primary current and voltage and
supply scaled down values to P&C, metering, SCADA, etc.
Regulators - voltage, current, VAR, phase angle, etc.
23
-
8/12/2019 3. Protection Primer-1
24/72
Types of Protection
Overcurrent Uses current to determine magnitude of fault Simple
May employ definite time or inverse time curves
May be slow
Selectivity at the cost of speed (coordination stacks)
Inexpensive
May use various polarizing voltages or ground currentfor directionality
Communication aided schemes make more selective.
24
-
8/12/2019 3. Protection Primer-1
25/72
Selection of the curves
uses what is termed as a
time multiplier or
time dial to effectively
shift the curve up or
down on the time axis
Operate region lies
above selected curve,
while no-operate region
lies below it.
Inverse curves can
approximate fuse curve
shapes
Time Overcurrent Protection (TOC)
25
-
8/12/2019 3. Protection Primer-1
26/72
26
-
8/12/2019 3. Protection Primer-1
27/72
27
-
8/12/2019 3. Protection Primer-1
28/72
Multiples of pick-up
Time Overcurrent Protection(51, 51N, 51G)
28
-
8/12/2019 3. Protection Primer-1
29/72
29
Un Restricted & Restricted Protection
No Specific Point downstream up to which protection willprotect. Will Operate for faults on the protection equipment. May also operate for faults on downstream equipment
which has its own protection. Need f0r discrimination with downstream protection
usually by means of time grading.
Unrestricted
Restricted
Has an accurately defined zone of protection. An item of power plant is protected as a unit Will not operate for out of zone faults thus no back up
protection for downstream faults
-
8/12/2019 3. Protection Primer-1
30/72
Types of Protection
Differential
current in = current out
Simple
Very fast
Very defined clearing area
Expensive
Practical distance limitations Line differential systems overcome this using digital
communications
30
-
8/12/2019 3. Protection Primer-1
31/72
Types of Protection
Voltage
Uses voltage to infer fault or abnormal condition
May employ definite time or inverse time curves
May also be used for under voltage loadshedding Simple
May be slow
Selectivity at the cost of speed (coordination stacks)
Inexpensive.
31
-
8/12/2019 3. Protection Primer-1
32/72
Types of Protection
Frequency
Uses frequency of voltage to detect powerbalance condition
May employ definite time or inverse time curves Used for load shedding & machinery under/over
speed protection Simple
May be slow Selectivity at the cost of speed can be expensive
32
-
8/12/2019 3. Protection Primer-1
33/72
Types of Protection
Power
Uses voltage and current to determine power flowmagnitude and direction
Typically definite time Complex
May be slow
Accuracy important for many applications
Can be expensive
33
-
8/12/2019 3. Protection Primer-1
34/72
Types of Protection
Distance (Impedance) Uses voltage and current to determine impedance of fault
Set on impedance [R-X] plane
Uses definite time Impedance related to distance from relay
Complicated
Fast
Somewhat defined clearing area with reasonable accuracy Expensive
Communication aided schemes make more selective
34
I d
-
8/12/2019 3. Protection Primer-1
35/72
Impedance
Relay in Zone 1 operates first
Time between Zones is called CTI
Source
A B
21 21
T1
T2
ZA
ZB
R
X ZL
35
-
8/12/2019 3. Protection Primer-1
36/72
1. Overlap is accomplished by the locations of CTs, the key source for protective
relays.
2. In some cases a fault might involve a CT or a circuit breaker itself, which
means it can not be cleared until adjacent breakers (local or remote) are
opened.
Zone A Zone B
Relay Zone A
Relay Zone B
CTs are located at both sides of CB-faultbetween CTs is cleared from both remote sides
Zone A Zone B
Relay Zone A
Relay Zone B
CTs are located at one side of CB-fault between CTs is sensed by both relays,
remote right side operate only.
Zone Overlap
36
-
8/12/2019 3. Protection Primer-1
37/72
1. One-line diagram of the system or area involved2. Impedances and connections of power equipment, system frequency,
voltage level and phase sequence
3. Existing schemes
4. Operating procedures and practices affecting protection
5. Importance of protection required and maximum allowed clearance
times
6. System fault studies
7. Maximum load and system swing limits
8. CTs and VTs locations, connections and ratios
9. Future expansion expectance
10. Any special considerations for application.
What Info is Required to Apply Protection
37
C T f
-
8/12/2019 3. Protection Primer-1
38/72
Current transformers are used to step primary system currents to
values usable by relays, meters, SCADA, transducers, etc.
CT ratios are expressed as primary to secondary; 2000:5, 1200:5,
600:5, 300:5
A 2000:5 CT has a CTRof 400
Current Transformers
38
-
8/12/2019 3. Protection Primer-1
39/72
39
-
8/12/2019 3. Protection Primer-1
40/72
40
-
8/12/2019 3. Protection Primer-1
41/72
41
-
8/12/2019 3. Protection Primer-1
42/72
-
8/12/2019 3. Protection Primer-1
43/72
Typical CT/VT Circuits
Courtesy of Blackburn, Protective Relay: Principles and Applications
43
-
8/12/2019 3. Protection Primer-1
44/72
System Grounding
Limits over voltages
Limits difference in electricpotential through local area
conducting objects Several methods
Ungrounded
Reactance Coil Grounded
High Z Grounded Low Z Grounded
Solidly Grounded
44
Prevents shock exposureof personnel
Provides current
carrying capability forthe ground-fault current
Grounding includesdesign and constructionof substation groundmat and CT and VTsafety grounding
Equipment Grounding
-
8/12/2019 3. Protection Primer-1
45/72
1. Ungrounded: There is no intentional
ground applied to the system-
however its grounded through
natural capacitance. Found in 2.4 -
15kV systems.
2. Reactance Grounded: Total system
capacitance is cancelled by equal
inductance. This decreases the currentat the fault and limits voltage across the
arc at the fault to decrease damage.
X0
-
8/12/2019 3. Protection Primer-1
46/72
3. High Resistance Grounded: Limitsground fault current to 10A-20A. Used
to limit transient overvoltages due to
arcing ground faults.
R0 = 2X0
System Grounding
46
-
8/12/2019 3. Protection Primer-1
47/72
5. Solidly Grounded: There is a
connection of transformer or generatorneutral directly to station ground.
Effectively Grounded: R0
-
8/12/2019 3. Protection Primer-1
48/72
Substation Types
Single Supply
Multiple Supply
Mobile Substations for emergencies
Types are defined by number of transformers,
buses, breakers to provide adequate service
for application
48
-
8/12/2019 3. Protection Primer-1
49/72
Industrial Substation Arrangements
-
8/12/2019 3. Protection Primer-1
50/72
Industrial Substation Arrangements(Typical)
50
Utilit S b t ti A t
-
8/12/2019 3. Protection Primer-1
51/72
Utility Substation Arrangements
Single Bus, 1 Tx, Dual supply Single Bus, 2 Tx, Dual Supply 2-sections Bus with HS Tie-Breaker, 2Tx, Dual Supply
(Typical)
51
Utilit S b t ti A t
-
8/12/2019 3. Protection Primer-1
52/72
Breaker-and-a-halfallows reduction ofequipment cost by using 3 breakers for each 2circuits. For load transfer and operation issimple, but relaying is complex as middlebreaker is responsible to both circuits
Utility Substation Arrangements
Bus 1
Bus 2
Ring busadvantage that one breakerper circuit. Also each outgoing circuit(Tx) has 2 sources of supply. Anybreaker can be taken from servicewithout disrupting others.
(Typical)
52
-
8/12/2019 3. Protection Primer-1
53/72
Double Bus: Upper Main andTransfer, bottom Double Main bus
Main bus
Aux. bus
Bus 1
Bus 2
Tie
breaker
Utility Substation Arrangements
Main
ReserveTransfer
Main-Reserved and Transfer Bus:Allows maintenance of any bus andany breaker
(Typical)
53
S it h D fi d
-
8/12/2019 3. Protection Primer-1
54/72
Switchgear DefinedAssemblies containing electrical switching,
protection, metering and management devices Used in three-phase, high-power industrial,
commercial and utility applications
Covers a variety of actual uses, including motor
control, distribution panels and outdoorswitchyards
The term "switchgear" is plural, even whenreferring to a single switchgear assembly (never
say, "switchgears") May be a described in terms of use:
"the generator switchgear"
"the stamping line switchgear"54
-
8/12/2019 3. Protection Primer-1
55/72
Switchgear Examples
55
-
8/12/2019 3. Protection Primer-1
56/72
A Good Day in System Protection
CTs and VTs bring electrical info to relays
Relays sense current and voltage and declare fault
Relays send signals through control circuits to circuit
breakers
Circuit breaker(s) correctly trip
What Could Go Wrong Here????
56
-
8/12/2019 3. Protection Primer-1
57/72
A Bad Day in System Protection
CTs or VTs are shorted, opened, or their wiring is Relays do not declare fault due to setting errors, faulty relay,
CT saturation
Control wires cut or batteries dead so no signal is sent from
relay to circuit breaker Circuit breakers do not have power, burnt trip coil or
otherwise fail to trip
Protection Systems Typically are
Designed for N-1
57
-
8/12/2019 3. Protection Primer-1
58/72
Contribution to Faults
58
-
8/12/2019 3. Protection Primer-1
59/72
Fault Types (Shunt)
59
-
8/12/2019 3. Protection Primer-1
60/72
FAULTS IN UNDERGROUND CABLES
60
-
8/12/2019 3. Protection Primer-1
61/72
61
Faults in Overhead Lines
-
8/12/2019 3. Protection Primer-1
62/72
62
Faults in Machines
-
8/12/2019 3. Protection Primer-1
63/72
63
Type of Fault
-
8/12/2019 3. Protection Primer-1
64/72
64
Type of Faults
-
8/12/2019 3. Protection Primer-1
65/72
65
Type of Fault
-
8/12/2019 3. Protection Primer-1
66/72
66
Type of Cable Faults
-
8/12/2019 3. Protection Primer-1
67/72
AC & DC Current Components
of Fault Current
67
P U i B i
-
8/12/2019 3. Protection Primer-1
68/72
Per Unit Basics
68
Establish two basequantities:
Standard practice isto define Base power 3 phase
Base voltage line toline
Other quantities
derived with basicpower equations
Short Circuit Calculations
-
8/12/2019 3. Protection Primer-1
69/72
Short Circuit Calculations
Per Unit System
Per Unit Value = Actual QuantityBase Quantity
Vpu = VactualVbase
Ipu = Iactual
Ibase
Zpu = ZactualZbase
69
-
8/12/2019 3. Protection Primer-1
70/72
A Study of a Fault.
70
-
8/12/2019 3. Protection Primer-1
71/72
71
-
8/12/2019 3. Protection Primer-1
72/72
YBL Systems and Solutions
(Electrical Power System Research Consultants)
www.sasidharan.webs.com
Regards,