3. protection primer-1

Upload: alejandro-ramirez-benites

Post on 03-Jun-2018

222 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/12/2019 3. Protection Primer-1

    1/72

    O&M of Protection System and RelayCoordinationDr. Sasidharan Sreedharan

    www.sasidharan.webs.com

    Over View of Power System Protection

  • 8/12/2019 3. Protection Primer-1

    2/72

    2

    Detailed Schedule

  • 8/12/2019 3. Protection Primer-1

    3/72

    Generation-typically at 4-20kV

    Transmission-typically at 230-765kV

    Subtransmission-typically at 69-161kV

    Receives power from transmission system and

    transforms into subtransmission level

    Receives power from subtransmission system and

    transforms into primary feeder voltage

    Distribution network-typically 2.4-69kV

    Low voltage (service)-typically 120-600V

    Typical

    Bulk

    Power

    System

    3

  • 8/12/2019 3. Protection Primer-1

    4/72

    Introduction

    Sub Station Transformer Explosion 4

    http://localhost/var/www/apps/conversion/tmp/scratch_7/Department%20of%20energy%20substation%20transformer%20explosion%20in%20Cheyenne%20Wyoming.mp4
  • 8/12/2019 3. Protection Primer-1

    5/72

    Introduction

    Equipment Failure

    5

  • 8/12/2019 3. Protection Primer-1

    6/72

    Winding Damage-1

    6

  • 8/12/2019 3. Protection Primer-1

    7/72

    Winding Damage-2

    7

  • 8/12/2019 3. Protection Primer-1

    8/72

    Generator Damage

    Generator Damage

  • 8/12/2019 3. Protection Primer-1

    9/72

    Transformer Winding Damage

    9

  • 8/12/2019 3. Protection Primer-1

    10/72

    Factors Affecting the Protection

    System

    Economics

    Personality

    Location of Disconnecting and Input Devices

    Available Fault Indicators

    10

  • 8/12/2019 3. Protection Primer-1

    11/72

    Protective Relay

    Relay: An electric device that is designed to respond toinput conditions in a prescribed manner and , afterspecified conditions are met, to cause contactoperation or similar abrupt change in associatedelectric control circuits. (IEEE)

    Protective Relay: A relay whose function is to detect

    defective lines or apparatus or other power systemconditions of an abnormal or dangerous nature and toinitiate appropriate control circuit action. (IEEE)

    11

  • 8/12/2019 3. Protection Primer-1

    12/72

    Typical Protective Relays

    12

  • 8/12/2019 3. Protection Primer-1

    13/72

    Classification of Relays

    Protective Relays

    Regulating Relays

    Reclosing, Synchronism Check, and SynchronizingRelays

    Monitoring Relays

    Auxiliary Relays

    Others

    13

  • 8/12/2019 3. Protection Primer-1

    14/72

    Protective Relay Performance

    Since many relays near the trouble area may beginto operate for any given fault, it is difficult tocompletely evaluate an individual relays

    performance. Performance can be categorized as follows:

    Correct: (a) As planned or (b) Not as planned orexpected.

    Incorrect: (a) Fail to trip or (b) False tripping No conclusion

    14

  • 8/12/2019 3. Protection Primer-1

    15/72

    Principles of Relay Application

    The power system is divided into protection zonesdefined by the equipment and available circuit breakers.

    Six possible protection zones are listed below:

    1. Generators and generator-transformer units

    2. Transformers

    3. Buses

    4. Lines (Transmission, sub transmission, anddistribution)

    5. Utilization equipment

    6. Capacitor or reactor banks

    15

  • 8/12/2019 3. Protection Primer-1

    16/72

    1. Generator or Generator-Transformer Units2. Transformers

    3. Buses

    4. Lines (transmission and distribution)

    5. Utilization equipment (motors, static loads, etc.)

    6. Capacitor or reactor (when separately protected)

    Unit Generator-Tx zone

    Bus zone

    Line zone

    Bus zone

    Transformer zoneTransformer zone

    Bus zone

    Generator

    ~

    XFMR Bus Line Bus XFMR Bus Motor

    Motor zone

    ProtectionZones

    16

  • 8/12/2019 3. Protection Primer-1

    17/72

    17

  • 8/12/2019 3. Protection Primer-1

    18/72

    18

  • 8/12/2019 3. Protection Primer-1

    19/72

    Desirable Protection Attributes1. Reliability: System operate properly

    Security: Donttrip when you shouldnt Dependability: Trip when you should

    2. Selectivity: Trip the minimal amount to

    clear the fault or abnormal operatingcondition

    3. Speed: Usually the faster the better in

    terms of minimizing equipment damageand maintaining system integrity

    4. Simplicity:

    5. Economics: Dontbreak the bank 19

  • 8/12/2019 3. Protection Primer-1

    20/72

    Selection of protective relays requires compromises:

    Maximum and Reliable protection at minimum

    equipment cost

    High Sensitivity to faults and insensitivity tomaximum load currents

    High-speed fault clearance with correct selectivity

    Selectivity in isolating small faulty area.

    Ability to operate correctly under all predictable

    power system conditions

    Art & Science of Protection

    20

  • 8/12/2019 3. Protection Primer-1

    21/72

    Cost of protective relays should be balanced

    against risks involved if protection is not sufficient

    and not enough redundancy.

    Primary objectives is to have faulted zonesprimary protection operate first, but if there are

    protective relays failures, some form of backup

    protectionis provided.

    Backup protection is local (if local primary

    protection fails to clear fault) and remote (if remote

    protection fails to operate to clear fault)

    Art & Science of Protection

    21

  • 8/12/2019 3. Protection Primer-1

    22/72

    Primary Equipment & Components

    Transformers- to step up or step down voltage level

    Breakers- to energize equipment and interrupt fault current to

    isolate faulted equipment

    Insulators - to insulate equipment from ground and other

    phases

    Isolators (switches) - to create a visible and permanent

    isolation of primary equipment for maintenance purposes and

    route power flow over certain buses.

    Bus - to allow multiple connections (feeders) to the same

    source of power (transformer).

    22

  • 8/12/2019 3. Protection Primer-1

    23/72

    Primary Equipment & Components

    Grounding- to operate and maintain equipment safely

    Arrester- to protect primary equipment of sudden

    overvoltage (lightning strike).

    Switchgearintegrated components to switch, protect, meter

    and control power flow

    Reactors- to limit fault current (series) or compensate for

    charge current (shunt)

    VT and CT - to measure primary current and voltage and

    supply scaled down values to P&C, metering, SCADA, etc.

    Regulators - voltage, current, VAR, phase angle, etc.

    23

  • 8/12/2019 3. Protection Primer-1

    24/72

    Types of Protection

    Overcurrent Uses current to determine magnitude of fault Simple

    May employ definite time or inverse time curves

    May be slow

    Selectivity at the cost of speed (coordination stacks)

    Inexpensive

    May use various polarizing voltages or ground currentfor directionality

    Communication aided schemes make more selective.

    24

  • 8/12/2019 3. Protection Primer-1

    25/72

    Selection of the curves

    uses what is termed as a

    time multiplier or

    time dial to effectively

    shift the curve up or

    down on the time axis

    Operate region lies

    above selected curve,

    while no-operate region

    lies below it.

    Inverse curves can

    approximate fuse curve

    shapes

    Time Overcurrent Protection (TOC)

    25

  • 8/12/2019 3. Protection Primer-1

    26/72

    26

  • 8/12/2019 3. Protection Primer-1

    27/72

    27

  • 8/12/2019 3. Protection Primer-1

    28/72

    Multiples of pick-up

    Time Overcurrent Protection(51, 51N, 51G)

    28

  • 8/12/2019 3. Protection Primer-1

    29/72

    29

    Un Restricted & Restricted Protection

    No Specific Point downstream up to which protection willprotect. Will Operate for faults on the protection equipment. May also operate for faults on downstream equipment

    which has its own protection. Need f0r discrimination with downstream protection

    usually by means of time grading.

    Unrestricted

    Restricted

    Has an accurately defined zone of protection. An item of power plant is protected as a unit Will not operate for out of zone faults thus no back up

    protection for downstream faults

  • 8/12/2019 3. Protection Primer-1

    30/72

    Types of Protection

    Differential

    current in = current out

    Simple

    Very fast

    Very defined clearing area

    Expensive

    Practical distance limitations Line differential systems overcome this using digital

    communications

    30

  • 8/12/2019 3. Protection Primer-1

    31/72

    Types of Protection

    Voltage

    Uses voltage to infer fault or abnormal condition

    May employ definite time or inverse time curves

    May also be used for under voltage loadshedding Simple

    May be slow

    Selectivity at the cost of speed (coordination stacks)

    Inexpensive.

    31

  • 8/12/2019 3. Protection Primer-1

    32/72

    Types of Protection

    Frequency

    Uses frequency of voltage to detect powerbalance condition

    May employ definite time or inverse time curves Used for load shedding & machinery under/over

    speed protection Simple

    May be slow Selectivity at the cost of speed can be expensive

    32

  • 8/12/2019 3. Protection Primer-1

    33/72

    Types of Protection

    Power

    Uses voltage and current to determine power flowmagnitude and direction

    Typically definite time Complex

    May be slow

    Accuracy important for many applications

    Can be expensive

    33

  • 8/12/2019 3. Protection Primer-1

    34/72

    Types of Protection

    Distance (Impedance) Uses voltage and current to determine impedance of fault

    Set on impedance [R-X] plane

    Uses definite time Impedance related to distance from relay

    Complicated

    Fast

    Somewhat defined clearing area with reasonable accuracy Expensive

    Communication aided schemes make more selective

    34

    I d

  • 8/12/2019 3. Protection Primer-1

    35/72

    Impedance

    Relay in Zone 1 operates first

    Time between Zones is called CTI

    Source

    A B

    21 21

    T1

    T2

    ZA

    ZB

    R

    X ZL

    35

  • 8/12/2019 3. Protection Primer-1

    36/72

    1. Overlap is accomplished by the locations of CTs, the key source for protective

    relays.

    2. In some cases a fault might involve a CT or a circuit breaker itself, which

    means it can not be cleared until adjacent breakers (local or remote) are

    opened.

    Zone A Zone B

    Relay Zone A

    Relay Zone B

    CTs are located at both sides of CB-faultbetween CTs is cleared from both remote sides

    Zone A Zone B

    Relay Zone A

    Relay Zone B

    CTs are located at one side of CB-fault between CTs is sensed by both relays,

    remote right side operate only.

    Zone Overlap

    36

  • 8/12/2019 3. Protection Primer-1

    37/72

    1. One-line diagram of the system or area involved2. Impedances and connections of power equipment, system frequency,

    voltage level and phase sequence

    3. Existing schemes

    4. Operating procedures and practices affecting protection

    5. Importance of protection required and maximum allowed clearance

    times

    6. System fault studies

    7. Maximum load and system swing limits

    8. CTs and VTs locations, connections and ratios

    9. Future expansion expectance

    10. Any special considerations for application.

    What Info is Required to Apply Protection

    37

    C T f

  • 8/12/2019 3. Protection Primer-1

    38/72

    Current transformers are used to step primary system currents to

    values usable by relays, meters, SCADA, transducers, etc.

    CT ratios are expressed as primary to secondary; 2000:5, 1200:5,

    600:5, 300:5

    A 2000:5 CT has a CTRof 400

    Current Transformers

    38

  • 8/12/2019 3. Protection Primer-1

    39/72

    39

  • 8/12/2019 3. Protection Primer-1

    40/72

    40

  • 8/12/2019 3. Protection Primer-1

    41/72

    41

  • 8/12/2019 3. Protection Primer-1

    42/72

  • 8/12/2019 3. Protection Primer-1

    43/72

    Typical CT/VT Circuits

    Courtesy of Blackburn, Protective Relay: Principles and Applications

    43

  • 8/12/2019 3. Protection Primer-1

    44/72

    System Grounding

    Limits over voltages

    Limits difference in electricpotential through local area

    conducting objects Several methods

    Ungrounded

    Reactance Coil Grounded

    High Z Grounded Low Z Grounded

    Solidly Grounded

    44

    Prevents shock exposureof personnel

    Provides current

    carrying capability forthe ground-fault current

    Grounding includesdesign and constructionof substation groundmat and CT and VTsafety grounding

    Equipment Grounding

  • 8/12/2019 3. Protection Primer-1

    45/72

    1. Ungrounded: There is no intentional

    ground applied to the system-

    however its grounded through

    natural capacitance. Found in 2.4 -

    15kV systems.

    2. Reactance Grounded: Total system

    capacitance is cancelled by equal

    inductance. This decreases the currentat the fault and limits voltage across the

    arc at the fault to decrease damage.

    X0

  • 8/12/2019 3. Protection Primer-1

    46/72

    3. High Resistance Grounded: Limitsground fault current to 10A-20A. Used

    to limit transient overvoltages due to

    arcing ground faults.

    R0 = 2X0

    System Grounding

    46

  • 8/12/2019 3. Protection Primer-1

    47/72

    5. Solidly Grounded: There is a

    connection of transformer or generatorneutral directly to station ground.

    Effectively Grounded: R0

  • 8/12/2019 3. Protection Primer-1

    48/72

    Substation Types

    Single Supply

    Multiple Supply

    Mobile Substations for emergencies

    Types are defined by number of transformers,

    buses, breakers to provide adequate service

    for application

    48

  • 8/12/2019 3. Protection Primer-1

    49/72

    Industrial Substation Arrangements

  • 8/12/2019 3. Protection Primer-1

    50/72

    Industrial Substation Arrangements(Typical)

    50

    Utilit S b t ti A t

  • 8/12/2019 3. Protection Primer-1

    51/72

    Utility Substation Arrangements

    Single Bus, 1 Tx, Dual supply Single Bus, 2 Tx, Dual Supply 2-sections Bus with HS Tie-Breaker, 2Tx, Dual Supply

    (Typical)

    51

    Utilit S b t ti A t

  • 8/12/2019 3. Protection Primer-1

    52/72

    Breaker-and-a-halfallows reduction ofequipment cost by using 3 breakers for each 2circuits. For load transfer and operation issimple, but relaying is complex as middlebreaker is responsible to both circuits

    Utility Substation Arrangements

    Bus 1

    Bus 2

    Ring busadvantage that one breakerper circuit. Also each outgoing circuit(Tx) has 2 sources of supply. Anybreaker can be taken from servicewithout disrupting others.

    (Typical)

    52

  • 8/12/2019 3. Protection Primer-1

    53/72

    Double Bus: Upper Main andTransfer, bottom Double Main bus

    Main bus

    Aux. bus

    Bus 1

    Bus 2

    Tie

    breaker

    Utility Substation Arrangements

    Main

    ReserveTransfer

    Main-Reserved and Transfer Bus:Allows maintenance of any bus andany breaker

    (Typical)

    53

    S it h D fi d

  • 8/12/2019 3. Protection Primer-1

    54/72

    Switchgear DefinedAssemblies containing electrical switching,

    protection, metering and management devices Used in three-phase, high-power industrial,

    commercial and utility applications

    Covers a variety of actual uses, including motor

    control, distribution panels and outdoorswitchyards

    The term "switchgear" is plural, even whenreferring to a single switchgear assembly (never

    say, "switchgears") May be a described in terms of use:

    "the generator switchgear"

    "the stamping line switchgear"54

  • 8/12/2019 3. Protection Primer-1

    55/72

    Switchgear Examples

    55

  • 8/12/2019 3. Protection Primer-1

    56/72

    A Good Day in System Protection

    CTs and VTs bring electrical info to relays

    Relays sense current and voltage and declare fault

    Relays send signals through control circuits to circuit

    breakers

    Circuit breaker(s) correctly trip

    What Could Go Wrong Here????

    56

  • 8/12/2019 3. Protection Primer-1

    57/72

    A Bad Day in System Protection

    CTs or VTs are shorted, opened, or their wiring is Relays do not declare fault due to setting errors, faulty relay,

    CT saturation

    Control wires cut or batteries dead so no signal is sent from

    relay to circuit breaker Circuit breakers do not have power, burnt trip coil or

    otherwise fail to trip

    Protection Systems Typically are

    Designed for N-1

    57

  • 8/12/2019 3. Protection Primer-1

    58/72

    Contribution to Faults

    58

  • 8/12/2019 3. Protection Primer-1

    59/72

    Fault Types (Shunt)

    59

  • 8/12/2019 3. Protection Primer-1

    60/72

    FAULTS IN UNDERGROUND CABLES

    60

  • 8/12/2019 3. Protection Primer-1

    61/72

    61

    Faults in Overhead Lines

  • 8/12/2019 3. Protection Primer-1

    62/72

    62

    Faults in Machines

  • 8/12/2019 3. Protection Primer-1

    63/72

    63

    Type of Fault

  • 8/12/2019 3. Protection Primer-1

    64/72

    64

    Type of Faults

  • 8/12/2019 3. Protection Primer-1

    65/72

    65

    Type of Fault

  • 8/12/2019 3. Protection Primer-1

    66/72

    66

    Type of Cable Faults

  • 8/12/2019 3. Protection Primer-1

    67/72

    AC & DC Current Components

    of Fault Current

    67

    P U i B i

  • 8/12/2019 3. Protection Primer-1

    68/72

    Per Unit Basics

    68

    Establish two basequantities:

    Standard practice isto define Base power 3 phase

    Base voltage line toline

    Other quantities

    derived with basicpower equations

    Short Circuit Calculations

  • 8/12/2019 3. Protection Primer-1

    69/72

    Short Circuit Calculations

    Per Unit System

    Per Unit Value = Actual QuantityBase Quantity

    Vpu = VactualVbase

    Ipu = Iactual

    Ibase

    Zpu = ZactualZbase

    69

  • 8/12/2019 3. Protection Primer-1

    70/72

    A Study of a Fault.

    70

  • 8/12/2019 3. Protection Primer-1

    71/72

    71

  • 8/12/2019 3. Protection Primer-1

    72/72

    YBL Systems and Solutions

    (Electrical Power System Research Consultants)

    www.sasidharan.webs.com

    Regards,