3064203 bm-2 programming unit installation instructions for

84
Installation instructions for contractors BM-2 programming unit Wolf GmbH Postfach 1380 D-84048 Mainburg Tel. +49-8751/74-0 Fax +49-8751/741600 Internet: www.wolf-heiztechnik.gb Document no.: 3064203_201508 Subject to technical modifications GB 14:12 20.01.13 1.5 bar 25.2 °C 1x Heating appliance Heating appliance Heating mode Pressure Burner ON

Upload: buidung

Post on 01-Feb-2017

228 views

Category:

Documents


4 download

TRANSCRIPT

Page 1: 3064203 BM-2 programming unit Installation instructions for

Vorlage Montageanleitungen_Umschlag 13.11.12 10:21 Seite 1

Installation instructions for contractors

BM-2 programming unit

Wolf GmbH • Postfach 1380 • D-84048 Mainburg • Tel. +49-8751/74-0 • Fax +49-8751/741600 • Internet: www.wolf-heiztechnik.gbDocument no.: 3064203_201508 Subjecttotechnicalmodifications GB

14:12 20.01.13

1.5 bar

25.2 °C

1x

Heating appliance

Heating appliance

Heating mode

Pressure

Burner ON

Page 2: 3064203 BM-2 programming unit Installation instructions for

2 3064203_201508

1 Checking the standard delivery 7

2 Appliance description 8

3 Safety and regulations 9

3.1 General safety instructions 9

3.2 Standards / directives 9

3.3 Installation / commissioning 9

3.4 CE designation 9

3.5 Symbols and warnings 10

3.5.1 Layout of warnings 10

4 Installation 11

4.1 Installation site requirements 11

4.2 Fitting / removing the BM-2 programming unit

in heating appliances 11

4.2.1 BM-2 programming unit in the CGB-2 11

4.2.2 BM-2 programming unit in the TOB 12

4.2.3 BM-2 programming unit in the MGK-2 12

4.3 Installing the BM-2 programming unit

with the wall mounting base 13

4.4 Electrical installation of the wall mounting base 14

4.5 Installing the outside sensor 15

5 Overview of the BM-2 programming unit 16

6 Quick start keys/rotary selector 17

7 Pressing the quick start keys 18

8 Overview of status pages 19

Table of contents

Page 3: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 3

9 Heating appliance status page 20

9.1 Using the key for 1x DHW heating 20

9.2 Using the key for emissions test mode 21

10 DHW status page 22

10.1 Changing the set DHW temperature 22

10.2 Changing the DHW operating mode 22

11 Heating circuit status page 23

11.1 Changing the set heating circuit temperature 23

11.2 Changing the heating circuit operating mode 23

12 Mixer status page 24

12.1 Changing the set mixer circuit temperature 24

12.2 Changing the mixer circuit operating mode 24

13 Solar thermal system status page 25

Display only

14 Ventilation unit status page 26

14.1 Changing the operating mode / Start - End / ON - OFF 26

15 Messages status page 27

15.1 Procedure for faults 27

15.2 Procedure for warnings 27

15.3 Acknowledging faults for users 27

15.4 Acknowledging faults for contractors 28

16 Main menu overview 29

16.1 Display of set / actual temperatures (chapter 17) 29

16.2 Default settings (chapter 18) 29

16.3 Time programs (chapter 19) 29

16.4 Contractor level (chapter 20) 29

Table of contents

1x

Page 4: 3064203 BM-2 programming unit Installation instructions for

4 3064203_201508

17 Set / actual temperature display 30

18 Default settings overview 31

18.1 Heating appliance 31

18.1.1 DHW operating mode 31

18.2 Heating circuit / mixer circuits 1-7 31

18.2.1 Setting economy factor in economy mode 32

18.2.2 Setting winter/summer changeover 32

18.2.3 Setting ECO ABS 33

18.2.4 Setting day temperature (room temperature) 33

18.2.5 Settingroominfluence 33

18.3 Language 34

18.4 Time 34

18.5 Date 34

18.6 Minimum backlighting 35

18.7 Screensaver 35

18.8 Key lock 35

19 Time programs 36

19.1 Pre-programmed switching times 36

19.2 Enabled time program 37

19.3 Displaying / selecting switching times 38

19.4 Editing switching times 39

19.5 Adding switching times 39

19.6 Deleting switching times 39

19.7 Copying switching times 40

20 Password for contractor level 41

21 Contractor level menu structure 42

22 Contractor level, system 43

22.1 Setting system parameters – example 43

22.2 Complete list of system parameters 44

22.2.1 BM-2 function (BUS address) 44

22.3 Description of system parameters 45

22.3.1 Settingtheroominfluencefactor(A00) 45

Table of contents

Page 5: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 5

22.3.2 Setting average outside sensor (A04) 45

22.3.3 Setting the pasteurisation function (A07) 45

22.3.4 Setting the frost protection limit (A09) 46

22.3.5 Enabling parallel operation (A10) 46

22.3.6 Room temperature shutdown (A11) 47

22.3.7 Setting setback stop (A12) 47

22.3.8 Setting the minimum DHW temperature (A13) 47

22.3.9 P component for room temperature PI controller (A17) 48

22.3.10 I component for room temperature PI controller (A18) 48

22.3.11 Start time of pasteurisation function (A23) 48

23 Contractor level, heating appliance 49

23.1 Setting the heating appliance 49

23.1.1 Complete list of heating appliance parameters 50

23.1.2 Relay test for CGB-2 heating appliance 51

23.1.3 Heating appliance parameter reset 52

24 Contractor level, heating circuit 53

24.1 Setting the heating curve 53

24.2 Heating curve description 54

24.3 Setting heating circuit screed drying 55

24.3.1 OFF 55

24.3.2 Automatic 55

24.3.3 Constant temperature 55

25 Contractor level, cascade module 56

25.1 Complete list of cascade module parameters 57

25.2 Relay test cascade module 57

26 Contractor level, mixer circuit 58

26.1 Heating curve – mixer 59

26.2 Complete list of mixer module parameters 59

26.3 Mixer relay test 59

26.4 Screed drying settings, mixer circuit 60

26.4.1 OFF 60

26.4.2 Automatic 60

26.4.3 Constant temperature 60

Table of contents

Page 6: 3064203 BM-2 programming unit Installation instructions for

6 3064203_201508

27 Contractor level, solar 61

27.1 Complete list of solar module parameters 61

28 Contractor level, ventilation unit 62

29 Contractor level, fault history 63

30 Heating curve / economy factor 64

30.1 Heating curves overview 64

30.2 Temperature selection -4 ... +4 for heating circuit 64

30.3 Economy factor 0 to 10 for heating circuit 65

30.4 Economy mode – calculation example 65

30.5 Temperature selection -4...+4, mixer circuit 66

30.6 Economy factor 0 to 10, mixer circuit 66

31 Overview of symbols 67

31.1 Symbols for the quick start keys 67

31.2 Symbols for possible changes using the rotary selector 68

31.3 Symbols in the status display 70

31.4 Symbols in the time programs submenu 71

32 Faults 72

32.1 Warning messages 74

33 Shutdown and disposal 75

33.1 Shutdown 75

33.2 Disposal and recycling 75

33.3 Maintenance / cleaning 75

34 Documentation information 76

34.1 Other applicable documents 76

34.2 Safekeeping of these documents 76

34.3 Applicability of these instructions 76

34.4 Handover to the user 76

35 Specification 77

36 Commissioning assistant 78

37 Composite system data sheet according to

EU regulation no. 811/2013 79

38 Keyword index 80

Table of contents

Page 7: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 7

Checking the standard delivery

1 Checking the standard delivery

Vorlage Montageanleitungen_Umschlag 13.11.12 10:21 Seite 1

Montageanleitung für den Fachhandwerker

Bedienmodul BM-2

Wolf GmbH • Postfach 1380 • 84048 Mainburg • Tel. 08751/74-0 • Fax 08751/741600 • Internet: www.wolf-heiztechnik.deWOLF Klima- und Heiztechnik GmbH • Eduard-Haas-Str. 44 • 4030 Linz • Tel. 0043-732/385041-0 • Internet: www.wolf-heiztechnik.atWolf Schweiz AG · Dorfstrasse 147 · 8802 Kilchberg · Tel.0 041/5004800 · Fax 0041/435004819 · Internet: www.wolf-heiztechnik.chArt.-Nr.: 3063305_201311 Änderungen vorbehalten

DE ATCH

14:12 20.01.2013

1,5 bar

25,2 °C1x

Heizgerät

Heizgerät

Heiz-/Warmwasserbetrieb

Druck

Vorlage Montageanleitungen_Umschlag 13.11.12 10:21 Seite 1

Montageanleitung für den Fachhandwerker

Bedienmodul BM-2

Wolf GmbH • Postfach 1380 • 84048 Mainburg • Tel. 08751/74-0 • Fax 08751/741600 • Internet: www.wolf-heiztechnik.deWOLF Klima- und Heiztechnik GmbH • Eduard-Haas-Str. 44 • 4030 Linz • Tel. 0043-732/385041-0 • Internet: www.wolf-heiztechnik.atWolf Schweiz AG · Dorfstrasse 147 · 8802 Kilchberg · Tel.0 041/5004800 · Fax 0041/435004819 · Internet: www.wolf-heiztechnik.chArt.-Nr.: 3063305_201311 Änderungen vorbehalten

DE ATCH

14:12 20.01.2013

1,5 bar

25,2 °C1x

Heizgerät

Heizgerät

Heiz-/Warmwasserbetrieb

Druck

No. Designation BM-2 without outside sensor

Part no. 2745306

BM-2 with outside sensor

Part no. 2745304

1Installation instructions

for contractors1 1

2Operating

instructions for users

1 1

3Outside sensor incl. screws and

rawl plugs1

4 BM-2 programming unit 1 1

1

2

4

3

Page 8: 3064203 BM-2 programming unit Installation instructions for

8 3064203_201508

Appliance description

2 Appliance description

f Intended use

The Wolf BM-2 programming unit is for use exclusively in conjunction with Wolf heating appliances and Wolf accessories.The Wolf BM-2 programming unit is used to control the entire heating system and tosetspecificheatingparameters.Intended use also includes observing the operating instructions and all other applicable documents.

Please note:

• TheBM-2programmingunitcan also be installed as a remote control, which requires the integration of an AM display module in the heating appliance.

f Incorrect use

Any use other than the intended use is not permissible. Any other use or changes totheproductatanytimeincludingduringfittingandinstallationinvalidateallwarranty claims. The user has sole liability for such use.

This appliance is not designed to be operated by persons (including children) with restricted physical, sensory or mental capacities or who lack the necessary experience and/or knowledge, unless they are supervised by a person responsible for their safety or have received instructions on how to use the appliance from this person.

14:12 20.01.13

1.5 bar

25.2 °C

1x

Heating appliance

Heating appliance

Heating mode

Pressure

Burner ON

Page 9: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 9

Safety and regulations

3 Safety and regulationsThe general safety instructions must be observed.

3.1 General safety instructionsTheBM-2programmingunitmustbeinstalledandcommissionedbyaqualifiedcontractor.

f Before installing the BM-2, disconnect the power supply from the heating appliance and all connected components.

f Be aware that there is mains power to the electrics, even when the heating appliance mains isolator is off.

f Only replace damaged or faulty components with original Wolf spare parts. f Do not remove, bypass or disable any safety and monitoring equipment. f Only run the system when it is in perfect technical condition. f Immediately rectify any faults and damage that impair safety. f If the domestic hot water temperature is set above 60 °C, install a thermostatic water mixer.

f Route mains power cables with a voltage of 230 V in a physically separate place to the eBUS cables.

f Electronic assemblies can be damaged by an electrical discharge. Touch earthed objects, e.g. heating or water pipes, before carrying out any work, in order to discharge the static charge.

3.2 Standards / directivesThe appliance and control accessories comply with the following regulations:

EC Directives f 2006/95/EC Low Voltage Directive f 2004/108/EC EMC Directive

EN Standards f EN 55014-1 Emission f EN 55014-2 Immunity f EN 60335-2-102 f EN 60529

3.3 Installation / commissioning

f AccordingtoEN50110-1,onlyqualifiedelectriciansmaycarryouttheinstallationand commissioning of the heating control unit and connected accessories.

f Observe all local and electrical regulations. f Observe all regulations regarding the installation of HV systems up to 1000 V. f Observe all local regulations regarding the installation of electrical systems.

3.4 CE designationWiththeCEdesignation,weasthemanufacturerconfirmthattheBM-2programming unit conforms to the basic requirements of the Electromagnetic Compatibility Directive (Council Directive 2004/108/EEC). The BM-2 programming unitfulfilsthebasicrequirementsoftheLowVoltageDirective(CouncilDirective2006/95/EEC).

Page 10: 3064203 BM-2 programming unit Installation instructions for

10 3064203_201508

Safety and regulations

3.5 Symbols and warnings

Symbol for additional information

f Symbol for a necessary action

Warnings in the text warn you of possible risks before the start of an instruction. The warnings provide you with information on the possible severity of the risk using a pictogram and a keyword.

Pictogram Keyword Explanation

Danger! Risk to life or risk of serious injury

Danger! Risk to life or risk of serious injury through electrocution

Warning Slight risk of injury

Caution Possible material damage

Table 3.1 Meaning of warnings

3.5.1 Layout of warnings

You will recognise warnings in these instructions by pictograms and a line above and below the warning section. These warnings are laid out as follows:

Keyword

Type and source of risk.Explanation of the risk.

f Instruction to prevent the risk.

Page 11: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 11

Installation

4 InstallationThe BM-2 programming unit can be installed in the following appliances:

CGB-2, CGS-2, CGW-2, CSZ-2, MGK-2 and TOB

and also be used as a remote control for the KM, MM, SM1, SM2, BWL-1-S(B) and CWL Excellent.

The BM-2 programming unit cannot be combined with the BM programming unit.

4.1 Installation site requirements

The installation site must be dry and permanently frost free.

4.2 Fitting / removing the BM-2 programming unit in heating appliances

− The installation site requirements for the heating appliance apply. − Please note the information in the heating appliance installation instructions. − WhenfittingtheBM-2programmingunit,pressuntilitclicksintoplace. − To remove the BM-2 programming unit, press down the locking snap on the

reverse using a screwdriver.

4.2.1 BM-2 programming unit in the CGB-2

f Switch OFF the heating appliance with the ON/OFF switch (Wolf logo). f Switch OFF the power supply to the appliances. f Secure the power supply against reconnection. f Fit the BM-2 programming unit into the base. f Switch ON the power supply to the appliances. f Switch ON the heating appliance with the ON/OFF switch (Wolf logo).

Fig. 4.1 Fitting the BM-2 programming unit in the CGB-2

21

3

ON/OFF switch

Page 12: 3064203 BM-2 programming unit Installation instructions for

12 3064203_201508

Installation

4.2.2 BM-2 programming unit in the TOB

f Switch OFF the heating appliance with the ON/OFF switch (Wolf logo). f Switch OFF the power supply to the appliances. f Secure the power supply against reconnection. f Fit the BM-2 programming unit into the base. f Switch ON the power supply to the appliances. f Switch ON the heating appliance with the ON/OFF switch (Wolf logo).

Fig. 4.2 Fitting the BM-2 programming unit in the TOB

4.2.3 BM-2 programming unit in the MGK-2

f Switch OFF the heating appliance with the ON/OFF switch (Wolf logo). f Switch OFF the power supply to the appliances. f Secure the power supply against reconnection. f Fit the BM-2 programming unit into the base. f Switch ON the power supply to the appliances. f Switch ON the heating appliance with the ON/OFF switch (Wolf logo).

Fig. 4.3 Fitting the BM-2 programming unit in the MGK-2

2 3

ON/OFF switch1

ON/OFF switch

1

23

Page 13: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 13

Installation

4.3 Installing the BM-2 programming unit with the wall mounting base

− The installation site should be located in a reference room (e.g. living room). − Aroomtemperaturesensorshouldbefittedataheightof1.5m. − The BM-2 programming unit and the room temperature sensor must not be subject

to draughts or direct radiated heat. − The BM-2 programming unit must not be concealed behind curtains or furniture. − All radiator valves in the reference room must be fully opened.

f Fixthewallmountingbaseonaflushbox(Ø60mm)OR

f Fix the wall mounting base to the wall using screws and rawl plugs

Fig. 4.4 FittingtheBM-2wallmountingbasetotheflushbox(on site)

Fig. 4.5 Fitting the BM-2 wall mounting base to the wall using screws and rawl plugs

Fig. 4.6 Fitting the BM-2 programming unit into the wall mounting base guide from above

68

35

60

113

Page 14: 3064203 BM-2 programming unit Installation instructions for

14 3064203_201508

Installation

4.4 Electrical installation of the wall mounting base

Danger!Danger to life through incorrect installation!Incorrect electrical installation can cause a danger to life.

f Ensurethatonlyaqualifiedelectricianundertakeselectricaltheinstallationoftheunit.

f All electrical work must be carried out in accordance with approved rules and guidelines.

Danger!Danger to life through electrocution!The terminals are 'live' even when the ON/OFF switch is in the OFF position.

f Switch OFF the power supply to the appliances. f Secure the power supply against reconnection.

On the heating appliance f See also the heating appliance installation instructions. f Switch OFF the heating appliance. f Switch OFF the power supply to the appliances. f Secure the power supply against reconnection. f Connect the eBUS connecting cables to the supplied heating appliance plugs. f Insert the plug into the designated location in the plug-in strip of the heating appliance control unit.

f Securethecablewithastrainrelieffitting.

On the wall mounting base f Connect the eBUS cable to the heating appliance via terminals 1(+) and 2(-). f Connect the remote switching contact via terminals 3 and 4 (optional). f Connect the outside sensor via terminals 5 and 6 (optional).

Remote switching contact f Withafloatingremote switching contact, you can enable the heating system for constant heating and DHW.

f The heating system operates in the set operating mode if the remote switching contact remains open.

f Reconnect all accessories in parallel with the control unit eBUS if you wish to connect several remote controls or a radio clock module.

f Be aware of correct polarity (+, -).

Fig. 4.7 Terminalblockconfigurationforwallmountingbase

1(+) / 2(-) = eBUS connection; observe correct polarity

3 / 4 = Remote switching contact5 / 6 = Outside sensor

1 2 3 4 5 6+ -

ϑ

Page 15: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 15

Installation

4.5 Installing the outside sensor

The outside sensor should be installed on a north or north-east facing external wall of the building at a height of 2 to 2.5 m.

Caution f Incorrect installation can cause moisture penetration of the external wall or damage to the outside sensor.

f Material damage due to moisture penetration.

− Use an existing empty conduit or wiring installed on-site for cable entry. − Use the external wireless sensor if no empty conduit is available. − Route the connecting cable with a drip loop. − Seal the casing of the outside sensor tightly. − If possible, connect the outside sensor to the heating appliance. − You can also connect the outside sensor to the wall mounting base. − Before installing the radio clock module, use the outside sensor to test

provisional reception of the DCF time signal*. − Route the eBUS cables in a physically separate place to the power cables.

* The DCF time signal transmits the exact time and the current date.

Terminal assignment, outside sensor

Fig. 4.8 Connecting the outside sensor to the heating appliance

1 Connection to the heating appliance AF terminal2 Outside sensor

Fig. 4.9 Connecting the radio clock module with the outside sensor (accessory)

1 eBUS connection to wall mounting base or heating appliance / extension module terminals

2 Outside sensor

Fig. 4.10 Connecting the external wireless sensor (accessory)

1 Wireless receiver2 eBUS connection3 External wireless sensor

Page 16: 3064203 BM-2 programming unit Installation instructions for

16 3064203_201508

Overview of the BM-2 programming unit

5 Overview of the BM-2 programming unit

After switching on the heating appliance, the software loads, and a progress bar and the Wolf logo appear. You are then taken to the start page (home page).

An automatic restart of all BM-2 units in the WRS is also performed after the following actions − Changetoasystemconfiguration(heatingappliance/extensionmodule) − Change to a function in the BM-2 (contractor – system) − Change to a parameter value on the heating appliance

FW x.xx

Software version

Key 1

Key 2

Key 3

Key 4 14:12 20.01.13

1.5 bar

25.2 °C

1x

Boiler temperature

Heating appliance

Heating mode

Pressure

Status display

Page heading

Time Date

Rotary selector with pushbutton function

Function display Quick start keys

System data display (content varies)

Quick start keysOperating mode

Burner status

Burner ON

eBUS connection No eBUS connection

Page 17: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 17

Quick start keys/rotary selector

6 Quick start keys/rotary selector

The 4 quick start keys and the rotary selector are used to program the BM-2.

The following settings canbeconfiguredusingthequickstartkeys:

− Key 1 – without function display, no function − Key 2 – variable functions (e.g. once-only DHW heating) − Key 3 – variable functions (e.g. enabling emissions test) − Key 4 – home key

Turn the rotary selector to switch between the individual status pages.

− Heating appliances − DHW − Heating circuit − Mixer − Solar yield − Ventilation unit − Messages

The main menu of the display, default settings, time programs and contractor level are enabled by pressing the rotary selector; the navigation is explained in the following chapter.

Activation and operation in the main menu / submenu / menu item

Operating procedure:

Press the rotary selector to access the main menu page. Press the again to access the submenu, and once more to access the menu item.The following actions are possible:

Clockwise rotation Cursor moves down through the menu Selected value is increased Selected parameter is increased

Anti-clockwise rotation Cursor moves up through the menu Selected value is decreased Selected parameter is decreased

Press rotary selector Menuselectionisconfirmedorenabled Selectedvalueisconfirmedorenabled Selectedparameterisconfirmedorenabled Selected function is executed or enabled

For visual orientation, a cursor is displayed that shows the current position in the display. Press the rotary selector once to highlight the currently selected item for editing. Turn the rotary selector to change the value, parameter or function.Presstheselectoragaintoconfirmthevalue.

Page 18: 3064203 BM-2 programming unit Installation instructions for

18 3064203_201508

Pressing the quick start keys

7 Pressing the quick start keys

Press quick start keys to perform the displayed functions. The functions vary according to the current status page.

Key 1

Key 2

Key 3

Key 4 14:12 20.01.13

1.5 bar

25.2 °C

1x

Boiler temperature

Heating appliance

Heating / DHW mode

Pressure

Page 19: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 19

Overview of status pages

8 Overview of status pages

Turn the rotary selector to display the different status pages. This enables the installed heatingappliancesandextensionmoduleswiththeassociatedconfigurations.

9 - Heating appliance

10 - DHW

11 - Heating circuit

12 - Mixer

13 - Solar

14 - Ventilation unit

15 - Messages

Values are only displayed for modules that are connected (mixer module MM, cascade module KM, solar module SM1/2, CWL-Excellent).

Setting options Info regarding system data − Once-only DHW heating − Operating mode − Emissions test mode

(BM-2 in heating appliance) − Burner status

− Call up home page − Heating appliance temp. − System pressure − Burner output

Setting options Info regarding system data − Change set DHW temperature − Selected DHW temperature − Change operating mode − Selected operating mode − Call up home page − DHW temp.

− Set DHW temperature

Setting options Info regarding system data − Change set heating circuit temperature − Selected temperature − Change operating mode − Selected operating mode − Call up home page − Room temperature

(BM-2 as remote control) − Outside temperature

(with outside temp. sensor in WRS) − Flow temperature

Setting options Info regarding system data − Change set mixer circuit temperature − Selected temperature − Change operating mode − Selected operating mode − Call up home page − Room temperature

− Outside temperature − Flow temperature

Display Info regarding system data − Monthly yield − Collector temperatures − Annual yield − Cylinder temperatures

Setting options Info regarding system data − Change operating mode − Selected operating mode − Call up home page − Airflowrate/extractairtemp.

Setting options Info regarding system data − Acknowledging faults for users − Current faults − Acknowledging faults for contractors

(locking faults)

Page 20: 3064203 BM-2 programming unit Installation instructions for

20 3064203_201508

Heating appliance status page

9 Heating appliance status page

If a KM module is integrated in the Wolf control system (WRS), then up to 4 heating appliances can also be connected. Each heating appliance is then displayed with its own status page.

9.1 Using the 1x key for 1x DHW heating

The special function 1x DHW bypasses the programmed switching times and heats up the DHW cylinder once, for one hour, to the set DHW temperature.

− Once-only DHW heating (displayed for all heating appliances) − All connected DHW cylinders are heated − Press key 2 again to disable once-only DHW heating − You are taken back to the home page after 5 seconds

Key 2

14:12 20.01.13

1.5 bar

1x

Once-only DHW heating enabled

Heating appliance

Heating mode

1x

Burner ON

Pressure

14:12 20.01.13

1.5 bar

25.2 °C

1x

Boiler temperature

Heating appliance

Heating mode

Burner ON

Pressure

1x DHW heating

enable

Screen display changes

Key 2

14:12 20.01.13

1.5 bar

25.2 °C

1x

Boiler temperature

Heating appliance

Heating mode

Burner ON

Pressure

1x DHW heating

disable

14:12 20.01.13

1.5 bar

1x

Once-onlyDHW heatingdisabled

Heating appliance

Heating mode

1x

Burner ON

Pressure

Screen display changes

Page 21: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 21

Heating appliance status page

9.2 Using the key for emissions test mode

− Variable functions (e.g. enabling emissions test). − Emissions testing is only displayed if the BM-2 is installed in the heating appliance.

Once the emissions test function (key 3) has been enabled, the burner runs for 15 minutes and the time counts down on the display. The time can be extended back to 15 minutes by pressing key 3 again.

Key 2

14:12 20.01.13

1.5 bar

25.2 °C

1x

Boiler temperature

Heating appliance

Heating / DHW mode

Pressure

14:12 20.01.13

1.5 bar

25.2 °C

1x

Boiler temperature

Heating appliance

Heating mode

Burner ON

Pressure

Key 3

Key 4

Back one level

Extend time

Home page

14:12 20.01.13

20 °C40.0 °C

T_returnBoiler temperature

Flue gas test

Flue gas test active

08 min

Rem. time

14:12 20.01.13

20 °C40.0 °C

T_returnBoiler temperature

Flue gas test

Flue gas test active

15 min

Rem. time

Key 3

14:12 20.01.13

1.5 bar

25.2 °C

1x

Boiler temperature

Heating appliance

Heating mode

Heating mode ON

PressureFlue gas test

Screen display changes

Screen display changes

Screen display changes

Screen display changes

14:12 20.01.13

2040.0 °C

T_returnBoiler temperature

Flue gas test

Flue gas test active

15 min

Rem. time

14:12 20.01.13

20 °C40.0 °C

T_returnBoiler temperature

Flue gas test

Flue gas test active

08 min

Rem. time

14:12 20.01.13

20 °C40.0 °C

T_returnBoiler temperature

Flue gas test

Flue gas test active

08 min

Rem. time

Page 22: 3064203 BM-2 programming unit Installation instructions for

22 3064203_201508

DHW status page

10 DHW status pageUp to 8 cylinders can be connected to the WRS. DHW heating for each cylinder is controlled by its own status page.

10.1 Changing the set DHW temperature

10.2 Changing the DHW operating mode

(For description of operating modes, see chapter 31 – Overview of symbols)

Return to the home page

Danger!Risk of scalding from hot water!Hot water temperatures in excess of 65 °C can result in scalding.

f Do not set the DHW temperature above 65 °C.

14:12 20.01.13

DHW

25, 30, 35, 40, 45, 50, 55, 60, 65

50.0

Change using rotary selectorConfirmwithOK

Key 3

14:12 20.01.13

DHW

Continue with rotary selectorConfirmwithOK

1x reheatAutomatic modeConstant op.Standby

1x

14:12 20.01.13

50.0 °C50.0 °CSetDHW

DHW

ON25, 30, 35, 40, 45, 50, 55, 60, 65

Key 414:12 20.01.13

1.5 bar

25.2 °C

1x

Pressure

Boiler temperature

Heating appliance

Heating mode

Burner ON

Change

Confirm14:12 20.01.13

50.0 °C50.0 °CSetDHW

DHW

ON25, 30, 35, 40, 45, 50, 55, 60, 65Key 2

Change

Confirm14:12 20.01.13

50.0 °C50.0 °CSetDHW

DHW

ON25, 30, 35, 40, 45, 50, 55, 60, 65

14:12 20.01.13

50.0 °C50.0 °CSetDHW

DHW

ON25, 30, 35, 40, 45, 50, 55, 60, 65

Home page

Page 23: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 23

Heating circuit status page

11 Heating circuit status page

11.1 Changing the set heating circuit temperature

(For description of temperature selection, see chapter 30 – Heating curve / economy factor)

11.2 Changing the heating circuit operating mode

(For description of operating modes, see chapter 31 – Overview of symbols)

Return to the home page

Key 3

Key 414:12 20.01.13

1.5 bar

25.2 °C

1x

Pressure

Boiler temperature

Heating appliance

Heating mode

Burner ON

Change

Confirm

Key 2

Change

Confirm

Home page

14:12 20.01.13

20.0 °C

Room

Heating circuit

OFF-4, -3, -2, -1, 0, +1, +2, +3, +4

40.0 °CFlow

16.0 °COutside

14:12 20.01.13

20.0 °C

Room

Heating circuit

OFF-4, -3, -2, -1, 0, +1, +2, +3, +4

40.0 °CFlow

16.0 °COutside

14:12 20.01.13

20.0 °C

Room

Heating circuit

OFF-4, -3, -2, -1, 0, +1, +2, +3, +4

40.0 °CFlow

16.0 °COutside

14:12 20.01.13

20.0 °C

Room

Heating circuit

OFF-4, -3, -2, -1, 0, +1, +2, +3, +4

40.0 °CFlow

16.0 °COutside

14:12 20.01.13

Heating circuit

Continue with rotary selectorConfirmwithOK

Party functionSetback modeAutomatic modeHeating modeEconomy modeStandby

14:12 20.01.13

Heating circuit

+1

Change using rotary selectorConfirmwithOK

-4, -3, -2, -1, 0, +1, +2, +3, +4

Page 24: 3064203 BM-2 programming unit Installation instructions for

24 3064203_201508

Mixer status page

12 Mixer status pageUp to 7 mixer modules can be connected to the WRS and operated via the BM-2. Each mixer module is controlled via its own status page.

12.1 Changing the set mixer circuit temperature

(For description of temperature selection, see chapter 30 – Heating curve / economy factor)

12.2 Changing the mixer circuit operating mode

(For description of operating modes, see chapter 31 – Overview of symbols)

Return to the home page

14:12 20.01.13

20.0 °C

Room

Mixer

OFF-4, -3, -2, -1, 0, +1, +2, +3, +4

25.0 °CFlow

16.0 °COutside

1

14:12 20.01.13

Mixer

+1

Change using rotary selectorConfirmwithOK

-4, -3, -2, -1, 0, +1, +2, +3, +4

1

14:12 20.01.13

Mixer

Continue with rotary selectorConfirmwithOK

Party functionSetback modeAutomatic modeHeating modeEconomy modeStandby

1

Key 3

Key 414:12 20.01.13

1.5 bar

25.2 °C

1x

Pressure

Boiler temperature

Heating appliance

Heating mode

Burner ON

Change

Confirm

Key 2

Change

Confirm

Home page

14:12 20.01.13

20.0 °C

Room

Mixer

OFF-4, -3, -2, -1, 0, +1, +2, +3, +4

25.0 °CFlow

16.0 °COutside

1

14:12 20.01.13

20.0 °C

Room

Mixer

OFF-4, -3, -2, -1, 0, +1, +2, +3, +4

25.0 °CFlow

16.0 °COutside

1

14:12 20.01.13

20.0 °C

Room

Mixer

OFF-4, -3, -2, -1, 0, +1, +2, +3, +4

25.0 °CFlow

16.0 °COutside

1

Page 25: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 25

Solar thermal system status page

13 Solar thermal system status pageThe solar thermal system settings are only displayed if a solar module has been recognised.

Actual collector temperature / actual cylinder temperature

Monthly yield

Annual yield

Return to the home page

Key 3

Key 414:12 20.01.13

1.5 bar

25.2 °C

1x

Pressure

Boiler temperature

Heating appliance

Heating mode

Burner ON

DisplayKey 2

Display

Home page

14:12 20.01.13

Solar thermal system

Collector 1 75 °CCollector 2 75 °CCylinder 1 60 °CCylinder 2 60 °C

14:12 20.01.13

Solar thermal system

Collector 1 75 °CCollector 2 75 °CCylinder 1 60 °CCylinder 2 60 °C

14:12 20.01.13

Solar thermal system

Collector 1 75 °CCollector 2 75 °CCylinder 1 60 °CCylinder 2 60 °C

14:12 20.01.13

Solar thermal system

Collector 1 75 °CCollector 2 75 °CCylinder 1 60 °CCylinder 2 60 °C

14:12 20.01.13

Solar thermal systemMonthly solar yields

01 02 03 04 05 06 07 08 09 10 11 12

1000

14:12 20.01.13

Solar thermal system

2010 - 2013

1000

Annual solar yields

Page 26: 3064203 BM-2 programming unit Installation instructions for

26 3064203_201508

Ventilation unit status page

14 Ventilation unit status page

The ventilation unit status page is only displayed if a CWL Excellent is connected to the WRS. Please note: Parallel operation in conjunction with a BML is not possible.

14.1 Changing the operating mode / Start - End / ON - OFF

(For description, see chapter 28 – Contractor level, ventilation unit)

For pre-programmed switching times in automatic mode, see chapter 19.1

Return to the home page

Key 414:12 20.01.13

1.5 bar

25.2 °C

1x

Pressure

Boiler temperature

Heating appliance

Heating mode

Burner ONHome page

14:12 20.01.13

49 m³/hAirflowrate

OFF

22.2 °CExt. air

Ventilation unit

Key 3

Change

Confirm

Call up

Select

14:12 20.01.13

Ventilation unit

Turn to change valuesPresstoconfirm

Start: 18.01.2014 11:03End: 19.01.2014 12:15

OFFON

Tempor. moist. prot. enabled

14:12 20.01.13

Continue with rotary selectorConfirmwithOK

Automatic modeTempor. moist. prot.Reduced vent.Std ventilationTempor. intens. vent.

Ventilation unit

14:12 20.01.13

49 m³/hAirflowrate

OFF

22.2 °CExt. air

Ventilation unit

Change

Confirm

14:12 20.01.13

49 m³/hAirflowrate

OFF

22.2 °CExt. air

Ventilation unit

Page 27: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 27

Messages status page

15 Messages status page

15.1 Procedure for faults

− Read fault message − Possible causes for the fault and remedies can be found in the "Faults" chapter − Determine and remedy the cause of the fault

A fault can be cleared on the fault message status page by pressing key 3. BM-2 installed in the heating appliance.

− Check that the system is functioning correctly

15.2 Procedure for warnings

− Read warning message − Possible causes for the warning and remedies can be found in the "Faults" chapter − Determine and remedy the cause of the warning message − With warnings there is no need to acknowledge the fault − Check that the system is functioning correctly

15.3 Acknowledging faults for users

In case of a fault, the current fault is displayed along with the fault code, date and time.

The fault can be cleared by pressing the acknowledge key.

General informationNever remove, bypass or otherwise disable any safety or monitoring equipment. Only operate the heating appliance when it is in perfect technical condition. Any faults or damage which impact or might impact upon safety mustberemediedimmediatelybyaqualifiedcontractor.Onlyreplacefaultycomponentsandequipmentwithoriginal Wolf spare parts.Faults and warnings are shown in plain text on the display of the control accessories – AM display module or BM-2 programming unit – and correspond to the messages listed in the following tables.A warning/fault symbol on the display (symbol: triangle with exclamation mark) indicates an active warning or fault message. Fault history is listed at contractor level.

Warning messages do not need to be acknowledged and do not lead directly to the boiler being switched off. However, the causes of the warnings can lead to malfunctions of the boiler / system or to faults and should therefore be repaired by a qualified contractor.

The control unit automatically acknowledges faults such as faulty temperature sensors or other sensors if the part concerned has been replaced and plausible test values have been supplied.

Please note

14:12 20.01.13

Access RESET

Heating appliance 1

Fault acknowledged!

14:12 20.01.13

Access RESET

Heating appliance 1

Fault 419.02.2013 12:03At burner start noflameestablished

Entry

Acknowledge key

Page 28: 3064203 BM-2 programming unit Installation instructions for

28 3064203_201508

Messages status page

15.4 Acknowledging faults for contractors

Faults must only be repaired by qualified personnel. If a lockout fault message is acknowledged several times without the cause of the problem being repaired, this can lead to component or system damage.

In case of a fault, the current fault is displayed along with the fault code, date and time. The fault can be cleared by pressing the RESET key and entering the contractor code.

Please note

14:12 20.01.13

Access RESET

Heating appliance 1

Fault 21Enter the contractor code:

1 1 1 1

14:12 20.01.13

Access RESET

Heating appliance 1

Fault 21Implement a RESET:

OK

14:12 20.01.13

Access RESET

Heating appliance 1

Fault acknowledged!

Rotary selector

14:12 20.01.13

Fault

Heating appliance 1

Fault 2118.01.2013 11:03Gas valve V2 fault, no emergency mode

Key 3

Key 4 14:12 20.01.13

1.5 bar

25.2 °C

1x

Pressure

Boiler temperature

Heating appliance

Heating mode

Burner ONHome page

14:12 20.01.13

Fault

Heating appliance 1

Fault 2118.01.2013 11:03Gas valve V2 fault, no emergency mode

Page 29: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 29

Main menu overview

16 Main menu overview

You can open the main menu on a status page (heating appliance, heating circuit, mixer, solar thermal system ...) by pressing the rotary selector.

This opens

− Display − Default settings − Time programs − Contractor level

in the main menu.

16.1 Display of set / actual temperatures (chapter 17)

All set and actual temperatures are displayed (however, these cannot be changed).

16.2 Default settings (chapter 18)

− Heating appliance − Heating circuit − Mixer 1-7 − Language − Time − Date − Min. backlighting − Screensaver − Key lock

In order to fully commission the controller, you should set the default settings in consultation with the user. The user can then adjust these default settings later to meet their requirements.

16.3 Time programs (chapter 19)

Time programs are available for all connected appliances. This allows the switching times to be adjusted for the heating circuit, mixer circuit, DHW heating, DHW circulationandventilationunit,accordingtotheconfigurationsandapplianceswhich are connected.

16.4 Contractor level (chapter 20)

Theheatingcontractorcanusethecontractorleveltosetsystem-specificandappliance-specificparameters.Thismenulevelmustonlybeusedbythecontractor.

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

Page 30: 3064203 BM-2 programming unit Installation instructions for

30 3064203_201508

Set / actual temperature display

17 Set / actual temperature displayAll values are displayed for heating appliances and modules that are connected (mixer module MM, cascade module KM, solar module SM).Displaysvarydependingonconfigurationandwhichmodulesareconnected.

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

Entry

14:12 20.01.13

Display

Heating appliance

Cascade module

Mixer

Solar

14:12 20.01.13

Boiler temperature Set 60 °C 42 °C

System pressure Set 2.5bar 2.0 bar

Flue gas temperature 100 °C

Outside temperature 15 °C

Heating appliance

Overview of menu level displaysHeating appliance 1 displayed if heating appliance is installedHeating appliance 2-4 displayed in conjunction with cascade module and if heating appliance 2-4 installedCascade module displayed if cascade module is installedMixer 1 displayed if mixer module 1 (MM) or cascade module (KM) is installedMixer 2-7 displayed if mixer module 2-7 (MM) is installedSolar (SM1/SM2) displayed if solar module SM1 or SM2 is installedVentilation unit displayed if ventilation unit is installedAverage outside temperature displayed if outside sensor is installed

Non-average outside temperature displayed if outside sensor is installed

Displays, heating appliance 1-4 ACT.Boiler temperature in °CSystem pressure in barCurrentfluegastemperaturein°COutside temperature in °CReturn temperature in °CDHW temperature in °CDHWflowratein°CDHWDFL(flowrate)inl/minInput E1Modulation level in %Actual I/O valueZHP speedBurner startsBurner hours runMains hoursPower ON countHCM2 FW

Displays, cascade module ACT.Flow temperature in °CDHW temperature in °CBuffer temperature in °CReturn temperature in °CHeader temperature in °C

Displays, mixer module 1-7 ACT.Flow temperature in °CDHW temperature in °CBuffer temperature in °CReturn temperature in °CHeader temperature in °C

Displays, solar ACT.Temperature, collector 1 °CTemperature, collector 2 °CTemperature, solar cylinder 1 °CTemperature, solar cylinder 2 °CTemperature, solar cylinder 3 °CTemperature, buffer sensor °CTemperature, return sensor °CHours run, pump 1Hours run, pump 2Hours run, pump 3Current outputTotal yieldYield todayYield this monthYield this year

Displays, ventilation ACT.Extract air in °COutside temp. in °CAirflowratem³/hBypassPreheater coil

Page 31: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 31

Default settings overview

18 Default settings overview

A list of all default settings is shown below: − Heating appliance (DHW operating mode) − Heating circuit − Mixer 1-7 − Language − Time − Date − Min. backlighting − Screensaver − Key lock

18.1 Heating appliance

18.1.1 DHW operating mode

Setting range: ECO / ComfortFactory setting: ECO

The DHW operating mode function only applies to combi boilers. The Comfort setting activates a DHW quick start and keeps the heating appliance at the right temperature to ensure rapid DHW heating. In the ECO setting, the heating appliance is not brought up to temperature until the tap is opened.

14:12 20.01.13

Heating appliance

Heating circuit

Mixer 1

Language English

Default settings

14:12 20.01.13

DHW operating mode

Value: Comfort

Heating appliance

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

Entry

18.2 Heating circuit / mixer circuits 1-7

14:12 20.01.13

Heating appliance

Heating circuit

Mixer 1

Language English

Default settings

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

Entry

The following is a list of all default settings for the heating circuit and mixer circuits 1-7:

− Economy factor in economy mode − Winter / summer changeover − ECO ABS − Daytemperature(BM-2inwallmountingbaseandroominfluence

enabled) − Roominfluence(BM-2inwallmountingbase)

Page 32: 3064203 BM-2 programming unit Installation instructions for

32 3064203_201508

Default settings overview

18.2.1 Setting economy factor in economy mode

Setting range: 0...10Factory setting: 4

For a detailed description see the "Heating curve / Economy mode" chapter

The economy factor describes by how much the heating curve sets back the heating circuit or the mixer circuit when in economy mode. This factor has the same effect as the -4...+4 setting, but is only used in the time program during the setback phase or in setback mode.

Example of economy factor setting (setting procedure is always the same).

18.2.2 Setting winter/summer changeover

Setting range: 0 °C to 40 °CFactory setting: 20 °C

The winter/summer changeover function is only enabled if an outside sensor is connected.

The winter/summer changeover function optimises the times when the system operates in heating mode. If the average outside temperature is above the set winter/summer temperature, the heating system switches to standby mode.If the average outside temperature is below the set winter/summer temperature, the heating system switches to automatic timer mode.The period used to calculate the average outside temperature is set via the A04 system parameter.

14:12 20.01.13

Economy factor 5

Roominfluence OFF

Winter / summerChangeover 20 °C

ECO ABS 20 °C

Default settings

14:12 20.01.13

Economy factor

Setting range: 0 - 10

Factory setting: 2

Value: 4

Default settings

14:12 20.01.13

Time 12:25

Date 18.12.2014

Heating circuit settings

Mixer circuit settings

Default settings

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

Entry

Page 33: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 33

Default settings overview

18.2.3 Setting ECO ABS

Setting range: -10 °C to 40 °CFactory setting: 10 °C

The ECO ABS function is only enabled if an outside sensor is connected.

If the average outside temperature is above the ECO ABS temperature when in economy mode, the heating/mixer circuit switches to standby mode.If the average outside temperature is below the ECO ABS temperature, the control unit switches back to economy mode.You should only change the ECO ABS setting after consulting your contractor.

18.2.4 Setting day temperature (room temperature)

Setting range: 5 °C to 30 °CFactory setting: 20 °C

Day temperature is only enabled for this heating/mixer circuit when the room influenceisenabledandtheBM-2isinstalledinthewallmountingbase.Use the day temperature to set the required room temperature in heating mode, party function mode and the heating phases during automatic mode. In setback mode, economy mode and during the setback phase in automatic mode, the room temperature is only set to the day temperature less the economy factor (see point 18.3.1).

18.2.5 Settingroominfluence

Setting range: ON / OFFFactory setting: OFF

Roominfluence is only active if the BM-2 programming unit is installed as a remote control.Room influencecanbeused tocompensate forfluctuations in room temperaturedue to external sources of heat and cold (e.g. insolation, woodburning stoves or open windows).

ON = RoominfluenceenabledOFF = Roominfluencedisabled

Page 34: 3064203 BM-2 programming unit Installation instructions for

34 3064203_201508

Default settings overview

18.3 Language

14:12 20.01.13

Language English

Time 14:25

Date 18.12.2012

Min. backlighting 10

Default settings

14:12 20.01.13

Language

Value: English

Default settings

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

Entry

In the Language submenu, 25 different languages can be selected

Setting range:German, English, French, Dutch, Spanish, Portuguese,Italian, Czech, Polish, Slovak, Hungarian, Russian,Greek, Turkish, Bulgarian, Croatian, Latvian, Lithuanian, Norwegian, Romanian, Swedish, Serbian, Slovenian, Danish, Estonian

Factory setting: German

18.4 Time

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

Entry

14:12 20.01.13

Time 14:25

Date 18.12.2012

Min. backlighting 10

Screensaver ON

Default settings

14:12 20.01.13

Time

Value: 14:25

Default settings

18.5 Date

14:12 20.01.13

Time 14:25

Date 18.12.2012

Min. backlighting 10

Screensaver ON

Default settings

14:12 20.01.13

Date

Value: 18.12.12

Default settings

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

Entry

Page 35: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 35

Default settings overview

18.6 Minimum backlighting

Setting range: 5 % – 15 %Factory setting: 10 %

The display will revert to minimum backlighting level if no further settings are made on the BM-2 for one minute.

18.7 Screensaver

You can enable a screensaver. The display reverts to minimum backlighting after one minute and the following values are shown:

f Time f Outside temperature (outside sensor connected) f Room temperature (BM-2 installed in wall mounting base)

18.8 Key lock

The key lock prevents a unintentional adjustment of the heating system (e.g. by children or when dusting). When the key lock is on, it is automatically enabled one minute after the last setting is made.

ON = Key lock onOFF = Key lock off

f To temporarily override the key lock, press and hold the right rotary selector for 3 seconds.

Page 36: 3064203 BM-2 programming unit Installation instructions for

36 3064203_201508

Time programs

19 Time programsInthe"Timeprogram"mainmenu,definethetimeswhenyouwanttohaveDHWwith the set DHW temperature. The DHW cylinder is not heated up by the heating appliance outside the switching times.

If you have a heating system with solar backup, the DHW cylinder will be heated up even outside the switching times, as long as solar energy is available.

3 different freely programmable time programs are available for each function. This menu item is also used to display and select the active time program. A maximum of3switchingtimescanbedefinedforeachday.

The preset switching times are listed below.

19.1 Pre-programmed switching times

Time program Day Switching time

HC Mixer DHW DHW circulation Ventilation

ON OFF ON OFF ON OFF ON OFF ON OFFTime prog 1

Mo 1 06:00 22:00 05:00 21:00 05:30 22:00 06:00 06:30 07:00 22:002 17:00 18:303

Tu 1 06:00 22:00 05:00 21:00 05:30 22:00 06:00 06:30 07:00 22:002 17:00 18:303

We 1 06:00 22:00 05:00 21:00 05:30 22:00 06:00 06:30 07:00 22:002 17:00 18:303

Th 1 06:00 22:00 05:00 21:00 05:30 22:00 06:00 06:30 07:00 22:002 17:00 18:303

Fr 1 06:00 22:00 05:00 21:00 05:30 22:00 06:00 06:30 07:00 22:002 17:00 18:303

Sa 1 07:00 23:00 06:00 22:00 06:30 23:00 06:30 07:00 08:00 23:002 11:00 12:003 17:00 18:30

Su 1 07:00 23:00 06:00 22:00 06:30 23:00 06:30 07:00 08:00 23:002 11:00 12:003 17:00 18:30

Time prog 2

Mo 1 06:00 08:00 05:00 07:00 05:00 06:00 06:00 06:15 07:00 08:002 15:00 22:00 14:00 21:00 17:00 18:00 17:00 22:003

Tu 1 06:00 08:00 05:00 07:00 05:00 06:00 06:00 06:15 07:00 08:002 15:00 22:00 14:00 21:00 17:00 18:00 17:00 22:003

We 1 06:00 08:00 05:00 07:00 05:00 06:00 06:00 06:15 07:00 08:002 15:00 22:00 14:00 21:00 17:00 18:00 17:00 22:003

Th 1 06:00 08:00 05:00 07:00 05:00 06:00 06:00 06:15 07:00 08:002 15:00 22:00 14:00 21:00 17:00 18:00 17:00 22:003

Fr 1 06:00 08:00 05:00 07:00 05:00 06:00 06:00 06:15 07:00 08:002 15:00 22:00 14:00 21:00 17:00 18:00 17:00 22:003

Sa 1 07:00 22:00 06:00 21:00 06:00 07:00 06:30 06:45 08:00 23:002 16:00 21:00 16:30 17:003

Su 1 07:00 22:00 06:00 21:00 06:00 07:00 06:30 06:45 08:00 23:002 16:00 21:00 16:30 17:003

Page 37: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 37

Time programs

19.1 Pre-programmed switching times

19.2 Enabled time program

The enabled time program can be determined for each menu entry (heating circuit, mixer circuit, DHW, DHW circulation and ventilation). You can choose between time programs 1, 2 and 3. Each enabled time program can be adjusted, as described in chapter 19.3.

Time program Day Switching time

HC Mixer DHW DHW circulation Ventilation

ON OFF ON OFF ON OFF ON OFF ON OFFTime prog 3

Mo 1 05:30 21:00 04:30 20:00 05:00 07:00 06:00 06:30 06:00 21:002 15:00 21:00 17:00 17:303

Tu 1 05:30 21:00 04:30 20:00 05:00 07:00 06:00 06:30 06:00 21:002 15:00 21:00 17:00 17:303

We 1 05:30 21:00 04:30 20:00 05:00 07:00 06:00 06:30 06:00 21:002 15:00 21:00 17:00 17:303

Th 1 05:30 21:00 04:30 20:00 05:00 07:00 06:00 06:30 06:00 21:002 15:00 21:00 17:00 17:303

Fr 1 05:30 21:00 04:30 20:00 05:00 07:00 06:00 06:30 06:00 21:002 15:00 21:00 17:00 17:303

Sa 1 05:30 21:00 04:30 20:00 05:00 07:00 06:00 06:30 06:00 21:002 15:00 21:00 17:00 17:303 17:00 18:30

Su 1 05:30 21:00 04:30 20:00 05:00 07:00 06:00 06:30 06:00 21:002 15:00 21:00 17:00 17:303 17:00 18:30

Time program Day Switching time

HC Mixer DHW DHW circulation Ventilation

ON OFF ON OFF ON OFF ON OFF ON OFFFreelyprogrammedtime program

Mo 123

Tu 123

We 123

Th 123

Fr 123

Sa 123

Su 123

14:12 20.01.13

Enabled time program 1

Time program 1

Time program 2

Time program 3

Time program Htg. circuit

Page 38: 3064203 BM-2 programming unit Installation instructions for

38 3064203_201508

Time programs

19.3 Displaying / selecting switching times

Press and turn the rotary selector to jump to the time program submenu, in order to display the switching times.

Call up the required circuit by turning / pressing the rotary selector (e.g. heating circuit).

Turn and then press the rotary selector to select and call up the required switching time program.

The current switching time program is displayed.

The times are shown at the start and end of the time bar. In the case of short time bars < 4 h, the start time is shown above the end time.

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

14:12 20.01.13

Time program

Heating circuit

Mixer circuit 1

DHW

DHW circulation

14:12 20.01.13

Enabled time program 1

Time program 1

Time program 2

Time program 3

Time program Htg. circuit

14:12 20.01.13

Time program 1 Htg. circuit

0 3 6 9 12

12 15 18 21 24

06:00 12:00

12:30 22:00

Turn to select the dayEdit times with OK

Mo SuTu We Th Fr Sa

Page 39: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 39

Time programs

19.4 Editing switching timesTurn the rotary selector to select the day you want to edit.

Switch to editing mode by pressing the rotary selector (spanner symbol appears).

Press the rotary selector again to start editing for the selected day.

Edit times by turning the selectorYoucanconfirmthechangesandmoveontothestoptimebypressing the selector, then proceed in the same way. If there are 2 or 3 time bars, press the rotary selector several times to reach the 2nd or 3rd bar. The start time is always highlighted for editingfirst,followedbytheendtime.

19.5 Adding switching timesCall up the switching time program you wish to change, select the required day and press the rotary selector to switch to editing mode (spanner symbol appears). Continue by turning the rotary selector to the symbolandpresstoconfirm.

This inserts a new switching time block at 00:00 which you can adjust by turning and pressing the rotary selector.Save the program by pressing the selector again.

19.6 Deleting switching timesCall up the switching time program and select the required day. Then press the rotary selector to switch to editing mode (spanner symbol appears). Continue by turning the rotary selector to the symbolandpresstoconfirm.

Thisselectsthefirstswitchingtimeblock.Youcanselectanother block by turning the rotary selector.Delete the switching time block by pressing the selector.

14:12 20.01.13

Timesedit

Time program 1 Htg. circuit

0 3 6 9 12

12 15 18 21 24

06:00 12:00

12:30 22:00

14:12 20.01.13

Time program 1 Htg. circuit

0 3 6 9 12

12 15 18 21 24

06:00 12:00

12:30 22:00

Turn to select the dayEdit times with OK

14:12 20.01.13

Timesedit

Time program 1 Htg. circuit

0 3 6 9 12

12 15 18 21 24

06:00 12:00

12:30 22:00

Mo SuTu We Th Fr Sa

Mo SuTu We Th Fr Sa

Mo SuTu We Th Fr Sa

14:12 20.01.13

Time program 1 DHW

Mo SuTu We Th Fr Sa

0 3 6 9 12

12 15 18 21 24

00:00 04:1009:0011:28

Timesadd

14:12 20.01.13

Time program 1 DHW

Mo SuTu We Th Fr Sa

0 3 6 9 12

12 15 18 21 24

00:00 04:1009:0011:28

Timesdelete

Page 40: 3064203 BM-2 programming unit Installation instructions for

40 3064203_201508

Time programs

19.7 Copying switching times

To copy one day's switching times, turn the rotary selector to choose the day you wish to copy the times from.

Press the quick start key with the copy symbol (two pages) to reach the Copy level.

You can select the day (highlighted red) you wish to copy the day program to by turning and pressing the selector.

Turn and press again to select further days (highlighted red).

Then keep turning until you reach "Copy" and press the rotary selectortoconfirmtheoperation.Thedayprogramwillnowbecopied to all the selected days.

14:12 20.01.13

Time program 1 Mixer

CopyTurn to select the dayPress to highlight

copy to:

Mo

SuTu We Th Fr Sa

14:12 20.01.13

Timesedit

Time program 1 Htg. circuit

0 3 6 9 12

12 15 18 21 24

06:00 12:00

12:30 22:00

Mo SuTu We Th Fr Sa

14:12 20.01.13

Time program 1 Mixer

Copy

Turn to select the dayPress to highlight

copy to:SuTu We Th Fr Sa

Mo

14:12 20.01.13

Time program 1 Mixer

CopyTurn to select the dayPress to highlight

copy to:

Mo

SuTu We Th Fr Sa

Key 3

Page 41: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 41

Password for contractor level

20 Password for contractor level

To access the contractor level, enter password 1111 with the rotary selector to obtain authorisation. After authorisation the "Contractor level" menu item opens. Youcansetorcallupsystem-specificparametersinthecontractorlevel.

14:12 20.01.13

Main menu

Display

Default settings

Time programs

Contractor level

14:12 20.01.13

Contractor level

- - - -

Enter code

14:12 20.01.13

Contractor level

Enter code

14:12 20.01.13

Contractor level

1 1 - -

Enter code

1 - - -

Contractor level

System

Htg. appliance 1-4

Heating circuit

Cascade module

Mixer circuit 1-7

Solar

Ventilation unit

Fault history

Page 42: 3064203 BM-2 programming unit Installation instructions for

42 3064203_201508

Contractor level menu structure

21 Contractor level menu structure

After entering the password only the connected modules are displayed.

Heating appliance 1 - 4

ParametersComplete list

Relay test

Parameter reset

SystemParameters

Complete list

Cascade module KM

SettingsHeating curve

ParametersComplete list

Cascade parameters

Relay test

Screed drying

Screed drying rem. days

Heating circuitSettings

Heating curve

Screed drying

Screed drying rem. days

Solar SOLParameters

Complete list

Relay test

Mixer circuit 1 - 7 MM

SettingsHeating curve

ParametersComplete list

Relay test

Screed drying

Screed drying rem. days

Fault historyMessage 1

Message 2

...

System See chapter 22

Htg. appliance 1 - 4 See chapter 23

Heating circuit See chapter 24

Cascade module See chapter 25

Mixer circuit 1 - 7 See chapter 26

Solar See chapter 27

Ventilation unit See chapter 28

Fault history See chapter 29

Ventilation unitParameters

Complete list

Parameter reset

Page 43: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 43

Contractor level, system

22 Contractor level, system

22.1 Setting system parameters – example

Use the BM-2 programming unit to set the system parameters of the WRS (e.g. enabling parallel operation).

The system parameters may vary depending on the model of heating appliance.

The system parameters are not displayed for directly assigned programming units.

Enabling parallel operation – example (A10)

Enter the contractor code to access the contractor level, where you can call up the system by pressing the selector again. All the enabled parameters are listed and canbemodifiedhere.

System

14:12 20.01.13

A10 Parallel DHW operation ON / OFF

A11 Room temp dep. shutd. OFF / ON

A12 Setback stop -16 °C

14:12 20.01.13

A10 Parallel DHW operation

Setting range: OFF / ON

Factory setting: OFF

Value: ON

System

14:12 20.01.13

Contractor level

System

Heating appliance

Heating circuit

Cascade module

Page 44: 3064203 BM-2 programming unit Installation instructions for

44 3064203_201508

Contractor level, system

22.2 Complete list of system parameters

The complete list of system parameters below can be edited in the contractor level.

22.2.1 BM-2 function (BUS address)

The BM-2 programming unit is set at the factory with the "System" eBUS address, which allows all the connected heating system components to be controlled from the BM-2 programming unit.

Factory setting: SystemSetting range: MM1 ... MM7, system, not assigned

In the WRS, if several direct circuits e.g. MM1 ... MM7 are being operated, these MM modules can be controlled directly via the "MM1 ... MM7" setting.You are only able to access the parameters of assigned mixer modules.

− Ensure that at least one BM-2 programming unit with the "System" eBUS address is installed in the system.

− YoucanuseaBM-2programmingunitfittedinawallmountingbaseasaremotecontrol for each further mixer circuit, as long as the "BM-2 function" setting is assigned to the required mixer MM1 ... MM7.

− Ensure that each eBUS address is assigned only once in the system.

Parameter Setting range Factory setting

BM-2 function System, MM1 - MM7Not assigned System

A00 Roominfluencefactor 1 to 20 K/K 4 K/K

A04 Outside sensor avg. 0 to 24 h 3 h

A07 Pasteurisation function OFF, Mo...Su, daily OFF

A09 Frost protection limit -20 to +10 °C +2 °C

A10 Enable parallel operation OFF, ON OFF

A11 Room temp dep. shutd. OFF / ON OFF

A12 Setback stop OFF, -39 to 0 °C -16 °C

A13 Minimum DHW temperature 15 to 65 °C 45 °C

A17 P component 1 000...60 000 30 000

A18 I component 20 to 200 50

A23 Start time ALF (pasteurisation function) 00:00 - 23:59 18:00

Page 45: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 45

Contractor level, system

22.3 Description of system parameters

22.3.1 Settingtheroominfluencefactor(A00)

Factory setting: 4 KSetting range: 1 to 20 K

RoominfluenceisonlyenabledwhentheBM-2programmingunitisinstalledasaremotecontrolandroominfluenceissetinthedefaultsettings(chapter18.3.5).Roominfluencecanbeusedtocompensateforfluctuationsinroomtemperaturedue to external sources of heat and cold (e.g. insolation, woodburning stoves or open windows). The integral room temperature sensor compares the actual room temperature with the set value (day temperature or economy factor). The deviation fromthesetvalueismultipliedbytheheatingcurveandtheroominfluencefactor,andtheflowtemperatureisincreasedordecreasedbythisvalue.

Smallroominfluencefactor = littleeffectonflowtemperatureLargeroominfluencefactor = strongeffectonflowtemperature

22.3.2 Setting average outside sensor (A04)

Factory setting: 3 hSetting range: 0 to 24 h

For some automatic functions (e.g. summer/winter changeover, ECO ABS), the BM-2 programming unit calculates an average outside temperature using the current outside temperature over several hours. Set the calculation time period using the "Outside sensor avg." parameter.If the time is set to 0 hours, the BM-2 programming unit does not calculate an average value; instead the average value is always the same as the current outside temperature. The outside temperature display at control level 1 will not be adjusted.

22.3.3 Setting the pasteurisation function (A07)

Factory setting: OFFSetting range: OFF, Mo...Su, daily

Danger!Risk of scalding from hot water!

f When the pasteurisation function is enabled, the DHW temperature is set to 65 °C, as long as the actual DHW temperature has been maintained continuously for onehourat≥60°C.Oncethepasteurisationfunctionhasbeenenabled,itcanbe disabled either by removing the current from the BM-2 programming unit, or by modifying the A07 parameter. The DHW circulation pump is also enabled while the pasteurisationfunctionison.IftheactualDHWtemperatureof≥65°Cisachievedvia an external source (e.g. solar energy), and maintained for one hour, the pasteurisation function will be blocked for that day. Please inform the user about the timing of the pasteurisation function.

Use the A07 parameter to select the day on which the pasteurisation function should begin, e.g. A07 = daily – pasteurisation func. starts every day

Use the A23 parameter to preset the start time for pasteurisation for the relevant day.

Page 46: 3064203 BM-2 programming unit Installation instructions for

46 3064203_201508

Contractor level, system

22.3.4 Setting the frost protection limit (A09)

Factory setting: 2 °CSetting range: -20 to +10 °C

CautionMaterial damage from frostFrost can cause the heating system to freeze up and cause material damage to the system and the premises.

f Please observe the frost protection settings of the heating appliance. f Ensure that the system is adequately protected against frost. f Please inform the user about the frost protection measures taken. f Ensure that there is a constant power supply to the heating appliance.

The heating circuit pump will run continuously if the outside temperature falls below the selected value.The burner starts and heats up the boiler to the minimum boiler water temperature if the boiler water temperature falls below the permanently set value of +5 °C.

22.3.5 Enabling parallel operation (A10)

Factory setting: OFFSetting range: OFF / ON

CautionMaterialdamageduetohighflowtemperaturesParallelDHWoperationcanmaketheflowtemperatureoftheheatingcircuithigherthan the set value, which can lead to material damage. Set DHW priority control for underfloorheatingwithnoseparatemixer.

DHW priority controlDHW heating takes priority over heating mode. As long as water is being heated, heating mode does not run. The cylinder charging pump starts if the boiler water temperature is 5 °C hotter than the cylinder water temperature. As soon as the set DHW temperature is reached, the burner shuts down and the heating circuit pump starts. The cylinder pump runs on for the period set under parameter HG19 (SLP run-on time).

Parallel DHW operationHeating and DHW heating operate simultaneously. With simultaneous operation, the heating circuit can be heated to higher temperatures than needed or set.

0 = DHW priority control1 = Parallel DHW operation

For wall-mounted boilers with a priority changeover valve for DHW heating, this parameter has no function.

Page 47: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 47

Contractor level, system

22.3.6 Room temperature shutdown (A11)

Factory setting: ONSetting range: ON / OFF

When room temperature shutdown is enabled, the corresponding heating/mixer circuit shuts down if the day temperature exceeds + 0.5 K. The heating/mixer circuit pump does not restart until the room temperature falls below the day temperature. Roominfluencecanbeusedtocompensateforfluctuationsinroomtemperaturedue to external sources of heat and cold (e.g. insolation, woodburning stoves or open windows).

Example 1:Room temperature shutdown prevents the area from being overheated if room influenceisenabledandthelivingareaisheatedonlybytheheatingsystem.

Example 2:Room temperature shutdown can occur if a room where the programming unit is installed (e.g. living room) is heated by a second heat source (e.g. woodburning stove)androominfluenceisenabled.Thiswouldresultinotherroomscoolingdown.Remedy: Switch OFF room temperature shutdown (OFF).

22.3.7 Setting setback stop (A12)

Factory setting: -16 °CSetting range: -30 to 0 °C

The BM-2 programming unit switches from setback mode to heating mode if the average outside temperature falls below the set value.

22.3.8 Setting the minimum DHW temperature (A13)

Factory setting: 45 °CSetting range: 15 to 65 °C

The A13 minimum DHW temperature parameter is only enabled when a solar extension module is connected.

The solar thermal system can be used to heat up the DHW cylinder above the set DHW temperature, and solar heating is successful. When solar heating is successful, the heating appliance will not heat up the DHW cylinder unless it falls below the minimum DHW temperature, or the set DHW temperature is not reached by 14:00 h the next day. If the minimum DHW temperature is not achieved, the DHW cylinder will be heated by the heating appliance.

Page 48: 3064203 BM-2 programming unit Installation instructions for

48 3064203_201508

Contractor level, system

22.3.9 P component for room temperature PI controller (A17)

Factory setting: 30 000Setting range: 1 000 to 60 000

The P component of the PI controller is set using A17.

P component = gain factorIncreasePcomponent → PIcontrollerrespondsmorequicklyDecreasePcomponent → PIcontrollerrespondsmoreslowly

22.3.10 I component for room temperature PI controller (A18)

Factory setting: 50Setting range: 20 to 200

The I component of the PI controller is set using A18. I component = reset timeIncreaseIcomponent → PIcontrollerrespondsmoreslowlyDecreaseIcomponent → PIcontrollerrespondsmorequickly

22.3.11 Start time of pasteurisation function (A23)

Factory setting: 18:00 hSetting range: 00:00 to 23:59

The pasteurisation function can be started on the selected days (A07) using the A23 parameter.

Page 49: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 49

Contractor level, heating appliance

23 Contractor level, heating appliance

23.1 Setting the heating appliance

You can use the BM-2 programming unit to set all the heat generator parameters below separately for the heating appliances (e.g. maximum boiler temperature, input 1, output 1).The heating appliance parameters may vary, depending on the heat generatorversion.Adjustment options and explanations regarding the individual parameters can be found in the installation instructions for the heat generator.After selecting the parameter, the data is obtained from the heating appliance control unit and displayed approx. 5 seconds later.

Thecurrentlyselectedvalueisshownonthedisplayandcanbemodified,subjectto the parameter being available in the heating appliance control unit.

Modifying heating appliance parameters

Enter the contractor code to access the contractor level, where you can call up heating appliances 1-4 by turning and pressing the selector.

Follow the same procedure used to set system parameters. (The setting is repeated for the cascade module, heating circuit, mixer circuit, ventilation unit, solar):

Display ChapterComplete list of heating appliance parameters

23.1.1

Relay test for CGB-2 23.1.2Heating appliance parameter reset 23.1.3

Please also note the information/settings in the heating appliance installation instructions.

If a parameter is not available, it will not be shown on the display.

Page 50: 3064203 BM-2 programming unit Installation instructions for

50 3064203_201508

Contractor level, heating appliance

23.1.1 Complete list of heating appliance parameters

For set values and description, see heating appliance installation instructions If a parameter is not available, then no parameter will be shown in the display.

Thereisaspecialconfigurationoftheheatingapplianceparametersforeachheatingappliance.

Complete list of heating appliance parameters

HG01 Burner switching hysteresis

HG02 Lower burner output, heat generator in %

HG03 Upper burner output, DHWMaximum burner output, DHW in %

HG04 Upper burner output, heating Maximum burner output, heating in %

HG07 Heating circuit pump run-on time Heating circuit pump run-on time in heating mode

HG08 Maximum boiler temperature, heating (applicable to heating mode) TV-max

HG09 Burner cycle block, applicable to heating mode

HG10 Heat generator eBUS address

HG12 Gas type

HG13 Function, input E1 Various functions can be allocated to input E1.

HG14 Function, output A1 (230 V AC) Various functions can be allocated to output A1.

HG15 Cylinder hysteresis, switching differential during cylinder reheating

HG16 Pump rate HC, minimum

HG17 Pump rate HC, maximum

HG19 SLP run-on time (cylinder charging pump)

HG20 Max. cyl. heat. time

HG21 Minimum boiler temperature TK-min

HG22 Maximum boiler temperature TK-max

HG25 Boiler excess temperature during cylinder heating

HG33 Burner hysteresis runtime

HG34 eBUS feed

HG37 Pump control type (constant / linear / spread)

HG38 Set spread, pump control unit (spread)

HG39 Soft start time

HG40 Systemconfiguration(seechapter"Parameterdescription")

HG41 ZHP speed DHW

HG42 Hysteresis, header

HG43 IO reductn, default value

HG44 GPV curves offset

HG45 Flue length adaptation

HG46 Excess boiler temperature, headerHG33 Hysteresis timeHG34 eBUS feedHG35 0 – 5 V input for telecontrol systemHG36 Runtime modulation (only required in conjunction with KM module)HG37 Pump control type (constant / linear / spread) HG38 Set dT spread, pump controlHG39 Soft start timeHG40 Systemconfiguration(seechapter"Systemconfigurations")HG41 ZHP speed DHWHG42 Hysteresis, headerHG43 IO reductn, default valueHG44 GPV curves offsetHG45 No functionHG46 Excess boiler temperature, header

Page 51: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 51

Contractor level, heating appliance

23.1.2 Relay test for CGB-2 heating appliance

After entering the contractor code to access the contractor level, you can call up heating appliances 1-4 by turning and pressing the selector again.

Turn and press the selector to call up and modify the relay test.

The relay test parameter on the BM-2 programming unit is only enabled when the unit is installed in the heating appliance.

If the programming unit is used as a remote control, the relay test parameter is shown on the AM display module.

Follow the same procedure for each relay test.

CautionPossible damage to the heating applianceIncorrect setting of the parameters for the heating appliance can damage the heating appliance

Display MeaningZHP Feed / heating circuit pumpLP Cylinder charging pumpA1 Programmable output3WUV 3-way diverter valveBCU Burner control unit 230 V power supplyVentilation ZHP 20 min. every 30 s ON / 30 s OFF.

Ventilation is terminated by pressing any key

Heating appliance 1

14:12 20.01.13

Complete list of heating appliance parameters

Relay test

Parameter reset

14:12 20.01.13

ZHP

Setting range: OFF / ON

Factory setting: OFF

Value: OFF

Heating appliance 1

14:12 20.01.13

Contractor level

System

Heating appliance

Heating circuit

Cascade module

Relay test

14:12 20.01.13

ZHP OFF

LP OFF

A1 OFF3WUV OFF

Page 52: 3064203 BM-2 programming unit Installation instructions for

52 3064203_201508

Contractor level, heating appliance

23.1.3 Heating appliance parameter reset

The individual heating appliance parameter settings for the BM-2 programming unit can be restored to their factory settings.

After entering the contractor code to access the contractor level, you can call up heating appliances 1-4 by turning and pressing the selector again.

The reset can be performed by turning and pressing the selector.

The reset parameter on the BM-2 programming unit is only enabled when the unit is installed in the heating appliance.

If the programming unit is used as a remote control, the reset parameter is shown on the AM display module.

Heating appliance 1

14:12 20.01.13

Complete parameter list

Relay test

Parameter reset

14:12 20.01.13

Contractor level

System

Heating appliance

Heating circuit

Cascade module

14:12 20.01.13

Restore param. to default

No

Heating appliance 1

Yes

Page 53: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 53

Contractor level, heating circuit

24 Contractor level, heating circuit

Under heating circuit, you can apply the following settings.

24.1 Setting the heating curveFollow the same procedure for mixer / cascade heating curve.

The heating curve submenu is only displayed on systems with a connected outside sensor.

CautionRiskofdamageduetohighflowtemperaturesFlowtemperaturesabove40°Cwithunderfloorheatingcancausematerialdamage.

f Setthemixerheatingcurvesothattheflowtemperaturedoesnotexceed40°C.

This setting will be made separately by the contractor for each heating circuit, subject to the heating system, the thermal insulation of the building and the relevant climatic zone. These settings will adjust the heating water temperature to match these conditions.

The heating curve setting can still be adjusted later with the temperature selection -4 to +4 (parallel offset)and economy factor 0 ... 10 (setback in economy mode)

After entering the contractor code, enable the heating circuit by turning and pressing the selector and call up the heating curve settings by pressing the selector.

14:12 20.01.13

Contractor level

System

Heating appliance

Heating circuit

Cascade module14:12 20.01.13

Contractor level, htg circ

Heating curve settings

Screed drying

Screed drying rem. days

Display ChapterHeating curve 24.2Screed drying 24.3Screed drying rem. days 24.3

Page 54: 3064203 BM-2 programming unit Installation instructions for

54 3064203_201508

Contractor level, heating circuit

24.2 Heating curve description

(for further descriptions see chapter 30)The current heating curve is displayed. Press and turn the selector to change the heating curves.

- Flow temp. at standard outside temp. - Flow temperature at standard outside temperature-Lowendtemperature - Lowestflowtemperatureinconstanttemperaturemode-Heatingcurvestartpoint - Beginningoftheflowtemperatureincreasesubjecttooutside

temperature.- Standard outside temperature - The lowest average temperature over two days that is reached or

undershot ten times in 20 years.

The heating curve shown on the display changes according to setting.Follow the same procedure for setting the mixer / cascade heating curve.

14:12 20.01.13

Heating curve - htg. circ.

Flow temperature 55 °C

Outside

Flow

20 °C -16 °C20 °C

80 °C

Flow

tem

pera

ture

in °

C

Outside temperature °C

Heating curve

Economy mode

Low end temperature 20 °C

Hea

ting

curv

e

star

ting

poin

t 18

°C

EC

O A

BS

10

°C

Economy factor 2

Set

back

sto

p -1

6 °C

Win

ter /

sum

mer

C

hang

eove

r 20

°C

Stan

dard

out

side

te

mpe

ratu

re -1

6 °C

Flow temperature at 55 °C (radiator design point)

Page 55: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 55

Contractor level, heating circuit

24.3 Setting heating circuit screed drying

Mixer circuit 1

14:12 20.01.13

Heating curves

Complete parameter list

Relay test

Screed drying OFF

14:12 20.01.13

Contractor level

Heating circuit

Cascade module

Mixer circuit 1

Solar14:12 20.01.13

Factory setting: OFF

Value: OFF

Mixer circuit 1

Screed drying

Factory setting: OFFSetting range: OFF / Constant / Automatic

CautionPossible damage to the screedAgreethetimesequenceandthemaximumflowtemperaturewiththescreedcontractor,otherwisethescreed may be damaged, particularly through cracking. The screed drying program continues without interruption after a power failure. In the "Automatic" setting, the remaining time in days is shown on the display (BM-2).

Iftheheatingisstartedforthefirsttimeinanewbuilding,thereistheoptiontoregulatethesetflowtemperatureindependently of the outside temperature, either by setting a constant value or in accordance with an automatic screed drying program.

24.3.1 OFFScreed drying function disabled

24.3.2 AutomaticForthefirsttwodaysthesetflowtemperatureremainsataconstant25°C.Itwillthenberaisedautomaticallyeveryday(at0:00h)by5°CuptothemaximumHG08flowlimitminus7K(burnerhysteresis).Thattemperaturewillthenbeheldfortwodays.Subsequently,theflowtemperatureisautomaticallyreducedagainin5°Cstepsperdayto25°C.Theprogramfinishesafterafurthertwodays.Fortheheatingcircuitthereisanadditionallimitintegrated at 55 °C, so that with HG08 (TV max) > 62 °C an automatic limit takes effect at 55 °C.

Fig. 24.1 Flow temperature curve over time during "Automatic" screed drying at HG08=57 °C

24.3.3 Constant temperatureTheheatingcircuitisregulatedconstantlytothesetfixedminimumtemperatureHG21.

Flow

tem

pera

ture

(°C

)

Screed drying runtime (days)

HG08 = 57 °C

Page 56: 3064203 BM-2 programming unit Installation instructions for

56 3064203_201508

Contractor level, cascade module

25 Contractor level, cascade module

The menu level cascade will not be displayed if no cascade module is installed.

Thefollowingsettings(e.g.configuration)canbeadjustedviatheBM-2programming unit.

Setting options and explanations regarding the individual parameters can be found in the installation instructions of the mixer module or the cascade module. After selecting the parameter, the data is obtained from the mixer module or cascade module and displayed approx. 5 seconds later. The currently selected valueisshownonthedisplayandcanbemodified,subjecttotheparameterbeingavailable in the heating appliance control unit.

CautionPossible damage due to mixer module MM / cascade module KMIncorrect parameter settings for the mixer module / cascade module can cause damage.

Please also note the information/settings in the heating appliance installation instructions.

If a parameter is not available, it will not be shown on the display.

Display ChapterHeating curve 24.2Mixer parameters 26.2Cascade parameters 25.1Relay test 25.2Screed drying 26.4Screed drying rem. days 26.4

Page 57: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 57

Contractor level, cascade module

25.1 Complete list of cascade module parameters

For set values and descriptions, see cascade module KM installation instructions

Complete list of cascade module KM parametersKM01 ConfigurationKM02 Mode (single stage = 1; two-stage=2; modulating = 3)KM03 Maximum header temperatureKM04 Maximumflowtemperature,heatingKM05 Minimum header temperatureKM06 Hysteresis, header temperatureKM07 Blocking timeKM08 STD to htg appl seq. changeKM09 1/Kp header temperature control startKM10 1/Kp header temperature control stopKM11 Tn header temperature controlKM12 Selection, heating appliance sequenceKM13 Heating appliance sequence AKM14 Heating appliance sequence BKM15 Modulation level, shutdownKM16 Modulation level, start-upKM17 DHW circulation pumpKM18 Pump control, lead applianceKM19 Modulation stopKM20 Hysteresis, modulation stopKM21 Forced output during cylinder heatingKM22 Hysteresis, parallel operationKM23 -KM24 -KM25 -KM26 -KM27 Set boiler temperatureKM28 Hysteresis, set boiler temperatureKM29 Set buffer temperatureKM30 Hysteresis, set buffer temperatureKM31 Operating mode 0 -10 V inputKM50 Test functionKM60 Control deviationKM61 Overall modulation levelKM62 Modulation level, heating appliancesKM70 Input E1KM71 Input E2KM72 Flow sensor VFKM73 Header sensor SAFKM74 Input 0 - 10 V

25.2 Relay test cascade moduleFor description, see Relay test heating appliance, chapter 23.1.2Display MeaningMKP Mixer circuit pumpMM OPEN Mixer motor OPENMM CLOSE Mixer motor CLOSEA1 Programmable output

Page 58: 3064203 BM-2 programming unit Installation instructions for

58 3064203_201508

Contractor level, mixer circuit

26 Contractor level, mixer circuit

If neither the mixer module nor cascade module are available, the mixer circuit menu level will not be displayed. The parameters for mixer circuits 1-7 (e.g. configuration,heatingcurvegap)canbesetviatheBM-2programmingunit.Setting options and explanations regarding the individual parameters can be found in the installation instructions for the mixer module. After selecting the parameter, the data is obtained from the mixer module and displayed approx. 5 seconds later.

Display ChapterHeating curve 26.1Complete parameter list 26.2Relay test 26.3Screed drying 26.4Screed drying rem. days 26.4

CautionPossible damage due to mixer module MMIncorrect parameter settings for the mixer module can cause damage.

Please also note the information/settings in the heating appliance installation instructions.

If a parameter is not available, it will not be shown on the display.

Page 59: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 59

Contractor level, mixer circuit

26.1 Heating curve – mixer

For a description see Heating curve – heating circuit, chapter 24.2

26.2 Complete list of mixer module parameters For set values and descriptions, see mixer module MM installation instructions

Complete list of MI mixer module parameters

MI01 Min. mixer circuit temperature

MI02 Max. mixer circuit temperature

MI03 Heating curve gap

MI05 Configuration

MI06 Heating circuit run-on time

MI07 P range, mixer

MI08 Set return temperature

MI09 Max. cyl. heat. time

MI10 BUS feed (1 = ON)

MI12 Charging pump blocking

MI13 Charging pump run-on time

MI14 Constant temperature

MI15 dT OFF (shutdown differential)

MI16 dT ON (start differential)

MI17 Boiler excess temperature during cylinder heating

MI18 Burner blocked during return temperature raising

MI19 Frost protection LH

26.3 Mixer relay test For description, see Relay test heating appliance, chapter 23.1.2

Display MeaningMKP Mixer circuit pumpMM OPEN Mixer motor OPENMM CLOSE Mixer motor CLOSEA1 Programmable output

Page 60: 3064203 BM-2 programming unit Installation instructions for

60 3064203_201508

Contractor level, mixer circuit

26.4 Screed drying settings, mixer circuit

Mixer circuit 1

14:12 20.01.13

Heating curves

Complete parameter list

Relay test

Screed drying OFF

14:12 20.01.13

Contractor level

Heating circuit

Cascade module

Mixer circuit 1

Solar14:12 20.01.13

Factory setting: OFF

Value: OFF

Mixer circuit 1

Screed drying

Factory setting: OFFSetting range: OFF / Constant / Automatic

CautionPossible damage to the screedAgreethetimesequenceandthemaximumflowtemperaturewiththescreedcontractor,otherwisethescreed may be damaged, particularly through cracking. The screed drying program continues without interruption after a power failure. In the "Automatic" setting, the remaining time in days is shown on the display (BM-2).

Iftheunderfloorheatingisstartedforthefirsttimeinanewbuilding,thereistheoptiontoregulatethesetflowtemperature independently of the outside temperature, either by setting a constant value or in accordance with an automatic screed drying program.

26.4.1 OFFScreed drying function disabled

26.4.2 AutomaticForthefirsttwodaysthesetflowtemperatureremainsataconstant25°C.Itwillthenbeautomaticallyraisedevery day (at 0:00 h) by 5 °C up to the maximum mixer circuit temperature (MI 02). That temperature will then beheldfortwodays.Subsequently,theflowtemperatureisautomaticallyreducedagainin5°Cstepsperdayto25°C.Theprogramfinishesafterafurthertwodays.

Flow

tem

pera

ture

(°C

)

Screed drying runtime (days)

MI02 = 50 °C

Fig. 26.1 Flow temperature curve over time during "Automatic" screed drying at MI02=50 °C

26.4.3 Constant temperatureThemixercircuitisregulatedconstantlytothesetfixedminimumtemperatureMI01.

Page 61: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 61

Contractor level, solar

27 Contractor level, solar

The solar menu will only be displayed if a solar module has been connected.Solar module parameters (e.g. start-up differential, shutdown differential) can be adjusted via the BM-2 programming unit.After selecting the parameter, the data is obtained from the solar module and displayed approx. 5 seconds later.

f Please note the information and setting options for the parameters in the solar module installation instructions.

27.1 Complete list of solar module parameters

Para-meterBM/BM-2

Para-meterBM Solar

Meaning

SOL 01 P 01 Start differential, solar cylinder 1SOL 02 P 02 Stop differential, solar cylinder 1SOL 03 P 03 Collector cooling functionSOL 04 P 04 Critical collector temperatureSOL 05 P 05 Maximum collector temperatureSOL 06 P 06 Maximum temperature, solar cylinder 1SOL 07 P 07 Assignment, solar cylinder 1SOL 08 P 08 Heat metering

SOL 09 P 09

P 08=0→P 09 not adjustable P 08=1→Pulse value, pulse generatorP 08=2→Constant flow rateP 08=3or4→Pulse value External heat meter

SOL 10 P 10

Glycol selection:0 = Water1 = Tyfocor L (Anro)2 = Tyfocor LS (Anro LS)3 = Propylene glycol4 = Ethylene glycol

SOL 11 P 11 BUS feedSOL 12 P 12 Configuration

SOL 13 P 13Speed control, solar circuit pump(Inconnectionwith"highefficiencypumps",neverchange the factory setting of parameter SOL13)

SOL 14 P 14 Start differential, solar cylinder 2SOL 15 P 15 Stop differential, solar cylinder 2SOL 16 P 16 Maximum temperature, solar cylinder 2SOL 17 P 17 Assignment, solar cylinder 2

SOL 18 P 18 Burner blocked during return temperature raising

SOL 19 P 19 Start differential, return temperature raisingSOL 20 P 20 Stop differential, return temperature raisingSOL 21 P 21 Priority, solar cylinder 1

SOL 22 P 22 Start differential, parallel cylinder operation

SOL 23 P 23 Differential temperature, bypassSOL 24 P 24 Function output A4

SOL 25 P 25 Start temperature Thermostat function 1/2

SOL 26 P 26 Stop differential, thermostat function 1/2SOL 27 P 27 Tube collector functionSOL 28 P 28 Frost protection functionSOL 29 P 29 Start differential, solar cylinder 3SOL 30 P 30 Stop differential, solar cylinder 3SOL 31 P 31 Maximum temperature, solar cylinder 3

SOL 32 P 32 Assignment, solar cylinder 3

SOL 33 P 33 Hysteresis, solar cylinder 1

Para-meterBM/BM-2

Para-meterBM Solar

Meaning

SOL 34 P 34 Hysteresis, solar cylinder 2

SOL 35 P 35 Hysteresis, solar cylinder 3

SOL 36 P 36 Solar cylinder emergency shutdown 1

SOL 37 P 37 Solar cylinder emergency shutdown 2

SOL 38 P 38 Solar cylinder emergency shutdown 3

SOL 39 P 39 Minimum collector limit

SOL 40 P 40 Minimum buffer limit

SOL 41 P 41 Functioncheck,flowrate

SOL 42 P 42 Function check Gravity brake

SOL 43 P 43 Lower pump rate

SOL 44 P 44 Reverse cooling function

SOL 45 P 45 Selection cylinder, thermostat function

SOL 46 P 46 Priority, solar cylinder 2

SOL 47 P 47 Cylinder operating mode

SOL 48 P 48 Cyclical heating time

SOL 49 P 49 Idle time

SOL 50 P 50 Blocking time, solar circuit pump or electrical valve

SOL 51 P 51

Glycol content in water

P 10=0→P 51 not adjustableP 10 = 1 : Tyfocor L (Anro)P 10 =2→P 51 not adjustableP 10 =3→P 51 not adjustableP 10 =4→Ethyleneglycol

SOL 52 P 52 Cylinder control with external cylinder heating

SOL 55 P 55 Upper pump rate

SOL 56 P 56 Blocking time, solar circuit pump

SOL 57 P 57 Hysteresis, tube collector function

SOL 58 P 58 Max. control deviation

SOL 59 P 59 Correctionvalue,flowrateP08=1SOL 6O P 60 Relay test

Page 62: 3064203 BM-2 programming unit Installation instructions for

62 3064203_201508

Contractor level, ventilation unit

28 Contractor level, ventilation unit

The ventilation unit menu level will not be displayed if no CWL Excellent is installed.

The parameters for the ventilation unit (e.g. Flow reduced, Flow normal) can be set via the BM-2 programming unit.

Setting options and explanations of the individual parameters are given in the table below. After selecting the parameter, the data is obtained from the ventilation unit anddisplayedapprox.5secondslater,whereitcanbemodified.

Contractor level, vent.

14:12 20.01.13

CWL01 Flow reduced 100m³/h

CWL02 Flow normal 150 m³/h

CWL03 Flow high 225 m³/h

CWL04 Flow holiday 50 m³/h

14:12 20.01.13

Contractor level

Heating circuit

Mixer

Ventilation

Fault history

Setting options

Explanation(see also main menu, ventilation unit)

The system targets the set air volume of parameter CWL1.Temporary moisture protection can only be enabled by entering the start and end times. Once this time has elapsed, the program switches back to the previously selected operating mode.

During "reduced ventilation", the ventilation unit runs permanently in accordance with the settings in parameter CWL2.

During "Std ventilation", the ventilation unit runs permanently in accordance with the settings in parameter CWL3.

The system targets the set air volume of parameter CWL4. Temporary intensive ventilation can only be enabled by entering the start and end times. Once this time has elapsed, the program switches back to the previously selected operating mode.

Complete list of CWL ventilation unit parameters

Contractor level, vent. Factory setting Setting rangeCWL1 Airflowmoist.prot 50 m³/h 50 - 400 m³/h CWL2 Airflow,reduced 100 m³/h 50 - 400 m³/hCWL3 Airflow,stdvent. 150 m³/h 50 - 400 m³/hCWL4 Airflow,intensive 225 m³/h 50 - 400 m³/hCWL5 Bypass temp. 22 °C 15 °C – 35 °CCWL6 Bypass hyst. 2 °C 0 °C – 5 °C

Page 63: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 63

Contractor level, fault history

29 Contractor level, fault history

All faults and messages can be found in the fault code list in the fault history, and if necessary can be given to the contractor over the telephone. Faults are logged with start and end dates and times. In many cases the fault can be resolved over the telephone, without the need to call out the contractor. Fast reaction to faults can be crucial with heating systems.

The fault history records up to 40 faults.

After entering the contractor code, enable the fault history by turning and pressing the selector.

Entry

You can display all fault messages by turning the selector.

Whenyouhavefinishedremovingfaults, you can press the "Recycle bin" button to delete the entire fault history.

14:12 20.01.13

Fault history

Heating appliance 1

Fault 21Start: 18.01.2013 11:03End: 19.01.2013 12:15

Fault 1 of 1

Page 64: 3064203 BM-2 programming unit Installation instructions for

64 3064203_201508

Heating curve / economy factor

30 Heating curve / economy factor

Theflowtemperatureintheeconomyfactorisdeterminedusingthepreviouslysetheatingcurve,thetemperature selection -4 to +4, and the economy factor 0 to 10.

30.1 Heating curves overview

30.2 Temperature selection -4 ... +4 for heating circuit

Theflowtemperature/heatingcurvefortheheatingcircuitischangedwith"temperatureselection-4…+4equals temperature correction" as follows:

Flow

tem

pera

ture

in °

C

Outside temperature °C

Heating curve

Economy mode

Low end temperature 20 °C

Heating curve starting point 18 °C

ECO ABS 10 °C

Economy factor 2

Setback stop -16 °C

Winter / summerchangeover 20 °C

Standard outside temperature -16 °C

Flow temperature(radiator design point)

Heating circuit heating curve (factory setting):

Economy factor 2Temperature correction 0

Wi/Su changeover .............................................. 20 °CECO ABS ............................................................ 10 °CSetback stop .......................................................-16 °CHeating curve starting point ................................ 18 °CStandard outside temperature ............................-16 °CLow end temperature ......................................... 20 °CFlow temp. at standard outside temperature ...... 55 °C (radiator design point)

Temperature correction -4Heating circuit heating curve is reduced

Temperature correction +4Heating circuit heating curve is increased

Flow

tem

pera

ture

in °

C

Outside temperature °C

Heating curve

Economy modeFl

ow te

mpe

ratu

re in

°C

Outside temperature °C

Flow

tem

pera

ture

in °

C

Outside temperature °C

Heating curve

Heating curve

Economy mode

Economy mode

Temperature correction 0

Page 65: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 65

Heating curve / economy factor

30.3 Economy factor 0 to 10 for heating circuit

Theflowtemperatureineconomymodeischangedwith"Economyfactor0to10"asfollows:

30.4 Economy mode – calculation example

Flow temperature (economy mode) =

Flow temperature heating mode + (flowtemperatureatstandardoutsidetemperature–lowendtemperature)/10x(-economyfactor)

Example:

Low end temperature 20 °CStart point heating curve 18 °C outside temperatureFlow temperature at standard outside temperature 55 °C (radiator design point)Standard outside temperature -16 °CEconomy factor 2Temperature selection 0

Anoutsidetemperatureof-10°C,accordingtotheheatingcurve,willresultinaflowtemperatureof48.2°Cinheating mode.

Economy mode will produce the following flowtemperature

Flow temperature in economy mode = 48.2 °C + (55 °C - 20 °C) / 10 x -2 = 48.2 °C + (3.5 K x -2) = 48.2 °C - 7 K = 41.2 °C

Economy factor 2Economy mode (factory setting)

Economy factor 5

Flow

tem

pera

ture

in °

C

Outside temperature °C

Heating curve

Economy mode

Flow

tem

pera

ture

in °

C

Outside temperature °C

Heating curve

Economy mode

Heating circuit heating curveEconomy factor 2

Flow

tem

pera

ture

in

°C

Outside temperature °C

Heating curve

Economy mode

48.2 °C

-10 °C

41.2 °C

Page 66: 3064203 BM-2 programming unit Installation instructions for

66 3064203_201508

Heating curve / economy factor

30.5 Temperature selection -4...+4 for mixer circuit

Theflowtemperature/heatingcurveforthemixercircuitischangedwith"temperatureselection-4…+4equals temperature correction" as follows:

30.6 Economy factor 0 to 10 for mixer circuit

Theflowtemperatureineconomymodeischangedwitheconomyfactor0to10asfollows:

Mixer circuit heating curve (factory setting):

Economy factor 2Temperature correction 0

Wi/Su changeover ............................................. 20 °CECO ABS ........................................................... 10 °CSetback stop ......................................................-16 °CHeating curve starting point ............................... 18 °CStandard outside temperature ...........................-16 °CLow end temperature......................................... 20 °CFlow temp. at standard outside temperature ..... 35 °C (underfloorheatingdesignpoint)

Temperature correction 0

Temperature correction -4Mixer circuit heating curve is reduced

Temperature correction +4Mixer circuit heating curve is raised

Flow

tem

pera

ture

in °

C

Outside temperature °C

Heating curve

Economy mode

Flow

tem

pera

ture

in °

C

Outside temperature °C

Flow

tem

pera

ture

in °

C

Outside temperature °C

Economy mode

Economy modeHeating curve

Heating curve

Economy factor 2Economy mode (factory setting)

Economy factor 5(only reduced in economy mode)

Flow

tem

pera

ture

in °

C

Outside temperature °C

Flow

tem

pera

ture

in °

C

Outside temperature °C

Heating curve

Economy mode

Heating curve

Economy mode

Page 67: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 67

Overview of symbols

31 Overview of symbols

31.1 Symbols for the quick start keys

Symbol FunctionThethermometerallowsmodificationofthesettemperature

Therotaryselectorallowsmodificationoftheoperatingmode

Press the home key to return to the start page

Press the arrow key to go back one step

Press the emissions test key to access emissions test modeEmissionstestmodeisonlynecessaryforthefluegastest.The heating appliance provides maximum heating output in emissions test mode (full load operation). In full load operation, the heating system is heated up to the maximum set temperature and the DHW cylinder is heated up to the set DHW temperature.Whentheheatingapplianceisinfullloadoperation,thefluegasinspectorcancarryoutthenecessaryfluegastests.Emissionstestmodeterminatesautomaticallyeitherafter15minutesorifthemaximumflowtemperaturehasbeen exceeded.You can only enable emissions test mode using the BM-2 programming unit if it is installed in the heating appliance.

1x

The special function 1x DHW bypasses the programmed switching times and heats up the DHW cylinder once, for one hour, to the set DHW temperature.

Call up the annual solar yield

Call up the monthly solar yield

In time programs, copy a selected day to other days

Acknowledge fault key in the case of faults

Resetthefilterwarning(onlyfortheCWLExcellent)

Recycle bin, fault history is deleted

Page 68: 3064203 BM-2 programming unit Installation instructions for

68 3064203_201508

Overview of symbols

31.2 Symbols for possible changes using the rotary selector

Symbol FunctionThe automatic timer switches the heating circuit on and off at the programmed switching times.Within the switching times, the heating circuit heats up to the set room temperature (day temperature) with the enabledroominfluenceorinaccordancewiththesetheatingcurve.

The automatic timer switches the mixer circuit on and off at the programmed switching times.Within the switching times, the mixer circuit heats up to the set room temperature (daytemperature)attheenabledroominfluenceorinaccordancewiththesetheatingcurve.

The DHW cylinder is heated up to the set DHW temperature within the switching times.

The DHW circulation pump (if installed) is only switched on within the switching times.

In automatic mode with the CWL Excellent, the system only switches between "Std ventilation" within the switching time and "reduced ventilation" outside the switching time.

Party modeIn party mode, the time and date are entered at which the heating system goes into continuous heating mode. The time and date at which the heating system returns to the previously selected operating mode are also entered.(see chapters "Heating circuit status page" and "Mixer status page", section "Changing the mixer circuit operating mode")

Setback mode In setback mode, the time and date are entered at which the heating system goes into continuous economy mode. The time and date at which the heating system returns to the previously selected operating mode are also entered.(see chapters "Heating circuit status page" and "Mixer status page", section "Changing the mixer circuit operating mode")

Permanent heating modeIn permanent heating mode, the heating system is continuously on.The heating system heats up to the set room temperature (day temperature) or in accordance with the settings of the heating curve.

In economy mode, the heating system heats up to the set economy temperature.

In standby mode, the heating system and DHW heating are switched off.The DHW circulation pump (if installed) is switched off.The frost protection function is enabled.The heating system pumps are switched on at regular intervals to prevent the equipment from seizing up.

Mo SuWeekdays

Page 69: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 69

Overview of symbols

Symbol FunctionDHW modeIn DHW mode, the BM-2 programming unit keeps DHW heating switched on continuously.

1x

The special function 1x DHW bypasses the programmed switching times and heats up the DHW cylinder once, for one hour, to the set DHW temperature.

The system targets the set air volume of parameter CWL1. Temporary moisture protection can only be enabled by entering the start and end times. Once this time has elapsed, the program switches back to the previously selected operating mode.

During "reduced ventilation", the ventilation unit runs permanently in accordance with the settings in parameter CWL2.

During "Std ventilation", the ventilation unit runs permanently in accordance with the settings in parameter CWL3.

The system targets the set air volume of parameter CWL4. Temporary intensive ventilation can only be enabled by entering the start and end times. Once this time has elapsed, the program switches back to the previously selected operating mode.

Page 70: 3064203 BM-2 programming unit Installation instructions for

70 3064203_201508

Overview of symbols

31.3 Symbols in the status display

Symbol FunctionHeating appliances

DHW

Heating circuit

1

Mixer circuit 1

Solar

Message

Ventilation unit

Main menu

Display

Default settings

Modificationmodeorcontractorlevel

Time programs

Page 71: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 71

Overview of symbols

31.4 Symbols in the time programs submenu

Symbol FunctionUse this submenu to change switching times

Use this submenu to add switching times

Use this submenu to delete switching times

Use this quick start key to copy settings for the selected day

Burner stage symbol in the heating appliance

Symbol FunctionThis displays the current burner stage in steps of 20 %

Page 72: 3064203 BM-2 programming unit Installation instructions for

72 3064203_201508

Faults

32 FaultsFault code

Fault Cause Remedy

1 HLSC excess temp. The high limit safety cut-out (thermostat) has responded. The boiler temperature has exceeded 107 °C

Test heating circuit pump, vent system, press reset, clean heat exchanger

2 TL excess temp. One of the temperature sensors eHLSC1 or eHLSC2 has exceeded the high limit safety cut-out limit (105 °C).

Test heating circuit pump, test sensor, vent system, press reset, clean heat exchanger

3 dT – eHLSC drift Temperature differential between temperature sensors eHLSC1 and eHLSC2 > 6 °C

Test sensor, test heating circuit pump, vent system, press reset, clean heat exchanger

4 No flame At burner start, no flame at the end of the safety time, monitoring electrode faulty, ignition electrode faulty, ignition transformer faulty

Test monitoring electrode, ignition electrode and ignition transformer, press reset, check gas pressure

5 Flame failure (during operation)

Flame failure during operation, monitoring electrode faulty, flue gas path blocked, condensate drain blocked

Test monitoring electrode, press reset, test flue system, test condensate drain

6 TC excess temp. One of the temperature sensors eHLSC1 or eHLSC2 has exceeded the limit of the temperature limiter (97 °C)

Test heating circuit pump, vent system, test sensor, press reset, clean heat exchanger

7 TL flue gas excess temp. The flue gas temperature has exceeded the limit of the flue gas temperature limiter shutdown temperature

Clean heat exchanger, test sensor, check flue system

8 Flue gas damper does not switch

Flue gas damper contact (E1) closes or does not open on demand; output A1 does not switch flue gas damper

Check flue gas damper and wiring; check settings HG13 and HG14

9 Fault code unknown This fault is not known in this software Check software version of the PCBs10 eHLSC sensor faulty Temperature sensor eHLSC1, eHLSC2 or

sensor lead has short circuit or breakCheck sensor and lead

11 Flame pretence A flame is recognised before the burner starts Press reset, test monitoring electrode

12 Boiler sens. faulty Boiler sensor > 105 °CBoiler sensor or sensor lead has short circuit or break

Check sensor and lead

13 Fl. gas sens faulty Flue gas sensor or sensor lead has short circuit or break

Check sensor and lead

14 DHW sensor faulty DHW sensor (cylinder sensor) or sensor lead has short circuit or break

Check sensor and lead

15 Outs. sensor faulty Outside sensor or sensor lead has short circuit or break

Check sensor and lead

Page 73: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 73

Faults

Fault code

Fault Cause Remedy

16 Rtn sensor faulty Return sensor or sensor lead has short circuit or break

Check sensor and lead

18 Ext. safety circuit The contact for the external safety circuit has responded (maximum pressure limiter, low water indicator, etc.)

Press reset and repair fault

20 GCV relay test The internal relay test failed Press reset and replace burner control unit

21 Gas valve fault24 Fan speed < The fan does not reach the set speed. Test the fan PWM and power

cables, test the fan, press reset26 Fan speed > The fan does not stop Test the fan PWM and power

cables, test the fan, press reset, test flue system for strong draught

30 CRC burner control unit The EEPROM record is invalid Switch the power supply OFF and ON. If unsuccessful, replace the burner control unit.

32 Fault in 23 V AC supply 23 V AC supply outside the permissible range (e.g. short circuit)

Switch the power supply OFF and ON. If unsuccessful, replace the PCB.

35 BCC missing Boiler coding card has been removed or not correctly inserted

Refit the correct boiler coding card

36 BCC faulty Faulty boiler coding card Replace boiler coding card37 Incorrect BCC The boiler coding card is incompatible with

the PCBRefit the correct boiler coding card

38 BCC update required Boiler coding card fault; PCB requires a new boiler coding card (replacement)

Reinsert or replace boiler coding card

39 BCC system error Faulty boiler coding card Replace boiler coding card41 Flow monitoring Return temperature > flow temperature Vent system, check heating circuit

pump, test flow and return pipe connection

42 Condensate pump not pumping

Faulty condensate pump, drain line blocked, no power supply to pump

Check pump, check drain line, check mains plug and fuse

44 Flue gas press. sw. Flue system back pressure too high Heat exchanger contaminated, check flue system, test flue gas damper, press reset

52 Max. cyl. heat. time Cylinder heating takes longer than permissible

Test the DHW sensor and sensor lead, press the reset key

53 IO control deviatn Wind recognition, severe storm, insufficient ionisation signal during operation, burner contaminated

Test monitoring electrode, check flue system, press reset, clean burner

60 Siphon back pressure Siphon or flue system is blocked Clean siphon, check flue system, check ventilation air, check monitoring electrode

78 Header sensor fault Faulty sensor or lead Check sensor and lead; replace if required

Page 74: 3064203 BM-2 programming unit Installation instructions for

74 3064203_201508

Faults

32.1 Warning messagesThe system can display the following warnings:

Fault code

Fault Cause Remedy

90 BCU communication Emergency stop via ChipCom, faulty communication between PCB and burner control unit

Switch the power supply OFF and ON. If unsuccessful, call out a contractor

95 Prog. mode Burner control unit is controlled by PC No action96 Reset Reset key pressed too often Switch the power supply OFF and

ON. If unsuccessful, call out a contractor

98 Flame amplifier Internal burner control unit faultShort circuit, monitoring electrode

Press the reset key,Switch the power supply OFF and ON. If unsuccessful, call out a contractor, test monitoring electrode

99 Burner control unit system fault

Internal burner control unit fault Switch the power supply OFF and ON. If unsuccessful, call out a contractor

107 HC pressure Water pressure too low, water pressure too high

Test system pressure, test cable, press reset, test water pressure sensor

Number Fault Description Cause and remedy1 Burner control unit

replacedThe PCB has detected that the burner control unit has been replaced

Insert boiler coding card that corresponds to appliance output; if necessary, reinsert boiler coding card

2 HC pressure The water pressure has fallen below the warning limit

Check system pressure, check sensor

3 Parameter changed Another boiler coding card has been inserted

Make sure that the correct boiler coding card has been inserted; if necessary, reinsert boiler coding card

4 No flame At the last attempt to start the burner, no flame was detected

Wait for another start attempt, test ignition electrode and ignition transformer, test monitoring electrode, test gas supply pressure

5 Flame failure duringstabilisation timeFlame failure aftersafety time

Flame failure during operation Monitoring electrode faulty, flue gas path blocked, condensate drain blocked, test gas supply pressure

24 Speed below or abovelimit

Fan does not reach set speed or does not stop

Test flue system, test the fan PWM and power cables

32 ProgMode set on BCU Burner control unit is controlled by PC No action

Page 75: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 75

Shutdown and disposal

33 Shutdown and disposal

33.1 Shutdown

f To shut down the BM-2 programming unit, follow the installation sequence in reverse order.

f Dispose of the BM-2 programming unit correctly.

33.2 Disposal and recycling

Appliance

When it reaches the end of its service life, the BM-2 programming unit must not be disposed of in the household waste.

f Ensure that the BM-2 programming unit and any accessories used are disposed of correctly.

Packaging

f Ensure that the packaging of the BM-2 programming unit and any accessories used are disposed of correctly.

33.3 Maintenance / cleaning

The BM-2 programming unit is maintenance-free. Do not use a cleaning agent. Please just wipe clean with a damp cloth.

Page 76: 3064203 BM-2 programming unit Installation instructions for

76 3064203_201508

Documentation information

34 Documentation information

34.1 Other applicable documents

Installation instructions for contractors – BM-2 programming unitOperating instructions for users – BM-2 programming unitHeating appliance installation instructions

The instructions for all accessory modules and other accessories may also apply.

34.2 Safekeeping of these documents

The system user or operator should ensure the safekeeping of all instruction manuals.

f Pass on these installation instructions as well as all other applicable manuals to the system user or operator.

34.3 Applicability of these instructions

These installation instructions apply to the BM-2 programming unit.

34.4 Handover to the user

The user of the heating system must be instructed in the handling and functions of their heating system.

f Hand over all applicable documents to the system operator and/or user. f Make the system user aware that the instructions should be stored near the appliance.

f Make the system user aware that they should hand over the applicable documents to the next user (e.g. if moving house).

Instruction in the use of the heating system

f Instruct the system user how to set the temperatures and thermostatic valves in an energy saving way.

f Instruct the system operator and/or user on maintenance of the heating system.

Page 77: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 77

Specification

35 Specification

Table 35.1 Specification

DesignationDisplay LCD display 3.5"

eBUS supply voltage 15-24 V

Power consumption Max. 1.3 WIP rating in appliance as per appliance IP ratingIP rating in wall mounting base IP20Power backup > 48 hAmbient temperature 0 - 50 °CData memory EEPROM (non-volatile)

Page 78: 3064203 BM-2 programming unit Installation instructions for

78 3064203_201508

Commissioning assistant

36 Commissioning assistant

f If there is only one BM-2 programming unit in the WRS (Wolf control system), all heating appliances and extension modules will be assigned automatically.

f If there is more than one BM-2 programming unit in the WRS (Wolf control system), a commissioning assistant opens automatically, which must be worked through by turning and pressing the rotary selector.

See chapter 22.2.1 BM-2 Function (BUS address) for a description of the individual setting options. Any subsequent corrections can be performed in the same way.

14:12 20.01.13

Commissioning assistant

System

KM/MM1

MM2

no allocation

Page 79: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 79

37 Composite system data sheet according to EU regulation no. 811/2013Product group: Controller

Supplier’s name or trade mark

Supplier’s model identifier Class of the temperature control

Contribution of the temperature control to seasonal space heating energy efficiency

Wolf GmbH BM-2Unit control

II 2,0BM-2 operating module with outside sensor (outside temperature sensor, EBUS external sensor or radio clock with outside sensor)Unit control

VI 4,0

BM-2 operating module with outside sensor (outside temperature sensor, EBUS external sensor or radio clock with outside sensor)AFB analogue remote control (wired variant or wireless variant)Unit control

V 3,0BM-2 operating module without outside sensor (setting as room temperature controller)AFB analogue remote control (wired variant or wireless variant)Unit control

VI 4,0

BM-2 operating module with outside sensor (outside temperature sensor, EBUS external sensor or radio clock with outside sensor)Display module AM without external sensorWall holder for BM-2Unit control

V 3,0BM-2 operating module without outside sensor (setting as room temperature controller)Display module AM without outside sensorWall holder for BM-2

Composite system data sheet according to EU regulation no. 811/2013

Page 80: 3064203 BM-2 programming unit Installation instructions for

80 3064203_201508

Keyword index

AAcknowledging faults for contractors ......................................................................................... 28

Acknowledging faults for users .................................................................................................. 27

Automatic timer mode................................................................................................................ 32

BBM-2 and BM............................................................................................................................. 11

BM-2 as remote control ............................................................................................................... 8

BUS address ............................................................................................................................. 44

CCascade module........................................................................................................................ 56

Cascade module relay test ........................................................................................................ 57

Cleaning .................................................................................................................................... 75

Complete list of cascade module parameters ........................................................................... 57

Complete list of heating appliance parameters ......................................................................... 50

Complete list of mixer module parameters ................................................................................ 59

Complete list of solar module parameters ................................................................................. 61

Complete list of system parameters .......................................................................................... 44

Connecting outside sensor ........................................................................................................ 14

DDay temperature ........................................................................................................................ 33

Default settings .......................................................................................................................... 31

Documentation information........................................................................................................ 76

DHW cylinder status page ......................................................................................................... 22

DHW priority control .................................................................................................................. 43

Disposal and recycling............................................................................................................... 75

EECO ABS ................................................................................................................................... 33

Economy factor.................................................................................................................... 32, 64

Economy mode – calculation example ...................................................................................... 65

Electrical installation, wall mounting base ................................................................................. 14

Emissions test mode ................................................................................................................. 21

FFault history ............................................................................................................................... 63

Faults – cause / remedy ............................................................................................................ 72

Flow temperature....................................................................................................................... 54

Frost protection limit .................................................................................................................. 46

38 Keyword index

Page 81: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 81

Keyword index

GGeneral safety instructions .......................................................................................................... 9

HHandover to the user ................................................................................................................. 76

Heating appliance status page .................................................................................................. 20

Heating circuit status page ........................................................................................................ 23

Heating curve ...................................................................................................................... 54, 64

Heating curve starting point ....................................................................................................... 54

IInstallation ................................................................................................................................. 11

KKey lock ..................................................................................................................................... 35

LLow end temperature................................................................................................................. 54

MMain menu ................................................................................................................................. 29

Maintenance .............................................................................................................................. 75

Menu structure, contractor level ................................................................................................ 42

Messages status page............................................................................................................... 27

Minimum backlighting ................................................................................................................ 35

Minimum DHW temperature ...................................................................................................... 47

Mixer relay test .......................................................................................................................... 59

Mixer status page ...................................................................................................................... 24

OOnce-only DHW heating ............................................................................................................ 20

Outside sensor average ............................................................................................................ 45

Overview of symbols ................................................................................................................. 67

Overview of the BM 2 programming unit ................................................................................... 16

PParallel DHW operation ............................................................................................................. 46

Parameter reset ......................................................................................................................... 52

Password ................................................................................................................................... 41

Pasteurisation function ........................................................................................................ 45, 48

QQuick start keys ......................................................................................................................... 16

Page 82: 3064203 BM-2 programming unit Installation instructions for

82 3064203_201508

Keyword index

RRelay test................................................................................................................................... 51

Remote switching contact.......................................................................................................... 14

Roominfluence.......................................................................................................................... 65

Roominfluencefactor................................................................................................................ 45

Room temperature shutdown .................................................................................................... 47

Rotary selector .......................................................................................................................... 17

SSafekeeping of these documents .............................................................................................. 76

Screed drying, heating circuit .................................................................................................... 55

Screed drying, mixer circuit ....................................................................................................... 60

Screensaver .............................................................................................................................. 35

Set / actual temperature display ................................................................................................ 30

Setback mode............................................................................................................................ 47

Setback stop .............................................................................................................................. 47

Settingroominfluence ............................................................................................................... 33

Shutdown................................................................................................................................... 75

Software version ........................................................................................................................ 16

Solar thermal system status page ............................................................................................. 25

Specification .............................................................................................................................. 77

Standard delivery......................................................................................................................... 7

Standard outside temperature ................................................................................................... 54

Standby mode ........................................................................................................................... 32

Status pages.............................................................................................................................. 19

Switching times

Copying switching times ............................................................................................................ 40

Deleting switching times ............................................................................................................ 39

Pre-programmed switching times .............................................................................................. 36

Editing switching times .............................................................................................................. 39

Symbols and warnings .............................................................................................................. 10

System parameters ................................................................................................................... 44

TTemperature selection -4 ... +4 for heating circuit ..................................................................... 64

Temperature selection -4 ... +4 for mixer circuit ........................................................................ 66

Terminal assignment, outside sensor ........................................................................................ 15

Time program ............................................................................................................................ 36

Page 83: 3064203 BM-2 programming unit Installation instructions for

3064203_201508 83

Keyword index

VVentilation unit ........................................................................................................................... 62

Ventilation unit status page........................................................................................................ 26

WWall mounting base ................................................................................................................... 13

Warning messages .................................................................................................................... 74

Warnings ................................................................................................................................... 10

Winter/summer changeover ...................................................................................................... 32

Page 84: 3064203 BM-2 programming unit Installation instructions for

Wolf GmbH

Postfach1380•D-84048Mainburg•Tel.+49-8751/74-0•Fax+49-8751/741600

Internet: www.wolf-heiztechnik.de

BM-2 installation instructions for contractors – 3064203_201508 Subjecttotechnicalmodifications