3415

1
Document Code BAUER INTERNATIONAL PHILIPPINES, INC. BIPI-SM-PP-014-00-14 Subject Prepared Date Page Nestle Pulilan August 11, 2014 Page 1 of 1 Proposed WWTP Upgrading POWER CONSUMPTION Ite m No. Name of Equipment Number Installed Number Running Hours Run Power Rating (kW) Absorbed Power (kW) kW-hrs./ day Proposed Equipment Submersible Mixer for High Strength 1 1 24 1.5 1.275 30.6 Submersible Mixer for Equaliozation Tank 1 1 24 1.5 1.275 30.6 Submersible Mixer for Pre-react Tank 1 1 24 2.2 1.87 44.88 H2 SO4 Dosing Pump 1 1 18 0.048 0.0408 0.7344 ACH Dosing Pump 1 1 24 0.048 0.0408 0.9792 Bauer International (Phils.), Inc. Power Consumption ACH Dosing Pump 1 1 24 0.048 0.0408 0.9792 pH/ORP Controller 1 1 18 0.093 0.07905 1.4229 Air Motorized Valve 1 1 18 0.024 0.0204 0.3672 NaOH Dosing Pump 1 1 18 0.048 0.0408 0.7344 ACH Dosing Pump 1 1 24 0.048 0.0408 0.9792 DAF System 1 1 24 5 4.25 102 pH/ORP Controller 1 1 18 0.093 0.07905 1.4229 0 Existing Equipment 0 Fresh Dairy Pump Pit Pump 1 1 18 1.5 1.275 22.95 Ice Cream Dairy Pump Pit Pump 1 1 12 1.5 1.275 15.3 Fresh Dairy & Ice Cream B.T. Pump 1 1 24 2.2 1.87 44.88 DAF SYSTEM 1 1 24 11 9.35 224.4 WAS Pump 1 1 1.5 1.50 1.275 1.9125 RAS Pump 2 2 24 3.70 3.145 150.96 Aeration Blower 2 2 12 55.00 41.25 990 Effluent Pit Pump 1 1 6 3.70 3.145 18.87 Polymer Dosing Pump 1 1 12 0.048 0.0408 0.4896 Sludge Feed Pump 1 1 12 2.2 1.87 22.44 Centrifuge Decanter 1 1 12 7.50 6.375 76.5 Total kW-hr of Energy Consumption per day 1,783.42 Cost of kW-hr of Power 7.50 COST OF POWER/DAY 13,375.67 Cost of Power per cu.m. @ 350 m3/day 38.22 Bauer International (Phils.), Inc. Power Consumption

Upload: makmak9

Post on 09-Nov-2015

214 views

Category:

Documents


0 download

DESCRIPTION

4fsgsfg45345

TRANSCRIPT

  • Document Code

    BAUER INTERNATIONAL PHILIPPINES, INC. BIPI-SM-PP-014-00-14

    Subject Prepared Date Page

    Nestle Pulilan August 11, 2014 Page 1 of 1Proposed WWTP Upgrading

    POWER CONSUMPTION

    Item

    No.Name of Equipment Number

    InstalledNumberRunning

    HoursRun

    PowerRating (kW)

    Absorbed Power(kW)

    kW-hrs./day

    Proposed EquipmentSubmersible Mixer for High Strength 1 1 24 1.5 1.275 30.6Submersible Mixer for Equaliozation Tank 1 1 24 1.5 1.275 30.6Submersible Mixer for Pre-react Tank 1 1 24 2.2 1.87 44.88H2 SO4 Dosing Pump 1 1 18 0.048 0.0408 0.7344ACH Dosing Pump 1 1 24 0.048 0.0408 0.9792

    Bauer International (Phils.), Inc.Power Consumption

    ACH Dosing Pump 1 1 24 0.048 0.0408 0.9792pH/ORP Controller 1 1 18 0.093 0.07905 1.4229Air Motorized Valve 1 1 18 0.024 0.0204 0.3672NaOH Dosing Pump 1 1 18 0.048 0.0408 0.7344ACH Dosing Pump 1 1 24 0.048 0.0408 0.9792DAF System 1 1 24 5 4.25 102pH/ORP Controller 1 1 18 0.093 0.07905 1.4229

    0Existing Equipment 0Fresh Dairy Pump Pit Pump 1 1 18 1.5 1.275 22.95Ice Cream Dairy Pump Pit Pump 1 1 12 1.5 1.275 15.3Fresh Dairy & Ice Cream B.T. Pump 1 1 24 2.2 1.87 44.88DAF SYSTEM 1 1 24 11 9.35 224.4WAS Pump 1 1 1.5 1.50 1.275 1.9125RAS Pump 2 2 24 3.70 3.145 150.96Aeration Blower 2 2 12 55.00 41.25 990Effluent Pit Pump 1 1 6 3.70 3.145 18.87Polymer Dosing Pump 1 1 12 0.048 0.0408 0.4896Sludge Feed Pump 1 1 12 2.2 1.87 22.44Centrifuge Decanter 1 1 12 7.50 6.375 76.5

    Total kW-hr of Energy Consumption per day 1,783.42Cost of kW-hr of Power 7.50COST OF POWER/DAY 13,375.67Cost of Power per cu.m. @ 350 m3/day 38.22

    Bauer International (Phils.), Inc.Power Consumption